HomeMy WebLinkAbout17212 51st Ave Ne Ste 111_BLD5508_2026 GENERAL NOTES REFRIGERANT HVAC LEGENDS HVAC LEGENDS z 0 G1 THESE DRAWINGS ARE DIAGRAMMATIC; THEY DO NOT SHOW EVERY OFFSET, BEND, TEE, OR d ELBOW WHICH MAY BE REQUIRED TO INSTALL WORK IN THE SPACE PROVIDED AND AVOID 1. REFRIGERANT PIPING SHALL CONSISTION OF ACR TYPE L COPPER TUBING WITH LONG RADIUS ROUND DUCTWORK CONFLICTS. THE CONTRACTOR SHALL FOLLOW THE DRAWINGS AS CLOSELY AS IS PRACTICAL WROUGHT COPPER FITTINGS 12"x12' INDICATES UNLINED 12" x 12" SM DUCT TO DO SO AND INSTALL ADDITIONAL BENDS, OFFSETS, TEES, AND ELBOWS WHERE REQUIRED /� GO BY LOCAL CONDITIONS FROM MEASUREMENTS TAKEN AT THE SITE, SUBJECT TO APPROVAL, 2. PURGE REFRIGERANT TUBING WITH NITROGEN GAS WHILE BRAZING WITH MINIMUM 6%SILVER Z LU AND WITHOUT ADDITIONAL COST TO THE OWNER. 90 DEG ELBOW O BRZING ROD (R=1.5xDIA) 12"x12"/W INDICATES UNLINED 12" x 12" SM DUCT GO G2 MECHANICAL SYSTEMS AND MATERIALS SHALL BE IN ACCORDANCE WITH THE FOLLOWING 1.5 x DIA 1.5 x DIA WITH INSULATED WRAP 3. PRIOR TO CHARGING SYSTEM WITH REFRIGERANT, PIPING SYSTEM SHALL BE PRESSURE LU CODES AND LOCAL AMENDMENTS: TESTED AND AND EVACUATED TO A VACUUM OF 500 MICRONS FOR A MINIMUM OF 30 MINUTE PERIOD •2018 INTERNATIONAL BUILDING CODE WITH WASHINGTON STATE AMENDMENTS I FLEXIBLE DUCT MJ 4 INSULATE ALL REFRIGERANT LINES TO MEET THE WASHINGTON STATE ENERGY CODE (SUPPLY/OUTSIDE AIR) / •2018 INTERNATI .ONAL MECHANICAL CODE WITH WASHINGTON STATE AMENDMENTS f Q •2018 INTERNATIONAL FIRE CODE WITH WASHINGTON STATE AMENDMENTS REQUIREMENTS. ALL EXTERIOR INSULATION SHALL BE UV RATED OR COVERED WITH UV 90 DEG ELBOW(DOWN OR •2018 INTERNATIONAL FUEL GAS CODE WITH WASHINGTON STATE AMENDMENTS PROTECTANT BARRIER i�(RETURN) AWAY) -024"4 INDICATES ROUND DUCT •2018 WASHINGTON ENERGY CODE r�(EXHAUST) 10,10 SPIN-IN TAKE-OFF & VOLUME DAMPER WITH G6 INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. RIGID ROUND SM DUCT Z N a r rn G7 ALL TRADES TO LEAVE 30" OR 42" CLEARANCE IN FRONT OF MECHANICAL EQUIPMENT ACCESS PANELS FOR SERVICING, PER NEC REQUIREMENTS. HVAC LEGENDS RISE OR DROP IN DIRECTION OF FLOW G8 PROVIDE MANUAL BALANCING DAMPERS IN ALL FINAL BRANCH DUCTS SERVING INLETS AND OUTLETS, AND AS REQUIRED FOR FULL SYSTEM AIR BALANCING; INSTALL MANUAL 00 00 BALANCING DAMPERS AS FAR FROM INLET OR OUTLET AS PRACTICAL. CYIS CONDENSER WATER SUPPLY 1 A T �(SUPPLY/OUTSIDE AIR) fa1R CONDENSER WATER RETURN DIFFUSER /GRILLE CALLOUT ` GO CD CONDENSATE DRAIN 01�(RETURN) 90 DEG ELBOW(UP OR } G9 DUCTWORK DIMENSIONS INDICATED ARE NET INSIDE DIMENSIONS. RL REFRIGERANT LIQUID TOWARD) . GO Mu MAKE UP WATER (EXHAUST) SIZE OR �� TYPE G10 PROVIDE FIRE SEALANT AT PENETRATIONS OF FIRE RATED ASSEMBLIES; CAULKING OR aS REFRIGERANT SUCTION �` ,,,,—NECK SIZE CD-' 8x8 OTHER ADHESIVE SEALANTS SHALL NOT BE USED TO FILL VOIDS BETWEEN FIRE SPRINKLER 350 CFM w GATE VALVE COVER PLATES AND WALLS OR CEILINGS. 45 DEG ELBOW AIRFLOW--""' LU G11 CONTRACTOR SHALL VERIFY THAT ALL EQUIPMENT, AS SHOWN ON THESE DRAWINGS, WILL PRESSURE REDUCING NOT CONFLICT WITH ANY DRAINS, SCUTTLES, JOINTS, VENTS, ETC. VALVE 1.5 x DIA 1.5 x DIA + a Z `qa L U G12 ALL ONTSIDE AI PNTAKES SVHALL ENT,BE A MINIMUM OF 10'-0" FROM ANY EXHAUST Iol BALL VALVE ~ CHECK VALVE RECTANGULAR DUCTWORK < LU U HVAC ABBREVIATIONS % G13 VERIFY ALL WARRANTIES ON EQUIPMENT INSTALLED. 90 DEG ELBOW WITH GAS COCK THREE WAY VALVE 44 TURNING VANES G14 COORDINATE ALL DUCT AND AIR TERMINAL LOCATIONS WITH CEILING PLAN AND LIGHTING %P.G. PERCENT PROPYLENE GLYCOL HP HORSEPOWER LAYOUTS AS REQUIRED. DOUBLE REDUCED PRESSURE Z� CHECK VALVE ASSEMBLY RPBP BACKFLOW PREVENTER /CW CERAMIC WRAP HWR HEATING WATER RETURN G15 COORDINATE ALL REQUIRED OPENINGS AND EXCAVATIONS. ALL REQUIRED OPENINGS IN /PERE WITH INTERIOR PERFORATED METAL LINER HWS HEATING WATER SUPPLY FOUNDATIONS, FLOORS, WALLS AND ROOFS SHALL BE DESIGNED INTO THE STRUCTURE /SL SOUND/ACUSTICAL LINED ID INSIDE DIMENSION INITIALLY BY THE USE OF SLEEVES, CURBS, ETC. CUTTING AND PATCHING SHALL BE HELD 90 DEG ELBOW DOWN OR /W WRAPPED (INSULATED) DUCT INSUL. INSULATION TO A MINIMUM. I�"�-/--,���♦ AWAY AFF ABOVE FINISHED FLOOR KW KILOWATT G16 TRANSITION ALL DUCTS AS REQUIRED TO ATTACH TO EQUIPMENT CONNECTIONS. HVAC LEGENDS VVI T (W/ TURNING VANES) APP ACCESS PANEL LAT LEAVING AIR TEMPERAURE BDD BACKDRAFT DAMPER LPG LIQUIFIED PROPANE G17 OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL HAVE A MAXIMUM LEAKAGE RATE THAT DETAIL SYMBOL BHP BRAKE HORSE POWER LWT LEAVING AIR TEMPERATURE COMPLIES WITH THE WASHINGTON STATE ENERGY CODE. e G7 GENERAL NOTE - APPLIES TO BOD BOTTOM OF DUCT M MEZZANINE r A-IDENTIFYING NUMBER BOU BOTTOM OF UNIT MET THOUSANDS BTU PER HOUR g ALL DRAWINGS �® BTU BRITISH THERMAL UNIT MCA MINIMUM CIRCUIT AMPANCITY c7 G18 PROVIDE PIPE MARKERS IN ACCORDANCE WITH ASME 13.1 SCHEME FOR THE IDENTIFICATION B-SHEET WHERE DETAIL IS SHOWN OF PIPING SYSTEMS; BRADY, SETON, OR EQUAL. O1 DETAIL NOTE - APPLIES ONLY �I—I 90 DEG ELBOW UP OR C.C. CONTROL CONTRATOR MHP MOTOR HORSEPOWER m TO SPECIFIC DETAIL _II { TOWARD �� CBBDD COUNTER BALANCE BACKDRAFT DAMPER MOP MAXIMUM OVER-CURRENT PROTECTION G19 HEAT AND COOLING LOAD CALCULATIONS, EQUIPMENT SIZING, AND DUCT LAYOUT TO ELEVATION OR SECTION SYMBOL c�u (W/ TURNING VANES) CFM CUBIC FEET PER MINUTE NA, N A NOT APPLICABLE COMPLY WITH ASHRAE HANDBOOKS. A POINT OF CONNECTION / 8 A-IDENTIFYING NUMBER � t—® CO CARBON MONOXIDE NC NORMALLY CLOSED G20 FURNISH ALL ACCESS PANELS. MOST ACCESS PANELS WILL BE COORDINATED WITH B-SHEET WHERE DETAIL IS SHOWN HWR CHILLED WATER RETURN NIC NOT IN CONTRACT ARCHITECT. SOME OR ALL ACCESS PANELS MAY NOT APPEAR ON THE ARCHITECTURAL CHWS CHILLED WATER SUPPLY NO NORMALLY OPEN DRAWINGS. ARCHITECT SHALL DETERMINE WHICH ACCESS PANELS REQUIRE FIRE RATING. A CKTS CIRCUITS NOM NOMINAL ONUMBERED KEYED NOTE. MISCELLANEOUS HVAC CLG CEILING NTS NOT TO SCLAE G21 STRUCTURAL UNIT SENGINE R AND C TOO DETERMINE NS HAVE B BUILDINGEEN STRUCTDINATES ALWITHADEQUACY, I ARCHITECT F IT IS APPLIES TO KEYED ITEM IN SYMBOLS COP COEFFICIENT OF PERFORMACE CA OUTSIDE AIR NECESSARY TO RELOCATE A UNIT, NOTIFY DK SYSTEMS DESIGN DEPARTMENT FOR THE DRAWING CONTAINING THE NOTE ONLY D DOWN OBD OPPOSED BLADE DAMPER RE-COORDINATION. VAV MECHANICAL EQUIPMENT TAG DID DRY BUILB OSA OUTSIDE AIR t SUPPLY DIFFUSER /GRILLE (FLOW ARROWS DIA DIAMETER P.G. PROPYLENE GLYCOL ® INDICATE DIRECTION OF BLOW. IF NO ARROWS DIN DOWN PH PHASE ARE SHOWN, DIFFUSER IS 4-WAY BLOW.) DP DIFFERENTIAL PRESSURE POC POINT OF CONNECITON PIPE DOWN PIPE UP E.C. ELECTRICAL CONTRACTOR P/T PRESSURE TEMPERATURE PORT METAL 1 T BRANCH OFF RETURN GRILLE EA EACH /EXHAUST AIR PRESS PRESSURE PIPE RISE OR T SHEET M E TA L NOTES DROP � BOTTOM/TOP EAT ENTERING AIR TEMPERATURE PRV PRESSURE REDUCING VALVE EER ENERGY EFFICEINCY RATIO PSI POUNDS PER SQUARE INCH PIPE TEE EXHAUST GRILLE ESP EXTERNAL STATIC PRESSURE PSIG POUNDS PER SQUARE INCH GAUGE PIPE UNION �� DOWN/UP EWT ENTERING WATER TEMPERATURE R RISE F.P.I. FINS PER INCH RA RETURN AIR 1. DUCT SIZES INDICATED ON THE DRAWINGS ARE INSIDE DIMENSIONS. DUCT SIZE SHALL BE PIPE REDUCER PIPE COUPLING SIDEWALL GRILLE FC FLEX CONNECTOR RM ROOM PERMIT INCREASED TO COMPENSATE FOR ACOUSTICAL DUCT LINER THICKNESS. FD FIRE DAMPER RPM REVOLUTIONS PER MINUTE 2. DUCT ELBOWS SHALL BE RADIUS TYPE WITH FULL WIDTH THROAT RADIUS ON ALL PRIMARY SUPPLY AIR FLOW ARROW FEE FINISHED FLOOR ELEVATION SA SUPPLY AIR SET DUCT FLA FULL LOAD AMPERAGE SF SQUARE FOOT THICKNESS TURNING VANOESN OTHERWISE. TURNING INSTALLED IN EVERY RAILNTABLBOWS SHALL HAVE DOUBLE HVAC LEGENDS �'r RETURN OR ARROW EXHAUST AIR FLOW FOB FLAT ON BOTTOM SD SMOKE DETECTOR FOT FLAT ON TOP SEER SEASONAL ENERGY EFFICIENCY RATIO 3. EXHAUST DUCTWORK SHALL BE UNLINED GALVANIZED SHEET METAL (UNLESS OTHERWISE G.C. GENERAL CONTRACTOR TIED TO BE DETERIMED INDICATED). ELBOWS SHALL BE CONSTRUCTED WITH A MINIMUM CENTERLINE RADIUS TO DUCT G NATURAL GAS SP STATIC PRESSURE DIAMETER OF 1.0. DUCT SHALL BE UNINSULATED UNLESS OTHERWISE INDICATED. DRYER MANUAL VOLUME DAMPER DUCTWORK TRANSITIONS GPM GALLONS PER MINUTE T-STAT THERMOSTAT EXHAUST DUCT SHALL NOT BE JOINED WITH SCREWS OR OTHER FASTENERS THAT PROTRUDE GYP. GYPSUM (SHEETROCK) TSP TOTAL STATIC PRESSURE MORE THEN 1/8" INTO THE INSIDE OF THE DUCT. FABRICATE AND SEAL EXHAUST DUCTWORK TYP. TYPICAL Z PER SMACNA 1/2" PRESSURE CLASS MOTORIZED DAMPER SQUARE TO SQUARE OR ROUND TO ROUND _O 4. ALL DUCTWORK SHALL BE SEALED WITH WATER BASED LATEX SEALANT PER WSEC AND Eu rn SMACNA PRESSURE AND SEAL CLASSIFICATION BELOW: BACK DRAFT DAMPER ANGLE 30° a STATIC PRESSURE CONSTRUCTION CLASS SEAL CLASS SEALING REQUIREMENTS SMOKE DETECTOR OR LESS �MM 1/2" - 2" wg C TRANSVERSE JOINTS ONLY co j 3" wg B TRANSVERSE JOINTS AND SQUARE TO ROUND 2--�-t jU LONGITUDINAL SEAMS FIRE DAMPER (1-1/2 HOUR) OUT OF AIRSTREAM SHEET INDEX LL 4" - 10' w9 A ALL JOINTS, SEAMS, AND WALL RUSKIN MODEL DIB2 STYLE B, VERTICAL MOUNT PENETRATIONS SQUARE ''^^ FIRE DAMPER (1-1/2 HOUR) OUT OF AIRSTREAM DUCT VJ M RUSKIN MODEL DIB2 STYLE B, HORIZONTAL MOUNT N 5. THROUGH PENETRATION AND MEMBRANE PENETRATION FIRE STOP AS REQUIRED IN THE IBC ROUND a`� E SHALL BE PROVIDED AND INSTALLED BY THE MECHANICAL CONTRACTOR. FIRE STOP SYSTEM 3 HR FIRE DAMPER (3 HOUR) OUT OF AIRSTREAM DUCT a 0 N SHALL BE HILTI CP 601 S OR 3M BRAND FIRE BARRIER SEALANT IC 15WB+ OR APPROVED RUSKIN MODEL DIB2 STYLE B, VERTICAL MOUNT > Ll.i 00 0 EQUIVALENT. SHEETNUMBER SHEETTIILE W Z 0) 3 HR FIRE DAMPER (3 HOUR) OUT OF AIRSTREAM M0.00 MECHANICAL COVERSHEET Q 6. ACCESSORIES: RUSKIN MODEL DIB2 STYLE B, HORIZONTAL MOUNT MISCELLANEOUS CONTROLS > rn M0.01 MECHANICALCODE ACUSTICAL LINER INDOORS: BACK DRAFT DAMPER THERMOSTAT OR M0.02 MECHANICAL SCHEDULES Q 0 1" THICK, FIBERGLASS DUCTLINER WITH BLACK MAT FACING. JOHNS MANVILLE, LINACOUSTIC RUSKIN MODEL BD2/A1, LOCAL VELOCITY<1500 FPM a HUMIDISTAT OH U AV-1 TEMPERATURE SENSOR w/ M1.01 MECHANICAL SITE PLAN Z RC. BACK DRAFT DAMPER CONTROLLED UNIT ICI M2.00 MECHANICAL ME27ANINE CEILING PLAN C (/� 0 j (MINIMUM INSTALLED R-VALUE TO BE PER WSEC) RUSKIN MODEL BD2/A2, LOCAL VELOCITY<2500 FPM 4 SOLENOID ACTUATOR MOTOR ACTUATOR ITI C M2.01 MECHANICAL ROOF LEVEL PLAN 0 0 ACOUSTICAL LINER OUTDOORS: 2" THICK, FIBERGLASS DUCTLINER WITH BLACK MAT FACING. M3.00 MECHANICAL DETAILS N Z y JOHNS MANVILLE, LINACOUSTIC RC. (MINIMUM INSTALLED R-VALUE TO BE PER WSEC) SMOKE DAMPER ® SMOKE DETECTOR REMOTE SENSOR (� M3.01 MECHANICAL DETAILS ' J M4.00 MECHANICAL LOAD CALCULATION LOW PRESSURE INSULATED FLEX DUCT: HART& COOLEY F-114, JPL PR-25, OR EQUAL. TOTAL 9 0 0 0 0 O Q COMBINATION SMOKE AND FIRE DAMPER UNINSULATED VAPOR PROOF FLEX DUCT: THERMAFLEX S-LP. 12"x12" INDICATES 14" x 14" O.D. SHEETMETAL WITH Last Revision Date: DUCT INSULATION (INDOORS): REFLECTIX R-4.2 DUCT INSULATION 1" SOUNDLINER (U.N.O.), 12" x 12" NET ID 7/25/2023 i DUCT INSULATION (OUTDOORS): RELECTIX R-8.0 DUCT INSULATION DwE—D BY. --: a K.K K.D a MECHANICAL D COVERSHEET SCALE, INTS M0.00 WASHINGTON ENERGY CODE NOTES WASHINGTON ENERGY CODE NOTES WASHINGTON ENERGY CODE NOTES WASHINGTON ENERGY CODE NOTES z 0 C403.2 SYSTEM DESIGN. MECHANICAL SYSTEMS SHALL BE DESIGNED TO COMPLY WITH SECTIONS EXCEPTION: THE USE OF MIXED AIR TEMPERATURE LIMIT CONTROL SHALL BE TOW UO3•� d C403.2.1 AND C403.2.2. WHERE ELEMENTS OF A BUILDINGS MECHANICAL SYSTEMS ARE EXCEPTIONS: PERMITTED FOR SYSTEMS THAT ARE BOTH Fur Contra ADDRESSED IN SECTIONS C403.3 THROUGH C403.13, SUCH ELEMENTS SHALL COMPLY WITH 1. CONTROL OF HEATING OR COOLING PROVIDED BY TRANSFER AIR THAT WOULD OTHERWISE cy CONTROLLED FROM SPACE TEMPERATURE (SUCH AS SINGLE ZONE SYSTEMS) AND tears sy.rm c•.51•b aUarwul U THE APPLICABLE PROVISIONS OF THOSE SECTIONS. BE EXHAUSTED, HAVING COOLING CAPACITY LESS THAN 65,000 BTU/H. TW sQ` t�•a Z 0) 2. VESTIBULE HEATING ONLY SYSTEMS ARE PERMITTED TO BE CONTROLLED WITHOUT AN ILL! C403.2.2 VENTILATION AND EXHAUST. OUTDOOR AIR TEMPERATURE LOCKOUT WHEN CONTROLLED BY A THERMOSTAT LOCATED IN O 0403.5.3.3 HIGH-LIMIT SHUTOFF. AIR ECONOMIZERS SHALL BE CONFIGURED TO AUTOMATICALLY z•z.sso m•n C403.2.2.1 VENTILATION, VENTILATION, EITHER NATURAL OR MECHANICAL, SHALL BE THE VESTIBULE CONFIGURED TO LIMIT HEATING TO A TEMPERATURE NOT GREATER THAN REDUCE OUTDOOR AIR INTAKE TO THE DESIGN MINIMUM OUTDOOR AIR QUANTITY WHEN a+•e..•r.Mo U PROVIDED IN ACCORDANCE WITH CHAPTER 4 OF THE INTERNATIONAL MECHANICAL CODE. 45°F(7°C) WHERE REQUIRED FOR FREEZE PROTECTION OF PIPING AND SPRINKLER HEADS OUTDOOR AIR INTAKE WILL NO LONGER REDUCE COOLING ENERGY USAGE. HIGH-LIMIT ��row zip W WHERE MECHANICAL VENTILATION IS PROVIDED, THE SYSTEM SHALL BE CONFIGURED TO LOCATED IN THE VESTIBULE, SHUTOFF CONTROL TYPES SHALL BE CHOSEN FROM TABLE C403.5.3.3. HIGH-LIMIT SHUTOFF 10� PROVIDE NO GREATER THAN 150 PERCENT OF THE MINIMUM OUTDOOR AIR REQUIRED BY CONTROL SETTINGS FOR THESE CONTROL TYPES SHALL BE THOSE SPECIFIED IN TABLE C403.10 CONSTRUCTION OF HVAC SYSTEM ELEMENTS. DUCTS, PLENUMS, PIPING AND OTHER CHAPTER 4 OF THE INTERNATIONAL MECHANICAL CODE OR OTHER APPLICABLE CODE OR C403.4.1.5 HOT WATER BOILER OUTDOOR TEMPERATURE SETBACK CONTROL. HOT WATER BOILERS C403.5.3.3 ELEMENTS THAT ARE PART OF AN HVAC SYSTEM SHALL BE CONSTRUCTED AND INSULATED IL STANDARD, WHICHEVER IS GREATER. THAT SUPPLY HEAT TO THE BUILDING THROUGH ONE- OR TWO-PIPE HEATING SYSTEMS IN ACCORDANCE WITH SECTIONS C403.10.1 THROUGH C403.10.3.1 Q SHALL HAVE AN OUTDOOR SETBACK CONTROL THAT LOWERS THE BOILER WATER C403.5.3.4 RELIEF OF EXCESS OUTDOOR AIR. SYSTEMS SHALL BE CAPABLE OF RELIEVING C403 3 EQUIPMENT SELECTION. HEATING AND COOLING EQUIPMENT INSTALLED IN MECHANICAL TEMPERATURE BASED ON THE OUTDOOR TEMPERATURE. EXCESS OUTDOOR AIR DURING AIR ECONOMIZER OPERATION TO PREVENT C403.10.1 DUCT AND PLENUM INSULATION AND SEALING. SYSTEMS SHALL BE SIZED IN ACCORDANCE WITH SECTION C403.3.1 AND SHALL BE NOT OVER-PRESSURIZING THE BUILDING. THE RELIEF AIR OUTLET SHALL BE LOCATED TO AVOID C403.10.1.1 DUCTS CONVEYING OUTDOOR AIR. DUCTS, SHAFTS AND PLENUMS CONVEYING LESS EFFICIENT IN THE USE OF ENERGY THAN AS SPECIFIED IN SECTION C403.3.2. C403.4.1.6 DOOR SWITCHES FOR HVAC SYSTEM THERMOSTATIC CONTROL. DOORS THAT OPEN TO RECIRCULATION INTO THE BUILDING. OUTDOOR AIR FROM THE EXTERIOR OF THE BUILDING TO THE MECHANICAL SYSTEM SHALL O N a h rn THE OUTDOORS FROM A CONDITIONED SPACE MUST HAVE CONTROLS CONFIGURED TO DO MEET ALL AIR LEAKAGE AND BUILDING ENVELOPE INSULATIONREQUIREMENTS OF SECTION Z C403.3.1 EQUIPMENT AND SYSTEM SIZING. THE OUTPUT CAPACITY OF HEATING AND THE FOLLOWING ONCE DOORS HAVE BEEN OPEN FOR 5 MINUTES: C403.5.3.5 ECONOMIZER DAMPERS. RETURN, EXHAUST/RELIEF AND OUTDOOR AIR DAMPERS USED C402, PLUS BUILDING ENVELOPE VAPOR CONTROL REQUIREMENTS FROM THE INTERNATIONAL COOLING EQUIPMENT SHALL BE NOT GREATER THAN THAT OF THE SMALLEST AVAILABLE 1. DISABLE THE MECHANICAL HEATING TO THE ZONE OR RESET THE SPACE HEATING IN ECONOMIZERS SHALL COMPLY WITH SECTION EXHAUST/RELIEF BUILDING CODE, EXTENDING CONTINUOUSLY FROM THE BUILDING EXTERIOR TO AN EQUIPMENT SIZE THAT EXCEEDS THE LOADS CALCULATED IN ACCORDANCE WITH SECTION TEMPERATURE SET POINT TO 55 'F OR LESS WITHIN 5 MINUTES OF THE DOOR OPEN AUTOMATIC SHUTOFF DAMPER OR HEATING OR COOLING EQUIPMENT. FOR THE PURPOSES C403.1.2. A SINGLE PIECE OF EQUIPMENT PROVIDING BOTH HEATING AND COOLING SHALL ENABLE SIGNAL. OF BUILDING ENVELOPE INSULATION REQUIREMENTS, DUCT SURFACES SHALL BE C403.5.5 ECONOMIZER FAULT DETECTION AND DIAGNOSTICS (FDD). AIR-COOLED UNITARY SATISFY THIS PROVISION FOR ONE FUNCTION WITH THE CAPACITY FOR THE OTHER 2. DISABLE THE MECHANICAL COOLING TO THE ZONE OR RESET THE SPACE COOLING INSULATED WITH THE MINIMUM INSULATION VALUES IN TABLE C403.10.1.1. DUCT SURFACES � FUNCTION AS SMALL AS POSSIBLE, WITHIN AVAILABLE EQUIPMENT OPTIONS. TEMPERATURE SET POINT TO 85 'F OR MORE WITHIN 5 MINUTES OF THE DOOR OPEN DIRECT-EXPANSION UNITS WITH A COOLING CAPACITY OF 54,000 BTU/H OR GREATER INCLUDED AS PART OF THE BUILDING ENVELOPE SHALL NOT BE USED IN THE CALCULATION � ENABLE SIGNAL. LISTED IN TABLES C403.3.2(1) THROUGH C403.3.2(3) THAT ARE EQUIPPED WITH AN OF MAXIMUM GLAZING AREA AS DESCRIBED IN SECTION C402.4.1. oy EXCEPTIONS: ECONOMIZER IN ACCORDANCE WITH SECTION C403.5 SHALL INCLUDE A FAULT DETECTION 1. REQUIRED STANDBY EQUIPMENT AND SYSTEMS PROVIDED WITH CONTROLS AND DEVICES EXCEPTIONS: AND DIAGNOSTICS (FDD) SYSTEM. EXCEPTIONS: U) THAT ALLOW SUCH SYSTEMS OR EQUIPMENT TO OPERATE AUTOMATICALLY ONLY WHEN THE 1. BUILDING ENTRANCES WITH VESTIBULES. 1. OUTDOOR AIR DUCTS SERVING INDIVIDUAL SUPPLY AIR UNITS WITH LESS THAN 2,800 CFM . U) PRIMARY EQUIPMENT IS NOT OPERATING. 2. ALTERATIONS TO EXISTING BUILDINGS. C403.7 VENTILATION AND EXHAUST SYSTEMS. IN ADDITION TO OTHER REQUIREMENTS OF SECTION OF TOTAL SUPPLY AIR CAPACITY, PROVIDED THESE ARE INSULATED TO THE MINIMUM 2. MULTIPLE UNITS OF THE SAME EQUIPMENT TYPE WITH COMBINED CAPACITIES EXCEEDING 3. LOADING DOCKS. C403 APPLICABLE TO THE PROVISIONS OF VENTILATION AIR OR THE EXHAUST OF AIR, INSULATION VALUES IN TABLE C403.10.1.1. THE DESIGN LOAD AND PROVIDED WITH CONTROLS THAT ARE CONFIGURED TO SEQUENCE VENTILATION AND EXHAUST SYSTEMS SHALL BE IN ACCORDANCE WITH SECTIONS C403.7.1 2. UNHEATED EQUIPMENT ROOMS WITH COMBUSTION AIR LOUVERS, PROVIDED THEY ARE THE OPERATION OF EACH UNIT BASED ON LOAD. C403.4.2 OFF-HOUR CONTROLS. FOR ALL OCCUPANCIES OTHER THAN GROUP R, EACH ZONE THROUGH C403.7.8. ISOLATED FROM CONDITIONED SPACE AT SIDES, TOP AND BOTTOM OF THE ROOM WITH R-11 W SHALL BE PROVIDED WITH THERMOSTATIC SETBACK CONTROLS THAT ARE CONTROLLED BY NOMINAL INSULATION. m C403.3.2 HVAC EQUIPMENT PERFORMANCE REQUIREMENTS. EQUIPMENT SHALL MEET THE MINIMUM EITHER AN AUTOMATIC TIME CLOCK OR PROGRAMMABLE CONTROL SYSTEM. C403.7.8 SHUTOFF DAMPERS. MECHANICAL OPENINGS SHALL BE PROVIDED WITH SHUTOFF EFFICIENCY REQUIREMENTS OF TABLES C403.3.2(1) THROUGH C403.3.2(12) WHEN TESTED DAMPERS IN ACCORDANCE WITH SECTIONS C403.7.8.1 THROUGH C403.7.8.4. AND RATED IN ACCORDANCE WITH THE APPLICABLE TEST PROCEDURE. PLATE-TYPE C403.4.2.1 THERMOSTATIC SETBACK. THERMOSTATIC SETBACK CONTROLS SHALL BE CONFIGURED o Z LIQUID-TO-LIQUID HEAT EXCHANGERS SHALL MEET THE MINIMUM REQUIREMENTS OF TABLE TO SET BACK OR TEMPORARILY OPERATE THE SYSTEM TO MAINTAIN ZONE TEMPERATURES C403.7.8.1 SHUTOFF DAMPERS FOR BUILDING ISOLATION. OUTDOOR AIR SUPPLY, EXHAUST rm rr. ILL!C403.3.2(10). DOWN TO 55-F (13'C) OR UP TO 85-F (29'C). OPENINGS AND RELIEF OUTLETS AND STAIRWAY AND ELEVATOR HOISTWAY SHAFT VENTS ^"' °" •, Q Z SHALL BE PROVIDED WITH CLASS I MOTORIZED DAMPERS. SEE SECTIONS C403.10.1 AND W GAS-FIRED AND OIL-FIRED FORCED AIR FURNACES WITH INPUT RATINGS OF 225,000 C403.4.2.2 AUTOMATIC SETBACK AND SHUTDOWN. AUTOMATIC TIME CLOCK OR PROGRAMMABLE C403.10.2 FOR DUCTWORK INSULATION REQUIREMENTS UPSTREAM AND DOWNSTREAM OF ,..w „. < U BTU/H (65 KW) OR GREATER AND ALL UNIT HEATERS SHALL ALSO HAVE AN INTERMITTENT CONTROLS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR SEVEN THE SHUTOFF DAMPER. ,�, J IGNITION OR INTERRUPTED DEVICE (IID), AND HAVE EITHER MECHANICAL DRAFT(INCLUDING DIFFERENT DAILY SCHEDULES PER WEEK AND RETAINING THEIR PROGRAMMING AND TIME EXCEPTIONS: SETTING DURING A LOSS OF POWER FOR AT LEAST 10 HOURS. ADDITIONALLY, THE 1. GRAVITY(NONMOTORIZED) DAMPERS SHALL BE PERMITTED IN LIEU OF MOTORIZED DAMPERS POWER VENTING) OR A FLUE DAMPER. A VENT DAMPER IS AN ACCEPTABLE ALTERNATIVE CONTROLS SHALL HAVE A MANUAL OVERRIDE THAT ALLOWS TEMPORARY OPERATION OF AS FOLLOWS: TO A FLUE DAMPER FOR FURNACES WHERE COMBUSTION AIR IS DRAWN FROM THE THE SYSTEM FOR UP TO 2 HOURS; A MANUALLY OPERATED TIMER CONFIGURED TO 1.1. RELIEF DAMPERS SERVING SYSTEMS LESS THAN 5,000 CFM TOTAL SUPPLY SHALL BEiea CONDITIONED SPACE. ALL FURNACES WITH INPUT RATINGS OF LOCATED 0 BTU/H (65 KW) OR OPERATE THE SYSTEM FOR UP TO 2 HOURS; OR AN OCCUPANCY SENSOR. PERMITTED IN BUILDINGS LESS THAN THREE STORIES IN HEIGHT. GREATER, INCLUDING ELECTRIC FURNACES, THAT ARE NOT LOCATED WITHIN THE 1.2. GRAVITY(NONMOTORIZED) DAMPERS WHERE THE DESIGN OUTDOOR AIR INTAKE OR EXHAUST CONDITIONED SPACE SHALL HAVE JACKET LOSSES NOT EXCEEDING 0.75 PERCENT OF THE C403.4.2.3 AUTOMATIC START AND STOP. AUTOMATIC START AND STOP CONTROLS SHALL BE CAPACITY DOES NOT EXCEED 400 CFM (189 L/S). C403.10.1.2 OTHER SUPPLY AND RETURN DUCTS. ALL OTHER SUPPLY AND RETURN AIR DUCTS INPUT RATING. AND PLENUMS SHALL BE INSULATED WITH A MINIMUM OF R-6 INSULATION WHERE LOCATED IN PROVIDED FOR EACH HVAC SYSTEM. THE AUTOMATIC START CONTROLS SHALL BE 1.3. SYSTEMS SERVING AREAS WHICH REQUIRE CONTINUOUS OPERATION FOR 24/7 OCCUPANCY UNCONDITIONED SPACES, AND WHERE LOCATED OUTSIDE THE BUILDING WITH A MINIMUM OF R-8 C403.4 HVAC SYSTEM CONTROLS. HVAC SYSTEMS SHALL BE PROVIDED WITH CONTROLS IN CONFIGURED ORDER TO BRING AUTOMATICALLY ADJUST THE DAILY START TIMEG EACH SPACE TO THE DESIRED OCCUPIED TEMPERATURE IMMEDIATELY THE HVAC SYSTEM IN SCHEDULES. INSULATION IN CLIMATE ZONE 4 AND R-12 INSULATION IN CLIMATE ZONE 5. WHERE LOCATED N ACCORDANCE WITH SECTIONS C403.4.1 THROUGH C403.4.11 AND SHALL BE CAPABLE OF WITHIN A BUILDING ENVELOPE ASSEMBLY, THE DUCT OR PLENUM SHALL BE SEPARATED FROM PRIOR TO SCHEDULED OCCUPANCY. THE AUTOMATIC STOP CONTROLS SHALL BE 2. SHUTOFF DAMPERS ARE NOT REQUIRED IN: AND CONFIGURED TO IMPLEMENT ALL REQUIRED CONTROL FUNCTIONS IN THIS CODE. THE BUILDING EXTERIOR UNCONDITIONED EXEMPT SPACES BY MINIMUM INSULATION VALUE CONFIGURED TO REDUCE THE HVAC SYSTEMS HEATING TEMPERATURE SET POINT AND 2.1. COMBUSTION AIR INTAKES. AS REQUIRED FOR EXTERIOR WALLS BY SECTION C402.1.3. C403.4.1 THERMOSTATIC CONTROLS. THE SUPPLY OF HEATING AND COOLING ENERGY TO INCREASE THE COOLING TEMPERATURE SET POINT BY AT LEAST 2°F(1.1°C) BEFORE 2.2. SYSTEMS SERVING AREAS WHICH REQUIRE CONTINUOUS OPERATION IN ANIMAL HOSPITALS, EACH ZONE SHALL BE CONTROLLED BY SCHEDULED UNOCCUPIED PERIODS BASED UPON THE THERMAL LAG AND ACCEPTABLE DRIFT KENNELS AND POUNDS, LABORATORIES, AND GROUP H, I AND R OCCUPANCIES. r : RESPONDING TO TEMPERATURE WITHIN THHEE INDIVIDUAL THERMOSTATIC CONTROLS CAPABLE OF ZONE. CONTROLS IN THE SAME ZONE OR IN IN SPACE TEMPERATURE THAT IS WITHIN COMFORT LI EXCEPTIONS MITS. AT A MINIMUM, THE CONTROLS 2.3. SUBDUCT EXHAUST SYSTEMS OR OTHER SYSTEMS THAT ARE REQUIRED TO OPERATE rn SHALL BE A FUNCTION OF THE SPACE TEMPERATURE, OCCUPIED AND UNOCCUPIED CONTINUOUSLY BY THE INTERNATIONAL MECHANICAL CODE. M NEIGHBORING ZONES CONNECTED BY OPENINGS LARGER THAN 10 PERCENT OF THE FLOOR 1. WHERE LOCATED WITHIN EQUIPMENT. AREA OF EITHER ZONE SHALL NOT ALLOW FOR SIMULTANEOUS HEATING AND COOLING. AT TEMPERATURES, AND THE AMOUNT OF TIME PRIOR TO SCHEDULED OCCUPANCY. 2.4. TYPE I GREASE EXHAUST SYSTEMS OR OTHER SYSTEMS WHERE DAMPERS ARE PROHIBITED 2. SUPPLY AND RETURN DUCTWORK LOCATED IN UNCONDITIONED SPACES WHERE THE DESIGN BY THE INTERNATIONAL MECHANICAL CODE TO BE IN THE AIRSTREAM. co A MINIMUM, EACH FLOOR OF A BUILDING SHALL BE CONSIDERED AS A SEPARATE ZONE. TEMPERATURE DIFFERENCE BETWEEN THE INTERIOR AND EXTERIOR OF THE DUCT OR PLENUM C403.4.2.4 EXHAUST SYSTEM OFF-HOUR CONTROLS. FOR ALL OCCUPANCIES OTHER THAN GROUP 2.5. UNCONDITIONED STAIRWELLS OR UNCONDITIONED ELEVATOR HOISTWAY SHAFTS THAT ARE DOES NOT EXCEED 15°F 8'C AND INSULATED IN ACCORDANCE WITH TABLE C403.10.1.2. CONTROLS ON SYSTEMS REQUIRED TO HAVE ECONOMIZERS AND SERVING SINGLE ZONES ( ) SHALL HAVE MULTIPLE COOLING STAGE CAPABILITY AND ACTIVATE THE ECONOMIZER WHEN R, EXHAUST SYSTEMS SERVING SPACES WITHIN THE CONDITIONED ENVELOPE SHALL BE ONLY CONNECTED TO UNCONDITIONED SPACES.CECON MI SHUTOFF DAMPERS FOR RETURN WHERE LOCATED WITHIN CONDITIONED SPACE, SUPPLY DUCTS WHICH CONVEY SUPPLY AIR AT APPROPRIATE AS THE FIRST STAGE H COOLING. SEE SECTION DIFICA FOR FURTHER CONTROLLED BY EITHER AN AUTOMATIC TIME CLOCK, THERMOSTATIC CONTROLS E AIR. RETURN AIR OPENINGS USED FOR AIRSIDE ECONOMIZER OPERATION SHALL BE TEMPERATURES LESS THAN 55°F OR GREATER THAN 105°F SHALL BE INSULATED WITH A MINIMUM ECONOMIZER REQUIREMENTS. WHERE HUMIDIFICATION OR DEHUMIDIFICATION FOR BOTH IS PROGRAMMABLE CONTROL SYSTEM TO OPERATE ON THE SAME SCHEDULE AS THE HVAC EQUIPPED WITH CLASS MOTORIZED DAMPERS. INSULATION R-VALUE IN ACCORDANCE WITH TABLE C403.10.1.2. PROVIDED, AT LEAST ONE HUMIDITY CONTROL DEVICE SHALL BE PROVIDED FOR EACH SYSTEMS PROVIDING THEIR MAKE-UP AIR. HUMIDITY CONTROL SYSTEM. 0403.7.8.3 DAMPER LEAKAGE RATING. CLASS I DAMPERS SHALL HAVE A MAXIMUM LEAKAGE EXCEPTION: DUCTWORK EXPOSED TO VIEW WITHIN A ZONE THAT SERVES THAT ZONE IS NOT EXCEPTIONS: RATE OF 4 CFM/FT2 (20.3 L/S X M2) AT 1.0 INCH WATER GAUGE (W.G.) (249 PA) WHEN EXCEPTIONS: TESTED IN ACCORDANCE WITH AMCA 500D AND SHALL BE LABELED BY AN APPROVED REQUIRED TO BE INSULATED. 1. EXHAUST SYSTEMS REQUIRING CONTINUOUS OPERATION. AGENCY FOR SUCH PURPOSE. GRAVITY(NONMOTORIZED) DAMPERS SHALL HAVE AN AIR 2 EXHAUST SYSTEMS THAT ARE CONTROLLED BY OCCUPANCY SENSOR CONTROL CONFIGURED WHERE LOCATED WITHIN CONDITIONED SPACE, RETURN OR EXHAUST AIR DUCTS THAT CONVEY . 1. INDEPENDENT PERIMETER SYSTEMS THAT ARE DESIGNED TO OFFSET ONLY BUILDING LEAKAGE RATE NOT GREATER THAN 20 CFM/FT2 WHERE NOT LESS THAN 24 INCHES (610 RETURN OR EX WITH AIR DOWNSTREAM OF ENERGY RECOVERY MEDIA SHALL BE INSULATED ENVELOPE HEAT LOSSES OR GAINS OR BOTH SERVING ONE OR MORE PERIMETER ZONES WITH AUTOMATIC ON AND AUTOMATIC SHUTOFF WITHIN 15 MINUTES AFTER OCCUPANTS MM) IN EITHER DIMENSION AND 40 CFM/FT2 WHERE LESS THAN 24 INCHES IN EITHER WITH A MINIMUM R-VALUE IN ACCORDANCE WITH TABLE C403.10.1.2. ALSO SERVED BY AN INTERIOR SYSTEM PROVIDED: HAVE LEFT THE SPACE. DIMENSION. THE RATE OF AIR LEAKAGE SHALL BE DETERMINED AT 1.0 INCH W.G. (249 PA) ALL DUCTS, AIR HANDLERS, AND FILTER BOXES SHALL BE SEALED. JOINTS AND SEAMS SHALL 1.1. THE PERIMETER SYSTEM INCLUDES AT LEAST ONE THERMOSTATIC CONTROL ZONE FOR EACH C403.4.11 DIRECT DIGITAL CONTROL SYSTEMS. DIRECT DIGITAL CONTROL (DDC) SHALL BE WHEN TESTED IN ACCORDANCE WITH AMCA 500D FOR SUCH PURPOSE. THE DAMPER SHALL COMPLY WITH SECTION 603.9 OF THE INTERNATIONAL MECHANICAL CODE BUILDING EXPOSURE HAVING EXTERIOR WALLS FACING ONLY ONE ORIENTATION (WITHIN REQUIRED T SPECIFIED IN SECTIONS S. DIRECT THROUGH CONTROL .11.3. BE LABELED BY AN APPROVE AGENCY. GRAVITY DAMPERS FOR VENTILATION AIR INTAKES +/-45 DEGREES) (0.8 RAD) FOR MORE THAN 50 CONTIGUOUS FEET(15,240 MM); SHALL BE PROTECTED FROM DIRECT EXPOSURE TO WIND. TARLEU07.10.1.2 1.2. THE PERIMETER SYSTEM HEATING AND COOLING SUPPLY IS CONTROLLED BY A THERMOSTAT C403.4.11.1 DDC APPLICATIONS. DDC SHALL BE PROVIDED IN THE APPLICATIONS AND SUPPLY,RETURN,EXHAUST,sr+O RELIEF M DUCTWORK INSULATION LOCATED WITHIN THE ZONES SERVED BY THE SYSTEM; AND QUALIFICATIONS LISTED IN TABLE C403.4.11.1. EXCEPTIONS: ramp 1.3. CONTROLS ARE CONFIGURED TO PREVENT THE PERIMETER SYSTEM FROM OPERATING IN A 1. GRAVITY(NONMOTORIZED) DAMPERS ARE NOT REQUIRED TO BE TESTED TO VERIFY THE AIR MLIMA DIFFERENT HEATING OR COOLING MODE FROM THE OTHER EQUIPMENT WITHIN THE ZONES OR LEAKAGE RATING WHEN INSTALLED IN EXHAUST SYSTEMS WHERE THE EXHAUST CAPACITY sna:y:e.r,r Or.a L•urim aM u•• GI^'r� R.•r x•r•s FROM NEIGHBORING ZONES CONNECTED BY OPENINGS LARGER THAN 10 PERCENT OF THE C403.4.11.2 DDC CONTROLS. WHERE DDC IS REQUIRED BY SECTION C403.4.11.1, THE DDC SYSTEM Zu w.•I,r•., FLOOR AREA OF EITHER ZONE. SHALL BE CAPABLE OF ALL OF THE FOLLOWING, AS REQUIRED TO PROVIDE THE SYSTEM DOES NOT EXCEED 400 CFM (189 L/S) AND THE GRAVITY DAMPER IS PROVIDED WITH A R.a.•+• AND ZONE CONTROL LOGIC REQUIRED IN SECTIONS C403.2, C403.4.3, C403.5, AND GASKETED SEAL. wopy a.a R.••n 0-m•wnai taulaows•ro 5••5•cUonG 3.10.1Rb 2. ANY INTERIOR ZONE OPEN TO A PERIMETER ZONE SHALL HAVE SET POINTS AND DEAD C403.6.8: 2. MO MINIMUMRS ON RE RATE NAIR AVOPENI EGS IN FROMUNITARY MANUFACTURER.PACKAGED EREQUIPMENT THAT ar •uoswto�,..+n«F K RA o.w• PERMIT BANDS COORDINATED SO THAT COOLING IN THE INTERIOR ZONE SHALL NOT OPERATE WHILE uMororoon.e so•ula•,oloaw wr Sn 5•mon G03.t0.12b 1. MONITORING ZONE AND SYSTEM DEMAND FOR FAN PRESSURE, PUMP PRESSURE, HEATING g' 'MOr R'01n rvmmma was wanww �ii0 Ra aws THE PERIMETER ZONE IS IN HEATING UNTIL THE INTERIOR ZONE TEMPERATURE IS 5°F AND COOLING. C403.7.8.4 DAMPER ACTUATION. OUTDOOR AIR INTAKE, RELIEF AND EXHAUST SHUTOFF DAMPERS ^' •,,.N�•I a0 � SET (2.8'C) HIGHER THAN THE PERIMETER ZONE TEMPERATURE, UNLESS THE INTERIOR AND 2. TRANSFERRING ZONE AND SYSTEM DEMAND INFORMATION FROM ZONES TO AIR DISTRIBUTION SHALL BE INSTALLED WITH AUTOMATIC CONTROLS CONFIGURED TO CLOSE WHEN THE u��ororoon.s apau nN•n m•s.a 5••IML s.rnon soatzb PERIMETER ZONES ARE SEPARATED BY A PARTITION WHOSE PERMANENT OPENINGS ARE SYSTEM CONTROLLERS AND FROM AIR DISTRIBUTION SYSTEMS TO HEATING AND COOLING SYSTEMS OR SPACES SERVED ARE NOT IN USE OR DURING UNOCCUPIED PERIOD WARM-UP S,-,y lliw Rmm wn.2y..r m•<is w,�t5•F as,• •C•,rJ fit] tlM1Ewlreyememsb SMALLER THAN 10 PERCENT OF THE PERIMETER ZONE FLOOR AREA. PLANT CONTROLLERS, AND SETBACK OPERATION, UNLESS THE SYSTEMS SERVED REQUIRE OUTDOOR OR EXHAUST ar .ir r.mw•••ean+a.,ra.,alro se m,a....sm mno-a•r AIR IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE OR THE DAMPERS ARE 3. DEDICATED OUTDOOR AIR UNITS THAT PROVIDE VENTILATION AIR, MAKE-UP AIR OR C403.4.11.3 DDC DISPLAY, WHERE DDC IS REQUIRED BY SECTION C403.4.11.1 FOR NEW OPENED TO PROVIDE INTENTIONAL ECONOMIZER COOLING. STAIRWAY AND ELEVATOR wnn.I•o.nain•rwa.q.naow t.n>ol.n,.•h..wr.w REPLACEMENT AIR FOR EXHAUST SYSTEMS ARE PERMITTED TO BE CONTROLLED BASED ON HOISTWAY SHAFT VENT DAMPERS SHALL BE INSTALLED WITH AUTOMATIC CONTROLS s,oay ar•r R•bm •awm•y �•^^ R-te °iwA�"0'""'IOO' BUILDINGS, THE DDC SYSTEM SHALL BE CAPABLE OF TRENDING AND GRAPHICALLY a. se semnly wn m•m.:mrm SUPPLY AIR TEMPERATURE. THE SUPPLY AIR TEMPERATURE SHALL BE CONTROLLED TO A DISPLAYING INPUT AND OUTPUT POINTS. CONFIGURED TO OPEN UPON THE ACTIVATION OF ANY FIRE ALARM INITIATING DEVICE OF .rwl.eo�hw MAXIMUM OF 65°F(18.3°C) IN HEATING AND A MINIMUM OF 72-F (22°C) IN COOLING UNLESS THE BUILDINGS FIRE ALARM SYSTEM OR THE INTERRUPTION OF POWER TO THE DAMPER, wa.,..raoon•a wK••r�•m• s••s•mo„cwaaa.t.zb -3o THE SUPPLY AIR TEMPERATURE IS BEING RESET BASED ON THE STATUS OF COOLING OR Swpy At wppy wnca�wys a�nn•rnr•a •C•ntl waz s•wa C403.5.1 INTEGRATED ECONOMIZER CONTROL. ECONOMIZER SYSTEMS SHALL BE INTEGRATED WITH 5a O HEATING IN THE ZONES SERVED OR IT BEING RESET BASED ON OUTDOOR AIR THE MECHANICAL COOLING SYSTEM AND BE CONFIGURED TO PROVIDE PARTIAL COOLING C403.8.5 FAN CONTROLS. CONTROLS SHALL BE PROVIDED FOR FANS IN ACCORDANCE WITH tna"x•c o,oa.<.,m.�,os•c TEMPERATURE. EVEN WHERE ADDITIONAL MECHANICAL COOLING IS REQUIRED TO PROVIDE THE REMAINDER SECTION C403.8.5.1 AND AS REQUIRED FOR SPECIFIC SYSTEMS PROVIDED IN SECTION C403. wnnm_mai",.a.o.«m.nn.euy s••s.alon uas.w.tzb OF THE COOLING LOAD. CONTROLS SHALL NOT BE CAPABLE OF CREATING A FALSE LOAD Tny+•rv•+•++•n m•.wnya,�r •c.,a aws L C403.4.1.1 HEAT PUMP SUPPLEMENTARY HEAT. UNITARY AIR COOLED HEAT PUMPS SHALL s' '^' �,,.•y:.r m.na__-or 5s Na•• r INCLUDE MICROPROCESSOR CONTROLS THAT MINIMIZE SUPPLEMENTAL HEAT USAGE DURING IN THE MECHANICAL COOLING SYSTEM BY LIMITING OR DISABLING THE ECONOMIZER OR ANY C403.8.5.1 FAN AIRFLOW CONTROL. EACH COOLING SYSTEM LISTED IN TABLE C403.8.5.1 or..u,m.ry,os•c "a START-UP, SET-UP, AND DEFROST CONDITIONS. THESE CONTROLS SHALL ANTICIPATE NEED OTHER MEANS, SUCH AS HOT GAS BYPASS, EXCEPT AT THE LOWEST STAGE OF SHALL BE DESIGNED TO VARY THE INDOOR FAN AIRFLOW AS A FUNCTION OF LOAD AND wnnm w„e-e,,,•e,.•aw<,•m• FO IN •R HEAT AND USE COMPRESSION HEATING AS THE FIRST STAGE OF HEAT. CONTROLS MECHANICAL COOLING. UNITS THAT INCLUDE AN AIR ECONOMIZER SHALL COMPLY WITH THE SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: swcy At wpoy aun cmwy.•wnwas5•c ee Kon• SHALL INDICATE WHEN SUPPLEMENTAL HEATING IS BEING USED THROUGH VISUAL MEANS FOLLOWING: mP r,e toy•F•.rs• ( co E.G., LED INDICATORS). HEAT PUMPS CE-60 2018 WASHINGTON STATE ENERGY CODE 1. DIRECT EXPANSION (DX) AND CHILLED WATER COOLING UNITS THAT CONTROL THE wN.,ce^a-eo.,•a w•o.. N EQUIPPED WITH SUPPLEMENTARY HEATERS SHALL BE INSTALLED WITH CONTROLS THAT 1. UNIT CONTROLS SHALL HAVE THE MECHANICAL COOLING CAPACITY CONTROL INTERLOCKED CAPACITY OF THE MECHANICAL COOLING DIRECTLY BASED ON SPACE TEMPERATURE SHALL RMum k Ra LL M meEr.,gnnuna�a6rru•c ,onem PREVENT SUPPLEMENTAL HEATER OPERATION ABOVE 40°F (4.4°C). WITH THE AIR ECONOMIZER CONTROLS SUCH THAT THE OUTDOOR AIR DAMPER IS AT THE HAVE NOT FEWER THAN TWO STAGES OF FAN CONTROL. LOW OR MINIMUM SPEED SHALL .nu .•« 100 PERCENT OPEN POSITION WHEN MECHANICAL COOLING IS ON AND THE OUTDOOR AIR NOT BE GREATER THAN 66 PERCENT OF FULL SPEED. AT LOW OR MINIMUM SPEED, THE '^ EXCEPTION: PACKAGED TERMINAL HEAT PUMPS (PTHPS) OF LESS THAN 2 TONS DAMPER DOES NOT BEGIN TO CLOSE TO PREVENT COIL FREEZING DUE TO MINIMUM FAN SYSTEM SHALL DRAW NOT MORE THAN 40 PERCENT OF THE FAN POWER AT FULL FAN Ras•rar E4,o1a. co�aoo,.a w.«•"e aomnv..•or kan0 R-ts V_, M (24,000 BTU/HR) COOLING CAPACITY PROVIDED WITH CONTROLS THAT PREVENT COMPRESSOR RUN TIME UNTIL THE LEAVING AIR TEMPERATURE IS LESS THAN 45-F(7'C). SPEED. LOW OR MINIMUM SPEED SHALL BE USED DURING PERIODS OF LOW COOLING LOAD .•.rv*�m.u.:n„mn a.mp•. eB N E AND VENTILATION-ONLY OPERATION. 0 N SUPPLEMENTARY HEATER OPERATION ABOVE 40°F. 2. DIRECT EXPANSION (CA UNITS WITH COOLING CAPACITY FOLLOWING: BTU/H (19 KW) OR 2, OTHER UNITS INCLUDING DX COOLING UNITS AND CHILLED WATER UNITS THAT CONTROL THE C403.10.2 DUCT CONSTRUCTION. DUCTWORK SHALL BE CONSTRUCTED AND ERECTED IN w Qp o GREATER OF RATED CAPACITY SHALL COMPLY WITH THE FOLLOWING: SPACE TEMPERATURE BY MODULATING THE AIRFLOW TO THE SPACE SHALL HAVE ACCORDANCE WITH THE INTERNATIONAL MECHANICAL W Z C403.4.1.2 DEAD BAND. WHERE USED TO CONTROL BOTH HEATING AND COOLING, ZONE 2.1. OX UNITS THAT CONTROL THE CAPACITY OF THE MECHANICAL COOLING DIRECTLY BASED ON(2.8'C) WITHIN WHICH THE SUPPLY OF HEATING AND TEMPERATURE SHALL HAVE NOT FEWER THAN TWO STAGES OF MECHANICAL COOLING CAPACITY CODE. LOW-PRESSURE DUCT SYSTEMS. LONGITUDINAL AND TRANSVERSE JOINTS, THERMOSTATIC CONTROLS SHALL BE CONFIGURED TO PROVIDE A TEMPERATURE RANGE OR OCCUPIED SPACE MODULATING FAN CONTROL. MINIMUM SPEED SHALL BE NOT GREATER THAN 50 PERCENT n/ w Q DEAD BAND OF AT LEAST 5'F . OF FULL SPEED. AT MINIMUM SPEED, THE FAN SYSTEM SHALL DRAW NO MORE THAN 30 SEAMS AND CONNECTIONS OF SUPPLY AND RETURN DUCTS OPERATING AT A STATIC PRESSURE LL COOLING ENERGY TO THE ZONE IS SHUT OFF OR REDUCED TO A MINIMUM. 2.2. OTHER OX UNITS, INCLUDING THOSE THAT CONTROL SPACE TEMPERATURE BY MODULATING PERCENT OF THE POWER AT FULL FAN SPEED. LOW OR MINIMUM SPEED SHALL BE USED LESS THAN OR EQUAL TO 2 INCHES WATER GAUGE (W.G.) (500 PA) SHALL BE SECURELY Q THE AIRFLOW TO THE SPACE, SHALL BE IN ACCORDANCE WITH TABLE C403.5.1. DURING PERIODS OF LOW COOLING LOAD AND VENTILATION-ONLY OPERATION. FASTENED AND SEALED WITH WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS Q n 3. UNITS THAT INCLUDE AN AIRSIDE ECONOMIZER IN ACCORDANCE WITH SECTION C403.5 EMBEDDED FABRIC SYSTEMS OR TAPES INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS U Z of C403.4.1.3 SET POINT OVERLAP RESTRICTION. WHERE A ZONE HAS A SEPARATE HEATING AND A C403.5.3. AIR ECONOMIZERS. AIR ECONOMIZERS SHALL COMPLY WITH SECTIONS C403.5.3.1 SHALL HAVE NOT FEWER THAN TWO SPEEDS OF FAN CONTROL DURING ECONOMIZER INSTALLATION INSTRUCTIONS. PRESSURE CLASSIFICATIONS SPECIFIC TO THE DUCT SYSTEM SHALL Q SEPARATE COOLING THERMOSTATIC CONTROL LOCATED WITHIN THE ZONE, A LIMIT SWITCH, THROUGH C403.5.3.5. OPERATION. BE CLEARLY INDICATED ON THE CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE. MECHANICAL STOP OR DIRECT DIGITAL CONTROL SYSTEM WITH SOFTWARE PROGRAMMING Lr) N SHALL BE CONFIGURED TO PREVENT THE HEATING SET POINT FROM EXCEEDING THE C403.5.3.1 DESIGN CAPACITY. AIR ECONOMIZER SYSTEMS SHALL BE CONFIGURED TO MODULATE EXCEPTIONS: 0 i 1. MODULATING FAN CONTROL IS NOT REQUIRED FOR CHILLED WATER AND EVAPORATIVE EXCEPTION: CONTINUOUSLY WELDED AND LOCKING-TYPE LONGITUDINAL JOINTS AND SEAMS ON L N Z COOLING SET POINT AND TO MAINTAIN A DEAD BAND IN ACCORDANCE WITH SECTION OUTDOOR AIR AND RETURN AIR DAMPERS TO PROVIDE UP TO 100 PERCENT OF THE DESIGN r^ C403.4.1.2 SUPPLY AIR QUANTITY AS OUTDOOR AIR FOR COOLING. COOLING UNITS WITH FAN MOTORS OF LESS THAN 1 HP (0.746 KW) WHERE THE UNITS ARE DUCTS OPERATING AT STATIC PRESSURES LESS THAN 2 INCHES WATER GAUGE (W.G.) (500 PA) L.L N J NOT USED TO PROVIDE VENTILATION AIR AND THE INDOOR FAN CYCLES WITH THE LOAD PRESSURE CLASSIFICATION. C403.4.1.4 HEATED OR COOLED VESTIBULES. THE HEATING SYSTEM FOR HEATED VESTIBULES AND C403.5.3.2 CONTROL SIGNAL. ECONOMIZER CONTROLS AND DAMPERS SHALL BE CONFIGURED TO O Q AIR CURTAINS WITH INTEGRAL HEATING SHALL BE PROVIDED WITH CONTROLS CONFIGURED SEQUENCE THE DAMPERS WITH MECHANICAL COOLING EQUIPMENT AND SHALL NOT BE 2. WHERE THE VOLUME OF OUTDOOR AIR REQUIRED TO COMPLY WITH THE VENTILATION C403.10.3.1 PROTECTION OF PIPING INSULATION. PIPING INSULATION EXPOSED TO WEATHER TO SHUT OFF THE SOURCE OF HEATING WHEN THE OUTDOOR AIR TEMPERATURE IS CONTROLLED BY ONLY MIXED AIR TEMPERATURE. AIR ECONOMIZERS ON SYSTEMS WITH REQUIREMENTS OF THE INTERNATIONAL MECHANICAL CODE AT LOW SPEED EXCEEDS THE SHALL BE PROTECTED FROM DAMAGE, INCLUDING THAT DUE TO SUNLIGHT, MOISTURE, EQUIPMENT Last Revision Date: GREATER THAN 45°F (7'C). VESTIBULE HEATING AND COOLING SYSTEMS SHALL BE COOLING CAPACITY GREATER THAN 65,000 BTU/H SHALL BE CONFIGURED TO PROVIDE AIR THAT WOULD BE DELIVERED AT THE MINIMUM SPEED DEFINED IN SECTION C403.8.5, MAINTENANCE AND WIND, AND SHALL PROVIDE SHIELDING FROM SOLAR RADIATION THAT CAN CONTROLLED BY A THERMOSTAT LOCATED IN THE VESTIBULE CONFIGURED TO LIMIT HEATING PARTIAL COOLING EVEN WHEN ADDITIONAL MECHANICAL COOLING IS REQUIRED TO MEET THE THE MINIMUM SPEED SHALL BE SELECTED TO PROVIDE THE REQUIRED VENTILATION AIR. CAUSE DEGRADATION OF THE MATERIAL. ADHESIVES TAPE SHALL NOT BE PERMITTED. 7/25/2023 TO A TEMPERATURE NOT GREATER THAN 607 (16°C) AND COOLING TO A TEMPERATURE REMAINDER OF THE COOLING LOAD. m C403.13 COMMISSIONING. MECHANICAL SYSTEMS SHALL BE COMMISSIONED IN ACCORDANCE WITH NOT LESS THAN 85°F (29°C). SECTION C408. c,rveerseo sv. anwry sv. a K.K K.D a MECHANICAL DCODE N,S M 0.01 Z O a U U Z U O p AIR HANDLER HEAT PUMP SYSTEM w TOTAL NOMINAL SUPPLY COOUNG HEATING SOUND MECHANICAL COMPLIANCE SUMMARY W ma CONDENSING BASIS OF DESIGN AIR ESP CAPACITY CAPACITY MERV ELECTRICAL HEIGHT POWER WEIGHT CONDENSATE _ npliao. d -11 RZ R3& r3soriex ai1 R l stered by::l zJ NEEA,Al,igh,e--d Q TAG MARK UNIT CA LOCATION MANUF MODEL (SCFM) (IN WC) (BTU/HR) (BTU/HR) RATING M VOLTS PHASE IN dBA LBF IN NOTES Pmint Title OPNMCAREDISTRIB-ONCENTER-21318WSEC For Building Dcpmmxmt Usc: IDBte: Jm125,2023 !DU 1 CU-1 MEZZANINE MITSUBISHI PEAD-Al2AA7 494 0.50 12,000 15,000 8 1.45 20 230 1 9-7 8 34 58 1-1/4 Id 3 pplic+nr P.Jnl Add. 1721251STAVENE Pro'xt&A Arlingloe,WA E NE Inf+rmanon Applicant Name KADDUATOUDUMBUYA nn Z N 01 ApPlit Phone 3 -J50.574J LOSES: KADDUA DKSYSTEMSINCCOM 1.VERIFY ELECTRICAL VOLTAGE PRIOR TO PLACING ORDER. For oesemisnboutmie n,mvmn WSECCmmnemid Wm IS m360.539-5300wvumreil m mm ba r rodesmm 2.FURNISH ONE FUSED DISCONNECT PER SYSTEM FOR INSTALLATION BY DIV 26. Generel Oem n All Commerciil Ceuerel Buildb Ure W+aM1oure,Generd Sm BuiMm Cond.Floor A- 14,940 3.PROVI DE 24 HOU R/7 DAY FROG RAMMABLE TH ER MOSTAT CAPABLE OF AUTOMATI C SETBACK OR SH UTDOWN D U RI NG PERIODS OF NON-USE Naw BVWing a Prn'ml C+nd.Floor Aro 411 General Projnt Types Altmdov wAdditloe A1te an°° Single Zave Systms&Eq°ipmem FI°on AM1ove Grade 1 J 4.14/3 WIRE FROM THE INDOOR UNITTO THE OUTDOOR UNIT. MmM1vnkW Smpe e•nm+l5cope Compllavtt Method compliance Memos l-Genml N 00 MxM1anlnl Protect Deseriptlgn . � Economizer Equipment EDidevev ` U) Prejeet DOAS VenNlvtlon Higher Equipment Mtthvninl Scope Exreption(s) (emPllance } Mnhvnlcvl C'ompllentt Type pro Provided'.' Emeieney Option Applied? VerifinH+n fn Srope end Method Single Zone System,& Y Altcrosion Vcs sNACObIPLIF.g Additional Emuieney VRV CONDENSING UNITS Credin lnnnded,,,EG, �, g Deaie•ted outside air systems(nOAS) W Donbuilding include wmpavcy elvssiRnHom We Yes Don lade DOAS 1, DOHS^ Pmlen inc equipment? LY) NOMINAL NOMINAL MINIMUM Bared on pmjectsmpe do TSPR Dodl sv�st ms comply-1,Appendix Datandvrd reference deign or qualify for an exteptloe to requirements apply'? No TNPRI No COOLING HEATINGL GAS EFFIQ ENCY SOUND m o Z BASISOF DESIGN CAPACITY CAPACITY CONN REFRIGERANT COOLING HEATING ELECTRICAL POWER WEIGHT CoBdINBBiBg AL1E a LU r in TAG MARK LOCATION MANUF MODEL (MBH) (MBH) IIN) TYPE SEER COP47 HSPF MCAMOCPZ Single tuneAir Syrams Csagon'-Hevt pump,vnimry,thl-wall,SDHV WCU I OUTDOOR MITSUBISHI 5UZ-KAl2NA2 12,000 15,000 319 R-410A 20.5 3.79 13.0 9.0 16.0 208-230 1 51 81 1-2 Q U Alr Systems Summary ln(ormanov � J NOTES: System/Equip lD Ouvnfry SOPPIy - yentllatlon 6anderd VenHlvtlon CFM Ventilation Polred witM1 DOAS Vennlatl+n energy mmvery Energy Recovery of Ilemr ConAtrolr (Total if Muln k ItemH AIr B+uree ElTklen (Y.1 1.VERI FY ELECTRICAL VOLTAGE PRI OR TO PLACING ORDER. IDU-1 Constant volume IMC Ventilation S to DOAR ­1 Provided but not aired 66 2.FURNISH ONE FUSED DISCONNECT PER SYSTEM FOR INSTALLATION BY DIV 26. AIrSnamv& rat-Coo11n Syvam/ Cooling 6ysfem/Equip Type gperifc Type Cooling Capaeiry AECEmeien<y Erovo Exeepdon Combined Effid-, Propoved Cooling CE Propored Part PL Emeieney Compliavtt F,quip lD per item(BfufH Multiplier MuI6pIwr(FL&PL) Mulnpwr(A Fenno) E1Reieney Unia Load Eifieiew Unit Wriffeation IDU-I Hmsp-p. d 1 20.5 1 SEER I I IEFR I COMPLIES Airs namr&E vim 1-Heann Heeling gystemlEquip Type Sp-d-Type Nevl Pump He+flog Capvcity(Bmlh) Coo tu/ling Clpvmly(BM AF.0 Emeienq Proposedn-Pump HPII Prop-Low OSA LTH Emei`ney Complientt /E yule lD Mulnlfer Hnfin EM,w U­ Tem Emekne UM I-- ENERGY RECOVERY VENTILATORS DL-1 He rolN,bnHn 5 lif t stem 15.000 12dddd 13D I.Sp'l COP OMPI IFS FAN Air Seams& e.De.M SENSIBILE Se•tem/e+i mm Are.p)Served uuHonm Pro ntDwumen em9n SUPPLY FAN EXHAUST FAN ELECTRICAL SOUND WEIGHT IDU-1 OFFICFISTORAGFIJANITOR M0 Q,M2.Ign r TAG MARK CITY LOCATION RECOVERY NOTES S st +i mfmasin Icmmdti le itmu?:Sin le itm BASIS OF DESIGN EFF(%) AIRFLOW ESP AIRFLOW ESP POWER (") MANUF MODEL (SCFM) (IN WC) (SC (IN WC) MCA(A) POWER(KW) VOLTS PHASE D8A (LBF) Hutin Stttian/Auxiliv Hmtin T :ElnWc resisanu(w None) Ennom Cum liantt MnhW Economian not uirea WSEC ui Emcimc Ref ce Table-Conlin:Table C403.3.2 2-Uni and A lied Hns Pd.' ERV I I CEILING WHISPER COMFORT FV-04VE1 66% 20 0.10 20 0.10 0.10 0.021 120 1 W.3 1-2 DO O ERV 2 1 CEILING WHISPER COMFORT FV-04VE1 66% 20 0.30 20 0.10 0.10 0.021 120 1 <0.3 1-2 NOTES: I.VERIFY ELECTRICAL VOLTAGE AND PHASE PRIOR TO PLACING ORDER. Low OSATm Emnm LTHUw..COP 2.UNIT OPERATION BY A LINE VOLTAGE OCCUPANCY SENSOR-PROVIDED BY MECH.,WIRED/INSTALLED BY ELECTRICIAN. WSEC Equip Emci Ref qe Table-Huting:TAk C4n3.3.2(2)-Unimryavd App]WHem Pumps EXHAUSTFANS SOUND BASIS OF DESIGN AIRFLOW ESP ELECTRICAL POWER WEIGHT TAG MARK LOCATION MANUF MODEL (SCFM) (INWQ POWER(W) MCA VOLTS PHASE (SONES) (LBF) NOTES EF 1 BATHROOM PANASONIC FV-0S10V51 50 0.30 4A 0.39 120 NOTES WIT: f7 1. H BACKDRAFT DAMPER AT FAN. PERMIT 2.WITH OOCUPANY SENSOR OR UGTHS-BY ELECTRICAN ET GRILLES,REGISTERS,AND DIFFUSERS BASIS OF DESIGN CONSTRUCTION TAG TYPE FACE SIZE NOTES D ESCRIPNON MOUNT TYPE NECK CONNECTION O p MANUF MODEL (I NAN) CSD CEILING SUPPLY DIFFUSER TITUS MOD 4:0RE ADJUSTABLE 24"g24" IAY-IN ROUND I LL CRG CEILING RETURN GRILLE TITUS SOF 1/2 Xi/2'Xi'ALUMIUM G RID 24"X24" IAY-IN ROUND 1 r 'o CEG CEILING EXHAUSTGRILLE GREENHECK SP-A DESIGNER GRILLE 19"X19" LAY-IN ROUND I co NOTES: 1.STANDARD WHITE FINISH N I 1 M E 0 N o MINIMUM LU Z OCCUPANTS PER 2018 VENTILATION RATE PER VENTILATION RATE 2018 VENTILATION RATES NN Q IMC TABLE 403.3.1.1 2018 IMC TABLE 403.3.1.1 IMC TABLE 403.3.1.1 PER ROOMTYPE L.1_ Q VENTILATION CALCULATIONS SQFT/OCC SOFT OCC CFM/QSFT CFM/OCC CFM Q o OFFICE 200 113 1 0.06 5 12 U z j STORAGE 227 0 0.06 10 14 CC i TOTAL 26 G O N J Q Last Revision Date: 7/25/2023 N BY. a K-K KID a MECHANICAL SCHEDULE S NTS M 0.0 2 Z O a U U Z U O p U) w w 0 Z J W M UU N Y w W m z o Z z $Z QU m J AREA OF WORK O 77 1-71 E-71 77 L rn co M co O I LEVEL 1 KEY PLAN PERMIT SET TRUE PROJECT NORTH NORTH Z O H o � m 0 N LU z rn Lu Q Q Q U � z o N Z N J O Q Last Revision Date: 7/25/2023 N 7KD a K.K a MECHANICAL SITE PLAN SCAM WS M1 .01 NOTES z O 1 EXHUAST FAN DISCHARGE NEEDS TO BE ATLEAST 10 FEET AWAY FROM ANY INTAKE a_ AND/OR 3FEET OR MORE ABOVE INTAKE LOCATION U U Z U O ROUTE CONDENSATE AND REFRIGERANT LINES AS SHORT AND DIRECT AS POSSIBLE. O 0 U w O INSTALL GALVANIZED DUCTWORK AND R-8.0 DUCT WRAP INSULATION w H Q Z ERV 04 00 • SUPPLY UP 40 SECURE TO WALL OFFSET BELOW ROOF PENETRATION Y ATLEAST 3'FEET FROM OUTSIDE WALL CRG 24X24" 157of CSD 24"X24' 0w0 157 T 1 7 o Z `qa W r U) o Z W EXHAUST UP V QU SECURE TO WALL m J OFFSET BELOW ROOF PENETRATION ATLEAST 3'FEET FROM OUTSIDE WALL a a � ro DU 1 r rn M 1 0 Xk 07 O I 100 CSD 24'X24" SUPPLY UP 2 00 SECURE TO WALL OFFSET BELOW ROOF PENETRATION 40 ATLEAST 3'FEET FROM OUTSIDE WALL ERV 2 GRG 24*X24' PERMIT 337 SET a a EXHAUST UP SECURE TO WALL OFFSET BELOW ROOF PENETRATION CSD 24°X24" ATLEAST 3'FEET FROM OUTSIDE 87 WALL EF Z 0 i o m i N a M E 0 N LU z rn Lu Q Q Q 0 < z o N Z EXISTING 08 EXHAUST UP ^ THROUGH ROOF O Q Last Revision Date: 7/25/2023 N 7KD N MECHANICAL MEZZANINE a EK.KE�oeY CEILING PLAN i SCALE: 1/2"=1' M2.00 KEYED NOTES o F- EXHUAST FAN DISCHARGE NEEDS TO BE ATLEAST 10 FEET AWAY FROM ANY INTAKE a.1 AND/OR 3FEET OR MORE ABOVE INTAKE LOCATION Ir U) U Z 1n LU O2 ROUTE CONDENSATE AND REFRIGERANT LINES AS SHORT AND DIRECT AS POSSIBLE. O 0 U) w W H Q Z J N DID } S PLY U) O_ W DO 7 o Z W z o Z QU m J PARAPET ON WESTSIDE IS E AUST Y-6'FEET TALL. CONDENSING UNIT HEIGHT IS 21-5/8"INCHES.UNIT WILL BE COVERED BY THE PARAPET r rn M 0 C PPL PERMIT SET HAU ;o Z _O i o m i N LLL U) M E 0 N LLI z rn Lu M U Q z 0 N Z N J � Q Last Revision Date: 7/25/2023 a N MECHANICAL ROOF LEVEL PLAN ENGINEERED BY. oKDaY. FLOOR PLAN i SCALE: 1/4"=1' M 2.01 Z O a it U U Z U O p U) LU UJ Q NOTES: 1. REFER TO SPECIFICATIONS FOR HANGER SPACINGS. Z cv a r rn 2. ATTACHMENTS TO OVERHEAD STRUCTURE SHALL BE MADE IN ACCORDANCE WITH 1. REFER To SPECIFICATIONS FOR HANGER SPACINGS. MANUAL VOLUME DIRECTION OF AIR STRUCTURAL ENGINEER'S REQUIREMENTS AND WEIGHT UMITATIONS. SUBMIT FOR REVIEW 2. ATTACHMENTS TO OVERHEAD STRUCTURE SHALL BE MADE IN ACCORDANCE WITH STRUCTURAL DAMPER FLOW-TYP. AND APPROVAL ENGINEER'S REQUIREMENTS AND WEIGHT UMITATIONS. SUBMIT FOR REVIEW AND APPROVAL ADJUSTABLE 3. PROVIDE SWAY AND SEISMIC BRACING PER SMACNA SEISMIC GUIDEUNES. 3. PROVIDE SWAY AND SEISMIC BRACING PER SMACNA SEISMIC GUIDELINES. AIR EXTRACTOR TURNING VANES `J THESE TWO HANGERS ARE TO BE USED UNLESS CFM MAX. 04 SIZE OF SPLIT PROPORTIONAL UNLESS OTHER- 000 ON DUCTS 25"AND LARGER THIS HANGER IS FOR DUCTS rn (MAY BE USED ON SMALLER DUCTS) 24'0 AND SMALLER TO AIR FLOW QUANTITIES. WISE NOTED _ AIR FLOW DIRECTION-TYP. BRANCH TAKE-OFF U TEE-SPLII DUCT INCREASED • Y a"B ROD OR 1"X 163a. }"B ROD.(TYP.) 2°X 2"X b" rO ROD OR 1"X 16Gu. TURNING VANES PRIOR TO INLET 1'X 16Ga.HANGER STRAP(TYP.) I HANGER STRAP(TYP.) ANGLE TOP AND HANGER STRAP.(TYPICAL) MANUAL VOLUME BOTTOM DAMPER of 2A A LU _-FOR RETURN AND 00 EXHAUST AIR DUCTS 1"X 16Ga. SIZE OF SPLIT PROPORTIONAL MAX SLOPE a Z STRAP OVER J"BOLT NUT AND STAR TO AIR FLOW QUANTITIES. 1°IN 5'ANY SIDE EXPANDED TAP W DUCT(TYP.) WASHER(TYP.) AIR FLOW o Z SHEET METAL SCREWS BOLT NUT 2"MAX INCREASING �') AND STAR WASHER SINGLE BRANCH TAKE-OFF < U 1-1/2'X 22Ga. MANUAL VOLUME AIR FLOW J HANGER STRAP DAMPER MAX.SLOPE DECREASING 1"IN 6"ANY SIDE liff CONTINUOUS X 22Ga. - DUCT TRANSITION NUT AND LOCKNUT CON/2"X 2 COLLAR -i 30' TRIM AT 45" 60' 61" DRAWN TIGHT DIFFUSER NG VANES MAX ANGLE(TYP.) MAX. 2"X2'Xa° AND OVER AROUND DUCT SIZETURNIOF SPLIT PROPORTIONAL A 10 TO ANGLE(�) !\NECK SIZE EACH STRAP ADJACENT DOUBLE BRANCH TAKE OfFLOW UMJTBIES DUCT TERMINATION `CHUNG DIFFUSER 1-4"COL X 12Ga.SPLIT RING COLLAR AROUND DUCT TO ONE ANOTHER AT HANGER LOCATION RECTANGULAR DUCT HANGER DETAIL ROUND DUCT HANGER DETAIL TYPICAL RECTANGULAR DUCT FITTING DETAIL co SCALE. NITS SCALE: NTS v SCALE: NTS m O TABLE 1: DUCT OVERALL ASSEMBLY HEIGHT AT MIN INSIDE HEIGHT DUCT R-VALUE CONSTRUCTION DUCT HEIGHT DUCT HEIGHT(WIDTH>22") R-4.2 R-4.2 LINER 10.5" 11.5" R-4.2 R-4.2 FOIL 8.5' 9.5" PERMIT R-6 R-6 FOIL 8.625" 9.625" R-8 R-4.2 FOIL + LINER* 10.5" 11.5" SET R-8 R-8 FOIL 9.25" 10.25" NOTES: 1. OFFSET OR ROTATE PIPE SECTION'B',45'FROM PIPE * BEST ACOUSTICAL PERFORMANCE SECTION'A"TO PROVIDE CLEAR ACCESS FOR CLEAR-OUT. ADDMONAL INSULATION TO MEET ENERGY CODE, 2. DRAIN PIPE SIZES SHALL BE 3/4"SERVING MR SEE TITLE 24 REPORT FOR REQUIRED VALUED CONDITIONERS UP TO 20 TONS OF COOLING AND 1" EXTERIOR INSULATION ADDITIONAL EXTERIOR R VALUE SERVING MR CONDITIONERS FROM 21 TO 40 TONS OF A.C. FOIL 5/16'=R-4.2 DRAIN PIPE SHALL NOT BE SMALLER THAN THE AIR 3/4"SPACER+5/16° =R-6 CONDITIONING UNITS CONNECTION. Z 3/4"SPACER+5/8' =R-8 3. DIMENSION"A"=S.P.z 1.5+2"DIMENSION'B'=S.P.z 0.5+ 1" O BATT(K=0.29): 1-1/2' =R-4.2 2-3/16'=R-6 IF LENGTH OF HORIZONTAL .0 3' =R-8.4 1/4'CLEARANCE DRAIN PIPE IS GREATER THAN 15',INSTALL FULL SIZE VENT -- r co ----------------------1 N Gas to Eauicntient Pioine Detail 6" 0 ''^^ U ABOVE BDRAINT PAN F c J Ch E Bell SeiAment CV SEE TABLE 1 MIN CLEAR HEIGHT=6' DRAW-THROUGH AIR 0 N o Valve Trap Union C.O. CONDITIONING UNIT DRAIN PAN. LLI 00 W z MAX WIDTH=4zHEIGHT A DI-ELECTRIC PIPE COUPUNG OR Q To Appliance or 1'LINER(R4.2/IN) -- �- PIPE UNION AS REQUIRED. Equipment - -�- - Q > o __ Lu n ___________ _D SLOPE DRAIN PIPE DOWN U a Z IN DIRECTION OF FLOW O i 1'FLANGE AT 1/8"PER FOOT UCT (WIDTH>22':1.5'FLANGE) LO CD C,4 Z DRAIN INTO APPROVED J PLUMBING RECEPTACLE 3"MINIMUM O � Q AIR CONDITIONING UNIT CONDENSATE TRAP Last Revision Date: GAS TO EQUIPMENT PIPING DETAIL RECTANGULAR DUCT INSTALLATION DETAIL 6 ScxE: NTS 7/25/2023 4 SCALE: NITS 5 SQALE: "'� MECHANICAL a'"E` DBY DETAILS K.K KA a a I SCALE: NTS o M3.00 Z O a U U Z U O p U) w w Q Z FLEA.EFLECION FOR PIPING OUTSIDE AIR INTAKE ROOM DETAIL SEE M_ RESTRAININGT'STAT��7——— ELECTRONIC DAMPER LOCATE DAMPER AS 00 REMOTE TO DIFFUSER N CABLE(TYP.4) ACTUATOR2 POSITION AS POSSIBLE . } INTERNA 1 1 1 1 L Q 1"ACOUSTIC IF1"LINING CONTROL INPUT FOR O.SA LINING 10'MIN. ��ECONOMISER COOLING BOWDEN CABLE(OR EQUAL) STRUCTURE CONTROL WIRE LENGTH AS REQ'D 2 POSITION DAMPERS ANCHOR LU SUPP CONTROL KIT MOUNTING o] DU1 RETURN AIR BRACKET. FIELD FAB&INSTALL FROM PLENUM I I IN INSULATED PLENUM o Z 24" SPRING HANGER ISOLATOR FLEXIBLE DUCT CONNECTOR I YOUNG REGULATOR MODEL w THREADED ROD I 270-275(OR APPROVED EQUAL) a Z BACKDRAFT DAMPER CONTROL KIT RETURN AIR PLENUM I < U_ SPRING ISO . TO MATCH FAN COIL IN I FLEXIBLE INLET SIZE 24"DEEP { INSULATED SLOT DIFFUSER J P-1000 CONNECTION UNISTRUT SUPPORT FILTERS HARD CEILING WITH PLENUM CHANNEL OR EQUIVALENT NO ACCESS DOOR SLOT DIFFUSER CONDENSATE DRAIN FLEXIBLE DUCT CONNECTOR MAIN SUPPLY DUCT WALL FRAMING SEE PLUMBING DWG (A)100%O.SA-0%REYURN • 45'SQUARE-TO-ROUND(B)MINIMUM O.SA(SEE FAN COIL SCHEDULES)&REMAINING RETURN SIDE TAKE OFF WALL FINISH MATERIALS GRILLE ACCESS PANEL (APPROX.13"LONG) YOUNG REGULATOR MODEL 50200C DUCT 0 L VOLUME DAMPER FOR BOWDEN 6" to" CABLE CONTROL SYSTEM FAN COIL UNIT SCHEMATIC �� IN-LINE EXHAUST FAN DETAIL (OR EQUAL)(SEE CHART FOR LENGTH) 10" to" r7 1 SCALE: NTS L SCALE: 12" 12" FLEXIBLE DUCTWORK CONNECTION m 14" 14" O 16" 16" 18° 18" YOUNG REGULATOR MODEL 502OCC VOLUME DAMPER FOR BOWDEN CABLE CONTROL SYSTEM (OR EQUAL)(SEE 140280 M8.02) LOCATE DAMPER AS REMOTE TO DIFFUSER AS POSSIBLE L BOWDEN CABLE(OR EQUAL) PERMIT MAIN SUPPLY DUCT CONTROL WIRE LENGTH AS REQ'D SET If Concrete pad,provide N8'x 3'concrete FLEXIBLE DUCT anchors x 4��er5 �—SUPPORT ELBOW R•r�� CONNECTED TO BUILDING STRUCTURE 30 YOUNG REGULATOR MODE CEILING O i 270-301 (OR APPROVED EQUAL) DIFFUSER oRACK&PINION CONTROL KIT. G. 'ftvApd� HARD CEILING NO 3"0 PLATED COVER co iM� r LIB 4„�y� ACCESSS D DOOR ON CEILING IJ�d�ln br[ir1r�� nw40 M WTALCM Lu o I w z 0) _ REMOTE BALANCE DAMPER �� SCALE: NITS LLI Q U < Z p 1 Ln CD DFD/INSTALLFD BY GC N Z_ N J Q I I Last Revision Date: 7/25/2023 Outdoor Linit Attachment MECHANICAL G'"E` DBY 7KD a OUTDOOR UNIT ATTACHMENT DETAIL ��� DETAIS I<.I< 3 SCALE: NTS SCALE: NTS o M 3.01 Z O a HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Date U OPTUM CARE DC-TI 7/21/2023 Z System Name Floor Area O W p System 435 O ENGINEERING CHECKS SYSTEM LOAD W Number of Systems COIL COOLING PEAK COIL G.PEAK Heating System CFM Sensible Latent CFM Sensible W Output Par 3 tam Total Room Loads 287 5,500 569 44 1,890 Q Total Output Btuh Return Vented Lighting 0 Output Shm/ h Return Air Ducts 275 90 Cooling System ReturnFan 0 0 Z Output er3 tam Ventilation 40 301 147 40 2,282 Total Output Btuh Supply Fan 0 0 Total Output(Tons) Supply Air Ducts 275 94 Total Out ut Btuhis Total Output a h7ron TOTAL SYSTEM LOAD 8,357 716 4,.0 N Air System Obi CFM perSystem HVAC EQUIPMENT SELECTION U) umow(cfa) �. Almow cfrNe R `L Almow cfrnrran Outside Air X Total Adjusted System Output Outside Air chnia it (Adjusted for Peak Dealgn Conditions) W m Note:values above given at ARI conditions TIME OF SYSTEM PEAK Jul 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of HeatingPeak o Z 16°F 60°F 110°F W ® II Outside Air o Z m J 40 cfm Heating Coil 110°F ROOM 70°F 70°F � Ill �e COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 62/66°F 76/63°F 55/54°F B Outside Air Li r O 40 cfin Cooling Coil 56/54°F M 50.2% R DO OOM 75162'F 74/62°F PERMIT SET Z O o � m CM E 0 N LU z rn LU Q Q Q U � z o N Z N J O � Q Last Revision Date: 7/25/2023 N BY. a K.K KID a MECHANICAL LOAD CALCULATIONS S NTS M 4.00 Table of Contents Ductless Heat Pump 2 Energy Recovery Ventilator (ERV) 10 Exhaust Fan 11 SUBMITTAL 1 DATA: 1 1 P 1 , 1 1 1 & 1 1 12,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM Art ELECTRIC Job Name:Optum Care Distribution Center TI System Reference:Ductless Mini Split - 12K Heat Pump Date: Indoor Unit: Outdoor Unit: PEAD-Al2AA7 SUZ-KAl2NA2 .. J �� I���IIIIIIIIIIIIIIIIIIIII�IIIIIIIII111 ELECTRISCHI �IIIIIIIIIIIII�IIIII[IIIIIIIIIIIIIIIII V` ..,�IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII '+°�i��IIIIIIIIIIIIDi�'''� INDOOR UNIT FEATURES • Unobtrusive ceiling-concealed design for short-run ductwork. • Wide ranging external static pressure(0.14-0.60 in.WG) • Built-in condensate lift mechanism(up to 27-9/16") • Auto fan speed mode • Optional FB Series filter boxes for easy access and service • Ideal for residential homes,retail shopping centers, larger classrooms,office complexes,conference ballrooms,fitness centers,and more OUTDOOR UNIT FEATURES • Variable speed INVERTER-driven compressor • Innovative Joint Lap DC Motor leads to high efficiency and reliability • Pulse Amplitude Modulation technology • High-performance grooved piping for increased heat exchange efficiency Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. SPECIFICATIONS: , 1 ' 1 1 1 1 Maximum Capacity Btu/h 12,000 Rated Capacity Btu/h 12,000 Minimum Capacity Btu/h 4,400 Maximum Power Input W 930 Cooling at 95°F1 Rated Power Input W 930 Moisture Removal Pints/h 1.1 Sensible Heat Factor 0.9 Power Factor(208/230V) % 95 Maximum Capacity Btu/h 13,200 Rated Capacity Btu/h 13,200 Cooling at 82°F Minimum Capacity Btu/h 4,900 Maximum Power Input W 860 Rated Power Input W 860 Maximum Capacity Btu/h 17,000 Rated Capacity Btu/h 15,000 Minimum Capacity Btu/h 4,800 Heating at 47°FZ Maximum Power Input W 1,400 Rated Power Input W 1,160 Power Factor % 97 Maximum Capacity Btu/h 9,900 Rated Capacity Btu/h 9,900 Heating at 17°F3 Maximum Power Input W 1,070 Rated Power Input W 1,070 Maximum Capacity Btu/h 7,900 Heating at 5°F4 Maximum Power Input W 810 Heating at-4°F5 Maximum Capacity Btu/h 5,900 SEER 20.5 EER' 12.9 HSPF(IV) 13.0 Efficiency COP at 47°F2 3.79 COP at 17°F in Maximum Capacity3 2.71 COP at 5°F in Maximum Capacity4 2.85 ENERGY STAR®Certified(ENERGY STAR products are third-party certified by Yes an EPA-recognized Certification Body.) Voltage, Phase, Frequency 208/230V, 1 phase,60Hz Guaranteed Voltage Range V AC 187-253 Voltage: Indoor-Outdoor,S1-S2 V AC 208/230 Electrical Voltage:Indoor-Outdoor,S2-S3 V DC 24 Voltage:Indoor-Remote Controller V DC 12 Recommended Fuse/Breaker Size A 15 Recommended Wire Size(Indoor-Outdoor) AWG 14 Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. SPECIFICATIONS: , 1 ' 1 1 1 1 MCA A 1.45 Fan Motor Full Load Amperage A 1.16 Fan Motor Output W 85 Airflow Rate at Cooling,Dry CFM 494-424-353 Airflow Rate at Cooling,Wet CFM 445-382-318 Sound Pressure Level(Cooling) dB(A) 34-30-28 Sound Pressure Level(Heating) dB(A) 34-30-28 External Static Pressure in.WG 0.14-0.20-0.28-0.40-0.60 Drain Pipe Size In.(mm) 1-1/4(32) Condensate Lift Mechanism,Maximum Distance In.(mm) 27-9/16(700) Indoor Unit Heat Exchanger Type Plate fin coil External Finish Color Galvanized W:In.(mm) 35-7116(900) Unit Dimensions D: In.(mm) 28-7/8(732) H: In.(mm) 9-7/8(250) W:In.(mm) 45-5/16(1,150) Package Dimensions D: In.(mm) 34-11/16(880) H: In.(mm) 13-7/16(380) Unit Weight Lbs.(kg) 58(26) Package Weight Lbs.(kg) 69(31) Indoor Unit Operating Cooling Intake Air Temp(Maximum/Minimum)* °F 90F D.B/71 F W.B//67F D.B/57F W.B Temperature Range Heating Intake Air Temp(Maximum/Minimum) °F 80F D.B//70F D.B MCA A 9 MOCP A 16 Fan Motor Full Load Amperage A 0.5 Fan Motor Output W 55 Airflow Rate CFM 1,229/1,172 Refrigerant Control LEV Defrost Method Reverse cycle Heat Exchanger Type Plate fin coil Blue Fin Coating on Heat Exchanger Yes Outdoor Unit Sound Pressure Level,Coolingi dB(A) 49 Sound Pressure Level,Heating2 dB(A) 51 Compressor Type DC INVERTER-driven Twin Rotary Compressor Model SNB092FQAMT Compressor Rated Load Amps A 6.6 Compressor Locked Rotor Amps A 8.2 Compressor Oil Type//Charge oz. FV50S//11.8 External Finish Color Ivory Munsell 3Y 7.8/1.1 Base Pan Heater Optional Unit Dimensions W:In.(mm) 31-1/2(800) Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. SPECIFICATIONS: • 1 ' 1 1 1 1 1 D: In.(mm) 11-1/4(285) H: In.(mm) 21-5/8(550) W:In.(mm) 38(940) Package Dimensions D: In.(mm) 14-15/16(380) H: In.(mm) 24-13/16(630) Unit Weight Lbs.(kg) 81 (37) Package Weight Lbs.(kg) 88(40) Cooling Air Temp(Maximum/Minimum)* °F 115/14 Outdoor Unit Operating Cooling Thermal Lock-out/Re-start Temperatures** °F -1 /3 Temperature Range Heating Air Temp(Maximum/Minimum) °F 75/-4 Heating Thermal Lock-out/Re-start Temperatures** °F -9/-4 Type R410A Refrigerant Charge Lbs,oz 2,9 Gas Pipe Size O.D.(Flared) In.(mm) 3/8(9.52) Liquid Pipe Size O.D.(Flared) In.(mm) 1/4(6.35) Piping Maximum Piping Length Ft.(m) 65 Maximum Height Difference Ft.(m) 40 Maximum Number of Bends 10 Notes AHRI Rated Conditions 1 Cooling(Indoor//Outdoor) °F 80 DB,67 WB//95 DB,75 WB (Rated data is 2Heating at 47°F(Indoor//Outdoor) °F 70 DB,60 WB H 47 DB,43 WB determined at a fixed compressor speed) 3Heating at 17°F(Indoor//Outdoor) °F 70 DB,60 WB//17 DB, 15 WB 4Heating at 5*F(Indoor//Outdoor) °F 70 DB,60 WB//-4 DB,-5 WB Conditions 5Heating at-4°F(Indoor//Outdoor) °F 70 DB,60 WB//-4 DB,-5 WB *Applications should be restricted to comfort cooling only;equipment cooling applications are not recommended for low ambient temperature conditions. **System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures. Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. ACCESSORIES: • 1 ' 1 1 1 Filter Box with MERV 13 Filters ❑FBM2-2 Wireless Signal Receiver ❑PAR-SA9CA-E Wireless Signal Receiver ❑PAR-FA32MA-W Wireless Signal Receiver ❑PAR-FA32MA-E Wireless Remote Controller ❑PAR-FL32MA-E Backlit,Wall-mounted,Wireless Controller ❑MHK1 Portable Central Controller ❑MCCH1 Wired MA Controller ❑PAR-33MAA Simple MA Controller ❑PAC-YT53CRAU Touch MA Controller ❑PAR-CT01 MAU-SB Airzone ZBS Wired Blueface Principal Controller White ❑AZZBSBLUEFACECB Airzone ZBS Wired Think Controller White ❑AZZBSTHINKCB Airzone ZBS Wireless Think Controller White ❑AZZBSTHINKRB Airzone ZBS Wired Lite Controller White ❑AZZBSLITECB Airzone ZBS Wireless Lite Controller White ❑AZZBSLITERB Wired Remote Sensor ❑PAC-SE41TS-E Wireless Temperature and Humidity Sensor ❑PAC-USWHS003-TH-1 Outside Air Sensor for MHK1 ❑MOS1 Flush Mount Remote Temperature Sensor ❑PAC-USSEN001-FM-1 System Control Interface ❑MAC-3331F-E Wireless Interface ❑PAC-USWHS002-WF-1 Thermostat Interface ❑PAC-US444CN-1 kumo station® ❑PAC-WHS01 HC-E USNAP Interface ❑PAC-WHS01 UP-E IT Extender ❑PAC-WHS011E-E BACnet®and MODBUS®Interface ❑PAC-UKPRC001-CN-1 External Fan/Heater Control Relay Adapter ❑CN24RELAY-KIT-CM3 Connector cable for remote display ❑PAC-SA88HA-EP Connector for CN32(remote on/off) ❑PAC-SE55RA-E Lockdown Bracket for Hand-held Remote Controllers ❑RCMKP1CB Remote Operation Adapters ❑PAC-SF40RM-E Blue Diamond Sensor Extension Cable—15 Ft. ❑C13-103 MegaBlue Advanced Blue Diamond Condensate Pump w/Reservoir&Sensor ❑X87-835-110 to 250V Advanced Blue Diamond Mini Condensate Pump w/Reservoir&Sensor(2081230V)[recommended] ❑X87-721 -208/230V Drain Pan Level Sensor ❑DPLS2 (30A/600V/UL)[fits 2"X 4"utility box]-Black ❑TAZ-MS303 (30A/600V/UL)[fits 2"X 4"utility box]-White ❑TAZ-MS303W Unable to use with wireless remote controller Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. ACCESSORIES: • 1 1 Air Outlet Guide ❑MAC-881 SG Optional Defrost Heater ❑MAC-640BH-U Hail Guard ❑HG-B4 Outdoor Unit 3-1/4 inch Mounting Base(Pair)-Plastic ❑DSD-400P Condensing Unit Mounting Pad 16"x 36"x 3" ❑ULTRILITEI Outdoor Unit Stand—12"High ❑QSMS1201 M Outdoor Unit Stand—18"High ❑QSMS1801 M Outdoor Unit Stand—24"High ❑QSMS2401M Heavy Duty Wall Mounting Bracket—Coated Steel ❑QSWB2000M-1 Heavy Duty Wall Mounting Bracket—316 Series Stainless Steel ❑QSWBSS 15'x 1/4"x 15'/3/8"Lineset(Twin-Tube Insulation) ❑MLS143812T-15 30'x 1/4"x 30'/3/8"Lineset(Twin-Tube Insulation) ❑MLS143812T-30 50'x 1/4"x 50'/3/8"Lineset(Twin-Tube Insulation) ❑MLS143812T-50 65'x 1/4"x 65'/3/8"Lineset(Twin-Tube Insulation) ❑MLS143812T-65 Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. 1 • 1 Opposite piping 378(14-15/16) 153(6-1/16) Note 1.Use an M10 screw for the suspension bolt side view (field supply). Drain a O.D o32 1-1/4 Fresh air intake o100(3-15/16) knock out hole 2.Keep the service space for maintenance (Emergency drain) 120� Note 4 at the bottom. Bottom l 3-o2.9(1/8)mount hoe ,t 331his drawing is for PEAD-A24-30.36-42 4= AA7 models,which have 2 fans.PEAD-A09- 0125 it, Inlet air I side view 12.15.18AA7 models have 1 fan. 18(3/4) 210(8-5/16) 4.If the inlet duct is used,remove the air 15(5/8) ToN filter(supplied with the unit),then 2xE-02.s 1/e install the filter(Feld supply)at the suction side. Outlet air Top 5.Heat air to D'C(32'F)or higher when side view I view I taking fresh air with a fresh air intake. LL n W X a Air filter Air Air o outlet inlet M n o " � r'n M __ o Unit:mm(in.) Model J (+DGas pipe DLiquid pipe 10(7/16) %'' 62 e9.52 06.35 N ' �/ PEAD-A09AA7 (2-1/2) (3/8) (1/4) PEAD-Al2,15, 62 o12.7 06.35 18AA7 (2-1/2) (1/2) (1/4) r (Suspension bolt pitch) C PEAD-A24,30AA7 66 015.88 o9.52 57(2-1/4) 643(25-3/8) N a (2-5/8) (5/8) (3/8) N PEAD-A36,42AA7 732(28-7/8) N 32(1-5/16) 700(27-9/16) '? v, 238(9-3/8) Drain pipe Drain pump Unit:mm(in.) Refrigerant piping(liquid) 10(7n6) (Integral liR pump outlet) Model A B C D E F G H a e (O.De32(1-1/4)) To PEAD-A09,12, 900 954 1000 860 800 858 72 15,18AA7(35-7/16) (37-9/16) (39-3/8) (33-7/8) 9 (31-1/2) (33-13/16) (2-7/8) 1100 1154 1200 1060 1000 1058 �T _ _ �, m PEAD-A24,30AA7(43-5116 45-7116 47-114 41-314 11 ( ) ( ) ( ) (39-3/8) (41-11116) 78 1400 1454 1500 1360 1300 1358 (3-1/8) t5 PEAD-A36,42AA7 (55-1/8) (57-1/41 (59-1116)153-9116114 (51-3/16) (53-1/2) Control box Bottom ^ .' of (1)Refrigerant piping(gas) Terminal block Transmission M (136) R 6716) Terminal block Power source Piping side view 356(14-1/16) Drain pipe(O.Do32(1-1/4))(Gravity drain) Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. DIMENSIONS: SUZ-KAl2NA2 Unit: inch(mm) REQUIRED SPACE '1 4 in. (100 mm)or more when front and sides of the unit are clear m 4. a� U �l ��� e (100 �Ore0z"J 15-3/4 v Air in Drain hole 01-21/32(KA09112/15NA) M n Drain hole 01-5/16(KA09n2n5NAH) �L 0 mml 74/n v Air in t o m o gir'l2 2 0,�5�� O N 01 C� Oro �J o i '^ 0 N N '2 When any 2 sides of left, right 1-9/16 and rear of the unit are clear Air our 2-holes 3/8x13/16 Service one[ 7/8 11/16 Handle Liquid refrigerant pipe joint Refrigerant pipe(flared)o 1/4 N N r - Gas refrigerant pipe joint N (V N Refrigerant pipe(flared)a 3/8(KA09/12) m Ln "' o 1/2(KA15) � N m 3 n 11-29/3 I 5-11/32 5-15/16 19-11/16 6-23/32 Bolt pitch for installation 31-1/2 2-3/4 MITSUBISHI ELECTRIC COOLING & HEATING 1340 Satellite Boulevard,Suwanee,GA 30024 Toll Free:800-433-4822 www.mehvac.com GIRIM % s FORM#PEAD-Al2AA7/SUZ-KAl2NA2-201901 Intertek Specifications are subject to change without notice. ©2019 Mitsubishi Electric Trane HVAC US LLC.All rights reserved. Optum Care Distribution Center TI ERV S / p0 ICOm19�-Energ Recovery ventilator FV-04VE1 FAN Specification Submittal Data /Panasonic Ventilation Fan 2 X 4°ducts / �a Description Grille: �18' Energy Recovery Ventilator provides a tempered •Attractive design using ABS material. air supply,humidity control,and a balanced •Attaches directly to housing with torsion amount of exhaust to help maintain neutral springs. / pressure throughout the home.Panasonic ERV Warranty: I �16Y shall not be installed in a bathroom.Only one .ALL Parts:For period of 3 years from the date I� o unit is needed for a 1,750 sq.ft.2 bedroom home to meet the ASHRAE 62.2 ventilation of the original purchase. � requirement. Architectural Specifications: Motor/Blower: ERV shall be of the ceiling mount type with no less than 40 CFM on the exhaust port,30 CFM •Totally enclosed AC condenser motor rated for on the supply port,and no more than 0.8 sone continuous run. as tested in accordance with HVI 915 and 916 •Power rating shall be 120 volts and 60 Hz. standards at 0.1 static pressure in inches water •Two highly efficient blower wheels running on gauge.Power consumption shall be no greater single motor for lower power consumption and than 23 watts.Apparent Sensible Effectiveness FV-04VE1 decreased noise. for heating shall be no less than 66%at 30 •Motor equipped with thermal cut-off fuse CFM net air flow under 32°F(0°C)as tested in Title-24,and WA Ventilation Code compliant. control. accordance with CSA-C439.Total Recovery Effectiveness for cooling shall be no less than ERV Core Technology: Housing: 36%at 29 CFM net air flow under 95°F(35,q. •Indoor and outdoor air passes through •Rust proof paint,galvanized steel body. The supply port damper shall close below 20°F Panasonic's capillary core technology. •Dual 4"intake and exhaust ducts. (-7°C)to prevent freezing of the core.The motor This process tempers supply air while •Built in backdraft damper on exhaust duct. shall be totally enclosed,AC condenser type transferring moisture and energy engineered to run continuously.Power rating •Built in Frost Prevention Mode prevents the •Filters on supply and exhaust air extend the shall be 120v/60Hz.Duct diameter shall be core from freezing.Frost Prevention Mode is free life of the ERV core. no less than 4". Fan shall be ASHRAE 62.2, of interaction and operates without intervention. •Expandable mounting bracket up to 16"on LEED,ENERGY STAR IAP,EarthCraft,California center. Performance: WhisperComfort FV-04VE1 Air Volume Setting 40 CFM 20 CFM 10 CFM 3 0.50 Static Pressure in inches w.g. 0.1 0.1 0.1 5 V 0.40 Exhaust Air Volume(CFM) 40 20 10 FV-04VE1 —(Exhaust) Supply Air Volume(CFM) 30 20 10 a` FV-04VE1 `—' 0.30 —(Supply) Noise(sones) 0.8 <0.3 N/A h — 20 Feet Power Consumption(watts) 23 21 17 • ----40 Feet 0.20 —'60 Feet Speed(RPM) 1479 1292 1095 ;' �� --80 Feet Current(amps) 0.15 0.10 0.09 100 Feet 0.10 Power Rating(V/Hz) 120/60 Energy Performance:WhisperComfort FV-04VE1 0.00 Apparent Sensible Effectiveness for Heating 66%at 30 CFM and 32°F(0°C) 0 10 20 30 40 50 60 Airflow(CFM) Total Recovery Efficiency for Cooling 36%at 29 CFM and 95°F(35°C) As of date 4/11 For complete Installation Instructions visit www.panasonic.com/building Model Quantity Comments Project: Location: Architect: Engineer: Contractor: Submitted by: Date: Panasonic Home and Environment Company Division of Panasonic Corporation of North America One Panasonic Way Secaucus,NJ 07094 www.panasonic.com/building cexnrieo �s m Panasonic ideas for life VF11144SS Optum Care Distribution Center TI FV Wh iserVaIue® DCfM Exhaust Fan -0510VS1 pN VENTILATION FA Specification Submittal Data / Panasonic Ventilation Fan 4" Oval duct Description: Ceiling Radiation Damper: ° Ventilating fan shall be Low Noise ceiling or wall •WhisperValue DC is UL listed for use with the mount type rated for continuous run. Fan shall Panasonic Ceiling Radiation Damper(Model#: be ENERGY STAR®rated and certified by the PC-RD05C5,sold separately). Home Ventilation Institute(HVI).Evaluated by Grille: Underwriters Laboratories and conform to both a �/ UL and cUL safety standards. •Attractive design using Poly Pro material. •Attaches directly to housing with torsion Motor/Blower: springs. •Enclosed DC brushless ECM motor Warranty: technology rated for continuous run. e DC Motor:6 Years from original purchase •Fan ventilation rates shall be manually date. FV-051OVS1 adjustable for 50-80-100 CFM. •ALL Parts:3 Years from original purchase •Power rating shall be 120 volts and 60 Hz. date. •Fan shall be UL and cUL listed for tub/shower 120V/60Hz.Duct diameter shall be no less enclosure when GFCI protected and used in Architectural Specifications: than 4".Optional 24 gauge steel,fire code insulated ceiling(TYPE I protected Ventilation fan shall be UL and cUL listed for rated 4"oval to 3"round duct adaptor sold •PCB beard equipped with thermal-cutoff ceiling or wall mount and tub/shower enclosure separately(Model#FV-VS43R).Fan can fuse. when GFCI protected.Fan shall also be be used to comply with ASHRAE 62.2, •Removable with permanently lubricated plug- ENERGY STAR°certified,with a built-in speed LEED,EarthCraft,California Title-24 and WA in motor. selector.Choose from 50-80-100 CFM and Ventilation Code. no more than<0.3/0.4/0.9 sone as certified Whis erValue Contractor Pack* Housing: by the Home Ventilating Institute(HVI)at 0.1 p •26 gauge galvanized steel body. static pressure in inches water gauge(w.g.) The Contractor Pack includes four complete •Built-in 4"Oval duct collar.Also compatible with no less than 53/81/100 CFM and no fans.The housing and motor/grille are packaged with 4"round duct. more than 0.5/0.8/1.3 sone as certified by HVI separately for flexibility during installation. •Optional 24 gauge steel,fire code rated at 0.25 w.g.Power Consumption shall be no te 4"oval to 3"round duct adaptor sold greater than 4.4/7.2/11.1 watts at 0.1 w.g.and g Motor/Grille Assembly ' ' - Fan nit separately(Model#FV-VS43R). 7.5/11.5/16.0 watts at 0.25 w.g.,with efficiency •Built in backdraft damper. of no less than 12.8/11.4/9.2 CFM/watt at 0.1 FV-0510VSA1 I FV-0510VSB1 I FV-0510VS1 1 4 •Built-in metal flange provides blocking for w.g.and 7.9/7.2/6.4 CFM/watt at 0.25 w.g.The penetrations through drywall as an Air Barrier, motor shall be totally enclosed with a brushless Must order in quantities of 4.Shipment will contain 1 box with 4 units. and assists with the decrease in leakage in the ECM motor engineered to run continuously. Building Envelope during blower door testing. ECM motor speed shall automatically increase Performance Curve 4"Oval duct •Unique L-shaped bracket simplifies installation when the fan senses static pressure to and provides strong support. maintain selected CFM.Power rating shall be 0.80 Specifications:WhisperValueDC FV 0510VS1 a"Oval a"Oval a"Oval r�., G Eu�50CFM a.eo --FV-0510V51 Static Pressure in inches w.g. 0.1 t 0.1 r 0.1 r 'o I _ 05 MOC M 3 0.50 FV 4&Wio0 CFM Air Volume(CFM) 100 100 80 81 50 53 `-� - c20nd- Noise(sones) 0.9 1.3 0.4 0.8 <0.3 0.5 2 040 t - Cann d­ Ventilation Fan Power Consumption(watts) 11.1 16.0 7.2 11.5 4.4 7.5 12 0.30 1 ,'� -seona c Characteristics Energy Efficiency(CFM/Watt) 9.2 6.4 11.4 7.2 12.8 7.9 2 ; -a a0nduc1 (HVI Certified Speed(RPM) 902 1121 797 1070 708 1025 N 020 -c10arcd- Data ` Current(amps) 0.20 0.27 0.13 0.20 0.09 0.14 o.10 MAX.Current(amps) 0.39 = a.0o Power Rating(V/Hz) 120/60 0 20 40 60 80 100 ENERGY STAR rated YES Airflow(CFM) 0.25=Installed Performance For complete Installation Instructions visit us.panasonic.com/ventfans Model Quantity Comments Project: Location: Architect: Engineer: Contractor: Submitted by: Date: Panasonic Eco Solutions North America ECM Motor Technology Eco Products Division �i;&Wn When the fan senses static pressure,its speed is automatically increased to ensure Two ark,NJ 0 Plaza that the desired CFM is not compromised,which allows the fan to perform as rated. Newark,NJ 07102 us.panasonic.com/ventfans ce M Ly J1. �s Panasonic VF16549SS0517 GENERAL \. 'ES REFRIGERANT HVAC LEGENDS HVAC LEGENDS z 0 G1 THESE DRAWINGS ARE DIAGRAMMATIC; THEY DO NOT SHOA E✓ERY OFFSET, BEND. TEE, OR H- ELBOW WHICH MAY BE REQUIRED TO INSTALL \ORK IX TUr SPACE PTO'.IDL ND AVOID 1, REFRIGERANT PIPING SHALL CONSIS ION OF ACR TYPE L COPPER TUBING WITH LONG RADIUS ROUND D CTWORK " " IL CONFLICTS. THE CONTRACTOR SHALL FOLLOW THE DRAWINGS AS LO Lv AS IS PRACTICAL WROUGHT COPPER FITTINGS TO DO SO AND INSTALL ADDITIONAL BENDS, OFFSETS, TEES, AND ELBON+S WHERE REQUIRED 2--� 12 x12 INDICATES UNLINED 12" x 12" SM DUCT CO BY LOCAL CONDITIONS FROM MEASUREMENTS TAKEN AT THE SITE, SUBJECT TO APPROVAL, 2. PURGE REFRIGERANT TUBING WITH NITROGEN GAS WHILE BRAZING WITH MINIMUM 6%SILVER 90 DEG BOW' p O AND WITHOUT ADDITIONAL COST TO THE OWNER. BRZING ROD 1.5 x DIA (R EG BO LS x DIA 12"A2"/W INDICATES UNLINED 12" x 12" SM DUCT G2 MECHANICAL SYSTEMS AND MATERIALS SHALL BH IN ACCORDANCE WITH THE FOLLOWING 3. PRIOR TO CHARGING SYSTEM WITH EFRIGERANT, PIPING SYSTEM SHALL BE PRESSURE WITH INSULATED WRAPLU CODES AND LOCAL AMENDMENTS: TESTED AND AND EVACUATED TO A VACUUM OF 500 MICRONS FOR A MINIMUM OF 30 m MINUIE PERIOD•2018 IN z= TERNATIONAL BUILDING CODE WITH WASHINGTON STATE AMENDMENTS (SUPPLY/OUTSIDE AIR) FLEXIBLE DUCT�® W •2018 INTERNATIONAL MECHANICAL CODE WITH WASHING.ON STATE AMENDMENTS 4. INSIH ATE ALL REFRIGERANT LINES 0 MEET THE WASHINGTON STATE ENFRCY CODE Q •2018 INTERNATIONAL FIRE CODE WITH WASHINGTON SIAIE AMENDM-N IS REQUIREMENTS. ALL EXTERIOR INS LATION SHALL BE UV RATED OR C,. R=D :',ITH UV � 90 DEG ELBOW(DOWN OR O i`C.G�(RETURN) �O 24"0 INDICATES ROUND DUCT •2018 INTERNATIONAL FUEL GAS CODE WITH WASHINGTON STATE AMENDMENTS PROTECTANT BARRIER AWA ) •2018 WASHY\G TON ENERGY CODE II r t (EXHAUST) G6 INSTALL ECUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. 1�� SPIN-IN TAKE-OFF& VOLUME DAMPER WITH Z :. RIGID ROUND SM DUCT G7 ALL TRADES TO LEAVE 30" OR 42" CLEAT NE IN FRONT OF MECHANICAL EQUIPMENT , ACCESS PANELS :OR SERVICING, PER NEC .F U!REMENTS. HVAC LEGENDS RISE OR DROP IN DIRECTION OF FLOW G8 PROVIDE MANUAL BALANCING DAMPERS :N ALL FINAL BRANCH DUCTS SERVING INLETS AND OUTLETS, AND' AS R=QUI3ED I i SJLL SYSTEM AIR BALANCING; INSTALL MANUAL 4 CIA J BALANCING DAMPERS AS FAR FROM INLET OR OiJTLET AS PRACTICAL CONDENSER WATER SUPPLY ®(SUPPLY/OUTSIDE AIR) t—A + co CONDENSER WATER RETURN DIFFUSER /GRILLE CALLOUT 90 DEG ELBO ; CONDFNS4 GRAIN �(RETURN) {UP OR �� } G9 DUCTWORK DIMENSIONS INDICATED ARE NET INSI E DIMENSIONS. TOWA ) REFRIGER V L UD S Y -- -- -- MAKE UP A F (EXHAUST) �� TYPE SIZE OR O G10 PROVIDE FIRE SEALANT AT PENETRATIONS OF FI E RATED ASSEMBLIES; CAULKING OR REFRIGERANT SUC"ION ciL1i �`CD-1 8x8��NECK SIZE __ ___ __ OTHER ADHESIVE SEALANTS Su AU_NOT BE USED T FILL VOIDS BETWEEN FIRE SPRINKLER 350 CFM W COVER PLATES AND o ALLS OR CG;IINGS /]� AIRFLOW---"' LU G11 CONTRACTOR SHALL VERIFY AT ALL EQUIPMENT, AS SHOWN ON THESE DRAWINGS, WILL �— PRESSURE REDUCING GATE VALVE FLU 45 DEG BOW f NOT CONFLICT WITH ANY SPANS, SCUTTLES, JC NTS -YTS, ETC. VALVE 'V�1.5 x DIA 15 x DIA- Y ,. Z LU G12 ALL OUTSIDE AIR INTAK-S SHALL BE A MINIMUM OF 10'-0" FROM ANY EXHAUST 101 BALL VALVE - CHECK VALVE - Z RECTANGULA DUCTWORK HVAC ABBREVIATIONS W TERMINATION OR PLUMBILG VENT. i U C13 VERY ' A_L WARRANTIES ON EQUIPMENT INSTALL D. TE ALL DUCT AND � GAS COCK �- THREE WAY VALVE � 90 DEG BILE)WWITH G14 COORDINATE AIR TERMINAL COCA IONS W9 TH CEILING PLAN AND LIGHTING TURNING ANES %P.G. PERCENT PROPYLENE GLYCOL HP HORSEPOWER LAYOUTS AS REQUIRED. DOUBLE REDUCED PRESSURE I . —� CHECK VALVE ASSEMBL RP9P REDUCED PRESENTER /CW CERAMIC WRAP HWR HEATING WATER RETURN G15 COORDIN4TE ALL REQUIRED OPENINGS AND EXCAVATIONS. ALL REQUIRED OPENINGS IN /PERE WITH INTERIOR PERFORATED METAL LINER HWS HEATNG WATER SUPPLY x FOUNDATIONS, FLOORS, WALLS AND ROOFS SHALL BE DESIGNED INTO THE STRUCTURE �/Ir-L /SL SOUND/ACUSTICAL LINED ID INS13L DIMENSION '4 INITIALt.Y BY THE USE OF SLEEVES, CURBS, ETC. CUTT',NS aND PATCHING SHALL BE HELD N T /W WRAPPED (INSULATED)DUCT INSUL. INSULATION TO A MINIMUM. HVAC I, '�I t 90 DEG EAWA DOWN OR �� AFF ABOVE FINISHED FLOOR KW KILOWATT Gib TRANSITION ALL DUCTS AS REQUIRED TO ATTAC TO EQUIPMENT CONNECTIONS. H VAIN EGENDS (W/TURNIN VANES) APR ACCESS PANEL LAT LEAVING AIR TEMPERAURE BDD BACKDRAFT DAMPER LPG UQUIFIRC PROPANE G17 OUTSIDE AIR AND EXHAUST AlR DAMPERS SHALLHAVE A MAXIMUM LEAKAGE RATE THAT DETAIL SYMBOL BHP BRAKE HORSE POWER LWT LEA✓NG AIR TEMPERATURE COMP✓E W H11 II OAS IN TON :-ATE ENERGY CODE. q G1 GENERAL NOTE- APPLIES TO BOP BO TCI✓ OF DUCT M MEZZ N,NE - A-IDENTIFYING NUMBER BOU B TOM CF UNIT M8H THOUSANDS BTU PER HOUR `./ ALL DRAWINGS �i�-� rn G18 PROVIDE f II " :J: RA_RS N P .'n CAN CL ,. H ASME 13.1 SCHEME FOR THE IDENTIFICATION 6-SHEET WHERE DETAIL IS SHOWN RED 7--® BTU BH ISI- HE4MAL UNIT MCA MIN IAUM CIRCUIT AMPANCITY OF PIPN S'_V BRAD'* LLAN, OR EQUAL DETAIL NOTE - APPLIES ONLY c�u 90 DEG ELB i'JP OR C.C. C NT:-JL 'ONTRATOR MHP MO F HORi_P;WER TO SPECIFIC DETAIL � TOWA D ?w CBBDD COON E BALANCE BACKDRAFT DAMPER MOP MAXIMI 4 0 ER CURRENT PROTECTION G19 HEAT Y CO^LNG AEOAU SA „O:_ATIONS, EQUIP ENT SIZING, AND DUCT LAYOUT TO W TURH'N„ VANES p q ELEVATION OR SECTION SYMBOL ( / ) CFM CJBIC L I .R MINUTE NA, N/A NO u L "B E - COMPLY WITH ASHRAE HANDBOOKS. POINT OF CONNECTION NOR 1 CI ;-D B A-IDENTIFYING NUMBER � i—® CO CARBrN MAR COS- NC G20 FURNISH ALL ACCESS PANELS. MOST ACCESS PANELS WILL BE COORD'NATFD WITH B-SHEET WHERE DETAIL IS SHOWN HWR C;,IL-L W AT-R RETURN NIC NO IN CONTRACT ARCHITECT. SOME OR ALL ACCESS PANELS MAY NOT APPEAR ON -HF ARCHITECTURAL CHWS CHILD WATER SUPPLY NO NORMALLY OPEN C21 UNIT WEIGHTS AND LOCAHONS HAVE BEEN COORDINATI) WHIT S QUIRE FIRE RATING CKTS CIRCUITS • ROM NOT N AL DRAWINGS. ARCHITECT SHALL DETERMINE WHICE ALCE S A CLG CEf_IG NTS NO` TO F- HMI MISCELLA EOUS HVAC TECT AND O NUMBERED KEYED NOTE. N SCLAE STRU T A. FN IAF R TO DETERMINE BUILD NG STRJ I PA -�.C-QJACY. IF IT IS APPLIES NI KEYED ITEM IN COP DOWN OF PERFORMAEE: CA OUTSIDE AIR THE iiR,-.ACING CONTAINING TH NOTE ONLY "- `� BOLS - N_CESORDI TO nELOOr.TL A UNIT, NOTIFY DK SYSIEII DES IGA ;F'ARTMENT FOR e D DOWN - OBD OPPOSED BLADE DAMPER y DB DRY BUILB OSA OUT 'DE AIR RE-COORDINATION. 1 MECHANICAL EQUIPMENT TAG DIA DIAMETER P.G. PR PYLENE GLYCOL ® SUPPLY DIFFU P GRILLE (FLOW.ARROWS DN DOWN PH PHASE INDICATE DIRECTION ^F BLOW. IF NO ARROWS G PIPE DOWN —O PIPE UP ARE SHOWN, DIFF ER IS 4-WAY BLOW.) DP Dj� RENTIAL FRESSURE POO POINT OF CONNECITON E_C. ELECTRICAL ONTRACTOR p/7 PRESSURE TEMPERATURE PORT EA _.CT /EXHELSi PRESS PR SIRE PIPE RISE OR x T BRANCH OFF RETU N GRILLE EAT LATER NG R IEt rRATC4E PRV PRL 'RE REDUCING VALVE SHEET pqf T MOTES -3 PIPE DROP �� BOTTOM/TOP FEE ENE PC hrFl ENC a T PSI POUNDS PER SQUARE INCH IVIC L IV PIPE TEE ESP EXTERN T�TC ESSU3F PSIG POUNDS PER SQUARE INCH GAUGE -III-- PIPE UNION —0 DOWN/UP ® EXHA ST GRILLE ENT -UI hIIJ. E: T 1PCRA"�? R RISE F. 1. DUCT SIZES INDIP TED OA II DR<.VNG ARE INST_DIMENSIONS. DUCT SIZE SHALL BE PC NS PE, VCI RA RETURN AIR PIPE REDUCER —�— PIPE COUPLING SIDEW LI_GRILLE EC F N\EC':iH RM ROOM PERMIT INCREASED TO N.,A ENSATL GR s.,CUSTICHL�GGI LIAEP. THICKNESS �� FD F P- L '_R RPM RE'OLU TIONS PER MINUTE c� 2. DUCT ELBOWS HALL BE RADIUS TYPE WITH FULL A D H TRROAT RADIUS ON ALL PRIMARY -� SUPPLY AN FLOW ARROW FEE F NI-r F P -VATION SA SUPPLY AIR ET DUCT WORK, UNLESS SHOWN OTHERWISE. TURNING VANE ELBOWS SHALL HAVE DG,BLF RETURN OR E RUST A.R FLOW FLA F M F -'G' SF SQUARE FOOT HVAC EGENDS FOB F AT N r T M SO SMOKE DETECTOR THICKNESS TURNING ANES INSTALI ED IN EVERY RAIL TAB. A <OW EDT F.AT V TO SEER SEASONAL ENERGY EFFICIENCY RATIO 3. EXHAL;S'DUCTWOR lP K S-A BE UNLINED GALVANIZED SHEET METAL(UNLESS OTHERWISE G.C. GENERAL CONTRACTOR TAD TO BE DETERMMED INDICATED". E'_B 1'S S I' 7CONS-RJC-EDL,A : A MINIMUM CENTERLINE ADG1S TO DUCT DIAMETER OF 1.: DUCT S'�ALL BE UY,NSULATED JNLESS OTH_RASE INDICATED. uKYEr'c GPM G 10STAT NATURAL A GALLONS PER MINUTE T-STAY SP STATIC PRESSURE EXHAUST DUCT SHALL NOT BE JOINED WITH SCREWS OR OTHER FASTENERS THAT PROTRUDE M NUAL VOLUME DAMPER DUCTWOR TRANSITIONS T GYP. GYPSUM (SHEETRGCK) TSP TOTOTAALL STATIC PRESSURE v MORE THEN 1/B" INTO THE INSIDE OF THE DUCT. FABRICATE AND SEAL EXHAUST DUCTWORK M TORIZED DAMPER TYP. TYP.CAL Z o PER SMACNA 1/2" PRESSURE CLASS SQUARE TO SQUARE Eu 1 a 1 0 4. ALL DUCTWORK SHALL BE SEALED V1.TH WATER BASED LATEX SEALANT PER WSEC AND OR ROU D TO ROUND SMACNA PRESSURE AND SEAL CLASSIFICATION BELOW: B CK DRAFT DAMPER ANGLE 30' o STATIC PR UR CONSTRUCTION CLASS SEAL.CLASS SEALING REQUIREMENTS OR LESS 1/2" - 2" wg C TRANSVERSE JOINTS ONLY S OKE DETECTORco 13 TRANSVERSE JOINTS AND SQUARE TO ROUND F LONGITUDINAL SEAMS F E DAMPER (1-1/2 HOUR) OUT OF AIRSTREAM SHEET INDEX 4" 10" wg ALL JOINTS, SEAMS, AND WALL R SKIN MODEL DIB2 STYLE B, VERTICAL MOUNT I PENETRATIONS F RE DAMPER (1-1/2 =3UR) OUT OF AI STREAMQUARE rr/^1 5. THROUGH PcNETRATIDN AND MEMBRANE PENET ATION FIRE STOP AS REQUIRED IN THE IBC R SK N MODEL DIB2 STYLE B HORIZON MOUNT j .,CT v/ SHALT BE PROVIDED AND INSTALLED 8Y THE M CHANICAL CONTRACTOR. FIRE STOP SYSTEM 3 HR F E DAMPER HJU R) OUT OF!I, `.M I f IJND a^�' N SHALL BE HILTI CIE 601 S OR 3M BRAND FIRE ARRIER SEALANT IC 15WA+ OR APPROVED R SK.N MODEL DIB2 STYLE B, VERII;: N'OUNT DUCT SHEE'NUMSER SHEETTITLE w ui co oa EQUI 4'_ENT. z 3 HR F RE DAMPER (3 HOUR) OUT OF I p n Ma 00 MECHANICAL COVERSHEET 6. ACCES:DRIES R SK\ MODEL DIB2 STYLE B, HORIZONTAL MOUNT MISCELLANEOUS CONTROLS W ; 8 A CK DRAFT DAMPER MD 07 MECHA4' ODE o ACUSTICAL LINER INDOORS: T THERMOSTAT OR Mc.02 MEC HAh ."EDUCES Q 1" THICK, FIBERGLASS DUCTLINER WITH BLACK MAT FACING. JOHNS MANVILLE, LINACOUSTIC R .,K N MODE'._ BD2/AT, LOCAL VELOCITY<1500 FPM HUMIDISTAT O Q j RC. �AV-1 TEMPERATURE SENSOR w/ rr ^. HEEHAW a PLAN U (MINIMUM INSTALLED R-VALUE TO BE PER WOES) B CK DRAFT DAMPER CONTROLLED UNIT Z ,,II H7S MECHF\"A IL1NINE CEILING PLAN C R SKIN MODEL BD2/A2, LOCAL VELOCITY<2500 FPM BSI SOLENOID ACTUATOR MOTOR ACTUATOR [,'I ATOR I,'I MUCH .C, .,JELEVE_PLAN 2 ACOUSTICAL LINER OUTDOORS: 2" THICK, FIBERGLASS DUCTLINER NTH BLACK MAT FACING. JOHNS MANVILLE, UNACOUSTIC RC. (MINIMUM INSTALLED R-VALUE TO BE PER WSEC) S ORE DAMPER REMOTE SENSOR 4'1` AV ='AILS � WI U SMOKE DETECTOR ®- l^.[^. A1.Jc _`ANES L^- N Z LOW PRESSURE INSULATED FLEX DUCT: HART COOLEY F-114, JPL PR-25, OR EgUAL. Ina.Oc ��A'v'Ca__oAD CALCu1ATi0N 0 LL N J C MBINATION SMOKE AND FIRE DAMPER TOTa_ 9 1 0 1 0 0 0 O Q a UNINSULATED VAPOR PROOF FLEX DUCT: THE MAFLEX S-LP. 12"x12" IND DATES 14" x 14" O.D. SHEETMETAL WITH - - Last Re%Ns1011 D3fE: 1" OUNDLINER(U.N.O.), 12" x 12"NET ID CLOP A.R.LI�IGTQN U DUCT INSULATION (INDOORS): REFLECTIX R-4. DUCT INSULATION 7/25/2023 i BUILDING DEPARTMENT 1° DUCT INSULATION (OUTDOORS): RELECTIX R-80 DUCT INSULATION APPROVED e"cw�a+we^': oanwz er: o_ Received MECHANICAL Dam 17�3g'- AUG o4?0 K.K K.D NO CHANGE$AUTHORIZED a COVERSHEET ONLESS APRRAI BYTHE V SCALE: NTS M 0.0 0 N WASHINGTON ENERGY CODE NOTES WASHINGTON ENERGY CODE NOTES WASHINGTON ENERGY CODE NOTES WASHINGTON ENERGY CODE NOTES z 0 C403,2 SYSTEM DESIGN. MECHANICAL SYSTEMS SHALL BE DESIGNED TO COMPLY WITH SECTIONS EXCEPTION: THE USE OF MIXED AIR T PERATURE LIMIT CONTROL SHALL BE Tab*G83.8.E.1 d C40,3 AND C403.2.2. WHERE ELEMENTS OF A BUILDINGS MECHANICAL SYSTEMS ARE EXCEPTIONS: PERMITTED FOR SYSTEMS THAT ARE B TH F.Coro,. ADDRESSED IN SECTIONS C403.3 THROUGH C4 3.13, SUCH ELEMENTS SHALL COMPLY WITH i. CONTROL OF HEATING OR COOLING PROVIDED BY TRANSFER AIR THAT WOULD OTHERWISE CONTROLLED FROM SPACE TEMPERATU E (SUCH AS SINGLE ZONE SYSTEMS) AND coe°o°ey.r.m r.,re•d r.aa•ira K BE EXHAUSTED. rac• sm• COo1n° 0y THE APPLICABLE PROVISIONS OF THOSE SECTIONS. HAVING COOLING CAPACITY LESS THAN 65,000 BTU/H. °+wW Z 2. VESTIBULE HEATING ONLY SYSTEMS RE PERMITTED TO BE CONTROLLED WITHOUT AN -- W C40322 VENTILATION AND EXHAUST. OUTDOOR AIR TEMPERATURE LOCKOUT WHEN CONTROLLED BY A THERMOSTAT LOCATED IN C403.5.3.3 HIGH-LIMIT SHUTOFF. AIR ECONOMIZES SHALL BE CONFIGURED TO AUTOMATICALLY O C C403.2.2.1 VENTILATION. VENTILATION, EITHER ATURAL OR MECHANICAL, SHALL BE THE VESTIBULE CONFIGURED TO LIMI HEATING TO A TEMPERATURE NOT GREATER THAN REDUCE OUTDOOR AIR INTAKE TO THE DESI N MINIMUM OUTDOOR AIR QUANTITY WHEN Me S PROVIDED IN ACCORDANCE WITH CHAPTER 4 F THE INTERNATIONAL MECHANICAL CODE. 45F(7'C) WHERE REQUIRED FOR FREEZE PROTECTION OF PIPING AND SPRINKLER HEADS OUTDOOR AIR INTAKE WILL NO LONGER RED CE COOLING ENERGY USAGE. HIGH-LIMIT a eano "'" E WHERE MECHANICAL VENTILATION IS PROVIDED, THE SYSTEM SHALL BE CONFIGURED TO LOCATED IN THE VESTIBULE. SHUTOFF CONTROL TYPES SHALL BE CHOSE I FROM TABLE C403.5.3.3. HIGH-LIMIT SHUTOFF IY PROVIDE NO GREATER THAN 150 PERCENT OF THE MINIMUM OUTDOOR AIR REQUIRED BY CONTROL SETTINGS FOR THESE CONTROL T ES SHALL BE THOSE SPECIFIED IN TABLE C403.10 CONSTRUCTION OF HVAC SYSTEM ELEMENTS, DUCTS, PLENUMS, PIPING AND OTHER CHAPTER 4 OF THE INTERNATIONAL MECHANIC L CODE OR OTHER APPLICABLE CODE OR 4 WATER BOILER OUTDOOR EMPERATURE SETBACK CONTROL, HOT WATER BOILERS C403.5.3.3 ELEMENTS THAT ARE PART OF AN HVAC SYSTEM SHALL BE CONSTRUCTED AND INSULATED li! STANDARD, WHICHEVER IS GREATER. THAT SUPPLY HEAT TO THE BUILDIN THROUGH ONE- OR TWO-PIPE HEATING SYSTEMS IN ACCORDANCE WITH SECTIONS C403.10.1 THROUGH C403.10.3.1 SHALL HAVE AN OUTDOOR SETBACK CONTROL THAT LOWERS THE BOILER WATER C403.5.3.4 RELIEF OF EXCESS OUTDOOR AIR. SY TEMS SHALL BE CAPABLE OF RELIEVING p C403.3 EQUIPMENT SELECTION. HEATING AND COOLING EQUIPMENT INSTALLED IN MECHANICAL TEMPERATURE BASED ON THE OUTO OR TEMPERATURE. EXCESS OUTDOOR AIR DURING AIR ECONOMI ER OPERATION TO PREVENT C403.10.1 DUCT AND PLENUM INSULATION AND SEALING. SYSTEMS SHALL BE SIZED IN ACCORDANCE WITH SECTION C403.3.1 AND SHALL BE NOT OVER-PRESSURIZING THE BUILDING. THE RE IEF AIR OUTLET SHALL BE LOCATED TO AVOID C403.10.1.1 DUCTS CONVEYING OUTDOOR AIR, DUCTS, SHAFTS AND PLENUMS CONVEYING LESS EFFICIENT IN THE USE OF ENERGY THAN AS SPECIFIED IN SECTION C403.3.2. DOORS THAT OPEN TO RECIRCULATION INTO THE BUILDING. OUTDOOR AIR FROM THE EXTERIOR OF THE BUILDING TO THE MECHANICAL SYSTEM SHALL O.-N M tiaD W O THE OUTDOORS FROM A CONDITIONEI SPACE MUST HAVE CONTROLS CONFIGURED TO DO MEET ALL AIR LEAKAGE AND BUILDING ENVELOPE INSULATIONREQUIREMENTS OF SECTION Z C403.3.1 EQUIPMENT AND SYSTEM SIZING. THE OUTPUT CAPACITY OF HEATING AND THE FOLLOWING ONCE DOORS HAVE IEEN OPEN FOR 5 MINUTES: C403.5.3.5 ECONOM17ER DAMPERS, RETURN, EXIT,UST/RELIEF AND OUTDOOR AIR DAMPERS USED C402, PLUS BUILDING ENVELOPE VAPOR CONTROL REQUIREMENTS FROM THE INTERNATIONAL COOLING EQUIPMENT SHALL BE NOT GREATER THAN THAT OF THE SMALLEST AVAILABLE 1. DISABLE THE MECHANICAL HEATING TO THE ZONE OR RESET THE SPACE HEATING IN ECONOMIZERS SHALL COMPLY WITH SEC TI N 0403.7.8. BUILDING CODE, EXTENDING CONTINUOUSLY FROM THE BUILDING EXTERIOR TO AN EQUIPMENT SIZE THAT EXCEEDS THE LOADS CALCULATED IN ACCORDANCE WITH SECTION TEMPERATURE SET POINT TO 55'F R LESS WITHIN 5 MINUTES OF THE DOOR OPEN AUTOMATIC SHUTOFF DAMPER OR HEATING OR COOLING EQUIPMENT. FOR THE PURPOSES C403.1.2. A SINGLE PIECE OF EQUIPMENT PROVIDING BOTH HEATING AND COOLING SHALL ENABLE SIGNAL. Q403AIR-COOLED UNITARY OF BUILDING ENVELOPE INSULATION REQUIREMENTS, DUCT SURFACES SHALL BE SATISFY THIS PROVISION FOR ONE FUNCTION WITH THE CAPACITY FOR THE OTHER 2. DISABLE THE MECHANICAL COOLING 0 THE ZONE OR RESET THE SPACE COOLING DIRECT-EXPANSION UNITS WITH A COOLING APACITY OF 54,000 BTU/H OR GREATER INSULATED WITH THE MINIMUM INSULATION VALUES IN TABLE C403.10.1.1. DUCT SURFACES 7 FUNCTION AS SMALL AS POSSIBLE, WITHIN AVAILABLE EQUIPMENT OPTIONS. TEMPERATURE SET POINT TO 85 7R MORE WITHIN 5 MINUTES OF THE DOOR OPEN INCLUDED AS PART OF THE BUILDING ENVELOPE SHALL NOT BE USED IN THE CALCULATION „cq ENABLE SIGNAL. LISTED IN TABLES C403.3.2(1) THROUGH C4 3.3.2(3) THAT ARE EQUIPPED WITH AN OF MAXIMUM GLAZING AREA AS DESCRIBED IN SECTION C402.4.1. ? j EXCEPTIONS ECONOMIZER IN ACCORDANCE WITH SECTION C403.5 SHALL INCLUDE A FAULT DETECTION 1. REQUIRED STANDBY EQUIPMENT AND SYSTEMS PROVIDED NTH CONTROLS AND DEVICES EXCEPTIONS: AND DIAGNOSTICS (FDD) SYSTEM. EXCEPTIONS: THAT ALLOW SUCH SYSTEMS OR EQUIPMENT TO OPERATE AUTOMATICALLY ONLY WHEN THE 1. BUILDING ENTRANCES WITH VESTIBUL S. 1. OUTDOOR AIR DUCTS SERVING INDIVIDUAL SUPPLY AIR UNITS WITH LESS THAN 2,800 CFM fA PRIMARY EQUIPMENT IS NOT OPERATING. 2. ALTERATIONS TO EXISTING BUILDING C403.7 VENTILATION AND EXHAUST SYSTEMS. IN ADDITION TO OTHER REQUIREMENTS OF SECTION OF TOTAL SUPPLY AIR CAPACITY, PROVIDED THESE ARE INSULATED TO THE MINIMUM Y - 2. MULTIPLE UNITS OF THE SAME EQUIPMENT TYPE WITH COMBINED CAPACITIES EXCEEDING 3. LOADING DOCKS. C403 APPLICABLE TO THE PROVISIONS OF NTILATION AIR OR THE EXHAUST OF AIR, INSULATION VALUES IN TABLE C403.10.1.1. THE DESIGN LOAD AND PROVIDED WITH CONTROLS THAT ARE CONFIGURED TO SEQUENCE VENTILATION AND EXHAUST SYSTEMS SHALL BE IN ACCORDANCE NTH SECTIONS C403.7.1 2. UNHEATED EQUIPMENT ROOMS WITH COMBUSTION AIR LOUVERS, PROVIDED THEY ARE ' THE OPERATION OF EACH UNIT BASED ON LOPID. C403.4.2 OFF-HOUR CONTROLS, FOR ALL OCCUPANCIES OTHER THAN GROUP R, EACH ZONE THROUGH C403.7.8. ISOLATED FROM CONDITIONED SPACE AT SIDES, TOP AND BOTTOM OF THE ROOM WITH R-11 W SHALL BE PROVIDED WITH THERMOSTATIC SETBACK CONTROLS THAT ARE CONTROLLED BY NOMINAL INSULATION. C40 HVAC PE RFORMAN REQUIREMENTS, EQUIPMENT SHALL MEET THE MINIMUM EITHER AN AUTOMATIC TIME CLOCK OR PROGRAMMABLE CONTROL SYSTEM. C403.7.8 SHUTOFF DAMPERS, MECHANICAL OPENI JOS SHALL BE PROVIDED WITH SHUTOFF m EFFICIENCY REQUIREMENTS OF TABLES C403.3.2(1) THROUGH C403.3.2(12) WHEN TESTED DAMPERS IN ACCORDANCE WITH SECTIONS 403.7.8.1 THROUGH 0403.7.8.4. °uroaw'un`°°uceprviw•161w°,x,+ram. AND RATED IN ACCORDANCE WITH THE APPLICABLE TEST PROCEDURE. PLATE-TYPE C403.4-2.1 THERMOSTATIC SETBACK, THERMOSTATIC SETBACK CONTROLS SHALL BE CONFIGURED w. Z LIQUID-TO-LIQUID HEAT EXCHANGERS SHALL MEET THE MINIMUM REQUIREMENTS OF TABLE TO SET BACK OR TEMPORARILY OPERATE THE SYSTEM TO MAINTAIN ZONE TEMPERATURES OUTDOOR AIR SUPPLY, EXHAUST ar ,eh. UJ C403.3.2(10). DOWN TO 55'F(13'C) OR UP TO 85' (29'C). OPENINGS AND RELIEF OUTLETS AND STAIR AY AND ELEVATOR HOISTWAY SHAFT VENTS SHALL BE PROVIDED WITH CLASS I MOTORIZ D DAMPERS, SEE SECTIONS C403.10.1 AND W GAS-FIRED AND OIL-FIRED FORCED AIR FURNACES WITH INPUT RATINGS OF 225,000 C403.4.2.2 AUTOMATIC AUTOMATIC TIME CLOCK OR PROGRAMMABLE C403.10.2 FOR DUCTWORK INSULATION REQ IREMENTS UPSTREAM AND DOWNSTREAM OF BTU/H (65 KW) OR GREATER AND ALL UNIT HEATERS SHALL ALSO HAVE AN INTERMITTENT CONTROLS SHALL BE CAPABLE OF S ARTING AND STOPPING THE SYSTEM FOR SEVEN THE SHUTOFF DAMPER. DIFFERENT DAILY SCHEDULES PER W EK AND RETAINING THEIR PROGRAMMING AND TIME EXCEPTIONS: G J IGNITION OR INTERRUPTED DEVICE(HID), AND HAVE EITHER MECHANICAL DRAFT(INCLUDING SETTING DURING A LOSS OF POWER OR AT LEAST 10 HOURS. ADDITIONALLY, THE 1, GRAVITY(NONMOTORIZED) DAMPERS SHALL 3E PERMITTED IN LIEU OF MOTORIZED DAMPERS +. POWER VENTING) OR A FLUE DAMPER. A VENT DAMPER IS AN ACCEPTABLE ALTERNATIVE CONTROLS SHALL HAVE A MANUAL VERRIDE THAT ALLOWS TEMPORARY OPERATION OF AS FOLLOWS: TO A FLUE DAMPER FOR FURNACES WHERE COMBUSTION AIR IS DRAWN FROM THE THE SYSTEM FOR UP TO 2 HOURS; k MANUALLY OPERATED TIMER CONFIGURED TO 1.1. RELIEF DAMPERS SERVING SYSTEMS LESS T AN 5,000 CFM TOTAL SUPPLY SHALL BE CONDITIONED SPACE. ALL FURNACES WITH INPIJT RATINGS OF 225,000 BTU/H (65 KW) OR OPERATE THE SYSTEM FOR UP TO 2 HOURS; OR AN OCCUPANCY SENSOR. PERMITTED IN BUILDINGS LESS THAN THREE STORIES IN HEIGHT. GREATER, INCLUDING ELECTRIC FURNACES, THAT ARE NOT LOCATED WITHIN THE 1.2. GRAVITY(NONMOTORIZED) DAMPERS WHERE THE DESIGN OUTDOOR AIR INTAKE OR EXHAUST CONDITIONED SPACE SHALL HAVE JACKET LOS ES NOT EXCEEDING 0.75 PERCENT OF THE C403.4.2.3 AUTOMATIC START AND STOP, AUTOMATIC START AND STOP CONTROLS SHALL BE CAPACITY DOES NOT EXCEED 400 CFM (189 L/S). C403.10.1.2 OTHER SUPPLY AND RETURN DUCTS. ALL OTHER SUPPLY AND RETURN AIR DUCTS INPUT RATING. PROVIDED FOR EACH HVAC SYSTEM. THE AUTOMATIC START CONTROLS SHALL BE 1.3. SYSTEMS SERVING AREAS WHICH REQUIRE C NTINUOUS OPERATION FOR 24/7 OCCUPANCY AND PLENUMS SHALL BE INSULATED WITH A MINIMUM OF R-6 INSULATION WHERE LOCATED IN CONFIGURED TO AUTOMATICALLY AD ST THE DAILY START TIME OF THE HVAC SYSTEM IN SCHEDULES. UNCONDITIONED SPACES, AND WHERE LOCATED OUTSIDE THE BUILDING WITH A MINIMUM OF R-8 C40.4 HVAC CONTROLS, HVAC SYSTEMS ALL BE PROVIDED WITH CONTROLS IN ORDER TO BRING EACH SPACE TO TIE DESIRED OCCUPIED TEMPERATURE IMMEDIATELY INSULATION IN CLIMATE ZONE 4 AND R-12 INSULATION IN CLIMATE ZONE 5. WHERE LOCATED ACCORDANCE WITH SECTIONS C403.4.1 THROUGH C403.4.11 AND SHALL BE CAPABLE OF PRIOR TO SCHEDULED OCCUPANCY. HE AUTOMATIC STOP CONTROLS SHALL BE 2. SHUTOFF DAMPERS ARE NOT REQUIRED IN: WITHIN A BUILDING ENVELOPE ASSEMBLY, THE DUCT OR PLENUM SHALL BE SEPARATED FROM AND CONFIGURED TO IMPLEMENT ALL REQUIRE CONTROL FUNCTIONS IN THIS CODE. CONFIGURED TO REDUCE THE HVAC YSTEM5 HEATING TEMPERATURE SET POINT AND THE BUILDING EXTERIOR OR UNCONDITIONED OR EXEMPT SPACES BY MINIMUM INSULATION VALUE 2.1. COMBUSTION AIR INTAKES. AS REQUIRED FOR EXTERIOR WALLS BY SECTION C402.1.3. C403 41 THERMOSTATIC CONTROLS. THE SUPP Y OF HEATING AND COOLING ENERGY TO INCREASE THE COOLING TEMPERATUFE SET POINT BY AT LEAST 27(1.1'C) BEFORE 2.2. SYSTEMS SERVING AREAS WHICH REQUIRE C NTINUOUS OPERATION IN ANIMAL HOSPITALS, SCHEDULED UNOCCUPIED PERIODS BASED UPON THE THERMAL LAG AND ACCEPTABLE DRIFT KENNELS AND POUNDS, LABORATORIES, AN GROUP H, I AND R OCCUPANCIES. r EACH ZONE SHALL BE CONTROLLED BY INDIVIDUAL THERMOSTATIC CONTROLS CAPABLE OF EXCEPTIONS: IN SPACE TEMPERATURE THAT IS WI THIN COMFORT LIMITS. AT A MINIMUM, THE CONTROLS 2.3. SUBDUCT EXHAUST SYSTEMS OR OTHER SYSTEMS THAT ARE REQUIRED TO OPERATE RESPONDING TO TEMPERATURE WITHIN THE ZO E. CONTROLS IN THE SAME ZONE OR IN Q+ SHALL BE A FUNCTION OF THE SPA(E TEMPERATURE, OCCUPIED AND UNOCCUPIED CONTINUOUSLY BY THE INTERNATIONAL MECIIANICAL CODE. ro NEIGHBORING ZONES CONNECTED BY OPENINGS LARGER THAN 10 PERCENT OF THE FLOOR TEMPERATURES, AND THE AMOUNT TIME PRIOR TO SCHEDULED OCCUPANCY. 2.4. TYPE I GREASE EXHAUST SYSTEMS OR OTH R SYSTEMS WHERE DAMPERS ARE PROHIBITED 1. WHERE LOCATED WITHIN EQUIPMENT. AREA OF EITHER ZONE SHALL NOT ALLOW FO SIMULTANEOUS HEATING AND COOLING. AT 2. SUPPLY AND RETURN DUCTWORK LOCATED IN UNCONDITIONED SPACES WHERE THE DESIGN qq�� BY THE INTERNATIONAL MECHANICAL CODE 0 BE IN THE AIRSTREAM. D] A MINIMUM, EACH FLOOR OF A BUILDING SHALLBE CONSIDERED AS A SEPARATE ZONE. q 3 4. 4 F- FOR ALL OCCUPANCIES OTHER THAN GROUP 2.5. UNCONDITIONED STAIRWELLS OR UNCONDIT10 ED ELEVATOR HOISTWAY SHAFTS THAT ARE TEMPERATURE DIFFERENCE BETWEEN THE INTERIOR AND EXTERIOR OF THE DUCT OR PLENUM 0 CONTROLS ON SYSTEMS REQUIRED TO HAVE ECONOMIZERS AND SERVING SINGLE ZONES R, EXHAUST SYSTEMS SERVING SPACES WITHIN THE CONDITIONED ENVELOPE SHALL BE ONLY CONNECTED TO UNCONDITIONED SPAC S.C403.7.8.2 SHUTOFF DAMPERS FOR RETURN DOES NOT EXCEED 15-F(8'C) AND INSULATED IN ACCORDANCE WITH TABLE C403.10.1.2. SHALL HAVE MULTIPLE COOLING STAGE CAPABILITY AND ACTIVATE THE ECONOMIZER WHEN CONTROLLED BY EITHER AN AUTOMA IC TIME CLOCK, THERMOSTATIC CONTROLS OR AIR. RETURN AIR OPENINGS USED FOR AIRS E ECONOMIZER OPERATION SHALL BE WHERE LOCATED WITHIN CONDITIONED SPACE, SUPPLY DUCTS WHICH CONVEY SUPPLY AIR AT APPROPRIATE AS THE FIRST STAGE OF COOLING. SEE SECTION C403.5 FOR FURTHER PROGRAMMABLE CONTROL SYSTEM To OPERATE ON THE SAME SCHEDULE AS THE HVAC EQUIPPED WITH CLASS I MOTORIZED DAMPEF S. TEMPERATURES LESS THAN 55F OR GREATER THAN 105-F SHALL BE INSULATED WITH A MINIMUM ECONOMIZER REQUIREMENTS.WHERE HUMIDIFICATION OR DEHUMIDIFICATION OR BOTH IS SYSTEMS PROVIDING THEIR MAKE-UP AIR. INSULATION R-VALUE IN ACCORDANCE WITH TABLE C403.10.1.2. PROVIDED, AT LEAST ONE HUMIDITY CONTROL DEVICE SHALL BE PROVIDED FOR EACH C403.7.8.3 DAMPER LEAKAGE RATING, CLASS I D MPERS SHALL HAVE A MAXIMUM LEAKAGE HUMIDITY CONTROL SYSTEM. EXCEPTIONS: RATE OF 4 CFM/FT2(20.3 L/S X M2) AT 10 INCH WATER GAUGE (W.G.) (249 PA) WHEN EXCEPTION: DUCTWORK EXPOSED TO VIEW WITHIN A ZONE THAT SERVES THAT ZONE IS NOT TESTED IN ACCORDANCE WITH AMCA 500D ND SHALL BE LABELED BY AN APPROVED REQUIRED TO BE INSULATED. EXCEPTIONS: 1: EXHAUST SYSTEMS REQUIRING CONTINUOUS OPERATION. AGENCY FOR SUCH PURPOSE. GRAVITY(NO MOTORIZED) DAMPERS SHALL HAVE AN AIR WHERE LOCATED WITHIN CONDITIONED SPACE, RETURN OR EXHAUST AIR DUCTS THAT CONVEY 2. EXHAUST SYSTEMS THAT ARE CONTROLLED BY OCCUPANCY SENSOR CONTROL CONFIGURED 1. INDEPENDENT PERIMETER SYSTEMS THAT ARE DESIGNED TO OFFSET ONLY BUILDING WITH AUTOMATIC ON AND AUTOMATIC SHUTOFF WITHIN 15 MINUTES AFTER OCCUPANTS LEAKAGE RATE NOT GREATER THAN 20 CFM FT2 WHERE NOT LESS THAN 24 INCHES (610 RETURN OR EXHAUST AIR DOWNSTREAM OF ENERGY RECOVERY MEDIA SHALL BE INSULATED ENVELOPE HEAT LOSSES OR GAINS OR BOTH ERVING ONE OR MORE PERIMETER ZONES HAVE LEFT THE SPACE. MM) IN EITHER DIMENSION AND 40 CFM/FT WITH WHERE LESS THAN 24 INCHES IN EITHER WITH A MINIMUM R-VALUE IN ACCORDANCE WITH TABLE C403.10.1.2. ALSO SERVED BY AN INTERIOR SYSTEM PROV1 ED: DIMENSION. THE RATE OF AIR LEAKAGE SHA L BE DETERMINED AT 1.0 INCH W.G. (249 PA) ALL DUCTS, AIR HANDLERS, AND FILTER BOXES SHALL BE SEALED. JOINTS AND SEAMS SHALL 1.1. THE PERIMETER SYSTEM INCLUDES AT LEAST ONE THERMOSTATIC CONTROL ZONE FOR EACH DIRECT DIGITAL CONTROL(DDC) SHALL BE WHEN TESTED IN ACCORDANCE WITH AMCA iOOD FOR SUCH PURPOSE, THE DAMPER SHALL COMPLY WITH SECTION 603.9 OF THE INTERNATIONAL MECHANICAL CODE BUILDING EXPOSURE HAVING EXTERIOR WALLS rACING ONLY ONE ORIENTATION (WITHIN REQUIRED AS SPECIFIED IN SECTIONS C403.4.11.1 THROUGH C403.4.11.3. BE LABELED BY AN APPROVE AGENCY. GRA ITY DAMPERS FOR VENTILATION AIR INTAKES _ +/-45 DEGREES) (0.8 RAD) FOR MORE THAN 50 CONTIGUOUS FEET(15,240 MM): SHALL BE PROTECTED FROM DIRECT EXPOS RE TO WIND. TAI°LE C4W.10.1.2 1.2. THE PERIMETER SYSTEM HEATING AND COOUN SUPPLY IS CONTROLLED BY A THERMOSTAT C403.4.11.1 DOC APPLICATIONS. DDC SHA L BE PROVIDED IN THE APPLICATIONS AND SUPPLY,RETURN,E1DIAU5T.•.d RELIEF AIR DutTwonK INSULATION LOCATED WITHIN THE ZONES SERVED BY THESYSTEM; AND QUALIFICATIONS LISTED IN TABLE C4 3.4.11.1. EXCEPTIONS: 1.3. CONTROLS ARE CONFIGURED TO PREVENT THE PERIMETER SYSTEM FROM OPERATING IN A 1. GRAVITY(NONMOTORIZED) DAMPERS ARE N T REQUIRED TO BE TESTED TO VERIFY THE AIR DIFFERENT HEATING OR COOLING MODE FROM HE OTHER EQUIPMENT WITHIN THE ZONES OR C4034.11.2 DDC CONTROLS, WHERE DDC REQUIRED BY SECTION C403.4.11.1, THE DDC SYSTEM LEAKAGE RATING WHEN INSTALLED IN EXHAI.ST SYSTEMS WHERE THE EXHAUST CAPACITY Darn oua�.a.E°n ra uw z Owl Nan FROM NEIGHBORING ZONES CONNECTED BY OP NINGS LARGER THAN 10 PERCENT OF THE SHALL BE CAPABLE OF ALL OF THE FOLLOWING, AS REQUIRED TO PROVIDE THE SYSTEM DOES NOT EXCEED 400 CFM (189 L/S) AN THE GRAVITY DAMPER IS PROVIDED WITH A FLOOR AREA OF EITHER ZONE. AND ZONE CONTROL LOGIC REQUIRE IN SECTIONS C403.2, C403.4.3, C403.5, AND GASKETED SEAL. w •ti,a anw m.w+aro ioaa°.,.w C403.6.8: 2. MOTORIZED DAMPERS ON RETURN AIR OPEN GS IN UNITARY PACKAGED EQUIPMENT THAT .,, 2. ANY INTERIOR ZONE OPEN TO A PERIMETER Z NE SHALL HAVE SET POINTS AND DEAD HAVE THE MINIMUM LEAKAGE RATE AVAILAB E FROM THE MANUFACTURER. ems' PERMIT BANDS COORDINATED SO THAT COOLING IN TH INTERIOR ZONE SHALL NOT OPERATE WHILE SwpyNr P_ uApOA4'"niO iO•°"'ntloi00"' +c."a °s s•a�u°ar°.vaa 1. MONITORING ZONE AND SYSTEM DEM ND FOR FAN PRESSURE, PUMP PRESSURE, HEATING „ann.w+aro aaax•.,.a ae THE PERIMETER ZONE IS IN HEATING UNTIL TH INTERIOR ZONE TEMPERATURE IS 57 AND COOLING. � C403.7.8.4 DAMPER ACTUATION. OUTDOOR AIR IN AKE, RELIEF AND EXHAUST SHUTOFF DAMPERS +"' �,..ao•I 6B eiWf SET (2.8'C) HIGHER THAN THE PERIMETER ZONE TEMPERATURE, UNLESS THE INTERIOR AND 2. TRANSFERRING ZONE AND SYSTEM D MAND INFORMATION FROM ZONES TO AIR DISTRIBUTION SHALL BE INSTALLED WITH AUTOMATIC CONIROLS CONFIGURED TO CLOSE WHEN THE urca,.,esw w.0 w.°„wa 5•.we s.+wo e°a�z br PERIMETER ZONES ARE SEPARATED BY A PAR 7ON WHOSE PERMANENT OPENINGS ARE SYSTEM CONTROLLERS AND FROM Al DISTRIBUTION SYSTEMS TO HEATING AND COOLING SYSTEMS OR SPACES SERVED ARE NOT IN IISE OR DURING UNOCCUPIED PERIOD WARM-UP sway A•w R...n crrwp warhwM,n ia•frw. w•„a asa .een.,r.°r• •lu SMALLER THAN 10 PERCENT OF THE PERIMETER ZONE FLOOR AREA. PLANT CONTROLLERS. AND SETBACK OPERATION, UNLESS THE SYSTEMS SERVED REQUIRE OUTDOOR OR EXHAUST "' a•°iPiO"° °e °onw.+.°on .r AIR IN ACCORDANCE WITH THE INTERNATION L MECHANICAL CODE OR THE DAMPERS ARE O1C1Wp1t C403.4.11.3 DDC DISPLAY, WHERE DDC IS REQUIRED BY SECTION C403.4.11.1 FOR NEW 3. DEDICATED OUTDOOR AIR UNITS THAT PROVIDE VENTILATION AIR,MAKE-UP AIR OR OPENED TO PROVIDE INTENTIONAL ECONOM R COOLING. STAIRWAY AND ELEVATOR sway Mer n.°„n .u.mery �„ M,,,yo, REPLACEMENT AIR FOR EXHAUST SYSTEMS AR PERMITTED TO BE CONTROLLED BASED ON BUILDINGS, THE DDC SYSTEM SHALL E CAPABLE OF TRENDING AND GRAPHICALLY HOISTWAY SHAFT VENT DAMPERS SHALL BE INSTALLED WITH AUTOMATIC CONTROLS �: sa R''° „ ,° 0ywpi SUPPLY AIR TEMPERATURE, THE SUPPLY AIR MPERATURE SHALL BE CONTROLLED TO A DISPLAYING INPUT AND OUTPUT POINTS. CONFIGURED TO OPEN UPON THE ACTIVATION OF ANY FIRE ALARM INITIATING DEVICE OF MAXIMUM OF 65-F(18.3'C)IN HEATING AND A MINIMUM OF 72-F(22'C) IN COOLING UNLESS THE BUILDINGS FIRE ALARM SYSTEM OR THE INTERRUPTION OF POWER TO THE DAMPER. w;u,,,eaeea,.a w..e.,,,,,a. •e r,a 7 s THE SUPPLY AIR TEMPERATURE IS BEING REST BASED ON THE STATUS OF COOLING OR 4 .1 RATE CO 0 ER CO ECONOMIZER SYSTEMS SHALL BE INTEGRATED WITH suwry.0 wwa a.x+e..+°n wmr.h,. a.aa aw. L "`°°'•°'9"•�"°""'°°'f O c HEATING IN THE ZONES SERVED OR IT BEING ESET BASED ON OUTDOOR AIR THE MECHANICAL COOLING SYSTEM AND CONFIGURED TO.PROVIDE PARTIAL COOLING C403.8.5 FAN CONTROLS, CONTROLS SHALL BE OVIDED FOR FANS IN ACCORDANCE WITH TEMPERATURE. EVEN WHERE ADDITIONAL MECHANIC COOLING SECTION C403.8.5.1 AND AS REQUIRED FOR SPECIFIC SYSTEMS PROVIDED IN SECTION C403.LING IS REQUIRED TO PROVIDE THE REMAINDER wa,"m�ew,,.a•..•..r.»aun s.a«n^"o'°a�°+.xro. Can3.41.1 HEAT PUMP SUPPLEMENTARY HEAT. UNI ARY AIR COOLED HEAT PUMPS SHALL OF THE COOLING LOAD. CONTROLS ALL NOT BE CAPABLE OF CREATING A FALSE LOAD sogy"` a�""•'""' fVN'w0""' .e«,a " aeu+. eomaT•wmra h.•ro.,ssf> aE L INCLUDE MICROPROCESSOR CONTROLS THAT MNIMIZE SUPPLEMENTAL HEAT USAGE DURING IN THE MECHANICAL COOLING SYSTEMBY LIMITING OR DISABLING THE ECONOMIZER OR ANY SHALL E FAN AIRFLOW CONTROL. EACH INDOOR OLING SYSTEM A F IN TABLE LOAD AN .,...,a,•n r°a-F 1� 'o START-UP, SET-UP, AND DEFROST CONDITIONS. THESE CONTROLS SHALL ANTICIPATE NEED OTHER MEANS, SUCH AS HOT GAS PASS, EXCEPT AT THE LOWEST STAGE OF SHALL BE DESIGNED TO VARY THE INDOOR AN AIRFLOW AS A FUNCTION OF LOAD AND w,�.,,,,,,,; ,0,,,,,M1 FOR HEAT AND USE COMPRESSION HEATING A3 THE FIRST STAGE OF HEAT. CONTROLS MECHANICAL COOLING. UNITS THAT I CLUDE AN AIR ECONOMIZER SHALL COMPLY WITH THE SHALL COMPLY WITH THE FOLLOWING REQUlf EMENTS: swoyw -.1, x It SHALL INDICATE WHEN SUPPLEMENTAL HEATIN IS BEING USED THROUGH VISUAL MEANS FOLLOWING: °'°iiein0 t0°rte1i' F (E.G., LED INDICATORS). HEAT PUMPS CE-60 2018 WASHINGTON STATE ENERGY CODE 1. DIRECT EXPANSION (DX) AND CHILLED WATE COOLING UNITS THAT CONTROL THE EQUIPPED 'NTH SUPPLEMENTARY HEATERS SH LL BE INSTALLED WITH CONTROLS THAT 1. UNIT CONTROLS SHALL HAVE THE ME CHANICAL COOLING CAPACITY CONTROL INTERLOCKED CAPACITY OF THE MECHANICAL COOLING DIP ECTLY BASED ON SPACE TEMPERATURE SHALL A-rEr °pn^y1"'"r'"°""oy^0°1°'y +c Ra IL PREVENT SUPPLEMENTAL HEATER OPERATION ROVE 40F(4.4'C). WITH THE AIR ECONOMIZER CONTROL 3 SUCH THAT THE OUTDOOR AIR DAMPER IS AT THE HAVE NOT FEWER THAN TWO STAGES OF FA q CONTROL. LOW OR MINIMUM SPEED SHALL 100 PERCENT OPEN POSITION WHEN IECHANICAL COOLING IS ON AND THE OUTDOOR AIR NOT BE GREATER THAN 66 PERCENT OF FILE L SPEED. AT LOW OR MINIMUM SPEED, THE // EXCEPTION: PACKAGED TERMINAL HEAT LIMPS (PTHPS) OF LESS THAN 2 TONS DAMPER DOES NOT BEGIN TO CLOSE TO PREVENT COIL FREEZING DUE TO MINIMUM FAN SYSTEM SHALL DRAW NOT MORE THAN 40 PERCENT OF THE FAN POWER AT FULL FAN NwMaEr•wM r;..a,p".a ww.ra eo,.°•..,,r r;w n.�a U) M COMPRESSOR RUN TIME UNTIL THE ACING AIR TEMPERATURE IS LESS THAN 45F 7'C. SPEED. LOW OR MINIMUM SPEED SHALL BE SED DURING PERIODS OF LOW COOLING LOAD •.•�^'•°•• °.Ts 8S B SUPPLEMENTARY BTU/HR) COOLING CAPACITY PROVIDED WITH CONTROLS THAT PREVENT ( ) AND VENTILATION-ONLY OPERATION. N SUPPLEMENTARY HEATER OPERATION ABOVE 40'F. 2. DIRECT EXPANSION (DX) UNITS WITH COOLING CAPACITY 6OLLO BTU/H (19 KW) OR C403.10.2 DUCT CONSTRUCTION. DUCTWORK SHALL BE CONSTRUCTED AND ERECTED IN N GREATER OF RATED CAPACITY SHAL COMPLY WITH THE FOLLOWING: 2. OTHER UNITS INCLUDING DX COOLING UNITS AND CHILLED WATER UNITS THAT CONTROL THE W Z 00 o THE SPACE SHALL HAVE ACCORDANCE WITH THE INTERNATIONAL MECHANICAL C403.4.1.2 DEAD BAND. WHERE USED TO CONTROL BOTH HEALING AND COOLING, ZONE 2.1. DX UNITS THAT CONTROL THE CAPA ITY OF THE MECHANICAL COOLING DIRECTLY BASED ON SPACE TEMPERATURE BY MODULATING THE IRFLOW TO MODULATING FAN CONTROL MINIMUM SPEED SHALL BE NOT GREATER THAN 50 PERCENT COOE.C403.10.2.1 LOW-PRESSURE DUCT SYSTEMS. LONGITUDINAL AND TRANSVERSE JOINTS, THERMOSTATIC CONTROLS SHALL BE CONFIGU ED TO PROVIDE A TEMPERATURE RANGE OR OCCUPIED SPACE SEAMS AND CONNECTIONS OF SUPPLY AND RETURN DUCTS OPERATING AT A STATIC PRESSURE tjf Q n DEAD BAND OF AT LEAST 5F(2.B'C) WITHIN WHICH THE SUPPLY OF HEATING AND TEMPERATURE SHALL HAVE NOT FEWER T AN TWO STAGES OF MECHANICAL COOLING CAPACITY. OF FULL SPEED. AT MINIMUM SPEED, THE F N SYSTEM SHALL DRAW NO MORE THAN 30 n_ 2.2. OTHER DX UNITS, INCLUDING THOSE AT CONTROL SPACE TEMPERATURE BY MODULATING PERCENT OF THE POWER AT FULL FAN SPE D. LOW OR MINIMUM SPEED SHALL BE USED LESS THAN OR EQUAL TO 2 INCHES WATER GAUGE (W.G.) (`SOO PA) SHALL BE SECURELY COOLING ENERGY TO THE ZONE IS SHUT OFF R REDUCED TO A MINIMUM. THE AIRFLOW TO THE SPACE, SHALL BE IN ACCORDANCE WITH TABLE C403.5.1. NTILATION-ONLY )DURING PERIODS OF LOW COOLING LOAD AN VE OPERATION. FASTENED AND SEALED WITH WELDS,GASKETS, MASTICS(ADHESIVES), MASTIC-PLUS Q o- 3. UNITS THAT INCLUDE AN AIRSIDE ECONOMIZER IN ACCORDANCE WITH SECTION C403.5 EMBEDDED FABRIC SYSTEMS OR TAPES INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S U Z � i3 SHALL HAVE NOT FEWER THAN TWO SPEEDS OF FAN CONTROL DURING ECONOMIZER INSTALLATION INSTRUCTIONS. PRESSURE CLASSIFICATIONS SPECIFIC TO THE DUCT SYSTEM SHALL C403.4.1.3 SET POINT OVERLAP RESTRICTION. WHE E A ZONE HAS A SEPARATE HEATING AND A C403 THROUGH AIR ECONOMIZERS. AIR ECONOM ZERS SHALL COMPLY WITH SECTIONS C403.5.3.1 O oOPERATION. IN CLEARLY INDICATED ON THE CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH THE SEPARATE COOLING THERMOSTATIC CONTROL LOCATED `N THIN THE ZONE, A LIMIT SWITCH, THROUGH C403.5.3.5. n INTERNATIONAL MECHANICAL CODE. � MECHANICAL STOP OR DIRECT DIGITAL CONTROL SYSTEM WITH SOFTWARE PROGRAMMING C403.5.3.1 DESIGN CAPACITY. AIR ECONOMIZER SYSTEMS SHALL BE CONFIGURED TO MODULATE o EXCEPTIONS: C7 N G THE m SHALL BE CONFIGURED TO PREVENT THE HEATING SET POINT FROM EXCEEDING 1. MODULATING FAN CONTROL IS NOT REQUIRE FOR CHILLED WATER AND EVAPORATIVE EXCEPTION: CONTINUOUSLY WELDED AND LOCKING-TYPE LONGITUDINAL JOINTS AND SEAMS ON f- N Z COOLING SET POINT AND TO MAINTAIN A DEAD BAND IN ACCORDANCE WITH SECTION SUPPLY AIR OUTDOOR AIR RETURN I QUANTITY AND ASAIR SFOR COOLING,TO PROVIDE UP TO 100 PERCENT OF THE DESIGN COOLING UNITS WITH FAN MOTORS OF LESS THAN 1 HP(0.746 KW) WHERE THE UNITS ARE DUCTS OPERATING AT STATIC PRESSURES LESS THAN 2 INCHES WATER GAUGE(W.G.) (500 PA) J •o C403.4.1.2 NOT USED TO PROVIDE VENTILATION AIR AN THE INDOOR FAN CYCLES WITH THE LOAD PRESSURE CLASSIFICATION. N a C403.4.1.4 HEATED OR COOLED VESTIBULES, THE HEATING SYSTEM FOR HEATED VESTIBULES AND C403.5.3.2 CONTROL SIGNAL. ECONOMIZE CONTROLS AND DAMPERS SHALL BE CONFIGURED TO AL HEATING SHALL BE PROVIDED WITH CONTROLS CONFIGURED SEQUENCE THE DAMPERS WITH MECHANICAL COOLING EQUIPMENT AND SHALL NOT BE 2. WHERE THE VOLUME OF OUTDOOR AIR REQUIREDRED TO COMPLY WITH THE VENTILATION C403.10.3.1 PROTECTION OF PIPING INSULATION. PIPING INSULATION EXPOSED TO WEATHER O Q AIR CURTAINS WITH INTEGRAL CONTROLLED BY ONLY MIXED AIR TE PERATURE. AIR ECONOMIZERS ON SYSTEMS WITH REQUIREMENTS OF THE INTERNATIONAL MEC ANICAL CODE AT LOW SPEED EXCEEDS THE SHALL BE PROTECTED FROM DAMAGE, INCLUDING THAT DUE TO SUNLIGHT, MOISTURE, EQUIPMENT _ -_------ TO SHUT OFF THE SOURCE OF HEATING WHEN THE OUTDOOR AIR TEMPERATURE IS COOLING CAPACITY GREATER THAN 5,000 BTU PROVIDE AIR THAT WOULD BE DELIVERED AT THE MIN MUM SPEED DEFINED IN SECTION C403.8.5, MAINTENANCE AND WIND, AND SHALL PROVIDE SHIELDING FROM SOLAR RADIATION THAT CAN Last Revision Date. o GREATER THAN 45F(7'C). VESTIBULE HEATING H SHALL BE CONFIGURED TO PROV AND COOLING SYSTEMS SHALL BE / THE MINIMUM SPEED SHALL BE SELECTED T PROVIDE THE REQUIRED VENTILATION AIR. CAUSE DEGRADATION OF THE MATERIAL. ADHESIVES TAPE SHALL NOT BE PERMITTED. CONTROLLED BY A THERMOSTAT LOCATED IN HE VESTIBULE CONFIGURED TO LIMIT HEATING PARTIAL COOLING EVEN WHEN ADDITI NAL MECHANICAL COOLING IS REQUIRED TO MEET THE 7/25/2023 TO A TEMPERATURE NOT GREATER THAN 607(16'C) AND COOLING TO A TEMPERATURE REMAINDER OF THE COOLING LOAD. C403.13 COMMISSIONING, MECHANICAL SYSTEMS SHALL BE COMMISSIONED IN ACCORDANCE WITH NOT LESS THAN 85F(29'C). SECTION C408. Ewaa!saso sr: °anwty sn MECHANICAL CODE N I SCALE: N15 o M 0.01 N N N n �Z O a N V Z � O p AIR HANDLER HEAT PUMP SYSTEM w TOTAL I NOMINAL SUPPLY COOUNG HEATING MECHANICAL COMPLIANCE SUMMARY ,r` SOUNDLU CONDENSING BASIS OF DESIGN AIR ESP CAPACITY CAPACITY MERV ELECTRICAL HEIGHT POWER WEIGHT CONDENSATE 201¢R'SF{. �a+Wiawe Forms fm Cammncki mddi g�- vdlag Group R2,Rl&R4 ovn3uone+aun an ul Apnmimiodiy;02023 NEEA,All siphwresrnW ~ Q TAG MARK UNIT LOCATION MANUF MODEL LSCFM) (IN WC) (BTU/HR) (BTU/HR) RATING MCA VOLTS PHASE IN dBA LBf IN NOTES Proi«talk OPfUM CARti DistituBti nON CF,NTER-20tS WBEC FnBmTdmg Dmam�„<Ux: DRh: Ad 25a 2023 0 9- !DU 1 CU-1 MEZZANINE MITSUBISHI PEAD-A72AA7 494 0.50 12,0DO 15,000 8P Addnu 17212 I nVE NE 1.45 208/230 1 7 8 3a 58 1-1/4 1-4 hoi«+6 apprant Arlb ,Wn 982_3 Inbrmatkv Iirant Nmne KADDUATOU DUMBUYA 0 NOTES. A BL=Phone W-3905743 Z ~ M1 Ilnnt EmWl KADDIJA DKSVSTEMSINC(XM 1.VERIFY ELECTRICAL VOLTAGE PRIOR TO PLACING ORDER. Fm umdona abam ibis svq W9EC Cmnvxmial i«hniral Su as 3tl0.539-53pBmvknrailWcom.kcM1eu ercodn.com 2.FURNISH ONE FUSED DISCONNECT PER SYSTEM FOR INSTALLATION BY DIV 26. (:romlOccu YaY AD Comvnnislncv GenerolHWle use Type Wmehoueu,CsmmvlSmmge Bvfltl Cona,Floor Aisa 1a,940 3.PROVIDE 24 HOUR/7 DAY PROGRAMMABLE THERMOSTAT CAPABLE OF AUTOMATIC SETBACK OR SHUTDOWN DURING PERIODS OF NON-USE New Homkg _ Project Cond.FloorArev 435 4.14/3 WIRE FROM THE INDOOR UNITTO THE OUTDOOR UNIT. G°a`ral Psolect iypn AIIemlmv nMdWon MeehaNuel scope Smgk tom 3yswm&Egmpmml Fbom AhoseGtmle 1 , N Merhevkel5eope Co Bavtt MeiM1od Compliance Meshod l-GeaLTW 04 MechaeieW Proled Dncri on Prefect Ee°n°®ix`r DOAS VentBntloo Hi%her R i meat EHlcknry MeehvokalSmpe Euepdan(v) 1"." t E9n Compilann 1' M«M1enical C.M.IWn Type A Iletiv Provided:' EHkknry Dptbv AppOed? VerMevmn Y Scopeaad Melhatl Sio51c 2m v S1'sie+ro& NmtreO° C vrPmc+t NA COMPLD?S [] Addnbnul EHk 1 Dedkmed opbke dreynemr10OAs) VRV CONDENSING UNITS milts ,,,Id AEC' Doer hiWlvg mrluae«eupapey elauifievtlonr regeidne non prelM mantle DOAS egmpmmtT vn m NOMINAL NOMINAL MINIMUM Down+ Do ae+yrn®r campy wkh ApceotlfiD mamimd ref ece deign orgn0y fnav<aeegbak ev e+sear prayed pe 1SYR segWnmenp apply? No ITS- COOLING No Z COOLING HEATING UQ GAS EFFlgENq SOUND 8 o Z BASIS OF DESI GN CAPACITY CAPACITY CONN CONN REFRIGERANT COOLING HEATING ELECTRICAL POWER WEIGHT s.,&Spxe Copdinpaing ALTERATTON-SINGLE TONE SYSTEMS&EQUIPMENT Complipace Venficstian COMPLIES LU GO TAG MARK LOCATION MANUF MODEL (MBH) (MBH) IIN) (IN) TYPE SEER GOP47 HSPF MCA ML-P VOLTS PHASE d8A (IBFI NOTES 5lagk Zan Ai.Sy+emnr Gregory-He.t pump askery,ihtnwa146DHV $ W cu 1 OUTDOOR MITSUBISHI SUZ-KAIAP 12,000 15000 4 38 R-410A 20.5 3.79 13.0 9.0 16.0 208-230 1 51 1 81 1 1-2 () Air Svskms Summv Informatio m J NOTES' S�,nem+Equip lD DfH Lew SnPCunlrerR� vevrllaEon Suedard M° k� �, a M'ved with DOAS ventJednv energy rerovery EERkka (hry I.FURIlY ISHOIEFUSVOLTAGNNECT PER PLACING ORDER. IDU-1 o Canmmvolmrc IMC Vrntiktion DOHS ERV-I Pmvidoa ymwi uiml b6 2.FURNISH ONE FUSED DISCONNECT PER SYSTEM FOR INSTALW ON BY DIV 26. Air S.sseme&Egoi meet-Coolie 5.s+ems CouNng system/Equip Type Specific Tpc Cvolivg C'apadly AECEffdency E<000 Eicepdoa Com6lnetl Ef&iemm Proposed Cooling CE Preparetl Pest PL EDIWeecy Compliance em I-.) MuM'«IFL&PL) M°M r AEC&Eeoni EDieleney Un%e I.And EHkkxy UNk VeriRrvdoo Heat Wr ceded Slits smm `r iil'm mul'iia D I1 20.5 IREER TEER COMPLIES ems&E olpmenl-Haile i55ysilemin Hemg$yskmBquip Type Speeitk Type Ren Pump HeWinB C.pdy(BmM1) Coolke Capadty(Btv2) �Mv mrger- H Ent PamP �nitHs ProPTf OxN MA NTH ERkienco�mpRante ENERGY RECOVERY VENTILATORS nD Hat ool d,h IA_ 1 I2,aoo 1 1 1 110 IHSPFI lco, COMPL ES FAN AI,Srkmr&Eqo meatDeI- SENSIBILE SUPPLY FAN EXHAUST FAN SOUND WEIGHT S e ® Arn(v)Senvd LoeadoelaPmednoevmevb-Fl_..# n TAG MARK QTY LOCATION RECOVERY ELECTRICAL IDU-I o+FlCE5TDR cFI ANITDR MQ02'-w BASIS OF DESIGN EFF(%) AIRFLOW ESP AIRFLOW ESP POWER NOTES S+ic+ IDf asmgl Ipk ucma'1 Sv;gl MANUF MODEL (SCFM) (INWC) - (SCFM) (IN WC) MCA(A) POWE0.(KW) VOLTS PHASE DBA a+m (LOT) S YPr' "' ane) Economva Cnm lientt Medmtl:Femmraawt 'mil Lary WSECE pCT Rc[ Ibis Cool �i 2(1)-Uo and Ifed Heat ERV 1 I CEILING WHISPER COMFORT FV-04VE1 66% 20 QIO 20 0.10 0.10 0.021 120 1 <0.3 1-2 O ,RV 2 1 CEILING WHISPER COMFORT I FV-04VE1 66% 20 0.10 20 0.10 0.10 1 0.021 1 120 1 <0.3 N32IE5: 1.VERIFY ELECTRICALVOLTAGE AND PHASE PRIOR TO PLACING ORDER. Low OSAT ERwa'm LTHUniD:CO? 2.UNIT OPERATION BY A LINE VOLTAGE OCCUPANCY SENSOR-PRJVI DED BY MECH.,WIRED/INSTALLED BY ELECTRICIAN. WSF.C. RRiu Re4 ence Tebk- :Tnhk C4a33:z{Z)-UnitwandA liM Hmt Puma EXHAUSTFANS SOUND -.:...-... -.. BASIS OF DESIGN AIRFLOW ESP CT ELERICAL POWER WEIGHT TAG MARK LOCATION MANUF DEL (SCFM) (IN WC) POWER(W) MCA VOLTS PHASE (SONES) (LBF) TES 71 BATHROOM PANASONIC TV 051CVS1 50 0.30 4.4 0.39 120 1 <D.3 8.8 L&2 NOTES: p 1L 1.WITH BACKDRAFT DAMPER AT FAN. PERMIT 2.WITH OCCUPANY SENSOR OR LIGTHS-BY ELECTRICAN SET I GRILLES,REGISTERS,AND DIFFUSERS oBASIS OF DESIGN CONSTRUCTIONTAG TYPE FACE SIZE NOTES MANUF MODEL o DESCRIPTION MOUNT TYPE NECK CONNECTION - (INx CSD CEILNG SUPPLY DIFFUSER TITUS nEcD IX ORE ADJUSTABLE O 24"@4" LAY-IN ROUND 1 gyp, CRG CEIU NG RETURN GRI LIE TITUS SOB 7l2 XilTXi'ALUMIUM GRID 24"X24" LAY-IN ROUND 1 'a CEG CEIUNG EXHAUST GRILLE GREENHECK SP-A DESIGNERGRILLE 19"X39" LAY-IN POUND 1 o` M I NOTES: C 1.STANDARD WHITE FINISH � LL M E Q N .'w MINIMUM LLI 0 O OCCUPANTS PER2018 VENTI LATION RATE PER VENTILATION RATE2018 VENTILATIONW Z RATES I IMC TABLE 403.3.1.1 '', 20181MC TABLE403.3.1.1 IMC TABLE 403.3.1.1 PER ROOM TYPE w Q "? VENTILATION CALCULATIONS SQFT/OCC SOFT OCC CFM/Q$FT CFM/OCC CFM S OFFICE 200 113 1 0.06 5 12 11 Q Z V nl STORAGE d - 227 0 0.06 10 14 - - --- ---- 0 c i TOTAL 26 C � 0 N z a Q Last Revision Date: i 7/25/2023 to ENGINEERED 9Y: OPANN BY a MECHANICAL K.ic K.D a &SCHEDULE SCALE: CUTS M 0.0 2 jZ 10 L F, a z O Z ti Lu � I 1 W H 0 Z J co co 0_ W m iZ W (A U `w J I AREA OF WORK i i7 W 0 J LEVE 1 KEY PLAN PERMIT SET TRUE PROJECT NORTH NORTH Z O o m F � o � U) cM E N o W Z00 0) Q Q U F z O Lo H N Z_ 0— N J a` O Q Last Revision Date: 7/25/2023 1/1 EWI-EDW DppNN BY: MECHANICAL K.K K.D a SITE PLAN i sue: M 1 .01 N NOTES o F- OEXHUAST FAN DISCHARGE NEEDS TO BE ATLEAST 10 FEET AWAY FROM ANY INTAKE AND/OR 3FEET OR MORE ABOVE INTAKE LOCATION U z to ZLU O ROUTE CONDENSATE AND REFRIGERANT LINES AS SHORT AND DIRECT AS POSSIBLE. O O OINSTALL GALVANIZED DUCTWORK AND R-8.0 DUCT WRAP INSULATION m LU Q O e Z 4 -. .. N � I f� co 40 SUPPLY UP i SECURE TO WALL OFFSET ' ROOF PENETRATION ATIFAST 3 3"FEET FROM OUTSIDE 4 It WALL I I m a 157 T 8 o Z LU EXHAUST UP �� U SECURE TO WALL { OFFSET BELOW ROOF PENETRATION - ATLEAST 3'FEET OUTSIDE WALL IDU a s I ' I x k t v n T s 100 SUPPLY UP 250 - SECURE TO WALL - OFFSET BELOW ROOF PENETRATION , - _ ATLEAST 3'FEET FROM OUTSIDE a — WALL ... .. a 2 6 t 3n < ._tl . I PERMIT h r -- SET EXHAUST UP - SECURE TO WALL OFFSET BELOW ROOF PENETRATION 87 ATLEAST 3'FEET FROM OUTSIDE 4 r v WALL Z DM 3 i I W e — 0 N Lu 00 W z rn W Q " - O t POSTING8 IXHMISf UP — J .oTHROUGH,,RDOF � O � Last Revision Date: 7/25/2023 � Errcir�aEo er: oan�ev: N MECHANICAL MEZZANINE K.K K.D CEICAM' 1 2 PLAN a M2.00 r KEYED NOTES o 1 EXHUAST FAN DISCHARGE NEEDS TO BE ATLEAST 10 FEET AWAY FROM ANY INTAKE a AND/OR 3FEET OR MORE ABOVE INTAKE LOCATION Urx N N ZLU 2O ROUTE CONDENSATE AND REFRIGERANT LINES AS SHORT AND DIRECT AS POSSIBLE. O a (n W LU H I I Z•-wrlv�n r J 00 N W } Y i Lu W m 8 Z LU G J PARAPET ON WESTSIDE IS 3'-6'FEET TALL. j CONDENSING UNR HEIGHT IS 21-5/6'INCHES.UNIT WILL BE COVERED BY THE PARAPET r rn 0 C PPL PERMIT SET luu Z o o co ry U I- Ucli M W 00 S W Z rn W Q Q Q N U d (n 0 M a I Q Last Revision Date: Y 7/25/2023 i N N MECHANICAL ROOF LEVEL PLAN EKI eY KEREDeY K� FLOOR PLAN SCALE: 1/4'a1• M 2.01 Z O 0- Of rn U Z (1) O uJ co LIJ c NOTES, 1. REFER TO SPECIFICATIONS FOR HANGER SPACINGS. Z N M r aD Oi 2. ATTACHMENTS TO OVERHEAD STRUCTURE SHALL BE MADE IN ACCORDANCE WITH 1. REFER TO SPECIFICATIONS FOR HANGER SPACINGS. MANUAL VOLUME DIRECTION OF AIR STRUCTURAL ENGINEER'S REQUIREMENTS AND WEIGHT LIMITATIONS. SUBMIT FOR REVIEW 2. ATTACHMENTS TO OVERHEAD STRUCTURE SHALL BE MADE IN ACCDROANCE WITH STRUCTURAL DAMPER FLOW-IYP. MO APPROVAL ENGINEER'S REQUIREMENTS AND WEIGHT UMRATIONS. SUBMIT FOR REVIEW AND APPROVAL. ADJUSTABLE 3. PROVIDE SWAY AND SEISMIC BRACING PER SMACNA SEISMIC GUIDELINES. 3. PROVIDE SWAY AND SEISMIC BRACING PER SMACNA SEISMIC GUIMJNES. AIR EXTRACTOR TURNING VANES 600 CFM MAX. THESE 7W0 HANGERS ARE TO BE USED SIZE OF SPLIT PROPORTIONAL UNLESS OTHER- T oNo ON DUCTS 25"AND URGER THIS HANGER IS FOR DUCTS TO AIR FLOW QUANTITIES. WISE NOTED P' (MAY BE USED ON SMALLER DUCTS) 24'0 ANDS AIR FLOW DIRECTION-TYP. BRANCH TAKE-OFF TEE SPL '. -- DUCT INCREASED .� U) a'B ROD OR 1'X 16Ga. }"0 ROD.(TYP.) 2'X 2"X d' rO ROD OR 1'X 16Ga. TURNING VANES PRIOR TO INLET 1'X 16Ga.HANGER STRAP(TYP.) HANGER STRAP(TYP.) ANGLE TOP AND HANGER STRAP.(TYPICAL) MANUAL VOLUME �. BOTTOM DAMPER A„i-FOR RETURN AND m EXHAUST AIR DUCTS 1'X 16Ga. SIZE OF SPLIT PROPORTIONAL MAX.SLOPE W 1"IN 5'ANY SIDE + >' Z STRAP OVER 'BOLT NUT AND STAR TO AIR ROW QUANTITIES. EXPANDED TAP gg DUCT(TYP.) WASHER(TYP.) AIR ROW E U) SHEET METAL SCREWS 2'MAX INCREASING Z BOLT NUT(TYP.) AND STAR WASHER SINGLE BRANCH TAKE-OFF U 1-1/2"X 22Ga. MANUAL VOLUME MAX. G:3HANGER STRAP SLOPE AIR ROW DAMPER 1'IN 6"ANY SIDE DECREASING NUT AND LOCKNUT 1-1/2'X 22Go. DUCT TRANSITION r TRIM AT 45' CONTINUOUS COLIAR -' (TYP.) DRAWN TIGHT MGLE IIMAX. I MAX. -2"X2'XJ' ANp 10VER AROUND DUCE *TURNING VANES DIFFUSER ANGLE(IYP.) F SPLIT PROPORTIONAL NECK SIZE i(io ROW QUANTITIES. `\ 1-f X 12Ga.SPLIT RING EACH STRAP ADJACENT DOUBLE BRANCH TAKE-OFF DUCT TERMINATIhN `CEILING DIFFUSER COLLAR AROUND DUCT TO ONE ANOTHER AT HANGER LOCATION(TYP.) RECTANGULAR DUCT HANGER DETAIL ROUND DUCT HANGER DETAIL TYPICAL RECTANGULAR DUCT FITTING DETAIL M I SCALE: TUTS '.. � SCALE: TUTS � SCALE: TUTS qk O TABLE 1: DUCT OVERALL ASSEMBLY HEIGHT AT MIN INSIDE HEIGHT DUCT R-VALUE CONSTRUCTION DUCT HEIGHT DUCT HEIGHT(WIDTH>22") R-4.2 R-4.2 LINER 10.5" 11.5" R-4.2 R-4.2 FOIL 8.5" 9.5" PERMIT R-6 R-6 FOIL 8.625" 9.625" R-8 R-4.2 FOIL+ LINER' 10.5" 11.5" SET R-8 R-8 FOIL 9.25" 10.25" NOTES. 1. OFFSET OR ROTATE PIPE SECTION'8",45'FROM PIPE • BEST ACOUSTICAL PERFORMANCE SECTION"A"TO PROVIDE CLEAR ACCESS FOR CLEAN-OUT. 2. DRAIN PIPE SIZES SHALL BE 3/4'SERVING AIR SEE TITLE ADDITIONAL 24 REPORT FOR REQUIRED VALUED ULATION TO MEET ENERGY CODE, CONDITIONERS UP TO 20 TONS OF COOLING AND 1" EXTERIOR INSULATION REPORT ADDITIONAL EXTERIOR R VALUE SERVING AIR CONDITIONERS FROM 21 TO 40 TONS OF A.C. FOIL 5/16'=R-4.2 DRAIN PIPE SHALL NOT BE SMALLER THAN THE AIR v 3/4'SPACER+5/16' =R-6 CONDITIONING UNTFS CONNECTION. Z 0 3/4"SPACER+5/8' -R-8 3. DIMENSION"A"=S.P.x 1.5+2"DIMENSION"B"=S.P.x 0.5+ 1" O ri BATT(K=0.29): 1-1/2" =R-4.2 2-3/16'=R-6 1/4"CLEMANCE-�( {� IF LENGTH OF HORIZONTAL �- ,0 3' =R-8.4 I I DRAIN PIPE IS GREATER THAN c` 15',INSTALL NLL SIZE VIM __ m F -- ----_- - - - - - - - -II! r- i fag s!uEg&jD 2 2L7 me 6" o ABOVE TOP OF DRAIN PAN U) M jBall Secimen, SEE TN3LE 1 N MIN CLEAR HEIGHT=6' C.O. DRAW-THROUGH AIR CV CONDITIONING UNIT DRAIN PAN. W Z 00 Valve Trep UU}nion Q 1 .��T MAX WIDTH=4xHFJGHT A DI-ELECTRIC PIPE COUPLING OR LLJ To Appliance or 1"LINER(R4.2/IN) - PIPE UNION AS REQUIRED. M Equipment E-_N PIPE DOWN NLODIRECTION OF FLOW F- Z b DUCT 1'FIL V IGE AT 1/8"PER FOOT Ln 0 o (WIDTH>22":1.5"FLANGE) Lo Ur H c\I Z DRAIN INTO APPROVED J .o PLUMBING RECEPTACLE 3'MINIMUM a N O Q AIR CONDITIONING UNIT CONDENSATE TRAP Last Revision Date: 4 GAS TO EQUIPMENT' PIPING DETAIL RECTANGULAR DUCT INSTALLATION DETAIL scaLE: NTs 712512023 sCALE: NTs 5 ficuE N� MECHANICAL -INEERMV: pRANM EV: DETAILS Ic.1< I<.D I SCALE: TUTS M3.00 Z 0 H EL x sn 0 Z Cl) 0 p U) ul LU 0 FLEXIBLE CONNECTION DR PIPING OUTSIDE AIR INTAKE ROOM ETAIL SEE M_ T'STAT N OD CABLEESTR/JN1 4) T 7——— ELECTRONIC DAMPER LOCATE DAMPER AS : ,�. I I ACTUATOR2 POSITION REMOTE TO DIFFUSER INTERNAL 1 L AS POSSIBLE � 1"AC'MIN. 1"UNING CONTROL INPUT FOR O.S.A. Y LINING 10'MIN. -- L�ECONOMISER COOLING BOWDEN GABLE(OR EQUAL) 2 POSITION DAMPERS STRUCTURE ANCHOR CONTROL WIRE LENGTH AS REQ'D - SUPPLY xrs ------- -_ __ ---- --- . ..---- -_- - CONTROL KIT MOUNTING W DUCT 1 ®1O �—RETURN AIR g / " m` FROM PLENUM i I IN PLENUM INSTALL --- - IBRACKET i Z 24" SPRING RANGER ISOLATOR -_- FLEXIBLE DUCT CONINE W _ .— I YOUNG REGULATOR MODEL � - 1"DEFLECTION RETURN AIR PLENUM THREADED ROD BACKDRAFT DAMPER ! CONTROL 270-275 KIT OR APPROVED EQUAL) o LZ SPRING ISOLATORS(TYP.-4) FLEXIBLE `<V TO MATCH FAN COIL P-1000 CONNECTION INLET SIZE 24"DEEP im EXHAUgj FAN ) INSULPLENATED SLOT DIFFUSER G J UNISRNUT SUPPORT FILTERS HARD CALING WTfH CHANNEL OR EQUIVALENT ND ACCESS DWR SLOT DIFFUSER CONDENSATE DRAIN (A)100%O.S.A.-OAF RETURN FLEXIBLE DUCT CONNECTOR MAIN SUPPLY DUCT WALL FRAMING SEE PLUMBING DWG (8)MINAMM O-SA(SEE FAN cal =--- _ _ _ -_ 46 SQUARE-TO-ROUND IALS SCHMULES)3 REMAINING RETURN SIDE TAKE OFF WALL EXHAUST GRILLE ACCESS PANEL (APPROX.13"LONG) YOUNG REGULATOR MODEL 502OCC DUCT 0 L VOLUME DAMPER FOR BOWDEN 6" lo" CABLE CONTROL SYSTEM FAN COIL UNIT SCHEMATIC �� IN—LINE EXHAUST FAN DETAIL (OR EQUAL)( °HARr Fa(LENCTx) 10" To" scALE: TUTS scuE: 12" 12" FLEXIBLE DUCTWORK CONNECTION le 14" p 16" 16" s YOUNG REGULATOR MODEL 502OCC VOLUME DAMPER FOR BOWDEN CABLE CONTROL SYSTEM (OR EQUAL)(SEE 140280 M8.02) .. LOCATE DAMPER AS REMOTE t sy TO DIFFUSER AS POSSIBLE ( BOWDEN CABLE(OR EQUAL) PERMIT MAIN SUPPLY DUCT CONTROL RE K. LENGTH AS REQ'D SET I� cncret- aa. ra �. x 3'^cncrete —� FLEXIBLE DUCT archc;•s x 4 comers CONNECTED T�O�"o BUILDING STRUCTURE $.' Z o YOUNG REGULATOR MODE CEILING O 270-301 (OR APPROVED EQUAL) DIFFUSER RACK&PINION CONTROL KIL— .o o '.V l M,?`,ss HARD CEIUNG WITH NO 3"f PLATED COVER _m i . ) ?d se}a (.;.'r!t.""s,4�'aA' ACCESS DOOR ON COILING o mA-i CAI,LrS 3M C» :W a f '7 N a +' 00 fy REMOTE BALANCE DAMPER W z Q n SCALE: TUTS Q Q M ; U Z w 0 CURB RAILS PROvHTFn/JbISTALLED BY rn— N Z Q. N J i O Q Last Revision Date: 7/25/2023 ENBINEERED BY Outdoor u IE Attachment ---- — - MECHANICAL : DRAYM BY: OUTDOOR UNIT ATTACHMENT DETAIL DETAILSK.K K.D 3 BCALE N,S M 3.01 N I z O HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Prefect Name Date OPTUM CARE DC-TI 7/2 112023 Z LU System Name Floor Area Q System 435 ENGINEERING CHECKS SYSTEM LOAD NumberofSy,t,ms COIL COOLING PEAK I COIL HTG.PEAK Meeting System CFM Sensible Latent ibl CFM Sense Output P,r.system Total Room Loads 207 6,500 5691 44 1,880 Q Total Output Btuh Return Vented Lighting 0 O O ut BNN Return Air Ducts 275 04 Coolln S bm Return Fan 0 0 Q N O O er9 Ventilation F 40 301 1471 40 2,202 Z Topl ut BWh Supply Fan 0 0 Total m(Tons) Supply Air Ducts 273 B4 Total Oqlput BtuN Total on TOTAL SYSTEM LOAD 8,701 718 4,380 /t'. N Air S tam '. �1 _ CFM per8 XVAC EQUIPMENT SELECTION y arrow cnN.chn Y arrow rn C arrow efmrton Out"Air% Total Adjusied System Output p? outaM.ar crmr (aalaatea ra peax oaaien condlmml W 07 Note:values above Ivan et MI mntllHona TIME OF SYSTEM PEAK JW 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS amtmam Tam eratures at Time of Heatin Peak Z 10°F nn"F "10°F Uj W outside Air C V G J 40 cim Heating Coil 1i0"r ROOM ---� 70°F II 70°F ll �1 4 I COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of CoolingPeak 82l68°F lGl c3`S 551 °F Outside All I 40 clm Cuuling Cop 56/54- 01 501% ROOM i o ..... 74 fY2°F 0 II 11� PERMIT SET Z s _p a .o m F N G Ll� c U) M N E 04 O W Z 0') Q Q d v, L.O. M N Z v N J o Q � a � Q t Last Revision Date: u 7/25/2023 i (%1 EN31NEE6EpaY'. GRAMM 6Y: MECHANICAL Ic.l< K.D a LOAD CALCULATIONS N ` I jSCALE: NTS M4.00 N ' N n CITY OF ARLINGTON 18204 59th Avenue NE,Arlington,WA 98223 INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551 BUILDING PERMIT 17212 51STAVE NE STE 111 Permit#: 5508 PERMIT EXPIRES 180 DAYS AFTER Parcel#: 31052100400100 DATE OF ISSUANCE. Scope of Work: Install(1)Ductless Heat Pump,(2)Energy Recovery Ventilators- Valuation: 31265.00 ERVs,(1)Exhaust Fan and Ducting. OWNER APPLICANT CONTRACTOR SMARTCAP ARLINGTON AIRPORT D.K. Systems,Inc.Dulce Herrera D.K. Systems,Inc INDUSTRIAL PARK QOZB,LLC 8201 164TH AVE NW,SUITE 110 PO Box 886 962 S Spruce Street REDMOND,WA 98052 Burlington,WA 98233 Burlington,WA 98233 360-755-1555 360-755-1555 LIC:602 204 164 EXP:05/31/2024 LIC:DKSYSI*982L1 EXP:06/21/2024 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR LIC#: EXP: LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: COMMERCIAL MECHANICAL CODE YEAR: 2018 STORIES: 1 CONST.TYPE: 111B DWELLING UNITS: OCC GROUP: BUILDINGS: OCC LOAD: PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any other ordinance or order of the City,of any state or federal law, or of any order,proclamation,guidance advice or decision of the Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation, guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City ordinance,regulation or order,state or federal law,or any order,proclamation,guidance or decision of the Governor. I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY;NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED.IBC 110/IRC 110. SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on your sales tax return form and coded City of Arlington#3101. Dlgi y aignetl ny Doke Herrera N:C=US,OU=Protects C,.Minator,O='D.K.Systems.Inc'. CeNa=sDounk aHe rre1ro 01 3E:.=tlu2l0DuIce Herreraowon.yomung iwocfe tn®iatltlksyws tmemm O 202-0&1 ing M1e si nc.com L 1 O 08/18/2023 e Foxit PnantomPDF Version:0.].5 Applicant Signature Date Building Official Date CONDITIONS ADHERE TO APPROVED PLANS.APPROVED JOB COPY SHALL BE ONSITE FOR CONSTRUCTION AND INSPECTIONS. CALL FOR INSPECTIONS. THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY.ANY CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS,SIDEWALKS,DRIVEWAYS, MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount 08/18/2023 Web Only-Mechanical Commercial Plan Review $443.12 08/18/2023 Processingrrechnology $25.00 08/18/2023 ExhaustNentsNent Fans $15.00 08/18/2023 Heat Pump-Condensing Unit $25.00 08/18/2023 Mechanical Misc. $25.00 Total Due: $533.12 Total Payment: $0.00 Balance Due: $533.12 CALL FOR INSPECTIONS Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon INSPECTION INFORMATION I Pass/Fail i COMMERCIAL MECHANICAL APPLICATION • Community&Economic Development City of Arlington• 18204 59th Ave NE•Arlington,WA 98223 • Phone(360) 403-3551 This application is for new, addition, altered or replaced mechanical installation and new or altered gas piping and must be accompanied by ELECTRONIC CONSTRUCTION DRAWINGS and CUT SHEETS and/or information outlined in the MECHANICAL SUBMITTAL REQUIREMENTS,if applicable. Type of Permit: ❑ New Installation ❑ Addition s❑ Alteration ❑ Replaced ❑ Gas Piping Type I and Type H Hood Systems required submittal of the Commercial Mechanical Addenda Property Address: 17212 - 51 st Ave. NE, Suite 110 Project Valuation: 31,265 Lot#: Parcel ID No.: 31052100400100 Preferred Contact: ❑ Owner O Contractor Project Description: Install (1) Ductless Heat Pump, (2) Energy Recovery Ventilators - ERVs, (1) Exhaust Fan and Ducting. Owner Name: UnitedHealth Group/CPM-Commercial Property Maintenance Office No.: 360-863-6705 Jody Daugherty,Controller jaugherty@cpmnw.com Email Address: Cell No.: Mailing Address: PO Box 1128 Cit ; Snohomish State: WA Zip: 98291 Contractor Name: D.K. Systems, Inc. Office No.: 360-755-1555 Email Address: dulce@dksystemsinc.com Cell No.: Mailing Address: PO Box 886 City: Burlington State: WA zip: 98233 L&I Contractor License Number: DKSYSI*9821_1 Expiration Date: 06/21/2024 • New gas piping requires a pressure test hooking to any appliance • Sediment traps (drips) are required on all gas lines • Gas lines are required to be supported/secured per IFGS,Section 415 • Proper Combustion air and venting required for all appliances • A shut-off valve is required within 6 feet of each appliance Gas Piping Specification and complete Schematic PAGE 3 ❑ Not Applicable ❑ CSST ❑ Brass ❑ Other Proposed Piping Material: ❑ Black Steel ❑ Galvanized Steel Proposed Piping Size: ❑ 1/2" ❑ 5/8" ❑ 3/4" ❑ 1" ❑ 11/2 ❑ 2" Inlet Pressure: Pressure Drop: Specific Gravity: REV03.2022 Page 1 of 3 MECHANICAL PERMIT FEES (per unit Type of Fixture No.of Units Cost per Unit Subtotal Additional Plan Review fees x $ 75.00 = $ Air Cond.Unit<_100Btu h x $ 15.00 = $ Air Cond.Unit>100Btu h x $ 25.00 = $ Air Cond.Unit>50OBtu/hp x $ 50.00 = $ Air Handling Units x $ 15.00 = $ Base Mechanical Fee $ 25.00 $ 25.00 Boiler<100Btu h>3h x $ 15.00 = $ Boiler>1 million Btu/h<50hp x $ 25.00 = $ Boiler>1.5 million Btu/h<50hp x $ 50.00 = $ Boiler>100Btu h 3-15h x $ 15.00 = $ Boiler>500Btu h 15-30hp x $ 25.00 = $ Commercial Hoods-Type I x $ 25.00 = $ Commercial Hoods-Type II x $ 50.00 = $ Diffusers x $ 15.00 = $ Dryer Ducting x $ 15.00 = $ Ductwork(drawings required) x $ 25.00 = $ Evaporative Coolers x $ 15.00 = $ Exhaust/Ventilation Fans 1 x $ 15.00 = $15.00 Fireplace/Insert/Stove x $ 15.00 = $ Forced Air Heat<_100 Btu h x $ 15.00 = $ Forced Air Heat>100 Btu h x $ 25.00 = $ Gas Clothes Dryer x $ 15.00 = $ Gas Fired AC<_100 Btu h x $ 15.00 = $ Gas Fired AC >100 Btu h x $ 25.00 = $ Gas Fired AC > 500 Btu h x $ 50.00 = $ Gas Pi in <_ 5 units x $ 15.00 = $ Gas Piping> 5 units (plus<5 units x $ 2.00 = $ Heat Exchangers x $ 15.00 = $ Heat Pump-Condensing Unit 1 x $ 25.00 = $25.00 Hot Water Heat Coils x $ 15.00 = $ Miscellaneous Appliance-Energy Recovery 2 x $ 15.00 _ $30.00 Ventilator regulated by mechanical code,not otherwise specified Pkg.Units<_100btu x $ 25.00 = $ Pkg.Units >100btu x $ 50.00 = $ Range/Cook top-Gas Fired x $ 15.00 = $ Refrigeration Unit<_100Btu h x $ 15.00 = $ Refrigeration Unit>100Btu h x $ 25.00 = $ Refrigeration Unit>500Btu h x $ 50.00 = $ Re-inspection fee all x $ 75.00 = $ Unit Heaters <_ 100 Btu h x $ 15.00 = $ Unit Heaters>100 Btu h x $ 25.00 = $ VAV Boxes (Variable Air Volume,part of air x $ 10.00 _ $ conditioning system) Wall Heaters-Gas Fired x $ 25.00 = $ Water Heater- Gas Fired x $ 25.00 = $ Permit Fee $95.00 Table 4-8; Plan Review Fee $ Processing/Technology Fee $25.00 Total $ REV2.2020 Page 2 of 3 Not Applicable PRESSURE PIPING SCHEMATIC COMPLETE FOR GAS PIPING ONLY ❑ SCHEMATIC IS TO SCALE ❑ SCHEMATIC NOT TO SCALE Show Pipe Size(s) and Length(s) from meter to all appliances NOTE: Any interior pressure regulators must be indicated I hereby certify that I am the❑Owner, ElApplicant, ElCon tractor,and authorized to sign this application and that the above information is correct and construction on,and the occupancy and the use of the above-described property will be in accordance with the laws,rules and regulation of the State of Washington,and the City of Arlington.A final inspection and approval shall be obtained when complete. D u l ce H e rre ra a`�� '� �'�"��� D u l ce Herrera 7/27/23 Signature Print Name Date REV2.2020 SAVE PRINT Page 3 of 3 Permit#: 5508 Permit Date: 07/27/23 Permit Type: COMMERCIAL MECHANICAL Project Name: Optum Care Distribution Center Applicant Name: D.K. Systems, Inc. Dulce Herrera Applicant Address: PO Box 886 Applicant, City, State,Burlington,WA 98233 Zip: Contact: Dulce Herrera Phone: 360-755-1555 Email: dulce@dksystemsinc.com Scope of Work: Install (1) Ductless Heat Pump, (2) Energy Recovery Ventilators - ERVs, (1) Exhaust Fan and Ducting. Valuation: 31265.00 Square Feet: 14941 Number of Stories: 1 Construction Type: 111B Occupancy Group: B; Business ID Code: CIC Permit Issued: 08/31/2023 Permit Expires: 02/27/2024 Form Permit Type: COMMERCIAL MECHANICAL Status: COMPLETE Assigned To: Kristin Foster Property Parcel# Address Legal Description Owner Name Owner Phone Zoning SMARTCAP 17212 51 ST AVE NE STE ARLINGTON 301 AP- 31052100400100 111 AIRPORT AIRPORT INDUSTRIAL/ INDUSTRIAL MANUFACTURING PARK QOZB,LLC Contractors Contractor Primary Contact Phone Address Contractor Type License License# D.K.Systems,Inc Dulce Herrera 360-755-1555 962 S Spruce CONSTRUCTION COA 602 204 164 Street CONTRACTOR D.K.Systems,Inc Dulce Herrera 360-755-1555 962 S Spruce CONSTRUCTION L&I DKSYSI*982L1 Street CONTRACTOR Inspections Date Inspection Type Description Scheduled Date Completed Date Inspector Status C 14. 09/19/2023 MECHANICAL 09/20/2023 09/20/2023 BUILDING Approved FINAL Plan Reviews Date Review Type Description Assigned To Review Status 08/10/2023 COMMERCIAL BUILDING Approved MECHANICAL Fees Fee Description Notes Amount Enter 1 if permit is for commercial Web Only-Mechanical Commercial Plan mechanical $443.12 Review (Table 4-1) Processing/Technology $25.00 ExhaustNentsNent Fans $15.00 Heat Pump-Condensing Unit Enter#of units $25.00 Mechanical Misc. Not otherwise specified $25.00 Total $533.12 Attached Letters Date Letter Description 08/18/2023 Building Permit Payments Date Paid By Description Payment Type Accepted By Amount 08/21/2023 XBP Con£ $533.12 152146445 Outstanding Balance $0.00 Notes Date Note Created By: 08/18/2023 Emailed that the permit is ready for issuance once payment is made. Kristin Foster 07/28/2023 Emailed for permit documents Kristin Foster Uploaded Files Date File Name 10/19/2023 17248447-20230817 BLD5508 ApprovedPlans.pdf 08/31/2023 16720981-20230831 BLD5508 IssuedPermit.pdf 08/01/2023 16369423-20230728 BLD5508 Specs.pdf