Loading...
HomeMy WebLinkAbout199th St Ne_BLD5512_2026 8117 267th Street NW Stanwood,WA 98292 North County Regional Fire Authority Phone:(360)629-2184 ` •, Fax(360)652-3166 www.northcountyfireems.com Comment Letter on Permit 5512/5513 August 9, 2023 Jeff Lincoln Air Gas USA LLC 5925 199th St NE Arlington, Wa. 98223 Hello, I am reviewing your permits for a propane tank and dispenser at the Air Gas facility. I came down and I was told there was previously a dispenser. I just need to make sure the dispenser and tank comply with the Fire Code. As you are in the business, I am sure you are aware of the distances, I just need to verify. I have the sketch and the table on the following pages. I also need to know what type of impact protection there will be for the tank. The area is pretty tight as you come in and the tank/dispenser will create more congestion. I have a spec on bollards if you need them. • Weeds, grass, brush, trash and other combustibles shall be not less than 10 feet away from the LP-gas tanks or containers. • The other gases in storage use would need to be 25 feet away from the filling area. On the day I was there I was not sure you had the distances • Each industrial plant, and distributing point shall be provided with at least one portable fire extinguisher in accordance with Section 4.7 having a minimum capacity of 18 Ibs with a B:C rating within 30 feet • No smoking signs within 25 ft of filling station 8117 267th Street NW Stanwood,WA 98292 North County Regional Fire Authority Phone:(360)629-2184 ` •, Fax(360)652-3166 www.northcountyfireems.com 30.000 GALLONS EACH UNDERGROUND S,000 GALLONS SO•-0'MINIMUM MINDALAM —5'-0'MINIMLAM STREET 25'-0-MINIMUM i i ® i -No GALLONS ' BUILDWO Y-WMINIMUMJ ® -•---•-.- 10'4r 2S'0' � BUILOfJG7-25-4r 1.000 GALLONS 4. Ply 000 GALLONS EACH �I NOTE:ALL LPG CYUINOERS.ALL ABOVE GROUND EXCEPT WHERE NOTED_ 8117 267th Street NW Stanwood,WA 98292 North County Regional Fire Authority Phone:(360)629-2184 ` •, Fax(360)652-3166 www.northcountyfireems.com y RL 1116TON a Al VZc,A-s Ulg R E H0145 E 0 Fe,ce - l 1 _ AAQJ. S� of /t{Dg..c rMk C,ATJE I I �1 uo �o c� } Q This is the table I am working from 8117 267th Street NW Stanwood,WA 98292 North County Regional Fire Authority Phone:(360)629-2184 ` •, Fax(360)652-3166 www.northcountyfireems.com TABLE 6104.3 LOCATION OF LP-GAS CONTAINERS MINIMUM SEPARATION BETWEEN LP-GAS CONTAINERS AND BUILDINGS,PUBLIC WAYS9 OR LOT LINES OF ADJOINING PROPERTY THAT LP-GAS CONTAINER CAPACITY CAN BE BUILT ON MINIMUM SEPARATION BETWEEN LP-GAS CONTAINERS'c (water gallons) Mounded or underground Above-ground LP-gas containersb (fit) LP-gas containers' (feet) (feet) Less than 125`d 10 5e None 125 to 250 10 10 None 251 to 500 10 10 3 501 to 2,000 10 25'1 3 2.001 to 30.000 50 50 5 30,001 to 70.000 50 75 70,001 to 90.000 50 100 (0,25 of sum of diameters of adjacent LP-gas containers) 90,001 to 120.000 50 125 For SI 1 fat=3048 min 191111n=3785L a.Minimum distance for underground LPgas containers shall 4 measured hom the pressure relief device and Me filling or Ipad-level gauge vrnl connection at the container.except Mat all parts of an undegound LPgas cmtainer shall be nbt kss than 10 feet from a building or lot In,of atioining abcedy Mal can be buin on b.For MM1er Man installations in rMicM1 the osreManging strvdure rs SO feel or more above Me relief-valve discharge w0et.In applying Me tlistance behveen buildings ant ASME LPgas containers wiM a wafer capacty o1125 gallms or more.not less Man 50 percent of Mis M1ori_ontal distance shall also apply to all podinns of Me WIdbg Mat pr 1more Man 5feet from Me bmldmgwall and that are higher than Merelief valve discharge bullet This ho,cbntal distance shall be measured from a point del—alb by pbbding Me outside edge o1 such overhanging structure vbin-Hy damvrad ro grate a other I...I on which Me LP-gas container is installed Distances to Me Wilding wall sM1all be not—than Mole p—bet in th5 table c._underground multiconlainer installations an,—p—a.1h.�itlual LPgas containers daring awaler c-ty of 125 gallons in more.such containers shall beinstalled so asto Ina—access at their entlsasides to faubale v:o st—cranes a hoists d.Ataconsumer stle if Me aggregate watercapacily ofa multiple.obtainerinslarabbn comprised of individual LP-gas containers raving.water -tybfless than 125 gallons.,500 gallons or more.Me minimum distance shall cbmpl,vnlh the appropriate poNm Ott"table applying the aggregate ceDacitY ranter Than Me capadty per LP-gas container If more Than one such installation is made each inslallalim shall W sepa,alet from olds indallafims by nd less Man 25 n-Minimum distances behreen LPgaz containers need nM be applie0 e.Tlie follovdng shall apply to aboveground cl ntai,rtrs installed alorgsitle b.b iN, 1.LPgas containers o1 kss Man a 125ga11mwafer capacity are all—wiM a separation tlislanm wherein ca.pliancew nth Items 23 and 4. 2.Depadmrnt of Transpbdation IDOTni specification LPgas containers shall De located and installed w that the discharge hom the container a—Iin,bt,f device Is not kss than 3 feet horizontalry bbbi buiking oprnngs bdov:the level of—discharge and shall nd ce'meant buikings unless the space is well v..blatetl to In,outside and It not enclosed for more Man 50 percent of ifs perimeter Th,discharge from LP-gas container aessure relief devices shall be locaret nor less Man 5 feel from eAedor sources of ignition openings into tired-vent lsealet omb-bi,syslemi al%rbances a mechanical ventilabm air Intakes 3.ASME IPgaz-tamers of—than a 125yallon ware,c,p,,ty shall beocated l and Installed such that the discharge tram essu prre,tlief d,,,a shall not tmminate In or beneah buik—till, and shall be located not less Man 5 f or�on fiat hrally from baiting openings W=the Iesal of sucM1 tiuhargecand not less Man 5 feel ham eAedor sources of ignition.openings into direct vent isealetl combustion syslemi appliances.or mechanical—hahb,air intakes. 4.The filling connection and Me vent from liquid-level gauges on either DOT.or ASME LPgas containers filled at Me point of installation shall W not less Man 10 1-1 from ededa swrtes b1 ignition openings into direct vent IsealM canWstion syslemi appliances or mechanical ve b abbe air intakes f.TNs tistance is aIt.-tb be r...d to not less Man 10—Ior a single LPgas cmtainer M 1200-garon water capacity or less.provitet that such container is not less than 25 feet I——LPgas containers of more than 125-galkn v,ah,.capacily. g.Aboveground LPgas containers th av:a capacily o12 OOD gallons or less stall be separated hom hbI.ways by a distance of not less M an 5 leer Containers—awaler capacity It,—,Man 2000 gallons stallbe separated flan pudic ways in—dance vah thistable. Steve Goforth,Assistant Chief/Community Risk Reduction North County Regional Fire Authority 8117 267111 St NW Stanwood,WA 98292 Office 360-629-2184 x105 Cell 360-502-6184 sgoforth@northcountyfireems.com "Serving our Communities with Compassion" Serving the Cities of Arlington and Stanwood,the rural communities of Bryant,Freeborn,Warm Beach, Kayak Point and the Stillaguamish Tribe of Indians. CONFIDENTIALITY NOTICE This e-mail message,including any attachments,is for the sole use of the intended reciplent(s)and may contain confidential,proprietary,and/or privileged information protected by law. If you are not the intended recipient,you may not use,copy,or distribute this e-mail message or its attachments. If you believe you have received this e-mail message in error,please contact the sender by reply e-mail and telephone immediately and destroy all copies of the original message.Thank you r COMMERCIAL MECHANICAL APPLICATION Community&Economic Development City of Arlington• 18204 59th Ave NE•Arlington,WA 98223• Phone (360)403-3551 This application is for new,addition,altered or replaced mechanical installation and new or altered gas piping and must be accompanied by ELETRONIC FILES and TWO (2) SETS OF CONSTRUCTION DRAWINGS and CUT SHEETS and/or information outlined in the MECHANICAL SUBMITTAL REQUIREMENTS,if applicable. Type of Permit: ❑ New Installation ❑ Addition ❑ Alteration 43 Replaced ❑ Gas Piping Property Address: 5925 199th St NE, Arlington, WA 98223 project Valuation: 15000.00 Lot#: Parcel ID No.: 00746300000100 Preferred Contact: 0 Owner 0 Contractor Project Description: Install 1-1000 gallon propane dispenser with equipment Owner Name: Air Gas USA LLC Home No.: Email Address: jeff.lincoln@airgas.com Cell No.: 206-713-4462 Mailing Address: 11900 NE 95th Street City, Vancouver State: WA Zip: 98682 Contractor Name. Propane Northwest Office NO.: 253-875-3000 Email Address: kellykte@thornpsongas.com Cell NO.: 253-380-0286 Mailing Address: 1906 Marc Ave. City, Tacoma State: WA Zip: 98421 L&I Contractor License Number: P ropan*835P D Expiration Date: 10-23-23 • New gas piping requires a pressure test hooking to any appliance • Sediment traps(drips) are required on all gas lines • Gas lines are required to be supported/secured per IFGS,Section 415. • Proper Combustion air and venting required for all appliances • A shirt-off valve is required within 6 feet of all appliances Gas Piping Specification and complete Schematic PAGE 3 2 Not Applicable O CSST 0 Brass O Other Proposed Piping Material: O Black Steel O Galvanized Steel Proposed Piping Size: O 1/2" O 5/8 O 3/4 1711 O 11/i" 1712 Inlet Pressure: Pressure Drop: Specific Gravity: I hereby certify that the above information is correct and that the construction on,and the occupancy and the use of the above described property will be in accordance with the laws,rules and regulation of the State of Washington. L�X m es - ct� Kelly Kite July 28, 2023 Key_fir'2...O................... Signaare Print Name Date FOR STAFF USE ONLY PERMIT# ACCEPTED BY: DATE STAMP REV2.2020 Pagel 43 MECHANICAL PERMIT FEES (per unit Type of Fixture No.of Units Cost per Unit Subtotal Additional Plan Review fees x $75.00 = $ 0 Air Cond Unit:5 100Btu i x $15.00 = $ 0 Air Cond.Unit>10OBtu h x $25.00 = $ 0 Air Cond.Unit>50OBtuAip x $50.00 = $ 0 Air Handling Units x $15.00 = $ 0 Base Mechanical Fee $25.00 $25.00 Boiler<10OBtu h>31i x $15.00 = $ 0 Boiler>1 million Btu/h<50hp x $25.00 = $ 0 Boiler>1.5 million]3tuAi<50lip x $50.00 = $ 0 Boiler>10OBtu 13-15h x $15.00 = $ 0 Boiler>50OBtu h 15-30lip x $25.00 = $ 0 Commercial Hoods-1ype I x $25.00 = $ Commercial Hoods-lype II x $50.00 = $ Diffusers x $15.00 = $ 0 Dryer Ducting x $15.00 = $ 0 Ductwork(drawings required) x $25.00 = $ Evaporative Coolers x $15.00 = $ Exhaust/Ventilation Fans x $15.00 = $ Fire lace Insert Stove x $15.00 = $ Forced Air Heat 15 100 Btu h x $15.00 = $ Forced Air Heat>100 Btu h x $25.00 = $ 0 Gas Clothes Dryer x $15.00 = $ 0 Gas Fired AC<_100 Btu Ai x $15.00 = $ 0 Gas Fired AC>100 Btu h x $25.00 = $ 0 Gas Fired AC> 500 Btu Ai x $50.00 = $ 0 Gas Pi in <_ 5 units x $15.00 = $ 0 Gas Piping> 5 units(plm<5 mits x $2.00 = $ 0 Heat Exchangers x 1 $15.00 = $ 0 Heat Pump-Condensing Unit x $25.00 = $ 0 Hot Water Heat Coils x $15.00 = $ 0 Miscellaneous Appliance-regulated by 1 x $15.00 = $ 15 mechalucal code,not otherwise specified Pkg.Units<_100btu x $25.00 = $ 0 Pkg.Units>100btu x $50.00 = $ 0 Range/Cook to Gas Fired x $15.00 = $ 0 Refrigeration Unit<_10OBtt1 h x $15.00 = $ 0 Refrigeration Unit>10OBtt1 h x $25.00 = $ 0 Refrigeration.Unit>50OBtu h x $50.00 = $ 0 Re-inspection fee all x $75.00 = $ 0 Residential Range Hood x $15.00 = $ 0 Unit Heaters 15 100 Btu h x $15.00 = $ 0 Unit Heaters>100 Btu x $25.00 = $ 0 VAV Boxes(Variable Air Voltune,part of air x $10.00 _ $ 0 conditioning system) Wall Heaters-Gas Fired x $25.00 = $ 0 Water Heater- Gas Fired x $25.00 = $ 0 Permit Fee $ 40 Table 4-8; Plan Review Fee $ Processing/Tecluiology Fee $25.00 Total $ REV2.2020 Page 2 of PRESSURE PIPING SCHEMATIC COMPLETE FOR GAS PIPING ONLY ❑ SCHEMATIC IS TO SCALE 0 SCHEMATIC NOT TO SCALE Show Pipe Size(s) and Length(s) from meter to all appliances NOTE: Any interior pressure regulators must be indicated 1,EV2.2020 Pagge 3 of3 9 v� cy Fe+nce6 r�3 i I i Z ct 3�5' ARCOSA 120-2,000 wg TANK Aboveground Domestic Tanks Finished with ArcClad" Superior Aboveground Coating Tank Features: • Superior Coating • Steel galvanized domes in select colors • Vacuum Purged • #72 liquid level outage valve orifice • Fabricated to A.S.M.E. code, Section VIII, Division 1 • Division 2 design available • Registered with the National Board • Registered with CRN (Canadian For more information Registration Number) 888.558.8265 ARCOSA TANK Aboveground Domestic Tanks OVERALLLENGTH DOME In O C4 = F Q o OUTSIDE j II j p DIAMETER O o j 0 LEG WIDTH LEG SPACING GENERAL SPECIFICATIONS WITHDRAWAL --� VALVE Conforms to the latest edition of the ASME code for Pressure FLOAT / oT,�E � ANODE Vessels,Section VIII, Division 1. Complies with NFPA 58. GUAGE CONNECTION Rated at 250 psig from -202 F.to 1252 F. All tanks may be ®!�\' VALVE evacuated to a full (14.7 psi)vacuum. 0 0 Vessel Finish: Coated with TGIC powder. ® n Liquid withdrawal opening located under the dome on the SERVICE/ I�I�NAME MULTIVALVE /. PLATE 120 wg vessels ONLY. -- RELIEF VALVE ABOVEGROUND VESSEL DIMENSIONAL INFORMATION Water Outside Head Overall Overall Leg Leg Quality Capacity Diameter Type Length Height Width Spacing Weight Full Per Load Stack *120 wg. 24" Ellip 5'-513/16" 2'-81/4" 101/8" 3'-0" 245 lbs. 96 12 454.2L 609.6 mm 1,671.6 mm 819.2 mm 257.2 mm 914.4 mm 111.1 kg. *250 wg. 31.5" Hemi 7'-21/2" 3'-3 3/4" 12 3/4" 3'-6" 472 lbs. 63 9 946.3 L 800.1 mm 2,197.1 mm 1,009.7 mm 323.9 mm 1,066.8 mm 214.1 kg. *320 wg. 31.5" Hemi 8'-113/4" 3'-3 3/4" 12 3/4" 4'-01/4" 588 lbs. 45 9 1,211.2 L 800.1 mm 2,736.9 mm 1,009.7 mm 323.9 mm 1,225.6 mm 266.7 kg. 500 wg. 37.42" Hemi 9'-10" 3'-911/16" 15" 5'-0" 871 lbs. 30 6 1,892.5 L 950.5 mm 2,997.2 mm 1,160.5 mm 381.0 mm 1,524.0 mm 395.1 kg 1000 wg. 40.96" Hemi 15'-1013/16" 4'-1 3/8" 161/4" 9'-0" 1729 Ibs 15 5 3,785.0 L 1,040.4 mm 4,846.6 mm 1,254.1 mm 412.8 mm 2,743.2 mm 784.3 kg. 1465 wg. 46.77" Ellip 17'-6 7/8" 4'-4 3/4" 21" 10'-0" 2745 kbs, 12 4 5,545.0 L 1,188 mm 5,356.2 mm 1,339.9 mm 533.4 mm 3,084 mm 1,245 kg. 2000 wg. 46.77" Ellip 23'-9" 4'-7" 21" 14'-0" 3676 lbs' 6 4 7,570.0 L 1,188 mm 7,239 mm 1,709.7 mm 533.4 mm 4,267.2 mm 1,667.5 kg. All vessels dimensions are approximate. *Drain plug not available. Eng.Update: April 5,2016 For more information 888.558.8265 A P 1 . M r .M � / .t 5925 ���►�►�.> 6011 i 'I I I c rt � I 1 7 y y r Iv P y i►, V _ 199th St NE Oi At M =ft Jp- MBA AAN.r� id'. N � - f ARL11i6TON o cr� f+l-K,A-5 sToR.l�. 0 FeHce6L ►15 aaeo. J gG.�k e �1unSa� ,51 D�-�R11 g,L I•�k GAT>< I ��l dL t-ti�s l. 3Gi r cprJG Q 5��Ott* CITY OF ARLINGTON BUILDING DEPARTMENT APPROVED DATE BY NO CHANGES AUTHORIZED UNLESS APPROVED BY THE BUILDING INSPECTOR Received JUL 2 8 2023 t ,p �l Z, CITY OF ARLINGTON 18204 59th Avenue NE,Arlington,WA 98223 INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551 BUILDING PERMIT 199TH ST NE Permit#: 5512 PERMIT EXPIRES 180 DAYS AFTER Parcel#: 00746300001600 DATE OF ISSUANCE. Scope of Work: Install new 1000 gallon propane tank with dispenser equipment Valuation: 15000.00 OWNER APPLICANT CONTRACTOR AIRGAS-NOR PAC INC Propane Northwest Propane Northwest 11900 NE 95TH ST STE 400 1906 Marc Ave 1906 Marc Ave VANCOUVER,WA 98682 Tacoma,WA 98421 Tacoma,WA 98421, 253-875-3000 253-875-3000 LIC:604 094 362 EXP:03/31/2024 LIC:PROPAN*835PD EXP: 10/04/2023 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR LIC#: EXP: LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: COMMERCIAL MECHANICAL CODE YEAR: 2018 STORIES: CONST.TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: OCC LOAD: PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation, guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City ordinance,regulation or order,state or federal law,or any order,proclamation,guidance or decision of the Governor. I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED.IBC 110/IRC 110. SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on your sales tax return form and coded City of Arlington#3101. 11/13/2023 Applicant Signature Date Building Official Date CONDITIONS Will require bollard protection,bollards to be placed 4'on center max T min.bollards to be set in 15"min dia,hole 36'deep in concrete,must extend min.36" above grade.Approved job copy shall be onsite for inspections. Call for inspections. The property owner shall ensure that the construction project complies with all applicable zoning codes and regulations.The property owner shall also ensure that the construction project does not cause any adverse impact on the surrounding environment or community.The property owner shall be responsible for obtaining all necessary permits and approvals from the relevant authorities before commencing construction.The property owner shall ensure that the construction project complies with all applicable design review requirements. THIS PEPCMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY.ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS, MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount 11/13/2023 Processing/Technology $25.00 11/13/2023 Mechanical Commercial Plan Review $244.36 11/13/2023 Fuel/LPG $100.00 Total Due: $369.36 Total Payment: $0.00 Balance Due: $369.36 CALL FOR INSPECTIONS Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon INSPECTION INFORMATION Pass/Fail Permit#: 5512 Permit Date: 07/31/23 Permit Type: COMMERCIAL MECHANICAL Project Name: Air Gas USA LLC Applicant Name: Propane Northwest Applicant Address: 1906 Marc Ave Applicant, City, State, Zip: Tacoma,WA 98421 Contact: Kelly Kite Phone: 253-875-3000 Email: kellykite@thompsongas.com Scope of Work: Install new 1000 gallon propane tank with dispenser equipment Valuation: 15000.00 Square Feet: 0 Number of Stories: 0 Construction Type: Occupancy Group: ID Code: Permit Issued: Permit Expires: 01/27/2024 Form Permit Type: COMMERCIAL MECHANICAL Status: IN PROCESS Assigned To: Kristin Foster Property Parcel# Address Legal Description Owner Name Owner Phone Zoning 910 AIRGAS-NOR UNDEVELOPED 00746300001600 199TH ST NE PAC INC (VACANT)LAND Plan Reviews Date Review Type Description Assigned To Review Status 07/31/2023 COMMERCIAL BUILDING In Review MECHANICAL 07/31/2023 COMMERCIAL FIRE In Review MECHANICAL Fees Fee Description Notes Amount PProaessing/Technology $25.00 Mechanical Commercial Plan Review Table 4-1 $244.36 Fuel/LPG Installation/Removal $0.00 Total $269.36 Notes Date Note Created By: 07/31/2023 The property where the tank is to be installed does not have an address.The address provided Kristin Foster on the application is for the Airgas office parcel. Uploaded Files Date File Name 07/31/2023 16346974-20230731 BLD5512 AcrialVicw.pdf 07/31/2023 16346857-20230728 BLD5512 SitePlan.pdf 07/31/2023 16346858-20230728 BLD5512 Tank Specs.pdf 07/31/2023 16346859-20230728 BLD5512 App.pff CITY OF ARLINGTON 18204 59th Avenue NE,Arlington, WA 98223 INSPECTIONS: 360-403-3417 - Permit Center: 360-403-3551 BUILDING PERMIT 199TH ST NE Permit #: 5512 PERMIT EXPIRES 180 DAYS AFTER Parcel #: 00746300001600 DATE OF ISSUANCE. Scope of Work: Install new 1000 gallon propane tank with dispenser equipment Valuation: 15000.00 OWNER APPLICANT CONTRACTOR AIRGAS - NOR PAC INC Propane Northwest Propane Northwest 11900 NE 95TH ST STE 400 1906 Marc Ave 1906 Marc Ave VANCOUVER, WA 98682 Tacoma, WA 98421 Tacoma, WA 98421, 253-875-3000 253-875-3000 LIC: 604 094 362 EXP: 03/31/2024 LIC: PROPAN*835PD EXP: 10/04/2023 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR LIC #: EXP: LIC #: EXP: JOB DESCRIPTION PERMIT TYPE: COMMERCIAL MECHANICAL CODE YEAR: 2018 STORIES: CONST. TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: OCC LOAD: PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for, or approval of, any violation of this Code or any other ordinance or order of the City, of any state or federal law, or of any order, proclamation, guidance advice or decision of the Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law, or order, proclamation, guidance advice or decision of the Governor of this State, this permit shall not authorize such work and shall not be valid. The building official is authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this jurisdiction or any other ordinance or executive order of the City, or of any state or federal law, or of any order, proclamation, guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect, inaccurate or incomplete information, or in violation of any City ordinance, regulation or order, state or federal law, or any order, proclamation, guidance or decision of the Governor. I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY; NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC 110/IRC 110. SALES TAX NOTICE: Sales to construction and c nstruction materials in the City of Arlington must be reported on your sales tax retu, form a coded City o Arlington #3101_ 11/13/2023 v�r App ' ant Signature Date Building Official Date CONDITIONS Will require bollard protection, bollards to be placed 4' on center max 3' min. bollards to be set in 15" min dia, hole 36 ' deep in concrete, must extend min. 36" above grade. Approved job copy shall be onsite for inspections. Call for inspections. The property owner shall ensure that the construction project complies with all applicable zoning codes and regulations. The Property owner shall also ensure that the construction project does not cause any adverse impact on the surrounding environment or community. The property owner shall be responsible for obtaining all necessary permits and approvals from the relevant authorities before commencing construction. The property owner shall ensure that die construction project complies with all applicable design review requirements. THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS, MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount 11/13/2023 Processing/Technology .00 11/13/2023 Mechanical Commercial Plan Review $$25$25.00 11/13/2023 Fuel/LPG 36 $100. Total Due: $369.36 Total Payment: $0.00 Balance Due: $369.36 CALL FOR INSPECTIONS Call by 3:30 pm for next day inspection, allow 48 hours for Fire Inspections When calling for an inspection please leave the following information: Permit Number, Type of Inspection being requested, and whether you prefer morning or afternoon INSPECTION INFORMATION Pass/Fail Permit#: 5512 Permit Date: 07/31/23 Permit Type: COMMERCIAL MECHANICAL Project Name: Air Gas USA LLC Applicant Name: Propane Northwest Applicant Address: 1906 Marc Ave Applicant, City, State, Zip: Tacoma,WA 98421 Contact: Kelly Kite Phone: 253-875-3000 Email: kkite@thompsongas.com Scope of Work: Install new 1000 gallon propane tank with dispenser equipment Valuation: 15000.00 Square Feet: 0 Number of Stories: 0 Construction Type: Occupancy Group: ID Code: Permit Issued: 12/22/2023 Permit Expires: 06/19/2024 Form Permit Type: COMMERCIAL MECHANICAL Status: COMPLETE Assigned To: Kristin Foster Property Parcel# Address Legal Description Owner Name Owner Phone Zoning AIRGAS-NOR 910 00746300001600 199TH ST NE UNDEVELOPED PAC INC (VACANT)LAND Contractors Contractor Primary Contact Phone Address Contractor Type License License# Propane Northwest Kelly Kite 253-875-3000 1906 Marc Ave CONSTRUCTION COA 604 094 362 CONTRACTOR Propane Northwest Kelly Kite 253-875-3000 1906 Marc Ave CONSTRUCTION L&I PROPAN*835PD CONTRACTOR Inspections Date Inspection Type Description Scheduled Date Completed Date Inspector Status C 14. 05/13/2024 MECHANICAL AM Requested 05/14/2024 05/14/2024 BUILDING Approved FINAL Plan Reviews Date Review Type Description Assigned To Review Status Will require bollard protection,bollards to be placed 4'on COMMERCIAL Approved with 07/31/2023 MECHANICAL center max 3'min.bollards to be set in 15"min dia,hole BUILDING Conditions 36'deep in concrete,must extend min.36"above grade 1000 gallon Propane tank 07/31/2023 COMMERCIAL 1000 gallon tank required to be 25 feet away from FIRE Approved MECHANICAL buildings,public ways,or LOT LINES of adjoining property that can be built on. 08/10/2023 OPERATING Dispenser FIRE Approved Fees Fee Description Notes Amount Processing/Technology $25.00 Mechanical Commercial Plan Review Table 4-1 $244.36 Fuel/LPG Installation/Removal $100.00 Credit Card Service $11.08 Total $380.44 Attached Letters Date Letter Description 11/13/2023 Building Permit Payments Date Paid By Description Payment Type Accepted By Amount 12/21/2023 XBP Conf: $369.36 161403435 12/21/2023 Kelly Kite 161403435 $11.08 Outstanding Balance $0.00 Notes Date Note Created By: 04/29/2024 sent expiration notice Hannah Hardwick 12/21/2023 sent link for payment again Hannah Hardwick 12/21/2023 Emailed the permit for signature. Kristin Foster 09/19/2023 Sent follow up email for resubmittal per SG 8.9.2023 review comment letter. Kristin Foster 09/19/2023 Received email from Kelly in response to SG comments.Waiting for SG to respond. Kristin Foster 08/16/2023 Do we need a Special Inspection and Testing Agreement for the anchoring? Kristin Foster 07/31/2023 The property where the tank is to be installed does not have an address.The address provided on Kristin Foster the application is for the Airgas office parcel. Uploaded Files Date File Name 12/22/2023 18005616-20230809 BLD5512 ApprovedSitePlan.pdf 12/22/2023 18005614-20231222 BLD5512 IssuedPermit.pdf 07/31/2023 16346974-20230731 BLD5512 AerialView.pdf 07/31/2023 16346858-20230728 BLD5512 Tank Specs.pdf 07/31/2023 16346859-20230728 BLD5512 App.pdf Date: 05/29/2026 Permit#: 5512 Permit Date: 07/31/2023 Review Date: 08/10/2023 Permit Type: COMMERCIAL MECHANICAL Review Type: OPERATING Target Date: 08/10/2023 Scheduled Time: 08:00 Completed Date: 08/10/2023 Description: Dispenser Review Status: Approved Assigned To: FIRE Time In: 07:00 Time Out: 07:30 Hours: 0.5 Notes 11/13/2023 Spoke with Steve on 11.8.2023 and he is ok to issue. Property Information Parcel#: 00746300001600 AIRGAS -NOR PAC INC AIRGAS -NOR PAC INC 11900 NE 95TH ST STE 400 199TH ST NE VANCOUVER,WA 98682 Zoning: 910 UNDEVELOPED (VACANT) LANDLot: Block: Uploaded Files Date File Name Uploaded By 08/10/2023 1646906 1-Comment Letter 8.9.23 Goforth.ndf Steve Goforth Date: 05/29/2026 Permit#: 5512 Permit Date: 07/31/2023 Review Date: 07/31/2023 Permit Type: COMMERCIAL MECHANICAL Review Type: COMMERCIAL MECHANICAL Target Date: 08/28/2023 Scheduled 10:00 Time: Completed 08/01/2023 Date: Description: 1000 gallon Propane tank 1000 gallon tank required to be 25 feet away from buildings, public ways, or LOT LINES of adjoining property that can be built on. Review Status: Approved Assigned To: FIRE Time In: 10:00 Time Out: 10:30 Hours: 0.5 Notes 11/13/2023 Spoke with Steve on 11.8.2023 and he is ok to issue Property Information Parcel#: 00746300001600 AIRGAS -NOR PAC INC AIRGAS -NOR PAC INC 11900 NE 95TH ST STE 400 199TH ST NE VANCOUVER, WA 98682 Zoning: 910 UNDEVELOPED (VACANT) LANDLot: Block: Date: 05/29/2026 Permit#: 5512 Permit Date: 07/31/2023 Review Date: 07/31/2023 Permit Type: COMMERCIAL MECHANICAL Review Type: COMMERCIAL MECHANICAL Target Date: 08/28/2023 Scheduled 00:00 Time: Completed 08/09/2023 Date: Description: Will require bollard protection, bollards to be placed 4' on center max 3'min. bollards to be set in 15" min dia, hole 36 ' deep in concrete, must extend min. 3 6" above grade Review Approved with Conditions Status: Assigned To: BUILDING Time In: 00:00 Time Out: 00:00 Hours: 0.75 Notes 08/09/2023 Will require bollard protection, bollards to be placed 4' on center max 3' min. bollards to be set in 15" min dia, hole 36 ' deep in concrete, must extend min. 36" above grade Property Information Parcel#: 00746300001600 AIRGAS -NOR PAC INC AIRGAS -NOR PAC INC 11900 NE 95TH ST STE 400 199TH ST NE VANCOUVER,WA 98682 Zoning: 910 UNDEVELOPED (VACANT) LANDLot: Block: