HomeMy WebLinkAbout205 Lenore Ave_BLD5707_2025
RESIDENTIAL
1778 1
1778 0 0 360
205 N LENORE AVE ARLINGTON, WA 98223 45000
10 00455400201000
CONVERT GARAGE INTO (2) BEDROOMS & LAUNDRY ROOM. PARTITION LOUNGE TO CREATE (1) BEDROOM &
STORAGE AREA. REMODEL (E)BATHROOM B TO CREATE A WALK IN SHOWER. REMODEL (E)BATHROOM A TO
CREATE A WALK IN SHOWER AND RELOCATE TOILET AND SINK AS SHOWN. REMODEL SF IS 640SF
WAMATU REGINA 206-468-4794
k.tan76@yahoo.com
206-468-4794
205 N LENORE AVE ARLINGTON WA 98223
HOME OWNER DOING THE WORK
HOME OWNER
1 15
2 50
GEORGE NGANGA 11/18/2023
2018 Washington State Energy Code Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family New & Additions (effective February 1, 2021) Version 1.0
These requirements apply to all IRC building types, including detached one- and two-family
dwellings and multiple single-family dwellings (townhouses).
Project Information Contact Information
Regina Remodel CSL Designs
205 N LENORE AVE E ARLINGTON, WA 2065486798
Instructions: This single-family project will use the requirements of the Prescriptive Path below and
incorporate the minimum values listed. Based on the size of the structure, the appropriate number of
additional credits are checked as chosen by the permit applicant.
Provide all information from the following tables as building permit drawings: Table R402.1 - Insulation and
Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits.
Authorized Representative Date 11/18/2023
All Climate Zones (Table R402.1.1)
R-Value a U-Factor a
Fenestration U-Factor b n/a 0.30
Skylight U-Factor b n/a 0.50
Glazed Fenestration SHGC b,e n/a n/a
Ceiling e 49 0.026
Wood Frame Wall g,h 21 int 0.056
Floor 30 0.029
Below Grade Wall c,h 10/15/21 int + TB 0.042
Slab d,f R-Value & Depth 10, 2 ft n/a
R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less
a than the label or design thickness of the insulation, the compressedR-value of the insulation from Appendix
Table A101.4 shall not be less than the R-value specified in the table.
b The fenestration U-factor column excludes skylights.
"10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on
the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at
c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on
the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB"
means R-5 thermal break between floor slab and basement wall.
d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1.
For single rafter- or joist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth
e
extends over the top plate of the exterior wall.
R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter
f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall
meet the requirements for thermal barriers protecting foam plastics.
For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for
g
climate zone 5 of ICC 400.
Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard
h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10
insulation.
Prescriptive Path Single Family 2018 Washington State Energy Code-R 1
2018 Washington State Energy Code Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family New & Additions (effective February 1, 2021)
Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel
normalization credits) and Table 406.3 (energy credits) to achieve the following minimum number of
credits. To claim this credit, the building permit drawings shall specify the option selected and the
maximum tested building air leakage, and show the qualifying ventilation system and its control sequence
of operation.
1. Small Dwelling Unit: 3 credits
Dwelling units less than 1,500 sf in conditioned floor area with less than 300 sf of fenestration area.
Additions to existing building that are greater than 500 sf of heated floor area but less than 1,500 sf.
2. Medium Dwelling Unit: 6 credits
All dwelling units that are not included in #1 or #3
3. Large Dwelling Unit: 7 credits
Dwelling units exceeding 5,000 sf of conditioned floor area
4. Additions less than 500 square feet: 1.5 credits
All other additions shall meet 1-3 above
Before selecting your credits on this Summary table, review the details in Table 406.3 (Single Family), on page 4.
Summary of Table R406.2
Heating Credits - select ONE
Fuel Normalization Descriptions User Notes
Options heating option
1 Combustion heating minimum NAECAb 0.0
2 Heat pumpc 1.0
3 Electric resistance heat only - furnace or zonal -1.0
4 DHP with zonal electric resistance per option 3.4 0.5
5 All other heating systems -1.0
Credits - select ONE
Energy
Energy Credit Option Descriptions energy option from each
Options category d
1.1 Efficient Building Envelope 0.5
1.2 Efficient Building Envelope 1.0
1.3 Efficient Building Envelope 0.5
1.4 Efficient Building Envelope 1.0
1.5 Efficient Building Envelope 2.0
1.6 Efficient Building Envelope 3.0
1.7 Efficient Building Envelope 0.5
2.1 Air Leakage Control and Efficient Ventilation 0.5
2.2 Air Leakage Control and Efficient Ventilation 1.0
2.3 Air Leakage Control and Efficient Ventilation 1.5
2.4 Air Leakage Control and Efficient Ventilation 2.0
3.1a High Efficiency HVAC 1.0
3.2 High Efficiency HVAC 1.0
3.3a High Efficiency HVAC 1.5
3.4 High Efficiency HVAC 1.5
3.5 High Efficiency HVAC 1.5
3.6a High Efficiency HVAC 2.0
4.1 High Efficiency HVAC Distribution System 0.5
4.2 High Efficiency HVAC Distribution System 1.0
Prescriptive Path Single Family 2018 Washington State Energy Code-R 2
2018 Washington State Energy Code Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family New & Additions (effective February 1, 2021)
Summary of Table R406.2 (cont.)
Credits - select ONE
Energy
Energy Credit Option Descriptions (cont.) energy option from User Notes
Options each category d
5.1d Efficient Water Heating 0.5
5.2 Efficient Water Heating 0.5
5.3 Efficient Water Heating 1.0
5.4 Efficient Water Heating 1.5
5.5 Efficient Water Heating 2.0
5.6 Efficient Water Heating 2.5
6.1e Renewable Electric Energy (3 credits max) 1.0
7.1 Appliance Package 0.5
Total Credits Calculate Total Clear Form
a. An alternative heating source sized at a maximum of 0.5 W/sf (equivalent) of heated floor area or 500 W,
whichever is bigger, may be installed in the dwelling unit.
b. Equipment listed in Table C403.3.2(4) or C403.3.2(5)
c. Equipment listed in Table C403.3.2(1) or C403.3.2(2)
d. You cannot select more than one option from any category EXCEPT in category 5. Option 5.1 may be combined
with options 5.2 through 5.6. See Table 406.3.
e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max.
See the complete Table R406.2 for all requirements and option descriptions.
f. Use the single radiobutton in the upper right of the second column to deselect radiobuttons in that group.
Please print only pages 1 through 3 of this worksheet for submission to your building official.
Prescriptive Path Single Family 2018 Washington State Energy Code-R 3
Window, Skylight and Door Schedule
Project Information Contact Information
Regina Remodel CSL Designs
205 N LENORE AVE E 2065486798
ARLINGTON, WA 98223
Width Height
Ref. U-factor Qt. Feet Inch Feet Inch Area UA
Exempt Swinging Door (24 sq. ft. max.) WSEC 0.00 0 0 0 0.0 0.00
Exempt Glazed Fenestration (15 sq. ft. max.) 0.0 0.00
Vertical Fenestration (Windows and doors)
Component Width Height
Description Ref. U-factor Qt. Feet Inch Feet Inch Area UA
Windows WSEC 0.28 2 4 0 4 0 32.0 8.96
Windows WSEC.028 1 6 0 3 0 18.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
Sum of Vertical Fenestration Area and UA 50.0 8.96
Vertical Fenestration Area Weighted U = UA/Area 0.18
Overhead Glazing (Skylights)
Component Width Height
Description Ref. U-factor Qt. Feet Inch Feet Inch Area UA
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
Sum of Overhead Glazing Area and UA 0.0 0.00
Overhead Glazing Area Weighted U = UA/Area 0.00
Total Sum of Fenestration Area and UA (for heating system sizing calculations) 50.0 8.96
Simple Heating System Size: Washington State
This heating system sizing calculator is based on the Prescriptive Requirements of the 2018 Washington State Energy Code (WSEC) and ACCA Manuals
J and S. This tool will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling loads.
Please complete the green drop-downs and boxes that are applicable to your project. As you make selections in the drop-downs for each section, some
values will be calculated for you. If you do not see the selection you need in the drop-down options, please contact the WSU Energy Program at
energycode@energy.wsu.edu or (360) 956-2042 for assistance.
Project Information Contact Information
Regina Remodel CSL Designs
205Â NÂ LENOREÂ AVEÂ NE 2065486798
ARLINGTON, WA 98223
Heating System Type: All Other Systems Heat Pump
To see detailed instructions for each section, place your cursor on the word "Instructions"
Design Temperature
Instructions Design Temperature Difference (∆T) 47
∆T = Indoor (70 degrees) - Outdoor Design Temp
Area of Building
Conditioned Floor Area
Instructions Conditioned Floor Area (sq ft) 347
Average Ceiling Height Conditioned Volume
Instructions Average Ceiling Height (ft) 7.0 2,429
Glazing and Doors U-Factor X Area = UA
Instructions
0.280 50 14.00
Skylights U-Factor X Area = UA
Instructions 0.50 ---
Insulation
Attic U-Factor X Area = UA
Instructions 0.026 347 9.02
Single Rafter or Joist Vaulted Ceilings U-Factor X Area UA
Instructions --- ________
Above Grade Walls (see Figure 1) U-Factor X Area UA
Instructions 0.056 412 23.07
Floors U-Factor X Area UA
Instructions 0.025 347 8.68
Below Grade Walls (see Figure 1) U-Factor X Area UA
Instructions No selection ---
Slab Below Grade (see Figure 1) F-Factor X Length UA
Instructions No selection ---
Slab on Grade (see Figure 1) F-Factor X Length UA
Instructions 0.360 0 ________
Location of Ducts
Instructions Duct Leakage Coefficient
1.10
Sum of UA 54.77
Envelope Heat Load 2,574 Btu / Hour
Figure 1. Sum of UA x ∆T
Air Leakage Heat Load 1,233 Btu / Hour
Volume x 0.6 x ∆T x 0.018
Above Grade Building Design Heat Load 3,807 Btu / Hour
Air leakage + envelope heat loss
Below Grade Building and Duct Heat Load 4,188 Btu / Hour
Ducts in unconditioned space: sum of building heat loss x 1.10
Ducts in conditioned space: sum of building heat loss x 1
Maximum Heat Equipment Output 5,235 Btu / Hour
Building and duct heat loss x 1.40 for forced air furnace
Building and duct heat loss x 1.25 for heat pump
(07/01/13)
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST
Code References: 2018 IRC Section R330 (WAC 51-51)
APPLICATION NUMBER:_____________________
SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION WILL BE PROCESSED
SECTION 1 SECTION - PROPERTY INFORMATION1 – PROPERTY INFORMATION
SITE ADDRESS: ______________________________________________________________________________ ASSESSOR’S TAX/PARCEL#:_ _ _ _ _ _ _ - _ _ _ _
SECTION 2 - APPLICANT INFORMATIONSECTION 2 – APPLICANT INFORMATION
PROPERTY OWNER NAME: ___________________________________________________________ DAYTIME PHONE: ____________________
AFH LICENSEE NAME (IF DIFFERENT): ________________________________________________________________________ DAYTIME PHONE: ____________________
SECTION 3 – FLOOR PLAN
SECTION 3 – FLOOR PLAN
On a separate sheet of paper (8 ½ x 11) draw a floor plan (including all
floors) of your prospective AFH. Include all sleeping rooms (bedrooms)
indicating which bedroom is: A, B, C D, E and F.
Label all components for exiting i.e., stairs, ramps, platforms, lifts and
elevators.
SECTION 4 – DISCLAIMER/SIGNATURE BLOCK
I certify under penalty of perjury that the information furnished by me is true and correct to the best of my knowledge, and that I am
requesting or I am authorized by the owner of the above premises to request inspection for the operation of an Adult Family Home
at this location. I agree to hold harmless the jurisdiction conducting such inspections, at my request, as to any claim (including costs,
expenses, and attorneys’ fees incurred in the investigation of such claim), which may be made by any person, including the undersigned,
and filed against the jurisdiction, but only where such claim arises out of the reliance of the jurisdiction, including its officers and
employees, upon the accuracy of the information supplied to the jurisdiction as a part of this application.
NAME/TITLE: _________________________________________________________________________ DATE: __________________________
PROPERTY OWNER APPLICANT LICENSEE
Implementation Date: 2021 February 01
Updated: 2021 February
(Effective Feb. 1, 2021
WAC 51-51-0330
Section R330 — Adult family homes.
SECTION R330
ADULT FAMILY HOMES
R330.1 General. This section shall apply to all newly constructed adult family homes and all existing single family homes being
converted to adult family homes. This section shall not apply to those adult family homes licensed by the state of Washington
department of social and health services prior to July 1, 2001.
R330.2 Reserved.
R330.3 Sleeping room classification. Each sleeping room in an adult family home shall be classified as:
1. Type S - Where the means of egress contains stairs, elevators or platform lifts.
2. Type NS1 - Where one means of egress is at grade level or a ramp constructed in accordance with R330.9 is provided.
3. Type NS2 - Where two means of egress are at grade level or ramps constructed in accordance with R330.9 are provided.
R330.4 Types of locking devices and door activation. All bedroom and bathroom doors shall be openable from the outside when
locked.
Every closet shall be readily openable from the inside.
Operable parts of door handles, pulls, latches, locks and other devices installed in adult family homes shall be operable with one
hand and shall not require tight grasping, pinching or twisting of the wrist. Pocket doors shall have graspable hardware available
when in the closed or open position.
The force required to activate operable parts shall be 5.0 pounds (22.2 N) maximum. Required exit doors shall have no additional
locking devices.
Required exit door hardware shall unlock inside and outside mechanisms when exiting the building allowing reentry into the adult
family home without the use of a key, tool or special knowledge.
R330.5 Smoke and carbon monoxide alarm requirements. All adult family homes shall be equipped with smoke and carbon
monoxide alarms installed as required in Sections R314 and R315.1. Alarms shall be installed in such a manner so that the
detection device warning is audible from all areas of the dwelling upon activation of a single alarm.
R330.6 Escape windows and doors. Every sleeping room shall be provided with emergency escape and rescue windows as
required by Section R310. No alternatives to the sill height such as steps, raised platforms or other devices placed by the openings
will be approved as meeting this requirement.
R330.7 Fire apparatus access roads and water supply for fire protection. Adult family homes shall be served by fire apparatus
access roads and water supplies meeting the requirements of the local jurisdiction.
R330.8 Grab bar general requirements. Where facilities are designated for use by adult family home clients, grab bars for water
closets, bathtubs and shower stalls shall be installed according to this section.
R330.8.1 Grab bar cross section. Grab bars with a circular cross section shall have an outside diameter of 1 1/4 inches minimum
and 2 inches maximum. Grab bars with noncircular cross section shall have a cross section dimension of 2 inches maximum and a
perimeter dimension of 4 inches minimum and 4 5/8 inches maximum.
R330.8.2 Grab bar installation. Grab bars shall have a spacing of 1 1/2 inches between the wall and the bar. Projecting objects,
control valves and bathtub or shower stall enclosure features above, below and at the ends of the grab bar shall have a clear space
of 1 1/2 inches to the grab bar.
EXCEPTION: Swing-up grab bars shall not be required to meet the 1 1/2 inch spacing requirement.
Grabs bars shall have a structural strength of 250 pounds applied at any point on the grab bar, fastener, mounting device or
supporting structural member. Grab bars shall not be supported directly by any residential grade fiberglass bathing or showering
unit. Acrylic bars found in bathing units shall be removed.
Fixed position grab bars, when mounted, shall not rotate, spin or move and have a graspable surface finish.
R330.8.3 Grab bars at water closets. Water closets shall have grab bars mounted on both sides. Grab bars can be a combination
of fixed position and swing-up bars. Grab bars shall meet the requirements of R330.8. Grab bars shall mount between 33 inches
and 36 inches above floor grade. Centerline distance between grab bars, regardless of type used, shall be between 25 inches
minimum and 30 inches maximum.
Implementation Date: 2021 February 01
Updated: 2021 February
R330.8.3.1 Fixed position grab bars. Fixed position grab bars shall be a minimum of 36 inches in length and start 12 inches from
the rear wall.
R330.8.3.2 Swing-up grab bars. Swing-up grab bars shall be a minimum of 28 inches in length from the rear wall.
R330.8.4 Grab bars at bathtubs. Horizontal and vertical grab bars shall meet the requirements of R330.8.
R330.8.4.1 Vertical grab bars. Vertical grab bars shall be a minimum of 18 inches long and installed at the control end wall and
head end wall. Grab bars shall mount within 4 inches of the exterior of the bath tub edge or within 4 inches within the bath tub. The
bottom end of the bar shall start between 36 inches and 42 inches above floor grade.
EXCEPTION: The required vertical grab bar can be substituted with a floor to ceiling grab bar meeting the
requirements of R330.8 at the control end and head end entry points.
R330.8.4.2 Horizontal grab bars. Horizontal grab bars shall be provided at the control end, head end, and the back wall within the
bathtub area. Grab bars shall be mounted between 33 inches and 36 inches above floor grade. Control end and head end grab bars
shall be 24 inches minimum in length. Back wall grab bar shall be 36 inches minimum in length.
R330.8.5 Grab bars at shower stalls. Where shower stalls are provided to meet the requirements for bathing facilities, grab bars
shall meet the requirements of R330.8.
EXCEPTION: Shower stalls with permanent built-in seats are not required to have vertical or horizontal grab
bars at the seat end wall. A vertical floor to ceiling grab bar shall be installed within 4 inches of
the exterior of the shower aligned with the nose of the built-in seat.
R330.8.5.1 Vertical grab bars. Vertical grab bars shall be 18 inches minimum in length and installed at the control end wall and
head end wall. Vertical bars shall be mounted within 4 inches of the exterior of the shower stall or within 4 inches inside the shower
stall. The bottom end of vertical bars mount between 36 inches and 42 inches above floor grade.
R330.8.5.2 Horizontal grab bars. Horizontal grab bars shall be installed on all sides of the shower stall mounted between 33
inches and 36 inches above the floor grade. Horizontal grab bars shall be a maximum of 6 inches from adjacent walls. Horizontal
grab bars shall not interfere with shower control valves.
R330.9 Ramps. All interior and exterior ramps, when provided, shall be constructed in accordance with Section R311.8 with a
maximum slope of 1 vertical to 12 horizontal. The exception to R311.8.1 is not allowed for adult family homes. Handrails shall be
installed in accordance with R330.9.1.
R330.9.1 Handrails for ramps. Handrails shall be installed on both sides of ramps between the slope of 1 vertical to 12 horizontal
and 1 vertical and 20 horizontal in accordance with R311.8.3.1 through R311.8.3.3.
R330.10 Stair treads and risers. Stair treads and risers shall be constructed in accordance with R311.7.5. Handrails shall be
installed in accordance with R330.10.1.
R330.10.1 Handrails for treads and risers. Handrails shall be installed on both sides of treads and risers numbering from one riser
to multiple risers. Handrails shall be installed in accordance with R311.7.8.1 through R311.7.8.4
R330.11 Shower stalls. Where provided to meet the requirements for bathing facilities, the minimum size of shower stalls for an
adult family home shall be 30 inches deep by 48 inches long.
[Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. 13-04-068, § 51-51-0325, filed 2/1/13, effective 7/1/13. Statutory
Authority: Chapter 19.27 RCW. 10-18-036, § 51-51-0325, filed 8/25/10, effective 9/25/10. Statutory Authority: RCW 19.27.190, 19.27.020, and
chapters 19.27 and 34.05 RCW. 09-04-023, § 51-51-0325, filed 1/27/09, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and
chapters 19.27 and 34.05 RCW. 07-01-090, § 51-51-0325, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-
01-109, § 51-51-0325, filed 12/17/03, effective 7/1/04.][Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-03-023, § 51-51-0330, filed
1/6/20, effective 7/1/20.]
Implementation Date: 2021 February 01
Updated: 2021 February
SECTION 5 MUST BE COMPLETED BY THE BUILDING DEPARTMENT IN THE JURISDICTION THE HOME WILL BE LOCATED.
PLEASE CHECK ALL APPLICABLE BOXES; MATCH THE LIST BELOW TO THE APPLICANT’S FLOOR PLAN – USING THEIR PROSPECTIVE
RESIDENT BEDROOM DESIGNATIONS OF A B C D E AND F AND CLASSIFICATION CODE S, NS1 OR NS2.
SECTION 5 – BUILDING INSPECTOR’S INSPECTION CHECKLIST
R330.3 Sleeping Room Classification: Each sleeping room in an Adult family Home shall be classified as:
Type S – where the means of egress contains stairs, elevators or platform lifts to evacuate residents to public area.
Type NS1 – where 1 means of egress at grade level (has no stairs) or ramp constructed compliant with R330.9 is provided to evacuate
residents to public area.
Type NS2 – where 2 means of egress at grade level (both have no stairs) or ramps constructed compliant with R330.9 are provided to
evacuate residents to public area.
SLEEPING ROOM A Type S Type NS1 Type NS2 YES NO
Closet door/s are readily openable from the inside Yes No N/A Smoke alarm is installed in the bedroom
Bedroom door opens easily and quickly from the outside when locked
Sleeping room window has a net opening of 5.7 SF (minimum dimensions at least 24â€high; at least 20†wide)
EXCEPT per R310.2.1: at-grade escape windows – may have net clearance opening 5 SF
Sleeping room window has a maximum sill height of 44†above floor to clear opening; no steps under window allowed
SLEEPING ROOM B Type S Type NS1 Type NS2 YES NO
Closet door/s are readily openable from the inside Yes No N/A Smoke alarm is installed in the bedroom
Bedroom door opens easily and quickly from the outside when locked
Sleeping room window has a net opening of 5.7 SF (minimum dimensions at least 24â€high; at least 20†wide)
EXCEPT per R310.2.1: at-grade escape windows – may have net clearance opening 5 SF
Sleeping room window has a maximum sill height of 44†above floor to clear opening; no steps under window allowed
SLEEPING ROOM C Type S Type NS1 Type NS2 YES NO
Closet door/s are readily openable from the inside Yes No N/A Smoke alarm is installed in the bedroom
Bedroom door opens easily and quickly from the outside when locked
Sleeping room window has a net opening of 5.7 SF (minimum dimensions at least 24â€high; at least 20†wide)
EXCEPT per R310.2.1: at-grade escape windows – may have net clearance opening 5 SF
Sleeping room window has a maximum sill height of 44†above floor to clear opening; no steps under window allowed
SLEEPING ROOM D Type S Type NS1 Type NS2 YES NO
Closet door/s are readily openable from the inside Yes No N/A Smoke alarm is installed in the bedroom
Bedroom door opens easily and quickly from the outside when locked
Sleeping room window has a net opening of 5.7 SF (minimum dimensions at least 24â€high; at least 20†wide)
EXCEPT per R310.2.1: at-grade escape windows – may have net clearance opening 5 SF
Sleeping room window has a maximum sill height of 44†above floor to clear opening; no steps under window allowed
SLEEPING ROOM E Type S Type NS1 Type NS2 YES NO
Closet door/s are readily openable from the inside Yes No N/A Smoke alarm is installed in the bedroom
Bedroom door opens easily and quickly from the outside when locked
Sleeping room window has a net opening of 5.7 SF (minimum dimensions at least 24â€high; at least 20†wide)
EXCEPT per R310.2.1: at-grade escape windows – may have net clearance opening 5 SF
Sleeping room window has a maximum sill height of 44†above floor to clear opening; no steps under window allowed
SLEEPING ROOM F Type S Type NS1 Type NS2 YES NO
Closet door/s are readily openable from the inside Yes No N/A Smoke alarm is installed in the bedroom
Bedroom door opens easily and quickly from the outside when locked
Sleeping room window has a net opening of 5.7 SF (minimum dimensions at least 24â€high; at least 20†wide)
EXCEPT per R310.2.1: at-grade escape windows – may have net clearance opening 5 SF
Sleeping room window has a maximum sill height of 44†above floor to clear opening; no steps under window allowed
Implementation Date: 2021 February 01
Updated: 2021 February
GENERAL YES NO
Bathroom doors are easily and quickly openable from the outside when locked
Carbon Monoxide alarms are installed as required in R315 on each level of the home.
Smoke alarms are installed on all levels of the dwelling, in each resident sleeping room, outside each separate
sleeping area in the immediate vicinity of sleeping rooms (R314).
Smoke and Carbon Monoxide alarms are installed in such a manner so that the audible warning may be heard in all
parts of the dwelling upon activation of a single device.
Access road and water supply meet local fire jurisdictional requirements.
R330.4 Operable parts of door handles, pulls, latches, locks and other devices installed in AFH shall be operable
with one hand and shall not require tight grasping, pinching or twisting of the wrist (lever-type).
Pocket doors shall have graspable hardware available when in the closed or open position.
R311.8 Ramps YES NO
Inside Ramp N/A
R311.8.1 Maximum Slope one unit vertical in twelve units horizontal (8.3% slope). (Exception R311.8.1 Not allowed in AFH
R330.9)
R311.8.2 Landing Requirements: min. 3X3 foot landing at top/bottom, where doors open onto ramps, and where
ramp changes directions.
R330.9.1 Handrails required on both sides of ramp.
Outside Ramp N/A YES NO
R311.8.1 Maximum Slope one unit vertical in twelve units horizontal (8.3% slope). (Exception R311.8.1 Not allowed in AFH
R330.9)
R311.8.2 Landing Requirements: min. 3X3 foot landing at top/bottom, where doors open onto ramps, and where
ramp changes directions.
R330.9.1 Handrails required on both sides of ramp.
R312.1.1 Guards shall be located along open-sided walking surfaces, that are located more than 30 inches measured
vertically to the floor or grade below at any point within 36 inches horizontally to the edge of the open side.
Guards below are depicted vertically as an example only.
Handrail both sides
Less than 4" 34" - 38"
Guard
36" min
3' x 3' min
landing
3' x 3' min
landing
3' One unit vertical in twelve units horizontal 3'
minimum is an 8.3% slope all along surface of the ramp. minimum
Implementation Date: 2021 February 01
Updated: 2021 February
R311.2 Means of Egress YES NO
R311.2 Door must be side-hinged with min. width of 32 inches between face of door and stop. Height not less than 78 inches.
R330.4 Operable parts of door handles, pulls, latches, locks and other devices installed in AFH shall be operable with one hand
and shall not require tight grasping, pinching or twisting of the wrist (lever-type).
R330.4 Required exit door hardware shall unlock inside and outside mechanisms when exiting the building allowing re-entry
without use of key, tool or special knowledge.
R311.7 Stairways N/A YES NO
R311.7.5.1 Riser Height: Max riser height shall be 7 ¾ inches (8 inches in structures built prior to July 1, 2004)
R311.7.5.2 Tread Depth: Min. tread depth shall be in 10 inches (9 inches in structures built prior to July 1, 2004)
R330.10.1 Handrails for Treads and Risers shall be installed on both sides of treads and risers numbering from one riser to multiple
risers. Handrails shall be installed in accordance with R311.7.8.1 – R311.7.8.4
R330.8 Grab Bars in Bathrooms N/A YES NO
Grab bars shall be installed for all water closets (toilets), bathtubs and showers according to R330.8.
Water Closets (toilet) shall have grab bars installed on both sides according to R330.8.3
Bathtubs shall have two vertical and three horizontal grab bars installed according to R330.8.4
Shower stalls have two vertical and horizontal grab bars mounted on all sides of shower according to R330.8.5
Shower stalls must be minimum size of 30 inches deep by 48 inches long (R330.11)
PASSED
NAME OF AFH: ____________________________________________________________________
_________________________________________________________________________________
Adult Family Home Project Address
_________________________________________________________________________________
BUILDING DEPT. INSPECTOR’S NAME (PRINT)
_______________________________________________________________________________ _______________________
BUILDING DEPT. INSPECTOR’S SIGNATURE DATE:
_______________________________________________________________________________ _______________________
BUILDING DEPT. OFFICE ADDRESS OFFICE PHONE NUMBER:
Application and inspection checklist developed by Washington Association of Building Officials (WABO), in cooperation with Department of Social and
Health Services (DSHS) for use by both departments and licensors in accordance with WAC 388-76-10700.
Implementation Date: 2021 February 01
Updated: 2021 February
CITY OF ARLINGTON
18204 59th Avenue NE, Arlington, WA 98223
INSPECTIONS: 360-403-3417 - Permit Center: 360-403-3551
BUILDING PERMIT
205 LENORE AVE Permit #: 5707
PERMIT EXPIRES 180 DAYS AFTER
Parcel #: 00455400201000
DATE OF ISSUANCE.
Scope of Work: CONVERT GARAGE INTO (2) BEDROOMS & LAUNDRY Valuation: 45000.00
ROOM. PARTITION LOUNGE TO CREATE (1) BEDROOM & STORAGE
AREA. REMODEL (E)BATHROOM B TO CREATE A WALK IN SHOWER.
REMODEL (E)BATHROOM A TO CREATE A WALK IN SHOWER AND
RELOCATE TOILET AND SINK AS SHOWN. REMODEL SF IS 640SF
OWNER APPLICANT CONTRACTOR
WAMATU REGINA George Nganga Wamatu Regina
205 N LENORE AVE 205 N Lenore Ave 205 N Lenore Ave
ARLINGTON, WA 98223 Arlington, Wa, 98223 Arlington, Wa 98223
2064684794 2064684794
LIC: EXP:
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC #: EXP: LIC #: EXP:
JOB DESCRIPTION
PERMIT TYPE: RESIDENTIAL ALTERATION CODE YEAR: 2018
STORIES: 1 CONST. TYPE: VB
DWELLING UNITS: OCC GROUP: R-3; Residential
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for, or approval of, any violation of this Code or any
other ordinance or order of the City, of any state or federal law, or of any order, proclamation, guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law, or order, proclamation, guidance advice
or decision of the Governor of this State, this permit shall not authorize such work and shall not be valid. The building official is
authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this jurisdiction or
any other ordinance or executive order of the City, or of any state or federal law, or of any order, proclamation, guidance advice or
decision of the Governor. The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or
on the basis of incorrect, inaccurate or incomplete information, or in violation of any City ordinance, regulation or order, state or
federal law, or any order, proclamation, guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY; NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE
STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/IRC110.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington #3101.
04/05/2024 04/04/2024
Applicant Signature Date Building Official Date
CONDITIONS
Adult Family Home Checklist and approved job copy shall be onsite for inspection. Adhere to approved plans. Call for inspections.
The property owner shall ensure that the construction project complies with all applicable zoning codes and regulations. The property
owner shall also ensure that the construction project does not cause any adverse impact on the surrounding environment or
community. The property owner shall be responsible for obtaining all necessary permits and approvals from the relevant authorities
before commencing construction. The property owner shall ensure that the construction project complies with all applicable design
review requirements.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS,
MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
04/04/2024 Building Plan Review $579.18
04/04/2024 Processing/Technology $25.00
04/04/2024 Building Permit $891.04
04/04/2024 State Surcharge - 1st DU $6.50
Total Due: $1,501.72
Total Payment: $1,501.72
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection, allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number, Type of Inspection being requested, and whether you prefer morning or afternoon
INSPECTION INFORMATION Pass/Fail
From: George Nganga
To: Hannah Hardwick
Subject: Permit Renewal - Permit BLD5707
Date: Wednesday, November 13, 2024 3:28:33 AM
This message is from an External Sender
This message came from outside the City of Arlington
Hello Hannah.
I am reaching out to request a renewal of permit #5707, which is currently set to expire on
12/02/2024 for address 205 N LENORE AVENUE, ARLINGTON, WA 98223.
Could you kindly guide us through the process for renewing this permit? We would greatly
appreciate any information you can provide regarding the necessary documentation, forms,
associated fees, or any additional steps required to facilitate the renewal.
We would like to complete the renewal process as smoothly and promptly as possible.
Please let us know how we can best proceed. Thank you.
Regards,
CSL Designs
“Success has a simple formula: do your best, and people may like it.â€
!"# $%&'($)*+$,
-."/
0$*1%$%('%(
#
-."/
$'*1$4$
-2233
-."/565
1,&'%9*':;(:<=
758
6 /" ;()(9>$%&'(
? / @A@=A <A
B. CD9(' @EF(G**DH*)
7" IJ K LM00NOPQRSTQDU
S0LNOPQR0DQNOPVQ
PL;WV;DQNOPVQL
;WV;LWV;DQX
@A X
Y.Z / A D
7[Z\ =
#Z] I
7 3
6 /3Z" /
MP
^""Z/"
`a$b&+$'9&(,
_ Z
c 6 2
c33Z2 A A
Bd3 @
\
7Z3 LQU
-33e/2 V(''(GV(1+f&HC
U(1H$,g++1$bb$%(,$bH1&h9&*'f'$1()$ f'$1UG*'$i*'&'%
0
A A
!"#"#!"!$
!"#"#!"!$
%
&'()*+),
-.+)
/' .012345637893::;<=>?@<4A4B1>;6A7
&*/"::;<=>?
C//%0).1#" D
E0,
F*,
G.* /H
I./
J 12>35>8<4KA;6L9>79>;79A58<4=>;5A<4A5K<;343?M27K36A2N9<6>H
"25<4>>?57<:;<=A?>>2>=37A<4534?:>;8>473B><K>O7>;A<;7937A5P>A4B8934B>?H!9>9<M5>A5
2<837>?LA79A479>$2?!<L4>5A?>47A32A57;A8734?5MPQ>877<79>$2?!<L4>5A?>47A32
>5AB4734?3;?5H
;>5MP6A7732
. E0R. .0
13;8>2S, T"U"!VD "
T"U"!VD "
# $"W
# $"W"# D!$ XT"JY
@<4A4B, D#Z"U#[
\#<7,]2<8^,
, /01/2-./203
6.,789
445 =:<;>4?
4:;<5<
6.,789
=;>:
4@;@
AB C
0
34@;@D ED -FG =<>@?
6.,789
444 =44>
4:5?
444 AB C
0
34:5?D ED -FG =5>5
HI +J+KLM+ NOPOO
QR
S7 -./9
?: T D ED -FG
45 T D ED -FG
08B 3U FVD ED -FG
4 UF00 W FEEXB0UF00>D ED -FG
2W E 3Y0- XB0 W 8E -3W8 0W/E0>.3W-B0
445 D ED -FG
Y3-FE3EXB0>
44;5 W BUFV3 W D ED -FG
4445 U- /0>Z0
W- W 0-BE03Y083WW[X-W 8UF>D ED -FG
445 D0F B E D ED -FG
445 0
W- W 8 /0 -E -UF>D ED -FG
\]MR^JM
_WS 0
4445 `abcddeef`g`dbbbahijklglh#$%&'mn'$!op!q$r$o'st u
: bekvbeglf`g`dhijklglhwxyz{$|}o'st u
: bekvbegdf`g`dhijklglh~oo$ #$%&'st u
beklcalcf`g`dgdgdhijklglhwtt%p$ #€!ost u
445 blkkbkbkf`g`abb`ghijklglhm!$%"‚p%}o{$$'st u
445 blkkbkbcf`g`abb`ghijklglhƒ€„!" |{$ $st u
445 blkkbkblf`g`abb`ghijklglhy$€'!" „!"‚p%}o{$$'st u
445 blkkbkbef`g`abb`ghijklglhwttst u