HomeMy WebLinkAbout20260312_PJA26-0143_Utility Availability Certificate i
WATER AND SEWER AVAILABILITY REQUEST
Community and Economic Development
City of Arlington • 18204 591h Avenue NE•Arlington,WA 98223 • Phone (360)403-3551
Submittal Requirements:
1 Complete Application
2 8-1/2"x 11"Site Plan/Sketch of the Proposal
Type of Request: ❑ Water Only ❑ Sewer Only ❑✓ Water and Sewer
Location/Legal Property Address: 4400 Block Airport Blvd
Lot#: Parcel ID No(s): 31052100202000 Subdivision:
Project Scope of work: Holman Recovery facility
Owner Name: Scott Wammack- Grandview Homes Office No.: 360-435-7171
Email Address: gv@grandviewinc.com Cell No.:
Mailing Address: PG Box 159 city: Arlington State: WA zip:98223
Owners Agent: David Harmsen - Harmsen LLC Office No.: 425-252-1884
Email Address: davidh@harmsenllc.com Cell No.:
Mailing Address: 2822 Colby Ave Suite 2^Ci : Everett State: WA zip: 98201
RESIDENTIAL INFORMATION
❑ Proposed Single Family Residence ❑ Existing Single Family Residence ❑Accessory Dwelling Unit
❑ Proposed Multi-Family Residence:#of Units #of Buildings ❑ Residential Plat: #of Lots
COMMERCIAL INFORMATION
❑ Binding Site Plan/Plat: #of Lots #of Phases ' #of Buildings Total Square Footag�C,8 qo
TYPE OF COMMERCIAL USE
❑ Hotel/Motel ❑ Food Service ❑ Medical/Dental ❑Office ❑ Retail
❑Vehicle Service ❑Warehouse/Storage ❑ Industrial 0 Other(specify): Recovery center
Commercial Water Usage: Monthly Estimation: unknown - Gallons
WATER,SEPTIC SYSTEM AND FIRE
Is there an existing Well on the property? ❑Yes 0No Is there an existing Septic System on-site? ❑Yes ❑✓ No
Water Meter Size Requested? ❑ 5/8" ❑ 1" ❑ 1.5" ❑✓ TL .❑✓ 3" ❑4" ❑ 6"
Type of Fire Protection Requested? ❑✓ Fire Sprinkler System ❑✓ Fire Hydrant ❑Unknown
I, the undersigned,request City of Arlington Utilities Division to certify willingness to provide water and/or sewer as indicated.
The above information is com fete and accurate to the best of my knowledge. I understand that any changes to the above
information must be report immediately to the City of Arlington Utilities Division as a condition of Utility Availability approval.
David Harmsen 7/9/25
signature owner/age t) rint Name Date
Page 1 of 2 REV02.2022
TO BE COMPLETED BY THE CITY OF ARLINGTON
CITY OF ARLINGTON UTILITIES DIVISION - PRELIMINARY INFORMATION I CERTIFICATION
This non-binding preliminary commitment is only valid for the above referenced property in accordance
with City of Arlington policies and for only 18 months.
YES A water main or other capital facility improvement ® is required; El is not required
(If required, refer to below conditions)
Water is presently available from City of Arlington to service the above referenced property and
YES specified number of connections per the below conditions and upon payment of applicable
connection fees and charges.
Fire Flow Estimate: STATIC PRESSURE 140 PSI RESIDUAL PRESSURE_59 PSI FLOW 1,378 GPM
NO A sanitary sewer main or other capital facility improvement El isrequired; ® is not required
(If required, refer to attached conditions)
Sanitary sewer is presently available from City of Arlington to service the above referenced
YES property and specified number of connections per the below conditions and upon payment of
applicable connection fees and charges.
Other: Water and Sewer service is available at this location per the below conditions.
Approved By: Date: al 17 hive S__
EXPIRES JS MONT S FR M DATE OF ISSUE
COMMENTS:
1. Water service is available for this application. The proposed water main improvements
contained with this application appear to meet the project needs and the City's future
needs. However, please coordinate with the Arlington City Engineer for water main line
extension alignment, service line connection, meter locations, backflow protection, utility
easements, and any other water supply requirements.
2. Sewer service is available for this project and the proposed sewer connection
improvements contained with this application appear to meet the project needs. However,
please coordinate with the Arlington City Engineer for specifics pertaining to off-site sewer
connection point, service location, utility easements, required pipe slope, monitoring
manhole location, pretreatment requirements, and any other City of Arlington sewer
requirements.
3. Any wells and septic systems on the development property are to be abandoned per Arlington
Municipal Codes 13.04.140 and 13.08.160 as a condition of service.
4. Water and Sewer system improvements shall be designed and constructed in accordance with
City of Arlington Design and Construction Standards.
5. Fire flow data is from Node 2025-J-505, near fire hydrant H-960 located on Airport Blvd near
Fire Station 48.