ALL WORK SHALL BE IN ACCORDANCE WITH PROPANE TANK WIND LOAD
NFPA 54-58, NATIONAL FUEL GAS CODE FORCE ON TANK = 0.00256V2•A*Cd
AND FLORIDA FUEL GAS CODE 2020 7th ED. = 0.00256(200mph)2 * 41.32ft= * 1.2 — 5078 LBS
& FLORIDA BUILDING CODE 2020 7th ED. 2155 Rockfill Rd.
TORQUE = 5078 x 2FT = 10156 FT'LBS Fort Myers,FL 33916
TANKS INSTALLED IN TRAFFIC AREAS
SHALL BE PROTECTED WITH GALV, STEEL FORCE ON A" CABLE = (5078 / 1.5FT) / 4 = 847 LBS
SCHED. 80 PIPE BOLLARDS (4.0) 6' LONG TENSILE STRENGTH OF J" CABLE = 9800 LBS / 5 = 1960 LHS
X 3' BURY DEPTH WITH CAP 0 3' O.C.
FORCE ON AUGER ANCHOR = 847 LEIS
MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBO
WIND LOAD CERTIFICATION:
CODE FBC 2020 / ASCE 7-10 ZO
WIND SPEED = 200 MPH, 3 SEC. GUST W
EXPOSURE D W
INTERNAL PRESSURE COEFF. 0.00 Q
C7
O
O
8"x16'x4' CONCRETE 7x19 GALV.
TYPICAL OF 8 AIRCRAFT CABLE
BLOCK
( 4 TOTAL (IN POLY.
MIN. — 2 PER LEG) SLEEVE) z
STRAPPING BOLT z 0
LP TANK: I Q r:4
1 i i I z W
G I I L
I hI hI I IT I I hI I I I I I I II I I I I III ITI ITI I I III _
AUGER ANCHOR, 36'
LONG W/ 6"0 HEUX Fort Pierce Engineering,Inc.
Dependable Mechanical,Electrical
8 TOTAL &Plumbing Design
C.A.No.28173
SIDE ELEVATION 315 South 7th Street
SCALE 1/4' = 1'-0' Fort Pierce,FL.34950
Phone:772 672-4636
Fax:772 672-4637
8'x16"x4" CONCRETE " 7x19 GALV.
BLOCK (TYPICAL OF 8 3 —1� AIRCRAFT CABLE
MIN. — 2 PER LEG) (IN POLY. SLEEVE)
� +
STRAPPING BOLT =c
Eric J. Svoboda, PE
LP TANK P.E. No. 60982
I I ISSUE DATE:
I
1 DRAWN: EJS
_—_ — L APPROVED:EJS
1-1 11-1 I I-1 I I-1 I I-1 I I I I-1 I I-1 I 1—= I F_=I I I-1 I I-1 11-111=1 I
DRAWING NUMBER
AUGER ANCHOR, 36'
LONG W/ 6'0 HEUX
8 TOTAL —
FRONT ELEVATION
SCALE I/4• = r-o' LP500AGR2
ITEM NO, PART NUMBER— DESCRIPTION QTY,
V V
6 7579 1 1 4"FILL VALVE 2
8 80-106-01 1 1 4"BALL VALVE 1
9 1 153C NIPPLE 1 1 4"X 4"XH 2
10 B182-S STRAINER'Y' 1 1 4"BRASS 1
11 1153 1 1/4"x Close nipple 1
Hose 1
18 - 1 DE l E 6 W
j 27 1151E 4 x6 nipple
/ 60 28 1193 1 1/4"x 3/4"coupling 1
31 W W-340 3/4"x 3/4"bypass 1
2 52 51 50 6
49 MultiV V Valve
TEE
3176
Valve
47 52 1139E 1 1/4"x 3/4"bushing1
54 54 -1 4- 1 4"B II V Iv 1
® F7 - 1 H E 4'X " RR 1
56 11 7 4 45 cleg. E ow 1
58 1103 1 1 4"9 F ELB W 2 # 1
18
60 T-443 BulkHead Fitting 1
I,
55
i
o -
m
27
28 23
12 11 �
18 8
58 5 i
m
Teeco Products Inc.
7471 Reese Road 1-800-225-6621
Sacramento,Ca.95828
PROPRIETARY THE INFORMATION CONTAINED IN
Drawn By Date AND THIS DRAWING IS THE SOLE
CONFIDENTIAL PROPERTY OF TEECO.ANY
REPRODUCTION INPART OR
1-28-08 ASAWHOLEWITHOUTTHEWRIITEN
PERMISSION OF TEECO IS PROHIBITED
Customer Ske Drawing Number Reviuon
Scale Release Date Sheet
i
COMMERCIAL MECHANICAL APPLICATION
• Community&Economic Development
City of Arlington• 18204 59th Ave NE•Arlington,WA 98223 • Phone(360) 403-3551
This application is for new, addition, altered or replaced mechanical installation and new or altered gas piping and
must be accompanied by ELECTRONIC CONSTRUCTION DRAWINGS and CUT SHEETS and/or information outlined
in the MECHANICAL SUBMITTAL REQUIREMENTS,if applicable.
Type of Permit: 0 New Installation ❑ Addition ❑ Alteration ❑ Replaced ❑ Gas Piping
Type I and Type H Hood Systems required submittal of the Commercial Mechanical Addenda
Property Address: 16900 51st Ave NE, Arlington WA Project Valuation: $16,000
Lot#: Parcel ID No.: 31052800100300 Preferred Contact: ❑ Owner O Contractor
Project Description: Set a 500g above ground LPG tank with dispenser for filling cylinders
Owner Name: Dwayne Paul/Valley Foods Office No.: 360.403.8218
Email Address: dpaul@nationalfoodnw.com Cell No.: 425.407.6216
Mailing Address: 16900 51st Ave NE City: Arlington State: WA Zip: 98223
Contractor Name: Joe Girard/ Ferrellgas LP Office No.: 360.635.2287
Email Address: joegirard@ferrellgas.com Cell No.: 360.635.2287
Mailing Address: 3611 AST SE City: Auburn State: WA Zip: 98002
L&I Contractor License Number: FERRELP055LH Expiration Date: 09/06/2024
• New gas piping requires a pressure test hooking to any appliance
• Sediment traps (drips) are required on all gas lines
• Gas lines are required to be supported/secured per IFGS,Section 415
• Proper Combustion air and venting required for all appliances
• A shut-off valve is required within 6 feet of each appliance
Gas Piping Specification and complete Schematic PAGE 3 O Not Applicable
❑ CSST ❑ Brass ❑ Other
Proposed Piping Material:
❑ Black Steel ❑ Galvanized Steel
Proposed Piping Size: ❑ 1/2" ❑ 5/8 ❑ 3/4" ❑ 1" ❑ 11/2 ❑ 2"
Inlet Pressure: Pressure Drop: Specific Gravity:
REV03.2022 Page 1 of 3
MECHANICAL PERMIT FEES (per unit
Type of Fixture No. of Units Cost per Unit Subtotal
Additional Plan Review fees x $ 75.00 = $
Air Cond.Unit<_100Btu h x $ 15.00 = $
Air Cond.Unit>100Btu h x $ 25.00 = $
Air Cond.Unit>50OBtu/hp x $ 50.00 = $
Air Handling Units x $ 15.00 = $
Base Mechanical Fee $ 25.00 $ 25.00
Boiler<100Btu/h>3hp x $ 15.00 = $
Boiler>1 million Btu/h<50hp x $ 25.00 = $
Boiler>1.5 million Btu/h<50hp x $ 50.00 = $
Boiler>100Btu h 3-15h x $ 15.00 = $
Boiler>500Btu h 15-30hp x $ 25.00 = $
Commercial Hoods-Type I x $ 25.00 = $
Commercial Hoods-Type II x $ 50.00 = $
Diffusers x $ 15.00 = $
Dryer Ducting x $ 15.00 = $
Ductwork(drawings required) x $ 25.00 = $
Evaporative Coolers x $ 15.00 = $
Exhaust/Ventilation Fans x $ 15.00 = $
Fireplace/Insert/Stove x $ 15.00 = $
Forced Air Heat<_100 Btu h x $ 15.00 = $
Forced Air Heat>100 Btu h x $ 25.00 = $
Gas Clothes Dryer x $ 15.00 = $
Gas Fired AC <_100 Btu/h x $ 15.00 = $
Gas Fired AC >100 Btu/h x $ 25.00 = $
Gas Fired AC > 500 Btu h x $ 50.00 = $
Gas Pi in <_ 5 units x $ 15.00 = $
Gas Piping> 5 units (plus <5 units x $ 2.00 = $
Heat Exchangers x $ 15.00 = $
Heat Pump-Condensing Unit x $ 25.00 = $
Hot Water Heat Coils x $ 15.00 = $
Miscellaneous Appliance-regulated by x $ 15.00 = $15
mechanical code,not otherwise specified
Pkg.Units 5100btu x $ 25.00 = $
Pkg.Units >100btu x $ 50.00 = $
Range/Cook top-Gas Fired x $ 15.00 = $
Refrigeration Unit<_100Btu h x $ 15.00 = $
Refrigeration Unit>100Btu h x $ 25.00 = $
Refrigeration Unit>500Btu h x $ 50.00 = $
Re-inspection fee (all) x $ 75.00 = $
Unit Heaters <_ 100 Btu h x $ 15.00 = $
Unit Heaters >100 Btu h x $ 25.00 = $
VAV Boxes (Variable Air Volume,part of air x $ 10.00 = $
conditioning system)
Wall Heaters - Gas Fired x $ 25.00 = $
Water Heater- Gas Fired x $ 25.00 = $
Permit Fee $40
Table 4-8; Plan Review Fee $
Processing/Technology Fee $25.00
Total $65
REV2.2020 Page 2 of 3
PRESSURE PIPING SCHEMATIC
COMPLETE FOR GAS PIPING ONLY
❑ SCHEMATIC IS TO SCALE ❑ SCHEMATIC NOT TO SCALE
Show Pipe Size(s) and Length(s) from meter to all appliances
NOTE: Any interior pressure regulators must be indicated
I hereby certify that I am the El Owner, ❑Applicant, ElCon tractor,and authorized to sign this application and that the above information is
correct and construction on,and the occupancy and the use of the above-described property will be in accordance with the laws,rules and
regulation of the State of Washington,and the City of Arlington.A final inspection and approval shall be obtained when complete.
F Joe Girard Jr Digitally signed by F Joe Girard Jr F Joe e Girard 6/27/23
Date:2023.06.27 15:12:14-07'00'
Signature Print Name Date
REV2.2020 SAVE PRINT Page 3 of 3
I - �
from property
fir 00• above • . i LPG tank
. .
of 38"
• . •�
• • pr ection
i dispenser
i
1 i - . - • blocks�, _ Plan Review
By
This tank is dispensing for internal industrial use. It will not be reselling LPG. City of Arlington
500 gallon above ground LPG tank. Cut sheet attached.
Dispenser cabinet with 1 hp pump and motor for dispensing LPG. Cut sheet attached.
Concrete "eco block" for crash protection set 3' from the skin of the tank. 2' wide x 2' high x 6' long. Set no more than 40" apart. Weight is 2,600 lbs.
Emergency shut-off valve will be mounted on building 21'from dispenser.
There will be an 18# BC rated, NFPA qualified,fire extinguisher mounted at the dispenser cabinet. Received
Tank will be anchored with 36" long anchors with 6" helix. Detail drawing attached.
Dispenser is 15' from the closest property line (shown). It is greater than that to the other three property lines. JUN 2 7 2023
mow+
Tank Location
Ll
1 ..
f o �� `'
CITY OF ARLINGTON
18204 59th Avenue NE,Arlington,WA 98223
INSPECTIONS: 360-403-3417-Permit Center:360-403-3551
BUILDING PERMIT
16900 51STAVE NE Permit#: 5435
PERMIT EXPIRES 180 DAYS AFTER
Parcel#: 31052800100300 DATE OF ISSUANCE.
Scope of Work: Set LPG tank and dispenser Valuation: 16000.00
OWNER APPLICANT CONTRACTOR
AMAZON.COM SERVICES LLC Ferrellgas LP Ferrell Gas
410 TERRY AVE N 3611 A ST SE 3611 A Street SE
SEATTL,WA 98109 Auburn Auburn,WA 98374
3606352287 360-635-2287
LIC:601553542 EXP:09/30/2024
LIC:FERRELP055LH EXP:09/06/2024
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: COMMERCIAL MECHANICAL CODE YEAR: 2018
STORIES: CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any
other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the
Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order,state or federal law, or any order,proclamation,guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED.IBC 110/IRCI 10.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
09/19/2023
Applicant Signature Date Building Official Date
CONDITIONS
SEE REDLINED SITE PLAN FOR ADDITIONAL REQUIREMENTS-ATTACHED. SPACING BETWEEN BLOCKS TO BE
36" OR LESS.ADHERE TO APPROVED SUBMITTAL.APPROVED JOB COPY SHALL BE ONSITE FOR INSPECTIONS.
CALL FOR INSPECITONS.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY.ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
09/19/2023 Processing/Technology $25.00
09/19/2023 Mechanical Commercial Plan Review $258.03
09/19/2023 Fuel/LPG $0.00
Total Due: $283.03
Total Payment: $0.00
Balance Due: $283.03
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
INSPECTION INFORMATION I Pass/Fail
z-.
CITY
OF ARLINGTON
18204 59th Avenue NE,Arlington, WA 98223
INSPECTIONS: 360-403-3417 - Permit Center: 360-403-3551
BUILDING PERMIT
16900 51ST AVE NE Permit#: 5435
PERMIT EXPIRES 180 DAYS AFTER
Parcel #: 31052800100300 DATE OF ISSUANCE.
Scope of Work: Set LPG tank and dispenser Valuation: 16000.00
OWNER APPLICANT CONTRACTOR
AMAZON.COM SERVICES LLC Ferrellgas LP Ferrell Gas
410 TERRY AVE N 3611 A ST SE 3611 A Street SE
SEATTL, WA 98109 Auburn Auburn, WA 98374
3606352287 360-635-2287
LIC: 601553542 EXP:09/30/2024
LIC: FERRELP055LH EXP: 09/06/2024
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC #: EXP: LIC #: EXP:
JOB DESCRIPTION
PERMIT TYPE: COMMERCIAL MECHANICAL CODE YEAR: 2018
STORIES: CONST. TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for, or approval of, any violation of this Code or any
other ordinance or order of the City, of any state or federal law, or of any order,proclamation, guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law, or order, proclamation, guidance
advice or decision of the Governor of this State, this permit shall not authorize such work and shall not be valid. The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City, or of any state or federal law, or of any order, proclamation,
guidance advice or decision of the Governor_ The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect, inaccurate or incomplete information, or in violation of any City
ordinance, regulation or order, state or federal law, or any order, proclamation, guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY; NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC I0/IRCI 10.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and c City of Arlington #3101.
:�/ �— j, O 09/19/2023
Applic ign Date Building Official Date
CONDITIONS
SEE REDLINED SITE PLAN FOR ADDITIONAL REQUIREMENTS -ATTACHED. SPACING BETWEEN BLOCKS TO BE
36" OR LESS. ADHERE TO APPROVED SUBMITTAL. APPROVED JOB COPY SHALL BE ONSITE FOR INSPECTIONS.
CALL FOR INSPECITONS.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS,
MARQUEES, ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
09/19/2023 Processing/Technology $25.00
09/19/2023 Mechanical Commercial Plan Review $258.03
09/19/2023 FueULPG $0.00
Total Due: $293.03
Total Payment: $0.00
Balance Due: $293.03
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection, allow 48 hours for Fire Inspections
When calling for an inspection please leave the following Information:
Permit Number,T�pe of Inspection being requested, and whether you prefer morning or afternoon
INSPECTION INFORMATION Pass/Fail
Permit#: 5435
Permit Date: 06/27/23
Permit Type: COMMERCIAL MECHANICAL
Project Name: LPG Tank set
Applicant Name: Ferrellgas LP
Applicant Address: 3611 A ST SE
Applicant, City, State, Zip: Auburn
Contact: Joe Girard
Phone: 3606352287
Email:joegirard@ferrellgas.com
Scope of Work: Set LPG tank and dispenser
Valuation: 16000.00
Square Feet: 0
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 09/20/2023
Permit Expires: 03/14/2024
Form Permit Type: COMMERCIAL MECHANICAL
Status: COMPLETE
Assigned To: Kristin Foster
Property
Parcel# Address Legal Description Owner Name Owner Phone Zoning
PAR A OF CITY ARL BLA AMAZON.COM 830 Open Space
31052800100300 16900 51 STAVE NE PROJ FILE NO PLN-439 SERVICES LLC Agriculture RCW
REC AFN 201812055003 84.34
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
Ferrell Gas Joe Girard 360-635-2287 3611 A Street SE CONSTRUCTION COA 601553542
CONTRACTOR
Ferrell Gas Joe Girard 360-635-2287 3611 A Street SE CONSTRUCTION L&I FERRELP055LH
CONTRACTOR
Inspections
Date Inspection Type Description Scheduled Date Completed Date Inspector Status
C 14. Above ground storage tank-
12/15/2023 MECHANICAL 12/19/2023 SafeBuilt Approved
FINAL after 9 am
Plan Reviews
Date Review Type Description Assigned To Review Status
06/28/2023 COMMERCIAL BUILDING Approved
MECHANICAL
Fees
Fee Description Notes Amount
Processing/Technology $25.00
Mechanical Commercial Plan Review Table 4-1 $258.03
Fuel/LPG Installation/Removal $0.00
Credit Card Service $8.49
Total $291.52
Attached Letters
Date Letter Description
09/19/2023 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
09/19/2023 XBP Conf: $283.03
154254587
09/19/2023 154254587 Raelynn Jones $8.49
Outstanding Balance $0.00
Notes
Date Note Created By:
09/20/2023 Emailed the permit for signature Kristin Foster
09/19/2023 Received COA license information Kristin Foster
07/14/2023 Sent a follow up email for the BL Kristin Foster
07/07/2023 Contractor needs COA business license-emailed info. Kristin Foster
07/07/2023 Emailed for an enlarged aerial view with tank location. Kristin Foster
Uploaded Files
Date File Name
09/20/2023 16941145-20230920 BLD5435 IssuedPermit.pdf
07/10/2023 16084684-20230707 BLD5435 AerialView.pdf
06/28/2023 15918912-20230627 BLD5435 Drawing.pdf
06/28/2023 15918913-20230627 BLD54351 App.pdf
06/28/2023 15918914-20230627 BLD5435 AnchorDetail.pdf