HomeMy WebLinkAboutCompleted Utility Availability Certificate WATER AND SEWER AVAILABILITY REQUEST
Community and Economic Development
City of Arlington• 18204 591h Avenue NE•Arlington,WA 98223 •Phone(360)403-3551
Submittal Requirements:
1. Complete Application
2 8-1/2"x 11"Site Plan/Sketch of the Proposal
Type of Request: ❑ Water Only ❑ Sewer Only 0✓ Water and Sewer
Location/Legal Property Address: 2310 WA-530 ARLINGTON, WA 98223
Lot#: Parcel ID No(S): 31050800301300,31050800301500,31050800301700 Subdivision:
Project Scope of Work: New restaurant with parking lot, and new water/sewer services
Owner Name: V12 Venture Capital, LLC Office No.:
Email Address: jagbir_singh92@yahoo.com Cell No.:
Mailing Address: City: State: Zip:
Owners Agent: Gerald Koh Office No.: 3106345204
Email Address: gkoh@milrose.com Cell No.: 3106345204
Mailing Address: 8370 Wilshire Blvd #330 city: Beverly Hills State: CA zip: 90211
RESIDENTIAL INFORMATION
❑Proposed Single Family Residence ❑Existing Single Family Residence ❑Accessory Dwelling Unit
❑Proposed Multi-Family Residence: #of Units #of Buildings ❑Residential Plat:#of Lots
COMMERCIAL INFORMATION
❑✓ Binding Site Plan/Plat:#of Lots 3 #of Phases 1 #of Buildings Total Square Footage 39,341
TYPE OF COMMERCIAL USE
❑Hotel/Motel ❑✓ Food Service ❑Medical/Dental ❑Office ❑ Retail
❑Vehicle Service ❑Warehouse/Storage ❑ Industrial ❑ Other(specify):
Commercial Water Usage:Monthly Estimation: Gallons
F_ WATER,SEPTIC SYSTEM AND FIRE
Is there an existing Well on the property? Yes �No Is there an existing Septic System on-site? Yes �✓ No
Water Meter Size Requested? ❑ 5/8" ❑r 1" ❑ 1.5" ❑r 2" ❑3" ❑4" ❑6"
Type of Fire Protection Requested? ❑r Fire Sprinkler System r❑Fire Hydrant ❑Unknown
I,the undersigned,request City of Arlington Utilities Division to certify willingness to provide water and/orsewer as indicated.
The above information is complete and accurate to the best of my knowledge. I understand that any changes to the above
information must be reported immediately to the City of Arlington Utilities Division as a condition of Utility Availability approval.
Gerald Koh 6/18/26
Signa ure(owner/agent) Print Name Date
Pagel of 2 REV02.2022
TO BE COMPLETED BY THE CITY OF ARLINGTON
j CITY OF ARLINGTON UTILITIES DIVISION - PRELIMINARY INFORMATION I CERTIFICATION
This non-binding preliminary commitment is only valid for the above referenced property in accordance
with City of Arlington policies and for only 18 months.
YES A water main or other capital facility improvement ® is required; ❑ is not required
(If required, refer to below conditions)
Water is presently available from City of Arlington to service the above referenced property and
YES specified number of connections per the below conditions and upon payment of applicable
connection fees and charges.
Fire Flow Estimate: STATIC PRESSURE 124 PSI RESIDUAL PRESSURE_23 PSI FLOW 1,361 GPM
A sanitary sewer main or other capital facility improvement ® is required; ❑ is not required
YES
(If required, refer to attached conditions)
Sanitary sewer is presently available from City of Arlington to service the above referenced
YES property and specified number of connections per the below conditions and upon payment of
applicable connection fees and charges.
Other: Water and sewer service is available at this location per the below conditions.
Approved By: Date: 071'f_G
EXPIRES 18 M TH FROM DATE OF ISSUE
COMMENTS:
1. Water service is available for this project; water main improvements will be required as a
condition of service. The existing 10-inch water main bordering the property frontage will
be replaced with a 12-inch ductile iron water main; includes the replacement of existing
fire hydrant (FH-1062) at a location necessary to meet site development requirements.
Please coordinate with the Arlington City Engineer for water main replacement, FH water
service line connection, meter locations, backflow protection, utility easements, and any
other City of Arlington water supply requirements.
2. Sewer service is available for this project; a sewer main replacement is required as a
condition of service. Replace existing MH-1826 and MH-1823, along with pipe segment
P-1923 between the two manholes (approx. 68-ft long, 8" dia.). The side sewer connection
point will beat MH-1826. Please coordinate with the Arlington City Engineer for specifics
pertaining to sewer main replacement, service location, utility easements, required pipe
slope, monitoring manhole location, pretreatment requirements, and any other City of
Arlington sewer requirements.
3. Water and Sewer system improvements shall be designed and constructed in accordance with
City of Arlington Design and Construction Standards.
4. Fire flow data is from water model node 2025-J-1264 near FH-1062.