HomeMy WebLinkAbout17216 51st Ave Ne Ste 110_BLD5756_2026 CITY OF ARLINGTON
18204 59th Avenue NE,Arlington,WA 98223
INSPECTIONS:360-403-3417-Permit Center:360-403-3551
BUILDING PERMIT Wr
17216 51ST AVE NE STE 110 Permit#:5756
Parcel#:31052100400100 PERMIT EXPIRES 180 DAYS AFTER
DATE OF ISSUANCE.
Scope of Work:Modify existing sprinkler system to protect tenant improvements to Valuation:19062.00
walls and ceiling
OWNER T APPLICANT CONTRACTOR i
SMARTCAP ARLINGTON AIRPORT Travis Mackey PATRIOT FIRE PROTECTION
INDUSTRIAL PA
8201 164TH AVE NE STE 110 2707,70th ave e 2707 70th Ave E
REDMOND,WA 98052 tacoma Tacoma,WA 98424
2533618603 4259262290
LIC:601269 686 EXP:08/31/2024
LIC:PATRIFP099CF EXP:10/05/2024
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
710001K-
PERMIT TYPE: FIRE SPRINKLER CODE YEAR: 2018
STORIES: I CONST.TYPE: IA
DWELLING UNITS: OCC GROUP: B;Business
BUILDINGS: OCC LOAD:
- PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any
other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the
Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance advice
or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building official is
authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this jurisdiction or
any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation,guidance advice or
decision of the Governor.The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or
on the basis of incorrect,inaccurate or incomplete information,or in violation of any City ordinance,regulation or order,state or
federal law,or any order,proclamation,guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY;NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE
STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED.IBCl l0/IRC110.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
Digllally Mackey.,OU S Travis Travis Mackey Dale cM24.02-07 42 3-8-00'aekey m,O=Paltlo Fire
02/O1/2024
Applicant Signature Date Building Official Date
CONDITIONS 9r
Approved job copy shall be onsite for inspections.Adhere to approved plans. Call for inspection.Permit shall be onsite for
inspection.
The property owner shall ensure that the construction project complies with all applicable zoning codes and regulations.The property
owner shall also ensure that the construction project does not cause any adverse impact on the surrounding environment or
community.The property owner shall be responsible for obtaining all necessary permits and approvals from the relevant authorities
before commencing construction.The property owner shall ensure that the construction project complies with all applicable design
review requirements.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY.ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS,SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES -
Date Description Fee Amount
02/01/2024 Web Only-Fire System Plan Review $200.00
02/01/2024 Fire System Plan Re\iew $99.88
02/01/2024 Credit Card Service $6.00
02/01/2024 Credit Card Service $3.00
02/01/2024 Fire Sprinkler System $600.00
02/01/2024 Processing/Technology $25.00
Total Due: $933.88
Total Payment: $933.88
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
INSPECTION INFORMATION I Pass/Fail
i
FIRE SPRINKLER PERMIT APPLICATION
• Community and Economic Development
City of Arlington• 18204 59th Ave NE•Arlington,WA 98223 • Phone(360) 403-3551
Type of Permit: ❑ New Installation ✓❑ System Modification ❑ Phased Installation
Property Address. 17310 51 st Ave Ne Suite No.: Project Valuation: 19,062.00.00
Lot#: Parcel ID No.: 31052100400100 Preferred Contact: ❑ Owner ❑Applicant
❑ Contractor
Project Description:
Modify existing system to protect new tenant improvements to walls and ceiling.
Owner Name: Smartcap Phone No.: 206-619-4472
Email Address: Kellanne@thesmartcapgroup.com Cell No.:
Mailing Address: 8201 164th Ave Ne City: Redmond State: WA Zip: 98233
Applicant Name: Travis Mackey Phone No.:
Email Address: Travis.mackey@patriotfire.com Cell No.: 253-361-8603
Mailing Address: 2707 70th ave E city: Tacoma State: WA Zip: 98424
Contractor Name: Patriot Fire Protection Office No.: 253-926-2290
Email Address: Travis.mackey@patriotfire.com Cell No.: 253-361-8603
Mailing Address: 2707 70th ave E City: Tacoma State: WA Zip: 98424
L&I Contractor License Number: PATRIFP099CF Expiration Date: 10/23
SUBMITTAL REQUIREMENTS: Provide Information on All Equipment to be Installed Prior to Installation
ELECTRONIC FILES OF THE FOLLOW:
0 Complete and Scaled Plans
❑ Hydraulic Calculations
Q Equipment Specifications for Each Fire Sprinkler Permit Application
❑ Specification Sheets
❑ Wiring Diagrams (Point to Point Wiring)
❑ Electrical Plans,if applicable
FIRE SPRINKLER SYSTEMS (105.7.1, 105.7.4, 105.7.11)
** DEVICES include separate individual portions of a Fire Sprinkler System such as: Sprinklers Heads,
Risers, Valves, Pull Stations, and other such devices. (Each piece is one device)
PLAN REVIEW FEES
Less than $5,000.00 = $100.00
$5,000.00 &over-based on project valuation
(Plan Review Fee is 65%of project valuation as calculated per Table 4-1)
REV11.2020 Page 1 of 3
REINSPECTION / PHASED INSTALLATION INSPECTIONS
Submit Phasing Plan with Application - review and approval required
REINSPECTION FEES SHALL BE PAID PRIOR TO INSPECTION FEE
Reinspection/Phased Installation fee is charged per hour (1 hour minimum) $75.00
Hydrostatic Pressure Test(1 test included per permit) $150.00
Cover Inspection (1 cover inspection included per permit) $75.00
Fire Pump (1 fire pump inspection per permit) inspection requires 2 hours $150.00
✓❑ TENANT IMPROVEMENT OR SYSTEM MODIFICATION (NFPA 13/13R)
Number of Devices" Device Fee Subtotal
1to2 $ 75.00 = $
3 to 5 $125.00 = $
6 to 10 $175.00 = $
11 to 20 $225.00 = $
21 to 40 $300.00 = $ 300.00
41 to 100 $375.00 = $
101 to 200 $475.00 = $
201 to 300 $575.00 = $
> 300 $600.00 plus$50.00 per 100 additional devices(round up)
Total Number of Devices = 33 $600.00 + $ _ $
Hydraulically Designed Systems Yes 0 No ❑ Yes = Permit Fee x 2 $
PERMIT FEE SUBTOTAL $
NEW COMMERCIAL SYSTEM (NFPA 13/13R)
Number of Devices" Device Fee Subtotal
1 to 100 $375.00 = $
101 to 200 $475.00 = $
201 to 300 $600.00 = $
> 300 $625.00 plus$50.00 per 100 additional devices(round up)
Total Number of Devices = $625.00 + 1 $ _ $
Hydraulically Designed Systems Yes ❑ No ❑ Yes = Permit Fee x 2 $
PERMIT FEE SUBTOTAL $
RESIDENTIAL (NFPA 13D)
Number of Devices" Device Fee Subtotal
1 to 10 $175.00 = $
11 to 25 $225.00 = $
26 + $275.00 = $
*NFPA 13D SYSTEM INSTALLED(NOT REQUIRED)Permit Fee Reduced 50% = $
PERMIT FEE SUBTOTAL $
REV2022 Page 2 of 3
❑ HOOD SUPPRESSION SYSTEM
Type of System No. of Units Cost per Unit Subtotal
Pre-Engineered x $200.00 = $
Custom Engineered x $275.00 = $
PERMIT FEE SUBTOTAL $
❑ STANDPIPE SYSTEM
Type of Standpipe No. of Units Cost per Unit Subtotal
Class I - new or existing x $150.00 = $
Class II - new or existing x $150.00 = $
PERMIT FEE SUBTOTAL $
❑ FIRE PUMP
Fire Pump x $300.00 each = $
PERMIT FEE SUBTOTAL $
❑ SPRAY BOOTHS (105.7) &INDUSTRIAL OVENS (105.7.7)
NOTE.SEPARATE SPRINKLER PERMIT REQUIRED
Type of Booth No. of Units Cost per Unit Subtotal
Pre-Engineered w/documents x $150.00 = $
Site-built or used w/o documents x $250.00 = $
Industrial Oven x $250.00 = $
PERMIT FEE SUBTOTAL $
Plan review fee due at time of submittal
TOTAL PERMIT FEE $
PLAN REVIEW FEE $
Processing/Technology Fee $25.00
TOTAL $
I hereby certify that I am the ❑ Owner, ✓❑Applicant, ❑ Contractor,and authorized to sign this application and that the above
information is correct and construction on, and the occupancy and the use of the above-described property will be in accordance
with the laws,rules and regulation of the State of Washington,and the City of Arlington.
Digitally signed by Travis Mackey
yDlatePmtection,O4520208TavislMackeyO=Patriot
Travis Macke Travis Mackey 1 /3/24
Signature Print Name Date
SAVE PRINT
REV2022 Page 3 0f 3
Bulletin 070 December 2022
Rel
® Model P25 ESFR
Pendent Sprinklers
175 psi (12 bar) rated
Features _
• FM Approved as a quick-response storage and non-storage Z
sprinkler
• Robust fusible link operating element
• Compact design
Product Description
The Reliable Model P25 is an Early Suppression Fast Response ;,
(ESFR)fire sprinkler with a nominal K-factor of 25.2(360
metric).The sprinkler uses a levered fusible alloy solder link in
either a 165°F(74°C)or a 212°F(100°C)temperature rating.
These sprinklers are designed to respond quickly to growing —
fires and will deliver a heavy water discharge to suppress a fire.
Suppression is considered a higher level of control characterized
by a sharp reduction in heat release rate along with preventing Model P25 ESFR Sprinkler
regrowth of the fire.
For systems designed in accordance with NFPA 13 standards,
the Model P25 is considered an ESFR fire sprinkler. FM Approvals
classifies the Model P25 as a quick-response storage and
non-storage sprinkler when used in accordance with FM Global :
Property Loss Prevention Data Sheets.
The Model P25 fire sprinkler may also be used as an in-rack
sprinkler where permitted by NPFA or FM. A sprinkler guard
and water shield is available when the Model P25 is used in this
application(threaded sprinkler only).
Model P25 ESFR sprinklers are designed to be shorter and more
compact than other ESFR sprinklers, allowing greater flexibility
with regard to distance from ceilings and obstructions. The
P25 ESFR sprinklers are also less susceptible to damage due
to smaller deflector and frame design.The lighter P25 ESFR
sprinklers passed rough use and abuse listing tests without
plastic protectors.
Model P25 sprinklers are available with 1" NPT or IS07/1-R1
(BSPT)threads, and also with the Victaulic®IGSTM Style V9 Model P25 ESFR Grooved
Sprinkler Coupling*.
*Note:Victaulic®and IGSTm are trademarks of Victaulic
Company
Model P25 ESFR Pendent Sprinklers , .I-
Model Nominal K-factor Approvals Sprinkler Identification
gpm/psi (L/min/bar,z) Number(SIN)
P25 25.2 (360) FM R602
www.reliablesprinkler.com
Model .1
Technical Specifications Sprinkler Finishes
Style:Pendent Bronze
Connection:
1"NPT Sensitivity
IS07-1 R1 (BSPT)threads Fast-Response
Victaulic®IGSTM Style V9 Coupling Quick-Response(FM)
Nominal K-Factor:25.2(360 metric) - -
Max.Working Pressure: 175 psi(12 bar) Temperature Ratings
Ordinary: 165°F(74°C)
Material Specifications Intermediate:212°F(100°C)
Thermal Sensor:Nickel Alloy Solder Link
Sprinkler Frame:Brass Alloy Sprinkler Wrench
Cap:Bronze Alloy Model W5
Sealing Assembly:Nickel Alloy with PTFE Model W16(with guard)
Load Screw:Bronze Alloy
Deflector:Bronze Alloy Guards&Shields*
Kick Spring:Nickel Alloy Model D-14 Guard — -
Model S-5 Shield
Listings and Approvals
FM Approved
*Note:Guard and guard/shield combination is available for threaded sprinklers only and is approved for in-rack or intermediate level use
only. Not approved for general use elsewhere.
Model P25 Sprinkler Dimensions and Components
215/16"[75mm]
2"[52mm]
THREADS
(ALT GROOVE)
1 5/8"[40mm] _
G SG WRENCH
BOSS
2 7/8"[74mm] 2 718"[73mm] >
® THERMAL - CAP/SEAL
a
®' ELEMENT
STRUT
LEVER LOAD SCREW
DEFLECTOR
THREADED GROOVED
070FG01
S� S�
0, 0 0
0 0
Bulletin 070 ReliablEt Page 3 of 5
December 2022 www.reliablesprinkler.com
Model P25 Sprinkler with Model D-14 Guard&S-5 Water Shield
41/2"[114mm]
(S-5 Water Shield)
070FG02
When used without the S-5
3 5116" Water Shield,a 1"lock-nut is
[85mm] required to secure the D-14
Guard.
3 5/16"
[85mm]
Note: Guard and guard/shield combination is available for threaded sprinklers only and is approved for in-rack or intermediate level use
only. Not approved for general use elsewhere.
Model P25 Commodity Selection and Design Criteria Overview 11171.101-
Storage Type NFPA FM GLOBAL
Sprinkler Type ESFR Storage
Response Type ESFR Quick Response
System Type Wet Wet
Temperature Rating T(°C) 165(74), 212(100) 165(74), 212(100)
Roof Construction See NFPA 13 See FM Global 2-0
Ceiling Slope See NFPA 13 See FM Global 2-0
Maximum Coverage Area See NFPA 13 See FM Global 2-0
Minimum Coverage Area See NFPA 13 See FM Global 2-0
Maximum Spacing See NFPA 13 See FM Global 2-0
Minimum Spacing See NFPA 13 See FM Global 2-0
Minimum Clearance to Commodity See NFPA 13 See FM Global 2-0
Sprinkler Distance to Ceiling See NFPA 13 See FM Global 2-0
Open Frame,Single, Double, Multiple
Row, or Portable Rack Storage of See NFPA 13 See FM 2-0&8-9
Class I-IV, and Group A Plastics
Solid Pile or Palletized Storage of See NFPA 13 See FM 2-0&8-9
Class I-IV and Group A Plastics
Idle Pallet Storage See NFPA 13 See FM 2-0, 8-9&8-24
Rubber Tire Storage See NFPA 13 See FM 2-0&8-3
Rolled Paper Storage See NFPA 13 See FM 8-21
Flammable Liquid Storage See NFPA 30 See FM 7-29
Aerosol Storage See NFPA 30B See FM 7-31
Auto Components in Portable Racks See NFPA 13 See FM 2-0 and 8-9
Bulletin 070 ReliablE� Page 4 of 5
December 2022 www.reliablesprinkler.com
Installation
Model P25 sprinklers are intended for installation in accordance
with NFPA 13 and FM Loss Prevention Data Sheets 2-0 and 8-9,
as well as the requirements of any Authorities Having Jurisdiction.
See Table B for information on NFPA and FM Global design
criteria for the Model P25 sprinkler.
Caution:When handling sprinklers, hold sprinklers only by the
frame arms and do not apply any force on the link assembly.
For threaded sprinklers only, use the Model W5 or W16 sprinkler Note: I" S/142 IGSTM grooved welded
wrench (see Figure 3)for removal and installation.Any other type outlets are also available from Reliable.
of wrench may damage the sprinkler.A grooved wrench boss
is provided on the sprinkler to limit the potential for the wrench
to slip during installation. After applying a thread sealant to the VictaulicO IGST^^Style V9
male sprinkler threads, Model P25 sprinklers should be tightened Sprinkler Coupling installation bit
between 22-30 lb-ft(30-40 N•m)torque. Exceeding the maximum -One bit provided in each box of
recommended torque may cause leakage or impairment of the 25 sprinklers.
sprinkler. Damaged sprinklers must be replaced immediately.
For grooved sprinklers, push the IGSTM Style V9 Sprinkler Cou-
pling onto the grooved outlet until contact with the center leg of Wrenches
the gasket occurs.Align the sprinkler frame arms and the pads
of the coupling with the sprinkler piping and tighten the coupling
until the pads of the coupling meet. For additional information,
please reference VictaulicO technical bulletin I-V9.
Failure to follow these installation instructions may results in leaks, Model W5 Wrench
inadvertent operation, or non-operation of sprinklers.
Maintenance
Reliable Model P25 sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25, as well
as the requirements of any Authorities Having Jurisdiction.
Prior to installation, sprinklers should remain in the original Model W16 Wrench (with guard)
cartons and packaging until used.This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation. Ordering Information
Do not clean sprinklers with soap and water, ammonia liquid or Specify:
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler. Sprinkler
• P25
Replace any sprinkler which has been painted (other than factory
applied). Temperature Rating
165°F(64°C)
Once operated,automatic sprinklers cannot be reassembled 212°F(100°C)
and/or reused.A stock of spare sprinklers should be maintained End Connection
to allow quick replacement of damaged or operated sprinklers. 1" NPT
IS07-1 R1 (BSPT)
Failure to properly maintain sprinklers may result in inadvertent Victaulic0 IGSTM Style V9 Sprinkler Coupling
operation or non-operation during a fire event.
Optional
• Model D-14 Guard
Guarantee Model S-5 Shield
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions,visit www.reliablesi2rinkler.com. Note:Victaulic0 and IGSTm are trademarks of Victaulic Company. Cl)
ti
rn
rn
rn
rn
Bulletin 070 Reliable Page 5 of 5 z
December 2022 www.reliablesprinkler.com a
Bulletin 034 February 2021
Rel
Q Model G5 Series Sprinklers
Standard Spray, Flat Concealed Pendent
Available with Gasketed Cover Plate
Features
• Standard Coverage,Concealed Pendent(K2.8,4.2,5.6,&8.0
[40,60,80,&115 metric])
• Flat concealed cover plate available in a variety of finishes.
• Available with Stainless Steel Clad cover plate(see Table 1).
• 3/4-inch(19 mm)cover plate adjustment.
• Cover plate available with optional gasket.
Model G5 Cover Plate Model G5 Cover Plate
Product Description with QR Gasket
Model G5 series sprinklers are standard coverage,flat plate
concealed sprinklers designed for installation in accordance with
NFPA 13 and FM Global Property Loss Prevention Data Sheets.All
Model G5 series sprinklers use a fusible-link operating element.
The sprinklers are offered with a standard Model G5 cover plate,
a Model G5 cover plate with a quick-response(QR)gasket,or a kfta�
Model G5 cover plate with a standard-response(SR)gasket. Model
G5 sprinklers with a gasketed cover plate are intended for use in Model G5 Cover Plate
dust free environments such as clean rooms. with SR Gasket
Model G5 sprinklers must only be used with the Model G5 cover Note:Gasket material is silicone rubber, available in white only.
plate listed or approved with the sprinkler.Table A provides a
summary of available Model G5 series sprinklers,along with
Listing and Approval information for each sprinkler and cover plate
combination.
Model G5 Series Sprinkler Summary
K-Factor Listings Max.Working Sprinkler
Sprinkler gpm/ps112 Cover Plate and Sensitivity Pressure Identification
Model Wrnlln/bar'1z) Model Approvals psi(bar) Number(SIN)
G5 cULus QR
SR
G5-28 2.8(40) G5 QR Gasket cULus QR 175(12) RA3411
G5 SR Gasket cULus, FM SR
4.2 G5
G5-42 (60) G5 QR Gasket cULus QR 175(12) RA3413
G5 SR Gasket cULus SR
G5 cULus QR 250(17)
FM, LPCB,VdS, CE SR 175(12)
G5-56 (80) G5 QR Gasket cULus QR 250(17) RA3415
G5 SR Gasket cULus SR 250(17)
FM SR 175(12)
G5
G5-56 300 (80) G5 QR Gasket cULus QR 300(21) RA4014
G5 SR Gasket cULus SR
8.0 G5
G5-80 ($1o) G5 QR Gasket cULus QR 175(12) RA3412
G5 SR Gasket cULus SR
G5-80F (8.0) G5 SR Gasket FM SR 175(12) RA3417
www.reliablesprinkler.com
StandardModel G5-28 .
Technical Specifications Sprinkler Temperature Ratings
Style:Flat Concealed Pendent 165°F(74°C)
Threads:1/2"NPT or ISO 7-1 R1/2 212°F(100°C)
Nominal K-Factor:2.8(40 metric) Sensitivity
Max.Working Pressure:175 psi(12 bar) (See Table B)
Material Specifications Cover Plates
Fusible Link:Beryllium Nickel Model G5
Sprinkler Body:Brass Alloy Model G5 QR Gasket(cULus only)
Levers:Bronze Alloy Model G5 SR Gasket -
Yoke:Brass Alloy
Cover Plate Finishes
Sealing washer:Nickel with PTFE
Load Screw:Bronze Alloy (See Table I)
Towers:Copper Alloy Sprinkler Wrench r
Pins:Stainless Steel Model W3
Deflector:Bronze Alloy Model FC
Cup:Steel Listings and Approvals
cULus Listed(Light Hazard only)
FM Approved
Model G5-28 Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Ceiling
Tower
Fusible Link 3/4"(19 mm)Max. ' --
Deflector(retracted)-I A" i Cover Plate Adjustment 3/16"(5 mm)
�,�����
Pin(extended)
Deflector(extended)
Model G4/G5 Cover Plate 3-5/16"(84 mm)Dia. Ceiling
Model G5-28 Sprinkler Sensitivity
Listing or Approval Agency
Cover Plate Model
cULus FM
G5 QR SR 7
G5 QR Gasket OR
G5 SR Gasket SR SR
QR: Quick-response
SR:Standard-response
Bulletin 034 Reliable Page 2 of 9
February 2021 www.reliablesprinkler.com
StandardModel G5-42 .
Technical Specifications Sprinkler Temperature Ratings
Style:Flat Concealed Pendent 165°F(74°C)
Threads:112"NPT or ISO 7-1 Ri/2 212°F(100°C)
Nominal K-Factor:4.2(60 metric) Sensitivity
Max.Working Pressure:175 psi(12 bar) (See Table C)
Material Specifications Cover Plates
Fusible Link:Beryllium Nickel Model G5
Sprinkler Body:Brass Alloy Model G5 QR Gasket ;
>n � q
Levers:Bronze Alloy Model G5 SR Gasket !;
Yoke:Brass Alloy
Sealing washer:Nickel with PTFE Cover Plate Finishes
Load Screw:Bronze Alloy (See Table I) r
Towers:Copper Alloy Sprinkler Wrench s o`
Pins:Stainless Steel Model W3
Deflector:Bronze Alloy Model FC
Cup:Steel Listings and Approvals
cULus Listed(Light Hazard only)
Model G5-42 Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Ceiling
Tower 43-5/16-
Fusible Link3/4"(19 mm)Max.Deflector(retracted) Cover Plate Adjustment3/16"(5 mm)
Pin(extended)Deflector(extended) __ _ Model G4/G5 Cover Plate . Ceiling
Model G5-42 Sensitivity
Listing or Approval Agency
Cover Plate Model
cULus
G5 QR
G5 QR Gasket OR
G5 SR Gasket SR
QR: Quick-response
SR: Standard-response
Bulletin 034 Reliable Page 3 of 9
February 2021 www.reliablesprinkler.com
StandardModel G5-56 .
Technical Specifications Sprinkler Temperature Ratings
Style:Flat Concealed Pendent 165°F(74°C)
Threads:1/2"NPT or ISO 7-1 R1/2 212'F(100°C)(cULus,FM,LPCB,CE only)
Nominal K-Factor:5.6(80 metric) Sensitivity
Max.Working Pressure: (See Table D)
175 psi(12 bar) Cover Plates
250 psi(17 bar)(cULus only) Model G5
Material Specifications Model G5 QR Gasket(cULus only) ^-
Fusible Link: Beryllium Nickel Model G5 SR Gasket(cULus and FM only)
Sprinkler Body:Brass Alloy
Levers:Bronze Alloy Cover Plate Finishes -
Yoke:Brass Alloy (See Table I)
Sealing washer:Nickel with PTFE Sprinkler Wrench
Load Screw:Bronze Alloy Model W3
Towers:Copper Alloy Model FC r
Pins:Stainless Steel Listings and Approvals a' d
Deflector:Bronze Alloy cULus Listed(Light&Ordinary Hazard only)
Cup:Steel FM Approved
LPCB Approved
VdS Approved[165'F(74'C)only]
CE Listed(2831-CPR-S2062)
Model G5-56 Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Ceiling
Tower 43-5116"(84mm)Dia.l_�
Fusible Link3/4"(19 mm)Max.Deflector(retracted)3c Cover Plate Adjustment3/16"(5 mm)
Pin(extended)
Deflector(extended) Model G4/G5 Cover PlateCeiling
Model G5-56 Sensitivity
Listing or Approval Agency
Cover Plate Model
cULus FM LPCB,VdS,CE
G5 OR SR SR
G5 QR Gasket QR -
G5 SR Gasket SR SR
QR: Quick-response
SR: Standard-response
Bulletin 034 Reliable Page 4 of 9
February 2021 www.reliablesprinkler.com
Model11 Standard Coverage, • • Pendent Sprinkler1
Technical Specifications Sprinkler Temperature Ratings
Style:Flat Concealed Pendent 165°F(74-C)
Threads:1/2"NPT or ISO 7-1 R1/2 212°F(100°C)
Nominal K-Factor:5.6(80 metric) Sensitivity
Max.Working Pressure:300 psi(21 bar) (See Table E)
Material Specifications Cover Plates
Fusible Link:Beryllium Nickel Model G5
Sprinkler Body:Brass Alloy Model G5 QR Gasket
K
Levers:Bronze Alloy Model G5 SR Gasket '
Yoke:Brass Alloy
Cover Plate Finishes
Sealing washer:Nickel with PTFE < »,
(See Table I)
Load Screw:Bronze Alloy q o
Towers:Copper Alloy Sprinkler Wrench
Pins:Stainless Steel Model W3
Deflector:Bronze Alloy Model FC
Cup:Steel Listings and Approvals
cULus Listed(Light&Ordinary Hazard only)
Model G5-56 300 Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Ceiling
Tower
Fusible Link 3/4"(19 mm)Max. -
3/16"(5 mm)
Deflector(retracted) Cover Plate Adjustment
Pin(extended)
Ili
Deflector(extended)
Model G4/G5 Cover Plate 3-5/16"(84 mm)Dia. Ceiling
Model G5-56 300 Sensitivity F1 el rM
Listing or Approval Agency
Cover Plate Model
cULus
G5 QR 7
G5 QR Gasket QR
G5 SR Gasket SR
QR: Quick-response
SR:Standard-response
Bulletin 034 Reliable Page 5 of 9
February 2021 www.reliablesprinkler.com
Model :1 Standard
Technical Specifications Sprinkler Temperature Ratings
Style:Flat Concealed Pendent 165°F(74°C)
Threads:3/4"NPT or ISO 7-1 R3/4 212°F(100°C)
Nominal K-Factor:8.0(115 metric) Sensitivity
Max.Working Pressure:175 psi(12 bar) (See Table F)
Material Specifications Cover Plates
Fusible Link:Beryllium Nickel Model G5
Sprinkler Body:Brass Alloy Model G5 QR Gasket
Levers:Bronze Alloy Model G5 SR Gasket
Yoke:Brass Alloy
Sealing washer:Nickel with PTFE Cover Plate Finishes
(See Table I)
Load Screw:Bronze Alloy
Towers:Copper Alloy Sprinkler Wrench {
Pins:Stainless Steel Model W3
Deflector:Bronze Alloy Model FC
Cup:Steel Listings and Approvals
cULus Listed(Light&Ordinary Hazard only)
Model G5-80 Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Ceiling
Tower
Fusible Link 3/4"(19 mm)Max. -
Deflector(retracted) I Cover Plate Adjustment 3/16"(5 mm)
Pin(extended)
Deflector(extended)
Model G4/G5 Cover Plate 3-5/16"(84 mm)Dia. Ceiling
Model G5-80 Sensitivity
Listing or Approval Agency
Cover Plate Model
cULus
G5 QR
G5 QR Gasket QR
G5 SR Gasket SR
QR: Quick-response
SR: Standard-response
Bulletin 034 Reliable Page 6 of 9
February 2021 www.reliablesprinkler.com
Model :1Standard Coverage,Concealed Pendent Sprinkler SIN RA3417
Technical Specifications Sprinkler Temperature Ratings
Style:Flat Concealed Pendent 165-F(74°C)
Threads:3/4"NPT or ISO 7-1 R3/4 212-F(100-C)
Nominal K-Factor:8.0(115 metric) Sensitivity
Max.Working Pressure:175 psi(12 bar) Standard Response
Material Specifications Cover Plates
Fusible Link:Beryllium Nickel Model G5
Sprinkler Body:Brass Alloy Model G5 SR Gasket
Levers:Bronze Alloy
Yoke:Brass Alloy Cover Plate Finishes
Sealing washer:Nickel with PTFE (See Table I)
Load Screw:Bronze Alloy Sprinkler Wrench
Towers:Copper Alloy Model W3
Pins:Stainless Steel Model FC
Deflector:Stainless Steel Listings and Approvals
Cup:Steel FM Approved `
Model G5-80F Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Ceiling
Towerit :� --
Fusible Link 3/4"(19 mm)Max. -
Deflector(retracted) I Cover Plate Adjustment 3/16"(5 mm)
Pin(extended)
Deflector(extended) == =x
Model G4/G5 Cover Plate 3-5/16"(84 mm)Dia. Ceiling
Model G5-80F Sensitivity
Listing or Approval Agency
Cover Plate Model
FM
G5 SR
GSSR Gasket SR
SR:Standard-response
Bulletin 034 Reliable Page 7 of 9
February 2021 www.reliablesprinkler.com
Installation Dimensions and Cover Plate Information
Min.to Max. Min.to Max.
Cover Plate Recommended Cover Plate Face of Fitting Dropped Cover Plate
Cover Plate Diameter Hole Diameter in Adjustment to Deflector Temperature
Ceiling Distance Rating
Model Inch Inch Inch Ceiling(') below Ceiling °F g
(mm) (mm) (mm) Inch(mm) Inch (°C)
(mm)
G5 3-5/16
(84) 135°F(3)
G5 QR Gasket(') 3-11/16 (57°C)
(94) 2-5/8 3/4 1-1/2 to 2-1/4 1/4 to 1
(67) (19) (38 to 57) (6 to 25) or
G5 SR Gasket(2) 4 165°F(4)
(101 mm) (74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on nominal thread make up.Verify dimensions based on fitting and thread sealing method
prior to installation.A 1/2"x 1/2"brass nipple extension(Reliable P/N 6999991900)is available to assist with replacement of Reliable Model
G4A sprinklers.
2. Model G5 QR Gasket and Model G5 SR Gasket cover plates are sold as assembled units including both the cover plate and gasket. Model
G5 QR Gasket and Model G5 SR Gasket cover plates and gaskets are not interchangeable.
3. For use with 165°F(74°C)temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F(38°C).
4. For use with 212°F(100°C)temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F(66°C).
Cover Plate FinishesM 2)
Standard Finishes Special Application Finishes Listing & Approval Agencies
White Paint off-White Paint Individual Model G5 series sprinkler may be listed or approved by
Chrome(4) Black Paint the following agencies:
Custom Color Paint(Specify)(3) Underwriters Laboratories, Inc.and UL Canada(cULus)
Raw Brass(Lacquered) Listing Category: Sprinklers,Automatic and Open
Bright Brass(4) Guide Number: N V p
Finished Bronze 4> FM Approvals(FM)
Black Plated Satin Chrome(4) Loss Prevention Certification Board (LPCB)
•
Stainless Steel Clad') VdS SchadenverhOtung GmbH (VdS)
• EC-Certificate of Conformity 0832-CPD-2062(CE)
Notes: See Table A and the individual sprinkler data sheets in this Bulletin
1. Paint or any other coating applied over the factory finish will void all for listings and approvals applicable to each sprinkler.
approvals and warranties.
2. Cover plates do not carry corrosion resistant listings or approvals.
3. Custom color paint is semi-gloss unless specified otherwise.
4. Not listed for use with QR sealing gasket. Installation
5. Stainless steel clad cover plates are Type 316 Stainless Steel on the
finished side and C102 Copper Alloy on the back side. Model G5 series sprinklers are intended to be installed in
accordance with NFPA 13, FM Global Property Loss Prevention
Application Data Sheets, and the requirements of applicable authorities
having jurisdiction. Model G5 series sprinklers must not be
Model G5 series sprinklers are standard coverage,flat plate installed in ceilings with positive pressure in the space above.
concealed pendent sprinklers.The sprinklers are intended for Ensure that the 4 slots in the cup are open and unobstructed
use in accordance with NFPA 13 and FM Global Property Loss following installation.
Prevention Data Sheets,as well as the requirements of the Model G5 series sprinklers are shipped with a wrench-able
applicable approval agencies. protective cap that should remain on the sprinkler until the
sprinkler system is placed in service following construction.
Model G5 series sprinklers are available as either Quick-response Model G5 series sprinklers can be installed without removing
(QR)or Standard-response(SR)depending on the approval the wrench-able protective cap using the Model W3 wrench.
agency and cover plate selected. Alternatively, Model G5 series sprinklers can be installed using
the Model FC wrench by temporarily removing the protective cap
Model G5 series sprinklers use Model G5 flat cover plates. Model during installation of the sprinkler.The use of any other wrench
G5 QR Gasket and G5 SR Gasket cover plates are available to to installed Model G5 series sprinklers is not permitted and may
limit air and dust movement through the ceiling. damage the sprinkler.
Bulletin 034 ReliablE� Page 8 of 9
February 2021 www.reliablesprinkler.com
Am
Model FC Model W3
For use with Model G5 Series sprinklers For use with Model G5 Series sprinklers with
without wrench-able cap installed wrench-able cap installed
Fully insert the Model W3 wrench over the cap until it reaches Replace any sprinkler or cover plate which has been painted(other
the bottom of the cup,or the Model FC wrench over the sprinkler than factory applied). Properly installed Model G5 cover plates will
until the wrench engages the body. Do not wrench any other have an air gap that is required for proper operation, do not seal
part of the sprinkler/cup assembly.The Model W3 and FC the gap or paint the cover plates. Model G5 series sprinklers have
wrenches are designed to be turned with a standard 1/2"square holes in the cup that must remain unobstructed.
drive.Tighten the sprinkler into the fitting after applying a PTFE Replace any sprinkler which has been damaged.A stock of spare
based thread sealant to the sprinkler's threads. Recommended sprinklers should be maintained to allow quick re-placement
installation torque is specified in Table J. of damaged or operated sprinklers. Failure to properly maintain
sprinklers may result in inadvertent operation or non-operation
during a fire event.
Installation Torque
Recommended Installation Guarantee
Sprinkler Threads Torque (min.—max.) For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
ft.lb N.m and conditions,visit www.reliablesprinkler.com.
'/2" NPT or IS07-1 R1/2 8-18 11-24
3/4" NPT or IS07-1 R3/4 14-20 19-27 Patents
Do not exceed the maximum recommended torque.Exceeding the Model G5 series sprinklers may be covered by one or more of the
maximum recommended torque may cause leakage or impairment following patents:
of the sprinkler. Use care when inserting or removing the wrench U.S. Patent 6,554,077, U.S. Patent 7,275,603, U.S. Patent
from the sprinkler to avoid damage to the sprinkler. 8,776,903, U.S. Patent 9,248,327
Install the cover plate by hand,pushing and then turning the cover Ordering Information
in the clockwise direction until it is tight against the ceiling. For Specify the following when ordering.
Model G5 QR Gasket and Model G5 SR Gasket cover plates, the
gasket should be attached to the flange of the cover plate skirt Sprinkler
only. Do not glue the gasket in place or allow the gasket to overlap • Model [G5-28] [G5-42] [G5-56] [G5-56 300]
both the cover plate and the flange of the skirt. [G5-80] [G5-80F]
• Temperature Rating [165°F(74°C)] [212°F(100°C)]
Maintenance • Threads[NPT or ISO 7-1]
Reliable Model G5 series sprinkler should be inspected and the Cover Plate
sprinkler system maintained in accordance with NFPA 25, as well • Model [G5, G5 QR Gasket, G5 SR Gasket]
as the requirements of any Authorities Having Jurisdiction. • Finish(See Table 1)
Prior to installation,sprinklers should remain in the original cartons Sprinkler Wrench
and packaging until used. This will minimize the potential for • Model W3
damage to sprinklers that could cause improper operation or non- • Model FC
operation.
Do not clean sprinklers with soap and water,ammonia liquid or any
other cleaning fluids. Remove dust by gentle vacuuming without oD
touching the sprinkler. rn
rn
rn
rn
z
Bulletin 034 Reliable Page 9 of 9
February 2021 www.reliablesprinkler.com
FLEXHEAD Flexible Sprinkler Connections
Z ANVIL
STANDARD TALL SERIES HOSE
Unlike traditional hard-piped fire protection systems,
FlexHead° sprinkler connections allow engineers,
architects, contractors and building owners a degree of
versatility previously unavailable, featuring:
• Industrial grade material
• Acceptable for use in a return-air plenum
STANDARD TALL HOSE:available in 24", 36",48", 60", 72"hose lengths. • Perfect center-of-tile and aesthetic uniformity
Rated working pressure 175psi, Straight model, Standard 1"I.D.
• Approved for use with medium and heavy load
grids (ASTM C635, 636)
_ • 100% leak-tested connections
• All welded, no o-rings
• Adjustable height and sprinkler alignment
• Proven technology
• Ceiling system compatibility
STANDARD ELBOW TALL HOSE: 24", 36",48", 60", 72"hose lengths. • Compatible with FM / UL sprinklers
Rated working pressure I75psi, Elbow model. • Meets 2013 NFPA 13 guidelines
• UL Approved for installation in dry wall ceiling grids
FM U�
APPROVED ® FLEXHEAD SUSPENDED CEILING DETAIL
The benefits of installing FlexHead Commercial `�.x.,�--=t-------- -= ------�='=�--'
Connections include: `''~
• Uniform bids / construction schedules lie
• Reduced man power and labor costs
• Retrofit existing buildings within confined spaces
quickly and easily
• Increased efficiency
• Quick and easy installation
• Simple friction loss /water pressure calculations FLEXHEAD SHEETROCK CEILING DETAIL
• Relocate and reconfigure without draining and
disassembling
• Flexible design provides versatility for changes in
floor plan or occupancy y
• Reduced service calls
i
• No call-backs due to quality manufacturing _
• Rapid construction schedules allowing fast-track
building occupancy
PROJECT
Project: ❑Approved
Address: ❑Approved as noted
Contractor: ❑Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
FP-8.18
c Z /ANVIL
FLEXHEAD Flexible Sprinkler Connections
STANDARD 1_ SERF HOSE
20XXT(STRAIGHT)
L,20mm
6.3 i8) 3
11591 TYP 304SS SCH 40 PIPE (76.21
I /
011
. 1
133.401
m . I; . . . . MEE=
OUTLET SIZE I"NPT THREADS
SEE CHART TO ANSI B1.20.1
MODEL NUMBER:
20XXT-XX
TT-50(l/2"NPT OUTLET SIZE)
OR 75(3/4"NPT OUTLET SIZE)
=TALL SERIES HOSE
All dimensions are in inches
=HOSE LENGTH(24",36",4S",60",OR 72")
FLEXHEAD STANDARD TALL HOSE SERIES - 1" INTERNAL DIAMETER (I.D.) HOSE SERIES
Hose Minimum Max.Number Equivalent Length of 1 in.Schedule 40 Pie(Ft.) Max.Rated
Model Outlet Assembly Braid Bend Radius of 90°Bends q g p Working Pressure
Number Orifice Length Length FM
Size (Ll (B) FM UL FM UL UL FM UL
5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor
In./cm. In./mm. In./mm. In./mm. In./mm. In./mm. In./mm. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. Ft./m. PSI/Kpa PSI/Kpa
24 14.7 11 18.4 7.7 7.6
2024T50 610 373.4 1 3 3.4 5.6 2.3 2.3
2036T-50 36 26.7 2 3 16 26.6 11.5 11.5
914 678.2 4.9 8.1 3.5 3.5
2048T-50 1/2 48 38.7 8 3 3 4 24 30.3 15.3 15.3 175 175
1.27 1219 983.0 200 76.2 7.3 9.2 4.6 4.7 1205 1205
60 50.7 29 35.8 19.1 19.3
2060T50 1524 1287.8 4 4 8.8 10.9 5.8 5.8
72 62.7 35 45.6 23 23.2
2072T50 1828 1592.6 4 4 10.7 13.9 7 7
2024T-75 24 14.7 1 3 12 NSA 14.7 7.1
610 373.4 3.7 4.5 2.1
36 26.7 18 21.5 21.6 21.8 10.9
2036T15 914 678.2 2 3 5.5 NSA 6.5 6.6 6.6 3.3
2048T 15 1.940 121B 38.7 9 983 0 200 76.2 3 4 �0 N/A 3.35 303E e 8 14$ i 05 i 05
206OT--75 60 50.7 4 4 29 NSA 39.5 39.6 36.1 18.7
1524 1 1287.8 8.8 12 12 11 5.6
2072T75 72 62.7 4 4 32 NSA 48.5 48.8 43.2 22.6
1828 1592.E 9.8 1 14.7 1 14.9 1 13.1 1 6.8
Model Numbers:The"T"designates Tall Series Hose.The"50"designates I/?Outlet Hose Series.The"75"designates 1/4"Outlet Hose Series.
Equivalent Lengths are shown with maximum number of 90'bends at the minimum bend radius per agency.2-A5'or 3-30°bends equal 1-90`bend.Different values were obtained by
FM and UL due to the difference in minimum bend radius,testing protocol and calculation methods.Please see individual standards for more information relative to Friction Loss(equivalent
length of pipe).
See listing(s)approval agency for the latest approval details.
FP-8.18
c Z /ANVIL
FLEXHEAD Flexible Sprinkler Connections
STANDARD 1- SERF HOSE
20XXET(ELBOW)
L±20mm
i1=B1 3
76.21
9 ttP 304SS SCH 40 PIPE
1"NPT THREADS
5V TO ANSI B1.20.1
W-
65'-
7.2 4T MODEL NUMBER:
[1831w 20XX ET-XX
ao'- �=50(1/2"NPT OUTLET SIZE)
OR 75(3/4"NPT OUTLET SIZE)
1"- =ELBOW TALL SERIES HOSE
iv-
IT- =HOSE LENGTH(a',36",48",0',OR 72")
OUTLET SIZE
SEE CHART O 31
[33.401
FLEXHEAD ELBOW HOSE SERIES 1" INTERNAL DIAMETER • HOSE SERIES
Hose Minimum Max.Number Equivalentg Length of 1 in.Schedule 40 Pipe(Ft.) Max.Rated
Model Outlet Assembly Braid Bend Radius of 90'Bends Working Pressure
Number Orifice Length Length FM
Size (L) (B) FM UL FM UL UL FM UL
5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor
In./cm. In./mm. In./mm. In./mm. In./ram. In./mm. In./mm. Ft./m. Ft./m. Ft./m. Ft./m. Ft./Fn. Ft./m. PSI/Kpa PSI/Kpa
2024ET-50 24 19.5 1 3 19 26.4 6.8 7.4
610 495.3 5.8 8.0 2 2.2
2036ET-50 36 31.5 2 3 23 30.1 11.8 12.5
914 800.1 7.0 9.1 3.6 3.8
2048ET-50 '�2 48 43.5 8 3 3 4 27 33.8 16.9 17.6 175 175
1.27 1219 1104.9 200 76.2 8.2 10.3 5.1 5.3 1205 1205
2060ET-50 60 55.5 4 4 32 37.5 21.9 22.1
1524 1409.7 9.8 11.4 6.6 6.9
2072ET-50 72 67.5 4 4 35 41.2 27 27.8
1828 1714.5 10.7 12.5 8.2 8.4
2024ET-75 24 19.5 1 3 18 NSA 14.7 8.2
610 495.3 5.5 4.5 2.5
2036ET-75 36 31.5 2 3 23 NSA 25.2 26 21.8 13
914 800.1 7.0 7.7 7.9 6.6 3.9
2048ET-75 1940 12119 1104.9 200 76.2 3 4 230 N/A 310.9 30 8.8 15.48 105 105
2060ET-75 60 55.5 4 4 29 NSA 40.6 40 36.1 22.6
1524 1409.7 8.8 12.3 12.1 11 6.8
2072ET-75 72 67.5 4 4 32 NSA 48.5 47 43.2 27.5
1828 1714.5 9.8 14.7 1 14.3 1 13.1 1 8.3
Model Numbers:The"ET"designates Elbow Tall Series Hose.The"50"designates 1h"Outlet Hose Series.The"75"designates 1/4"Outlet Hose Series.
Equivalent Lengths are shown with maximum number of 90'bends at the minimum bend radius per agency.2-45`or 3-30'bends equal 1-90`bend.Different values were obtained by
FM and UL due to the difference in minimum bend radius,testing protocol and calculation methods.Please see individual standards for more information relative to Friction Loss(equivalent
length of pipe).
See listing(s)approval agency for the latest approval details.
FP-8.18
Z /ANVIL
FLEXHEAD Flexible Sprinkler Connections ,�TEa�aT,o L
INSTALLATION INSTRUCTI011IK
MP024BKT2 Multi-Position Open Hub Bracket (MPO)
Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System
Recommend the use of proper PPE for installation. MP024BKT2
is approved for use with the standard FlexHead°Flexible
Sprinkler Hose in accordance to NFPA 13, 13D, & 13R for use
in wet and dry sprinkler system.The Standard Flexible
sprinkler hoses are UL approved for Limited flexibility and O
are intended for direct sprinkler connection. APPROVED
FlexHead® ,..
The MP02413KT2 is pre-assembled at Standard Tall FlexHead"o
center the position. (See below for 2024T,2036T,2048T,2060T, Standard Tall Elbow
additional installation configurations) 2072T,20XXH,20XXHE,20XXI 2024ET,2036ET,2048ET,2060ET,2072ET
T Bar Ceiling Fig.1 Taneuver
PO Bracket Installation
Grid Installation the flexible sprinkler drop from the branch to the
.�.,� MPO bracket. Review that the hose length, number of bends,
The MPO bracket is designed and bend radius are applicable for the installation per NFPA
for use on ceiling grids conforming guidelines. (See corresponding hose submittal for installation
to ASTM C 635". information.)
Locate the center of the The MPO bracket has an open hub for ease of installation.
ceiling tile marking, align the Open the hinge apparatus by turning the locking shaft t/4 turn.
offset screw with that marking for true center of tile installation. Slide the flexible hose drop into the hub. Ensure the drop is
Insert one bracket leg at a time, applying a downward pressure vertical, and the SS Flexible®hose is not applying a substan-
on the bracket leg and T-Bar. Place the second leg on the tial moment on the bracket causing sprinkler misalignment.
T-Bar and repeat process. (Fig. 1) Latch the hinge door closed
and adjust the sprinkler drop
2FlexHead Flexible Fig.2 for desired ceiling height.
Hose Installation Tighten the set screw till hand :*
tight plus 1"turn, (100 in-lbs). _
Apply Teflon®tape or pipe
sealant to the 1" NPT thread. Install desired sprinkler head,
Install into branch outlet.Any per the manufacturer's
direction is acceptable, ensure :k installation instructions.
the hose is allowed at least one
bend per installation to allow for Do not wrench on
seismic movement. (See Friction braided hose
Loss Chart on page 8 for
details.)
Tighten hose using the pipe drop section, never apply a
wrench to the braided hose for installation. (Fig. 2)
Installation Configurations Installation Complete
24"Tile—24/4-Quarter Mark Position
I i
141/2"Wood Stud-Center Position•
U.S and International Patent Pending: #6,123,154,#6,119,784,#6,752,218,#7,032,680,#6,488,097
20XXHE,20XXSF,20XXE&20XXI,20XXET with MP024BKT2 Bracket has not been evaluated by UL.
Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636.
•FM Approved,Installation has not been evaluated by UL.
FP-8.18
FLEXHEAD Flexible Sprinkler Connections
Z ANVIL
ADOXXBKT3 Adjustable Open Hub Bracket (ADO)
Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System
Recommend the use of proper PPE for installation.ADOXX- The ADOXXBKT3 is pre-assembled at FM UL
BKT3 is approved for use with the standard FlexHead°and center tile position. (See below for APPBOVm
SuperFlex'M Flexible Sprinkler Hose in accordance to NFPA 13, additional installation configurations)
13D, & 13R for use in wet and dry sprinkler system.The AD016BKT3&AD024BKT3 UL Listed and FM Approved.
Standard&SuperFlex'M Flexible sprinkler hoses are UL AD030BKT3&AD048BKT3 FM Approved.
approved for limited flexibility and are intended for direct
sprinkler connection.
FlexHead°
y Standard Tall FlexHead°
r Su erFlex'"
2024T,2036T,2048T,2060T, __� Standard Tall Elbow p
2072T,20XXH,20XXHE,20XXI � 2024ET,2036ET,2048ET,2060ET,2072ET 2036SF,2048SF,2072SF
T Bar Ceiling Fig.1 31nstallation
AD0 Bracket Fig.3a
Grid Installation
The ADO bracket is designed for Maneuver the flexible sprinkler
use on ceiling grids conforming to drop from the branch to the ADO
ASTM C 635*. bracket. Review that the hose
Locate the center of the length, number of bends, and
ceiling tile marking, align the bend radius are applicable for
offset screw with that marking for true center of tile installation. the installation per NFPA
Insert one bracket leg at a time, applying a downward pressure guidelines. (See corresponding /
on the bracket leg and T-Bar. Place the second leg on the hose submittal for installation
T-Bar and repeat process. (Fig. 1) information.)
The ADO bracket has an open
2FlexHead Flexible ig.2 hub for ease of installation.
Hose Installation Open the hinge apparatus by y
turning the locking shaft'/a turn. Fig.3b
A. For threaded fitting branch Slide the flexible hose drop into
connection:Apply TeflonR tape or the hub. Ensure the drop is vertical, and the SS Flexible®hose
pipe sealant to the 1" NPT _ is not applying a substantial moment on the bracket causing
thread. Install into branch outlet. sprinkler misalignment. Latch the hinge door closed and adjust
Tigthen the hose using the pipe the sprinkler drop for desired ceiling height.Tighten the set
section, never apply a wrench to Do not wrench on 3
the braided hose when installing. braided hose screw till hand tight plus /a turn,(130 in Ibs).(Fig.3a and 3b)
B. For groove connection follow the grooved coupling manufac- Install desired sprinkler head, per the manufacturer's
turer's installation instructions. installation instructions.
C. For SLT connection follow Gruvlok°installation instructions,
"Fig 7074SLT SlideLOK°Ready for Installation Cap&Fitting Instructions".
The FlexHead connection can be installed in any direction from
the branch. Ensure the hose is allowed at least one bend per
installation to allow for seismic movement. (See fiction Loss
Chart on Page 3 for details)
Installation Configurations Installation Complete
24"Tile—24/4-Quarter Mark Position 14'/2"Wood Stud-Center Position*
U.S and International Patent Pending: #6,123,154,#6,119,784,#6,752,218,#7,032,680,#6,488,097
20XXT,220XXET,20XXH,20XXHE,20XXI,with ADOXXBKT3 Bracket has not been evaluated by UL.
'Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636.
-FM Approved,Installation has not been evaluated by UL.
FP-8.18
FLEXHEAD Flexible Sprinkler Connections
Z ANVIL
MPT24BKT1 Multi-Position Tall Bracket (MPT)
Installation of FlexHead Commercial Ceiling Flexible Sprinkler Drop System
Recommend the use of proper PPE for installation. MPT-24- approved for limited flexibility and are <g> UL
BKT1 is approved for use with the standard FlexHead°and intended for direct sprinkler connection. ApPRM °
SuperFlexTm Flexible Sprinkler Hose in accordance to NFPA The MPT bracket is set for 24"center of tile installation. (See
13, 13D, & 13R for use in wet and dry sprinkler system.The back side for additional installation configurations)
Standard&SuperFlexTm Flexible sprinkler hoses are UL
FlexHead® 0000
FlexHead®
Standard Tall Standard Tall Elbow SuperFlex'"
2024T,2036T,2048T,2060T,2072T 2024ET,2036ET,2048ET,2060ET,2072ET 2036SF,2048SF,2072SF
1 T Bar Ceiling Grid Installation FlexHead Flexible Hose Installation
The MPT bracket is designed for use on ceiling grids 2A. For threaded fitting branch connection:Apply Teflon°
conforming to ASTM C 635`. tape or pipe sealant to the 1" NPT thread. Install into branch
Locate the center of the ceiling tile marking, align the offset outlet.Tigthen the hose using the pipe section, never apply a
screw with that marking for true center of tile installation.Insert wrench to the braided hose when installing.
one bracket leg at a time,applying a downward pressure on the B. For groove connection follow the grooved coupling manufac-
bracket leg and T-Bar. Screw the self tapping screw using a turer's installation instructions.
#2 square head driver. Place the second leg on the T-Bar and C. For SLT connection follow GruvloV installation instructions,
repeat process. (Fig. 1) "Fig 7074SLT SlideLOK®Ready for Installation Cap& Fitting
Instructions".
Fig.1 The FlexHead connection can be installed in any direction from
the branch. Ensure the hose is allowed at least one bend per
installation to allow for seismic movement. (See fiction Loss
�y Chart on Page 3 for details)
Fig.2
Do not wrench on braided hose
'Intended for use on ASTM C 635 intermediate or heavy duty ceilings systems installed in accordance to ASTM C 636.
FP-8.18
FLEXHEAD Flexible Sprinkler Connections
Z ANVIL
3Secure the Flexhead Sprinkler Drop to Ceiling Tile Installation —The flexible sprinkler
MPT Bracket — Maneuver the flexible sprinkler drop 4drop system with MPT Bracket is able to be installed prior
from the branch to the MPT bracket. Review that the hose to the ceiling tile installation, preventing the need for sprinkler
length,number of bends,and bend radius are applicable for the contractor tile adjustment.
installation per NFPA guidelines. (See corresponding hose For ease of tile installation, cut the largest sprinkler hole
submittal for installation information.) recommended by the manufacturer.The largest hole that
The MPT bracket has an open hub for ease of installation. is still covered by the sprinkler escutcheon allows for an easier
Open the hinge apparatus by turning the locking shaft 1/a turn. install.
Slide the flexible hose drop into the hub. Ensure the drop is Angle the tile at 45 degrees and push the tile through the hole
vertical, and the SS Flexible°hose is not applying a substantial and up above the ceiling T-bar, maneuver the tile and allow it
moment on the bracket causing sprinkler misalignment. Latch to drop in the proper location. (Fig.4)
the hinge door close and adjust the sprinkler drop for desired
ceiling height.Tightening the set screw till hand tight plus two
full revolutions, (130 in-lbs). (Fig. 3a and 3b) Fig.4
Install desired sprinkler head, per the manufacturer's installation
instructions.
3a Fig.3b..V�a
Installation Complete
1�
NOW
Installation Configurations
24"Tile—24/4 16"Tile—16/2 16"Metal Stud 141/2"Wood Stud
Quarter Mark Position Center Position Center Position• Center Position•
U.S and International Patent Pending: #6,123,154,#6,119,784,#6,752,218,#7,032,680,#6,488,097
20XXET with MPT-24BKT1 Bracket has not been evaluated by UL.
-FM Approved,Installation has not been evaluated by UL.
FP-8.18
c Z /ANVIL
FLEXHEAD Flexible Sprinkler Connections
FRICTION .
WRadiusof
mber Equivalent Length of 1 in.Schedule 40 Pie(Ft.) Max.Rated
Model Outlet Hose Bends q g p Working Pressure
Orifice Assembly
Number Size Length FM UL FM FM UL
5.6 k-Factor 8.0k-Factor 11.2k-Factar 14.0k-Factar 16.8k-Factar 22.4k-Factar
In./cm. In./mm. ln./mm. Ft./m. Ft./m. I Ft./m. I FUrn. I FUrn. I FUrn. Ft./m. PSI/Kpa PSI/Kpa
InternalSup Flex I I (I.D)Hose Series
2036SF-50 36 5 2 30 16.2 16.9 11.5
914 9.1 4.9 5.1 3.5
2048SF 50 1/248 7 2 8 3 47 28.7 29.3 15.4
1.27 1219 178 50.8 14.3 8.7 8.9 4.7
2072SF-50 72 12 4 71 53.9 54.3 23.2
1828 21.6 16.4 16.5 7
2036SF75 36 5 2 29 _ 21.5 21.6 21.8 22
914 8.8 6.5 6.5 6.6 6.7
2048SF-75 1/4 48 7 2 8 3 44 30.5 30.6 31.1 30.8
1.90 1219 178 50.8 13.4 9.2 9.3 9.4 9.3
2072SF 75 72 12 4 70 _ 48.5 48.8 49.9 48.6
1828 21.3 14.7 14.8 15.2 14.8
Elbow Diameter
2036ESF-50 36 _ 2 _ 25.8 26.1 12.5 _ _
914 7.8 7.9 3.8
2048ESF-50 1.227 1219 178 N/A - 3 _ 3111 3113 15.36 175- - - 1 05 12 5
2072ESF-50 72 _ 4 _ 57.3 56.9 27.8 _ _
1828 17.4 17.3 8.4
2036ESF-75 36 _ 2 _ _ 25.2 26 25.9 25.7
914 7.6 7.9 7.9 7.8
2048ESF 15 1/4 48 7 N A - 3 _ _ 32.9 33 33 33 _ 175 175
1.90 1219 118 / 10 10 10 10 1205 1205
2012ESF 15 72 _ 4 _ _ 48.5 47 47.3 47.6
1828 14.8 14.3 14.4 14.5
Flexhead Standard Tall I"Internal 1 (I.D)Hose Series
2024T-50 24 3 1 11 18.4 7.1 1.6
610 3.4 5.6 2.3 2.3
36 16 26.6 11.5 11.5
2036T 50 914 3 2 4.9 8.1 3.5 3.5 -
2048T-50 1.227 1219 200 76.2 4 3 3 9.23 la 63 15.4 175 4.7 - 1 05 1 05
60 29 35.8 19.1 19.3
2060T 50 1524 4 4 8.8 10.9 5.8 5.8 -
72 35 45.6 23.0 23.2
2072T-50 1828 4 4 10.7 13.9 7
24 12 7.3 5.9 14.7 7.1
2024T 15 610 3 1 3.7 - 2.2 1.8 4.5 2.1
36 18 21.5 10.4 21.8 10.9
2036T-75 914 3 2 5.5 - 6.5 3.1 6.6 3.3
2048T-75 1�4 48 8 3 4 3 23 _ 30.5 14.9 29 14.8 _ 175 175
1.90 1219 200 76.2 7.0 9.3 4.5 8.8 4.5 1205 1205
60 29 39.5 19.4 36.1 18.7
2060T 15 1524 4 4 8.8 - 12 5.9 11 5.6 -
2012T 15 72 4 4 32 _ 48.5 24.0 43.2 22.6
1828 9.8 14.7 7.3 13.1 6.8
Flexhead Standard Tall Elbowi Diameter
2024ET-50 24 3 1 19 26.4 6.8 1.4
610 5.8 8.0 2 2.2
2036ET-50 36 3 2 23 30.1 11.8 12.5
914 7.0 9.1 3.6 3.8
2048ET50 1/248 8 3 4 3 27 33.8 16.9 17.6 175 175
1.27 1219 200 76.2 8.2 10.3 5.1 5.3 1205 1205
2060ET-50 60 4 4 32 37.5 21.9 22.7
1524 9.8 11.4 6.6 6.9
2072ET-50 72 4 4 35 41.2 27.0 27.8
1828 10.7 12.5 8.2 8.4
See Table Notes on Page 8.
FP-6.18
c Z /ANVIL
FLEXHEAD Flexible Sprinkler Connections
FRICTION LOSS DATA & SPECIFICATIONS
Minimum Max.Number Equivalent Length of 1 in.Schedule 40 Pie(Ft.) Max.Rated
Model Outlet Hose Bend Radius of 90°Bends q g p Working Pressure
Orifice Assembly
Number Size Length FM UL UL FM UL FM FM UL
5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor 22.4 k-Factor
In./cm. In./mm. In./mm.ln./mm.ln./mm.ln./mm. FUrn. FUrn. Ft./m. FUrn. FUrn. FUrn. Ft./m. PSI/Kpa PSI/Kpa
24 18 8.8 8.7 14.7 8.2
2024ET75 610 3 1 5.5 - 2.6 2.6 4.5 2.5
2036ET-75 36 3 2 23 _ 25.5 14.2 21.8 13
914 7.0 7.7 4.2 6.6 3.9
2048ET-75 3�4 48 8 3 4 3 23 _ 32.9 18.4 29 17.8 _ 175 175
1.90 1219 200 76.2 7.0 10 5.6 8.8 5.4 1205 1205
2060ET-75 60 4 4 29 _ 40.6 22.7 36.1 22.6
1524 8.8 12.3 6.9 11.0 6.8
2072ET-75 72 4 4 32 _ 48.5 27.0 43.2 27.5
1828 9.8 14.7 8.2 13.1 8.3
Flexhead 1 (I.D)Hose Series
2024H-50 24 3 2 11 18.4 7.7 7.6
610 3.4 5.6 2.3 2.3
36 16 26.6 11.5 11.5
2036H 50 914 3 3 4.9 8.1 3.5 3.5 -
2048H-50 1.27 1289 200 76.2 4 4 3 9.23 14 63 14 7 - 20 8 20 8
206OH-50 60 4 4 29 35.8 19.1 19.3 -
1524 8.8 10.9 5.8 5.8
2072H-50 72 4 4 35 45.6 23.0 23.2
1828 10.7 13.9 7 7
24 12 14.7 6.8 14.7 7.1
2024H 15 610 3 2 3.7 - 4.5 2.0 4.5 2.1
36 18 21.5 11.4 21.8 10.9
2036H-75 914 3 3 5.5 - 6.5 3.4 6.6 3.3
2048H-75 1.90 12189 200 76.2 4 4 j p _ 3.25 16.0 $8 14.58 300- 2068 20 8
60 29 39.5 20.6 36.1 18.7
206OH-75 1524 4 4 8.8 - 12 6.2 11.0 5.7 -
2072H-75 72 4 4 32 _ 48.5 25.3 43.2 22.6
1828 9.8 14.7 7.7 13.1 6.8
a Elbow I D)Hose Series
24 19 14.7 6.8 1.4
2024HE 50 610 3 2 5.8 4.5 2 2.2 -
2036HE-50 36 3 3 23 21.8 11.8 12.5
914 7.0 6.6 3.6 3.8
2048HE 50 1/248 8 3 4 4 27 29.0 16.9 17.6 300 300
1.27 1219 200 76.2 8.2 8.8 5.1 5.3 2068 2068
2060HE-50 60 4 4 32 36.1 21.9 22.7
1524 9.8 11 6.6 6.9
2072HE-50 72 4 4 35 43.2 27.0 27.8
1828 10.7 13.1 8.2 8.4
2024HE-75 24 3 2 18 _ 14.7 - 14.7 8.2
610 5.5 4.5 4.5 2.5
2036HE-75 36 3 3 23 _ 25.2 26 21.8 13
914 7.0 7.7 7.9 6.6 3.9
2048HE-75 1/4 48 8 3 4 4 23 _ 32.9 33 29 17.8 _ 300 300
1.90 1219 200 76.2 7.0 10 10 8.8 5.4 2068 2068
2060HE-75 60 4 4 29 _ 40.5 40 36.1 22.6
1524 8.8 12.3 12.2 11.0 6.8
2072HE-75 72 4 4 32 48.5 47 43.2 27.5
1828 9.8 14.8 14.3 13.1 8.3
adI Diameter1
2024-DPS 24 _ 1 _ 18.4 7.7 7.6 _ 7.1 10.1
610 5.6 2.3 2.3 2.1 3.3
36 26.6 11.5 11.5 10.9 15.1
2036 DPS 914 - 2 - 8.1 3.5 3.5 - 3.3 4.6
2048 DPS 1 48 7 3 _ 30.3 15.3 15.4 _ 14.8 21.5 _ 175
2.54 1219 180 - 9.2 4.7 4.1 4.5 6.5 1205
2060-DPS 60 4 - 35.8 19.1 19.3 _ 18.7 25.3
1524 10.9 5.8 5.9 5.7 1.7
2012 DPS 72 _ 4 _ 45.6 23 23.2 _ 22.6 26.9
rl828 13.9 7 7 6.9 8.1
See Table Notes on Page 8.
FP-6.18
c Z /ANVIL
FLEXHEAD Flexible Sprinkler Connections
FRICTION LOSS DATA & SPECIFICATIONS
[Bend
nimum Max.NjBends
Equivalent Length of 1 in.Schedule 40 Pie(Ft.) Max.Rated
Model Outlet :Hose Radius of 90° q g p Working Pressure
Orifice Number Size UL UL FM FM UL
5.6 k-Factor 8.0 k-Factor 11.2 k-Factor 14.0 k-Factor 16.8 k-Factor 22.4 k-FactorIn./cm. m.ln./mm.ln./mm. FtJrn. I Ft./m. I Ft./m. I FtJrn. I FtJrn. I FUrn. PSI/Kpa PSI/Kpa
Flexhead Diameter RD)
20241 24 3 1 11 18.4
610 1 3.4 5.6
20361 36 3 3 16 26.6
914 4.9 8.1
20481 1/248 8 3 4 4 24 30.3 _ 175 175
1.27 1219 200 76.2 7.3 9.2 1205 1205
20601 60 4 4 29 35.8
1524 8.8 10.9
20721 72 4 4 35 45.6
1828 10.7 13.9
20241 24 3 1 12 - - - 11.6 - -
610 3.7 3.5
36 18 16
20361 914 3 2 5.5 - - - 4.9 -
20481 1/4 48 8 3 4 3 23 _ _ _ 17.9 _ _ 175 175
1.90 1219 200 76.2 7.0 5.4 1205 1205
20601 60 4 4 29 _ _ _ 24.7 _
1524 8.8 1.5
20121 M4 4 _ _ _ 28.9 9.8 8.8
Flexhead Institutional for use with Amerlux Ceilin System-I"Internal Diameter(I.D)Hose Series
20241A 24 - 1 11 _ 18.4
610 3.4 5.6
20361A 36 - 2 16 - 26.6 - - - -
914 4.9 8.1
20481A 1175
1/2 1289 200 - - 3 4 823 - 30.3 - - - - 175 1205
60 29 35.8
20601A 1524 - 4 8.8 - 10.9 - - - -
20721A 72 _ 4 35 _ 45.6
1828 10.7 13.9
NOTES:
Model Numbers:
• "SF"designates SuperFlex7'Hose series.
• "ESF"designates SuperFlex"Elbow Hose series.
• "E"designates elbow drop hose series
• "T"designates straight tall style hose
• "ET"designates elbow tall style hose series.
• "H"designates high pressure 300psi working pressure hose series.
• "HE"designates high pressure 300psi elbow hose series.
• "DPS"designates dry pendant system.
• "DT"designates drain tee hose series used in dry pendent/freezer application.
• "DPS"and"DT"models are approved for use in cold storage application(Freezer,Cold Chamber)and combine an approved flexible sprinkler hose and an approved dry
pendent sprinkler.UHO-1 or UHO-3 is required to connect the flexible sprinkler hose to the dry sprinkler.
• "I"indicates instiutional flexible hose.
• "A"indicates models for use with Amerlux Ceiling System.
• "50"designates '/2"Outlet Hose series.The"75"designates 1/4"Outlet Hose series.Inlet size 1".
• Max Ambient Temperature Rating on all model numbers are 300`F(148`C).
• Equivalent lengths are shown with maximum number of 90`bends at the minimum bend radius per agency.2-45°or 3-30°bend equal 1-90°bend.Different values were obtained
by FM and UL due to the difference in minimum bend radius,testing protocol and calculation methods.Please see individual standards for more information relative to Friction Loss
(equivalent length of pipe).
• All hoses require a minimum of one bend for installation.Bend radius tool available for 3"bend"T"hose,"SF"hose does not require bend radius tool.
• FM equivalent length calculation includes Sprinkler Head Friction Loss.
• See listing(s)approval agency for the latest approval details.
FP-6.18
HANGER LEGEND
A I"U" HOOK
B COACH SCREW ROD
D BM. CLAMP W "STRAP
E EYELET
F HDIP
G CEILING FLANGE
H SIDE BEAM BRACKET
K SHORT CLIP
M ALL THREAD ROD
N TOGGLE NUT
P POWDER DRIVEN STUD
R EXPANSION BOLT
S PIPE SPIKE
T
U
V
W
X
Y
Z
STATE CERTIFICATION SPRINKLER LEGEND
SPRINKLER
rc ORIFICE SIZES o w N
r AND TYPE W
216—0 I 2 - 8 16 ] SPRAY O
54-0 54-O I B t9-031E-0 n Le el3 I T 32 SPRAY O :3/•
PaRIa He PrDLaIXI G.Ga. ,
PATRI IF11 3 1 1 4 `� 1/2
1-3-24 1 2 8 I6 2 SIDEWALL ® ,
------ - DRY TYPE
2-WAY EARTHQUAKE BRACE TEMP RATING O J =o
O r 4-WAY EARTHQUAKE BRACE O 1GS' ut 30 n= so
9_0• F I F I 9_0• OF ICE • 9'-0" ERVER F I �n $ zlz° �01/2.0 +•
4 4 4 4 109 9'-0-0" 7 /o LINE C U E PIPED IN INCHES
2B6 ® /2.
1-
=CI - III ryI o' ryl 11 t'I FITTING LEGEND gag
3 P PIPE-O-LET
b I 2- �� 31 �I PLAIN END FIT FITTING APPROVAL REQUIRED
I 101 I b 1 ,Kb 11 102, �b �I I SN GROOVED SHAPED NIPPLE CITY OF ARLINGTON
I • 1_ , _ I TSN THREADED SHAPED NIPPLE
I \ \ • ,1Jillb • I SPRINKLER HEADS USED
SYM MANUF MODEL TYPE THREAD SIZE
READ FSCUTCII TEMP OTT
I �— - 1 I SIZE SIZE FIRISH MEN
q 0 6
6 • Fd11AB�E CS 56 OR CONCEVED W KS.6 BI'l WITE HU 19
107� `�I ■ RBIABIE P15 ESFR PENDENT 1° K=75 BRpfh N/A 166 14
4-0
RR
� 4-0
1-0 1
I db O EN FFI BEAK 1 I
B ,Vz 11& 11 1 V2 a 1+h P b , {i}
0- "In 0-6
.„ 1 CMIN. 4-00. 9o'-a
3_ I
1 I b I 0-11 SHOWER R,i 1 I
I I 1 1 5 p I
I rora 33
O O O L7 9 O
�y f SHOWER I QUALITY CONTROL BY DATE
1V2 1V2 \� 1 108 APPROVED FOR FABRICATION BY DATE
�0-6\ O G I
I I I I
GENERAL NOTES
GENERAL NOTES
1. Au MATERIAL AND EQUIPMENT To s xEw A uL usrzD OF ON ASPRovsD.
I I I I 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISERS AND DIMENSIONS
1. DENOTES EXISTING FIRE SPRINKLER PIPING. HSLY(I-a)wHCH ARE
1 2. DENOTES NEW FIRE SPRINKLER PIPING. 3. ENRTHO EBRACING SHNL BE PROWDED INNAC DANCE WITH
3. DENOTES EXISTING FIRE SPRINKLER PENDENT TO REMAIN. PIPA PAMPHLET NO.13.2016 EDITION.
4. n DENOTES EXISTING FIRE SPRINKLER TO RELOCATE. 4. NPE HRHGERS AND METNDD OF HANGING To BE IN ACCORDANCE WIN
FIRE SPRINKLER PLAN PIPPF SNALL IP";CCOP�WnINNFRA PAMPHLET NO.I NQN
N ADO ED
SCALE:lA°=,'-0' " G. AwIiI x"7wPx"Iir`xoxc:inie`EanoxLxD,suu BE IN AccaRonNCE
7. OWNER TO PROVIDE AOEDLMTE HEAT IN AREAS PROTECTED BY A WET PIPE SPRINKLER
EYSIERR TO PREVENT'WATER IN PIPES FROM FREEZING.
SCOPE O F WORK B. AIL WIRING OF EIEGNAGA1 DEVICES(IF REOUIREN TO BE PRO DOG
BY OTHERS
D. PAINNNG OF PIPE A EQUIPMENT(IF REQUIRED)TO BE PROVIDED
orHERS
MODIFY EXISTING FIRE SPRINKLER SYSTEM FOR T.I.WALLS&CEILINGS. 10.FURRING OF PIPE B EQUIPMENT(IF REWIRED)To WE PROVIDED
BY OTHERS
DESIGN CRITERIA
1. DESIGN PER NFPA 13 (2016 EDITION).
SmokeY F.7i -P
Area ND-tN_ 11
Smok Dint PIPE NOTES
1. ALL THREADED PIPE TO BE SCH. 40 BLK.
'C REVISIONS
Arlinglon -
Municipal NO DATE By DESCRIPTION
y Airport)AWO
GI
A Ee Il oneS vVly/Mary Ply "
n SVUe
QCONTRACT PIVOTAL
8201 164TH AVE HE SUITE 110
Q:�.alnan sUGe_en1eR REDMOND,WA 98052
/ NEW Ol1RET
�� PER PUW �mprr H`Ii` µ
METAL DECK) �SAMMYS'XPRESS HANGER Cro whQlesaleQ
MODEL NUMBER XP20 ANCHOR 1 PROJECT NAME:
�4'B°ALL THREAD ROD
ttPCW/MOUNTING BRACKET TENANT 48
"RAa*rwmeTo Ra 17310 51ST AVE HE
® ARLINGTON, WA 98223
_—PIPE RING �H GRQ
o1NTa Ie
l PATRIFP099CF
.,.._.......... ... PATRIOT WWW.PATRIOTFIRE.COM
f CEILING TILE —SPRINKLER HEAD � trovis.mackey®patr otFre com
FIRE PROTECTION,INC.
2707 70TH AVENUE EAST TEL (253)926-2290
TYP. HANGER DETAIL TYP.FLEXHEAD DETAIL VICINITY MAP TACOMA, WA 98424 FAX:(253)922-6150
SCALE:NONE SCAIE:NONE " DESIGNER TRAVIS MACKEY SHEET
DATE 1/3/24 F P 1
JOB NO. 12-23547 OF
3ZI5
¢ 0 0 331 = - n -
r r 7 Z 1NNN3dO•n.M0V•♦109WA5�®�e p �� v NG
W p0� Y r W w a C o I W�
w 1HOltldfl Olt-OJ 017 ®ONIN3d \ \ O i m N
W (� W p J w NM00 ONY d!I n
J 3 3 Z m >m rc Stl3l-HS d ti
QQ aorz a a �J dry a
d'YUQ� 4:2¢z j3z W w m N J¢ �c EE W3 E ..
Oy gr U' mU 2 W W NN Y iw� -n >O O W i B 4 IS
=x Uw Z r rw z - n• `n o o r cw � N . n $$_ Q _
Q. < Wa.7 wp (073aw Z '6"E. a e m
coimw=cWiinvxiaof
�awa ml" NIM Mlm -In a " _ _ r w� N�
SOtlHl ,�{,,�{, ¢ N �N S p
¢m o w I�U' x Y z a m f/I r»3 x r N N Ilds -" "< -^ w �'Fi'YIY a z e W 5 � o z N o
a ¢ VI r 2 zm € 9C n o W
OZ } a• �����r i o W m 3 y$ E W U' N am >
w 2' w E s �€ fa g� _ n ao u>i zm a W
p Y C7 W ` e S �`-. w < Y n
z _ - z m ffW „ £ � �E W _ a p¢ a ivNi 00 > spa" i n 4
i d3$ w a w wm �$_ �= z °° �F a3 _: >p
a vl �! �r En` 4 se o `°' r br a H I
lL' i C '.+.� I W w o - E 8 $ I,�, ¢ N Z
W Y € d > > c� a o _ mm o = �5 3• G r -J x3 Z Np x;
_ �5 '" 4� 4� 46 z x Fa-1pz Q oo
Q v --� ..I ' �` z33 J 3 oc Z MJ y�2/. oc�i i G W I\K ,, n¢ i
I y : sr o w •s as a6 o-mrc H �¢ o
w a a Q o
11
i
z 211
, ,
9 � �
�z ova
�aww
zwz
w aifA
N Y Y O
k ,
N N N
w ~
zzzz n
oo�� 0 a ..
U
Z w U
00 z 34
0 0 Di
LU
3
I
WZ
oo
' z
• r
�o°
LLI
Q _
. _ �
-C M'Id w
Yid
LLJ
W
—�
l I
Z OIIn b d O
/ Y
`
o w o
LLI
As
LU
p
z
a
a
C9
•, ' Flo a
o
0
'Li
- I - -- ------ _ ---,--
0
Permit#: 5756
Permit Date: 01/03/24
Permit Type: FIRE SPRINKLER
Project Name: Tenant 48
Applicant Name: Travis Mackey
Applicant Address: 2707, 70th ave e
Applicant, City, State,
tacoma
Zip:
Contact: Travis Mackey
Phone: 2533618603
Email: travis.Mackey@patriotfire.com
Scope of Work: Modify existing sprinkler system to protect tenant improvements to walls and
ceiling
Valuation: 19062.00
Square Feet: 2006
Number of Stories: 1
Construction Type: IA
Occupancy Group: B; Business
ID Code: CIC
Permit Issued: 02/02/2024
Permit Expires: 08/27/2024
Form Permit Type: FIRE SPRINKLER
Status: COMPLETE
Assigned To: Hannah Hardwick
Property
Parcel# Address Legal Description Owner Name Owner Phone Zoning
SMARTCAP
31052100400100 17216 51 STAVE NE STE ARLINGTON 090 MASTER
110 AIRPORT ADDRESS
INDUSTRIAL PA
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
PATRIOT FIRE Megan O'Brien 253 284 3522 2707 70th Ave E CONSTRUCTION COA 601 269 686
PROTECTION CONTRACTOR
PATRIOT FIRE CONSTRUCTION Construction
PROTECTION Megan O'Brien 253 284 3522 2707 70th Ave E CONTRACTOR Contractor PATRIFP099CF
Inspections
Date Inspection Type Description Scheduled Date Completed Date Inspector Status
09/05/2024 FS07.FIRE fire final 09/06/2024 09/06/2024 BUILDING Approved
SPRINKLER FINAL
Sprinkler tech to meet you
onsite Salvador G 253-883-
07/25/2024 FS07.FIRE 1720.Prefer a 12:00 pm 07/26/2024 07/26/2024 BUILDING Not
SPRINKLER FINAL inspection time.Please Completed
contact Salvador to confirm
time.Thank you
-Fire Sprinkler Cover
Inspection
02/28/2024 Inspection -Afternoon Requested 03/01/2024 03/01/2024 BUILDING Approved
-Sprinkler Tech onsite will
be Shawn 253-325-1603
Plan Reviews
Date Review Type Description Assigned To Review Status
01/04/2024 FIRE SPRINKLER BUILDING Approved
01/04/2024 FIRE SPRINKLER PW-WAT-REV No Comment
Received
Fees
Fee Description Notes Amount
Enter 1 if permit is for:fire alarm,or fire
Web Only-Fire System Plan Review sprinkler $200.00
Fire System Plan Review Table 4-2 299.88-200(previously $99.88
charged)=99.88
Credit Card Service $6.00
Credit Card Service $3.00
Fire Sprinkler System Commercial NFPA 13/13R $600.00
Processing/Technology $25.00
Credit Card Service $18.75
Total $952.63
Attached Letters
Date Letter Description
02/01/2024 Building Permit
01/03/2024 Web Form-Building Application
Payments
Date Paid By Description Payment Type Accepted By Amount
01/03/2024 XBP Con£ $200.00
162275471
01/03/2024 Permit Card 162275471 Hannah Hardwick $6.00
01/04/2024 XBP Con£ $99.88
162335243
01/04/2024 Permit Card 162335243 $3.00
02/01/2024 XBP Conf: $625.00
164637958
02/01/2024 Permit Card 164637958 $18.75
Outstanding Balance $0.00
Notes
Date Note Created By:
08/05/2024 Send final expiration notice. Kristin Foster
07/22/2024 sent expiration Notice Hannah Hardwick
06/21/2024 sent expiration notice Hannah Hardwick
02/01/2024 sent permit for signature via iworqs Hannah Hardwick
01/04/2024 sent additional plan review fees to be paid Hannah Hardwick
Uploaded Files
Date File Name
02/02/2024 18407744-2024 BLD5756 IssuedPermit.pdf
01/12/2024 18186695-20240112 BLD5756 Approved Plans.pdf
01/03/2024 4d8a9a48899ed234220264690be4774b tenant 48 application.pdf
01/03/2024 5bl63b33bb8b97e35cl47f097a482fa7 equip sub.pdf