Washington State Assn of Fire Marshals
WASHINGTON STATE Food Truck Inspection Checklist
FIRE MARSHALS
2021 IFC (as of 0212202-6)
The WSAFM Food Truck Inspection Program
A sing p s accepted
le inspection i by participating jurisdictions throughout Washington. This document is
a standardized inspection recognized by multiple fire jurisdictions. You may receive a single inspection
once every 12 months from any participating jurisdiction, and that inspection will be recognized by all r
participating jurisdictions. This document must be posted in the vehicle at all times. For a list of
_
participating jurisdictions please visit: www.wsafm.com/Food_Trucks
Local permits are still required. You must contact the local fire department where you are vending and,
if required, receive a food truck permit prior to operating in that jurisdiction. Many jurisdictions will
reduce their permit fees if you have received a valid WSAFM Food Truck inspection from another
jurisdiction.
Vehicle and Operator Information
Name of Mobile Food Vehicle :
Mailing Address :
Contact Person :
Phone Number : Email :
L & I Number ( VEN ) : ys "Z01 License Plate # :
Inspection Agency and Results �6v
3/13/26 Fire Agency:
North County Regional Fire Authority
Date Inspected :
Inspector Si nature � �� (��� 5 �1� c '
P g
r
Summary of Inspection — WSAFM
• Approved — No violations . Approved to operate , correct violations by date below .
Q Not approved to operate .
Violations noted must be corrected by , / Z/ When all violations are corrected ,
_/
email/call for,sign off and forr permit issuance f no permit issued during inspection .
Ins Name :` . � " �� r' �`—� Phone or email : _ � � _ �
P �r r�--- ------- - --- -�-----
WSAFM Ins ect- ,_lri Checklist Scv ,�-/-k
p J
Documentation 6V1_ PASS FAIL N/A
1 . Washington State L& I Approval Insignia 0
2 . Fire Department Permit ( 2021 WA IFC 319 . 2 ) 0
Cooking System Type - 1 Hood (If produces grease laden vapors) PASS FAI N/A
PP 1 .
Cookingsuppression system is UL300 listed , serviced , and cleaned . $L( 2021 WA IFC 319 . 4 . 1 and 319 . 10 . 1 ) �
Washington State Association of Fire Marshals Regional Food Truck Inspection Checklist, 2021 IFC (02122026), page 1
t,
r
Washington State Assn of Fire Marshals
STAT, d Truck Inspection Checklist
r F�tE �sx�s F°°
2021 IFC (as of 02122026)
LP tanks securely mounted , a piping p of
d ndprotected . ( 2021 WA IFC 319 • 8 • 2 Al 0 o
& 319 .8 . 4)
P as d operational and tested . ( 2021 WA IFC 319 . 8 . 5) }� � CJ
h• L g alarm installed , p
• Last test date :
® [7
P shut 2021 NFPA 96 17 .7 .4 . 1) �
�. L t off valves installed and accessible .
S. LP tanks used or stored outside of the vehicle shall be secured with a
non - combustible strapor chain in an upright position and protected
from impact . ( 2021 NFPA 96 17 . 7 )
PASS FAIL N/A
CNG Cooking Systems 0 0 0
1 .
CNG containers are NGV - 2 cylinders with a maximum aggregate
<ac
caPi of 1300 pounds . ( 1 ft3 = 8 Ibs ) (2021 WA IFC 319 .9 . 1 . 1)
• Num of tanks :
• Size of tan
• Tank expiration da .
• Date last inspected :
(Every 3 years) (IFC 319. 10. 3) -
• Date of last hydro :
securely mounted , piping protected , and not inst Ile. in areas .• -
2 . Tanks secu y
subject to direct vehicle impact . ( 2021 WA IFC 319 . 9 . 1 . 2 )
subs tailed
3 . Methane gas alarm installed , operational and tested per
manufacturer' s recommendation . ( 2021 WA IFC 319 .9 . 4)
• Last tested date : -
PA S FAIL N/A
Portable Fire Extinguishers deep fat fryer 0 0
installed along egre
Extinguisher instass path (If using .
1, Class K g or solid fuels). ( 2021 WA IFC 906 . 4 )
• Date last Serviced (Annually)
Extinguisher .
K Extin
ions stem use placard installed near Class g
2 . Fire protect Y
( NFPA 96 11 . 2 . 1 . 1 ) provided along egress
le extinguisher for combustibles shall be -300
3 . Portable Class K ( if required ) for U
A : 10B : C in addition to - '-
path . Minimum 2 . .. • a-, .
for generator use , and 2A: 40B : C for LP -gas/ propane
system , 20B . 0
( 2021 WA IFC 906 . 3 )
• Date last serviced (Annually)
PASS FAIL N/A
Electrical
1 . Extension cords protected from damage . C) C
2 . No open electrical junction boxes or wiring .
Fire Marshals Regional Food Truck Inspection Checklist, 2021 IFC v02122026), page 3
Washington State Association of
L.
,t
�T
J
f • Date of last service : (Semiannually)
• Date of last cleaning :
2. Manual Pull Station accessible and unobstructed .
3. Signage per 2021 Fire Code 904 . 13 , as amended by WA . C� 0
4. Cooking layout matches current approved/inspected layout . a 0
Cp in Oil Storage PASS FAIL N/A
1, Aggregate volume of containers is less than 120 gallons . ( 2021 WA IFC
319 . 6 )
Storage co stored in such a way as to not be toppled or �7
2 . g containers Y
damaged during transport . ( 2021 WA IFC 319 . 6) Ab a a
3 . Metallic cooking oil storage tank is listed per UL80 or UL 142 and
installed per manufacturer' s instructions . ( 2021 WA IFC 319 .7 . 1)
4. Nonmetallic storage tank installed per manufacturer' s instructions and 13 0
listed for use with cooking oil and does not exceed 200 gallons per
tank. ( 2021 WA IFC 319 . 7 . 2 ) ks Not 0 0
5 . Normal and emergency vents are provided for metallic tan [
required to vent to the exterior] ( 2021 WA IFC 319 .7 . 5) ,
Normal vent is provided for non - metallic tanks . [ Not required to vent
6
to the exterior . ] ( 2021 WA IFC 319 . 7 . 5 )
S stems PASS FAIL N/A _
LP-Gas Y 0 C)
1 . LP tanks are located on the outside of the vehicle or in a vapor tight
cabinet vented to the outside . -
LP tanks are not located on the back of the vehicle extending beyond 0
r
2 .
the bumper, except where approved by L& I in stamped plan set
available to fire inspector. 0
3
Maximum aggregate capacity of LP tank used for cooking is less than
200 pounds . ( N4 . 2 lb = 1 gal )
• Number of tanks :
Nu
• Size of tanks . .
for Tanks . Visual inspection is the
4a . Inspection & Hydro Testing
responsibility of the filling vendor . Receipts of filling by approved
re evidence of inspection . Tanks mounted permanently
vendor a _ .
to/under
vehicles are not subject to hydrostatic testing requirements _ .
r
(ASME ) .
• Date of last visual inspec
tion for tanks . (2021 WA IFC 319. 10. 3)
Iific ation from (see also
•
DOTPropaneCylinderSafetyFlYr.pj -----------------
in Inspection , LP-gas tanks and fuel - gas piping
4b . Fuel Gas Systems Pip g P . n approved inspect-ion agency
systems require annual inspection by a pP � ers
Y ,
including RVIA,
RVDA, NVRTA, LPG service technicians, gas fitters)
certified fuel gas installers,Ilers or a company registered w / USDOT . (2021
WA IFC 319 . 10 . 3 ) . Check for affixed inspection label
• Most recent inspection date : ---------------------
page2
s a s Regional Food Truck Inspection Checklist, 2021 IFC v
Was i on State -Association --- --
1
•1� 1 1'' 1 11.
I
It "�
1
I
l
l
i
..aerators Used with the Mobile Food Pre
Generators that are not vehicle - mounted
Vehicle PASS FAIL N /A
t• feet from mounted are located a minimum of 120 ® G bL
combustibles . ( 2021 NFPA 96
Refuelin 17 . 5 .2)
g of internal combustion engines s
cooking opera hall not be allowed during
operations and only when the electric generators and internal
combustion power sources are not i
Refuelin n use . (2021 NFPA 96 17 .8.3)
3 • g shall be performed in an approved location not less than 20 � 0
or membrane structures . ( 2021 WA IFC
3107 . 14 . 3 )
4 • Fire extinguisher rated 1A : 20 : BC is provided in egress path ma use 0 0
i
extinguisher identified in Fire Ex g ( y Extinguisher section above for this
purpose ) .
Keep Required Documentation in Your Food Truck
Operators must keep co of the following documents in the inspected food truck. You may be asked to
p P a PY
produce these at any time by a fire department inspector.
• Complete drawings for hood suppression system commissioning (NFPA 96 11.6.1)
• WSAFM Food Truck Inspection Checklist (this form or other documentation provided to you by the r 7
fire agency that completed your inspection). su ression system
• inspect
ion, test and/or cleaning reports for your commercial range hood, fire pp
and extinguishers, completed by the contractor you use. k
ermit s issued by a local fire department for your fo
i od truck
ins ection
• Any p )
filling s identifies the most recent "visual" p
• Most recent LP- Gas and CNG g receipts. Th
conducted by a qualified/certified filling vendor.
Checklist, 2021 IFC (v02122026), page 4
Tonal Food Truck Inspect'on Chec
te Associatio
n of Fire Marshals Reg
Washington sta