19405 68th Dr Ne_P25-0049_2026
DESIGN CRITERIA EXISTING HANGING AND BRACING TO REMAIN 1.THIS TENANT IMPROVEMENT INCLUDES THE INSTALLATION OF 15 PENDENT SPRINKLER HEADS AND 8 UPRIGHT SPRINKLERS IN A COMBUSTIBLE CONCEALED SPACE(BUILDING A FLOOR OUT OF WOOD ABOVE THE NEW T-BAR CEILING IN UNIT H ONLY,UNIT F T-BAR IS OPEN TO ABOVE,NO COMBUSTIBLE CONCEALED SPACE IS BEING CREATED)TO PROTECT NEW LIGHT HAZARD AREAS, T-BAR LID ON THIS SIDE ENCLOSED DESIGNED AND INSTALLED IN ACCORDANCE WITH M19 NFPA 13,20211FC&IBC,AS WELL AS LOCAL e71 U1111 L�I� IV IYI�L JURISDICTION SPECIFICATIONS/GUIDELINES. WOOD FRAMING/CREATES COMB. 2. BE WORK IS THE CHLINENEDICONTRACTED AREA ONLY.NEW SPRINKLER HEADS - -0 T-BAR LID ON THIS SIDE OPEN TOCONCEALED SPACE @ T-BAR AREAS TO BE FED FROM EXISTING BRANCHLINES. ,,I 3.HYDRAULIC CALCULATIONS HAVE BEEN NOT REQUIRED ON THIS TENANT IMPROVEMENT.AREA IS CURRENTLY DESIGNED AND INSTALLED TO PROTECT ORDINARY HAZARD 2,AND TI SPACE IS LIGHTHAZARD. 4.WFPASSUMESTHESTRUCTURETOBEADAQUATETOSUPPORTTHESPRINKLERSYSTEM.ALL MALL ROOM HANGING AND BRACING TO BE PER NFPA 13,2019 EDITION.5.AREASOF THE BUILDING BEING PROTECTED BVWET SPRINKLER SYSTEMS TO BE MAINTAINED ATULE NO LESS THAN 40°F YEAR ROUND,UNLESS HEAT TAPE AND TRACE HAVE BEEN UTILIZED. RE 2 MAINTAINING THESE AREAS AT 40°F OR GREATER ARE SOLELY THE RESPONSIBILITY OF THE I OWNER. 812 08.01 37 7 6.AREAS ON PLAN WHERE SMALL ROOM RULE HAS BEEN USED HAVE BEEN NOTED.RULE WAS UTILIZED TO BE ABLE TO BE GREATER THAN T-6"OFF ANYONE WALL IN THE ROOM,WHILE 19 MAINTAINING NO MORE THAN 225FP OF COVERAGE PER SPRINKLER HEAD. .ALL MATERIAL TO BE UL LISTED AND FM APPROVED FOR FIRE SPRINKLER USE. o = ALL STEEL PIPING (RED& BLUE) o .ALL ELECTRICAL WIRING AND MONITORING OF SPRINKLER SYSTEM TO BE DONE BY OTHERS. IS EXISTING & IS TO REMAIN ALL CLEANING AND PAINTING OF PIPING AND BAGGING OF HEADS TO BE DONE BY OTHERS. t1 .FIRE CAULKING TO BE DONE BY OTHERS. +9 -0 2 SPRINKLER OMISSIONS o T� �E 1'-°" � **CURRENT PLAN IS TO SPRINKLE THE SPACE FURNITUREBUILTINS 8'-4" 8'-4" ABOVE THE T-BAR LID. NO DETAILS HAVE BEEN - SPRINKLERS OMITTED FROM FURNITURE SUCH AS PORTABLE WARDROBE UNITS,CABINETS, I I 1 1 _ _ _ _ _ _ -- _ _ _ _ _ M _ GIVEN ON THIS AREA,SO WE CAN NOT CONFIRM TROPHY CASES,AND SIMILAR ITEMS NOT INTENDED FOR OCCUPANCY PER 2019 NFPA 139.2.9 I\�L///� _ ___ SUITE SUITE H DEPTH. AREA WILL BE PROTECTED OR OMITTED ExTE SPRINKLERIOR OMITTED - -- _ _ PER NFPA 13 2019 EDITION,ONCE DETAILS 9.23I.19.2.3.33W WHEN ALL REQUREDICONDITIONS HAVE R ENMOR PROJECTIONS IET.NG 4FEETPER2019NFPA13 EXISTING -- +9 -0 EXISTING IV V - J OF AREA ARE RELEASED OR CONSTRUCTION I , N NO-COMBUSTIBLEO CONCEALEDMITTED NON-COMBUSTIBLE 1°DROP IT, IS DONE TO REFERENCE. SPRINKLERS OMITTED FROM NON-COMBUSTIBLE CONCEALED SPACES WITH MINIMAL ��COM BUSIBLELOADINGANDHAVINGNOACCESSPER2019NFPA139.2.1.1 2 _ 2 NON-CORINKLER SHALL BE INS 25-11 -' _' `- 35-412 - PLAN REFLECTS COVERAGE ABOVE T SPRINKLERS SHALL INSTALLED MOVE THE BAT OTTOM OF TOF HETHE SHAHAFTANFT PER 19UNDER THE FIRSTACCESSIBL CO SPRINKLERS OMITTED FROM THE BOTTOM OF THE STAARWELL WHEN THESPACE NFPA 13 421 1 STORAGE +9'_0":,�-` _ �.'�-CT TJL--T STOR G UNDERNEATH IS BLOCKED SO THAT STORAGE CAN NOT OCCUR PER 2019 NFPA 139.3.4.2.3.1 J F101 8 I J H101 20� T-BAR IN COMB.CONCEALED SPACE SMALL ROOM 0 o SCHEDULE 40 SPECIFICATIONS TEE(4) RULE +9' 2"X 1"MECH N PIPE WALL INTERNAL WEIGHT OF CAPACITY IN $IZE THICKNESS DIAMETER END PREP TYPES FILLED PIPE GALLONS/FT. O N 1 TE c0 1 1 0.133 1.049 THREADED,CUT&ROLL GROOVED,PLAIN END 2.05 0.045 1 8 B RI E K Z 1- 7-11 1'/. 0.742 1.380 THREADED,CUT&ROLL GROOVED,PLAIN END 2.0 O.WS 1 h 0.145 1.610 THREADED,CUT&ROLL GROOVED,PLAIN END 3.61 0.116 24-9 1 0 -612 2 0.15/ 2.O6T THREADED,CUT&ROLL GROOVED,PLAIN END 5.13 0.190 1 1 SCHEDULE 10 SPECIFICATIONS PIPE WALL INTERNAL WEIGHT OF CAPACITY IN Q_ 4 SIZE THICKNESS DIAMETER END PREP TYPES FILLED PIPE GALLONS/FT. v+ 08.02 1'/. 0.109 1.442 ROLL GROOVED,PLAIN END(BUTT WELDING) 2.52 0.085 _ _ El 1% 0.109 1.682 ROLL GROOVED,PLAIN END(BUTT WELDING) 3.04 0.115 R O C E f 1 / O ,- 1 2 0.109 2.157 ROLL GROOVED,PLAIN END(BUTT WELDING) 4.22 0.190 8.02 10 1_ 8_6 2% 0.120 2.636 ROLL GROOVED,PLAIN END(BUTT WELDING) 5.89 0.283 - -- r Q2 -- I-D-Ffff 3 0.120 3.260 ROLL GROOVED,PLAIN END(BUTT WELDING) 7.94 0.433 r 4 0.120 4.260 ROLL GROOVED,PLAIN END(BUTT WELDING) 11.78 0.740 "' +9 _0 6 0.134 6.357 ROLL GROOVED,PLAIN END(BUTT WELDING) 23.03 1.649 O 2 2 CPVC PIPE 24-9 3- PIPE WALL INTERNAL WEIGHT IP CAPACITYIN F SIZE THICKNESS DIAMETER END PREP TYPES FILLED PIPE GALLONS/FT. p 02� 13-J S-� - 1 1 1 0.214 1.101 PLAIN END 0.6]4 .0495 U 1'/. 0.266 1.394 PLAIN END 1.0]9 .U]95 •uo xi _ __ __ __ __ 2-11 8-6 11A 0.302 1.598 PLAIN END 1.41T .1042 -°-'-® - -- -- -- -- 6� 9'6� 2 0.372 2.003 PLAIN END 2.Z23 .1637 cO u7 0l J 08.02 0 MAX DISTANCE BETWEEN HANGERS TO BE: z NOMINAL SIZE 3l4 1 1114 11/2 2 2112 S. 4 5 6 8 6] 10 GRV STEEL PIPE N/A 12-0 12-0 15.0 15-0 160 160 15-0 15-0 160 15-0 1 CO LQ THRDSTEELPIPE I NIA 12-0 12-0 12-0 1 12-0 1 12-0 1 12-0 N/A WA NIA N/A 2 CPVC PIPE SB 6-0 6-6 M 8-0 94 1M N/A WA NIA N/A 24-9 29 8 1 11 6-6 SPRINKLER LEGEND 3- a-o 1- BYM CNT POSITION FINISH TEMP K NPT SIN MFG. MODEL# SPACING Q 15 PENDENT OR SS CHROME 155° 5.8 1l2. M14 RELIABLE FFR56 15'-0X15-0 - ED Q�� E 0 8 UPRIGHT OR SS BRASS 200° 5.8 1l2 RA1425 25 RELIABLE FlFR56 130&.' 23 TOTAL HEADS ON PROJECT �( 2"X 1'/2"MECH TEE INTO OVER HEAD SYSTEM HANGING & BRACING NEW LOWER SYSTEM FED FROM NEW CPVC LOCATED AOVE T-BAR&HARD LIDS City of Arlington Building Department APPROVED Kevin Olander- 12/01/2025 _ N<44 No changes authorized unless approved by the Building Official SCALE: 3/1 6"=1'-O" JOB # F25063 WOLFE FIRE PROTECTION, INC. WEISS SUITES F & �H[ TL �-�� PERMIT# •NYMIMOTOM.TAT. -��fltlT'.�NMNLM.WTWMCY i CONTRACT# 832 80TH STREET S.W. ?C...YJemesYarSI.Y p1c,N APPROVAL: 19405 68TH DR NE :B{34D3,9-Q L..I E DRAWN BY:WY EVERETT, WA 98203 •Wo1h FIroP bdlo.Ine. DATE 11I10I2025 :WOLFEF DD • DATE 1111:ASNOTED25360 '794 8621 ARLINGTON, WA 98223SCAL s u Isl t REVISION DATE:N/A • LL CONTRACTOR#:WOLFEFP9006DD 5���������� �� City of Arlington Building Department APPROVED Kevin Olander - 12/01/2025 No changes authorized unless approved by the Building Official Wolfe Fire Protection OFFICE: (360) 794-8621 FAX: (360) 794-3080 SUBMITTAL PACK EQUIPMENT CUT SHEETS WEISS SUITES F & H T.I. 19405 68TH DR. NE ARLINGTON, WA 98223 �rrrr.rrrrrrrrrrrrrrrrrrrrrrr: Vi— ■ a>�IrM WMMINOTON STAY■ ■ ac s�,ae owTIFICATE OF 0000 MUCY am ■ Fl"SVRINKL■at SYST"S ■ is Casey James Yardley ■ i 6494.0319- Level3 a ■ Wolfe Fire ro action, c. ■ e WOLFEF D - Date ■ a sN�eaw i........... ................a WOLFE FIRE PROTECTION, INC 832 80th STREET SW EVERETT, WA 98203 (360) 794 - 7926 Bulletin 074 January 2023 Rel ® F1 FR56 Series Quick Response Sprinklers K-factor 5.6(80) Features gn • Standard coverage quick-response sprinklers • Upright, pendent, horizontal sidewall,and vertical sidewall deflectors • Low profile,compact design • Available in a wide variety of finishes Product Description Model F1 FR56 Pendent Model F1 FR56 Upright Reliable Model F1 FR56 series sprinklers are quick-response standard spray automatic fire sprinklers utilizing a sensitive 3.0 mm glass bulb thermal element. Pendent and horizontal sidewall sprinklers may be installed exposed or surface mounted using escutcheons such as the Reliable Models B, C,or HB(reference Technical Bulletin 204). When installed recessed or concealed,the Model F1 FR56 series sprinklers are specifically listed with and may only be installed with listed Reliable escutcheons and cover plates. Refer to the Model F1 FR56 Vertical Sidewall Model F1 FR56 technical information on the following pages for specific listings Horizontal Sidewall for recessed and concealed installations and refer to Figures 5 and 6 for dimensional information. Note: Not all versions of the product are shown. When fitted with an approved water shield,these sprinklers may considered intermediate sprinklers for use in racks, below grated walkways,and other areas where intermediate level sprinklers are required. Note:This bulletin may contain information on New and Legacy sprinklers that reflects a dimensional change only. Sprinkler Iden- Table Aprovides asummary of the approvals and availability of tification Number(SIN), application, performance,and listings/ specific Model F1 FIR series sprinkler configurations.Additional technical information for each sprinkler model is provided on the approval are not otherwise affected. Sprinklers with New frames will include the suffix otherwise in the order. following pages. F1 FR Series Sprinklers Summary Fril• - Sprinkler K-Factor gpm/psi'/2 Max Working Pressure Sprinkler . Model (Ipm/bar'/z) Orientation Listings&Approvals psi(bar) Identification Number(SIN) Upright cULus,FM,LPCB,VdS, 175 12 Intermediate Upright EC,WM,UKCA 250(17)(cULus only) Pendent cULus,FM,LPCB,VdS, 175(12) RA1414 EC,WM,UKCA 250(17)(cULus only) F1 FR56 5.6(80) Concealed Pendent cULus,VdS,EC,WM, 175(12) RA1414 UKCA 250(17)(cULus only) 175(12) 250(17)(cULus only) cULus,FM,LPCB, Vekiaal UKCA www.reliablesprinkler.com Model F1 FR56 Pendent Sprinkler SIN RA1414 Technical Specifications Recessed Escutcheons Style: Model F1 (cULus,LPCB,VdS,CE,WM) Pendent Model F2(cULus,FM,LPCB,VdS,CE, Recessed Pendent WM) Concealed Pendent Model FP(cULus,VdS,CE,WM) Threads: 1/2"NPT or ISO 7-R1/2 Nominal K-Factor:5.6(80 metric) Cover Plate Max.Working Pressure: Model CCP(cULus,VdS(2),CE(2) 175 psi(12 bar) 250 psi(17 bar)(cULus only) Guards&Shields(New Frames)(') Material Specifications F-1 Guard(FM) Thermal Sensor:3 mm Glass Bulb F-5 Guard/Shield Kit(FM) Sprinkler Frame:Brass Alloy F-7 Guard(cULus) Cap:Bronze Alloy F-8 Guard/Shield Kit(cULus) Sealing Washer:Nickel with PTFE S-1 Shield(cULus,FM) Load Screw:Copper Alloy Guards&Shields(Legacy Frames)(') Deflector:Brass Alloy C-1 Guard(FM) Sprinkler Finishes C-5 Guard/Shield Kit(FM) (See Table B) D-1 Guard(cULus,FM) D-4 Guard/Shield Kit(FM) Sensitivity D-5 Guard/Shield Kit(cULus,FM) Quick response S-1 Shield(cULus,FM) Temperature RatingsM Sprinkler Wrenches 135°F(57°C) Model W2(pendent) 155°F(68°C) Model W4(recessed or concealed) 175°F(79°C) Model J(New frame with guard installed) 200°F(93°C) Model JD(Legacy frame with guard 286°F(141°C) installed) Listings and Approvals(') cULus Listed FM Approved LPCB VdS EC WM U KCA:0832-U KCA-CPR-S 5045, 0831-UKCA-CPR-5072(CCP) Notes: 1. 286°F(141°C)temperature rated sprinkler not listed for recessed or concealed use. 2. VdS and CE approval for CCP concealed use is for 155°C(68°C)sprinkler ONLY. 3. Not suitable for recessed or concealed pendent installations. 4. When used surface mounted or exposed.See Recessed Escutcheon and Cover Plate section for specific approvals when installed recessed or concealed. Model F1 FR56 Pendent Sprinkler Components and Dimensions 3 1/4"[83mm] Threads V8 F1FR_HALF_PEND_INT 03 VH Wrench Flat 2 1/4"[57mm] I Cap/Seal Glass Bulb Assembly (3 mm) Deflector Load Screw 1"[25mm] Shown with Optional S-1 Water Shield(Ordered Separately) Note:Please refer to Figure 8 for recessed and concealed installation. Bulletin 074 Reliable Page 3 of 9 January 2023 www.reliablesprinkler.com Recessed and Concealed Installation: Pendent Sprinklers 2-1/4" 2-1/4" (57 mm)Dia. (57 mm)Dia. Hole in Ceiling Hole in Ceiling 1-15/16" 1-15/16" (49 mm)Dia. Reducing (49 mm)Dia. Reducing Fitting Fitting Face of Fitting Face of Fitting to Face of Ceiling to Face of Ceiling 1-1/8"(29 mm)at 7/8"(22 mm)at Max.Recess Max.Recess 3/8"(10 mm)at 3/8"(10 mm)at Ir Min.Recess Min.Recess 1-3/4" 1-3 (44 mm) 1" (44 mm) 1-1/4" (25 mm) (32 mm) Minimum Maximum Minimum Maximum Recess 2-7/8"(72 mm)Dia. Recess Recess 2-7/8"(72 mm)Dia. Recess Models F1&F1 FIR Pendent Sprinkler Models F1&F1 FR Pendent Sprinkler with Model F1 Recessed Escutcheon with Model F2 Recessed Escutcheon 3/4"(19mm)Nominal Adjustment 1/2"(13mm)Nominal Adjustment F1_REC PEND CCP 2-1/2" 2-1/2" (64 mm)Dia. (64 mm)Dia. Hole in Ceiling Hole in Ceiling 2-5/16" 2-5/16" (59 mm)Dia. Reducing (59 mm)Dia. Reducing Fitting Fitting Face of Fitting Face of Fitting Vented Cup to Face of Ceiling Vented Cup to Face of Ceiling 1-1/2"(38 mm)at 1-1/2"(38 mm)at Max.Recess Max.Recess 1"(25 mm)at 1"(25 mm)at Min.Recess I Min.Recess 1" 1" (25 mm) 1/2" (25 mm) 1/2" (12 mm) (12 mm) Minimum Minimum Recess 3-3/16"(78 mm)Dia. Recess Maximum Maximum Recess 3-5/16"(84 mm)Dia. Recess Models F1&F1 FIR Pendent Sprinkler with Model FP Recessed Escutcheon 1/2"(13mm)Nominal Adjustment Model F1 FR56 CCP Conical Concealed Sprinkler 1/2"(13mm)Nominal Adjustment Note:Model FP recessed assemblies may not be used where the (Nominal Cover Plate Projection is 1"(25 mm)) pressure in the space above the ceiling is positive with respect to the protected area.Ensure that the openings in the Model FP cup Note:Model CCP concealed assemblies may not be used where are unobstructed following installation. the pressure in the space above the ceiling is positive with respect to the protected area. Ensure that the openings in the Model CCP cup are unobstructed following installation. FP Escutcheon F1 Escutcheon CCP Cover Plate (F2 Similar) Bulletin 074 Reliable Page 6 of 9 January 2023 www.reliablesprinkler.com L�_ i Model W2(upright, pendent) Model J (New frame with guard installed) Model JD(Legacy frame with guard installed,similar but with zinc finish) Model W4 (recessed,concealed pendent) FinishesM Standard Finishes mMO Special Application Finishes Sprinkler F1,F2 and FP(z) CCP Cover Sprinkler F1, F2 and FP(z) CCP Cover Plate(2) Escutcheons Plate(') p Escutcheons Bronze Brass Chrome Electroless Nickel PTFE(3)(4) Bright Brass Bright Brass Chrome Chrome White Paint Bright Brass(-') Satin Chrome Satin Chrome White Polyester(3) White Polyester Satin Chrome Custom Color Polyester Custom Color Paint Custom Color Polyester(3) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Model FP escutcheons and Model CCP sprinklers utilize a galvanized steel cup with a finished trim ring or cover plate. 3. cULus Listed as corrosion resistant. 4. FM Approved as corrosion resistant. 5. For 200T(93°C)maximum temperature rated sprinklers only. Installation Maintenance Model F1 FR Series sprinklers must be installed in accordance with Reliable Model F1 FR series sprinklers should be inspected and NFPA13 and the requirements of all applicable authorities having the sprinkler system maintained in accordance with NFPA 25, as jurisdiction. Model F1 FR Series sprinklers must be installed with well as the requirements of any Authorities Having Jurisdiction. the Reliable sprinkler installation wrench identified in this Bulletin. Prior to installation, sprinklers should remain in the original Any other wrench may damage the sprinkler. The Models W2 and cartons and packaging until used.This will minimize the potential W4 wrenches have two sets of jaws. Use the smallest set of jaws for damage to sprinklers that could cause improper operation or that fit on the wrench flats of the sprinkler. A leak tight sprinkler non-operation. joint can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m). Do not tighten sprinklers over the maximum recommended Do not clean sprinklers with soap and water, ammonia liquid or installation torque. Exceeding the maximum recommended any other cleaning fluids. Remove dust by gentle vacuuming installation torque may cause leakage or impairment of the without touching the sprinkler. sprinkler. Replace any sprinkler which has been painted (other than factory applied).A stock of spare sprinklers should be maintained to Glass bulb sprinklers have orange bulb protectors or protective allow quick replacement of damaged or operated sprinklers. caps to minimize bulb damage during shipping, handling and Failure to properly maintain sprinklers may result in inadvertent installation. Reliable sprinkler installation wrenches are designed operation or non-operation during a fire event. to install sprinklers with bulb protectors in place. Remove the bulb protector at the time when the sprinkler system is placed in service for fire protection. Removal of the bulb protector before this time may leave the bulb vulnerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Bulletin 074 Reliable Page 8 of 9 January 2023 www.reliablesprinkler.com Guarantee For the guarantee,terms, and conditions,visit www. reliablesprinkler.com. Ordering Information Specify the following when ordering: Model • F1FR56 Deflector/Orientation • Upright • Intermediate Upright • Pendent • CCP Concealed Pendent • Horizontal Sidewall • Vertical Sidewall Temperature Rating • See sprinkler technical specifications Sprinkler Finish • See Table B Recessed EscutcheonO)(2) • F1 • F2 • FP Escutcheon Finish • See Table B CCP Cover Plate Temperature Rating • 135°F(57°C) [For use with 135°F(57°C) and 155°F(68°C)sprinklers.] • 165°F(74°C) [For use with 175°F(79°C) and 200°F(93°C)sprinklers.] CCP Cover Plate Finish • See Table B Sprinkler Wrench • Model W2 • Model W4(recessed, concealed) • Model J (New frame with guard installed) • Model JD(Legacy frame with guard installed) Notes: 1.286°F(141°C)sprinklers are not listed to be used recessed or concealed. 2. For FM, recessed sprinklers must use the Model F2 escutcheon. rn rn rn rn rn z a Bulletin 074 Reliable Page 9 of 9 January 2023 www.reliablesprinkler.com Bulletin 074 January 2023 Rel ® F1 FR56 Series Quick Response Sprinklers K-factor 5.6(80) Features s: • Standard coverage quick-response sprinklers • Upright, pendent, horizontal sidewall,and vertical sidewall deflectors • Low profile,compact design • Available in a wide variety of finishes Product Description Model F1 FR56 Pendent Model F1 FR56 Upright Reliable Model F1 FR56 series sprinklers are quick-response standard spray automatic fire sprinklers utilizing a sensitive 3.0 mm glass bulb thermal element. Pendent and horizontal sidewall sprinklers may be installed exposed or surface mounted using escutcheons such as the Reliable Models B, C,or HB(reference Technical Bulletin 204). When installed recessed or concealed,the Model F1 FR56 series sprinklers are specifically listed with and may only be installed r Z with listed Reliable escutcheons and cover plates. Refer to the Model F1 FR56 Vertical Sidewall Model F1 FR56 technical information on the following pages for specific listings Horizontal Sidewall for recessed and concealed installations and refer to Figures 5 and 6 for dimensional information. Note: Not all versions of the product are shown. When fitted with an approved water shield,these sprinklers may considered intermediate sprinklers for use in racks, below grated walkways,and other areas where intermediate level sprinklers are required. Note:This bulletin may contain information on New and Legacy sprinklers that reflects a dimensional change only. Sprinkler Iden- Table Aprovides asummary of the approvals and availability of tification Number(SIN), application, performance,and listings/ specific Model F1 FIR series sprinkler configurations.Additional technical information for each sprinkler model is provided on the approval are not otherwise affected. Sprinklers with New frames will include the suffix otherwise in the order. following pages. F1 FR Series Sprinklers Summary Fril• - Sprinkler K-Factor gpm/psi'/2 Max Working Pressure Sprinkler . Model (Ipm/bar'/z) Orientation Listings&Approvals psi(bar) Identification Number(SIN) Upright cULus,FM,LPCB,VdS, 175(12) RA1425 Intermediate Upright EC,WM,UKCA 250(17)(cULus only) cULus,FM,LPCB,VdS, 175 12 EC,WM,UKCA 250(17)(cULus only) F1 FR56 5.6(80) C01980910d cULus,VdS,EC,WM, 175 12 UKCA 250(17)(cULus only) Hdewall eul:d5'FM 175 12 250(17)(cULus only) cULus,FM,LPCB, 486 UKCA www.reliablesprinkler.com Model FlFR56 Upright Sprinkler SIN RA1425 Technical Specifications Guards&Shields(New Frames) Style:Upright,Intermediate Upright Factory Water Shield(cULus, FM) Threads: 112"NPT or ISO 7-R1/2 F-1 Guard(cULus,FM) Nominal K-Factor:5.6(80 metric) F-3 Guard with Shield(cULus, FM) Max.Working Pressure: 175 psi(12 bar) Guards and Shields(Legacy Frames) 250 psi(17 bar)(cULus only) Factory Water Shield Material Specifications C-1 Guard(FM) Thermal Sensor:3 mm Glass Bulb C-3 Guard with Shield(cULus,FM) D-1 Guard(cULus) Sprinkler Frame:Brass Alloy D-3 Guard with Shield(cULus) Cap:Bronze Alloy Sealing Washer:Nickel with PTFE Sprinkler Wrench Load Screw:Copper Alloy Model W2 Deflector:Brass Alloy Model J(New frame with guard installed) Model JD(Legacy frame with guard Sprinkler Finishes installed) (See Table B) Listings and Approvals Sensitivity cULus Listed Quick response FM Approved -PCB Temperature Ratings VdS 135°F(57°C) EC 155°F(68°C) WM 175-F(79°C) UKCA:0832-UKCA-CPR-S5045 200-F(93°C) 286°F(141°C) Model F1 FR56 Upright Sprinkler Components and Dimensions 3 1/4"[83mm] Load Screw 1 3/8"[33mm] Deflector Glass Bulb I � a (3 mm) F1FR_HALF_UPR_INT � 21/4"[58mm] Wrench Flat A CO RA CO Threads Cap/Seal Assembly Shown with Optional Factory Installed Water Shield (Intermediate Upright) Bulletin 074 Reliable Page 2 of 9 January 2023 www.reliablesprinkler.com L�_ i Model W2(upright, pendent) Model J (New frame with guard installed) Model JD(Legacy frame with guard installed,similar but with zinc finish) Model W4 (recessed,concealed pendent) FinishesM Standard Finishes mMO Special Application Finishes Sprinkler F1,F2 and FP(z) CCP Cover Sprinkler F1, F2 and FP(z) CCP Cover Plate(2) Escutcheons Plate(') p Escutcheons Bronze Brass Chrome Electroless Nickel PTFE(3)(4) Bright Brass Bright Brass Chrome Chrome White Paint Bright Brass(-') Satin Chrome Satin Chrome White Polyester(3) White Polyester Satin Chrome Custom Color Polyester Custom Color Paint Custom Color Polyester(3) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Model FP escutcheons and Model CCP sprinklers utilize a galvanized steel cup with a finished trim ring or cover plate. 3. cULus Listed as corrosion resistant. 4. FM Approved as corrosion resistant. 5. For 200T(93°C)maximum temperature rated sprinklers only. Installation Maintenance Model F1 FR Series sprinklers must be installed in accordance with Reliable Model F1 FR series sprinklers should be inspected and NFPA13 and the requirements of all applicable authorities having the sprinkler system maintained in accordance with NFPA 25, as jurisdiction. Model F1 FR Series sprinklers must be installed with well as the requirements of any Authorities Having Jurisdiction. the Reliable sprinkler installation wrench identified in this Bulletin. Prior to installation, sprinklers should remain in the original Any other wrench may damage the sprinkler. The Models W2 and cartons and packaging until used.This will minimize the potential W4 wrenches have two sets of jaws. Use the smallest set of jaws for damage to sprinklers that could cause improper operation or that fit on the wrench flats of the sprinkler. A leak tight sprinkler non-operation. joint can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m). Do not tighten sprinklers over the maximum recommended Do not clean sprinklers with soap and water, ammonia liquid or installation torque. Exceeding the maximum recommended any other cleaning fluids. Remove dust by gentle vacuuming installation torque may cause leakage or impairment of the without touching the sprinkler. sprinkler. Replace any sprinkler which has been painted (other than factory applied).A stock of spare sprinklers should be maintained to Glass bulb sprinklers have orange bulb protectors or protective allow quick replacement of damaged or operated sprinklers. caps to minimize bulb damage during shipping, handling and Failure to properly maintain sprinklers may result in inadvertent installation. Reliable sprinkler installation wrenches are designed operation or non-operation during a fire event. to install sprinklers with bulb protectors in place. Remove the bulb protector at the time when the sprinkler system is placed in service for fire protection. Removal of the bulb protector before this time may leave the bulb vulnerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Bulletin 074 Reliable Page 8 of 9 January 2023 www.reliablesprinkler.com Guarantee For the guarantee,terms, and conditions,visit www. reliablesprinkler.com. Ordering Information Specify the following when ordering: Model • F1FR56 Deflector/Orientation • Upright • Intermediate Upright • Pendent • CCP Concealed Pendent • Horizontal Sidewall • Vertical Sidewall Temperature Rating • See sprinkler technical specifications Sprinkler Finish • See Table B Recessed EscutcheonO)(2) • F1 • F2 • FP Escutcheon Finish • See Table B CCP Cover Plate Temperature Rating • 135°F(57°C) [For use with 135°F(57°C) and 155°F(68°C)sprinklers.] • 165°F(74°C) [For use with 175°F(79°C) and 200°F(93°C)sprinklers.] CCP Cover Plate Finish • See Table B Sprinkler Wrench • Model W2 • Model W4(recessed, concealed) • Model J (New frame with guard installed) • Model JD(Legacy frame with guard installed) Notes: 1.286°F(141°C)sprinklers are not listed to be used recessed or concealed. 2. For FM, recessed sprinklers must use the Model F2 escutcheon. rn rn rn rn rn z a Bulletin 074 Reliable Page 9 of 9 January 2023 www.reliablesprinkler.com Pipe HangersiSupports AS C '0, Engineered Solutions Two Hole 900 Side Mount Strap Fig. 187 (Formerly Afton Fig. 511) Size Range:3/4"through 2" i Finish: Zinc Plated Steel(Hot-Dip Galvanized optional) Service:Hanger for CPVC pipe in the horizontal position on the bottom of structural wood beams and Steel20 Ga.(min.)(Fig.A).Can be used as a restrainer,only in Steel20 Ga.(min)(Fig.B). During installation,adjust hanger mounting flanges such that pipe contacts both mounting surface and hanger,minimizing vertical pipe movement. Approvals:UL and ULC Listed. Installation e • Snap hanger over pipe. • Secure hanger to mounting surface with screws provided. • Do not anchor tightly to mounting surface.Pipe must be allowed to move freely through hanger. Steel applications require two(2)#14 x T'hex washer head self-drilling TEK screws. Not Supplied.Part Number STD-0090. c&us LISTED Features: • Beveled edge design helps protect the CPVC pipe from any rough surface. • Easily attaches to wood structure with#10 x T'hex washer head self threading screw supplied with product. No pre-drilling required. Ordering:Specify CPVC pipe size,figure number and description. A 0C -� + r _1 A B F E� Fig.A Fig.B Fig.187:Dimensions(in)•Weight(lbs) CPVC A B 0C E F Max.Hanger Approx. Pipe Size Spacing(ft.) Weight/100(lbs) 'A 16/16 T/2 3/16 13/16 21/2 51/2 5 1 1 19/16 3/16 13/16 23/4 6 6 11/4 VA6 13A 3/16 13/16 31/4 61/2 7 11/2 16/16 111/16 3/16 13/16 31/2 7 8 2 19/16 21/8 3/16 V/16 313/16 8 9 PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SS-11.19 page 1 SS-SUB-187-v0120220526 Pipe HangersiSupports l*)' mc. / Engineered Solutions Two Hole Standoff Hanger and Restrainer Fig. 188R (Formerly Afcon Fig. 514) Size Range:W'through 2" Material:Carbon Steel Finish:Pre-Galvanized per ASTM A653 Service: • Hanger and surge restraint for horizontal CPVC,steel,and copper piping when installed on the top,bottom,and side of the supporting structure. Guide for vertical CPVC,steel,and copper piping when installed on the side of the supporting structure. • Horizontal and vertical seismic restraint per NFPA 13-2016 requirements. • May be installed with concrete,steel structural members,and other structural members with fasteners which comply with the requirements of NFPA 13. ` C&US Approvals:cULus Listed \ LISTED Patents:No.6,648,278 Installation • Snap hanger over pipe.If needed,squeeze strap back around pipe. • CPVC pipe must be allowed to slide freely through the Fig.188R. • Secure hanger to mounting surface with screws provided or with listed fasteners. ` Feal • Beveled edge design helps protect the CPVC pipe from any rough surface and eliminates pipe abrasion. Easily attaches to wood structure with#10 x T'hex washer head self-threading screw supplied with product. No pre-drilling required. • Bottom of pipe is offset T/2"from the structure.Eliminates wooden spacer blocks. Ordering:Specify CPVC pipe size,figure number and description. Hanger& Restrainer 1.50 Hanger& Guide& Restrainer O Restrainer Installation-Backing Nut Hanger=1-At top fastener Restraint=2-On each fastener Per NFPA-13D and NFPA-13R ANVIL. An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SS-9.18 page 1 SS-SUB-188R-0120220629 i Pipe Hangers & Supports U *OASC V-4 Engineered Solutions Two Hole Standoff Hanger and Restrainer (cont.) Fig. 188R (Formerly Afcon Fig. 514) ° a B ° ° a A a ° ad a a ° E + Oc a a ° a a ° a ° a G a ° ° a°. a° a a a °. d. F D G Hanger and Restrainer Fig.188R:Dimensions(in)•Weight(lbs) CPVC Max.Hanger Approx. Pipe Size A B 0C D E F G Spacing(ft) Weight/100(lbs) 'A 28/4 31/2 1/4 2 1 21/8 11/2 51/2 11 1 213/16 31/2 1/4 23/16 1 2"/16 11/2 6 12 VA 21 A6 31/2 'A 25/16 1 31/4 11/2 61/2 13 Th 36/8 41/4 'A 27116 1 31/2 11/2 7 14 2 311/16 4% 'A 211/16 1 4 Th 8 16 Fig.188R:Listed Fasteners Pipe Wood and Composite Beams Steel(18ga.Minimum) CPVC Screw Supplied or#10 x 1"TEK Screw #14 x 1"TEK Screw or 1/d'x 1"TEK Screw Steel&Copper #14 x 1"TEK Screw or 1/4'x 11/2"Lag Screw #14 x 1"TEK Screw or 1/4'x 1"TEK Screw 0' ANVI L, '441PP� An ASC Engineered Solution SS-9.18 page 2 SS-SUB-188R-v0120220629 S/A 53 Spec Sheet A53 Pipe Specifications A/SA53 N PS 1/4" -30" Schedules 10 through 160, STD, XH and XXH Scope ASTM A53 pipe covers Seamless and Welded, Black and Hot-Dipped Galvanized nominal (average) wall pipe for coiling, bending, flanging and other special purposes and is suitable for welding. Continuous-Welded pipe is not intended for flanging. Purpose for which pipe is intended should be stated on order. Materials and Manufacture The steel for both seamless and welded pipe shall be made by one or more of the following processes: open-hearth, electric furnace, or basic-oxygen. The weld seam of electric-resistance welded pipe in Grade B shall be heat treated after welding. Chemical Requirements Type S Type E Type F (seamless) (electric- (furnace- resistance welded) welded pipe) Grade A Grade B Grade A Grade B Grade A Carbon max. % 0.25 0.30 0.25 0.30 0.3 Manganese % 0.95 1.2 0.95 1.2 1.2 Phosphorous, max. % 0.05 0.05 0.05 0.05 0.05 Sulfur, max. % 0.045 0.045 0.045 0.045 0.045 Copper, max.% 0.40 0.40 0.40 0.40 0.4 Nickel, max. % 0.40 0.40 0.40 0.40 0.4 Chromium, max. % 0.40 0.40 0.40 0.40 0.4 Molybdenum, max. % 0.15 0.15 0.15 0.15 0.15 Vanadium, max. % 0.08 0.08 0.08 0.08 0.08 Hot-Dipped Galvanizing Sets standards for coating of pipe with zinc inside and outside by the hot-dipped process. Weight of coating must not average less than 1.8 oz. per square foot and not less than 1.6 oz. per square foot. Permissible Variations in Wall Thickness The minimum wall thickness at any point shall not be more than 12.5% under the nominal wall thickness specified. Permissible Variations in Weights per Foot Plus or minus 10% Permissible Variations in Outside Diameter Outside Diameter at any point shall not vary from standard specified more than: For NPS 1 1/2 and For NPS 2 and Larger Smaller Sizes Sizes 1/64" 1/32" under 1% over 1%under Tensile Requirements Seamless and Electric-resistance-welded Continuous-Welded Grade A Grade B Tensile Strength, min., 48,000 60,000 45,000 psi Yield Strength, min., psi 30,000 35,000 25,000 Number of Tests Required Seamless and Electric-Resistance-Welded -- Bending, flattening, tensile on one length of pipe from each lot of 500 lengths or less of a size. Continuous-Weld -- Bending, flattening, tensile NPS 1 1/2 & smaller NPS 2 & larger one / 25 tons one / 50 tons Hydrostatic Testing Hydrostatic inspection test pressures for plain end and threaded and coupled pipe are specified. Hydrostatic pressure shall be maintained for not less than 5 seconds for all sizes of seamless and electric-resistance-weld pipe. Mechanical Tests Specified Tensile Test -- Transverse required on ERW for NPS 8 and large. Sending Test (Cold) -- STD and XS-NPS 2 and under XXS-NPS 1 1/4 and under. Degree of Bend Diameter of Mandrel For Normal A53 90 12 x nom dia. of Uses pipe For Close Coiling 180 8 x nom dia. of pipe Flattening Test -- NPS 2 and larger STD and XS. (Not required for XXS pipe.) Lengths Standard Weight Single Random -- 16' - 22'. 5% may be jointers. If Plain Ends -- 5% may be 12' - 16'. Double Random -- Shortest Length 22', minimum average for order 35'. Extra Strong and Double Extra Strong Single Random -- 12' -22'. 5% may be 6' - 12'. Double Random (XS and lighter) -- Shortest Length 22', minimum average for order 35'. Lengths longer than single random with wall thicknesses heavier than XS subject to negotiation. Required Markings on Each Length (On Tags attached to each Bundle in case of Bundled Pipe) Rolled, Stamped, or Stenciled (Mfrs. Option) Name brand of manufacturer Kind of pipe, that is, Continuous Welded, Electric-Resistance-Welded A, Electric-Resistance-Welded B, Seamless A, Seamless B, XS for extra strong, XXS for double extra strong. ASTM 53 Length of pipe General Information Couplings -- Applied handling tight. Couplings, 2" and smaller straight tapped, other sizes taper tapped. Thread Protection -- Applied to pipe 4" and larger. End Finish (unless otherwise specified) -- STD or XS, or wall thicknesses less than 0.500 in. (excluding XXS): Plain and beveled All XXS and wall thicknesses over 0.500 in.: Plain end square cut. Blazemaster 0 FIRE PROTECTION SYSTEMS B1azeMaster®Fire Protection Systems Sample Specifications—United States* PART 1 —GENERAL 1.0 PRODUCT DESCRIPTION BlazeMaster®CPVC fire sprinkler pipe and fittings are extruded/molded from CPVC compounds manufactured by Lubrizol Advanced Materials. The pipe and fitting compounds shall meet cell class 23547 and 24447,respectively, as defined by ASTM D1784, and shall be certified by NSF International for use with potable water. Both pipe and fitting compounds shall be pressure rated by Plastics Pipe Institute(PPI). 1.1 PIPE AND FITTINGS A. Pipe shall meet or exceed the requirements of ASTM F442 material designation CPVC 4120-06 in standard dimension ratio(SDR) 13.5.Additionally,the pipe must be marked with the following pressure ratings: "320 PSI @ 73'F", "175 PSI @ 150'F"and"100 PSI @ 180'F". B. Fittings shall meet or exceed the requirements of ASTM F437(schedule 80 threaded),ASTM F438 (schedule 40 socket)and ASTM F439 (schedule 80 socket). C. Both pipe and fittings shall be Listed by Underwriters Laboratories for use in wet automatic fire sprinkler systems and shall bear the logo of the Listing Agency. See UL Fire Protection Equipment Directory,categories VIWT and HFYH. D. Ancillary products coming into contact with pipe and fittings must be chemically compatible as determined by CPVC pipe and fittings manufacturer or compound manufacturer,and thus Listed on pipe, fittings or compound manufacturer's chemical compatibility program(i.e. FGG/BM/CZTM System Compatible Program). 1.2 SOLVENT CEMENT A. All socket type joints shall be made up employing solvent cements that meet or exceed the requirements of ASTM F493. The standard practice for safe handling of solvent cements shall be in accordance with ASTM F402. Solvent cement shall be certified by NSF International for use with potable water, and approved by the manufacturers. The solvent cements shall be compatible with their CPVC pipe and fittings. B. Follow manufacturer's instructions for set and cure times for solvent cement joints.Avoid significant stresses during set and cure times. Do not apply any stress that will disturb an un-dried joint. Sprinkler fittings shall be allowed to cure in accordance with the manufacturer's guidelines and the contractor shall assure the outlets are clear of any excess cement prior to installing sprinklers. 1.3 BASIC USE CPVC pipe and fittings shall be listed by UL and also either ULC or C-UL for use in: A. Light Hazard Occupancies as defined by NFPA 13. B. Ordinary hazard rooms of otherwise light hazard occupancies where the room does not exceed 400 square feet(i.e.Laundry room)as defined in NFPA 13. C. Residential Occupancies up to four stories in height as defined by NFPA 13R. D. One and two family dwellings and manufactured homes as defined by NFPA 13D. E. Air handling(plenum) spaces as defined by NFPA 90A. F. Underground water pressure service as defined by NFPA 24. G. Maximum design temperature/pressure rating shall not be less than175 psi at 150°F. H. Refer to UL and FM** (if applicable). I. Refer to CPVC pipe and fitting manufacturers' installation instructions. 1.4 QUALITY ASSURANCE Installer Qualifications: Contractor Training Certificates for Chlorinated Polyvinyl Chloride(CPVC)Fire Sprinkler Systems. Fire Sprinkler Contractor must submit to the Contracting Officer documentation that lists personnel assigned to this project prior to beginning construction who have successfully completed formal CPVC fire sprinkler systems training conducted by an authorized CPVC manufacturer's representative. The Contractor Training Certificates shall be specific to the manufacturer of the pipe and fittings. Personnel's training certificates must be current and have been updated within the past two(2)years. (Note: this training does not imply compliance with any local or state contractor certification or licensing laws.) PART 2 - PRODUCTS 2.0 MATERIAL The piping systems(pipe and fittings) shall be constructed from materials extruded/molded by manufacturers using the same compound manufacturer(i.e. BlazeMaster®CPVC compound). 2.1 MANUFACTURERS ❑ Georg Fischer Harvel,Kuebler Rd.,PO Box 757 Easton,PA 18044. Phone(610)252-7355. FAX(610)253-4436. ❑ NIBCO INC. 1516 Middlebury Street Elkhart, IN 46516. Phone (574)295-3000. FAX(574)295-3307. ❑ Tyco Fire Suppression&Building Products 451 N. Cannon Avenue Lansdale,PA 19446. Phone(215)362-0700. FAX(215) 362-5385. ❑ The Viking Corporation 210 N. Industrial Park Drive Hastings,MI 49058. Phone (269)945-9501. FAX(269) 945-4495. PART 3 -EXECUTION 3.0 SYSTEM DESIGN A. System design shall be in accordance with standard industry practice for fire sprinkler systems and the manufacturer's instructions. The design shall take into consideration such factors as pressure and flow requirements,friction loss, operating temperatures, support spacing,joining methods, and thermal expansion and contraction. B. The fire sprinkler piping system shall be hydraulically calculated using a Hazen-Williams C Factor of 150, and designed in accordance with the Standard for Installation of Sprinkler Systems, NFPA 13. C. The maximum design temperature/pressure rating shall not exceed 175 psi at 150°F. 3.1 INSTALLATION PROCEDURES Installation practices such as pipe support spacing,bracing, allowance for thermal expansion/contraction, solvent cementing and handling and storage shall be in accordance with the manufacturer's instructions and the UL Listing which includes installation limitations. 3.2 LIMITATIONS BlazeMaster®CPVC pipe and fittings are intended for use at a maximum working pressure of 175 psi at 150°F in accordance with the manufacturer's instructions and appropriate listing agencies. 3.3 TECHNICAL DATA A. APPLICABLE STANDARDS a. ANSI/NSF Standard 14 Plastic Piping Components and Related Materials b. ANSI/NSF Standard 61 Drinking Water System Components—Health Effects c. ASTM D1784 Specification for Rigid Poly(Vinyl Chloride)(PVC) Compounds and Chlorinated Poly(Vinyl Chloride)(CPVC)Compounds d. ASTM F402 Practice for Safe Handling of Solvent Cements,Primers and Cleaners Used for Joining Thermoplastics Pipe and Fittings e. ASTM F437 Specification for Threaded Chlorinated Poly(Vinyl Chloride)CPVC Plastic Pipe Fittings, Schedule 80 £ ASTM F438 Specification Socket-Type Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe Fittings, Schedule 40 g. ASTM F439 Specification Socket-Type Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe Fittings, Schedule 80 h. ASTM F442 Specification Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe(SDRPR) i. ASTM F493 Specification for Solvent Cements for Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe and Fittings j. NFPA 13 Standard for Installation of Sprinkler Systems k. NFPA 24 Installation of Private Fire Service Mains and Their Appurtenances 1. NFPA 25 Standard for the Inspection,Testing and Maintenance of Water Based Extinguishing Systems in. NFPA 13R Standard for Installation of Sprinklers in Residential Occupancies up to Four Stories in Height n. NFPA 13D Standard for Installation of Sprinkler Systems in One and Two Family Dwellings o. NFPA 90A Standard for Installation of Air Conditioning and Ventilating Systems p. UL 1887 Fire Test of Plastic Sprinkler Pipe for Flame and Smoke Characterization q. UL 1821 Outline of Proposed Investigation for Thermoplastic Sprinkler Pipe and Fittings for Fire Protection Service r. Piping compound has a 180°F Hydrostatic Design Basis(HDB)of 1250 psi as listed by the Plastic Pipe Institute s. Fitting compound has a 180°F Hydrostatic Design Basis(HDB)of 1000 psi as listed by the Plastic Pipe Institute B. APPLICABLE CODES a. ICC, International Building,Mechanical and Plumbing Codes b. IAPMO,Uniform Mechanical and Plumbing Codes c. NBC,National Building Code of Canada 3.4 TESTING After the system is installed and any solvent cement is cured per the manufacturer's installation instructions,the systems shall be hydrostatically tested per the requirements of the applicable NFPA Standard(NFPA 13, 13R or 13D). 3.5 MAINTENANCE Maintenance shall be in accordance with the Standard for Inspection,Testing and Maintenance of Water Based Extinguishing Systems as defined by NFPA 25. 3.6 WARRANTY Consult the manufacturer for specific warranty information. *Not intended to be a stand alone specification. The above specifications are to be added within your company's standard fire sprinkler systems specifications to specify the use of B1azeMaster®CPVC pipe and fittings. **As manufactured by Georg Fischer Harvel,NIBCO, Tyco Fire Suppression&Building Products, and The Viking Corporation August 2014 This building contains a CPVC BlazeMaster® fire sprinkler system. This CPVC fire sprinkler system is a Life Safety Assembly and must be treated carefully. Please read the following before any activity which could contact this system: CPVC piping components may be damaged by certain substances and construction practices. • DO NOT stack, support, hang equipment, or hang flemble wire%able, especially communications cable, or other material on the fire sprinkler system. • ONLY system compatible materials including, but not limited to solvent cements, caulks, sealants, cutting oils and thread pastes as noted by the CPVC fire sprinkler piping system manufacturer's installation instructions should be used in contact with this system. • DO NOT expose CPVC products to incompatible substances, such as cutting oils, non-water based paints,packing oils, traditional pipe thread paste and dope, fungicides, termiticides, insecticides, detergents, building caulks, adhesive tape, solder flux, flexible wire/cable (with special consideration for communications cabling), and non-approved spray foam insulation materials. • DO NOT expose CPVC products to edible oils, solvents, or glycol-based anti-freeze fluids. • DO NOT expose CPVC products to open flame, solder, and soldering flux. • DO NOT drop, distort, or impact CPVC products or allow objects to be dropped on them. • DO NOT handle CPVC products with gloves contaminated with oils (hydrocarbons)or other incompatible materials. Failure to follow this notice may cause cracks or fractures to develop in CPVC products resulting in property damage due to leaks or flooding. The presence of any visible cracks may require partial or full system replacement. For additional information contact the general contractor or the fire sprinkler system installer. FOR ADDITIONAL INFORMATION CONTACT VIKING AT 1-877-384-5464 R Rev 2.1—27 jan 2021 Availability:Americas Bulletin 213 April 2022 Rel ® Model RFB RASCOFLEX° Sprinkler Connections cULus Listed, FM Approved Product Description RASCOFLEX°Sprinkler Connections are intended to connect a branch line to a sprinkler using a flexible stainless steel hose assembly. RASCOFLEX°Sprinkler Connections are suitable for use in suspended and hard ceiling applications such as T-Bar ceiling grids,wood, metal stud,or hat furring channel hard lid ceilings. Every package contains one(1)fully assembled stainless steel flexible sprinkler system complete with hose, branch line connection,and sprinkler connection, as well as the pre- assembled bracket assembly to attach to the ceiling. RASCOFLEX°Sprinkler Connections are designed for use in hydraulically calculated wet, preaction,or dry sprinkler systems per NFPA 13, 13R, 13D,and FM Global Loss Prevention Data Sheets. Technical Data • ' RASCOFLEX°Sprinkler Connections Maximum Working Pressure FM:200 psi(13.8 bar) UL: 175 psi (12.1 bar) Maximum Working Temperature 300°F(149°C) Ordering Information Inlet/Branch Line 1" NPT Specify: Connections Outlet/Reducer 1/2"or 3/4" NPT Model Name Minimum Allowable UL: 3" (76 mm) • Model RFB Bending Radius FM: 7"(178 mm) Nominal Hose Length Maximum Number of Bends See Friction Loss Chart • 24" (610 mm) Maximum 1/2"Outlet 5.6(80 metric) • 31" (790 mm) • 40" (1015 mm) K-Factor 3/4"Outlet 14.0(200 metric) • 48" (1220 mm) • 60" 1525 mm) • 72" (1830 mm) Maintenance Reducer Outlet: 1/2" NPT or 3/4" NPT RASCOFLEX°Sprinkler Connections should be inspected and the sprinkler system maintained in accordance with NFPA 25,as Reducer Type well as the requirements of any Authorities Having Jurisdiction. Standard: • 6-1/8" (155 mm)straight Optional: Patents • 4-5/16" (110 mm)straight RASCOFLEX°Sprinkler Connections may be covered by • 5-5/16" (135 mm)straight one or more of the following US Patent Nos. 10,173,088 and • 11-3/4" (300 mm)straight 10,328,296. • 5-5/8" (143 mm)elbow • 7-3/8" (187 mm)elbow Listings and Approvals Bracket Assembly Length • 24" (610 mm)standard FM Approved Class No. 1637(FM) • 48" (1220 mm)optional UL Listed and UL Certified for Canada to ANSI/UL 2443(cULus) Accessories • See Table F www.reliablesprinkler.com Bracket Dimensions 28" [711]for 24"bracket or 52"[1320]for 48"bracket lIF IF 7 N N � O T n -CO =o 0 r V 'Co LO Nominal 1-11/16" (43mm)ceiling grid shown for reference only. Verify actual ceiling grid dimensions and ceiling tile reveal prior to ordering. v� v Reducer Dimensions 0 0 0 co � _ - N n O pp � 7 COu C7 r 0 m 0 � � `� E; LO ao m w �LO CO I p \ -� L _� c co CO CO CO 4-5/16"(110 mm) 5-5/16"(135 mm) 6-1/8"(155 mm) 11-13/16"(300 mm) 5-5/8"(143 mm) 7-3/8"(187 mm) Straight Straight Straight Straight Elbow Elbow Standard Bulletin 213 Reliably Page 2 of 8 April 2022 www.reliablesprinkler.com Installation Dimensions U m ch v Nominal 1-11/16" (43mm)ceiling grid shown for reference only. Verify actual ceiling grid dimensions and ceiling tile reveal prior to ordering. Minimum and Maximum Face of Fitting to Bottom of Ceiling Grid for Each Reducer 6-1/8" 4-5/16" 5-5/16" 11-13/16" 5-5/8" 7-3/8" Fitting Distance (155mm) (110mm) (135mm) (300mm) (143mm) (187mm) Straight Straight Straight Straight Elbow Elbow Standard Max. Face of Fitting 3" (7mm) Distance Above 3" (77mm) 3" (7mm) 3" (7mm) 3"(7mm) 3" (7mm) Bottom of Ceiling Grid Max. Face of Fitting 1/8" (3mm) 1-5/8"(42mm) 11/16" (17mm) 6-3/8" (148mm) 1-7/16" (36mm) 5/16"(60mm) Distance from Bottom below above above below above below of Ceiling Grid Note: Based on 1-11/16"(43mm)tall ceiling grid. Fig.3 Dimension C-Clearance Above Ceiling Required at Max.Sprinkler Recess Recessed Escutcheon or Reducer Concealed/Flush Sprinkler 5-5/8"(143mm)Elbow 7-3/8"(187mm)Elbow F1 recessed escutcheon NC 5-5/8" (144mm) F2 or FV recessed escutcheon NC 5-3/8" (138mm) FP recessed escutcheon NC 6-1/4" (160mm) CCP conical concealed cover plate NC 6-1/4" (160mm) G4 series concealed sprinklers 5-5/8" (144mm) 7-3/8" (188mm) G5 series concealed sprinklers 5-1/4" (134mm) 7" (179mm) RFC series concealed sprinklers 5-1/4" (134mm) 7" (179mm) XL commercial flush sprinkler with flat escutcheon 4-7/8" (125mm) 6-5/8" (169mm) XL commercial flush sprinkler with conical escutcheon 4-3/8" (112mm) 6-1/8" (157mm) Note: NC-Reducer not compatible with sprinkler adjustment range. Based on 1-11/16" (43mm)tall ceiling grid and flush ceiling tile. Bulletin 213 Reliable Page 3 of 8 April 2022 www.reliablesprinkler.com Materials Figure 4 Number Item Description Material 1 Flexible Hose/Bellow AISI Type 304 Stainless Steel 2 Isolation Ring Nylon 66 3 Gasket EPDM 4 Nut Zinc Plated Carbon Steel 5 Branch Line Nipple(1") Zinc Plated Carbon Steel 6 Reducer Zinc Plated Carbon Steel 7 Braid AISI Type 304 Stainless Steel 8 Welded Collar Fitting AISI Type 304 Stainless Steel I - Bar Stock Zinc Plated SGCC Steel - Brackets: Center and Side Zinc Plated SPCC Steel Flexible Hose Number of Bends Figure 5 One Bend Two Bends Three Bends Minimum bend radius 2x 2x Min i Min bend bend \ radius radius Minimum I OR OR bend radius Nradius imum9 radius————— — MinimumMinimum bend radius bbend radius bend radius Do NOT install the RASCOFLEXTM straight. Some flexibility in the form of an allowable bend (or bends) must be provided. Bulletin 213 Reliable Page 4 of 8 April 2022 www.reliablesprinkler.com c&us cLILus Friction Loss Data Nominal Reducer Maximum Maximum Equivalent Length Length of Flexible Sprinkler Number of of 1" (33.7mm) Hose K-Factor 90'Bends at 3" Sch.40 Pipe in(mm) NPT Threads Type gpm/psi112 (76mm) (C=120),ft(m) (Ipm/bar112) Bend Radius 24 1/2 Straight 5.6(80) 2 10(3) (610) 3/4 Straight 14.0(200) 2 13(4) 31 1/2 Straight 5.6(80) 3 14(4.3) (790) 3/4 Straight 14.0(200) 3 16(4.9) 40 1/2 Straight 5.6(80) 4 21 (6.4) (1015) 3/4 Straight 14.0(200) 4 23(7) 48 1/2 Straight 5.6(80) 4 24(7.3) (1220) 3/4 Straight 14.0(200) 4 26(7.9) 60 1/2 Straight 5.6(80) 4 25(7.6) (1525) 3/4 Straight 14.0(200) 4 30(9.1) 72 1/2 Straight 5.6(80) 5 36(11) (1830) 3/4 Straight 14.0(200) 5 33(10.1) UL Notes: 1. Available data for use with 6.1"straight reducers. 2. Sprinkler K-Factor: 5.6(80 metric)for 1/2-inch reducer and 14.0(200 metric)for 3/4-inch reducer. 3. RASCOFLEX°Sprinkler Connections have been tested and approved by Underwriter's Laboratories, Inc.for use in wet, preaction, and dry sprinkler systems per NFPA 13, 13D, 13R and UL2443. Bulletin 213 Reliable Page 5 of 8 April 2022 www.reliablesprinkler.com FM APPROVED FM Friction Loss Data Nominal Reducer Maximum Maximum Equivalent Length Length of Flexible Sprinkler Number of of 1" (33.7mm) Hose K-Factor 90'Bends at 7" Sch.40 Pipe in mm NPT Threads Type 1 Z p ( ) Yp (IIpm/bar'12) Bend Radius (C=120),ft(m) 1/2 Straight 5.6(80) 1 9.7(2.9) 1/2 90'Elbow 5.6(80) 0 11.5(3.5) 8.0(115) 1 9.9(3) 24 3/4 Straight 11.2(160) 1 9.8(2.9) (610) 14.0(200) 1 9.6(2.9) 8.0(115) 0 10.2(3.1) 3/4 90'Elbow 11.2(160) 0 10(3) 14.0(200) 0 9.8(2.9) 1/2 Straight 5.6(80) 2 12.4(3.8) 1/2 90'Elbow 5.6(80) 2 15.8(4.8) 8.0(115) 2 13.7(4.1) 31 3/4 Straight 11.2(160) 2 12.9(3.9) (790) 14.0(200) 2 12.2(3.7) 8.0(115) 2 14.5(4.4) 3/4 90' Elbow 11.2(160) 2 13.7(4.1) 14.0(200) 2 13(3.9) 1/2 Straight 5.6(80) 2 15.9(4.8) 1/2 90'Elbow 5.6(80) 2 21.6(6.6) 8.0(115) 2 18.5(5.6) 40 3/4 Straight 11.2(160) 2 17.4(5.3) (1015) 14.0(200) 2 16.3(4.9) 8.0(115) 2 20(6) 3/4 90'Elbow 11.2(160) 2 18.9(5.7) 14.0(200) 2 20(6) 1/2 Straight 5.6(80) 3 19.0(5.8) 1/2 90'Elbow 5.6(80) 3 25.9(7.9) 8.0(115) 3 22.7(6.9) 48 3/4 Straight 11.2 (160) 3 21.5(6.5) (1220) 14.0(200) 3 20.5(6.2) 8.0(115) 3 24.8(7.5) 3/4 90'Elbow 11.2 (160) 3 23.6(7.2) 14.0(200) 3 22.6(6.8) Bulletin 213 Reliable Page 6 of 8 April 2022 www.reliablesprinkler.com FM Friction Loss Data(cont.) Nominal Reducer Maximum Maximum Equivalent Length Length of Flexible Sprinkler Number of of 1"(33.7mm) Hose K-Factor 90'Bends at 7" Sch.40 Pipe in mm NPT Threads Type 112 p ( ) Yp (Ipm/bar"2) Bend Radius (C=120),ft(m) 1/2 Straight 5.6(80) 4 23.7(7.2) 1/2 90'Elbow 5.6(80) 4 33.1 (10) 8.0(115) 4 29.1 (8.8) 60 3/4 Straight 11.2(160) 4 28(8.5) (1525) 14.0(200) 4 27(8.2) 8.0(115) 4 32.2 (9.8) 3/4 90'Elbow 11.2(160) 4 31.1 (9.5) 14.0(200) 4 30(9.1) 112 Straight 5.6(80) 4 28.4(8.6) 1/2 90'Elbow 5.6(80) 4 40.4(12.3) 8.0(115) 4 35.5(10.8) 72 3/4 Straight 11.2(160) 4 34.3(10.4) (1830) 14.0(200) 4 33.2(10.1) 8.0(115) 4 39.5(12) 3/4 90' Elbow 11.2(160) 4 38.3(11.6) 14.0(200) 4 37.2(11.3) FM Notes: 1. RASCOFLEX°Sprinkler Connections have been tested and approved by FM Approvals for use in wet, preaction, and dry sprinkler systems per FM data sheets 2-0,2-5, and 2-8 per FM1637. 2. Maximum sprinkler K-Factor: 5.6(80 metric)for 1/2-inch reducer and 14.0(200 metric)for 3/4-inch reducer. 3. Differences in equivalent lengths are due to varying test methods, per FM 1637 standards. 4. Above data of friction loss for use with 6.1"straight reducers. Bulletin 213 Reliable Page 7 of 8 April 2022 www.reliablesprinkler.com Accessories List ' 5-5/8"(143mm) 7-3/8"(187mm) 4-5/16" (110mm) Elbow Reducer- Elbow Reducer- Straight Reducer — Short Long 1/2": 7 M 99003306 1/2": 7M99003303 1/2": 7M99003302 3/4": 7M99003325 3/4": 7M99003305 3/4": 7M99003304 Replacement 5-5/16" (135mm) 6-1/8"(155mm) 11-13/16"(300mm) Straight Reducer Standard Straight Straight Reducer Reducer z 1/2": 7M99003307 = 1/2":7M99003309 dam 3/4": 7M99003326 1/2": 7M99003308 3/4":7M99003328 3/4": 7M99003327 Hat Channel End Hat Channel En Metal Stud End Bracket-Short Bracket-Long Bracket-Short 1-112" 3"(76mm) 3-3/4"(95mm) (38mm) 7M99003310 7M99003311 7M99003312 Metal Stud End T-Bar End Bracket- T-Bar End Bracket- Bracket-Long I� Short 2-5/8" (68mm) Long 4-1/8"(105mm) 2-1/16" (53mm) 7M99003314 7M99003316 7M99003313 Wood Beam Stud 4` ti Replacement 3"(76 mm) End Bracket Center Bracket Bend Radius 7M99003317 7M99003321 Indicator 7M99004179 Replacement Replacement Gasket 1" NPT Inlet Adapter #2 Square Drive Bit 7M99004319 7M99003322 7M990045390 - 48" (1220mm) Bracket Assembly 41 7M99003301 0 0 0 ti rn rn rn Bulletin 213 Page 8 of 8 rn April2022 Reliabld www.reliablesprinkler.com Z .66 Mechanical-TO Bolted Branch Outlets SEE FM �c Vd3 LPCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS VNIIPO STYLES 920 AND 920N Victaulic Mechanical-TO Outlet provides a direct branch connection at any location a hole can be cut in pipe.The hole is cut oversize to receive a "holefinder" locating collar which secures the outlet in position permanently.A pressure responsive gasket seals on the pipe O.D. Cross-type connections can be achieved by utilizing two upper housings of the same style and size,with the same or differing branch size connections. NOTE: Style 920 and Style 920N 115 top housings cannot be mated to each other to achieve a cross connection. Style 920 and Style 920N Mechanical-T outlets are available with grooved or female threaded STYLES 920 AND 920N STYLE 920 CROSS outlet. Specify choice on order. Units are supplied painted with plated bolts. Galvanized hous- PATENTED ings are available,supplied with plated bolts. All sizes of Style 920 and 920N are rated at 500 psi/3450 kPa working pressure on Schedule 10 and 40 carbon steel pipe.They may also be used on high density polyethylene or poly- butylene(HDPE) pipe. Pressure ratings on HDPE are dependent on the pipe rating.Contact Victaulic for ratings on other pipe. Style 920 and 920N are not recommended for use on PVC plastic pipe. Standard piping practices dictate that the Mechanical-T Styles 920 and 920N must be installed so that the main and branch connections are a true 90°angle when permanently attached to the pipeline surface. Additionally,the Vic-Tap II®hole cutting tool,which allows for hole cutting capabilities on pressurized systems, utilizes the Style 920 Mechanical-T in conjunction with the Series 726 Vic-Ball Valve to create the Style 931 Vic-Tap II Mechanical-T unit.See page 8 for further information. MATERIAL SPECIFICATIONS Housing/Coating: Ductile iron conforming to ASTM A-536,grade 65-45-12,with orange enamel coating. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. • Optional: Hot dipped galvanized Gasket: (Specify choice*) • Grade"E" EPDM EPDM (Green color code).Temperature range—30oF to+230oF/-34oC to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180oF/+82oC. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. *Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iIIIIC 1I1C® REV_O 11.02_1 CARBON STEEL PIPE- HOLE CUT PRODUCTS 11 .02 Mechanical-r Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Size Dimensions min a I Size D. Inches +0.13 Inches Inches F Y �Z� �� - - 2 x Y215 d 920N 500 38.1 2.00 2.53 1.61 136 2.0 3.1 50 15 3450 38.1 51 64 41 136 70 1.5 V 3/4(a) 920N 500 1.50 1.97 2.53 1.61 5.35 2.75 3.1 20 3450 38.1 50 64 41 136 70 1.5 1(a)n 920N 500 1.50 1.85 2.53 _ 1.61 5.35 2.75 3.0 w 25 3450 38.1 47 64 41 136 70 1.4 1 Y4(a)to 920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2 GROOVED OUTLET 32 3450 44.5 52 70 76 41 136 76 1.7 1.5 11/2(a)to 920N 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 3.2 40 3450 44.5 52 70 79 41 136 83 1.7 1.5 Y Z 2 5 x 'k(a)§d 920N 500 L50 2.21 2.74 _ 1.82 143 2.0 3.4 65 a) 3450 1.5 .1 70 46 1.6 70 1.4 3/a(a)§d 920N 500 i 1.50 2.18 2.74 _ 1.82 5.64 2.75 3.0 V 20 3450 38.1 55 70 46 143 70 1.4 T 1(a)§n 500 1.50 2.06 2.74 _ 1.82 5.64 2.75 2.9 t25 920N 3450 38.1 52 70 46 143 70 1.4 // 1'/4 t(a)0 920N 500 1.75 2.30 3.00 3.25 1.82 6.29 3.00 3.5 3.2 32 3450 44.5 58 76 83 46 160 76 1.7 1.5 FEMALE THREADED OUTLET 1'/2 t(a)0 920N 500 2.00 2.28 3.00 3.25 1.82 6.26 3.25 3.6 3.3 40 3450 50.8 58 76 83 46 159 83 1.7 1.6 1/2(a) 300 1.50 2.22 2.75 _ 2.25 6.46 3.18 3.9 76.1 x 15 920N 2065 38.1 56 70 57 164 81 1.8 • Provides a direct branch connection at 3/4(a) 920N 300 1.50 2.19 2.75 2.25 6.46 3.18 3.9 any location where a hole can be cut 20 2065 38.1 56 70 - 57 164 81 1.8 in the pipe 1(a) 920N 300 1.50 2.07 2.75 _ 2.25 6.46 3.18 3.8 25 2065 38.1 53 70 57 164 81 1.7 • A pressure responsive gasket provides 1'/4(a)a 920N 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.2 the seal 32 3450 44.5 58 76 84 49 160 76 1.6 1.5 1 1/2(a)a 920N 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3 • Request Publication 11.03 for 40 3450 50.8 58 76 84 49 160 83 1.6 1.5 Mechanical-T cross assemblies 3 /2(a)a 500 1.50 2.52 3.05 _ 2.28 6.15 2.75 3.4 80 x 15 920N 3450 38.1 64 78 58 156 70 1.6 • Pressure rated up to 500 psi/3450 kPa 3/4(a)a 920N 500 1.50 2.49 3.05 2.28 6.15 2.75 3.4 on steel pipe; also available for use 20 3450 38.1 63 78 - 58 156 70 1.6 with HDPE pipe 1(a) 920N 500 1.50 2.38 3.06 _ 2.28 6.15 2.75 3.3 25 3450 38.1 61 78 58 156 70 1.6 • Sizes from 2 x 1/2'/50 x 15 mm 1'/4(a)to 920N 500 1.75 2.55 3.25 3.56 2.28 6.15 TOO 3.8 3.7 through 8 x 47200 x 100mm 32(b) 3450 44.5 65 83 90 58 156 76 1.8 1.8 1 1/2(a)to 920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8 40(b) 3450 50.8 71 89 90 58 156 83 1.9 1.8 2(a)o 920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.6 50 3450 63.5 70 89 90 58 172 99 2.3 2.1 3/2 x 2 920N 500 2.50 3.00 _ 3.75 2.44 6.72 3.88 _ 3.8 90 50 3450 63.5 76 95 62 171 99 1.8 IMPORTANT NOTES: TABLE CONTINUED ON PG.3 Style 920 and Style 920N housings cannot be **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). mated to one another t Available with grooved or female threaded outlet.Specify choice on order. to achieve cross connections. t Center of run to end of fitting. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 2'/2"BSPT clearly on order. §Vds approved for fire protection services o-PCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com ICtaUI1C° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 11.02_2 REV-0 CARBON STEEL PIPE- HOLE CUT PRODUCTS 11 .02 Mechanical-TO Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Size Dimensions Weight Each Inches +0.13 Inches Inches Inches Inches Inches inch Lbs. Lbs. E Y �Z� r0 TABLE CONTINUED FROM PAGE 2 - 4 1/2(a)❑ 500 1.50 3.03 3.56 2.69 7.01 2.75 3.7 V 100 x 15 920N 3450 38.1 77 90 68 178 70 1.8 r I 3/4(a)❑ 920N 500 1.50 3.00 3.56 _ 2.69 7.01 2.75 3.7 20 3450 38.1 76 90 68 178 70 1.8 w 1(a)a 500 1.50 2.88 3.56 _ 2.69 7.01 2.75 3.6 _ 25 920N 3450 38.1 73 90 68 178 70 1.8 GROOVED OUTLET 1 Y4(a)to 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6 32(b) 3450 1 44.5 78 96 102 68 178 76 1.9 1.8 1 Y2(a)tII 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9 40(b) 3450 50.8 83 102 102 68 178 83 2.0 1.9 Y �Z 2(a)to 920N 4 0 63.5 83 102 100 68 1 17 99 2.3 2.1 50 3450 63.5 83 102 102 68 178 99 2.3 2.1 v 2'/2(a)t 920 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0 T 65 3450 69.9 73 102 102 68 186 118 2.6 2.3 76.1 mm 920 500 2.75 2.88 _ 4.00 2.69 7.34 4.63 _ 6.4 w 3450 69.9 73 102 68 186 118 2.9 3(a)t 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.4 FEMALE THREADED OUTLET 80 920 3450 88.9 84 114 105 68 196 130 3.8 2.9 1 1/4(a)0 500 1.75 3.08 3.78 _ 2.63 7.64 3.05 5.0 _ 108.0 x 32 920N 3450 44.5 78 96 67 194 78 2.3 11/2(a)o 920N 500 2.00 3.28 4.00 2.63 7.64 3.25 5.0 • Provides a direct branch connection at 40 3450 50.8 83 102 - 67 1 194 83 2.3 any location where a hole can be cut 2(a) 920N 500 2.50 3.25 4.00 2.63 7.64 4.00 4.0 in the pipe 50 3450 63.5 83 102 - 67 194 102 1.9 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.0 7.8 • A pressure responsive gasket provides 76.1 mm 920 3450 69.9 73 102 ' 102 67 194 109 3.6 3.5 the seal 3(a) 920 500 3.50 3.31 4.50 4.50 2.63 7.63 4.88 6.8 6.5 80 3450 88.9 84 114 114 67 194 124 3.1 3.0 • Request Publication 11.03 for 5 1'/2(a)t 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 7.4 7.6 Mechanical-T cross assemblies 125 x 40 920 3450 50.8 102 121 121 80 246 94 3.4 3.4 2(a)t 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.0 • Pressure rated up to 500 psi/3450 kPa 50 920 3450 63.5 102 121 121 80 246 111 3.7 3.6 on steel pipe; also available for use 2v2(a)t 9zo 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 79 with HDPE pipe 65 3450 69.9 92 121 121 80 246 118 3.8 3.6 76.1 mm a 920 500 2.75 3.75 _ 4.75 3.16 9.70 4.63 _ 8.0 • Sizes from 2 x 1/2750 x 15 mm 3450 69.9 95 121 80 246 118 3.6 through 8 x 47200 x 100 mm 3(a)t 920 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8 80 3450 88.9 97 127 118 80 246 135 3.8 4.0 2 500 2.50 3.75 4.50 _ 3.17 8.00 3.88 8.0 _ 133.0 x 50 920N 3450 63.5 95 114 81 203 99 3.6 3 920 500 3.50 3.81 5.00 _ 3.00 9.46 5.31 8.0 80 3450 88.9 I 97 I 127 76 240 135 3.6 TABLE CONTINUED ON PG.4 IMPORTANT NOTES: **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). Style 920 and Style 920N housings cannot be t Available with grooved or female threaded outlet.Specify choice on order. mated to one another t Center of run to end of fitting. to achieve cross connections. # Female threaded outlets are available to NPT and BSPT specifications. @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order. §Vds approved for fire protection services ❑LPCB approved for fire protection services 0 Approved for use in China by Tianjin Approvals Company. www.victaulic.com iiiCtaILJIiiiC® VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_O 11.02_3 CARBON STEEL PIPE- HOLE CUT PRODUCTS 11 .02 Mechanical-r Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Size Dimensions minal Size D. Inches +0.13 Inches y �Z� r- 00 Inches mm mm mm m TABLE CONTINUED FROM PAGE 3 - 1 Yz t 500 2.00 3.78 4.50 3.30 1 8.23 3.25 1 7.0 i 139.7 x 40 920N 3450 50.8 96 114 - 84 1 209 83 3.2 - i I 2 t 920N 500 2.50 3.75 4.50 3.30 8.23 3.88 9.0 -- 50 3450 63.5 95 114 84 209 99 4.1 w 6 1/4(a) 500 1.75 4.43 5.13 5.13 3.79 9.15 3.25 5.1 4.8 150 x 32(b) 920N 3450 44.5 112 130 130 96 232 83 2.3 2.2 GROOVED OUTLET 1 Yz(a)trl 920N 500 2.00 4.40 5.13 5.13 3.79 9.15 3.25 5.4 5.1 40(b) 3450 50.8 112 130 130 "3.7 232 83 2.4 2.3 2(a)to 920N 500 2.50 4.38 5.13 5.139.15 3.88 6.0 5.6 50 3450 63.5 111 130 130 232 99 2.7 2.5 Y 7 Z� 2 Yz 500 69.9 110 130 130 94 10.51 118 8.3 3.4 '� 65 920 3450 69.9 110 130 130 94 267 118 3.8 3.4 V 500 2.75 4.15 _ 5.21 3.69 10.51 4.63 _ 8.4 76.1 mm 920 T 3450 69.9 105 132 94 267 118 3.8 3(a)t 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8.4 w 80 920 3450 88.9 110 140 130 94 267 135 4.5 3.8 4(a)to 920 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.1 100 3450 114.3 97 146 137 94 267 159 4.6 4.6 FEMALE THREADED OUTLET 1 1/2(a) 500 2.00 4.41 5.13 _ 3.63 9.40 3.25 7.8 159.0 x 40 920N 3450 50.8 1 112 130 1 92 239 83 3.5 2(a) 920N 500 2.50 4.38 5.13 _ 3.63 9.40 3.88 8.0 • Provides a direct branch connection at 50 3450 63.5 111 130 92 239 99 3.6 any location where a hole can be cut 76.1 mm 920 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63 9.5 9.5 in the pipe 3450 69.9 111 140 130 92 239 118 4.3 4.3 3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 14.0 • A pressure responsive gasket provides 80 920 3450 88.9 110 140 130 92 239 135 3.7 6.4 the seal 500 4.50 4.45 _ 5.38 3.63 9.40 6.12 _ 10.0 108.Omm 920 3450 114.3 113 137 92 239 155 4.5 • Request Publication 11.03 for 4 500 4.50 3.81 5.75 _ 3.63 9.40 6.25 18.0 Mechanical-T cross assemblies 100 920 3450 114.3 96.80 ' 146 92 239 159 1 .2 _ TABLE CONTINUED ON PG.5 • Pressure rated up to 500 psi/3450 kPa +.Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). on steel pipe; also available for use t Available with grooved or female threaded outlet.Specify choice on order. with H DPE pipe t Center of run to end of fitting. • Sizes from 2 x 1/2'/50 x 15 mm # Female threaded outlets are available to NPT and BSPT specifications. through 8 x 47200 x 100 mm @ See page 7 for Fire Protection approvals and pressure ratings. (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. (b)For 76.1 mm threaded outlet,specify 2/2'BSPT clearly on order. §Vds approved for fire protection services a-PCB approved for fire protection services IMPORTANT NOTES: 0 Approved for use in China by Tianjin Approvals Company. Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. www.victaulic.com ICtaUI1C° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 11.02_2 REV-0 CARBON STEEL PIPE- HOLE CUT PRODUCTS 11 .02 Mechanical-TO Bolted Branch Outlets STYLES 920 AND 920N DIMENSIONS Size Dimensions Weight Each Inches +0.13 Inches Inches Inches Inches Inches inch Lbs. Lbs. E Y �Z mm 4 -0.00 mm mm mm mm mm mm kg kg TABLE CONTINUED FROM PAGE 4 - 1 500 1.50 3.88 4.56 3.79 9.34 2.75 8.0 VI 165.1 x 25 920N 3450 38.1 99 116 96 237 70 3.6 V - - 1 Y°II 920N 500 1.75 4.43 5.13 3.79 9.34 3.25 8.4 32 3450 44.5 113 130 96 237 83 3.8 w 1/2(a)tR 920N 500 2.00 4.41 5.13 5.13 3.79 9.34 3.25 8.4 5.4 40 3450 50.8 112 130 130 96 237 1 83 3.8 2.4 GROOVED OUTLET 2(a)t 920N 500 2.50 4.38 5.13 5.13 3.79 9.34 3.88 8.5 6.0 50 3450 63.5 111 1 130 1 130 96 237 99 3.9 2.7 76.1 mm 920 500 2.75 4.01 5.13 5.21 3.63 10.51 4.63 8.6 7.6 3450 69.9 110 130 132 92 267 118 3.9 3.4 Y F Z� 3(8 t 920 500 88.9 110 140 130 92 10.51 135 10.2 8.8 80 3450 88.9 110 140 130 92 267 135 4.6 3.8 V T 4(a)to 920 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4 TL 100 3450 114.3 97 1 146 137 92 267 159 4.8 3.8 + 8 2(a)t 500 2.75 5.44 6.19 6.25 4.81 12.42 4.50 11.6 11.6 w 200 x 50 920 3450 69.9 138 157 159 122 316 114 5.3 5.3 2Y2(a)t 920 500 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6 65 3450 69.9 129 157 157 122 316 1 114 5.3 5.3 FEMALE THREADED OUTLET 76.1 mm tt 920 500 2.75 5.25 - 6.25 4.81 12.42 4.56 - 11.6 3450 69.9 133 159 122 316 116 5.3 3(a)to 500 3.50 5.31 6.50 6.50 4.81 12.42 5.31 12.6 11.6 • Provides a direct branch connection at 80 920 3450 88.9 135 165 165 122 316 135 5.7 5.3 any location where a hole can be cut 4(a)to 920 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5 in the pipe 100 3450 114.3 122 1 171 162 122 316 159 6.9 5.7 **Center of run to engaged pipe end,female threaded outlet only(dimensions approximate). • A pressure responsive gasket provides t Available with grooved or female threaded outlet.Specify choice on order. the seal # Center of run to end of fitting. • Request Publication 11.03 for # Female threaded outlets are available to NPT and BSPT specifications. Mechanical-T cross assemblies @ See page 7 for Fire Protection approvals and pressure ratings: • Pressure rated up to 500 psi/3450 kPa (a)British Standard female pipe threaded outlet is available as listed.Specify"BSPT"clearly on order. on steel pipe; also available for use (b)For 76.1 mm threaded outlet,specify 21/2"BSPT clearly on order. with HDPE pipe §Vds approved for fire protection services rt-PCB approved for fire protection services • Sizes from 2 x 1/2750 x 15 mm 0 Approved for use in China by Tianjin Approvals Company. through 8 x 47200 x 100mm IMPORTANT NOTES: Style 920 and Style 920N housings cannot be mated to each other to achieve cross connections. www.victaulic.com ictaill VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_O 11.02_5 CARBON STEEL PIPE- HOLE CUT PRODUCTS 11 .02 Mechanical-r Bolted Branch Outlets STYLES 920 AND 920N FLOW DATA Flow test data has shown that the total head loss between point(1)and (2)for the Style 920,920N and 929 Mechanical-TO fittings can best be expressed in terms of the pressure difference across the inlet and branch.The pressure difference can be obtained from the relationship below. 4z Cv and Kv Values Values for flow of water at+60°F/+16°C are shown in the table below. Formulas for CvrKV Values: AP = Qz Where: AP = Qz Where: O C 2 Q=Flow(GPM) K z Q=Flow(m3/hr) AP=Pressure Drop(psi) V AP=Pressure Drop(Bar) Q = C x AP C =Flow Coefficient Q = K„x AP K =Flow Coefficient j Exaggerated for clarity OutletEquivalent Length of 40 Carbon Steel Pipe OUTLET SIZE (C 120)t FT C,/K,Values NOMINq AL • . � GROOVED '/z 0.840 11 15 21.3 9.4 3/4 1.050 16 20 26.7 4 13.7 1 1.315 21 25 33.7 3.. 8 1.8 1'/< 1.660 50 48 32 42.7 5/z 6 42.9 41.1 1 Y2 1.900 53 53 40 48.3 11 11 45.4 45.4 2 2.375 112 104 50 60.3 9 10/z 96 89.1 2'/2 2.875 1 119 150 65 73.0 20 12/z 102 128.5 76.1 mm 3.000 16* 161 76.1 1 1 138.1 3 3.500 249 237 80 88.9 14 15/z 213.4 203.1 4 4.500 421 401 100 114.3 20 22 360.8 343.6 t Hazen-Williams coefficient of friction is 120. *Pipe with a wall thickness of 0.165in./4.2mm. 1"FireLock-Innovative Groove System(IGS)outlet www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt.'dUI1C° 11.02_6 REV-0 CARBON STEEL PIPE- HOLE CUT PRODUCTS 11 .02 Mechanical-TO Bolted Branch Outlets STYLES 920 AND 920N FIRE PROTECTION APPROVALS AND PRESSURE RATINGS The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies.Contact Victaulic for performance on other pipe and the latest listings and approvals. Approval Agency Run Size Outlet Size Pipe Rated Working Pressures—psi/kPa de Vds Size W . Inches/m Inches/mm *lnches/m cpheldule UL IJLC r—MR(Style 920) (Style 920N) dL 21/2-6 2.875-6.625 All 10,40 400 400 400 290 232 362 65-150 73.0-168.3 2755 2755 2755 1 1999 1599 2496 21/2-4 2.875-4.500 All DF 300 300 300 290 232 362 65-100 73.0-114.3 2065 2065 2065 1999 1599 2496 21/2-4 2.875-4.500 All SF 300 300 300 290 232 362 65-100 73.0-114.3 2065 2065 2065 1999 1599 2496 6 6.625 3,4 10 300 300 250 290 232 362 150 168.3 2065 2065 1724 1999 1599 2496 6 6.625 3,4 30,40 300 300 300 290 232 362 150 168.3 2065 2065 2065 1999 1599 2496 8 8.625 21/2 10,40 400 145 200 219.1 2755 1000 8 8.625 3,4 10 300 250 145 200 219.1 2065 1724 1000 8 8.625 3,4 30,40 300 _ 300 _ 145 200 219.1 2065 2065 1000 NOTES: 10 refers to Listed/Approved Schedule 10 steel sprinkler pipe. 40 refers to Listed/Approved Schedule 40 steel sprinkler pipe. DF refers to Listed/Approved Dyna-Flow steel sprinkler pipe manufactured by American Tube Company. SF refers to Listed/Approved Super-Flo steel sprinkler pipe manufactured by Allied Tube and Conduit Corporation. VIC-TAP II HOLE CUTTING TOOL FOR The Vic-Tap II hole cutting tool is designed for use with the Style 931 Vic-Tap II Mechanical-T unit, 4-8"/100- 200 MM CARBON STEEL PIPE which is a combination of the Style 920 Mechanical-T and Series 726 Vic-Ball Valve.The Vic-Tap II is capable of tapping into carbon steel pipe systems under pressures up to 500psi/3450kPa. The Style 931 Vic-Tap II Mechanical-T unit is a full port ball valve which can be mounted on 4"/100mm, 5Y125mm,67150mm and 87200 mm diameter pipe.The Style 931 comes with a 21/2"/65mm grooved outlet. The drill motor is an electric motor with ground fault circuit interrupter(GFCI) in accordance with safety codes. For more information, refer to publication 24.01. 1 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. X.A—c-tSUIiC® REV_O 11.02_7 rM1 Mechanical-r Bolted Branch Outlets STYLES 920 AND 920N INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 11.02 1480 REV 0 UPDATED 11/2018 L+tc�u�lC® VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2018 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 0 11.02_L FIRE SPRINK IER PERMIT APPLICATIO N For Instruction/Checklist,please click here Project Valuation: 7600 Preferred Contact: Owner Applicant Contractor Project Description: O mer Details Owner Nam e WEISS CO M RNY XI LLC Office No.: Em al Address: Cell No.: Mailing Address: 3023 80TH AVE SE STE 201 City: MERCER ISLAND State: WA Zip: 98040 Contractor Details Legal Business Nam e WO LFE FIRE PRO-ECTION Business Trade Nam e Business Address 832 80TH STREET SW City EVERETT State WA Zip 98203 Office Phone (360) 794-8621 EXT 206 Mailing Address 832 80TH STREET SW City EVERETT State WA Zip 98203 Business Ern dl Address JO DJ@WOLFEFP.CO M State License Num ber 602-377-322 Legal Structure EIN/Tax Num ber 20-0938162 L&IContractor License Num ber WOLFEFP906DD Issue Date 03/04/2010 Expiration Date 12/12/2026 Prim ay Contact Inform anon First Name JODI Last Name JOANIS Ern dl Address JO D J@WOLFEFP.CO M TENANT IMPROVEMENT O RSYSTEM `J MODIFICATIO N(NFPA 13/13R) Number of Devices" Device Fee S ubtotal 1 to 2 $ 75.00 = $ 3 to 5 $ 125.00 = $ 6 to 10 $ 175.00 = $ 11 to 20 $ IF 225.00 = $ 21 to 40 $ 300.00 = $ 300.00 41 to 100 $ 375.00 = $ 101 to 200 $ IF 475.00 = $ 201 to 300 $ 575.00 = $ > 300 ,$ 600.00 plus $50.00 per 100 additional devices (round up) Total Num ber of Devices = $600.00 + $ $ Hydraulically Designed System sYes O /No L-, Yes =Perm I Fee x 2 $ P ERM 1T FEE SUBTOTAL $ 300.00 O NEW COMMERCIAL SYSTEM (NFPA 13/13R) Num ber of Devices" IF Device Fee ubtotal l to 100 $ 375.00 — $ 101 to 200 $ 475.00 — $ 201 to 300 $ 600.00 — $ > 300 $ 625.00 plus $50.00 per 100 additional devices (round up) Total Number of Devices = $625.00 + $ $ Hydraulically Designed System sYes L / O No Yes =Perm 1 Fee x 2 $ P ERM 1T FEE SUBTOTAL $ O RESIDENTIAL(NFPA 13D) Num ber of Devices** IF Device Fee ubtotal 1 to 10 $ 175.00 — $ 11 to 25 $ 225.00 — $ 26+ $ 275.00 — $ > 300 $ 625.00 plus $50.00 per 100 additional devices (round up) Total Number of Devices = $625.00 + $ $ *NFPA 13D SYSTEM INSTALLED (NOT REQUIRED)Perm t Fee Reduced 50% _ $ P ERM 1T FEE SUBTOTAL I $ O H O O NUPPRESSIO NSYSTEM Type of System CF ost per Unit S IF ubtotal Pre-Engineered $ 200.00 — $ Custom Engineered $ 275.00 — $ 26+ $ 275.00 — $ > 300 $ 625.00 plus $50.00 per 100 additional devices (round up) Total Number of Devices = $625.00 + $ $ * NFPA 13D SYSTEM INSTALLED (NOT REQUIRED)Perm 1 Fee Reduced 50% _ $ P ERM1T FEE SUBTOTAL $ O IH O O SUPPRESSIO NSYSTEM Type of System No. of Unit C ost per Unit S ubtotal Pre-Engineered X $ 200.00 — $ Custom Engineered x $ 275.00 — $ PERM IT FEE ESUBTOTAL $ ❑ 1. STANDPIPE SYSTEM Standpipe Type of No. of Unit C ost per Unit S ubtotal Class I—new or existing x $ 150.00 — $ Class 11—new or existing x $ 150.00 — $ PERMIT FEE $ SUBTOTAL FIRE PUMP Type of FIRE No. of Unit C ost per Unit S ubtotal PUMP Fire PUMP $ 300.00 — $ X PERMIT FEE SUBTOTAL $ O SPRAY BO O TFI S(105.7) & INDUSTRIAL O VENS (105.7.7) NO'IE: SEPARATE SPRINK I.ER PERMIT REQ TIRED Type of Booth No. of Unit C ost per Unit S ubtotal Pre-Engineered $ 150.00 — $ w/docum cnts x Site-built or used w/o IF $ 250.00 — $ docum ants x IF Industrial O yen $ 250.00 — $ x PERM IT FEEL J $ SUBTOTAL Plan review fee due at tim eof subm ital TOTAL PERM IT FEE $ 300.00 PLAN REVIEW FEE $ Processing/Technology Fee V-5.00 TO 7AL 1 $ 325.00 I hereby certify that I am the Owner O Applicant Contractor and authorized to sign this application and that the above information is correct and construction on, and the occupancy and the use of the above- described property will be in accordance with the laws, rules and regulation of the State of W ahington, and the City of Arlington. Print Nam a Jodi Joanis Date: 11/13/2025 City of Arlington 14 (11 (0/1 18204 59th Avenue NE, Arlington, • • Washington 98223 Phone: 360-403-3551 jNG� WASHINGTON C Invoice Number: 25-0041 INVOICE Invoice Date: November 13, 2025 Account Number: 3618186221 Bill To: Invoice Questions? Wolfe Fire Protection Phone: 360-403-3551 832 80th St Sw Everett, WA 98203 Email: ced@arlingtonwa.gov Invoice Due Date: November 13, 2023 Record Number: Permit A25-0049 Parcel Number: 31051400302400 Location: 19405 68TH DR NE Date Description Paid Date Amount Paid Balance November 13, Fire System Plan Review(006.345.83.00.02) $148.67 2025 TOTAL: Permit Fees $148.67 $148.67 ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- --------------------------------------------------------- REMITTANCE INFORMATION If you are paying by check, please include this portion with your payment and remit to the address listed on this invoice. Remittance Information Invoice Account Total Due Your payment is due by November 13, 2025 Number Number This Invoice 25-0041 3618186221 1$148.67 Wolfe Fire Protection 832 80th St Sw Everett, WA 98203 City of Arlington 14 (11 (0/1 18204 59th Avenue NE, Arlington, • • Washington 98223 Phone: 360-403-3551 jNG� WASHINGTON C Invoice Number: 25-0125 INVOICE Invoice Date: December 17, 2025 Account Number: 3618186221 Bill To: Invoice Questions? Wolfe Fire Protection Phone: 360-403-3551 832 80th St Sw Everett, WA 98203 Email: ced@arlingtonwa.gov Invoice Due Date: December 17, 2023 Record Number: Permit A25-0049 Parcel Number: 31051400302400 Location: 19405 68TH DR NE Date Description Paid Date Amount Paid Balance November 13, Processing/Technology(320.341.43.00.02) $25.00 2025 December 17, Fire Sprinkler System(006.322.10.00.01) $300.00 2025 TOTAL: Permit Fees $325.00 $325.00 ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- --------------------------------------------------------- REMITTANCE INFORMATION If you are paying by check, please include this portion with your payment and remit to the address listed on this invoice. Remittance Information Invoice Account Total Due Your payment is due by December 17, 2025 Number Number This Invoice 25-0125 3618186221 1$325.00 Wolfe Fire Protection 832 80th St Sw Everett, WA 98203 18204 59th Avenue NE • ' • 14 op Arlington, Washington 98223 to tt Phone: 360-403-3551 jNG� WASHINGTON C Fire - Fire Sprinkler Permit Parcel:31051400302400 Permit#:23-0049 Permit Address:19405 68TH DR NE Date Issued:December 29,2025 Description of Work:THIS TENANT PERMIT EXPIRES 180 DAYS IMPROVEMENT INCLUDES THE INSTALLATION AFTER DATE OF ISSUANCE. OF 15 PENDENT SPRINKLER HEADS AND 8 UPRIGHT SPRINKLERS IN A COMBUSTIBLE CONCEALED SPACE(BUILDING A FLOOR OUT OF WOOD ABOVE THE NEW T-BAR CEILING IN UNIT H ONLY,UNIT F T-BAR IS OPEN TO ABOVE,NO COMUBISTIBLE CONCEALED SPACE IS BEING CREATED)TO PROTECT NEW LIGHT HAZARD AREAS,DESIGNED AND INSTALLED IN ACCORDANCE WITH 2O19 NFPA 13,2021 IFC& IBC,AS WELL AS LOCAL JURISDICTION SPECIFICATIONS/GUIDE LINES. Valuation:$7600 Code Year: OWNER APPLICANT CONTRACTOR Jodi Joanis Wolfe Fire Protection WEISS COMPANY XI LLC 832 80th St Sw,Everett,WA 98203 3023 80TH AVE SE STE 201 832 80th Street SW (360)794-8621 ext 206 602377322 jodij@wolfefp.com jodij@wolfefp.com registration number:WOLFEFP906DD PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for, or approval of, any violation of this Code or any other ordinance or order of the City, of any state or federal law, or of any order, proclamation, guidance advice or decision of the Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law, or order, proclamation, guidance advice or decision of the Governor of this State, this permit shall not authorize such work and shall not be valid. The building official is authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this jurisdiction or any other ordinance or executive order of the City, or of any state or federal law, or of any order, proclamation, guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect, inaccurate or incomplete information, or in violation of any City ordinance, regulation or order, state or federal law, or any order, proclamation, guidance or decision of the Governor. It is unlawful to use or occupy a building or structure until a final inspection has been made and approval or a Certificate of Occupancy has been granted. This permit authorizes only the work noted and covers work to be done on private property only. Any construction on public domain (curbs, sidewalks, driveways, marquees, etc.) will require a separate permit. The property owner shall ensure that the construction project complies with all applicable zoning codes and regulations. The property owner shall also ensure that the construction project does not cause any adverse impact on the surrounding environment or community. The property owner shall be responsible for obtaining all necessary permits and approvals from the relevant authorities before commencing construction. The property owner shall ensure that the construction project complies with all applicable design review requirements. CONDITIONS 1.) Adhere to approved plans. 2.) Permit shall be onsite for inspections 3.) Call for inspections. INSPECTIONS Inspection Line: 360-403-3417 Call for inspections by 3:30 pm for next day inspection. Please allow 48 hours for Fire Inspections. Please provide the following information when leaving a message: Permit Number, Type of Inspection, and provide preference of morning or afternoon inspection. Inspection Portal: Please login to customer portal and submit for the desired inspection type for the permit. r Kevin Olander Building Official ASSOCIATED FEES Date Description Paid Date Amount Paid Balance November 13, Processing/Technology(320.341.43.00.02) $25.00 2025 November 13, Fire System Plan Review(006.345.83.00.02) $148.67 2025 December 17, Fire Sprinkler System(006.322.10.00.01) $300.00 2025 TOTAL: Permit Fees $473.67 $473.67 Credit/Debit Card 41 Payment Successful November 13, 2025 $148.67 $325.00 Credit/Debit Card 125 Payment Successful December 18, 2025 $325.00 $0.00 DESIGN CRITERIA EXISTING HANGING AND BRACING TO REMAIN 1.THIS TENANT IMPROVEMENT INCLUDES THE INSTALLATION OF 15 PENDENT SPRINKLER HEADS AND 8 UPRIGHT SPRINKLERS IN A COMBUSTIBLE CONCEALED SPACE(BUILDING A FLOOR OUT OF WOOD ABOVE THE NEW T-BAR CEILING IN UNIT H ONLY,UNIT F T-BAR IS OPEN TO ABOVE,NO COMBUSTIBLE CONCEALED SPACE IS BEING CREATED)TO PROTECT NEW LIGHT HAZARD AREAS, T-BAR LID ON THIS SIDE ENCLOSED Approved DESIGNED AND INSTALLED IN ACCORDANCE WITH M19 NFPA 13,2021 IFC&IBC,AS WELL AS LOCAL e71 JURISDICTION SPECIFICATIONS/GUIDELINES. WOOD FRAMING/CREATES COMB. 2.WFP SCOPE OF WORK IS IN THE OUTLINEDICONTRACTED AREA ONLY.NEW SPRINKLER HEADS - = T-BAR LID ON THIS SIDE OPEN TOCONCEALED SPACE @ T-BAR AREAS 31eY•Goforih,NDRFA TO BE FED FROM EXISTING BRANCHLINES.3.HYDRAULIC CALCULATIONS HAVE BEEN NOT REQUIRED ON THIS TENANT IMPROVEMENT.AREAIS 1211]Y2025 112]58AM CURRENTLY DESIGNED AND INSTALLED TO PROTECT ORDINARY HAZARD 2,AND TI SPACE IS LIGHTHAZARD. 4.WFPASSUMESTHESTRUCTURETOBEADAQUATETOSUPPORTTHESPRINKLERSYSTEM.ALL MALL ROOM HANGING AND BRACING TO BE PER NFPA 13,2019 EDITION.5.AREASOF THE BUILDING BEING PROTECTED BYWET SPRINKLER SYSTEMS TO BE MAINTAINED ATULE NO LESS THAN 40°F YEAR ROUND,UNLESS HEAT TAPE AND TRACE HAVE BEEN UTILIZED. RE 2 MAINTAINING THESE AREAS AT 40°F OR GREATER ARE SOLELY THE RESPONSIBILITY OF THE I OWNER. 812 08.01 37 7 6.AREAS ON PLAN WHERE SMALL ROOM RULE HAS BEEN USED HAVE BEEN NOTED.RULE WAS UTILIZED TO BE ABLE TO BE GREATER THAN T-6"OFF ANYONE WALL IN THE ROOM,WHILE 19 MAINTAINING NO MORE THAN 225FP OF COVERAGE PER SPRINKLER HEAD. .ALL MATERIAL TO BE UL LISTED AND FM APPROVED FOR FIRE SPRINKLER USE. o = ALL STEEL PIPING (RED& BLUE) o .ALL ELECTRICAL WIRING AND MONITORING OF SPRINKLER SYSTEM TO BE DONE BY OTHERS. IS EXISTING & IS TO REMAIN ALL CLEANING AND PAINTING OF PIPING AND BAGGING OF HEADS TO BE DONE BY OTHERS. t1 .FIRE CAULKING TO BE DONE BY OTHERS. +9 -0 2 SPRINKLER OMISSIONS o � �TE 1'-°" � **CURRENT PLAN IS TO SPRINKLE THE SPACE FURNITUREBUILTINS 8'-4" 8'-4" ABOVE THE T-BAR LID. NO DETAILS HAVE BEEN - SPRINKLERS OMITTED FROM FURNITURE SUCH AS PORTABLE WARDROBE UNITS,CABINETS, I I 1 1 _ _ _ _ _ _ -- _ _ _ _ _ M _ GIVEN ON THIS AREA,SO WE CAN NOT CONFIRM TROPHY CASES,AND SIMILAR ITEMS NOT INTENDED FOR OCCUPANCY PER 2019 NFPA 139.2.9 I\�L///� _ ___ SUITE SUITE H DEPTH. AREA WILL BE PROTECTED OR OMITTED ExTE SPRINKLERIOR OMITTED - -- _ _ PER NFPA 13 2019 EDITION,ONCE DETAILS 9.23I.19.2.3.33W WHEN ALL REQUREDICONDITIONS HAVE R ENMOR PROJECTIONS IET.NG 4FEETPER2019NFPA13 EXISTING -- +9 -0 EXISTING IV V - J OF AREA ARE RELEASED OR CONSTRUCTION I , N NO-COMBUSTIBLEO CONCEALEDMITTED NON-COMBUSTIBLE 1°DROP IT, IS DONE TO REFERENCE. SPRINKLERS OMITTED FROM NON-COMBUSTIBLE CONCEALED SPACES WITH MINIMAL ��COM BUSIBLELOADINGANDHAVINGNOACCESSPER2019NFPA139.2.1.1 2 _ 2 NON-CORINKLER SHALL BE INS 25-11 -' _' `- 35-412 - PLAN REFLECTS COVERAGE ABOVE T SPRINKLERS SHALL INSTALLED MOVE THE BAT OTTOM OF TOF HETHE SHAHAFTANFT PER 19UNDER THE FIRSTACCESSIBL CO SPRINKLERS OMITTED FROM THE BOTTOM OF THE STAARWELL WHEN THESPACE NFPA 13 421 1 STORAGE +9'_0":,�-` _ �.'�-CT TJL--T STOR G UNDERNEATH IS BLOCKED SO THAT STORAGE CAN NOT OCCUR PER 2019 NFPA 139.3.4.2.3.1 J F101 �.J 111 18 I J H101 20� T-BAR IN COMB.CONCEALED SPACE SMALL ROOM o SCHEDULE 40 SPECIFICATIONS TEE(4) RULE +9' 2"X 1"MECH N PIPE WALL INTERNAL WEIGHT OF CAPACITY IN $IZE THICKNESS DIAMETER END PREP TYPES FILLED PIPE GALLONS/FT. O N 1 TE c0 1 1 0.133 1.049 THREADED,CUT&ROLL GROOVED,PLAIN END 2.05 0.045 1 8 B RI E K Z 1- 7-11 1'/. 0.742 1.380 THREADED,CUT&ROLL GROOVED,PLAIN END 2.0 0.WS 1 h 0.145 1.610 THREADED,CUT&ROLL GROOVED,PLAIN END 3.61 0.116 24-9 1 0 -612 2 0.15/ 2.06] THREADED,CUT&ROLL GROOVED,PLAIN END 5.13 0.190 1 1 SCHEDULE 10 SPECIFICATIONS PIPE WALL INTERNAL WEIGHT OF CAPACITY IN Q_ 4 SIZE THICKNESS DIAMETER END PREP TYPES FILLED PIPE GALLONS/FT. v+ 08.02 1'/. 0.109 1.442 ROLL GROOVED,PLAIN END(BUTT WELDING) 2.52 0.085 _ _ _ _ _ _ _ El 1% 0.109 1.682 ROLL GROOVED,PLAIN END(BUTT WELDING) 3.04 0.115 R O C E f 1 / O ,- 1 2 0.109 2.157 ROLL GROOVED,PLAIN END(BUTT WELDING) 4.22 0.190 8.02 10 1_ 8_6 2% 0.120 2.636 ROLL GROOVED,PLAIN END(BUTT WELDING) 5.89 0.283 - -- r Q2 -- I-D-Ffff 3 0.120 3.260 ROLL GROOVED,PLAIN END(BUTT WELDING) 7.94 0.433 r 4 0.120 4.260 ROLL GROOVED,PLAIN END(BUTT WELDING) 11.78 0.740 "' +9 _0 6 0.134 6.357 ROLL GROOVED,PLAIN END(BUTT WELDING) 23.03 1.649 O 2 2 CPVC PIPE 24-9 3- PIPE WALL INTERNAL WEIGHT IP CAPACITY IN F SIZE THICKNESS DIAMETER END PREP TYPES FILLED PIPE GALLONS/FT. 4 02� 13-3 S-� - 1 1 1 0.214 1.101 PLAIN END 0.6]4 .0495 U 1'/. 0.266 1.394 PLAIN END 1.0]9 .U]95 •uo xi _ __ __ __ __ 2-11 8-6 1'A 0.302 1.598 PLAIN END 1.41] .1042 -° - -- -- -- -- 6� 9'6� 2 0.372 2.003 PLAIN END 2.Z23 .1637 cO u7 0l J 08.02 0 MAX DISTANCE BETWEEN HANGERS TO BE: z NOMINAL SIZE 3l4 1 1114 11/2 2 2112 S. 4 5 6 8 6] 10 GRV STEEL PIPE N/A 12-0 12-0 15.0 15-0 160 160 15-0 15-0 160 15-0 1 CO LQ THRDSTEELPIPE I NIA 12-0 12-0 12-0 1 12-0 1 12-0 1 12-0 N/A WA NIA N/A 2 CPVC PIPE SB 6-0 6-6 ]-0 8-0 94 1M N/A WA NIA N/A 24-9 29 8 1 it S-6 SPRINKLER LEGEND s- a-o 1- BYM CNT POSITION FINISH TEMP K NPT SIN MFG. MODEL# SPACING Q 15 PENDENT OR SS CHROME 155° 5.8 il2" 14 RELIABLE FFR56 15'-0X15-0 - ED Q�� E 0 8 UPRIGHT OR SS BRASS 200° 5.8 il2" M RA1425 25 RELIABLE FlFR56 130ft.' 23 TOTAL HEADS ON PROJECT �( 2"X 1'/2'MECH TEE INTO OVER HEAD SYSTEM HANGING & BRACING NEW LOWER SYSTEM FED FROM NEW CPVC LOCATED AOVE T-BAR&HARD LIDS N Ct SU ITE F & H T.I. SPACE SCALE: 3/1 6"=1'-O" JOB # F25063 WOLFE FIRE PROTECTION, INC, WEISS SUITES F & �H[ TL �-�� PERMIT# •NYMIMOTOM.TAT. -��fltlT'.�IrMNLM.WTWMCY i CONTRACT# 832 80TH STREET S.W. ?C...YJemesYarSI.Y ptc,N APPROVAL: 19405 68TH DR NE :B{34D3,9-Q L..I E DRAWN BY:WY EVERETT, WA 98203 •Wo1h FIroP bdlo.Ine. DATE 11I10I2025 :WOLFEF DD • DATE 1111:ASNOTED25360 '794 8621 ARLINGTON, WA 98223SCAL s u Isl t REVISION DATE:N/A • LL CONTRACTOR#:WOLFEFP9006DD 5���������� �� 4rtk( tot( WASHINGTON Permit Information - - , 1 'nformat;^ Permit# 25-0049 Parcel # 31051400302400 Building ID Location 19405 68TH DR NE Permit Type Fire Permit Use Fire Sprinkler Zone Permit # Subdivision Applicant Name Jodi Joanis Address 832 80th Street SW Applicant Email jodij@wolfefp.com Phone (360) 794-8621 ext 206 Cell Owner Name WEISS COMPANY XI LLC Address 3023 80TH AVE SE STE 201 Owner Email Phone Cell Contractor Wolfe Fire Protection Address 832 80th St Sw, Everett, WA 98203 Contractor Email jodij@wolfefp.com Phone 602377322 Cell Property Information Type/Improveme Alteration Accessory/Struct nt ure Current Use S-2 Storage Proposed Use Current Zoning 3 Proposed Zoning Project Cost 7600 Project Value 7600 Current Use And THIS TENANT IMPROVEMENT INCLUDES THE INSTALLATION OF 15 PENDENT SPRINKLER HEADS AND 8 Proposed UPRIGHT SPRINKLERS IN A COMBUSTIBLE CONCEALED SPACE (BUILDING A FLOOR OUT OF WOOD ABOVE THE Changes NEW T-BAR CEILING IN UNIT H ONLY, UNIT F T-BAR IS OPEN TO ABOVE, NO COMUBISTIBLE CONCEALED SPACE IS BEING CREATED)TO PROTECT NEW LIGHT HAZARD AREAS, DESIGNED AND INSTALLED IN ACCORDANCE WITH 2O19 NFPA 13, 2021 IFC& IBC, AS WELL AS LOCAL JURISDICTION SPECIFICATIONS/GUIDELINES. Lot Width Lot Depth Map Number Total Area of Building &Accessory Total Area of All Man-made Improvements Structures (Sq Ft) (Sq Ft) General Notes Restrictions/ Variances @ Community Development Online Portal Page 1 of 6 July 8, 2026 10:56AM WASHINGTON Structure Information Structure Type IBC Building Type V-B # of Stories Usable Floor Area (Sq Ft) Structure Height # of Units Load per Floor (Lbs) Sign Dimensions # of Bedrooms # of Bathrooms Occupancy With Chairs Tables & Chairs Empty Room Foundation Foundation Type Footing Depth Material Foundation Information Setbacks Front& 0 0 Setbacks Right & 0 0 Rear Left Sides Setbacks Information Water Utility Public Sewage Utility Public Gas Utility Public Electric Utility Public Driveway Width # of Off Street # of Off Street Parking Loading Miscellaneous Information ©Community Development Online Portal Page 2 of 6 July 8, 2026 10:56AM WASHINGTON Contractors License # Business Name Type Contact WOLFEFP906DD Wolfe Fire Protection General Jodi Joanis ©Community Development Online Portal Page 3 of 6 July 8,2026 10:56AM WASHINGTON Inspections Inspection # Inspection Type Status Date Inspector 26-0039 Fire-Aboveground Pass January 16, 2026 Brian Grieve Cover 26-0102 Fire- Fire Alarm Final Pass February 19, 2026 Kevin Olander ©Community Development Online Portal Page 4 of 6 July 8,2026 10:56AM 4rtk( tot( WASHINGTON Contacts Contact Name Type Project Address Phone WEISS COMPANY XI LLC Owner 3023 80TH AVE SE STE 201 Jodi Joanis Applicant 832 80th Street SW (360) 794-8621 ext 206 Wolfe Fire Protection Contractor 832 80th St Sw, Everett, 602377322 WA 98203 ©Community Development Online Portal Page 5 of 6 July 8, 2026 10:56AM 4rtk( tot( WASHINGTON Fees Fee Type Date Debit Credit Balance Permit Fees November 13, 2025 $0.00 $0.00 $148.67 $-148.67 $325.00 $-473.67 T O T A L $0.00 $473.67 $-473.67 ©Community Development Online Portal Page 6 of 6 July 8, 2026 10:56AM WASHINGTON Permit #25-0049 Location:19405 68TH DR NE Routing Details ✓ Department: Permit Tech Intake Review - Approved: November 20, 2025 - Status: Approved Manual Update - Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at November 13, 2025 01:33PM Status: In Progress Activity Type: Documents Review The following permit has been updated manually. Permit Application #A25-0049 Location:19405 68TH DR NE Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at November 13, 2025 01:34PM Status: Pending Activity Type: Pending Payment Hello, Your invoice for the plan review fee is now ready for payment.You can access and process the payment through our portal. Please visit the following link to view and pay your invoice: https://www.civicgov4.com/wa_arlington/portal/index.php?r=site/dashboard Admin - Hannah Hardwick City of Arlington Fire Permit Technician II hhardwick@arlingtonwa.gov 360-403-3549 Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at November 20, 2025 10:21AM Status: Approved Activity Type: Application Sent Admin - Hannah Hardwick City of Arlington Fire Permit Technician II hhardwick@arlingtonwa.gov 360-403-3549 Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at November 20, 2025 10:22AM Status: Approved Activity Type: In Review Application is ready to review Admin - Hannah Hardwick ©Community Development Online Portal Page 1 of 5 July 8, 2026 10:56AM 4rtk( tot( WASHINGTON City of Arlington Fire Permit Technician II hhardwick@arlingtonwa.gov 360-403-3549 ✓ Department: Building - Approved: December 1, 2025 - Status: Approved Permit Application #A25-0049 Location:19405 68TH DR NE - by Kevin Olander- Building Official at December 1, 2025 02:58PM Status: Approved Activity Type: Application Sent Kevin Olander City of Arlington Building Official kolander@arlingtonwa.gov 3604033433 ✓ Department: Fire - Approved: December 17, 2025 - Status: Approved Permit Application #A25-0049 Location:19405 68TH DR NE- by Steve Goforth -Assistant Chief/Community Risk Reduction at December 17, 2025 11:29AM Status: Approved Activity Type: Application Sent Approved Steve Goforth North County Regional Fire Authority Assistant Chief/Community Risk Reduction sgoforth@northcountyfireems.com 360-629-2184 ✓ Department: Permit Tech Final Approval - Approved: July 8, 2026 - Status: Closed Manual Update- Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at November 13, 2025 01:32PM Status: In Progress Activity Type: Documents Review The following permit has been updated manually. Permit Application #A25-0049 Location:19405 68TH DR NE Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at December 17, 2025 02:39PM Status: In Progress Activity Type: Pending Payment Hello, @ Community Development Online Portal Page 2 of 5 July 8, 2026 10:56AM WASHINGTON Your invoice is now ready for payment.You can access and process the payment through our portal. Please visit the following link to view and pay your invoice: https://www.civicgov4.com/wa_arlington/portal/index.php?r=site/dashboard Admin - Hannah Hardwick City of Arlington Fire Permit Technician II hhardwick@arlingtonwa.gov 360-403-3549 Permit Application #A25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at December 29, 2025 09:58AM Status: Approved Activity Type: Permit Issued Admin - Hannah Hardwick City of Arlington Fire Permit Technician II hhardwick@arlingtonwa.gov 360-403-3549 Permit #25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at December 29, 2025 10:04AM Status: Approved Activity Type: Permit Issued Hello, Please find attached the issued building permit. Please review any conditions and reach out should you have any questions. Inspection request instructions can be found on the permit. Admin - Hannah Hardwick City of Arlington Fire Permit Technician II hhardwick@arlingtonwa.gov 360-403-3549 Manual Closure - Permit#25-0049 Location:19405 68TH DR NE - by Admin - Hannah Hardwick- Fire Permit Technician II at July 8, 2026 10:55AM Status: Closed Activity Type: Documents Review The following permit has been closed manually. Permit#25-0049 Location:19405 68TH DR NE ©Community Development Online Portal Page 3 of 5 July 8, 2026 10:56AM 4rtk( tot( WASHINGTON Record Actions New Permit Application #A25-0049 Location: 19405 68TH DR NE By Admin - Hannah Hardwick- Fire Permit Technician II at November 13, 2025 01:16PM Hello, A new permit application has been submitted for review. Please login to your CIVICGov Web Application account and visit the link below to view the permit details. https://www.civicgov4.com/wa_arlington/permits/details/50 If you cannot click on the link above, please copy and paste the entire link in the browser address bar. Sincerely, CIVICGov Team. Manual Update- Permit Application #A25-0049 Location:19405 68TH DR NE By Admin - Hannah Hardwick- Fire Permit Technician II at November 13, 2025 01:32PM The following permit has been updated manually. Permit Application #A25-0049 Location:19405 68TH DR NE Manual Update- Permit Application #A25-0049 Location:19405 68TH DR NE By Admin - Hannah Hardwick- Fire Permit Technician II at November 13, 2025 01:33PM The following permit has been updated manually. Permit Application #A25-0049 Location:19405 68TH DR NE Condition #1 Added By Admin - Hannah Hardwick- Fire Permit Technician II at December 29, 2025 09:57AM Condition: Adhere to approved plans. Condition #2 Added By Admin - Hannah Hardwick- Fire Permit Technician II at December 29, 2025 09:57AM Condition: Permit shall be onsite for inspections Condition #3 Added By Admin - Hannah Hardwick- Fire Permit Technician II at December 29, 2025 09:57AM Condition: Call for inspections. Inspection #26-0039: Result- Pass By Steve Goforth -Assistant Chief/Community Risk Reduction at January 16, 2026 03:12PM Fire-Aboveground Cover Inspection #26-0039: Result- Pass Hard Lids in Bathroom, 2 heads CPVC, Contractor added uprights Inspection #26-0102: Result- Pass By Kevin Olander- Building Official at February 23, 2026 02:19PM Fire-Other Inspection #26-0102: Result- Pass the contact on site will be clan shook his number is 206-245-8896 if you have any questions you can call me at brady at 360-631-1089 thank you for your time Manual Closure - Permit#25-0049 Location:19405 68TH DR NE By Admin - Hannah Hardwick- Fire Permit Technician II at July 8, 2026 10:55AM The following permit has been closed manually. ©Community Development Online Portal Page 4 of 5 July 8, 2026 10:56AM WASHINGTON Permit#25-0049 Location:19405 68TH DR NE ©Community Development Online Portal Page 5 of 5 July 8, 2026 10:56AM