HomeMy WebLinkAbout8421 175th St Ne_BLD4317_2025 Three Nail Designs 425-512-3090 BeamChek v2020 licensed to: Three Nail Designs Reg # 8551-66863 Roberson Upper HDR's (Worse Case) Prepared by: JWH Date: 12/11/21 Selection 4x 8 DF-L #2 Lu = 0.0 Ft Conditions NDS 2018 Min Bearing Area R1= 2.7 in² R2= 2.7 in² (1.5) DL Defl= 0.03 in Data Beam Span 5.0 ft Reaction 1 LL 1031 # Reaction 2 LL 1031 # Beam Wt per ft 6.17 # Reaction 1 TL 1665 # Reaction 2 TL 1665 # Bm Wt Included 31 # Maximum V 1665 # Max Moment 2082 '# Max V (Reduced) 1263 # TL Max Defl L / 240 TL Actual Defl L / 958 LL Max Defl L / 360 LL Actual Defl L / >1000 Attributes Section (in³) Shear (in²) TL Defl (in) LL Defl Actual 30.66 25.38 0.06 0.03 Critical 21.35 10.52 0.25 0.17 Status OK OK OK OK Ratio 70% 41% 25% 20% Fb (psi) Fv (psi) E (psi x mil) Fc l (psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1170 180 1.6 625 Adjustments CF Size Factor 1.300 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Uniform LL: 413 Uniform TL: 660 = A Uniform Load A R1 = 1665 R2 = 1665 SPAN = 5 FT Uniform and partial uniform loads are lbs per lineal ft. Three Nail Designs 425-512-3090 BeamChek v2020 licensed to: Three Nail Designs Reg # 8551-66863 Roberson Cant Joist Under HDR Prepared by: JWH Date: 12/11/21 Selection (2) 2x 10 DF-L #2 Lu = 0.0 Ft Lu @OH = 0.0 Ft Conditions NDS 2018, Overhang Min Bearing Area R1= 0.3 in² R2= 3.7 in² (1.5) DL Defl= 0.08 in. Data Beam Span 13.0 ft Reaction 1 LL 175 # Reaction 2 LL 1456 # Beam Wt per ft 6.74 # Reaction 1 TL 204 # Reaction 2 TL 2312 # Bm Wt Included 101 # Maximum V 1678 # Overhang Length 2.0 ft Max Moment 3343'# Max V (Reduced) 1673 # Total Beam Length 15.0 ft TL Max Defl L / 240 TL Actual Defl L / < -1000 OH TL Actual Defl L / 320 LL Max Defl L / 360 LL Actual Defl L / < -1000 OH LL Actual Defl L / 679 Attributes Section (in³) Shear (in²) TL Defl (in) LL Defl OH TL Defl OH LL Defl Actual 42.78 27.75 -0.10 -0.04 0.15 0.07 Critical 40.53 13.94 0.65 0.43 0.20 0.13 Status OK OK OK OK OK OK Ratio 95% 50% 15% 8% 75% 53% Fb (psi) Fv (psi) E (psi x mil) Fc l (psi) Values Reference Values 900 180 1.6 625 Adjusted Values 990 180 1.6 625 Adjustments CF Size Factor 1.100 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Cl Stability @ OH 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Uniform LL: 40 Uniform TL: 50 = A (Uniform Ld on Backspan) Point LL Point TL Distance Par Unif LL Par Unif TL Start End 1031 F = 1665 (OH) 2.0 40 H = 50 0 2.0 H Uniform Load A Pt loads: F R1 = 204 R2 = 2312 BACKSPAN = 13 FT OH = 2 FT Uniform and partial uniform loads are lbs per lineal ft. Overhanging load distances are from R2. Three Nail Designs 425-512-3090 BeamChek v2020 licensed to: Three Nail Designs Reg # 8551-66863 Roberson Kitchen Bay Prepared by: JWH Date: 12/11/21 Selection 3-1/2x 9-1/4 2.0E TJ Parallam W.S. PSL Lu = 0.0 Ft Conditions NDS 2018 Min Bearing Area R1= 4.1 in² R2= 4.1 in² (1.5) DL Defl= 0.12 in Data Beam Span 8.0 ft Reaction 1 LL 2860 # Reaction 2 LL 2860 # Beam Wt per ft 10.12 # Reaction 1 TL 4460 # Reaction 2 TL 4460 # Bm Wt Included 81 # Maximum V 4460 # Max Moment 8921'# Max V (Reduced) 3601 # TL Max Defl L / 240 TL Actual Defl L / 366 LL Max Defl L / 360 LL Actual Defl L / 674 Attributes Section (in³) Shear (in²) TL Defl (in) LL Defl Actual 49.91 32.38 0.26 0.14 Critical 28.89 12.00 0.40 0.27 Status OK OK OK OK Ratio 58% 37% 66% 53% Fb (psi) Fv (psi) E (psi x mil) Fc l (psi) Values Reference Values 3600 450 2.0 1100 Adjusted Values 3706 450 2.0 1100 Adjustments CF Size Factor 1.029 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Uniform LL: 715 Uniform TL: 1105 = A Uniform Load A R1 = 4460 R2 = 4460 SPAN = 8 FT Uniform and partial uniform loads are lbs per lineal ft. Three Nail Designs 425-512-3090 BeamChek v2020 licensed to: Three Nail Designs Reg # 8551-66863 Roberson Mid Span Prepared by: JWH Date: 12/11/21 Selection 4x 6 DF-L #2 Lu = 0.0 Ft Conditions NDS 2018 Min Bearing Area R1= 2.2 in² R2= 2.2 in² (1.5) DL Defl= 0.02 in Data Beam Span 4.0 ft Reaction 1 LL 1080 # Reaction 2 LL 1080 # Beam Wt per ft 4.68 # Reaction 1 TL 1359 # Reaction 2 TL 1359 # Bm Wt Included 19 # Maximum V 1359 # Max Moment 1359'# Max V (Reduced) 1048 # TL Max Defl L / 240 TL Actual Defl L / 865 LL Max Defl L / 360 LL Actual Defl L / >1000 Attributes Section (in³) Shear (in²) TL Defl (in) LL Defl Actual 17.65 19.25 0.06 0.04 Critical 13.94 8.73 0.20 0.13 Status OK OK OK OK Ratio 79% 45% 28% 30% Fb (psi) Fv (psi) E (psi x mil) Fc l (psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1170 180 1.6 625 Adjustments CF Size Factor 1.300 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Uniform LL: 540 Uniform TL: 675 = A Uniform Load A R1 = 1359 R2 = 1359 SPAN = 4 FT Uniform and partial uniform loads are lbs per lineal ft. Three Nail Designs 425-512-3090 BeamChek v2020 licensed to: Three Nail Designs Reg # 8551-66863 Roberson Living Bay Prepared by: JWH Date: 12/11/21 Selection 3-1/2x 9-1/2 2.0E TJ Parallam W.S. PSL Lu = 0.0 Ft Conditions NDS 2018 Min Bearing Area R1= 5.0 in² R2= 5.0 in² (1.5) DL Defl= 0.19 in Data Beam Span 9.0 ft Reaction 1 LL 3533 # Reaction 2 LL 3533 # Beam Wt per ft 10.39 # Reaction 1 TL 5492 # Reaction 2 TL 5492 # Bm Wt Included 94 # Maximum V 5492 # Max Moment 12356'# Max V (Reduced) 4526 # TL Max Defl L / 240 TL Actual Defl L / 255 LL Max Defl L / 360 LL Actual Defl L / 467 Attributes Section (in³) Shear (in²) TL Defl (in) LL Defl Actual 52.65 33.25 0.42 0.23 Critical 40.13 15.09 0.45 0.30 Status OK OK OK OK Ratio 76% 45% 94% 77% Fb (psi) Fv (psi) E (psi x mil) Fc l (psi) Values Reference Values 3600 450 2.0 1100 Adjusted Values 3695 450 2.0 1100 Adjustments CF Size Factor 1.026 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Uniform LL: 785 Uniform TL: 1210 = A Uniform Load A R1 = 5492 R2 = 5492 SPAN = 9 FT Uniform and partial uniform loads are lbs per lineal ft. Three Nail Designs 425-512-3090 BeamChek v2020 licensed to: Three Nail Designs Reg # 8551-66863 Roberson Entry Door Prepared by: JWH Date: 12/11/21 Selection 4x 10 DF-L #2 Lu = 0.0 Ft Conditions NDS 2018 Min Bearing Area R1= 4.2 in² R2= 5.0 in² (1.5) DL Defl= <0.01 in. Data Beam Span 3.0 ft Reaction 1 LL 1663 # Reaction 2 LL 1941 # Beam Wt per ft 7.87 # Reaction 1 TL 2641 # Reaction 2 TL 3106 # Bm Wt Included 24 # Maximum V 3106 # Max Moment 3356'# Max V (Reduced) 2226 # TL Max Defl L / 240 TL Actual Defl L / >1000 LL Max Defl L / 360 LL Actual Defl L / >1000 Attributes Section (in³) Shear (in²) TL Defl (in) LL Defl Actual 49.91 32.38 0.02 <0.01 Critical 37.29 18.55 0.15 0.10 Status OK OK OK OK Ratio 75% 57% 10% 8% Fb (psi) Fv (psi) E (psi x mil) Fc l (psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1080 180 1.6 625 Adjustments CF Size Factor 1.200 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Point LL Point TL Distance Par Unif LL Par Unif TL Start End 1969 B = 3203 1.5 360 H = 530 0 1.5 730 I = 1150 1.5 3.0 I H Pt loads: B R1 = 2641 R2 = 3106 SPAN = 3 FT Uniform and partial uniform loads are lbs per lineal ft. m o .c s n s ig n s ig e s d e il 0 a 9 D n 0 il e 3 a er -2 N h 1 e .t 5 e w - r 5 h w 2 T w 4 A W , n OVERVIEWS N to NOT TO SCALE O g S in R rl E A B , E O N R t E S IM th A 5 J 7 1 1 2 4 8 APPROXIMATE FOOTAGE SUMMARY LOWER FLOOR 824 10-23-2021 UPPER FLOOR 715 REVISED TOTAL LIVING 1539 12-12-2021 GARAGE AREA 438 COVERED PORCH 98 1 EXISTING STRUCTURE 25'-6" 11'-5" 2'-4" 11'-9" 3'-10 1/4" 4'-0" 3'-6 3/4" 3'-10 1/2" 4'-0" 3'-10 1/2" 4040RS 4040RS m o 8 60 .c 4 s n " " s ig 6 BDR 3 BDR 2 6 '-1 '-1 n s 1 1 ig e s d e il 0 86 a 9 0 4 D n 0 il e 3 a er -2 2668 2668 N h 1 e .t 5 " 86 e w - 6'- 42 r 5 3 h w 2 T w 4 " 2668 " 0 0 '- " '- 1 9 1 3 '- 3 DN 8 40'-6" 8 7'-8" 2'-0" 4'-0" 2'-0" 9'-0" 4'-4" 5'-6" 6'-0" 6 0 1'-0" 1'-0" 6 6" 3'-0" 6" 3'-0" 5'-0" 4'-0" 6" " 3040SH " 9 0 '- '- 2 16 4 FX 4 1 BDR 1 40 0F " " 6 X 0 0 1 5068 '- 4040RS '- S 2 2 R "0 03 '- " 0 2 9 2 '- 8 " 86 /2 OPEN TO 42 "0 11 86 '- '-5 " BELOW 42 4 0'- A NOOK 7 W " " , 0 0 " '-2 '-2 0 FAMILY n '- S 3 "0 R 1 6 3068 '-4 30 N to 4040RS 4040RS 4 O g 1'-0" 1'-0" S in 4'-0" 6" 4'-0" " 0'- rl 3'-6" 2'-4" 3'-10 1/2" 10'-6" 5'-3 1/2" " 6 R /2 8 25'-6" 10 60 E A 1 3 , '- 3 3068 B E UPPER FLOOR O N SCALE 1/4" = 1FT 86 R t 4 2 " 0 E '- S 5 " 3 0 '-3 IM th 3 A 5 J 7 1 " 0 1 '- 41 LIVING 2 4 8 UP GARAGE "0 '- 0 2 1 3068 65 X 0 0F FX 5 6 1 " 0 4050RS '- 6 PORCH 8070 8070 10-23-2021 1'-6" 2'-3" 8'-0" 8'-0" 2'-3" REVISED 18'-6" 22'-0" 12-12-2021 40'-6" LOWER FLOOR SCALE 1/4" = 1FT 2 m o UPPER FLOOR .c MATCH EXISTING s PLT HT 8'-1 1/8" n ASSUMED s ig n s ig e s d e il 0 a 9 D n 0 il e 3 a er -2 UPPER FLOOR N h 1 FRAMING 10 1/4" ee .tw 5- r 5 h w 2 LOWER FLOOR T w 4 PLT HT 8'-1 1/8" LOWER FLOOR FRAMING 10 1/4" FRONT ELEVATION SCALE 1/4" = 1FT A 12x18 GABLE END VENT W , n N to O g S in R rl E A B , E O N R t E S IM th A 5 J 7 3 TAB COMP. ROOF 1 LEFT ELEVATION SCALE 1/8" = 1FT OVER 30lb FELT RIGHT ELEVATION SCALE 1/8" = 1FT 1 2 4 8 APPROXIMATE FOOTAGE SUMMARY LOWER FLOOR 824 UPPER FLOOR 1172 10-23-2021 ( NEW 457 ) REVISED REAR ELEVATION SCALE 1/8" = 1FT TOTAL LIVING 1996 12-12-2021 GARAGE AREA 438 COVERED PORCH 98 3 PROPOSED ADDITION m o .c s n s ig n s ig e s d e il 0 a 9 D n 0 il e 3 a er -2 8'-0" N h 1 3040SH e .t 5 1 X 64 - 0F 0 e w 4 FX r 5 6 1 5068 4040RS h w 2 T w 4 3 1/2 x 9 1/4 2.0E PSL NOOK " 0'- S FAMILY 3 R 1 6 3068 3 0 4 8 6 0 3 3068 4 x 6 DF #2 A 86 W 4 2 , n NO CHANGES TO LOWER FLOOR PLAN N to * NOTE NEW BEAMS O g S in " rl 0 R '- 4 A 1 LIVING E , B E UP GARAGE O N R t ADD OR VERIFY MIN 4 x 10 DF #2 HEADER E S 3 1/2 x 9 1/2 2.0E PSL IM th A 5 J 7 1 3068 65 X 0F 0F 1 X 65 1 1 4050RS 2 9'-0" PORCH 4 8 8070 8070 LOWER FLOOR SCALE 1/4" = 1FT 10-23-2021 REVISED 12-12-2021 4 m o .c s n s ig n s ig e s d e il 0 a 9 D n 0 15'-0" il e 3 a e - 5'-2 1/2" 5'-0" 4'-9 1/2" r 2 N h 1 5040RS WALL LINE "C" 4040RS 4040RS ee .tw 5- r 5 R602.10.4.2 R310 h w 2 CONTINUOUS SHEATHING EGRESS T w 4 WINDOW EXTERIOR HEADERS TO BRACED WALL METHOD BE 4x8 DF #2 U.N.O. 8 6 0 4 R602.10.4.2 & TABLE 602.10.4 METHOD: CS-WSP "6 BDR 4 BDR 3 '- BDR 2 EXTERIOR SHEATHING 1 1 3/8" 24/0 RATED ON STUDS AT 16" OC VERIFY OR CHANGE EXISTING SHEATHING TO MIN 6d COMMON AT 6" OC EDGES AND 12" OC FIELD 3/8" 24/0 RATED ON STUDS AT 16" OC PER TABLE R602.3(3) 6d COMMON AT 6" OC EDGES AND 12" OC FIELD PER TABLE R602.3(3) 8 INTERIOR SHEATHING 6 0 1/2" GWB 1 1/4" SCREWS TYPE W OR S 4 R314 SD 7" OC EDGES AND 7" OC FIELD - OR - 5/8" GWB W/ 1 5/8" SCREWS TYPE W OR S 7" OC EDGES AND 7" OC FIELD PER TABLE R602.3(1) 6068 2668 2668 2668 " 4'- NO CHANGES TO 8 TABLE R602.10.5 2 64 MINIMUM PANEL LENGTH 24" 0 CROSS HATCHED AREA 2 3x 2 C S " 7 2 I SE " B 0 N T C 2668 A 0 " 8 I T C '- E R314 SD R M A A TABLE R602.10.3(3) - SDC D1 13 IN W (INTERPOLATION USED) LL R315 CM DN DETERMINES LENGTH OF L M1505.4 , BRACED WALL PANELS A " ADD OR VERIFY MIN W D 120 cfm WHOLE HOUSE n FOR EACH WALL LINE. " E FAN TO RUN 2 OUT IN OF EVERY 4 HOURS N to L 8 LL 60 O g VERIFY OR CHANGE EXISTING SHEATHING TO MIN A 6 WALL LINE MIN. REQ. BRACED ACTUAL CONTRIBUTING 3/8" 24/0 RATED ON STUDS AT 16" OC W S in DESIGNATION PANEL LENGTH BRACED WALL LENGTH " 6d COMMON AT 6" OC EDGES AND 12" OC FIELD 2 PER TABLE R602.3(3) rl '- R A 3.2' 4.0' 51 A B 6.2' 29.0' BDR 1 E C 3.2' 10.0' , D 6.2' 25.5' BONUS S B R E 0 ROOM 30 O HATCHING INDICATES 2 N BRACED WALL PANEL R t PER TABLE R602.10.4 8 6 OPEN TO 42 E S 8 6 BELOW 42 IM th A 5 " " J 7 0 WALL LINE "A" 0 '- '- 2 2 1 1 4040RS 4040RS 4040RS 4040RS 2 UPPER FLOOR 4 1'-0" 1'-0" TABLE M1505.4.3(1) SCALE 1/4" = 1FT 4'-0" 6" 4'-0" 8 DWELLING UNIT NUMBER OF BEDROOMS 2'-6" 10'-6" 2'-0" FLOOR AREA 0-1 2-3 4-5 6-7 >7 (square feet) Airflow in CFM <1,500 30 45 60 75 90 1,501-3,000 45 60 75 90 105 3,001-4,500 60 75 90 105 120 TABLE M1505.4.3(2) RUN TIME % OF 4 HOUR SEGMENT 25 33 50 66 75 100 FACTOR 4 3 2 1.5 1.3 1 10-23-2021 REVISED 12-12-2021 5 m o .c s n s ig n s ig e s d e il 0 a 9 D n 0 il e 3 9" CANTILEVERED DOUBLE JOISTS a e - FLOOR JOISTS UNDER HEADER r 2 N h 1 e .t 5 e w - r 5 R502.7 h w 2 GN SOLID BLOCKING T w 4 I E M R A E R H F T T U R O A Y T A S L " EXISTING 0 '- 3 ( CROSS HATCHED ) 1 FLOOR TO REMAIN AS IS ADD OR VERIFY MIN 4x4 POST ON CONCRETE PAD WITHIN 24" OF NEW POINT LOAD 15'-2" 3'-4" R502.7 A SOLID BLOCKING ADD OR VERIFY MIN OVER WALL 4 x 10 DF #2 UNDER WALL ON 4x4 POSTS W OR 4x6 POSTS AT SPLICES SPACED NO MORE THAN 4'-9" o.c. , n N to FLOOR JOISTS TO BE O g " 2 x 10 DF #2 AT 16" o.c. 0 '-4 S in 1 R rl E A , UP B E O N R502.7 R t NO CHANGES TO FOUNDATION WALLS FLOOR AND LOWER SOLID BLOCKING E S OVER BEAM ROOF FRAMING th SCALE 1/4" = 1ft CANTILEVERED IM FLOOR JOISTS A 57 FOUNDATION J G SCALE 1/4" = 1ft 1 N A LOWER ROOF FRAMING TO H " 1 RE 21 MATCH EXISTING LOWER ROOF. V : SE 6:12 PITCH ASSUMED 2 O L L AC BA 4 I P G Y T 8 T A MATCH OVERHANG 10-23-2021 REVISED 12-12-2021 6 GENERAL NOTES (REV 12-07-2021) 2018 WSEC - 1.5 CREDITS REQUIRED 1.1 - 0.5 credits Prescriptive compliance is based on Table R402.1.1 with the following modifications: ALL CONSTRUCTION MUST COMPLY WITH Vertical fenestration U = 0.24. 2018 IBC, 2018 IRC, AND 2015 WSEC. 3.1 - 1.0 credits Energy Star rated (U.S. North) Gas or propane furnace with minimum AFUE of 95% or LOADS, GRADES, ETC.* Energy Star rated (U.S. North) Gas or propane boiler with minimum AFUE of 90%. m To qualify to claim this credit, the building permit drawings shall specify the option being selected and shall specify the o ROOF LIVE LOAD - 25 heating equipment type and the minimum equipment efficiency. .c ROOF TOTAL LOAD - 40 s FLOOR LIVE LOAD - 40 n FLOOR TOTAL LOAD - 50 s ig n s JOISTS - DF #2 / MFG I-JOISTS ig e STUDS - HF STUD s d e il 0 RAFTERS - HF #2 a 9 CONCRETE - 2500 psl D n 0 il e 3 SEISMIC ZONE - D a er -2 WIND SPEED - 85 N h 1 EXPOSURE - B TYPICAL OVERHANG e .t 5 FROST DEPTH - 24" AT EAVES: 18" er w -5 SOIL BEARING - 1500 psf h w 2 T w 4 R806 ATTIC VENTING * USE ENGINEER'S DESIGN SPECS AND TOTAL NET FREE VENTILATING AREA TO BE 1/300 OF THE AREA OF SPACE VENTILATED CONNECTIONS WHEN DIFFERENT IF 40-50& OF VENTS ARE NOT MORE THAN 3'-0" (VERTICALLY) BELOW RIDGE AND REMAINDER OF VENTING IS PROVIDED S IN LOWER 1/3 OF THE ATTIC SPACE I S AF50 VENTS PROVIDE 50 sq. in. NFV ATTIC VENTING GABLE END VENTS PROVIDE 75 sq. in. NFV ) A PER R806 RAFTERS AND TRUSSSES N DOUBLE TOP PLATE PER PLAN OR TRUSS MFG 2" HOLE IN BIRD BLOCKS PROVIDE 3 sq. in. NFV D WITH SPLICES OVER STUDS E I (3 HOLES PER BLOCK GIVE 9 sq. in.) MIN 24" SPACING OF SPLICES H A NAILING PER TABLE R602.2(1) LINES 12 & 13 3/8" - 1/2" ROOF OSB C M NAILED 8d AT 6" O.C. EDGE VAULTED (RAFTER) CEILING (65,808) Square inches of attic space R502.11 T E AND 12" O.C. FIELD * TO HAVE R-38 BATTS (219) Square inches of venting required MFG TRUSSES AT 24" o.c. G A R DESIGNED AND ENGINEERED N H O Requirements met by: BY TRUSS MFG AND INSTALLED I SS T (1) AF50 Vents PER TRUSS MFG SPECS. T F CEILING TO HAVE R-49 (1) Gable Vents MATCH EXISTING PITCH. S O O HURRICANE CLIP BLOWN IN INSULATION (8) Bird Blocks 6:12 PITCH ASSUMED. I R HEADER PER PLAN AT EACH RAFTER X C O E ( R TOENAIL (3) 16d BOX OR 10d COMMON EACH TRUSS OR RAFTER TO PLATE R602.7.5 (2) ON ONE SIDE AND JACK AND (1) ON OPPOSITE SIDE * A KING STUDS HEADER PER PLAN W 3/8" - 1/2" WALL OSB NAILED 8d AT 6" O.C. EDGE INSULATED WALLS TO BE , AND 12" O.C. FIELD * 2x6 HF #2 AT 16" O.C WITH R-21 BATTS n DN N to ALL CONNECTIONS PER TABLE R602.3(1) ALL CONNECTIONS PER TABLE R602.3(1) O g S in 2-2 2-1 R rl E A B , R311.7.8 PLYWOOD FLOOR DIAPHRAGM E CONTINUOUS 1-1/4" - 2" GLUED AND NAILED WITH 1-1/2" G DIAMETER HANDRAIL RING OR SCREW SHANK MIN -16d AT 16" O.C. SOLE PLYWOOD FLOOR DIAPHRAGM N O REQUIRED ON AT LEAST ONE -16d AT 16" O.C. SOLE 12.5 ga (0.099") SHANK DIA. PLATE TO JOISTS OR GLUED AND NAILED WITH 1-1/2" AH " N SIDE AND TO BE BETWEEN 34" PLATE TO JOISTS OR BLOCKING * RING OR SCREW SHANK MIN R 2 AND 38" VERTICALLY ABOVE BLOCKING * -END NAIL (2) 16d 12.5 ga (0.099") SHANK DIA. EV 1: t DOUBLE JOIST -END NAIL (2) 16d SOLE PLATE S R TREADS AT TOP OF SOLE PLATE TO EACH STUD * OL EL LSC CONNECTOR OR EQUAL STAIRS TO EACH STUD * AC BA E S I P G Y T T A IM th5 RIM JOIST TOE NAILED A 7 TO TOP PLATE WITH J FLOOR JOISTS 8d AT 6" O.C. * R302.7 SOFFIT BOARD PER PLAN FLOOR JOISTS PER PLAN GIRDER TRUSS 1 MIN 1/2" GWB UNDER STAIRS SHEAR WALL SHEATHING 1 LAPS RIM JOIST * 2 R-30 BATTS DOUBLE TOP PLATE 2x12 STRINGER WITH (2) 16d END NAIL WITH 2x4 SPACER OR (3) 16d TOE NAIL* 4 DOUBLE TOP PLATE WITH (2) 16d TO EACH STUD * R311.7.5 OR MUD SILL WITH (3) 8d TOENAILED EACH JOIST * 8 -RISER SHALL BE NO MORE THAN 7.75" -TREAD SHALL BE NO LESS THAN 10" ROOF FRAMING GABLE PITCH TO MATCH EXISTING FRONT GABLE. 12:12 ASSUMED -GREATEST RISER OR TREAD SHALL NOT ALL CONNECTIONS PER TABLE R602.3(1) ALL CONNECTIONS PER TABLE R602.3(1) EXCEED THE SMALLEST BY MORE THAN 3/8" SCALE 1/4" = 1ft 1-3 TYPICAL STAIRS 1-2 TYPICAL CANTILEVER 1-1 WALLS TO FLOOR 10-23-2021 REVISED 12-12-2021 7 2018 Washington State Energy Code Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Single Family New & Additions (effective February 1, 2021) These requirements apply to all IRC building types, including detached one- and two-family dwellings and multiple single-family dwellings (townhouses). Project Information Contact Information Jaime Roberson 8421 175th St NE, Arlington, WA Instructions: This single-family project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1 - Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. Authorized Representative Date All Climate Zones (Table R402.1.1) R-Value a U-Factor a Fenestration U-Factor b n/a 0.30 Skylight U-Factor b n/a 0.50 Glazed Fenestration SHGC b,e n/a n/a Ceiling e 49 j 0.026 Wood Frame Wall g,h 21 int 0.056 Floor 30 0.029 Below Grade Wall c,h 10/15/21 int + TB 0.042 Slab d,f R-Value & Depth 10, 2 ft n/a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less a than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified in the table. b The fenestration U-factor column excludes skylights. "10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" means R-5 thermal break between floor slab and basement wall. d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. For single rafter- or joist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth e extends over the top plate of the exterior wall. R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for g climate zone 5 of ICC 400. Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10 insulation. Prescriptive Path Single Family 2018 Washington State Energy Code-R 1 2018 Washington State Energy Code Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Single Family New & Additions (effective February 1, 2021) Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) to achieve the following minimum number of credits. To claim this credit, the building permit drawings shall specify the option selected and the maximum tested building air leakage, and show the qualifying ventilation system and its control sequence of operation. 1. Small Dwelling Unit: 3 credits Dwelling units less than 1,500 sf in conditioned floor area with less than 300 sf of fenestration area. Additions to existing building that are greater than 500 sf of heated floor area but less than 1,500 sf. 2. Medium Dwelling Unit: 6 credits All dwelling units that are not included in #1 or #3 3. Large Dwelling Unit: 7 credits Dwelling units exceeding 5,000 sf of conditioned floor area 4. Additions less than 500 square feet: 1.5 credits All other additions shall meet 1-3 above Before selecting your credits on this Summary table, review the details in Table 406.3 (Single Family), on page 4. Summary of Table R406.2 Heating Credits - select ONE Fuel Normalization Descriptions User Notes Options heating option 1 Combustion heating minimum NAECAb 0.0 2 Heat pumpc 1.0 3 Electric resistance heat only - furnace or zonal -1.0 4 DHP with zonal electric resistance per option 3.4 0.5 5 All other heating systems -1.0 Credits - select ONE Energy Energy Credit Option Descriptions energy option from each Options category d 1.1 Efficient Building Envelope 0.5 ï‚´ 1.2 Efficient Building Envelope 1.0 1.3 Efficient Building Envelope 0.5 1.4 Efficient Building Envelope 1.0 1.5 Efficient Building Envelope 2.0 1.6 Efficient Building Envelope 3.0 1.7 Efficient Building Envelope 0.5 2.1 Air Leakage Control and Efficient Ventilation 0.5 2.2 Air Leakage Control and Efficient Ventilation 1.0 2.3 Air Leakage Control and Efficient Ventilation 1.5 2.4 Air Leakage Control and Efficient Ventilation 2.0 a 3.1 High Efficiency HVAC 1.0 ï‚´ 3.2 High Efficiency HVAC 1.0 3.3a High Efficiency HVAC 1.5 3.4 High Efficiency HVAC 1.5 3.5 High Efficiency HVAC 1.5 3.6a High Efficiency HVAC 2.0 4.1 High Efficiency HVAC Distribution System 0.5 4.2 High Efficiency HVAC Distribution System 1.0 Prescriptive Path Single Family 2018 Washington State Energy Code-R 2 2018 Washington State Energy Code Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Single Family New & Additions (effective February 1, 2021) Summary of Table R406.2 (cont.) Credits - select ONE Energy Energy Credit Option Descriptions (cont.) energy option from User Notes Options each category d 5.1d Efficient Water Heating 0.5 5.2 Efficient Water Heating 0.5 5.3 Efficient Water Heating 1.0 5.4 Efficient Water Heating 1.5 5.5 Efficient Water Heating 2.0 5.6 Efficient Water Heating 2.5 6.1e Renewable Electric Energy (3 credits max) 1.0 7.1 Appliance Package 0.5 Total Credits 1.5 CLEAR FORM a. An alternative heating source sized at a maximum of 0.5 W/sf (equivalent) of heated floor area or 500 W, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category 5. Option 5.1 may be combined with options 5.2 through 5.6. See Table 406.3. e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See the complete Table R406.2 for all requirements and option descriptions. Please print only pages 1 through 3 of this worksheet for submission to your building official. Prescriptive Path Single Family 2018 Washington State Energy Code-R 3       !"#$  %&'( )*+,-). /0'1( 2345+)*+,-). /0'1/6677 8   9:; /0'1<=<><? ,@5.A:).BCD8 =%1' 2345+)*+,-). E%1 9F 8F 9 G0 H,)*+,-). 9IA435@JK)4 >'%%LM%N OO5:5).:):;+-+K).OP@)),Q*).R-,))43.O*+O,))4S T0U%1 VJVV >WUX V (UY%L>%7 V =%17U'%1 Z''U1'[%U \=%6 \77U6 G]7 X% >U7 $ ^_ /77`16% 3+@a..2).+- % _3,K+@b OO,+--+A3@+-K,5c:5). d.+,34+ d.+,_;).+ ).5.A VV! "$ef VVD989VVVV VV8   9e #^g e $ 01hij7 3:+ +k5+dac++-K,5c:5).--5A.+O)+k5+d:3:R-  !  V lm! "#$   !  V )k3e+3:). "#$   !  V )@3.OR-+5--R+-P),.O-:),a3OO5:5).J_! "#$   !  V )K)44+.:-Bfn_CF^F! "#$                         ! "  #$%& ' ()* #++*),-!.++"!/*-# ' *%--0!- 1  +" /)!21!-)-3 ").),)!-$ 454!.67),761# -) ##2 !7 1 6 "*)- "2--)-3 *!-37  11)# !.7 7!( 8 7 +"!+!1 ###))!-.!"76!2*#7/ ,!/ " #7 1 6 " *)- 8  ++*),-)1-!6+"!+!1)-3!3!/ "),*6)77)1- 69!-)-312:()*6)7-!,7-3 1!7  *%--0!- 1 ;)1)-3.!!+")-!.7 7!( 3"3 8 !1)9 &<4;4=>?=8=1. ;)1)-3!!/ "3 &='<1. @ABCDDEFB  )*  (  GHIJGKKHLGJLGMNOPQRSTPUNVRWXTYZ[\  GHIJGKKGLGJLGMNOPQRSTPUN]^WUTYZ[\  GHIJGKKJLGJLGMNOPQRSTPUN_`abYZ[\  GHIJGKIcLKIGdNeZZ^fgWhfPUWU[`fhR]^WUYZ[\