HomeMy WebLinkAbout17501 59TH AVE NE_982950_2026 INSPECTION REPORT---
41.
Permit No. 1V"Zg5CLot#
Address �l 52 PY,
Contractor
Owneri���=/iJ�,�9L`
•
Date
Taken By
APPROVAL ❑ PARTIAL APPROVAL
❑ VI TION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INSPECTION - 24 hour notice required.
Inspector Date
PE OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove ❑ Rough-in Plumb. inal
❑ Masonry ❑ Drainage ❑ Insu ation
❑ Other
INSPECTION REPORT
Permit No.0 0 Lot #
• Address 75V r7t-
r �
Contractor ( �0,01'Lijif: 9� j
Owner -7;1� -7�v��
Date / ,-2-4'L
❑ APPROVAL Cl PARTIAL APPROVAL
❑ VIOLATION "CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
CALL 435-0724 FOR RE-INSPECTION - 24 hour notice requir
cJ� Lffi�S �1 S
Inspector Date
TYPE OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ $truct. Slab
❑ Wood Stove ❑ Rough-in final
❑ Masonry ❑ Drainage ❑ Insulation
❑ Other
INSPECTION REPORT
Permit No.q'g Lot#
• Address i'7 t) i S-9 c/- l r
Contractor
Owner
Date
,U-KPPROVAL ❑ PARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INSPECTION - 24 hour notice required.
l9�fr�
Insp _ Date -
u
TYPE OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
—ies! — ❑ Grid ❑ Struct. Slab
❑ Wood Stove ❑ Rough-in ❑ Final
❑ Masonry ❑ Drainage ❑ Insulation
❑ Other
L
INSPECTION REPORT
Permit No. — Lot #
Address 1 SD /
Contractor
• Owner p
Date ��� —9
APPROVAL PARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INSPECTION - 24 hour notice required.
Ins ctor Date
TYPE O INSPECTION REQUESTED
❑ Under-floor ,framing ❑ Gas Piping
❑ Footing Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove ❑ Rough-in ❑ Final
❑ Masonry ❑ Drainage ❑ Insulation
❑ Other
orm
INSPECTION REPORT
Permit No. 9Y,_,-P 9.j o Lot #
Address /�,a�% I Sy tk -,-�
Contractor
Owner
Date J-/.x -
APPROVAL ❑ PARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INSPECTION - 24 hour notice required.
In r Date
TY4 OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove ❑ Rough-in ❑ Final
❑ Masonry ❑ Drainage Insulation
❑ Other
L
INSPECTION REPORT
Permit No. 945 o Lot #
Address
Contractor
• Owner
Date - l 1 9
VAL ❑ PARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INS ECTION - 24 hour notice required.
Inspector Date
TYPE OF INSPECTION REQUESTED
❑ Under-floor Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove '*—Rough-in ❑ Final
❑ Masonry ❑ Drainage ❑ Insulation
❑ Other L
INSPECTION REPORT
Permit No. ' " Lot#
• Address
ContractorOwner
Date
Date 7-/ �'- 9 k
Taken By �.
APPROVAL ❑ PARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INSPECTION - 24 hour notice required.
DateN*W -
OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing Cl Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove5ZRough-in Plumb. ❑ Final
❑ Masonry ❑ Drainage ❑ Insulation
❑ Other
INSPECTION REPORT
Permit No. _ Lot#
Address j-7&C, y 774-
Contractor "._az
T
Owner
Date G ��
Taken By
APPROVAL ❑ PARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ CALL 435-0724 FOR RE-INSPECTION - 24 hour notice required.
101
In c ors - Date
TYPE OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove ❑ Rough-in Plumb. ❑ Final
D Masonry ❑ Drainage ❑ Insulation
Other
^n INSPECTION REPORT
(�` CagZ Lot#Permit No.
Address 1°7c / f
Contractor ( n MYLO_4Y1,Y
Owner
17
Date
— �
Taken By
❑ APPROVAL WPARTIAL APPROVAL
❑ VIOLATION ❑ CORRECTION REQUESTED
❑ Corrections listed below MUST BE MADE before work can be approved.
❑ Please contact inspector.
❑ Was not able to perform inspection.
❑ C L 435-0724 FOR RE-INSPECTION - 24 hour notice required.
Inspector Date L/ -.:7 - 9�
TY OF INSPECTION REQUESTED
❑ Under-floor ❑ Framing ❑ Gas Piping
❑ Footing ❑ Drywall, Nailing ❑ Consultation
❑ Foundation ❑ Shear Nailing ❑ Groundwork
❑ Mechanical ❑ Grid ❑ Struct. Slab
❑ Wood Stove ❑ Rough-in Plumb. ❑ Final
J Masonry ❑ Drainage ❑ Insulation
Other
L
1
CITY OF ARLINGTON /
CONSTRUCTION PERMIT
PERM I T NO- c 9 8—a9 5!i0
Owner: CEMENT DISTRIBUTORS INC. 813 OLIVIA PARK ROAD ARLINGTON 98223
Value of Work: $164, 000.00 Tax ID: 223105-4-017-0005 1=,hone: 425 31;5-0592
Describe Work: MNEW CONSTRUCTION
Proposed Use: REPAIR GARAGE
Legal Description:
Job Address: 17501 59TH AVE
Contractors Name Type Address License#
BLUE RIBBON STEEL BUILDINGS G 47 ALDER LN BLUERSB101LL
P E R M I T F E E 5
Equipment and Fixtures Number Fee Total Charge
BOILER OVER 100,000 1 $24.25 $24.25
SUBTOTAL.... .. $24.25
TOTALS Fee
Site Civil Fee $3,699. 40
Equipment $24.25
Mech Permit $22.00
Permit Fee $1,089.00
Plan Fee $707.8 5
Park Mitigation $9,487.37
Plumb Permit $90.00
State fee $4.50
Street Improvements. . . . . . . . $33,257.00 jk-
Traffic Mitigation $9,881.80
SIGNATURE:
TOTAL FEE. . .. ........ ..... $58,263. 17 I HEREBY CERTIFY THAT I HAVE READ
AND EXAMINED THIS APPLICATION AND
PAYMENTS. ..... ... .... ..... $405.93 KNO THE SAME TO BE TRUE AND COR-
REC LL PROVISIONS OF LAWS AND
TOTAL DUE.... ........ . .... 157,857.24 ORD N NC ES GOVERN NG To
IS TYPE OF
WOR ILL COMP IED ITH WHETHER
S G FIED R R N T.
E -GEIPT # �`q 3
Qr q 3 rl AU-TLb-Ihb '001FICRT
/cY
-} ,��� �
� ��
i _
.. u - ! - �
t - - - - - - - - _ _
.i�
I
�F� .<.ry.
1 � ��
t.
ti `_ maMrtmcl.m,�+m.mmte -,ori n,mr4*magV.mAmm, �,.
CD R:
M m
(D
En
O z
O n LPL
o z O
m Q rD • (�
c H "'
Z ,,;.�•
n zCD
r� O ;>>,
r i n r 'rS til O n ►� �" k
t r O z .� .
rt Ito m z o r, tw d
R o [ Cl
Q. O z
r
p Z d z �- z
[
rD
�C
ti fit' o o rz
�•
r ao �° O rrTl
f
tCr7 � n
> Cn (D � n
M t
M
z
z n O O
. K
{. 1\ :;.... .,,,,..w4•%/ Yq1[0®WJYwNY.l+f41Gti0GtifOiLUYD?Ill(H400uG:i➢OAWWWID+S�+1i�vdi0KG4 -..VIftlW.':9WomMSSm4uIWi. S�GdAO)YOYIfAYAO.ul�ull�D)x �-ab uwndX,uw,:.wsoo. azaw�saYuxavnsam[w.w�.:ux�uvA:- f f� ;E
(�:� �"���....� Y/ �59�,. �ftpymam••�_n, \,�'t"'�:-...^nimrc•y0.•nm",,::r� ���'e't"`i �\�a.: \�t S 1
y
�,
, I ��I I, t •1 V
aL µ ••
� r
l
•ram.._: � •• e ��'
�r SAD
�a
I
1 ` •v��Od�i9�v ^� ' tC��r � ������ I� �S��ti-11 r\ I \
_ 'flr
ENGrN SL j
eejW V EYING
A%'NGr � INiz '
102 a pivision• �N' WA Surveyors
(360)435-5551/.O Box 326 98223
FAx(360)4(36652-5-g012 �572 Engineers
Planners
COST F-STIMATE
CEAIE1Vr )IS
TRIBUT
r_1_iY sryv�lt
oRs, 1Nc.
884 r.�. r)r
r�rA�
3
NpLCS A T$20()(A)•pp-3/L.F.
AC P1 $ 27,619,00
�7_�lZ
$ 6,000.00
OF
6 CATL V )-1.r. A r S 151r.•1-
31.1YDRANTS ATE 5 SEA.A.A
$ 16.500.00
U_pkR;q $ 11500,00
$ 4,500.00
12"Co
2 -RE7OI[/{� CR�:TE Plpr
Nr1O ' i aW.50.�j.
h7"C1tS q�- �
UMP.S1;AQ `� 1,500.00
LACING $ 1 0.000.00
$ 5,000.00
CRUSH&D-25(g
FA VEMEN7'-240 j S 13/yD.
Of"ASP11A j $ 32 500.00
�O F' L JR $- F00.00
RL'yIE W- $114,719.00
Cz_ %) $ 2,867.98
RECEIVED
goc) MAY 2 8 1998
C"y OFARU IG
TON
C
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
ARLINGTON,WA engineers
r
102 E Division•PO Box 326 98223
(360)435-5551 •(360)652-7572 - Planners
FAX(360)435-4012
COST ESTIMATE
FOR
IMPROVEMENTS ALONG 59TH AVE. N.E.
FOR
CEMENT DISTRIBUTORS, INC.
547 L.F. OF CURB AT $7/L.F. $ 3,829.00
547 L.F. OF 5' W]DE SIDEWALK AT $7/L.F. 3,829.00
6" CRUSHED R.00K BASE AT $22/C.Y. 2,451.00
4" A.T.B. AT $40/TON 6,030,00
3" CLA")5 "B" ASPHALT AT $40/'I'ON 4,568.00
4 '.I'YP1" [ .CATCII BASINS AT $700/EAC:H 2,800.00
300 L.F. OF INF'ILTRA'Ti0N T'IZENCH AT' $25/1,.F. 7,500.00
150 L.F. (:F 8" P.V.C. AT $15/1-F• 2,250.00
$33,257.00 T�''0 '7
RECEIVED
MAY 2 8 1998 Nk�
�Y=i]
R
CITY OF ARLINGTON V I c
0
0
II
.LT'825
m
a
0
F
CQ
EU A
a
m
Q
z
m Fa
h �
b U.
,YY
I
K i l i I B
Rc
- _ _
i
0
0
II
v2
.LT'82S
m
a
0
H
m
t7 %0
a
m
H �
b
n
pa
� R
lei
8S'9bS
i
I
PROJECT ENVIRONMENTAL MITIGATION AGREEMENT OIL
Cement Distributors
4/27/98
SEPA #262
This agreement is entered into by and between the City of Arlington, a municipal corporation,
hereinafter referred to as the "City", and Cement Distributors hereinafter referred to as the
"Developer"
WHEREAS, this agreement is executed pursuant to Chapter 43.21 RCW, the State
Environmental Policy Act (SEPA), and Chapter VII of Arlington's Unified Development Code, to
provide for mitigation of existing and known environmental impacts associated with the development
hereinafter described. This agreement is a voluntary agreement entered into pursuant to the statutes of
the State of Washington. This agreement does not preclude any evaluation and determination by the
City upon later actions or proposals undertaken by the Developer which may require a determination of
significance and environmental review under SEPA and
WHEREAS, the Developer is proposing to construct a 78' x 96' (7,488 sq. ft.) shop and 2,492
sq. ft. office. The Developer is re-locating their current operation from Everett, WA to the Arlington
site, and
WHEREAS, the Responsible Official has made findings that the proposed development will
result in the following probable significant adverse impacts to the environment;
1. Storm water run-off resulting from impervious surfaces and related potential
contamination of ground water from automobile.
2. Traffic impacts of an estimated rate of 80 ADT per day for the new business.
3. Need for provision of water and sewer utilities, to and through the site, to serve this
project and those which may occur.
4. Need provisions of additional fire protection ability in conjunction with construction
and occupancy of Project.
NOW, THEREFORE, the City and the Developer agree that the following mitigation measures
shall be employed by the Developer to ensure that probable significant adverse environmental impacts
created by the proposed project are minimized or eliminated:
Transportation
1. Full frontage lot improvements along 59th Ave. NE shall include, but not limited to,
curb, gutter, sidewalk, right turn lane for north bound traffic and storm drainage.
2. The Developer shall dedicate right-of-way along 59th Ave NE to the City of Arlington
at 30' from center line of road. All dedications shall be completed prior to the issuance
of a building permit.
mitagre.doc
Page 1 of 3
Q
3. All street construction shall meet the standard City street requirements per the City of
Arlington Public Works Construction Standards and Specification Manual.
4. All areas frequent to street traffic shall be paved and meet the standard street
requirements of the City.
5. The Developer shall pay traffic mitigation fees, prior to the issuance of building permit
for the impacts to 172 St. NE (SR 531) at the following rates:
Transportation Mitigation Requirements
Project Total ADT Mitigation Per Total Mitigation
Trips $ Require $
Signalize SR 531 20 $19.12 $382.40
/67th Ave NE
I-5/SR 531 Interchange 60 $85.79 $5,147.40
Improvements
Widening SR 531 80 $54.40 $4,352.00
43rd Ave to 67th Ave
TOTAL 160 $159.31 $9,881.80
Utilities
1. Sanitary Sewer and Water lines shall be extended to the site by the applicant at their
expense. Applicant shall submit construction drawings, drawn to City standards, for
review and approval prior to construction. The applicant shall pay the required
connection fees prior to the installation of the services.
2. Additional fire protection maybe required by the Arlington Fire Department. The City
of Arlington will inform the applicant of their responsibility during the construction
review process. Fire protection systems shall meet adequate flow standards as required
by the Fire Chief and Director of Public Works.
Recreational
1. The Developer shall pay a parks mitigation fee of$0.05 per gross sq. ft. of total land
area of land being developed for a total of $9,487.37. This shall be paid at the
issuance of the building permit.
General
1. All construction drawings shall be submitted to the Department of Planning and
Community Development. The Department of Public Works will review and approve
prior to issuance of building permit. This includes all on and off-site public facilities
constructed as part of this process.
2. Construction shall be limited to the hours between 7:00 a.m. and 7:00 p.m.
mitagre.doc
Page 2 of 3
3. Approval of the building permit is subject to submittal of an engineered Storm
Drainage Plan and Temporary Erosion and Sediment Control Plan (TESCP) for review
and approval by the Building Department, prior to any site construction. These plans
shall be designed to the Puget Sound Water Quality Manual and AMC 16.10. The
Applicant will be responsible for the cost of outside consultant review for the Storm
Drainage Plan.
4. Adequate measures shall be taken to mitigate noise and visual impacts on the
surrounding parcels. A landscaping plan shall be submitted to the Department of
Planning and Community Development for review and approval.
5. All development on this property shall conform to the requirements of the A.A
Investments Short Plat Auditor's File No. 9608015001 and any other conditions tied to
this plat from previous agreements.
mitagre.doc
Page 3 of 3
I
Developer/Owner
State of Washington)
) ss
County of Snohomish)
On this day personally appeared before me to me known to be the individual
described in and who executed the within and foregoing instrument, and acknowledged that signed
the same as free and voluntary act and deed for the uses and purposes therein mentioned.
Given under my hand and official seal this day of .1998.
NOTARY PUBLIC in and for the State of Washington
residing at
My appointment expires
City of Arlington
State of Washington)
) ss
County of Snohomish)
On this day personally appeared before me to me known to be-the individual
described in and who executed the within and foregoing instrument, and acknowledged that signed
the same as free and voluntary act and deed for the uses and purposes therein mentioned.
Given under my hand and official seal this day of .1998.
NOTARY PUBLIC in and for the State of Washington
residing at
My appointment expires
mitagre.doc
Page 4 of 3
i -
c
r
I
I
ti
CASCADE SURVEYING Surveyors
I& ENGINEERING, INC.
Engineers
ARLINGTON,WA
102 E Division•PO Box 326 98223
(360)435-5551 •(360)652-7572 — Planners
FAX(360)4354012
REVISED PROJECT NOTEBOOK FOR
CONCRETE DISTRIBUTORS, INC.
Narrative
A review of city records included the Stormwater Management Plan for the City of Arlington. The SWP
did not discuss this basin area.
Pollution from the proposed Cement Distributing facility will contribute both petroleum and metals
pollution and raise the ph of the stormwater. The treatment Best Management Plan selected for this site(CPS
Oil/Water Separators and Infiltration Ponds)will provide a combination of two of the approved methods for
removing pollutants from stormwater.
The project notebook is made up of the Construction Plans, and the Drainage Report. The following list indicates
where the required sections of the Project Notebook are located.
1. Stormwater runoff and Drainage System Calculations (See Drainage Report)
2. Storm Drainage Report Narrative (See Drainage Report)
3. Erosion and Sediment Control Plans (See Sheets 1 & 5)
4. Grading and Drainage Plans (See Sheet 5)
5. Operation and Maintenance Plan for E.S.C. (See Report and Sheet 5)
6. Operation and Maintenance Plan for Stormwater System (See Report, & sh. 4,5,6)
7. Financial Liability Instruments (To be attached)
8. Source Control Narrative for urban setting uses (See Drainage Report)
9. Copy of the filed Maintenance agreement (To be attached)
10. Legal Descriptions of SWM facilities to be deeded to the City (N/A)
11.Estimate of construction costs as per item 11. (N/A)
12. Inspection and Construction Control Schedule (See Report, & sh. 1)
�,zff$ K F.
5' O wA �-
4� o
J
RECEIVED
RE"JISED
127 6
MAY 2 8 1998
�S,31 NAL
CITY OF ARLINGTON 'ex
PtRes_12/23/�i'9 � i
I
�,
I
1
1, �
CASCADE SURVEYING Surveyors
& ENGINEERING, INC. Engineers
ARLINGTON,WA , •
102 E Division•PO Box 326 98223 — + Planners
(360)435-5551 •(360)652-7572
FAX(360)4354012
DRAINAGE REPORT FOR
CONCRETE DISTRIBUTORS, INC.
BASIC ANALYSIS
The proposal is to construct a Cement Distribution facility on lot 4 of the AA Investments Short Plat
recorded under A.F.#9608015001. The site is zoned industrial by the City of Arlington. The proposed buildings
are approximately 7,500 sq. ft. and 2,775 sq. ft. and there will also be approximately 200,000 sq.ft. of parking,
driving, and other impervious surfaces. The site falls South of the Airport Basin of Arlington Stormwater
Management Plan,and the plan indicates that soil types in the area fall within the Lynnwood grouping(An SCS
Type"A" soil).The Soil Survey of Snohomish County describes typical Lynnwood deposits as follows"This very
deep, somewhat excessively drained soil is on terraces and outwash plains""The surface layer is grayish brown
loamy sand about I" duck the upper part of the subsoil is dark brown loamy sand about 14"thick. The substratum
to a depth of 60 inches or more is grayish brown sand." Actual soil types on site were loamy sands to a depth of 0
inches, then a gravelly medium sand to at least 80". The water table was encountered at 80 to 100 inches in depth.
Because of the lack of slope and high infiltration rates in the area of this site there is no off site flow.
There are no known ponding problems even during heavy rains. There are no natural or constructed conveyences
within 300 vards that atIcct or are affected by this site. (see U.S.G.S. quad map image below). Stormwater from
the proposed site will be managed with Wct Ponds and Infiltration Ponds. Based on the above information no
drainage problems are foreseen. • �„ �,
Ion
A PO
,rig -
- ,w
W SITE
Edgecom b
2 DST. NE c Q• '� •
r•
N
SCALE: V = 1000' •
i . .
� .
,�
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC. Engineers
ARLINGTON,WA ,
102 E Division-PO Box 326 98223 `�- _ Planners
(360)435-5551 -(360)652-7572
FAX(360)435-4012
TEMPORARY EROSION AND SEDIMENTATION CONTROL
A variety of T.E.S.C. measures are being implemented on the construction plans,these measures provide for the following
areas of concern:
1. Stabilization and Soil Trapping (See TESC Notes, Sh. 1)
2. Delineate clearing and easement limits (See Grading Plans, Sh. 5)
3. Protection of Adjacent Property (Silt Fence)
4. Timing and Stabilization of Sediment Trapping Measures (See TESC Notes, Sh. 1)
5. Cut and Fill Slopes (See Gen. Notes, Sh. 1)
6. Controlling Off-site erosion (Infiltration Pond)
7. Stabilization of temporary conveyance channels and outlets (N/A)
8. Storm Drain Inlet Protection (See Details, Sh. 6)
9. Underground Utility Construction (See plans)
10. Construction Access Route. (See Grading Plan, Sh. 5)
11.Removal of Temporary BMP's (See TESC Notes, Sh. 1)
12.Dewatering Construction Site (N/A)
13. Control of Pollutants other than Sediment on Construction Site (Spill Control)
14.Maintenance (See TESC Notes, Sh. 1)
15.Financial Liability (See Financial Liability
in this report)
PRESERVATION OF NATURAL DRAINAGE FEATURES
There are no natural drainage features on the site due to the high infiltration rate of the soil. There is no flow from the site
as the existing vegetation cover, and site soils are capable of absorbing a high amount of rainfall.
SOURCE CONTROL OF POLLUTION
The type of activity that is to be going on this site(Cement Distribution)falls into the DOE catagory of Fleet Vehicle Yard
(See DOE Stormwater Manual, IV-2.2.2). The Stormwater Manual for the Puget Sound Basin recommends the following
for these activities.
"Stormwater from parking lots and maintenance areas where dripping oil or hydraulic fluids is likely to be occurring shall
be treated by an API or CPS-type oil/water separator(BMP RD.35 in Volume III,Runoff Control). Stormwater from
employees parking lots shall also be treated either in with or separately fromt the fleet vehicle parking areas using one of
the systems described in Volume III.
Stormwater runoff from rooftops may be discharged to the storm drain system as long as the drainage requirements of the
local Public Works Dept. are met. there is no stormwater drainage system(Storm Sewer)to disharge to, runoff from
rooftops should be disposed of through the use of an infiltration facility wherever possible(see BMP's RI.15 and RI.16 in
Chapter III-3 of the Runoff Control Volume)."
The source control BMP proposed for this site would be BMP S.200(Maintenance of Storm Drainage Facilities)as detailed in
Volume IV of the Stormwater Manual for the Puget Sound Basin(see the operations and maintenance section of this report for
details). The other recommend BMP's for the fleet vehicle yard(1.10, 1.20, 1.30, 1.40, 1.80,2.20)are not required based on the
proposed uses of this site by the owner.
i � ,
i
..
,�. . ..
�. -
CASCADE SURVEYING Surveyors
& ENGINEERING, INC.
Engineers
ARLINGTON,WA
102 E Division-PO Box 326 98223
(360)435-5551 •(360)652-7572 Planners
FAX(360)4354012
ON
SOURCE C01 TROL OF POLLUTION (continued)
The Stormwate�ndelayed
om the frontage road is not being treated at this time. All frontage road improvements(other than driveway
access)have and are to be included into a future L.I.D. as per an agreement with the City of Arlington.
The flow a site is being diverted via interceptor ditches to two CPS Oil/Water Separators. Flow from approximately half the
site(100, 0 sf)goes to each separator. The design flow from the 6 month storm event is 0.32 cfs(1/2 of the 6 month flow from the
site, see Attached Hydra Calculations). The projected plate area required is therefore(.32/.033)or about 10 sf. The Oil Water
Separator selected for this site will be the 48-CPS, Oil Water Separator,constructed by the Utility Vault Co., located in Auburn,WA.
This separator has a projected plate area of 592 sq. ft., a design flow rate of 0.33 cfs(146 gpm)and a maximum process flow of 1.24
cfs(555 gpm).
This separator was selected as it's manufacturer's design flow rate was closest to the expected flow rate for the 6 month
storm event for each separator and that also met the DOE's minimum requirements. Since the maximum flow expected off the site
to each separator is 0.52 cfs(See attached Hydra Calculations, 100 year Storm),the separators can be expected to provide some level
of treatment up to and including the 100 Year Storm Event. The Separators will however be provided with an overflow pipe,to
prevent overtopping of the Oil Retaining Baffle and release of the stored pollutants.
RUNOFF TREATMENT BMP'S
The stormwater from the site will be treated via Coalescing Plate(CPS)Oil/Water Separator, and an Infiltration Pond. The
oil/water separator will provide a level of treatment capable of removing high percentages of spilled or leaking pollutants
from the stormwater associated with the fleet vehicle storage and maintenance. This system will directly target the primary
pollutants to the stormwater and is an approved watery qupality treatment method of the DOE Stormwater Manual
'�titT l 5 1-.I- UV�`s
STREAMBANK EROSION CONTROL
This requirement is met by discharging all runoff from the site to the Infiltration Pond. See Calculations Section below for
Pond sizing calculations.
WETLANDS
There are no wetlands on the property.
WATER QUALITY SENSITIVE AREAS
No water quality sensitive areas have been identified on the site, and there is no stormwater discharge from the site to such
an area.
OFF-SITE ANALYSIS AND MITIGATION
There is no offsite discharge from the site, other than to groundwater during normal operation of the stormwater
management system. An overflow spillway will discharge from the west end of the pond to the roadside ditch along 59th
Ave. The flow in this ditch travels South to 172nd,thence East along 172nd, eventually crossing and joining the irrigation
ditches, and ultimately the Quilceda Creek Drainage. However due to extremely high infiltration capacity of the soils in the
area,little if any water is observed in the ditchline during storm events.
The discharge to groundwater from the site is being treated via the CPS Oil/Water Separators, and an infiltration
pond. The site is being graded to provide positive drainage to the ponds from all onsite areas. The flow from the buildings
will be discharged to splashpads, and thence will sheet flow to the interceptor ditches.
The water quality B1v1P when combined with Source Control,and an entergcnc y spill control plan,which is
required by both state and federal regulations for any hazardous materials stored or utilized on site, should be adequate to
prevent or control the spills and discharge or hazardous and priority pollutants.
1 � � '
- �.
.,
CCASICAOE SURVEYING Surveyors
Sc ENGINEERING, INC. Engineers
ARLINGTON,WA ,
102 E Division•PO Box 326 98223 `,,
(360)435-5551 •(360)652-7572 — Planners
FAX(360)435-4012
BASIN PLANNING
There is no off-site stormwater discharge, so no Basin Planning issues are applicable.
OPERATIONS AND MAINTENANCE
The owners shall be responsible for the operations and maintenance of the facilities. See following Maintenance
Requirements for Privately Maintained Drainage Facilities. The owner/applicant will record a binding
inspection/maintenance agreement for the City of Arlington as per AMC 16,10.210.
FINANCIAL LIABILITY
Financial Liability assurance will be provided as assessed by the City of Arlington.
CALCULATIONS
Drainage facilities were designed exclusively for improvements on site. Because of their lack of slope and high infiltration
rates the adjacent lots will not contribute any flow to the site. The flow from the parking, loading and driving surfaces will
be treated by Oil/Water Separators on its way to the infiltration pond.The infiltration pond is designed to accomodate the
flow from the entire site,except the frontage road. A separate treatment system will be designed and installed as part of
future frontage improvements.
Soils work performed on this site on February 6, 1998 indicate brown sandy loams(to 2' deep) overlaying gravelly medium
sands with a water table encountered at between 7' to 9' down. The proposal is to construct the infiltration pond's bottom
in the medium sands.
INFILTRATION POND:
The infiltration pond will consist of a 18' wide(bottom)by 367' long(bottom) main cell with 3:1 side slopes. The cell data is
summerized in the following table.
CELL ELEVATION AREA STORAGE
INFILTRATION CELL 128.0 6606 0
INFILTRATION CELL 129.0 8952 7780
INFILTRATION CELL 130.0 11370 17,975
TOTAL STORAGE 131.0 13860 30699
The storage calculations were performed using Hydra(Ver. 5.20),by Pizer, Inc. The calculation method used was a modified
(urban) Soil Conservation Service. The storm used was an SCS Type 1-A storm. Variables used in the calculations included
vegetation cover, slope,percent impervious,basin sizes,and curve numbers for the soil type. The curve numbers were taken from
the Department of Ecology's Stormwater Manual for the Puget Sound Basin,Table III-1.3. A curve number normally associated with
paved surfaces was used for the gravel parking area to account for future paving potential.
It is proposed to store all the storm events in the pond system. At the peak of the 2 year storm event the total required
storage will be 3446 cubic feet(link I page 5 of Hydra, 2 Year Storm). At the peak of the 10 year storm event the total
required storage will be 8561 cubic feet(link 1 page 6 of Hydra, 10 Year Storm). At the peak of the 100 year storm event
the total required storage will be 15974 cubic feet(link 1, page 7,Hydra, 100 Year Storm)leaving over 1' of excess I
storage remaining in the pond before overtopping occurs.
I
CDI February 2, 1998 JOB #12636 DOE Perc. Rate IN/HR
SOIL LOG 1: 0-12" Brown Sandy Loam 1.02
12-30" Tan loamy Sand 2.41
30-93" Gray Gray. med. Sand 8.27
93-96" Saturated. gray, Gray. med. Sand 0.00
9617+ Water table 0.00
SOIL LOG 2: 0-12" Brown sandy loam 1.02
12-20" Tan loamy Sand 2.41
,'20-80" Gray gravelly med. sand 8.27
80"+ Water table 0.00
SOIL LOG 3: 0-10" Brown sandy loam 1.02
10-24" Tan loamy sand 2.41
24-96" Gray gravelly medium sand 8.27
96-104" Saturated Gray, Gray. med. Sand 0.00
104"+ Water Table
SOIL LOG 4: 0-8" Brown sandy loam 1.02
8-22" Tan Loamy Sand 2.41
22-91" Gray Gravelly med. sand 8.27
91-101" Saturated Gray, Gray. med. Sand 0.00
10111+ Water Table
0.
MAINTENANCE AND OPERATIONS
CHECKLIST
All components of the stormwater system should be cleaned by October 15th of each
year to remove material that has accumulated during the dry season. The system
needs to be inspected at the end of any major storm event according to the attached
checklists.
The Oil/Water separator must be cleaned frequently to keep accumulated oil from
escaping during storms. They must always be cleaned by Oct. 15th to remove material
that has accumulated during the dry season, and again after a signigicant storm. In
addition:
1. The facility shall be inspected weekly by the owner.
2. Oil absorbent pads are to be replaced as needed but shall always be replaced
in the Fall prior to the wet season and in the Spring.
3. The effluent shutoff valve is to be closed during cleaning operations.
4. Waste oil and residuals shall be disposed in accordance with current local
government Health Department requirements.
5. Any standing wter removed during the maintenance operation must be disposed to
a sanitary sewer at a discharge location approved by the local government.
6. Any standing water removed shall be replaced with clean water to prevent oil
carry-over through the outlet weir ro orifice.
• 1. ! 1
•
MAINTENANCE REQUIREMENTS FOR
PRIVATELY MAINTAINED DRAINAGE FACILITIES
PONDS
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH&DEBRIS ANY TRASH AND DEBRIS WHICH EXCEED 1 TRASH AND DEBRIS CLEARED
CUBIC FOOT PER 1,000 SQUARE FEET(THIS IS FROM SITE.
ABOUT EQUAL TO THE AMOUNT OF TRASH IT
WOULD TAKE TO FILL UP ONE STANDARD
SIZE OFFICE GARBAGE CAN). IN GENERAL,
THERE SHOULD BE NO VISUAL EVIDENCE OF
DUMPING.
POISONOUS ANY POISONOUS VEGETATION WHICH MAY NO DANGER OF POISONOUS
VEGETATION CONSTITUTE A HAZARD TO COUNTY VEGETATION WHERE COUNTY
PERSONNEL OR THE PUBLIC. EXAMPLES OF PERSONNEL OR THE PUBLIC
POISONOUS VEGETATION INCLUDE: TANSY MIGHT NORMALLY BE.
RAGWORT,POISON OAK,STINGING NETTLES, (COORDINATION WITH HEALTH
DEVILS CLUB. DEPARTMENT).
POLLUTION OIL,GASOLINE,OR OTHER CONTAMINANTS NO CONTAMINANTS PRESENT
OF ONE GALLON OR MORE OR ANY AMOUNT OTHER THAN A SURFACE FILM.
FOUND THAT COULD: 1)CAUSE DAMAGE TO (COORDINATION WITH HEALTH
PLANT,ANIMAL,OR MARINE LIFE;2) DEPARTMENT).
CONSTITUTE A FIRE HAZARD;OR 3)BE
FLUSHED DOWNSTREAM DURING RAIN
STORMS.:
UNMOWED IF FACILITY IS LOCATED IN PRIVATE WHEN MOWING IS NEEDED,
GRASS/GROUND RESIDENTIAL AREA,MOWING IS NEEDED GRASS/GROUND COVER SHOULD
COVER WHEN GRASS EXCEEDS 18 INCHES IN HEIGHT. BE MOWED TO 2 INCHES HEIGHT.
IN OTHER AREAS,THE GENERAL POLICY IS TO
MAKE THE POND SITE MATCH ADJACENT
GROUND COVER AND TERRAIN AS LONG AS
THERE IS NO INTERFERENCE WITH THE
FUNCTION OF THE FACILITY.
RODENT HOLES ANY EVIDENCE OF RODENT HOLES IF RODENTS DESTROYED AND DAM
FACILITY IS ACTING AS A DAM OR BERM,OR OR BERM REPAIRED.
ANY EVIDENCE OF WATER PIPING THROUGH (COORDINATION WITH HEALTH
DAM OR BERM VIA RODENT HOLES. DEPARTMENT
INSECTS WHEN INSECTS SUCH AS WASPS AND INSECTS DESTROYED OR
HORNETS INTERFERE WITH MAINTENANCE REMOVED FROM SITE.
ACTIVITIES.
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
TREE GROWTH TREE GROWTH DOES NOT ALLOW TREES DO NOT HINDER
MAINTENANCE ACCESS OR INTERFERES WITH MAINTENANCE ACTIVITIES.
MAINTENANCE ACTIVITY(I.E.,SLOPE SELECTIVELY CULTIVATE TREES
MOVING,SILT REMOVAL,VACTORING,OR SUCH AS ALDERS FOR FIREWOOD.
EQUIPMENT MOVEMENTS). IF TREES ARE NOT
INTERFERING WITH ACCESS,LEAVE TREES
ALONE.
SIDE SLOPES OF EROSION ERODED DAMAGE OVER 2 INCHES DEEP SLOPES SHOULD BE STABILIZED
POND WHERE CAUSE OF DAMAGE IS STILL PRESENT BY USING APPROPRIATE EROSION
OR WHERE THERE IS POTENTIAL FOR CONTROL MEASURE(S);E.G.,ROCK
CONTINUE EROSION. REINFORCEMENT,PLANTING OF
GRASS,COMPACTION.
STORAGE AREA SEDIMENT ACCUMULATED SEDIMENT THAT EXCEEDS SEDIMENT CLEANED OUT TO
10%OF THE DESIGNED POND DEPTH. DESIGNED POND SHAPE AND
DEPTH;POND RESEEDED IF
NECESSARY TO CONTROL
EROSION.
POND DIKES SETTLEMENTS ANY PART OF DIKE WHICH HAS SETTLED 4 DIKE SHOULD BE BUILT BACK TO
INCHES LOWER THAN THE DESIGN THE DESING ELEVATION.
ELEVATION.
EMERGENCY ROCK MISSING ONLY ONE LAYER OR ROCK EXISTS ABOVE REPLACE ROCKS TO DESIGN
OVERFLOW/ NATIVE SOIL IN ARE FIVE SQUARE FEET OR STANDARDS.
SPILLWAY LARGER,OR ANY EXPOSURE OF NATIVE SOIL.
i �
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFOR-IF,D
INFILTRATION
GENERAL TRASH&DEBRIS SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.1
POISONOUS SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.1
VEGETATION
POLLUTION SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.1
UNMOWED GRASS/ SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.1
GROUND COVER
RODENT HOLES SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.I
INSECTS SEE"PONDS"STANDARD NO.I SEE"PONDS"STANDARD NO.1
STORAGE AREAS SEDIMENT A PERCOLATION TEST PIT OR TEST OF SEDIMENT IS REMOVED AND/OR
FACILITY INDICATES FACILITY IS ONLY FACILITY IS CLEANED SO THAT
WORKING AT 90%OF ITS DESIGNED INFILTRATION SYSTEM WORKS
CAPABILITIES. IF TWO INCHES OR MORE ACCORDING TO DESIGN.
SEDIMENT IS PRESENT,REMOVE.
SHEET COVER(IF SHEET COVER IS VISIBLE AND HAS MORE SHEET COVER REPAIRED OR
APPLICABLE) THAN THREE 1/4 INCH HOLES IN IT. REPLACED.
SUMP FILLED WITH ANY SEDIMENT AND DEBRIS FILLING VAULT CLEAN OUT SUMP TO DESIGN
SEDMIMENT AND TO 10%OF DEPTH FROM SUMP BOTTOM TO DEPTH.
DEBRIS(IF BOTTOM OF OUTLET PIPE OR OBSTRUCTING
APPLICABLE) FLOW INTO THE CONNECTOR PIPE.
FILTER BAGS FILLED WITH SEDIMENT AND DEBRIS FILL BAG MORE REPLACE FILTER BAG OR
SEDIMENT AND THAN 1/2 FULL. REDESIGN SYSTEM.
DEBRIS
ROCK FILTERS SEDIMENT AND BY VISUAL INSPECTION,LITTLE OR NO REPLACE GRAVEL IN ROCK
DEBRIS WATER FLOWS THROUGH FILTER DURING FILTER
HEAVY RAIN STORMS.
SIDE SLOPES OF EROSION SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.I
POND
EMERGENCY ROCK MISSING SEE"PONDS"STANDARD NO.1
OVER FLOW
SPILLWAY
SETTING PONDS SEDIMENT REMOVE WHEN 6"OR MORE.
AND AULTS
MAINTENANCE DEFLCT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
NOTE: SEDIMENT ACCUMULATION OF MORE THAN.25 INCHES PER YEAR MAY INDICATE EXCESSIVE EROSION IS OCCURRING
UPSTREAM OF THE FACILITY OR THAT CONVEYANCE SYSTEMS ARE NOT BEING PROPERLY MAINTAINED. THE CONTRIBUTING
DRAINAGE AREA SHOULD BE CHECKED FOR EROSION PROBLEMS OR INADEQUATE MAINTENANCE OF CONVEYANCE SYSTEMS IF
EXCESSIVE SEDIMENTATION IS NOTED IN AN INFILTRATION FACILITY.
CHECK TWICE A YEAR DURING FIRST 2 YEARS OF OPERATION; ONCE A YEAR THEREAFTER. CLEAN MANHOLES/CATCH BASINS,
REPAIR DAMAGED INLETS/OUTLETS,CLEAN TRASH RACKS.
MAINTENANCE REQUIREMENTS FOR
PRIVAELY MAINTAINED DRAINAGE FACILITIES
CONTROL STRUCTURE/FLOW RESTMCTOR
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
' COMPONENT MAINTENANCE IS NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH AND DEBRIS DISTANCE BETWEEN DEBRIS BUILD- ALL TRASH AND DEBRIS REMOVED.
(INCLUDES UP AND BOTTOM OF ORIFICE PLATE
SEDIMENT) IS LESS THAN 1 1/2 FEET.
STRUCTURAL STRUCTURE IS NOT SECURELY STRUCTURE SECURELY ATTACHED TO
DAMAGE ATTACHED TO MANHOLE WALL WALL AND OUTLET PIPE.
AND OUTLET PIPE STRUCTURE
SHOULD SUPPORT AT LEAST 1,000
POUNDS OF UP OR DOWN PRESSURE.
STRUCTURE IS NOT IN UPRIGHT STRUCTURE IN CORRECT POSITION.
POSITION(ALLOW UP TO 10%FROM
PLUMB).
CONNECTIONS TO OUTLET PIPE ARE CONNECTIONS TO OUTLET PIPE ARE
NOT WATERTIGHT AND SHOW WATERTIGHT;STRUCTURE REPAIRED OR
SIGNS OF RUST. REPLACED AND WORKS AS DESIGNED.
ANY HOLES-OTHER THAN
DESIGNED HOLES-IN THE
STRUCTURE.
CLEANOUT GATE DAMAGED OR CLEANOUT GATE IS NOT GATE IS WATERTIGHT AND WORKS AS
MISSING WATERTIGHT OR IS MISSING DESIGNED.
GATE CANNOT BE MOVED UP AND GATE MOVES UP AND DOWN EASILY AND
DOWN BY ONE MAINTENANCE IS WATERTIGHT.
PERSON.
CHAIN LEADING TO GATE IS CHAIN IS IN PLACE AND WORKS AS
MISSING OR DAMAGED. DESIGNED.
GATE IS RUSTED OVER 50%OF ITS GATE IS REPAIRED OR REPLACED TO MEET
SURFACE AREA. DESIGN STANDARDS.
ORIFICE PLATE DAMAGED OR CONTROL DEVICE IS NOT WORKING PLATE IS IN PLACE AND WORKS AS
MISSING PROPERLY DUE TO MISSING,OUT OF DESIGNED.
PLACE,OR BENT ORIFICE PLATE.
i
� � .
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCE IS NEEDED MAINTENANCE IS PERFORMED
OBSTRUCTIONS ANY TRASH,DEBRIS,SEDIMENT,OR PLATE IS FREE OF ALL OBSTRUCTIONS
VEGETATION BLOCKING THE PLATE. AND WORKS AS DESIGNED.
OVERFLOW PIPE OBSTRUCTIONS ANY TRASH OR DEBRIS BLOCKING PIPE IS FREE OF ALL OBSTRUCTIONS AND
(OR HAVING THE POTENTIAL OF WORKS AS DESIGNED.
BLOCKING)THE OVERFLOW PIPE.
MANHOLE SEE"CLOSED DETENTION SYSTEMS" SEE"CLOSED DETENTION SYSTEMS"
STANDARD NO.3 STANDARD NO.3
CATCH BASIN SEE"CATCH BASIN"STANDARD NO. SEE"CATCH BASIN"STANDARD NO.5
5
i r. �
�.
r
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES
DEBRIS BARRIERS (E.G.TRASH RACKS)
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH AND DEBRIS TRASH OR DEBRIS THAT IS PLUGGING BARRIER CLEAR TO RECEIVE
MORE THAN 20%OF THE OPENINGS IN THE CAPACITY FLOW.
BARRIER
METAL DAMAGED/MISSING BARS ARE BET OUT OF SHAPE MORE THAN 3 BARS IN PLACE WITH NO BENDS
BARS INCHES MORE THAN 3/4 INCH.
BARS ARE MISSING OR ENTIRE BARRIER IS BARS IN PLACE ACCORDING TO
MISSING DESIGN.
BARS ARE LOOSE AND RUST IS CAUSING REPAIR OR REPLACE BARRIER TO
50%DETERIORATION TO ANY PART OF DESIGN STANDARDS.
BARRIER
BARS ARE LOOSE AND RUST IS CAUSING REPAIR OR REPLACE BARRIER TO
50%DETERIORATION TO ANY PART OF DESIGN STANDARDS.
BARRIER.
J
MAINTENANCE REQUIREMENTS FOR PRIVATELY
MAINTAINED DRAINAGE FACILITIES.
CONVEYANCE SYSTEMS(PIPES AND DITCHES)
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
PIPES SEDIMENT&DEBRIS ACCUMULATED SEDIMENT THAT EXCEEDS PIPE CLEANED OF ALL SEDIMENT
20%OF THE DIAMETER OF THE PIPE. AND DEBRIS.
VEGETATION VEGETATION THAT REDUCES FREE ALL VEGETATION REMOVED SO
MOVEMENT OF WATER THROUGH PIPES. WATER FLOWS FREELY THROUGH
PIPES.
DAMAGED PROTECTIVE COATING IS DAMAGED; RUST PIPE REPAIRED OR REPLACED.
IS CAUSING MORE THAN 50%
DETERIORATION TO ANY PART OF PIPE.
ANY DENT THAT DECREASES THE CROSS PIPE REPAIRED OR REPLACED.
SECTION AREA OF PIPE BY MORE THAN
20%.
TRASH&DEBRIS TRASH AND DEBRIS EXCEEDS 1 CUBIC FOOT TRASH AND DEBRIS CLEARED FROM
PER 1,000 SQUARE FEET OF DITCH AND DITCHES.
SLOPES.
OPEN DITCHES SEDIMENT ACCUMULATED SEDIMENT THAT EXCEEDS DITCH CLEANED/FLUSHED OF ALL
20%OF THE DESIGN DEPTH. SEDIMENT AND DEBRIS SO THAT IT
MATCHES DESIGN.
VEGETATION VEGETATION THAT REDUCES FREE WATER FLOWS FREELY THROUGH
MOVEMENT OF WATER THROUGH DITCHES. DITCHES.
EROSION DAMAGE SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. 1
TO SLOPES
ROCK LINING OUT OF MAINTENANCE PERSON CAN SEE NATIVE REPLACE ROCKS TO DESIGN
PLACE OR MISSING SOIL BENEATH THE ROCK LIMING. STANDARD.
(IF APPLICABLE)
CATCH BASINS SEE"CATCH BASINS"STANDARD NO.5 SEE"CATCH BASINS"STANDARD NO.
5
DEBRIS BARRIER E.G. SEE"DEBRIS BARRIERS"STANDARD NO.6 SEE"DEBRIS BARRIERS"STANDARD
TRASH RACK NO.6
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES.
GROUNDS (LANDSCAPING)
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCE IS MAINTENANCE IS PERFORMED
NEEDED
WEEDS WEEDS GROWING IN WEEDS PRESENT IN LESS THAN 5%OF
(NONPOISONOUS) MORE THAN 20%OF THE THE LANDSCAPED AREA.
LAND-SCAPED AREA
(TREES AND SHRUBS
ONLY).
GENERAL
SAFETY HAZARD ANY PRESENCE OF POISON NO POISONOUS VEGETATION PRESENT IN
IVY OR OTHER POISONOUS A LANDSCAPED AREA.
VEGETATION.
TRASH OR LITTER PAPER,CAN,BOTTLES, AREA CLEAR OF LITTER.
TOTALING MORE THAN I
CUBIC FOOT WITHIN A
LANDSCAPED AREA
(TREES AND SHRUBS
ONLY)OF 1,000 SQUARE
FEET.
DAMAGE LIMBS OR PARTS OF TREES TREES AND SHRUBS WITH LESS THAN 5%
OR SHRUBS THAT ARE OF THE TOTAL FOLIAGE WITH SPLIT OR
SPLIT OR BROKEN WHICH BROKEN LIMBS.
AFFECT MORE THAN 25%
OF THE TOTAL FOLIAGE
OF THE TREE OR SHRUB.
TREES AND
SHRUBS
TREES OR SHRUBS THAT TREE OR SHRUB IN PLACE FREE OF
HAVE BEEN BLOWN DOWN INJURY.
OR KNOCKED OVER-
TREES OR SHRUBS WHICH TREE OR SHRUB IN PLACE AND
ARE OT ADEQUATELY ADEQUATELY SUPPORTED;REMOVE ANY
SUPPORTED OR ARE DEAD OR DISEASED TREES.
LEANING OVER,CAUSING
EXPOSURE OF THE ROOTS.
i
I
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES.
ACCESS ROADSIEASEMENTS
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCE IS NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH AND DEBRIS TRASH AND DEBRIS EXCEEDS 1 TRASH AND DEBRIS CLEARED FROM
CUBIC FOOT PER 1,000 FEET,I.E., SITE.
TRASH AND DEBRIS WOULD FILL
UP ONE STANDARD SIZE GARBAGE
CAN.
BLOCKED DEBRIS WHICH COULD DAMAGE ROADWAY FREE OF DEBRIS WHICH
ROADWAY VEHICLE TIRES(GLASS OR COULD DAMAGE TIRES.
METAL).
ANY OBSTRUCTIONS WHICH ROADWAY OVERHEAD CLEAR TO 14
REDUCE CLEARANCE ABOVE FEET HIGH.
ROAD SURFACE TO LESS THAN 14
FEET.
ANY OBSTRUCTIONS RESTRICTING OBSTRUCTION REMOVED TO ALLOW
THE ACCESS TO A 10 TO 12 FOOT AT LEAST A 12 FOOT ACCESS.
WIDTH FOR A DISTANCE OF MORE
THAN 12 FEET OR ANY POINT
RESTRICTING ACCESS TO LESS
THAN A 10 FOOT WIDTH.
ROAD SURFACE SETTLEMENT, WHEN ANY SURFACE DEFECT ROAD SURFACE UNIFORMLY SMOOTH
POTHOLES,MUSH EXCEEDS 6 INCHES IN DEPTH AND WITH NO EVIDENCE OF SETTLEMENT,
SPOTS,RUTS 6 SQUARE FEET IN AREA IN POTHOLES,MUSH SPOTS,OR RUTS.
GENERAL,ANY SURFACE DEFECT
WHICH HINDERS OR PREVENTS
MAINTENANCE ACCESS.
VEGETATION IN WEEDS GROWING IN THE ROAD ROAD SURFACE FREE OF WEEDS
ROAD SURFACE SURFACE THAT ARE MORE THAN 6 TALLER THAN 2 INCHES.
INCHES TALL AND LESS THAN 6
INCHES APART WITHIN A 400
SQUARE FOOT AREA
EROSION DAMAGE EROSION WITHIN 1 FOOT OF THE SHOULDER FREE OF EROSION AND
ROADWAY MORE THAN 8 INCHES MATCHING THE SURROUNDING
WIDE AND 6 INCHES DEEP. ROAD.
SHOULDERSAND
DITCHES
WEEDS AND BRUSH WEEDS AND BRUSH EXCEED 18 WEEDS AND BRUSH CUT TO 2 INCHES
INCHES IN HEIGHT OR HINDER IN HEIGHT OR CLEARED IN SUCH A
MAINTENANCE ACCESS. WAY AS TO ALLOW MAINTENANCE
ACCESS.
1
�,.
HYDRA CALCULATIONS
DEVELOPED STORM MODEL
1
��
I
• •Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 1
C:\HYDRA\CMD\12636.CMD 9:06 27-May-98
Status of DEFAULTS at start of run. ( * May be reset by SET)
I
I Command file : C:\HYDRA\CMD\12636.CMD
I Input units are read as : USA
(* Output sent to display : Brief
I* Output sent to printer : Off
I* Output sent to file : Brief
I Paper width in inches : 8.000
I String to reset printer : 27 51 36 18
String to set printer to compressed : 17 15
I String to set printer to 8 lines/inch : 8 27 51 27
Name of printer : Epson, FX series
I Print heading at top of page : True
I
Number of steps in hydrograph : '240
I Step length in minutes 10
Significant flow in hydrograph 0.000
I* Maximum plot value Selected by HYDRA
I Type of hydrographic plot Compact
I
Sanitary flow by Peaking Factor
Delay to start of actual storm : 0.00
Rational Method computations : Hydrograph
SCS computations : Santa Barbara
Continuous simulation computations : On
I* Maximum d/D for pipe design/analysis : 0.900
(* Match point position on pipe : 0.00 or Invert
I* Number of allowable diam drops : 999
I * Mimimum drop thru manhole : 0.000
I Routing technique : Quick
I
I* Calculate sanitary flows : True
(* Calculate infiltration flows : False
I* Calculate storm flows : True
I* Calculate misc flows : True
I
+--------------------------------------------------------------------
1: JOB 12636
2: TOT 0.90 (6mo=0.90 2yr=1.8, 10YR=2.75, 25yr=3.2, 100yr=3.75)
3: STE 10
4: FIL SCS_1A.INC
------START OF SUB-FILE------
1: REM SCS Type 1A Distribution (100 year - 24 hour)
2: HYE 10 0.0040 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
3: 0.004 0.005 0.005 0.005 0.005 0.005 0.005 0.006 0.006 0.006 +
4: 0.006 0.006 0.006 0.007 0.007 0. 007 0.007 0.007 0.007 0.0082
5: 0.0082 0.0082 0.0082 0.0082 0.0082 0.0095 0.0095 0.0095 +
6: 0.0095 0.0095 0.0095 0.0133 0.0133 0.0133 0.018 0.018 0.034 +
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 2
------------------------------------------------------------------------------
C:\HYDRA\CMD\12636.CMD 9:06 27-May-98
7 : 0.054 0. 027 0. 018 0. 0133 0.0133 0.0133 0.0088 0. 0088 0.0088 +
8 : 0.0088 0.0088 0.0088 0. 0088 0.0088 0.0088 0.0088 0.0088 +
9: 0.0088 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 +
10: 0.0072 0.0072 0.0072 0.0072 0.0072 0.0057 0. 0057 0.0057 +
11: 0.0057 0.0057 0. 0057 0. 0057 0.0057 0.0057 0.0057 0.0057 +
12: 0.0057 0.005 0.005 0.005 0.005 0.005 0.005 0.005 0.005 +
13: 0.005 0.005 0.005 0.005 0.004 0.004 0.004 0. 004 0.004 +
14: 0. 004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
15: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0. 004 0.004 +
16: 0. 004 0.004 0.004 0. 004 0.004 0. 004 0.004 0.004 0.004 +
17: 0.004 0.004 0.004 0.004 0.004 0.004 0. 004 0. 004 0. 004 +
18: 0.004 0.004 0.0006
Total in original hyetograph 0.17 Inches
Total volume rain in production hyetograph 0.90 Inches
Maximum intensity 0.29 Inches/Hr
19: RET
------ END dF SUB-FILE ------
5: PDA 0.012, 6, 1, 0.5, 2, 0.004, 60
6:
7: NEW SITE
8: SCS 0.47, 1, 98, 68, 20, .003, 600 (BLDGS AND PAVED PARKING)
Computed concentration time 9.13 Minutes
9: SCS 5.27, .95, 98, 68, 15, . 003, 600 (REST OF SITE)
Computed concentration time 12.17 Minutes
10: RES 207 0/0 66/0.63 17904/1.08 (INFILTRATION CELL)
NOTE: No flow to inlet.
11: REM CALCULATIONS BASED ON A 369' LONG POND WITH A 18 ' BOTTOM.
12: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
13: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
14: REM 0. 01' DEEP: (6606 X 4.13 / 43200 = 0. 63) VOL. = 66 CU. FT.
15: REM 2.00' DEEP: (11370 X 4.13 / 43200 = 1.08) VOL. = 17904 CU. FT.
16: END
1
I
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 3
C:\HYDRA\CMD\12636.CMD 9:06 27-May-98
------ S U M M A R Y O F A N A L Y S I S ------
Run number on command file : 16
Number of links : 1
Number of hydrographs : 35
Total sanitary population : 0
Total sanitary area : 0.00 Acres
Total storm area : 5.74 Acres
Number of pumps : 0
Number of reservoirs : 1
Number of diversion structures : 0
Number of inlets : 0
Length of new pipe : 0.00 Feet
Length of existing pipe : 0.00 Feet
Length of channel : 0.00 Feet
Length of gutter : 0.00 Feet
Length of transport units : 0.00 Feet
Length of pressure pipe : 0.00 Feet
I
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 6 MONTH STORM Page 4
C:\HYDRA\CMD\12636.CMD 9:07 27-May-98
12636
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
1 Unknown Discharge : 0.00 0.00 0.64 0.00 0.64 0
Unknown Stored : 0 0 421 0 421
Incoming : 0.00 0.00 0.96 0.00 0.96
----------------------------------------------------
Lateral length= 0 Upstream length= 0
i
' • s
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 2 YEAR STORM Page 5
C:\HYDRA\CMD\12636.CMD 9:09 27-May-98
12636
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
1 Unknown Discharge : 0.00 0.00 0.72 0.00 0.72 0
Unknown Stored : 0 0 3446 0 3446
Incoming : 0.00 0.00 2.16 0.00 2.16
----------------------------------------------------
Lateral length= 0 Upstream length= 0
i.
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 10 YEAR STORM Page 6
------------
C:\HYDRA\CMD\12636.CMD 9:11 27-May-98
12636
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
1 Unknown Discharge : 0.00 0.00 0.85 0.00 0.85 0
Unknown Stored : 0 0 8561 0 8561
Incoming : 0.00 0.00 3.41 0.00 3.41
----------------------------------------------------
Lateral length= 0 Upstream length= 0
scade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 100 YEAR STORM Page 7
C:\HYDRA\CMD\12636.CMD 9:16 27-May-98
12636
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
1 Unknown Discharge 0.00 0.00 1.03 0. 00 1.03 0
Unknown Stored 0 0 15974 0 15974
Incoming 0.00 0.00 4.74 0.00 4.74
----------------------------------------------------
Lateral length= 0 Upstream length= 0
" r
CASCADE SURVEYING Surveyors
t& EINGINEERING, INC.
Engineers
ARLINGTON,WA
'
102 E Division•PO Box 326 98223
(360)435-5551 •(360)652-7572 - Planners
FAX(360)435-4012
PROJECT NOTEBOOK FOR
CONCRETE DISTRIBUTORS, INC.
Narrative
A review of cite rcc ds included the Stormwater Management Plan for the City of A riigton. The SWP
(lid not discuss this basin area.
Pollution from the propos d Cement Distributing facility will contribute both pcir cum and metals
pollution and raise the ph of the stor water. The treatment Best Management Plan scle cd for this site(We[
Ponds and Infiltralion Ponds)will pro%i c a combination of two of the best approved it thods for removing
pollutaflls fioin slormwater.
The project notebook is made up of the Constru ion Plans, and the Drainage R ort. The following list indicates
where the required sections of the Project Notcbo are located.
1. Stonmvater nmuofTaud Drainage System 'alculations (See Drainage i?eporL) ,
2. Siorm Drainage Report Narrative (See Drainage Rej�%s�)
?. Erosion and Sediment Control Plans (See Sheets I & 5 j
4. Grading and Drainage Plans (See Sheet 5)
5. Cipr..ration and Maintenance Plan for E.S.C. (See Report and Sheet 5)
6. Operation and Maintenance Plan for Stormwater S% t a (See Report, &, sh. 4,5,6)
' Financial Liability Instruments Jobe attached)
R_ Source Control Narrative for urban setting us s (See Drainage Report)
`) Copy of the filed Maintenance agreement (To be attached)
1). Legal Descriptions of SWM facilities be deeded to the Cit. (N/A)
1 I Estimate of construction costs as pe tem I I. (N/A)
�lq��}�—C��st }�q See Report, & sh. 1)
1 nspc 1,I I T V 1'ni cH i fe¢N (
BUILDING DE- RTMENT
P V E D k.9
DATE QY
NO ANGES AU 1 0 `' Y4 F
U SS APPROVED BY THE Q[i F A j2
UILDING INSPECTOR
Ems,
12716
SS1 AL
EXPIRES 1212 99
• ti i
�_
f:
r
t,
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
Engineers
ARLINGTON,WA
102 E Division•PO Box 326 98223
(360)435-5551 •(360)652-7572 _ Planners
FAX(360)435-4012
DRAINAGE REPORT FOR
CONCRETE DISTRIBUTORS, INC.
BASIC ANALYSIS
The proposal is to construct a Cement Distribution facility on lot 4 of the A.A. Investments Short Plat
recorded under A.F.#9608015001.The site is zoned industrial by the City of Arlington. The proposed buildings
arc approximately 7,500 sq. ft. and 2,775 sq. ft. and there will also be approximatcl},200,000 sq. ft. of parking,
driving, and other impervious surfaces. The site falls South of the Airport Basin of Arlington Stormwater
Management Plan, and the plan indicates that soil types in the area fall within the Lynnwood grouping(An SCS
Type"A" soil). The Soil Survey of Snohomish County describes typical Lynnwood deposits as follows"This very
deep, somewhat excessively drained soil is on terraces and outwash plains""The surface layer is grayish brown
loamy sand about 1" thick, the upper part of the subsoil is dark brown loamy sand about 14" thick. The substratum
to a depth of 60 inches or more is grayish brown sand." Actual soil types on site were loamy sands to a depth of 30
inches, then a gravelly medium sand to at least 80". The water table was encountered at 80 to 100 inches in depth.
Because of the lack of slope and high infiltration rates in the area of this site there is no off site flow.
There are no known ponding problems even during licavy rains. There are no natural or constructed conveyences
within 300 vards that affect or are'affected by this site. (see U.S.G.S. quad map image below). StorniNvater from
the proposed site will be managed with Wet Ponds and Infiltration Ponds. Based on the above information no
drainage problems are foreseen. �m�{ I
I n
A PO tjjj
till
/ `
Z SITE
it W
lEdgeeon ilb
172ND o Q• Ar
N
1
J ,ZI
1
SCALE: V = 1000'
i
� 4�
1
�. - � r- r �
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
ARLINGTON,WA Engineers
102 E Division•PO Box 326 98223
(360)435-5551 •(360)652-7572 — Planners
FAX(360)435-4012
TEMPORARY EROSION AND SEDIMENTATION CONTROL
A variety of T.E.S.C. measures are being implemented on the constriction plans, these measures provide for the following
areas of concern:
1. Stabilization and Soil Trapping (See TESC Notes, Sh. 1)
2. Delineate clearing and easement limits (See Grading Plans, Sh. 5)
3. Protection of Adjacent Property (Silt Fence)
4. Timing and Stabilization of Sediment Tripping Measures (See TESC Notes, Sh. 1)
5. Cut and Fill Slopes (See Gen. Notes, Sh. 1)
6,' Controlling Off--site erosion (Infiltration Pond)
7. Stabilization of temporary conveyance channels and outlets (N/A)
8. Storm Drain Inlet Protection (See Details, Sh. 6)
9. Underground Utility Constriction (See plans)
10. Construction Access Route. (See Grading Plan, Sh. 5)
11. Removal of Temporary BMP's (See TESL Notes, Sh. 1)
12. Dewatering Construction Site (N/A)
13. Control of Pollutants other than Sediment on Construction Site (Spill Control)
14. Maintenance (See TESC Notes, Sh. 1)
15. Financial Liability (See Financial Liability
in this report)
PRESERVATION OF NAT.UR.AL DRAINAGE FEATURES
There are no natural drainage features on the site due to the high infiltration rate of the soil. There is no flow from the site
as the existing vegetation cover, and site soils are capable of absorbing a high amount of rainfall.
SOURCE CONTROL OF POLLUTION
The type of activity that is to be going on this site(Cement Distribution) falls into the DOE catagory of Fleet Vehicle Yard
(See DOE Stonnwater Manual, IV-2.2.2). The Stonnwater Manual for the Puget Sound Basin recommends the following
for these activities.
"Stonnwater from parking lots and maintenance areas where dripping oil or hydraulic fluids is likely to be occurring shall
be treated by an API or CPI-type oil/water separator(BMP RD.35 in Volume III,Runoff Control). Stormwater from
employees parking lots shall also be treated either in with or separately front the fleet vehicle parking areas using one of
the systems described in Volume III.
Stonnwater runoff from rooftops may be discharged to the storm drain system as long as the drainage requirements of the
local Public Works Dept. are met. If there is no stonnwater drainage system(Storm Sewer) to disharge to, runoff from
rooftops should be disposed of through the use of an infiltration facility wherever possible(see BMP's RI.15 and RI.16 in
Chapter III-3 of the Runoff Control Volume)."
The source control BMP proposed for this site would be BMP RD.35 as detailed in Volume III of the Storinvater Manual for the
Puget Sound Basin. The stormvater from the site is being treated via a combination of an oil/water separator with a debris and two
stage oil control system, Wet Ponds and an Infiltration Pond. The oil/water separator with an installed two stage oil control system
(See attachments from Aqua Treatment systems)will provide a level of treatment capable of removing high percentages of spilled or
leaking pollutants from the stormwater associated with the flee(vehicle storage and maintenance. This system will directly target the
primary pollutants to the stonnwater and in combination with the wct ponds will provide adequate water quality treatment.
1 ,
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
ARLINGTON,WA Engineers
102 E Dlvislon-PO Box 326 98223
(360)435-5551 -(360)652-7572 — Planners
FAX(360)435-4012
SOURCE CONTROL OF POLLUTION (continued)
The Stormwaler from the frontage road improvements is being treated via an Infiltration Trench with oil/water separator and an
installed debris and two stage oil control system. The oil/water separator with an installed two stage oil control system(See
attachments from Aqua Treatment systems)will provide a level of treatment capable of removing high percentages of spilled or
leaking pollutants from the stormwater associated with vehicular traffic. This system;will directly target the primary pollutants to
the stormwater and should provide adequate water quality treatment.
Alternative water quality treatment BMP's such as Bioswales or Wet Pond excel at lowering the stormwater PH, and removing heavy
metals from the stormwater. These are two types of pollution which will not be generated in appreciable amounts by the activities on
the frontage road., or the project site.
RUNOFF TREATMENT BMP'S
Runoff from all storm events from the site is being directed to the Wet Ponds, and thence to an Infiltration Pond. The Wet
Ponds are the water quality best management plan(bmp)while the infiltration Pond is the Streambank Erosion control
13W. All flow entering the system from the parking lots passes through an oil/water separator before entering any of the
ponds both-protectingthe ponds-and providing additional;watcr quality treatment. r'
Runoff from the frontage improvements is being treated by a combination of a Debris and Two Stage Oil Control System
(by Aqua Treatment Systems, at (206) 343-5221) installed in a catch basin with an Oil/Water Separator also installed. This
."system will provide waver quality,treatmcnt-to4he slormwater,collectcd off the road:This management plan-directel3• targets
the most common type of pollutants for roads. After passing through one of these systems the stormwater enters an
infiltration trench which will provide streambank erosion control treatment.
I
STREAMBANK EROSION CONTROL
This requirement is met by discharging all runoff from the site to the Infiltration Pond, and all runoff from the frontage
improvements to the Infiltration trenches in the road right-of-way. See Calculations Section below for Pond and Trench
sizing calculations.
WETLANDS
There are no wetlands on the property.
WATER QUALITY SENSITIVE AREAS
No water quality sensitive areas have been identified on the site, and there is no stormwater discharge from the site to such
an area.
OFF-SITE ANALYSIS AND MITIGATION
There is no offsite discharge from the site, other than to groundwater. The discharge to groundwater from the site is being
treated via wet ponds, and an infiltration pond,while the discharge from the infiltration trenches is being treated via an
oil/water separator device installed in the inlet catch basins. These water quality BMP's when combined with Source
Control, and an emergency spill control plan,which is required by both state and federal regulations for any hazardous
materials stored or utilized on site, should be adequate to prevent or control the spills and discharge or hazerdous and
priority pollutants.
.�
�1 f
�i, .}..i 1 �� � I . :7y:1� y � ,N
7
�. T i � - -
FCASCADE SURVEYING Surveyors
ENGINEERING, INC.
Engineers
ARLINGTON,WA
102 E Dlvislon•PO Box 326 98223
(360)435-5551 •(360)652-7572 — Planners
FAX(360)435-4012
BASIN PLANNING
There is no off-site stonmwater discharge, so no Basin Planning issues are applicable.
OPERATIONS AND MAINTENANCE
The owners shall be responsible for the operations and maintenance of(lie facilities. See following Maintenance
Requirements for Privately Maintained Drainage Facilities.The owner/applicant will record a binding
inspection/maintenance agreement for the City of Arlington as per AMC 16.10.210.
FINANCIAL LIABILITY
Financial Liability assurance will be provided as assessed by the City of Arlington.
CALCULATIONS
Drainage facilities were designed exclusively for improvements on-site and for improvements in the right-of-tvay. Because
of their lack of slope and high infiltration rates the adjacent lots will not contribute any flow to the site. The flow from the
parking, loading and driving surfaces will be treated by wct ponds on its way to the infiltration pond. The infiltration pond
is designed to accomodate.the flow-from the er.tirc sitc,:exeept the frontage road, The infiltration trench in the road right-of
-way is designed to treat the frontage improvements.
Soils work performed on this site on February 6, 1998 indicate brown sandy loams(to 2' deep) overlaying gravelly medium
sands with a water table encountered at bctwecn 7' to 9' down. The proposal is to construct infiltration trench's and pond
bottom in the medium sands.
INFILTRATION TRENCH:
The infiltration trench will be 3 feel wide by 2.5 feet deep by 290 feet long. The trench will be divided into 2 parts
(separated by a catch basin)and located between the southerly 3 catch basins in the road right-of-way (sec Site Plan).The
D.O.E. recommended rate of infiltration for medium sands is 8.27 inches per hour. We are proposing to contain all storm
events within the above mentioned trench. The dimensions of the trench will have a bottom width of 3 ft. and be 290 ft.
long. Using these variables the maximum infiltration from the trench may be calculated:
3.Oft x 290 ft. x 4.13 in x I hr. x 1 min. x 1 ft. = 0.083 c.f.s.
f} hr. 60 min. 60 see. 12 in.
The Volume of the Trench can be calculated as follows:
290' x 3' wide x 2.5' high x 35% void space = 761 cu. ft. +
290' x 3.14(.33)2 x 65% = 64 cu. ft + 761 cu. ft. or 825 cu. ft. of trench storage
The storage calculations were performed using Hydra(Ver. 5.20), by Pizer, Inc. The calculation method used was a
modified(urban)Soil Conservation Service. The storm used was an SCS Type 1-A storm. Variables used in the
calculations included vegetation cover, slope,percent impervious, basin sizes,and curve numbers for the soil type. The
curve numbers were taken from the Department of Ecology's Stormwater Manual for the Puget Sound Basin,Table III-1.3.
It is proposed to store all the storm events in the trench. At the peak of the 2 year storm event the total required storage will
be 116 cubic feet(link 3 page 5 of Hydra, 2 Year Storm). At the peak of the 10 year stonn event the total required storage
will be 293 cubic feet(link 3 page 6 of Hydra, 10 Year Storm). At the peak of the too year storm event the total required
storage will be 596 cubic feet (link 3, page 7,Hydra, too Year Storm)leaving 229 cf of storage remaining is the trench.
" _ I cx• •
1 rtiL�' 1 �y:J�-� • ■►I �1 spit-/I\
y'
CASCADE SURVEYING Surveyors
t& ENGINEERING, INC.
ARLINGTON,WA Engineers
102 E Division-PO Box 326 98223 `.
(360)435-5551 -(360)652-7572 -- Planners
FAX(360)4354012
CALCULATIONS (CONTINUED)
INFILTRATION POND:
The infiltration pond system will consist of 3 cells, a main infiltration cell bracketed by two smaller wet pond cells on the East and
West ends of the main cell (see Site Plan). The stage-storage relationship for the three cells is summarized in the following tables.
CELL ELEVATION AREA STORAGE
WEST WET CELL 127.5 641 0
WEST WET CELL 128.0 759 0/350 (WET)
WEST WET CELL 129.0 1020 890
WEST WET CELL 130.0 1313 2056
CELL ELEVATION AREA STORAGE
EAST WET CELL 127.5 639 0
WEST WET.CELL 128.0 756 0/349 (WET)
WEST WET CELL 129.0 1016 886
WEST WET CELL 130.0 1308 2048
CELL ELEVATION AREA STORAGE
INFILTRATION CELL 128.0 7029 0
INFILTRATION CELL 129.0 8131 7580
INFILTRATION CELL 130.0 9259 15919
TOTAL STORAGE 130.0 20023
The storage calculations were performed using Hydra (Ver. 5.20), by Pi•r_er, Inc. The calculation method used was a modified
(urban) Soil Conservation Service. The storm used was an SCS Type 1-A storm. Variables used in the calculations included
vegetation cover, slope, percent impervious, basin sizes, and curve numbers for the soil type. The curve numbers were taken from
the Department of Ecology's Stormwater Manual for the Puget Sound Basin,Table III-1.3. A curve number normally associated with
paved surfaces was used for the gravel parking area to account for future paving potential.
It is proposed to store all the storm events in the pond system. At the peak of the 2 year storm event the total required
storage will be 3362 cubic feet (link 4 page 5 of Hydra, 2 Year Storm). At the peak of the 10 year stonn event the total
required storage will be 8889 cubic feet(link 4 page 6 of Hydra, 10 Year Storm). At the peak of the 100 year storm event
the total required storage will be 18062 cubic feet(link 4, page 7, Hydra, 100 Year Storm) leaving just over V of excess
storage remaining in the pond before overtopping occurs.
WET POND SIZING:
A Hydra caculation was performed to determine the required storage for the wet pond cells. The wet ponds are sized to
store at:cast the 6 mo. storm.e:�ent. The fcquircd storage amount %vas Bete,mined to be 367.f(See Link 4, page 8, Hydra,
6 Month Storm). The actual storage provided was approximately 700 cf, the larger volume will compensate for storage
volume lost to sedimentation during construction and on going usage.
� �. �. �.�� � 'n}� .. 1'r '' ♦ice r
�r
CAS CAD E SURVEYING Surveyors
Sc ENGINEERING, INC. Engineers
ARLINGTON,WA ,
102 E Division•PO Box 326 98223 `.
(360)435-5551 •(360)652-7572 — Planners
FAX(360)435-4012
CDI February 2, 1998 JOB #12636 DOE Perc. Rate IN/H-R
SOIL LOG 1: 0-12" Brown Sandy Loam 1.02
12-30" Tan loamy Sand 2.41
30-93" Gray Grav, med. Sand 8.27
93-96" Saturated. gray, Gray. med. Sand 0.00
96"+ Water table 0.00
SOIL LOG 2: 0-12" Brown sandy loam 1.02
12-20" Tan loamy Sand 2.41
20-80" Gray gravelly med. sand 8.27
80"+ Water table 0.00
SOIL LOG 3: 0-10" Brown-sandy loam 1.02
10-24" Tan loamy sand 2.41
24-96" Gray gravelly medium sand 8.27
96-104" Saturated Gray,-Gray. med. Sand 0.00
104"+ Water Table
SOIL LOG 4: 0-8" Brown sandy- loam 1.02
8-22" Tan Loamy Sand 2.41
22-91" Gray Gravelly med. sand 8.27
91-101" Saturated Gray, Gray. med. Sand 0.00
101"+ Water Table
�+.
I
I
I
t
MAINTENANCE AND OPERATIONS
CHECKLIST
i
I
MAINTENANCE REQUIREMENTS FOR
PRIVATELY MAINTAINED DRAINAGE FACILITIES
PONDS
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH&DEBRIS ,u Y TRASH AND DEBRIS WHICH EXCEED 1 TRASH AND DEBRIS CLEARED
CUBIC FOOT PER 1,000 SQUARE FEET(THIS IS FROM SITE.
ABOI JT EQUAL TO THE AMOUNT OF TRASH IT
WOULD TAKE TO FILL UP ONE STANDARD
SIZE OFFICE GARBAGE CAN). IN GENERAL,
THERE SHOULD BE NO VISUAL EVIDENCE OF
DUMPING.
i
POISONOUS ANY POISONOUS VEGETATION WHICH MAY NO DANGER OF POISONOUS
VEGETATION CONSTITUTE A HAZARD TO COUNTY VEGETATION WHERE COUNTY
PERSONNEL OR THE PUBLIC. EXAMPLES OF PERSONNEL OR THE PUBLIC
POISONOUS VEGETATION INCLUDE: TANSY MIGHT NORMALLY BE.
RAGWORT,POISON OAK,STINGING NETTLES, (COORDINATION WITH HEALTH
DEVILS CLUB. - DEPARTMENT).
POLLUTION OIL.GASOLINE,OR OTHER CONTAMINANTS NO CONTAMINANTS PRESENT
OF ONE GALLON OR MORE OR ANY AMOUNT OTHER THAN A SURFACE FILM.
FOUND THAT COULD: 1)CAUSE DAMAGE TO (COORDINATION WITH HEALTH
PLANT,ANIMAL,OR MARINE LIFE;2) DEPARTMENT).
• CONSTITUTE A FIRE HAZARD;OR 3)BE
FLUSHED DOWNSTREAM DURING RAIN
STORMS.:
UNMOWED IF FACILITY IS LOCATED IN PRIVATE WHEN MOWING IS NEEDED.
GRASS/GROUND RESIDENTIAL AREA.MOWING IS NEEDED GRASS/GROUND COVER SHOULD
COVER WHEN GRASS EXCEEDS 18 INCHES IN HEIGHT. BE MOWED TO 2 INCHES HEIGHT.
IN OTHER AREAS,THE GENERAL POLICY IS TO
M:UCE THE POND SITE MATCH ADJACENT
GROUND COVER AND TERRAIN AS LONG AS
THERE IS NO INTERFERENCE WITH THE
FUNCTION OF THE FACILITY.
RODENT HOLES ANY EVIDENCE OF RODENT HOLES IF RODENTS DESTROYED AND D.AOM
FACILITY IS ACTING AS A DAM OR BERM,OR OR BERM REPAIRED.
ANY EVIDENCE OF WATER PIPING THROUGH (COORDINATION WITH HEALTH
DAM OR BERM VIA RODENT HOLES. DEPARTMENT
INSECTS WHEN INSECTS SUCH AS WASPS AND INSECTS DESTROYED OR
HORNETS INTERFERE WITH MAINTENANCE REMOVED FROM SITE.
ACTIVITIES.
�� ,
_ f.' ..
.r..7 • - _
J
• ?.
NIAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFOKNIED
TREE GROWTH TREE GROWTH DOES NOT ALLOW TREES DO NOT HINDER
MAINTENANCE ACCESS OR INTERFERES WITH MAINTENANCE ACTIVITIES.
MAINTENANCE ACTIVITY(I.E..SLOPF, SELECTIVELY CULTIVATE TREES
MOVING,SILT REMOVAL,VACTORING,OR SUCH AS ALDERS FOR FIREWOOD.
EQUIPMENT MOVEMENTS). IF TREES ARE NOT
INTERFERING WITH ACCESS,LEAVE TREES
AI,ONF,.
SIDE SLOPES OF EROSION ERODED DAMAGE OVER 2 INCHES DEEP SLOPES SHOULD BE STABILIZED
POND WHERE CAUSE OF DAMAGE IS STILL PRESENT BY USING APPROPRIATE EROSION
OR WHERE THERE IS POTENTIAL FOR CONTROL MEASURE(S);E.G.,ROCK
CONTINIJE EROSION. _ REINFORCEMENT,PLANTING OF
GRASS,COMPACTION.
STORAGE AREA SEDIMENT ACCUMULATED SEDIMENT THAT EXCEEDS SEDIMENT CLEANED OUT TO
10%OF THE DESIGNED POND DEPTH. DESIGNED POND SHAPE AND
DEPTH;POND RESEEDED IF
NECESSARY TO CONTROL
EROSION.
POND DIKES SETTLEMENTS ANY PART OF DIKE WHICH HAS SETTLED 4 DIKE SHOULD BE BUILT BACK TO
INCITES LOWER THAN THE DESIGN THE DESING ELEVATION.
EI,EVA'ITON.
EMERGENCY ROCK\dISSING ONLY ONE LAYER OR ROCK EXISTS ABOVE REPLACE ROCKS TO DESIGN
OVERFLOW/ NATIVE SOIL IN ARE FIVE SQUARE FEET OR STANDARDS.
SPILLWAY LARGER,OR ANY EXPOSURE OF NATIVE SOIL.
. 2
i
r
.�
-.
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS FXPECTED WIIEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
INFILTRATION
GENERAL. TRASH&DEBRIS SEE."PONDS"STANDARD NO.I SEE"PONDS"STANDARD NO. 1
POISONOUS SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. 1
VEGETATION
POLLUTION SEE"PONDS"STANDARD NO.I SEE"PONDS"STANDARD NO. 1
LTNMOWED GRASS/ SEE"PONDS"STANDARD NO. I SEE"PONDS"STANDARD NO. I
GROUND COVER
RODENT HOLES SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. i
INSECTS SEE"PONllS"STANDARD NO.1 SEE"PONDS"STANDARD NO. 1
STORAGE AREAS SEDIMENT A PERCOLATION TEST PIT OR TEST OF SEDIMENT IS REMOVED ANDiOR
FACILITY INDICATES FACILITY IS ONLY FACILITY IS CLEANED SO THAT
WORKING AT 90%OF ITS DESIGNED INFILTRATION SYSTEM WORKS
CAPABILITIES. IF TWO INCHES OR MORE ACCORDING TO DESIGN.
SEDIMENT IS PRESENT,REMOVE.
SHEET COVER(IF SHEET COVER IS VISIBLE AND HAS MORE SHEET COVER REPAIRED OR
APPLICABLE) THAN THREE 1/4 INCH HOLES IN IT. REPLACED.
SUMP FILLED WITII ANY SEDIMENT AND DEBRIS FILLING VAULT CLEAN OUT SUMP TO DESIGN
SEDMIMENT AND TO 10%OF DEPTH FROM SUMP BOTTOM TO DEPTH.
DEBRIS(IF BOTTOM OF OUTLET PIPE OR OBSTRUCTING
APPLICABLE) FLOW INTO THE CONNECTOR PIPE.
FILTER BAGS FILLED WITH SEDIMENT AND DEBRIS FILL BAG MORE REPLACE FILTER BAG OR
SEDIMENT AND THAN 1/2 FULL. REDESIGN SYSTEM.
DEBRIS
ROCK FILTERS SF.DIiMENT AND BY VISUAL INSPECTION,LITTLE OR NO REPLACE GRAVEL IN ROCK
DEBRIS WATER FLOWS THROUGH FILTER DURING FILTER.
HEAVY RAIN STORMS.
SIDE SLOPES OF EROSION SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. I
POND
EMERGENCY ROCK MISSING SEE"PONDS"STANDARD NO. I
OVERFLOW
SPILLWAY
SETTING PONDS SEDIMENT REMOVE WHEN 6"OR MORE.
AND AI ILTS
3
J
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
NOTE: SEDIMENT ACCUMULATION OF MORE THAN.25 INCHES PER YEAR MAY INDICATE EXCESSIVE EROSION IS OCCURRING
UPSTREAM OF THE FACILITY OR THAT CONVEYANCE SYSTEMS ARE NOT BEING PROPERLY MAINTAINED. THE CONTRIBUTING
DRAINAGE AREA SHOULD BE CHECKED FOR EROSION PROBLEMS OR INADEQUATE MAINTENANCE OF CONVEYANCE SYSTEMS IF
EXCESSIVE SEDIMENTATION 1S NOTED IN AN INFILTRATION FACILITY.
CHECK TWICE A YEAR DURING FIRST 2 YEARS OF OPERATION; ONCE A YEAR THEREAFTER. CLEAN MANHOLES/CATCH BASINS,
REPAIR DAMAGED INLETS/OUTLETS,CLEAN TRASH RACKS.
e
4
MAINTENANCE REQUIREMENTS FOR
PRIVAELY MAINTAINED DRAINAGE FACILITIES
CONTROL STRUCTUREIFLOW RESTRICTOR
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCE IS NEEDED MAINTENANCF.IS PERFORMED
GENERAL TRASH AND DEBRIS DISTANCE BETWEEN DEBRIS BUILD- ALI,TRASH AND DEBRIS REMOVED.
(INCLUDES l TP:UND BOTTOM OF ORIFICE PLATE
SEDIMENT) is LESS THAN 1 1/2 FEET.
STRUCTURAL. STRUCTURE IS NOT SECURELY STRUCTURE SECURELY ATTACIIED TO
DAMAGE ATTACIIED TO MANHOLE WALL WAIL AND OUTLET PIPE.
AND OUTLET PIPE STRUCTURE
SHOULD Si TPORT AT LEAST 1,000
POUNDS OF UP OR DOWN PRESSURE.
STRUCTURE IS NOT IN UPRIGHT STRUCTURE IN CORRECT POSITION.
POSITION(ALLOW UP TO 10%FROM
PLUMB).
C ONNF.CTIONS TO OUTLET PIPE.ARE CONNECTIONS TO OUFLET PIPE ARE
NOT\►WATERTIGHT AND SHOW WATERTIGHT;STRUCTURE REPAIRED OR
SIGNS OF RUST. REPLACED AND WORKS AS DESIGNED.
ANY HOLES-OTHER THAN
DESIGNED HOLES-IN THE
STRUCTURE.
CLEANOUT GATE DAMAGED OR CLEANOUF GATE IS NOT GATE IS WATERTIGHT AND WORKS AS
MISSING WATERTIGHT OR IS MISSING DESIGNED.
GATT;CANNOT BE MOVED UP AND GATE MOVES UP AND DOWN EASILY AND
DOWN BY ONE MAINTENANCE IS WATERTIGHT.
PERSON.
CHAIN LEADING TO GATE IS CHAIN IS IN PLACE AND WORKS AS
MISSING OR DAMAGED. DESIGNED.
MATE IS RUSTED OVER 50%OF ITS GATE IS REPAIRED OR REPLACED TO MEET
SURFACE AREA. DESIGN STANDARDS.
ORIFICE PLATE DAMAGED OR CONTROL DEVICE IS NOT WORKING PLATE IS IN PLACE AND WORKS AS
MISSING PROPERLY DUE TO MISSING,OUT OF DESIGNED.
PLACE,OR BENT ORIFICE PLATE.
6
I
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCI:IS NEEDED MAINTENANCE IS PERFORMED
OBSTRUCTIONS ANY TRASH,DEBRIS,SEDIMENT,OR PLATE IS FREE OF ALL OBSTRUCTIONS
VEGETATION BLOCKING THE PLATE. AND WORKS AS DESIGNED.
OVERFLOW PIPE OBSTRUCTIONS ANY TRASH OR DEBRIS BLOCKING PIPE IS FREE OF ALL OBSTRUCTIONS AND
(OR IIAN'ING THE POTENTIAL OF WORKS AS DESIGNED.
BLOCKING)THE OVERFLOW PIPE.
MANHOLE SEE"CLOSED DETENTION SYSTEMS" SEE"CLOSED DETENTION SYSTEMS"
STANDARD NO.3 STANDARD NO.3
CATCH BASIN SEE"CATCH BASIN"STANDARD NO. SEE"CATCH BASIN"STANDARD INTO.5
5
i
MAIIVNTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES
CATCH BASINS
MAINTENANCE. DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
GENERAL, 'TRASH&DEBRIS TRASH OR DEBRIS OF MORE THAN 1/2 NO TRASH OR DEBRIS LOCATED
(INCLUDES CUBIC FOOT WHICH IS LOCATED IMMEDIATELY IN FRONT OF
SEDIMENT) IMMEDIATELY IN FRONT OF THE CATCH CATCH BASIN OPENING.
BASIN OPENING OR IS BLOCKING CAPACITY
OF BASIN BY MORE THAN 10%.
TRASH OR DEBRIS(IN THE,BASIN)THAT NO TRASH OR DEBRIS IN THE
EXCEEDS 1/3 THE DEPTH FROM THE CATCH BASIN.
BOTTOM OF BASIN TO INVERT T OF THE
LOWEST PIPE INTO OR Ol PT OF THE BASIN.
TRASH OR DEBRIS IN ANY INLET OR INLET AND OUTLET PIPES FREE.
OUI'LET PIPE BLOCKING MORE.THAN 1/3 OF OF TRASH OR DEBRIS.
ITS HEIGHT.
DEAD ALNIM;lLS OR VEGETATION THAT NO DEAD ANIMALS OR
COULD GENERATE ODORS THAT WOULD VEGETATION PRESENT WITHIN
CAUSE COMPLAINTS OR DANGEROUS THE CATCH BASIN.
(LASES(E.G..METHANE).
DEPOSITS OF GARBAGE EXCEEDING 1 NO CONDITION PRESENT WHICH
ClIBIC FOOT IN VOLUME. WOULD ATTRACT OR SUPPORT
THE BREEDING OF INSECTS OR
RODENTS.
STRUCTURAL CORNER OF FRAME EXTENDS MORE THAN FRAME IS EVEN WITH CURB.
DAMAGE TO FRAIME 3/4 INCH PAST CURB FACE INTO THE
AND/OR TOP SLAB STREET(IF APPLICABLE).
TOP SLAB HAS HOLES LARGER THAN 2 TOP SLAB IS FREE OF HOLES AND
SQUARE INCHES OR CRACKS WIDER THAN CRACKS,
1/4 INCH(INTENT IS TO MAKE SURE AL.I,
MATERIAL IS RT JNNING INTO THE BASIN).
FILAIE NOT SITTING FLUSH ON TOP SLAB.1. FRAME IS SITTING FLUSH ON TOP
E._SEPARATION OF MORE THAN 3/4 INCH OF SLAB.
TITE FFlAME FROM THE TOP SLAB.
i
CRACKS IN BASIN CRACKS WIDER THAN 1/2 INCH AND BASIN REPLACED OR REPAIRED
WALLS;BOTTOU LONGER TITAN 3 FEET,ANY EVIDENCE OF TO DESIGN STANDARDS.
SOIL PARTICLES ENTERING CATCH BASIN
THROI JGH CRACKS,OR MAINTENANCE
PERSON JUDGES THAT STRUCTURE IS
UNSOUND.
CRACKS WIDER THAN 1/2 INCH AND NO CRACKS MORE TITAN 1/4
LONGER THAN 1 FOOT AT THE JOINT OF INCH WIDE AT THE JOINT OF
,ANT"INLET/OUTLET PIPE OR ANY EVIDENCE INLET/OUTLET PIPE.
OF SOIL PARTICLES ENTERING CATCH
BASIN THROUGH CRACKS.
8
1 ..
. . - -
f
r
%%INTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED%%IIEN
COMPONENT NEEDED M�UNTENANCE IS PERFORMED
SETTLEMENT/ BASIN HAS SETTLED MORE THAN 1 INCH OR BASIN REPLACED OR REPAIRED
MISALIGNMENT HAS ROTATED MORE THAN 2 INCHES OUT TO DESIGN STANDARDS.
OF ALIGNMENT.
FIRE HAZARD PRESENCE OF CHEMICALS SUCH AS NO FLAMMABLE CHEMICALS
NATURAL.GAS.OIL,GASOLINE. PRESENT.
VEGETATION VEGETATION GROWING ACROSS AND NO VEGETATION BLOCKING
BLOCKING MORE THAN 10%OF THE BASIN OPENING TO BASIN.
OPENING.
VEGETATION GROWING IN INLET/OUTLET NO VEGETATION OR ROOT
PIPE JOINTS THAT IS MORE THAN SLY GROWTH PRESENT.
INCITES TALL AND LESS THAN SIX INCHES
PART.
POLLUTION NONFLAMMABLE CHEMICALS OF MORE NO POLLUTION PRESENT OTHER
TH:VN 1/2 CUBIC FOOT PER THREE FEET OF THAN SURFACE FILM.
BASIN LENGTH.
CATCH BASIN COVER COVER NOT IN COVER IS MISSING OR ONLY PARTIALLY IN CATCH BASIN COVER IS CLOSED.
PLACE PLACE. ANY OPEN CATCH BASIN REQUIRED
M AINTEN;ANC E.
LOCKING \MECH.L\ISM CANNOT BE OPENED BY ONE MECHANISM OPENS WITH
MECII.ANIS\[NOT MAINTENANCE PERSON WITH PROPER PROPER TOOLS.
WORKING TOOLS. BOLTS INTO FRAME HAVE LESS
TB,),N 1/2 INCH OF THREAD.
COVER DIFFICULT TO ONE MAINTENANCE PERSON CANNOT CO'v.R CAN BE REMOVED BY
REMOVE REMOVE LID AFTER APPLYING 80 LBS.OF ONE MAINTENANCE PERSON.
LIFT-,INTENT 1S KEEP COVER FROM
SEALING OFF ACCESS TO MAINTENANCE.
LADDER LADDER RUNGS LADDER IS UNSAFE DUE TO MISSING LADDER MEETS DESIGN
UNSAFE RUNGS,MISALIGNMENT,RUST,CRACKS,OR STANDARDS AND ALLOWS
SHARP EDGES. MAINTENANCE PERSON SAFE
ACCESS.
METAL GRATE (IF GRATE OPENING WIDER THAN 7/8 INCH. GRATE OPENINGS MEET DESIGN
APPLICABLE) STANDARDS.
TRASH AND DEBRIS TRASH AND DEBRIS THAT IS BLOCKING GRATE.FREE OF TRASH AND
MORE THAN 20%OF GRATE SURFACE. DEBRIS.
DAMAGED OR GRATE MISSING OR BROKEN MEMBER(S)OF GRATE IS IN PLACE AND MEETS
MISSING THE GRATE. DESIGN STANDARDS.
9
i
r
MAINTENANCE REQUIREMENTS FOR PRIVATELY
MAINTAINED DRAINAGE FACILITIES.
CONVEYANCE SYSTEMS (PH'ES AND DITCHES)
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTI?D WHEN
COMPONENT NEEDED MiUNTENANCE IS PERFORMED
PIPES SEDIMENT&DEBRIS AC'CUML1LATED SEDIMENT THAT EXCEEDS PIPE CLEANED OF ALL SEDIMENT
204 o OF THE DIAMETER OF THE PIPE. AND DEBRIS.
VEGETATION VEGETATION THAT REDUCES FREE ALL VEGETATION REMOVED SO
INIOVENIENT OF WATER THROUGH PIPES. WATER FLOWS FREELY THROUGH
PIPES.
DAMAGED PROTECTIVE COATING;IS DAMAGED; RUST PIPE REPAIRED OR REPLACED.
1S CAUSING MORE THAN 50%
DETERIORATION TO ANY PART OF PIPE.
:1NY DENT TIIAT DECREASES THE CROSS PIPE REPAIRED OR REPLACED.
SECTION AREA OF PIPE BY MORE THAN
200'.
TRASH&DEBRIS TRASH AND DEBRIS EXCEEDS I CUBIC FOOT TRASH AND DEBRIS CLEARED I'RORI
PER I.0O0 SQUARE FEET OF DITCH AND DITCHES.
SLOPES.
OPEN DITCHES SEDIMENT \CCLnILTLATED SEDIMENT THAT EXCEEDS DITCH CLEANED/FLUSHED OF ALL
20"o OF THE DESIGN DEPTH. SEDIMENT AND DEBRIS SO THAT IT
MATCHES DESIGN.
VEGETATION VEGETATION THAT REDUCES FREE WATER FLOWS FREELY TIiROUGiH
;MOVEMENT OF WATER THROUGH DITCHES. DITCHES.
EROSION DAMAGE SEE"PONDS"ST; DARD NO.1 SEE"PONDS"STANDARD NO. l
TO SLOPES
ROCK LINING OUT OF ;MAINTENANCE PERSON CAN SEE NATIVE REPLACE ROCKS TO DESIGN
PLACE OR MISSING SOIL BENEATH THE ROCK LINING. STANDARD.
(IF APPLICABLE)
CATCH BASINS SEE"CATCH BASINS"STANDARD NO.5 SEE"CATCH BASINS"STANDARD NO.
5
DEBRIS BARRIER E.G. SEE"DEBRIS BARRIERS"STANDARD NO,6 SEE"DEBRIS BARRIERS"STANDARD
TRASH RACK NO.6
14
i .,
� _ _ _ _
r ._
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES.
GROUNDS (LANDSCAPING)
MAINTENANC.'E DEFE(:''r CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCE IS MAINTENANCE IS PERFORMED
NEEDED
WEEDS WEEDS GROWING IN WEEDS PRESENT IN LESS THAN 5%OF
(NONPOISONOUS) MORE THAN 2Mo OF THE THE LANDSCAPED AREA.
LAND-SCAPED AREA
(TREES AND SHRUBS
ONLY).
GENERAL
SAFETY"IIA7.ARD ANY PRESENCE OF POISON NO POISONOUS VEGETATION PRESENT IN
IVY OR OTHER POISONOUS A LANDSCAPED AREA.
VEGETATION.
TRASH OR Ln-rER PAPER CAN,BOTTLES. AREA CLEAR OF LITTER.
TOTALING MORE THAN I
CUBIC FOOT WITHIN A
L:NDSCAPED.AREA
(TREES.AND SHRUBS
ONLY)OF 1,000 SQUARE
FEET.
DAALAGE LIMBS OR PARTS OF TREES TREES AND SHRUBS WITH LESS TIIAN 5%
OR SHRUBS THAT ARF, OF THE TOTAL FOLIAGE WITH SPLIT OR
SPLIT OR BROKEN WHICH BROKEN LIMBS.
AFFECT MORE THAN 25%
OF THE TOTAL FOLIAGE
OF THE TREE OR SHRUB.
TREES AND
SHRUBS
TREES OR SHRUBS THAT TREE OR SHRUB IN PLACE FREE OF
HAVE BEEN BLOWN DOWN INJURY.
OR KNOCKED OVER.
TREES OR SHRUBS WHICH TREE OR SHRUB IN PLACE AND
ARE OT ADEQUATELY ADEQUATELY SUPPORTED;REMOVE ANY
SUPPORTED OR ARE DEAD OR DISEASED TREES.
LEANING OVER,CAUSING
EXPOSURE OF THE ROOTS.
r,
HYDRA CALCULATIONS
DEVELOPED STORM MODEL
y
.ti
f
r.
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 1
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
Status of DEFAULTS at start of run. ( * May be reset by SET)
Command file : C:\HYDRA\CMD\12636.CMD
Input units are read as USA
� * Output sent to display Brief
� * Output sent to printer Off
� * Output sent to file Brief
Paper width in inches 8.000
String to reset printer 27 51 36 18
String to set printer to compressed 17 15
String to set printer to 8 lines/inch 8 27 51 27
Name of printer Epson, FX series
Print heading at top of page True
Number of steps in hydrograph 240
Step length in minutes 10
Significant flow in hydrograph 0.000
� * Maximum plot value Selected by HYDRA
Type of hydrographic plot Compact
Sanitary flow by Peaking Factor
Delay to start of actual storm 0.00
Rational Method computations Hydrograph
SCS computations Santa Barbara
Continuous simulation computations On
� * Maximum d/D for pipe design/analysis 0.900
� * Match point position on pipe 0.00 or Invert
� * Number of allowable diam drops 999
� * Mimimum drop thru manhole : 0.000
Routing technique : Quick
� * Calculate sanitary flows : True
� * Calculate infiltration flows False
� * Calculate storm flows True
� * Calculate misc flows True
+---------------------------------------------------------
1: JOB 12636
2: TOT 1.8 (6mo=0.90 2yr=1 .8,10YR=2.75, 25yr=3.2, 100yr=3.75)
3: STE 10
4: FIL SCS 1A.INC
------START OF SUB-FILE------
1: REM SCS Type lA Distribution (100 year - 24 hour)
2: HYE 10 0.0040 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
3: 0.004 0.005 0.005 0.005 0.005 0.005 0.005 0.006 0.006 0.006 +
4: 0.006 0.006 0.006 0.007 0.007 0.007 0.007 0.007 0.007 0.0082
5: 0.0082 0.0082 0.0082 0.0082 0.0082 0.0095 0.0095 0.0095 +
6: 0.0095 0.0095 0.0095 0.0133 0.0133 0,0133 0.018 0.018 0.034 +
i
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 2
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
7: 0.054 0.027 0.018 0.0133 0.0133 0.0133 0.0088 0.0088 0.0088 +
8: 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 +
9: 0.0088 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 +
10: 0.0072 0.0072 0.0072 0.0072 0.0072 0.0057 0.0057 0.0057 +
11: 0.0057 0.0057 0.0057 0.0057 0.0057 0.0057 0.0057 0.0057 +
12: 0.0057 0.005 0.005 0.005 0.005 0.005 0.005 0.005 0.005 +
13: 0.005 0.005 0.005 0.005 0.004 0.004 0.004 0.004 0.004 +
14: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
15: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
16: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
17: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
18: 0.004 0.004 0.0006
Total in original hyetograph 0.17 Inches
Total volume rain in production hyetograph 1.80 Inches
Maximum intensity 0.59 Inches/Hr
19: RET
------ END OF SUB-FILE ------
5: PDA 0.012, 6, 1, 0.5, 2, 0.004, 60
6:
7: NEW ROAD
8: SCS 0.06, 1, 98, 68, 20, 0.005, 70 BASIN (A)
Computed concentration time 0.82 Minutes
9: PIP 150, 132.15, 132.60, 130.15, 128.15, 8
NOTE: No flow to inlet.
10: SCS 0.10, 1, 98, 68, 20, 0.005, 120 BASIN (B)'
Computed concentration time 1.41 Minutes
11: SCS 0.10, 1, 98, 68, 20, 0.005, 120 BASIN (C)
Computed concentration time 1.41 Minutes
12: SCS 0.10, 1, 98, 68, 20, 0.005 120 BASIN (D)
Computed concentration time 1.41 Minutes
13: RES 207 0/0 25/0.088 825/.083
NOTE: No flow to inlet.
14: REM CALCULATIONS BASED ON A 110' LONG TRENCH WITH A 6' BOTTOM.
15: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
16: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
17: REM RATE: (290' X 3' WIDE X 4.13IN/HR / 43200 = 0.083 CFS)
18: REM VOLUME: (290' X 3' WIDE X 2.5' HIGH X 35% = 761 CU. FT.
i
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 3
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
19: REM + 290' x PI( .33)"2 x 65% = 64 CU. FT OR 825 CU. FT. TOTAL
20: HOL ROAD
21:
22: NEW SITE
23: SCS 0.47, 1, 98, 68, 20, .003, 600 (BLDGS AND PAVED PARKING)
Computed concentration time : 9.13 Minutes
24: SCS 5.271 .95, 98, 68, 151 .003, 600 (REST OF SITE)
Computed concentration time : 12.17 Minutes
25: RES 207 0/0 85/0.67 20023/0.885
NOTE: No flow to inlet.
26: REM CALCULATIONS BASED ON A 265' LONG POND WITH A 27 ' BOTTOM.
27: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
28: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
29: REM 0.01 ' DEEP: (7029 X 4.13 / 43200 = 0.67) VOL. = 85 CU. FT.
30: REM 2.00' DEEP: (9259 X 4.13 / 43200 = 0.885) VOL. = 20023 CU. FT.
31: END
I
.,
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 4
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
------ S U M M A R Y O F A N A L Y S I S ------
Run number on command file : 34
Number of links : 3
Number of hydrographs : 46
Total sanitary population : 0
Total sanitary area : 0.00 Acres
Total storm area : 6.10 Acres
Number of pumps : 0
Number of reservoirs : 2
Number of diversion structures : 0
Number of inlets : 0
Length of new pipe : 150.00 Feet
Length of existing pipe : 0.00 Feet
Length of channel : 0.00 Feet
Length of gutter : 0.00 Feet
Length of transport units : 0.00 Feet
Length of pressure pipe : 0.00 Feet
i -
_ _ i �. . .
:i
I
�.
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 2 YEAR STORM Page 5
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.0 1.53 0.03 0
128.15 4.45 0.0 0.0 0.12
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge 0.00 0.00 0.09 0.00 0.09 0
207.00 Stored 0 0 116 0 116
Incoming 0.00 0.00 0.19 0.00 0.19
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.71 0.0'0 0.71 0
Unknown Stored 0 0 3362 0 3362
Incoming 0.00 0.00 2.16 0.00 2.16
----------------------------------------------------
Lateral length= 0 Upstream length= 0
i
:.,
.�
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 10 YEAR STORM Page 6
----------------------------------------------------------------------------
C:\HYDRA\CMD\12636.CMD 14:05 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.1 1.76 0.05 0
128.15 4.45 0.0 0.0 0.15
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge 0.00 0.00 0.09 0.00 0.09 0
207 .00 Stored 0 0 293 0 293
Incoming 0.00 0.00 0.30 0.00 0.30
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.77 0.00 0.77 0
Unknown Stored 0 0 8889 0 8889
Incoming 0.00 0.00 3.41 0.00 3.41
----------------------------------------------------
Lateral length= 0 Upstream length= 0
Y
ti
N
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 100 YEAR STORM Page 7
C:\HYDRA\CMD\12636.CMD 14:06 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.1 1.88 0.07 0
128.15 4.45 0.0 0.0 0.17
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge : 0.00 0.00 0.09 0.00 0.09 0
207 .00 Stored : 0 0 596 0 596
Incoming : 0.00 0.00 0.42 0.00 0.42
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.86 0.0'0 0.86 0
Unknown Stored 0 0 18062 0 18062
Incoming 0.00 0.00 4.74 0.00 4.74
----------------------------------------------------
Lateral length= 0 Upstream length= 0
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 6 MONTH STORM Page 8
C:\HYDRA\CMD\12636.CMD 14:07 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.0 1.15 0.01 0
128.15 4.45 0.0 0.0 0.08
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge : 0.00 0.00 0.07 0.00 0.07 0
207.00 Stored : 0 0 18 0 18
Incoming : 0.00 0.00 0.08 0.00 0.08
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert --------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.67 0.00 0.67 0
Unknown Stored 0 0 367 0 367
Incoming 0.00 0.00 0.96 0.00 0.96
-----------------------------------------------------
Lateral length= 0 Upstream length= 0
r � - ..
�:.. _
i
,,
i
�::
70
�, ,� -„t��� e•[ ,r;tit,#M a� t ak �y�,.. 1.,.,'.
i?!1•.'.?- lp
Llral ! .'.'1 } �f' ' 7l .. ��°.✓R,�»t �:' ^S�' t'j,:
�+�1•�k..i� � .�.'ftr�4a«C•.��«.`+ns 14'.' � -� ilI•�r��. �;��v�i
Bb
1
6�` 1 1•
1�'�N ` }t• tti��•I+,�g �"'' C't`T' •-.�ikc+C����D•�•y[; � Q�r s
•,S• •I i �l�='iat ,��.Y;���iar3-l�'n�:} ,r
I r . , ` . -
_ �� - .�
,��
K \
'?
T
i
��
- - .. _ ..0
DEBRIS AND OIL CONTROL SYSTEM FOR TYPE I CATCH BASINS
r 18gauge
stainless steel top
11111 Stainless steel rivets
— ----- -- - - and washers
Hydraulic bypass
16 gauge, galvanized,
k plastic coated, 1/2"xl/2"
wire mesh
` 7
__Oil selective polymer or
cellulose absorbent
„ . Trapped oil
77.
-+{r.:-s. -tins' -'t-�S�.s �''�'^ ��•.� .-.`c+i 7„
�,,;�. i •,y t`i , r, 3
_ 3 r f•�n N L�..a. r-T� s-�•�: a .,,?i<.�..�r. �i tw'fI tea..
Stainless god eyes_for lifting
+ � �/f� �/f� / J �• Oil selective polymer
of celluiose absorbent
/ / / / / / / pillow
Stainless steel rivets
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following condltions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Reqular sweeping is
recorn;-nended for enhancad absorbent performance,
(C) 1997 Aqua Treatment Systems,Inc.
i � ��
• DEBRIS AND TWO STAGE OIL CONTROL SYSTEM FOR TYPE I CATCH BASINS
18gauge LLL1 ill
stainless steel top � � �` Stainless steel rivets
and washers
Hydraulic bypass 16 gauge, galvanized,
----- _- plastic coated,
1/2"x1/2" wire mesh
f --
Oil selective polymer
or cellulose filter pillow
Oil selective,
polymer
mini boomsge
r
7.
.�. for lifting
J/; f r � �• Oil selective polymer
/ /' / / / !'• / or cellulose absorbent
pillow
l• �. +�. �. 1. �. f. �.
/' /
�• ,. / ,•'/ ,; _Stainless steel rivets _
Suggested Applications:
1. Primary stormwoter treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins ore not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Reqular sweeping is
recommended for enhanced cibsor�,ent perfcn-nonce.
u 1997 Aqua Treatment Systems,Inc.
Il
II
M
3 DEBRIS AND OIL CONTROL SYSTEM FOR CB-42 OR CB-42HBSS STEEL BASINS
18 gauge stainless
steel support funnel �v Stainless steel
rr r�rm rivets and washers
Hydraulic
�— bypass
16 gauge,galvanized,
plastic coated.
1/2"xl/2"wire mesh
Oil selective polymer Outlet
or cellulose absorbent _
440
tti •rµ .1i�fJ. :dl vw.-.
w,
ac
zg
of
9
18 gauge stainless steel support funnel
'• ' /`' Stainless steel rivets
Stainless steel pad eyes for lifting
Suggested Applications:
1. Primary stormwoter treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers,
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Reqular sweeping is
recommended for enhanced nbsorbent performance.
(C) 1997 Aqua Treatment Systems,Inc.
' SEDIMENT TRAP BASKETS FOR SELF CLEANING BASINS AND DRY WELLS 4
18 gauyge stainless steel
Stainless pad eyes _ top (removable)
#1 brass snaps 10. -- --
Hydraulic bypass ,
reinforcing 17.• —
t �
t a 10.5 gauge, galvanized,
plastic coated, 2"x2
mesh wire
t
a
30 mesh stainless basket
t a or specify
t I
i a
to outfall
--
_stainless pad —
-
for lifting
: 30 mesh stainless
steel finer or specify-
........ ......... .......... Stainless steel rivets
Suggested applications:
1. Removal of coarse sediments from stormwater under the following conditions%
a. Existing basins are self cleaning and not connected to settling vault.
b. Basin is a dry well and the objective is to prolong infiltration.
c. Area is under construction.
2. Industrial pretreatment for sanitary sewers.
Maintain yearly or as needed ic.)r sires with heavy sedimenil iouding.
CC) 1997 Aqua Tiealment systems,Inc.
r �n .. '� _ . ..
'1.
N
5 - SEDIMENT TRAP AND OIL FILTER SYSTEM FOR SELF CLEANING BASINS AND DRY WELLS
18 gauge stainless steel top
(removable) • -- -- -
Stainless pad eyes __ Hydraulic
#1 brass snaps bypass
Double wire reinforcing
10.5 gouge, galvanized. - f
plastic coated, 2"x2"
wire mesh '
Qi[iselective polymer
or cellulose filter sock
Oil selective polymer
or cellulose filter pillow
to outfall
Stainless steel pad
eyes for lifting
_ Wire spacer
i �---
��— , Stainless steel rivets
-�-- —-- Oil selective filter. ilp low_
�,;�, _ Oil selective filter sock
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins not connected to an oil-water separator.
c, Existing catch basins not connected to a settling vault.
2. Industrial pretreatment for sanitary sewers.
Maintain monthly or until filter blinds. Note, regular sweeping is recommended for enhanced filter performance.
CC1 1997 Aqua Treatment Systems, Inc,
i
:�
i
i�
��
i ,.
. -
DEBRIS AND OIL CONTROL SYSTEM FOR TYPE II CATCH BASINS 6
Support funnel
Stainless steel _ Hydraulic bypass
rivets and washers
16 gauge, galvanized,
plastic coated 1/2"x 1/2"
wire mesh
Polymer minl-
j boom
* Trapped oil
to outfoll - , ��•�
om
MW
F.
dc-q a�ia� �-,J}(f +23i=•�5,;s`>;'r'tl�y •+� +k'�'• t 9+[y�1+
1Y i A Y 7 .rS
NAW FM
PR
Mull'AW s t y
may' �� ,c +�r �`•�'•.2 t
18 gauge stainless steel support
.. �' qjfunnel for rectangular cast iron
frames and grates or type I
catch basins with welded
steel grates.
nr 0.080" 3003-Hl4 aluminum y
support funnel for cast rings and
grates. Please call for specifications.
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or coalescing plate oil-water separators.
2. Industrial pretreatment for sanitary sewers.
Maint^in yearly or as needed with nolymer absorbent. Regular sweeping is recommended for enhanced absorbent performance.
(C; 1997 Aqua Treatment Systems,Inc.
'I
��
DEBRIS AND TWO STAGE OIL CONTROL SYSTEM FOR TYPE II CATCH BASINS
Support funnel
Hydraulic� _ $IaiNeSS sleet
bypass rivets and washers
• icy raulrc�y(�055
Tee section 16 aouae.gglvonized,
Filter cell plastic coated, 1/2'xl/2'
wire mesh
r Oil selective
r polymer
m.iry Loco,
Trapped al
to outfoll
- qi
Nx ON
d��+:�'' �%' :.z
}Y� ;x�a-�ri}'`• .ice` >�.?;'ta ..Arr�f s �•-
�tiC - `� *s•r-�
Stainless steel screws_
...
Pad eye,cord and hook /- 0.080"3003-H 14 \
.4 for securing top pan �:�: •� •I i, r otumrnum Dons �
�• Lifting Cable or Corrrbeaner
16 gouge,goNianized.
FV1 Ai { + plastic coated. 1/2'kl/2' 1r 1 i`- J.
Y) Yt wire mesh
Stainless steel wire cloth !�j.'r1 .r i
or plastic media netting
r Oil selective polymer
Stainless steel
or cellulose absorbent ��,�
rivets and washers
filter
Stainless steel support
pins or screws Filter cell plan view
PVC pipe stub
(optional)
Suggested Applications; Filter cell sectional view
1, Primary stormwater treatment for redevelopment and small site devolopment under the following conditions;
a. Physical constraints or cost prohibits the use of bio•swales or coalescing plate oil-water separators.
2. Industrial pretreatment for sanitary sewers.
Maintain yearly with polymer or cellulose absorbent. Note, confined space entry is required to install and maintain this system.
Specify oversize ring and grate or frame and grate for cell installation and removal. Special order item
C; 1997Aqua Treatment Systems, Inc,
-46
SAMPLE SPECIFICATION
8
Basket charged with melt blown polypropylene net bag absorbent
for CB42 OIL CB42-HBSS steel catch basins
18 gouge stainless ►
steel support runnel gym,••- 3/16'SS rivets and
3/16'k 3/4.55 woshe(s
Hydraulic IQ —
bypass
16 gouge.golvanrzed,
Pros Ti c—oted. X
wire mesh
—► r �— v —► re m•
CO selective polymer
a Cellulose obso(bent > s
sr y
Engineer specify minimum
funnel opening. Minimum
distances between basket
walls catch basin walls
should be specified as
needed for hydraulic bypass.
28• — -----------►
♦
Q"
I
�— e' —► Engineer specify minimum -- 12' ►
--- ....-_. _ ► 4
hydraulic bypass cut-outs
.o
Anti-floatation cords ,
I I i: required for polypropylene
absorbents
6"xl 6"x2l melt blown polypropylene spaghetti net bag
! •/•f 1 Clean basket and replace absorbent minimum once per year.
i'�f /'�i Quarterly absorbent replacement recommended.
.� �
� (C) 1997 Aqua Treatment Systems, Inc.
Gullywashe(R
h
.t.
9
GullywasherT Geotexfiile Catch Basin Inserts jV
SEDIMENT CONTROL FOR CONSTRUCTION SITES AND INDUSTRIAL YARDS
18 gouge stainless
♦— steel support funnel
+�stainless steel bolts Easy to Install - One Person!
and wing nuts. Remove the catch basin grate. Place
Stainless
support funnel on the grating ledge,
28" steel plates �j. _ Replace the catch basin grating. Support
a Hydraulic bypass
(approximately 14 funnel prevents grate, workers and fully
square inches per side loaded inserts from falling into the catch
,•:'.::»�. 28 square inches total) basin during change out,
N
Easy to Maintain- One Person!
'► ll •`� Inserts can be removed, emptied, and
reinstalled in a matter of minutes! No need
/7- Double stitching to disassemble, simply empty the insert
through the top of the funnel. Back flush if
Non woven needle punched desired and place back in catch basin.
polypropylene geotextile
Easy to Assemble - One Person
Place funnel on the ground, bolt side up,
Stainless Remove wing nuts and plates. Center insert
steel support boot over funnel, Cut slits in geotextile
funnel where bolts protrude and slide geotextile ove
the bolts, Replace plates and tighten wing
Fs♦ `+ >; 'l nuts pinching the fabric between support Stainless funnel bottom and steel plates. Trim extra
_> ' ' "'`- • = - � material as desired or leave and trim after
`.� r y .�:.` -�� a- : welded
Lifting �z� , ,� replacing grate to create a positive seal.
Strap
Stainless Durable
' steel Insert filters are manufactured
lifting with 8 ounce nonwoven needle
pad eyes punched polypropylene geotextile and
Support funnels available in standard and custom sizes, double stitched for lasting quality,
Use with Gullywasher geotextile replacement inserts. Support funnels are fabricated with
Pre-trimmed filters with precut bolt holes available to fit your top! 18 gauge stainless steel.
(minimum order required) Reusable
Gullywasher inserts can be used again and
again. Simply replace the geotextile as
Geotextile Specifications desired.
Inexpensive
Property Test Method MARV Tired of paying too much? Call your local
Aqua Treatment System's dealer and ask
for Gullywasher inserts.
Grab Tensile,lbs, ASMT D 4632 200
Grab Elongation % ASTM D 4632 60 Distributed by:
Mullen Burst, psi ASTM D 3786 400
Trapezoid Tecr, Ibs, ASTN1 D 4533 80
Puncture, Ibs, ASTM D 4833 120
U 1997 Aqua Treatment Systems,Inc
- .�
,. r
.�+ -
' _ :�
I
I
$�
y.f 10
,.Gullywasher(R) Geotexfiile Catch Basin Inserts •: ��.
Oil AND SEDIMENT CONTROL FOR INDUSTRIAL YARDS AND PARKING LOTS N.
A _ 18 au a stainless
f steel support funnel
Stainless steel bolts Easy to Install - One Person!
Stainless and wing nuts. Remove the catch basin grate. Place
steel plates i; support funnel on the grating ledge.
Hydraulic bypass
28„ Trapped ;. r (approximately 14 Replace the catch basin grating. Support
Oil li =`•`. square inches per side funnel prevents grate, workers and fully
j 28 square inches total) loaded inserts from falling into the catch
Oil `: G• basin during change out.
absorbent
pillow Easy to Maintain- One Person!
Inserts can be removed, emptied, and
reinstalled in a matter of minutes! No need
��-Double stitching to disassemble, simply empty the insert
/ through the top of the funnel. Back flush if
Non woven needle punched desired and place back in catch basin.
polypropylene geotextile
Easy to Assemble - One Person!
! Place funnel on the ground, bolt side up.
Remove wing nuts and plates. Center insert
Stainless steel support boot over funnel. Cut slits in geotextile
to funnel where bolts protrude and slide geotextile over
I.j the bolts, Replace plates and tighten wing
-. .� •� ' .Y' Y LF
_ ,;;�:: ,,.„•__,.., :€ nuts pinching the fabric between support
Stainless funnel bottom and steel plates. Trim extra
p _ a��, 0� ' - material as desired or leave and'trim after
- --slbbl bolts
Lifting welded replacing grate to create a positive seal.
Strap
Stainless Durable
' 0 steel Insert filters are manufactured
lifting with 8 ounce nonwoven needle
pad eyes punched polypropylene geotextile and
double stitched for lasting quality,
Support funnels available in standard and custom sizes. Support funnels are fabricated with
Use with Gullywosher geotextile replacement inserts. pp
Pre-trimmed filters with precut bolt holes available to fit your topl 18 gauge stainless steel.
(minimum order required) Reusable
Gullywasher inserts can be used again and
again, Simply replace geotextile with
Geotextile Specifications absorbent as desired.
Inexpensive
Property Test Method MARV Tired of paying too much? Call your local
Aqua Treatment System's dealer and ask
for Gullywasher inserts.
Grab Tensile,lbs. ASMT D 4632 200
Grab Elongation % ASTM D 4632 60 Distributed by;
Mullen Burst, psi ASTM D 3786 400
Trcpezoid Tear, lbs. ASTM D 4533 80
Puncture, lbs. ASTM D 4833 120
!� 1997 Aqua Treatment Systems,Inc.
_,
1
�•
_ .�...1
'•i>r1►•:-a• � ♦'•;fit►'`•'!:t.•.,... .4...�y Q""�'.:S•a`,�,'' �"'."''•q +. •"�.J'•.. •�� _
ti `v �..a•t....• 'a+1t;.•�•11.• .'••t%;Ri .,; Fig.-'4, w ,.' .i.�+.r_�.•
�t..w•wV�`,y'w�ti C'rrf�-r� l,t�'"i'°�+ <1.,.v,f •. !�" /t�cwi,y�� �� .�+ ;., a.•�... ► _-,n •.N. .,
�.t!•4"'"• r >. .t. '"''•�� 'i'%'�.��''.ti`�y; .'! t6�iy`..,•_.t�.:-5 `..,
.•- %r r `r.,•... •s}N a,�t L - +:: ?� r..:t.. ,.{n"*„f: t,,' yip•a. -.4" :.^
•. " *r • 'Y�' or4j lit"• �tJ4^"�' + + .,�•' —: 1, v
ay,n i..yt�a ~ (:Sr' ys•. •YFr�wY;"`=b`' + 'tom - i. • • • - • • - •
t'Z. ••l"06V41�1,
Mot `'r ;l' tom.. �'►tA.
15
N RAPOW
.�• 'y< �tyr�'•` �< ,•����>.• .?+�� i�i ,ten c�-rr� ►.�, •-- • • •• • ••- •
*�=r r" ► + Iry �r? ^ } 3��r, It ►. t �.
Nt
.��� 7^•s .J7.• �'�,'.••^'}+`7ai�77`, 'a t;•` ,y�,a�'�:�aisRC;t"�, ��w' � • • - • • •-•
��t' .• .L"•:� � �' .1•",�j '�' c`'i\:r' `V. �� 's��<;•'�L .•�:'C:i�' .�Li��,�h� • • •
-�.y,. ,f4 • • •• • • • •- •
i - J t •�j.` ,Y� � 3 -•,.'ate
O
1
�v
1
1
-r
� ��
t - i^�`\'�01t'l.�t t�tY� �q '��.t41••"•,tct..
�w 4t!y5:�.u6!:..s1�.^'tY':`•^-. •) �� �,.�•tyrM�! �t4'Y"`•�lY1.• ttv;Y �`"1,�'•�`4v
i.*"' i.hr. 4•ri',,ryK�l�w�iT���'q v`t�;,��-r ljaT`�'£':�
k,F =�.���t' 'c+'•'�S=ia.tt t�,%,i�'��`�rS�t��f'Yl`'rY,�r� .�' • — —• —• ••— —
FA•C"�t F .. �.�;;�t,ry�l„•.,`-
.mow t` J'I tt. ••^� .sr'.' •�
��` - r�r�$�_�•2r�wa�rt r••• 1s_ i..w `ram� �—�l �t Y' I ,��a�r�:�� •^ _ -1• • • — — —
a cif �_ Y'[ "^� �V.,�,.�.A+• �:t-♦ Y •• • •
^JN� Ia t •—• — — — •• •
t tr r •.� � r z .�� i 'siy� +•t-' �?_�, at vY� x ry? ` • • ••• • — •• •
� .�{"� Ysr'� •'� r� '�'.ts�:����- ' ii�.",vryF e: f'� �; j :i i•i
mot• -N�• + »,,� et -,. '•
Isla�-
���•�y�?� �.C �,L Lam,v.•�s r • • • • •— •
MH
WIWI
�J�i. +r'� [ '.xCs.y� v t - ,, a.; 4„t'j: �.�.r y8• K�i� C '• ,•� >� —
sh�+•.•�`y� �i;t••'f I����t,�C:y"•�.�-o'TJh} i 1'r'x�fyii}��'a�f�Jik�gJixiF�y. •t,�t�i�,,���b.� ••— • •• •
�e��`t-,��,' �K►i��a"±'��b/Z�t'�v^tuy'1<S P�,C��(�+k�t�'�i.�"J.���.!l;�-��,�y'ti�-�•�'.ji:t;�.-.,yet"a
-r a' 4�'i t'4�..I Ct ��tyJ•�i t �two-�if�� '7..1�ry�i,�. -s+l� � v v�1`r ;
r r � f'�+t�� Yr ~;Y•I.'_T�t{ ,�'.rk:{1��:„��'�f�"1��'t�••��".:����5:".%:^"
•f x•�-,,r.: ci:iiii?i?::i�ii:iei� �.-�.
v;
r
' �."' '"'
_�. . .�
..
I
I
1 ••
l
1
� u - -- ..
' 13
Gullywasherg Stormwater Funnel
The Gullywashers Stormwater Funnel
is a quick and easy-to-install erosion
11/ control device. Simply place the
' funnel where breakthrough occurs
in silt fence, at the top of slopes
where channeling occurs, and
other areas where there is a need
to divert runoff to a lower elevation
• _, ti �, and avoid erosion.
To assemble, cut a short piece of
6 corrugated plastic pipe, Slit the
RIVAlJw:Si
ar a� �`, yrt' end of the pipe stub a few inches
i'v4�-�':1�G:•�Vr ...�•...aa»..:3.4-+'F.7..s.triAM e:v�l ' \�►D.�4 a�S �•
and sleeve it through the hole in
the back of the funnel. Connect to
ire+. x`�N.•, `.?`t 6 extension pipe with standard fittings
�eKr and smaller diameter extension pipe
�'� ' +' '' '. ? •" ` with reducers.
The funnel is installed with 12" spikes
and porfland cement. Excavate an
area slightly larger than the footprint
of the funnel, loosen soil, mix thoroughly
with 5-10 pounds of portland cement,
T- ' _ -►;,. '` press the funnel in place, and drive the
spikes through the pre-drilled holes.
tea,.•r {` .;,. :�
Pack the soil around the sides of the
funnel and dust with porfland cement.
The soil cement will harden, adhere to
the spikes and prevent wash out.
Specifications
!� ).M 1 C• 5.; �5`ral4 • 4 `ip�'r.r:..ti.''wIIR'_-"�/ �y,�T—�•.��, F~ •S�
Mft
Material, molded polyethylene
Wall Thickness: 1/8"
r r�,• ; :: Weight: 4 pounds
Pipe hole diamter: 6"
Spike hole diameter: 3/8"
-4 14•
Ogj
.•i•.•M10,
.
l iC' r• --GTG.1 •i :a....,v_'.deV .i%', ♦ 1
7 �
UC1997 Aqua Treatment Systems, Inc.
i
1
.. �. - .
�'
J
�.
l
Gullywasher�Small Scale Oil-Water Separator 14
• TREAT COMPRESSOR CONDENSATE u.
• FILTER OILY MOP WATER ' = x�., t
• FILTER OILY BILGE WATER '
CLEAN UP OIL SPILLS
• REMOVE OIL FROM ANTIFREEZE
• PRETREAT INDUSTRIAL WASTEWATER
• PROCESS CONTAMINATED SUMP WATER
The Gullywasher2small scale oil-water separator is an easy-to-use funnel which makes cleaning
up messy oil-water mixtures a snap! Simply fill the funnel with the completely safe, non-toxic
absorbent and place over a 5 gallon bucket. Pour your oil-water mixtures into the top of the
funnel. The cellulose allows water to pass through freely while removing oils. Use the absorbent
material until a sheen can be seen on top of the filtered water, then simply replace the spent
absorbent with new material, pack firmly, and continue filtering. The small-scale oil water
separator uses reclaimed cellulose fibers,a pulp and paper manufacturing by-product. Utilizing
capillary action, the sorbent draws liquids deep within the fibers where they cannot leach out.
The fibers are clean, light weight, and dust free.
Drdlea ride
gaHem --- •
' op;�, � After use, the spent absorbent may be placed in
an approved landfill or burned in approved low-
<
Type I funnel
temperature boilers, cement kilns, asphalt plants
= - for 5 gallon and industrial processing facilities reclaiming
buckets energy from the oil and cellulose that would
have otherwise been discarded.
Note the cellulose will not remove emulsified oils.
12'
For emulsified oils and hard to remove sheens,
try our unique carbon-polymer blend. Use the
30M cellulose to reduce the bulk of the oils then
' filter the residue water through the carbon-
;sC` �= Type II funnel
for 55 gallon polymer of mer blend. If sheens persist, place carbon-
closed top polymer blend and residue water in a 5 gallon
A"� p drums
bucket and let soak overnight. Pour the entire
contents back through the empty funnel to
remove the carbon-polymer blend for further use.
The Gullywasherosmall scale oil-water separtor
can be stacked for use with both filter mediums,
*— — Place the cellulose in the top funnel for gross
reduction of hydrocarbons and place the carbon-
>; �:x; polymer blend in the bottom flannel for removal
1,';. slaclungnng of sheens and emulsified oils,
�C1 1997 Aqua flealmenl Syslems,Inc.
;�
�.
�� L
�,
I
t
15' Small-Scale Water Treatment Systems
System Components: REUSE
Single-Ste treatment system for removal of oil, 1.Treatment Tank(fittings Included)
sediment, heavy metals, PCBs, etc. from water, 2.High-Shear Mixer(120V)
3, Sludge Dewatering Unit YOUR
4.Treated Water Filter
5. 50 Pounds Treatment Powder
6.Tank Stand WATER!
Miter/
350gallon Treatment Instructions: ELIMINATE
mWng lank 1.Fill treatment tank
2.Start mixer and add treatment
powder(mix 5 minutes) WASTEWATER
3.Stop mixer and let settle(30 min.)
4.Decant water for reuse
5.Drain sludge to drying bed DISCHARGE!
F�tet
Sluage Dewafenng Crean water Discharge
Surrp Purrp
REDUCE INJURIES SAVE TIME
"L T
The Gullywashel'Jergonomic grate
puller is ideal for heavy or large
slotted grates. It can reduce the
Y y , risk of injury and in some cases
C eliminate the need for equipment
, and multiple personnel required for
�zt -.� ��•� A � � ,�� .Pr
storm drain grate removal.
aft .^ �_. .1. _. A �.iy5 ti7..ri'`�f�Q.'{!�F•.t. �M �i.'.ly
`���,.r ,`T .r '' `�''' -• ; '•. - �1 Try our standard grate puller.
It has a grip for both hands unlike
-l0110. conventional pullers.
54
30' 27"
7"
♦ ♦ 5"
AQUA TREATMENT SYSTEMS,INC.WARRANTS ITS PRODUCTS TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP. AQUA TREATMENT
SYSTEMS, INC. MAKES NO WARRANTIES, EITHER EXPRESS OR IMPLIED,WITH RESPECT TO ITS PRODUCTS INCLUDING THEIR PERFORMANCE,
MERCHANTABIILITY.OR FITNESS FOR A PARTICULAR PURPOSE. USE AQUA TREATMENT SYSTEMS,INC.PRODUCTS IN CONJUNCTION WITH STRINGENT
MAINTENANCE PLANNING,TRAFFIC CONTROL AND SAFETY PLANNING.AND POLLUTION PREVENTION PLANNING. AQUA TREATMENT SYSTEMS,INC.
PRODUCTS ARE NOT INTENDED FOR USE AS THE EXCLUSIVE MEANS OF REDUCING THE AMOUNT OF POLLUTANTS ENTERING THE ENVIRONMENT.
PURCHASERS AND USERS OF AQUA TREATMENT SYSTEMS, INC.PRODUCTS ARE SOLELY RESPONSIBLE FOR COMPLIANCE WITH LOCAL, STATE.AND
FEDERAL LAWS GOVERNING THE DISCHARGE AND DISPOSAL OF FILTERED WATER,TREATED WATER,SPENT ABSORBENT MEDIA,AND GENERATED SLUDGE.
PURCHASERS SOLE REMEDY WILL BE REPLACEMENT OF AQUA TREATMENT SYSTEMS, INC. PRODUCTS. IN NO EVENT WILL AQUA TREATMENT SYSTEMS, INC.
BE LIABLE FOR ANY LOST PROFITS,CONSEQUENTIAL OR SPECIAL DAMAGES. QC)1997 Aqua Treatment Systems, Inc.
I
I
ti
i
M1. .
G ull ywash erti:
Stormwater, Wastewater, and Erosion Control Products
yi
�h�arYn r,� L9c �6
Ditch Dam Pages 11 - 12 Stormwater Funnel Page 13
-nix wft)rM 11•v fin n lu n n rr LZI-u
1
A�y�
Wire Catch Basin Inserts Pages 1 8
Geotextile Catch Basin Inserts
Pages 9- 10
i -
Oil-Water Separator Page 14 Ergonomic Grate Puller Page 15
M
PRODUCT OVERVIEW AND SELECTION GUIDE
Aqua Treatment Systems,Inc. Phone(206)343-52
3200 Occidental Avenue South Fax(206)343-8504
Seattle,Washington 98134
Gullywashe(V is a registered trademark of Aqua Treatment Systems,Inc.
DEBRIS AND OIL CONTROL SYSTEM FOR TYPE I CATCH BASINS '
w•
' 18 gauge
stainless steel top
Stainless steel rivets
i -- and washers
X. Hydraulic bypass
a -
16 gauge, galvanized,
plastic coated, 1/2"xl/2"
wire mesh
Oil selective polymer or
cellulose absorbent
Trapped oil
Stainless pad eves
for lifting
Oil selective polymer
or/ !` ceilL-lose absorbent
• % % / % /• pillow
♦' ♦ /- /' / /' /' ♦'
• /� / /, / � / ,// Stainless steel rivets
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a, Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2, industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent, Regular sweeping is
recommended for enhanced absorbent performance.
CU 1997 Aqua Treatment Systems,Inc.
2
DEBRIS AND TWO STAGE OIL CONTROL SYSTEM FOR TYPE I CATCH BASINS
18 gauge 711
stainless steel top Y Stainless steel rivets
and washers
Hydraulic bypass 16 gauge, galvanized,
plastic coated,
1/2"xl/2" wire mesh
Oil selective polymer
_ - - or cellulose filter pillow
Oil selective ;}
.- -
polymer
mini booms
^..~W..�.1 ��:a'i.ri...f.7.�.."�`i H't4Y�.Gl.�a..4ST�sG✓ZwCv��y.r
_-Stainless pad-ems_- .
for lifting.
/ J J ! J f J f Oil selective polymer
�� or cellulose absorbent
/* pillow
f f J / f/ •� -f ,•% Stainless steel rivets
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Regular sweeping is
recoimrnenu-ed for enhanced absofbent pertoi i orlce,
u 1997 Aqua Treatment Systems,Inc.
3 DEBRIS AND OIL CONTROL SYSTEM FOR CB-42 OR CB-42HBSS STEEL BASINS
18 gauge stainless
steel support funnel r �m Stainless steel
rivets and washers
_ Hydraulic
bypass
16 gauge,galvanized,
plastic coated, •
1/2"xl/2"wire mesh
Oil selective polymer Outlet
or cellulose absorbent 0.
ti
18 gauge stainless steel support funnel
Stainless steel rivets
Stainless steel pad eyes for lifting
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Requlor sweeping is
recommended for enhanced absorbent performance.
(C) 1997 Aqua Treatment Systems,Inc.
SEDIMENT TRAP BASKETS FOR SELF CLEANING BASINS AND DRY WELLS 4
Stainless pad eyes 18 gauyge stainless steel
_ .._ top (removable)
#1 brass snaps
DmbAwke- Hydraulic bypass
reinforcing
10.5 gauge, galvanized,
plastic coated, 2"x2
I mesh wire
�I
{ 30 mesh stainless basket
T.
or specify
k :I
I �I
to outfall
Stainless pad eyes
for lifting
V.
:: :.;...... .::::: - .
•::-.: 30 mesh stainless
: :::!..... steel liner or specify
Stainless steel rivets
Suggested applications:
1. Removal of coarse sediments from stormwater under the following conditions:.
a. Existing basins are self cleaning and not connected to settling vault,
b. Basin is a dry well and the objective is to prolong infiltration.
c. Area is under construction,
2. Industrial pretreatment for sanitary sewers.
Maintain yearly or as needed for sites with heavy sediment loading.
CC 1997 Aqua Treatment Systems,Inc.
5 SEDIMENT TRAP AND OIL FILTER SYSTEM FOR SELF CLEANING BASINS AND DRY WELLS
18 gauge stainless steel top
(removable)_- -_..-~
Stainless pad eyes 4
#1 brass snaps .4 Hydraulic
-- -- � bypass
Double wire reinforcing — —
10,5 gauge, galvanized, L. _
plastic coated, 2"x2" ` `
wire meshrz
f
oil selective polymer ! .. 14 !
or cellulose filter sock
Oil selective polymer
or cellulose filter pillow
x•
to outfall
t:
r:.
Stainless steel pad
eyes for lifting
i'
Wire spacer
Stainless steel rivets
Oil selective filt r- ilp low
Oil selective filter sock
!' !' i i i
Suggested Applications:
1, Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins not connected to an oil-water separator.
c, Existing catch basins not connected to a settling vault.
2. Industrial pretreatment for sanitary sewers.
Maintain monthly or until filter blinds. Note, regular sweeping is recommended for enhanced filter performance.
L� 1997 Aqua Treatment Systems, Inc.
DEBRIS AND OIL CONTROL SYSTEM FOR TYPE II CATCH BASINS 6
Support funnel
Stainless steel -4
Hydraulic bypass
rivets and washers
16 gauge, galvanized,
plastic coated 1/2"xl/2"
wire mesh
4111
Polymer mini-
-boom
` / Trapped oil
to outfall
a
18 gauge stainless steel support
funnel for rectangular cast iron
r frames and grates or type I ♦ r. ,
catch basins with welded
steel grates. ' '
1
1
1�
0.080" 3003-H14 aluminum
support funnel for cast rings and
grates. Please call for specifications.
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or coalescing plate oil-water separators.
2. Industrial pretreatment for sanitary sewers.
Maintain yearly or as needed with polymer nbsorbent, Regular sweeping is recommended for enhanced absorbent performance,
(C) 1997 Aqua Treatment Systems, Inc.
DEBRIS AND TWO STAGE OIL CONTROL SYSTEM FOR TYPE II CATCH BASINS
im Support funnel
Hydraulic r Stainless steel
bypass rivets and washers
rout c bypass
Tee section it 16 a__ge ag Ivanized,
filter cell plastic coated, 1/2"xl/2"
wife mesh
Oil selective
polymer
mini boom _
Trapped oil
to outfoll
.StanIpSS stP.P.I srfew,S
Pod eye,cord and hook j- 0.080"3003-Hl4
for securing top pan e'/' fill1 1� � all l
Uftina cable or carribeaner
16 gouge,galvanized, /_ ,/•
plastic coated. 1/2'xl/2' r l !
wife mesh
Stainless steel wire cloth /- f
or plastic media netting
i Oil selective polymer
•�-
21 ._ Stainless steel
or cellulose absorbent
_ filter rivets and washers
Stainless steel support
pins or screws Filter cell plan view
PVC plpe stub
(optional)
Suggested Applications; Filter cell sectional view
1, Primary stormwater treatment for redevelopment and small site devolopment under the following conditions;
a. Physical constraints or cost prohibits the use of bio-swales or coalescing plate oil-water separators,
2. Industrial pretreatment for sanitary sewers,
Maintain yearly with polymer or cellulose absorbent. Note, confined space entry is required to install and maintain this system.
Specify oversize ring and grate or frame and grate for cell installation and removal. Special order item
�C) 1997Aqua Treatment Systems, Inc.
SAMPLE SPECIFICATION 8
Basket charged with melt blown polypropylene net bag absorbent
for CB42 OR CB42-HBSS steel catch basins
18 gauge stainless
steel support funnel mr► rrrr ,n 3/16"SS rivets and
3%16"x 3/4"SS washers
Hydaullc I r
16 gauge,galvanized, bypass
plastic coo07
l
wire mesh
--► 3• -4— v —► 7e
16'
Oil selective polymer
or cellulose absorbent 2
Engineer specify minimum
funnel opening. Minimum
distances between basket
walls catch basin walls
should be specified as
needed for hydraulic bypass.
Q"
I
. j
'I
Q8. Engineer specify minimumIT A
f hydraulic bypass cut-outs -►
T. 18
Anti-floatation cords ,
required for polypropylene
absorbents '
tor
r
- 18" — -- ►
6"xl6"x21" melt blown polypropylene spaghetti net bag
f�•' -f�•f, ' f f ,r Clean basket and replace absorbent minimum once per year.
r' i� i' i' i Quarterly absorbent replacement recommended,
Gullywasher R1 <C) 1997 Aqua Treatment Systems, Inc.
9 �, .
Gullywasher(R,' Geotextile Catch Basin Inserts ;
SEDIMENT CONTROL FOR CONSTRUCTION SITES AND INDUSTRIAL YARDS
18 gauge stainless
~ steel support funnel
��_ Stainless steel bolts Easy to Install - One Person!
jand wing nuts. Remove the catch basin grate. Place
Stainless i support funnel on the grating ledge.
28" steel plates �i Replace the catch basin grating. Support
'• Hydraulic bypass
(approximately 14 funnel prevents grate, workers and fully
square inches per side loaded inserts from falling into the catch
28 square inches total) basin during change out,
Easy to Maintain- One Person!
Inserts can be removed, emptied, and
reinstalled in a matter of minutes! No need
Double stitching to disassemble, simply empty the insert
through the top of the funnel. Back flush if
Non woven needle punched ` desired and place back in catch basin,
polypropylene geotextile /
� Easy to Assemble - One Person
Place funnel on the ground, bolt side up,
Stainless
Remove wing nuts and plates. Center insert
steel support boot over funnel, Cut slits in geotextile
funnel where bolts protrude and slide geotextile ove
I the bolts, Replace plates and tighten wing
nuts pinching the fabric between support
Stainless funnel bottom and steel plates. Trim extra
�
steel bolts� _ ,�• 0-4 - material as desired or leave and trim after
Lifting ; welded replacing grate to crentr= a poslt!vP sPnl.
Strap -- -
Stainless Durable
' C 0 steel Insert filters are manufactured
lifting with 8 ounce nonwoven needle
pad eyes punched polypropylene geotextile and
Support funnels available in standard and custom sizes. double stitched for lasting quality.
Use with Gullywasher geotextile replacement inserts. Support funnels are fabricated with
Pre-trimmed filters with precut bolt holes available to fit your top! 18 gauge stainless steel,
(minimum order required) Reusable
Gullywasher inserts can be used again and
again, Simply replace the geotextile as
Geotextile Specifications desired.
Inexpensive
Property Test Method MARV Tired of paying too much? Call your local
Aqua Treatment System's dealer and ask
for Gullywasher inserts.
Grab Tensile,lbs• ASMT D 4632 200 _
Grab Elongation % ASTM D 4632 60 UIStrI�UteC1 by
Mullen Burst, psi ASTM D 3786 400
Trapezoid Tear, Ibs. ASTM D 4533 80
Puncture, Ibs. ASTM D 4833 120
U 1997 Aqua Treatment Systems, Inc.
10
Gullywasher(R) Geotextile Catch Basin Inserts
Oil AND SEDIMENT CONTROL FOR INDUSTRIAL YARDS AND PARKING LOTS
h�tiw
_ 18 gauge stainless
steel support funnel
Stainless steel bolts Easy to Install - One Person!
Stainless "
steel plates and wing nuts. Remove the catch basin grate, Place
j ► support funnel on the grating ledge,
Hydraulic bypass
28„ Trapped _- (approximately 14 Replace the catch basin grating, Support
Oil �• i� square inches per side funnel prevents grate, workers and fully
�. i 28 square inches total)
Oil !� ; loaded inserts from falling into the catch
absorbent I!_ � basin during change out.
pillow Easy to Maintain- One Person!
V- Inserts can be removed, emptied, and
reinstalled in a matter of minutes! No need
` Double stitching to disassemble, simply empty the insert
through the top of the funnel. Back flush if
Non woven needle punched desired and place back in catch basin,
polypropylene geotextile
Easy to Assemble - One Person!
f Place funnel on the ground, bolt side up.
Stainless Remove wing nuts and plates. Center insert
steel support boot over funnel. Cut slits in geotextile
funnel where bolts protrude and slide geotextile over
the bolts. Replace plates and tighten wing
nuts pinching the fabric between support
funnel bottom and steel
Stainless plates. Trim extra
- steel bolts material as desired or leave and trim after
Lifting _ welded replacing grate to create a positive seal.
Strop
Stainless Durable
p p I steel Insert filters are manufactured
lifting with 8 ounce nonwoven needle
pad eyes punched polypropylene geotextile and
Support funnels available in standard and custom sizes. double stitched for lasting quality.
Use with Gullywasher geotextile replacement inserts. Support funnels are fabricated with
Pre-trimmed filters with precut bolt holes available to fit your top! 18 gauge stainless steel,
(minimum order required) Reusable
Gullywasher inserts can be used again and
again. Simply replace geotextile with
Geotextile Specifications absorbent as desired,
Inexpensive
Property Test Method MARV Tired of paying too much? Call your local
Aqua Treatment System's dealer and ask
Grab Tensile,lbs, ASMT D 4632 200 for Gullywasher inserts.
Grab Elongation % ASTM D 4632 60 Distributed by:
Mullen Burst, psi ASTM D 3786 400
Trapezoid Tear. lbs. ASTM D 4533 80
Puncture, Ibs, ASTM D 4833 120
,C, 1997 Aqua Treatment Systems, Inc
•,,� °bS.a'^-y 'GtaC{x �„��.,;2��1�,` N+�;a.�!.".,-sa \•,,�^ Z{. ,-� 4� ;- • —
i-+. ?�tL�' e�yyyst�*'i � ,,2� ..r i r:�.l•.e.;,;ti, � '' t -• •i� -+tur;.. • � �•
r �.�
'GV' h R a�.� 4•t4�'+6*F�,.�1tv,�-,• fr:'..1� d. �i.{f
a, .JF.��z �•'�IF�r � � rn _ 1 \'9�+'. .?�'tiyyy����`•N �, 1 r
.ter 1 ., R .i, A .. ..: T,y( "`'?•rY • • •• — —•• — —
!,�q,���(':�k�: d.a._� r 1 .7�< 4�a.'•iSty�+l'l, v�:t'�1`},� -
t+yY f ^r q
�yr ~i' :.,!wry r ..Ne. s v � - '�e�a-- � • •• • • —
_ -. .•J y�*A�iar a i1f�i•• - � 1"-,i
�pf ♦Tt r- �_ • • • • • •
�, ^�. ,::.ri+a�!J. ��\fir= •1 - - •• • • • ••
ra.
41'Vl"•`�•Y ,��.. �t • .•�413 k"�' A,•i �,ro �G`F•f — •—• — — • • •
w�{�e,Y•�� r �!•� '•� �t�i� .K�i,.��' �'- S 1. ....� — • •• • • — —
1���. tea• �C•� •-�w 2, '!'�`�-_?a- - •• - •• • - •• • -•
' aApmr t ",.
lb
i may,, • • •• •— —
Q.
's�i.'i' 1r,T���: ��; �Hy +}�c' `�w.:FQ�7ldfiv,>••. 1 d*►4"/ a• Y +4I�� •;�'C••
�.1�� -`�,.� COS -.. `.' '�•,�. • •— •— —• —
� Sri��i. - vSCf �>!• •_. ♦ �F'"_�•• .taa..,`Y.- • • • • •—•
b�• mot• ,5'f,.�' ` -y��tf���'y�; � �.�`Yy'�� • • • - • • •• •
_.� T- 4. „ r �Y7 nf77•S
12
�:;.• :' GullywasherO Ditch Dams
are easily linked together
;.., . ,y1� for wide span applications.
t ,}.M, �� w,•1.1 T.•� Ofkg.
Simply overlap the wire and
Is, ".� fi �� _` � .. geotextile, then hog ring
56 along the top and bottom,
Overlap the wire portion of
t the ditch dam b" to 12"•
For greater strength,
increase the overlap area
L � ANY - 7�♦,75�4'�in
1• and apply more hog rings,
Gullwasher-11'Ditch Dams
are easily transported,
Rpw*
K�r•.: They take up much less
4!w•-rn�I L ti� ,
z `" ? Y;i. ;,> � ' •. space than straw bales,
_h, -fix _ are light weight, and
can be stacked in a
variety of ways, If you
have a difficult to access
site, this product is for you!
GulywasherO Ditch Dams
'- come in two types, type V
a for V ditches and type T for
trapezoidal ditches,
24 ► -
AvadatNe in nonwoven needle
Geotextile ` 4—' - punched polypropylene or woven
polypropylene geotextile•
Wire mesh ! A \�\ Specify preference.
nut
Flow control point 1'M"14 page steel wire mesh or
. ` 1/2'kl/ •16 gauge steel wire mesh.
54' -► Available in plain steel,galvanized,
�- or galvanized and plastic coated.
Elevation view of type-V ditch dam Elevation view of type-V ditch dam Plan view of type-V
ditch dam layed flat
---------------------- toe' - ---------'--'► , 1oa• --------11,
----- 72' - — ► -
24' ,'L1Lt;ek:°ter ,�f"1i1�
-. _ _ _ �-,:, ♦ -.}'tijin:El rEIU,n fit'i L�L!Lgl:ill
Elevation view of type-T ditch dam Elevation view of lype-T ditch dam Plan view of type-T
ditch dam loved flat
(C)1997 Aqua Treatment Systems,Inc.
13
� .:_ r rY
Gullywasher Stormwater Funnel
►' ,r-- The Gullywasherg Stormwater Funn
} ; r � :•tQ : m is a quick and easy-to-install erosio n
control device. Simply place the
funnel where breakthrough occurs
rt,.# in silt fence, at the top of slopes
where channeling occurs, and
other areas where there is a need
to divert runoff to a lower elevation
and avoid erosion.
M ,tt.• ,� t.. •- a
To assemble, cut a short piece of
6" corrugated plastic pipe. Slit the
end of the pipe stub a few inches
and sleeve it through the hole in
the back of the funnel. Connect to
?��'" ,: w ' � •� _ �1 6" extension pipe with standard fittin
and smaller diameter extension pipe s
. w�-_ " rr �:' _.`, i ,j% :, •t .;r zI with reducers.
RM
At-
' ..
�, � • r � ,4 ,����a . >� �:.;� t The funnel is installed with 12" spikes
; ��yam- a 73 � and portland cement. Excavate an
��"_o� y'Y"r�t� ++ r.
area slightly larger than the footprint
of the funnel, loosen soil, mix thorough
with 5-10 pounds of porfland cement,
press the funnel in place, and drive the
spikes through the pre-drilled holes.
Pack the soil around the sides of the
funnel and dust with porfland cement.
ter = Ir. ;,r ,,-�'- � �rz� ;. .• The soil cement will harden, adhere to
the spikes and prevent wash out.
Specifications
Material: molded polyethylene
Wall Thickness: 1/8"
Weight: 4 pounds
Pipe hole diamter: 6"
4 Spike hole diameter: 3/8"
14•12
►
/f
CJ1997 Aqua Treatment Systems, Inc. •
C'oullywasheraSmall Scale Oil-Water Separator 14
A �\
• TREAT COMPRESSOR CONDENSATE
•,I%
• FILTER OILY MOP WATER
• FILTER OILY BILGE WATER •��:` • �� �: + s;,r.
r
• CLEAN UP OIL SPILLS ><r
• REMOVE OIL FROM ANTIFREEZE .
• PRETREAT INDUSTRIAL WASTEWATER
• PROCESS CONTAMINATED SUMP WATER
The Gullywashe0small scale oil-water separator is an easy-to-use funnel which makes cleaning
up messy,oil-water mixtures a snap! Simply fill the funnel with the completely safe, non-toxic
absorbent and place over a 5 gallon bucket, Pour your oil-water mixtures into the top of the
funnel. The cellulose allows water to pass through freely while removing oils, Use the absorbent
material until a sheen can be seen on top of the filtered water, then simply replace the spent
absorbent with new material, pack firmly, and continue filtering. The small-scale oil water
separator uses reclaimed cellulose fibers, a pulp and paper manufacturing by-product. Utilizing
capillary action, the sorbent draws liquids deep within the fibers where they cannot leach out.
The fibers are clean, light weight, and dust free.
Drilled hole
pattern
`•..e (screens �-
>` optional) After use, the spent absorbent may be placed in
Molded an approved landfill or burned in approved low-
..:•% .,! Polyelhylene temperature boilers, cement kilns, asphalt plants
bucket ! Type I funnel
funnel for 5 gallon and industrial processing facilities reclaiming
buckets energy from the oil and cellulose that would
have otherwise been discarded,
� I a' ►
Note the cellulose will not remove emulsified oils.
121 k For emulsified oils and hard to remove sheens,
Ir try our unique carbon-polymer blend. Use the
i - spin v 0IIHng inn
30 mean skinless cellulose to reduce the bulk of the oils then
Heel screen
Type II funnel filter the residue water through the carbon-
`Y for 55 gallon polymer blend. If sheens persist, place carbon-
-
' closed top polymer blend and residue water in a 5 gallon
drums bucket and let soak overnight. Pour the entire
contents back through the empty funnel to
remove the carbon-polymer blend for further use.
The Gullywasher®R small scale oil-water separtor
can be stacked for use with both filter mediums.
�_ �— — Place the cellulose in the top funnel for gross
• reduction of hydrocarbons and place the carbon-
h fir reM0Vcl
polI ymer blend in the bottom funnel
Slacking ringto rrsi 31 S
of sheens and emulsified oils.
�J 1997 Aqua irealmenl Systems,Inc,
15 Small-Scale Water Treatment Systems
System Components; REUS
Shale-Step treatment system for removal of oil, 1.Treatment Tank(fittings Included)
sediment, heavy metals, PCBs, etc. from water. 2. High-Shear Mixer(120V)
3•Sludge Dewatering Unit YOUF;�
4.Treated Water Filter
5.50 Pounds Treatment Powder
b,Tank Stand WATE ll-;� i
Mixer�
350 gallon Treatment Instructions;
mixing tank 1• Fill treatment tank E LI M I N,,-"T
2.Start mixer and add treatment
powder(mix 5 minutes)
3. Stop mixer and let settle(30 min,) WASTEW,/\TE,R
4. Decant water for reuse
5,Drain sludge to drying bed
DISCHARGE t
Finer
[Sludge Dewalenng Oeon Woler Disctalge
Sump Pump
REDUCE INJURIES SAVE TIME
The Gullywashe�R'ergonomic grates
b �. puller is ideal for heavy or large
` slotted grates. It can reduce the
risk of injury and in some cases
eliminate the need for equipment
r `- and multiple personnel required for
storm drain grate removal.
r rti Try our standard grate puller.
It has a grip for both hands unlike
'r f J� 10_► conventional pullers.
I
,�- 30, 1
27
7; t
AQUA TREATMENT SYSTEMS, INC.WARRANTS ITS PRODUCTS TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP AQUA TREATMENT f
SYSTEMS, INC. MAKES NO WARRANTIES, EITHER EXPRESS OR IMPLIED,WITH RESPECT TO ITS PRODUCTS INCLUDING THEIR PERFORMANCE,
MERCHANTABIILITY,OR FITNESS FOR A PARTICULAR PURPOSE. USE AQUA TREATMENT SYSTEMS, INC.PRODUCTS IN CONJUNCTION WITH STRINGENT
MAINTENANCE PLANNING, TRAFFIC CONTROL AND SAFETY PLANNING,AND POLLUTION PREVENTION PLANNING. AQUA TREATMENT SYSTEMS, INC.
PRODUCTS ARE NOT INTENDED FOR USE AS THE EXCLUSIVE MEANS OF REDUCING THE AMOUNT OF POLLUTANTS ENTERING THE ENVIRONMENT.
PURCHASERS AND USERS OF AQUA TREATMENT SYSTEMS, INC.PRODUCTS ARE SOLELY RESPONSIBLE FOR COMPLIANCE WITH LOCAL, STATE,AND
FEDERAL LAWS GOVERNING THE DISCHARGE AND DISPOSAL OF FILTERED WATER,TREATED WATER,SPENT ABSORBENT MEDIA,AND GENERATED SLUDGE,
PURCHASERS SOLE REMEDY WILL BE REPLACEMENT OF AQUA TREATMENT SYSTEMS, INC.PRODUCTS. IN NO EVENT WILL AQUA TREATMENT SYSTEMS,INC,
BE LIABLE FOR ANY LOST PROFITS, CONSEQUENTIAL OR SPECIAL DAMAGES. O1997 Aqua Treatment Systems, Inc.
ASCADE SU RVEYE NG Surveyors
161
ENGINEERING, IINEI
ARLINGTON,WA
Engineers
102 E Division•PO Box 326 98223 +,
(360)435-5551 •(360)652-7572 _
FAX(360)435-4012 Planners
HECL, vED
FEB 8 1999
DRAINAGE CALCULATP&PF ARLINGTON
FOR
CEMENT DISTRIBUTORS, INC. J
(REVISED 1-28-99)
The proposal is to sheet flow all storm water to the South end of the project site
and route the storm water through bio-swales and then into an infiltration pond sized for
the 6 month storm. Larger storms will flood the bio-swales and the parking lot but will
not leave the site.
The bio-swales are designed to take the storm water from half the site, maintain a
residence time of more than 300 seconds, and a depth of less than three inches. This
resulted in the bio-swales being 7 feet wide with 3:1 side slopes and at a grade of 1.0%.
The residence time is 370 seconds and the depth is 2.76 inches.
The infiltration pond was sized to hold the 6 month storm to allow for the
maximum use of the bio-swales. The pond bottom area was established at 1800 square
feet (150'xl2') and an elevation of 1.0 feet below the ends of the bio-swales.
With 3 to 1 side slopes and a depth of 1.0 feet, the infiltration area at half the
wetted perimeter would be 2295 square feet (153 x 15) and the storage volume available
would be 2295 cubic feet before backing up into the bio-swales. Based on a 6 month,
T1A storm, the storage volume required would be 2240 cubic feet. The infiltration rate
was based on 4.13 inches per hour which is what the D.O.E. recominends for the soils that
exist on this site.
►'Z K F. 7p 1'
O� pF Ayr
0 7�
� a
,0 12 16
SS�nNAL
EXPIRES 12/23/
x
t•,
1
,j
Cg5=ade Surveying and Engineering, Inc. HYDRA Version 5 .12
p,=lington, Washington Page 1
C : \HYDRA\CMD\12636DV1.CMD 15 :36 27-Jan-99
Status of DEFAULTS at start of run . ( * May be reset by SET)
Command file : C: \HYDRA\CMD\12636DV1 .CMD
Input units are read as : USA
* Output sent to display : Brief
* Output sent to printer : Brief
* Output sent to file Off
Paper width in inches 8 . 000
String to reset printer 27 38 108 54 68 27 40 115 49 48 72
String to set printer to compressed : 17 .16 27 38 107 48 56 72
String to set printer to 8 lines/inch 8 27 38 108 56 68
Name of printer Hewlett-Packard, LaserJet/LaserJet
Print heading at top of page True
Number of steps in hydrograph 200
Step length in minutes 10
Significant flow in hydrograph 0 . 005
* Maximum plot value Selected by HYDRA
Type of hydrographic plot Compact
Sanitary flow by Diurnal Curve
Delay to start of actual storm 0 . 00
Rational Method computations Off
SCS computations Santa Barbara
Continuous simulation computations On
* Maximum d/D for pipe design/analysis : 0 . 900
* Match point position on pipe : 0 . 00 or Invert
* Number of allowable diam drops : 999
* Mimimum drop thru manhole : 0 . 000
Routing technique : Quick
* Calculate sanitary flows False
* Calculate infiltration flows True
* Calculate storm flows True
* Calculate misc flows False
+-- - - - - - - --- - - - - - --- - -- - - - - - - - - ---- -- - - --- -- - - - -- --- - - -- - -- - - - - - - - - - -
1: JOB 12636
2 : TOT 0 . 9 (6mo=0 . 90 2yr=1. 8, 10YR=2 . 75, 25yr=3 .2, 100yr=3 . 75)
3 : STE 10
4 : FIL SCS_1A. INC
------START OF SUB-FILE------
1 : REM SCS Type lA Distribution (100 year - 24 hour)
2 : HYE 10 0 . 0040 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
3 : 0 . 004 0 . 005 0 . 005 0 .005 0 . 005 0 . 005 0 . 005 0 . 006 0 . 006 0 . 006 +
4 : 0 . 006 0 . 006 0 . 006 0 . 007 0 . 007 0 . 007 0 . 007 0 . 007 0 . 007 0 . 0082
5 : 0 . 0082 0 . 0082 0 . 0082 0 . 0082 0 . 0082 0 . 0095 0 . 0095 0 . 0095 +
6 : 0 . 0095 0 . 0095 0 . 0095 0 . 0133 0 . 0133 0 . 0133 0 . 018 0 . 018 0 . 034 +
� �j - .�
M
III
C HYDRA Version 5 .12ascade Surveying and Engineering, Inc . Page 2
Arlington, Washington
15 :36 27-Jan-99
C: \HYDRA\CMD\12636DV1 .CMD
7 : 0 . 054 0 . 027 0 . 018 0 . 0133 0 . 0133 0 . 0133 0 . 0088 0 . 0088 0 . 0088 +
8 : 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 +
9 : 0 . 0088 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 +
10 : 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0057 0 . 0057 0 . 0057 +
11 : 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 +
12 : 0 . 0057 0 . 005 0 . 005 0 . 005 0 . 005 0 . 005 0 . 005 0 . 005 0 .005 +
13 : 0 . 005 0 . 005 0 . 005 0 . 005 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
14 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
15 • 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
16 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 .004 0 . 004 0 . 004 +
17 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
18 • 0 . 004 0 . 004 0 . 0006 0 .17 Inches
Total in original hyetograph
Total volume rain in production hyetograph 0 . 90 Inches
Maximum intensity 0 .29 Inches/Hr
19 : RET
--- - END OF SUB-FILE ------
5 : PDA 0 . 012, 6, 1, 0 .5 , 2, 0 . 004, 60
6 : NEW W-SITE
7 : SCS 2 . 87, . 95 , 98, 68, 15, . 003 , 600 (1/2 SITE AS PAVED)
Computed concentration time : 12 .17 Minutes
8 : CHA 100, 129 .50, 128 .50 , .2, 3 , 7, 3 (BIOSWALE @ 1 . 0%)
NOTE: No flow to inlet .
9 : HOL W-SITE
10 : NEW E-SITE
11: SCS 2 . 87, . 95 , 98, 68 , 15, 003 , 600 (1/2 SITE AS PAVED)
Computed concentration time 12 .17 Minutes
12 : CHA 100, 129 .50, 128 .50, .2, 3 , 7 , 3 (BIOSWALE @ 1. 0%)
NOTE : No flow to inlet .
13 : REC W-SITE
14 : RES 127 .50 0/0 40/0 .219 10000/0 .220 (INFILTRATION POND)
15 : REM NOTE: A 100 ' LONG BIOSWALE @ 1. 09.; GIVES THE REQUIRED
16 : REM RESIDENCE TIME OF 300 SECONDS FOR A FLOW OF 0 .5 CFS
17 : REM CALCULATIONS ARE BASED ON A TWO 100 ' LONG, BY 71WIDE SWALES
18 : REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4 .13 in/hr
19 : REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
20 : REM 2295 X 4 . 13 / 43200 = 0 .219 CFS THIS IS A POND AREA OF 2295 SQ.FT
21 : REM AT HALF THE WETTED PERIMETER (153*15) OR A BOTTOM AREA OF 1800 SQ
FT
22 : REM WITH 3 TO 1 SIDE SLOPES
�v.
Cascade Surveying and Engineering, Inc. HYDRA Version 5 .12
Arlington, Washington Page 4
C: \HYDRA\CMD\12636DV1 .CMD 15 :36 27-Jan-99
- - - - - - S U M M A R Y O F A N A L Y S I S - - - - - -
Run number on command file 7
Number of links 3
Number of hydrographs 38
Total sanitary population 0
Total sanitary area 0 . 00 Acres
Total storm area 5 .74 Acres
Number of pumps 0
Number of reservoirs 1
Number of diversion structures 0
Number of inlets 0
Length of new pipe : 0 . 00 Feet
Length of existing pipe : 0 . 00 Feet
Length of channel : 200 . 00 Feet
Length of gutter : 0 . 00 Feet
Length of transport units : 0 . 00 Feet
Length of pressure pipe 0 . 00 Feet
f
Cascade Surveying and Engineering, Inc. HYDRA Version 5 .12
Arlington, Washington Page 3
C: \HYDRA\CMD\12636DV1 .CMD 15 :36 27-Jan-99
23 : END
s
- - r. � _
L
x
.�
I
Cascade Surveying and Engineering, Inc . -,—HYDRA Version 5 . 12
Arlington, Washington Page 1
C: \HYDRA\CMD\12636DV1.CMD ALP 15 :36 27-Jan-99
iKV 12636 / ►` ,
***
SITE- �/V Channel
W /
i
Ditch Shape Invert Surface Width San Sto Flow Cost
Link Loz�tg Lft/Ctr/Rht Slope Up/Dn Up/Dn epth Inf Mis el
1 �100/ 3 . 00 3� 00 0 . 010 129 .50 129 .73 0 214 214 0
7 . 00 128 .50 128 . 73 0 .23 0 0 0 .27
----------- ----------------- - - - -----
Lateral length= 100 Upstream length= 100 '*** E-SITE Channel
Ditch Shape Invert Surface Width San Sto Flow Cost
Link Long Lft/Ctr/Rht Slope Up/Dn Up/Dn Depth Inf Mis Vel
2 100 3 . 00 3 . 00 0 . 0100 129 .50 129 . 73 8 .4 0 214 214 0
7 . 00 128 .50 128 .73 0 .23 0 0 0 .27
*** E-SITE Reservoir
Invert ------------- - Maximum Flow Values - - - - ----- - - - -- - - -
Link Up/Dn San Inf Sto Mis Design Cost
3 128 .50 Di s ge - 0 0 98 0 8—�_ 0
127 .50 Store 0 0 2240 0 - 2240� \�
In 0 0 401 0 401
-- - - - - - - - - -- - - - - - - - - - - - - - - - -- - - - - - - - - - - -- - - - -- - -----
Lateral length= 100 Upstream length= 200
L
_ ' a
L
i�
F
Christopher Young
From: Chris Tauzin <christ@spdtrucking.com>
Sent: Tuesday, July 09, 2013 2:37 PM
To: Christopher Young
Cc: Amy Rusko; Launa Peterson; Paul Ellis _ p ���
Subject: RE: SPD Expansion 2013 �� �CJI
Cement Distributors
17501 5910 Avenue NE y —C
Arlington, WA 98223 i� D(A --
Parcel#: 31052200401700
Built: 1999
I will contact Launa or Amy to schedule a meeting right away.
Thank you again for your help.
Chris Tauzin
Special Projects Manager
Smokey Point Distributing, Inc.
17305 59tn Ave NE
Arlington, WA 98223
425-508-3959
360-925-3023 Fax
From: Christopher Young [mailto:cyoung@arlingtonwa.gov]
Sent: Tuesday, July 09, 2013 2:22 PM
To: Chris Tauzin
Cc: Amy Rusko; Launa Peterson; Paul Ellis
Subject: RE: SPD Expansion 2013
Chris—please provide me with the legal address of this property and I will forward to the appropriate people to compile
any information. Also, I recommend a General Information Meeting,which would provide you with a lot of
information. If you would like to take advantage of this free service please let Amy or Launa know and they can
schedule you in. We could have the documentation available during that meeting if you schedule out a few weeks.
Thanks,
Christopher Young
Building Official
City of Arlington
360-403-3432
cVoung arlingtonwa.gov
"The importance of a strong building code is most evident after a disaster."
1
t
:�
' I
I
r
From: Chris Tauzin [ma i Ito:christ@spdtrucking.com]
Sent: Tuesday, July 09, 2013 1:44 PM
To: Christopher Young
Subject: SPD Expansion 2013
Chris,
We are purchasing the 5 acre property North of us from Cement Distributors. With this I would like to get whatever
public records I can get my hands on to make sure our vision of how this will play out and will it work or not.
Can you please direct me to any plans, drawings or documents that I can get copies of or who to talk to?
If there is any drawings on the pond between us is going to be a key factor.
I would also like to talk to you about our big picture plan for the future (next couple years) of removing all these small
mobile offices and creating one corporate office.
Thank you for your assistance.
Chris Tauzin
Special Projects Manager
Smokey Point Distributing, Inc,
17305 59th Ave NE
Arlington, WA 98223
425-508-3959
360-925-3023 Fax
2
M
}.
CASCADE SUF�►rEY1NG Surveyors
& ENGINEERING, INC.
Engineers
ARLINGTON,WA
y
102 E Division-PO Box 326 98223
(360)435-5551 -(360)652-7572 - Planners
FAX(360)435-4012
CALCULATIONS SUPPLEMENT
INFILTRATION TRENCHES:
Three infiltration trenches were designed for the flow off the two buildings. The three trenches are all 2' high and are to be
installed at a bottom depth of about 5 to 5/12 feet. Since soils work performed on this site on February 6, 1998 indicate
brown sandy loams(to 2' deep)overlaying gravelly medium sands with a water table encountered at between 7' to 9' down,
the proposal is to construct the infiltration trenches in the medium sands over 1' above the water table.
Calculations for sizing the the three trenches were performed using Hydra storm modeling software,by Pizer, Inc. The SCS
method with a type 1-A storm was used to calculate flows. The trenches were sized to contain a 100 Year storm event. The
infiltration rate used in the calculations is 4.13 in/hr which is half the recommended DOE rate for sand. The trenches are
not designed for water quality treatment since they are handling rooftop and footing drainage only. The catchbasins are to
have solid metal lids to prevent stormwater from the parking areas from entering the trench system
Trench#1 is sized to handle the office building(2468 sq.ft.). The hydra calculations(see attached)indicate the 62' long
by 3' wide by 2' high trench will fill with 119 cu.ft out of a possible 130 cu. ft. during the 100 year storm event.
Trench#2 is sized to handle the West half of t} liop building(4872 sq. ft.)The hydra calculations(see attached)indicate
the 92' long by 3.25' wide by 2' high trencl will fiI I with 201 cu.ft out of a possible 209 cu. ft. during the 100 year storm
event.
Trench#3 is sized to handle the East half of the shop building(2616 sq.ft.)The hydra calculations(see attached)indicate
the 92' long by 2.0'wide by 2'high trench will fill with 106 cu.ft out of a possible 128 cu. ft. during the 100 year storm
event.
l
1$
oF! WA O
y� 0
,0 12 16 4
0� F'I
I
f' CEIVE Al-
EXPIRES 121231
" 1 1998
CITY OF ARLINGTON
.,
I
I
r
HYDRA CALCULATIONS
DEVELOPED STORM MODEL
Supplemental Trench Calculations
r
I
I
Casgade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 1
C:\HYDRA\CMD\12636SUP.CMD 9:09 1-Jun-98
Status of DEFAULTS at start of run. ( * May be reset by SET)
I
Command file : C:\HYDRA\CMD\12636SUP.CMD
Input units are read as USA
I* Output sent to display Brief
I * Output sent to printer Off
I * Output sent to file Brief
Paper width in inches 8.000
String to reset printer : 27 51 36 18
String to set printer to compressed : 17 15
String to set printer to 8 lines/inch : 8 27 51 27
I Name of printer : Epson, FX series
I Print heading at top of page : True
I
Number of steps in hydrograph 240
I Step length in minutes 10
I Significant flow in hydrograph 0.000
I * Maximum plot value Selected by HYDRA
I Type of hydrographic plot Compact
I
Sanitary flow by Peaking Factor
Delay to start of actual storm : 0.00
I Rational Method computations : Hydrograph
SCS computations : Santa Barbara
Continuous simulation computations : On
I
I * Maximum d/D for pipe design/analysis : 0.900
I * Match point position on pipe : 0.00 or Invert
I * Number of allowable diam drops : 999
I* Mimimum drop thru manhole : 0.000
Routing technique : Quick
I
I * Calculate sanitary flows : True
I * Calculate infiltration flows : False
i* Calculate storm flows : True
I * Calculate misc flows : True
I
+--------------------------------------------------------------------
1: JOB 12636
2: TOT 3.75 (6mo=0.90 2yr=1. 8,10YR=2.75, 25yr=3.2, 100yr=3.75)
3: STE 10
4: FIL SCS_1A.INC
------START OF SUB-FILE------
1: REM SCS Type lA Distribution (100 year - 24 hour)
2: HYE 10 0.0040 0.004 0.004 0.004 0.004 0. 004 0.004 0. 004 0. 004 +
3: 0.004 0. 005 0.005 0.005 0.005 0.005 0.005 0.006 0.006 0.006 +
4: 0.006 0.006 0.006 0.007 0.007 0.007 0. 007 0.007 0.007 0.0082
5: 0.0082 0.0082 0.0082 0.0082 0.0082 0.0095 0.0095 0.0095 +
6: 0.0095 0.0095 0.0095 0.0133 0.0133 0.0133 0.018 0.018 0.034 +
�1
r
1
I
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Page
Arlington, Washington
---------------------
C:\HYDRA\CMD\12636SUP.CMD 9:09 1-Jun-98
7: 0.054 0.027 0.018 0.0133 0.0133 0.0133 0.0088 0.0088 0.0088 +
8: 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 +
9: 0.0088 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 +
10: 0.0072 0.0072 0.0072 0.0072 0.0072 0.0057 0.0057 0.0057 +
11: 0.0057 0.0057 0. 0057 0.0057 0.0057 0.0057 0.0057 0.0057 +
12: 0.0057 0.005 0.005 0.005 0.005 0.005 0.005 0.005 0.005 + {
13: 0.005 0.005 0.005 0.005 0. 004 0.004 0.004 0.004 0.004 +
14: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
15: 0.004 0.004 0.004 0.004 0.004 0. 004 0.004 0.004 0.004 +
16: 0. 004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
17: 0. 004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
18: 0.004 0.004 0.0006
Total in original hyetograph 0.17 Inches
Total volume rain in production hyetograph 3.75 Inches
Maximum intensity 1.22 Inches/Hr
19: RET
------ END OF ,SUB-FILE ------
5: PDA 0.012, 6, 1, 0.5, 2, 0.004, 60
6:
7: NEW OFF-BLDG
8: SCS 0. 06, 1, 98, 68, 20, .003, 50 (Office BLDG)
Computed concentration time 0.76 Minutes
9: RES 129 0/0 40/.016 126/0.016 500/.016 (INFILTRATION trench)
NOTE: No flow to inlet.
10: REM CALCULATIONS BASED ON A 62' LONG TRENCH WITH A 3' BOTTOM.
11: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
12: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
13: REM RATE DEEP: (62' X 3' X 4.13 IN/HR / 43200 = 0.018 CFS) .
14: REM VOLUME: (62' X 3' WIDE X 2' HIGH X 35%) VOL. = 130 CU. FT.
15: HOL OFF-BLDG
16:
17: NEW SHOP-WEST
18: SCS 0.11, 1, 98, 68, 20, .003, 50 (Office BLDG)
Computed concentration time : 0.76 Minutes
19: RES 129 0/0 50/.029 209/0.029 500/.029 (INFILTRATION trench)
NOTE: No flow to inlet.
20: REM CALCULATIONS BASED ON A 92' LONG TRENCH WITH A 3.25' BOTTOM.
21: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
22: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
23: REM RATE DEEP: (92' X 3.25' X 4.13 IN/HR / 43200 = 0.029 CFS) .
24: REM VOLUME: (92' X 3.25' WIDE X 2' HIGH X 35%) VOL. = 209 CU. FT.
25: HOL SHOP-WEST
26:
I'
r
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 3
C:\HYDRA\CMD\12636SUP.CMD 9:09 1-Jun-98
27:
28: NEW SHOP-EAST
29: SCS 0.06, 1, 98, 68, 20, .003, 50 (Office BLDG)
Computed concentration time : 0.76 Minutes
30: RES 129 0/0 40/.018 128/0.018 500/.018 (INFILTRATION trench)
NOTE: No flow to inlet.
31: REM CALCULATIONS BASED ON A 92' LONG TRENCH WITH A 2' BOTTOM.
32: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
33: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
34: REM RATE DEEP: (92' X 2' X 4.13 IN/HR / 43200 = 0.018 CFS) .
35: REM VOLUME: (92' X 2' WIDE X 2' HIGH X 35%) VOL. = 128 CU. FT.
36: HOL SHOP-EAST
37:
38:
39:
40: END
i
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 4
C:\HYDRA\CMD\12636SUP.CMD 9:09 1-Jun-98
------ S U M M A R Y O F A N A L Y S I S ------
Run number on command file : 11
Number of links : 3
Number of hydrographs : 53
Total sanitary population : 0
Total sanitary area : 0.00 Acres
Total storm area : 0.23 Acres
Number of pumps : 0
Number of reservoirs : 3
Number of diversion structures : 0
Number of inlets : 0
Length of new pipe : 0.00 Feet
Length of existing pipe : 0.00 Feet
Length of channel : 0.00 Feet
Length of gutter : 0.00 Feet
Length of transport units : 0.00 Feet
Length of pressure pipe : 0.00 Feet
/� 'S'
r
I
I
Casr_ade Surveying and Engineering, Inc. HYDRA Version 5. 12
Arlington, Washington 100 Year Storm Page 5
C:\HYDRA\CMD\12636SUP.CMD 9:09 1-Jun-98
12636
*** OFF-BLDG Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
1 Unknown Discharge : 0.00 0.00 0.02 0.00 0.02 0
Unknown Stored : 0 0 119 0 119
Incoming : 0.00 0.00 0.07 0.00 0.07
----------------------------------------------------
Lateral length= 0 Upstream length= 0
*** SHOP-WEST Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 Unknown Discharge : 0.00 0.00 0.03 0.00 0.03 0
Unknown Stored : 0 0 201 0 201
Incoming : 0.00 . 0.00 0.13 0.00 0.13
----------------------------------------------------
Lateral length= 0 Upstream length= 0
*** SHOP-EAST Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0. 00 0.00 0.02 0.00 0.02 0
Unknown Stored 0 0 106 0 106
Incoming 0. 00 0.00 0.07 0.00 0.07
----------------------------------------------------
Lateral length= 0 Upstream length= 0
;: y
I
t
I
I
'Y•YF �
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
Engineers
ARLINGTON,WA
102 E Division-PO Box 326 98223 `.
(360)435-5551 -(360)652-7572 - Planners
FAX(360)435-4012
DRAINAGE CALCULATIONS
FOR
CEMENT DISTRIBUTORS, INC.
(REVISED 1-28-99)
The proposal is to sheet flow all storm water to the South end of the project site
and route the storm water through bio-swales and then into an infiltration pond sized for
the 6 month storm. Larger storms will flood the bio-swales and the parking lot but will
not leave the site.
The bio-swales are designed to take the storm water from half the site, maintain a
residence time of more than 300 seconds, and a depth of less than three inches. This
resulted in the bio-swales being 7 feet wide with 3:1 side slopes and at a grade of 1.0%.
The residence time is 370 seconds and the depth is 2.76 inches.
The infiltration pond was sized to hold the 6 month storm to allow for the
maximum use of the bio-swales. The pond bottom area was established at 1800 square
feet (I50'xl2') and an elevation of 1.0 feet below the ends of the bio-swales.
With 3 to 1 side slopes and a depth of 1.0 feet, the infiltration area at half the
wetted perimeter would be 2295 square feet (153 x 15) and the storage volume available
would be 2295 cubic feet before backing up into the bio-swales. Based on a 6 month,
T 1 A storm, the storage volume required would be 2240 cubic feet. The infiltration rate
was based on 4.13 inches per hour which is what the D.O.E. recommends for the soils that
exist on this site.
12 1
FSS/ONAL �G
EXPIRES 12123/
i
�4
Cascade Surveying and Engineering, Inc . HYDRA Version 5 .12
Arlington, Washington
Page
C: \HYDRA\CMD\12636DV1 .CMD 15 :36 27-Jan-99
Status of DEFAULTS at start of run. ( * May be reset by SET)
Command file : C: \HYDRA\CMD\12636DV1 .CMD
Input units are read as USA
* Output sent to display Brief
* Output sent to printer Brief
* Output sent to file Off
Paper width in inches 8 . 000
String to reset printer 27 38 108 54 68 27 40 115 49 48 72
String to set printer to compressed 17 .16 27 38 107 48 56 72
String to set printer to 8 lines/inch 8 27 38 108 56 68
Name of printer Hewlett-Packard, LaserJet/LaserJet
Print heading at top of page True
Number of steps in hydrograph 200
Step length in minutes 10
Significant flow in hydrograph 0 . 005
* Maximum plot value Selected by HYDRA
Type of hydrographic plot Compact
Sanitary flow by Diurnal Curve
Delay to start of actual storm 0 . 00
Rational Method computations Off
SCS computations Santa Barbara
Continuous simulation computations On
* Maximum d/D for pipe design/analysis 0 . 900
* Match point position on pipe 0 . 00 or Invert
* Number of allowable diam drops 999
* Mimimum drop thru manhole 0 . 000
Routing technique Quick
* Calculate sanitary flows False
* Calculate infiltration flows : True
* Calculate storm flows : True
* Calculate misc flows : False
- - -- - -- -- -- - -- -- - -- - - - -- - - ---- - --- -- - - - - ---- - -
1: JOB 12636
2 : TOT 0 . 9 (6mo=0 . 90 2yr=1 . 8, 10YR=2 . 75, 25yr=3 .2, 100yr=3 . 75)
3 : STE 10
4 : FIL SCS_1A. INC
--- --START OF SUB-FILE-----
1: REM SCS Type lA Distribution (100 year - 24 hour)
2 : HYE 10 0 . 0040 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
3 : 0 . 004 0 . 005 0 . 005 0 . 005 0 . 005 0 . 005 0 . 005 0 . 006 0 . 006 0 . 006 +
4 : 0 . 006 0 . 006 0 . 006 0 . 007 0 . 007 0 . 007 0 . 007 0 . 007 0 . 007 0 . 0082
5 : 0 . 0082 0 . 0082 0 . 0082 0 . 0082 0 . 0082 0 . 0095 0 . 0095 0 . 0095 +
6 : 0 . 0095 0 . 0095 0 . 0095 0 . 0133 0 . 0133 0 . 0133 0 . 018 0 . 018 0 . 034 +
'L
,.
I
I
I
I�
Cascade Surveying and Engineering, Inc . HYDRA Version 5 .12
Arlington, Washington
Page=====
C: \HYDRA\CMD\12636DV1.CMD 15 :36 27-Jan-99
7 : 0 . 054 0 . 027 0 . 018 0 . 0133 0 . 0133 0 . 0133 0 . 0088 0 . 0088 0 . 0088 +
8 : 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 0 . 0088 +
9 : 0 . 0088 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 +
10 : 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0072 0 . 0057 0 . 0057 0 . 0057 +
11: 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 0 . 0057 +
12 : 0 . 0057 0 . 005 0 . 005 0 . 005 0 . 005 0 .005 0 . 005 0 . 005 0 . 005 +
13 : 0 . 005 0 . 005 0 . 005 0 . 005 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
14 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
15 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
16 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
17 : 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 0 . 004 +
18 : 0 . 004 0 . 004 0 . 0006
Total in original hyetograph : 0 .17 Inches
Total volume rain in production hyetograph : 0 . 90 Inches
Maximum intensity : 0 .29 Inches/Hr
19 : RET
------ END OF SUB-FILE ------
5 : PDA 0 . 012, 6, 1, 0 .5, 2, 0 . 004, 60
6 : NEW W-SITE
7 : SCS 2 .87, . 95 , 98, 68, 15 , . 003 , 600 (1/2 SITE AS PAVED)
Computed concentration time : 12 .17 Minutes
8 : CHA 100, 129 .50, 128 .50, .2, 3 , 7, 3 (BIOSWALE @ 1 . 0%)
NOTE: No flow to inlet.
9 : HOL W-SITE
10 : NEW E-SITE
11 : SCS 2 . 87, . 95 , 98, 68 , 15 , . 003 , 600 (1/2 SITE AS PAVED)
Computed concentration time : 12 .17 Minutes
12 : CHA 100, 129 .50, 128 .50, .2, 3 , 7, 3 (BIOSWALE @ 1 . 0%)
NOTE: No flow to inlet.
13 : REC W-SITE
14 : RES 127 .50 0/0 40/0 .219 10000/0 .220 (INFILTRATION POND)
15 : REM NOTE: A 100 ' LONG BIOSWALE @ 1. 0% GIVES THE REQUIRED
16 : REM RESIDENCE TIME OF 300 SECONDS FOR A FLOW OF 0 .5 CFS
17 : REM CALCULATIONS ARE BASED ON A TWO 100 ' LONG, BY 7 'WIDE SWALES
18 : REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4 . 13 in/hr
19 : REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
20 : REM 2295 X 4 . 13 / 43200 = 0 .219 'CFS THIS IS A POND AREA OF 2295 SQ.FT
21: REM AT HALF THE WETTED PERIMETER (153*15) OR A BOTTOM AREA OF 1800 SQ
FT
22 : REM WITH 3 TO 1 SIDE SLOPES
i
i
M
1
A'
Cascade Surveying and Engineering, Inc. HYDRA Version 5 .12
Arlington, Washington Page 4
C: \HYDRA\CMD\12636DV1.CMD 15 : 36 27-Jan-99
- - -- -- S U M M A R Y O F A N A L Y S I S - - ----
Run number on command file 7
Number of links 3
Number of hydrographs 38
Total sanitary population 0
Total sanitary area 0 . 00 Acres
Total storm area 5 .74 Acres
Number of pumps 0
Number of reservoirs 1
Number of diversion structures 0
Number of inlets 0
Length of new pipe 0 . 00 Feet
Length of existing pipe 0 . 00 Feet
Length of channel 200 . 00 Feet
Length of gutter 0 . 00 Feet
Length of transport units 0 . 00 Feet
Length of pressure pipe 0 . 00 Feet
,1
I
Cascade Surveying and Engineering, Inc . HYDRA Version 5 .12
Arlington, Washington Page 3
C:\HYDRA\CMD\12636DV1.CMD 15 :36 27-Jan-99
23 : END
Cascade Surveying and Engineering, Inc. ,-HYDRA Version 5 .12
Arlington, Washington Page 1
C: \HYDRA\CMD\12636DV1 .,CMD ��Q i 15 :36 27-Jan-99
12636
jO
*** W-SITE /V Channel
Ditch Shape Invert Surface Width San Sto Flow Cost
Link Lon �Lft/Ctr'/Rht 'Slope Up/Dn Up/Dn epth Inf Mis 'Vel
/� 1 12 12 9 .7 3 0 214 214 0
1 100 3 . 0000 0 . 0100 9 .50 4�
( 7 . 00 `—� 128 .50 128 . 73 0 .23 0 0 0 . 27
------ --------------------------
Lateral length= 100 Upstream length= 100
Sr-_c.
*** E-SITE Channel
Ditch Shape Invert Surface Width San Sto Flow Cost
Link Long Lft/Ctr/Rht Slope Up/Dn Up/Dn Depth Inf Mis Vel
2 100 3 . 00 3 . 00 0 . 0100 129 . 50 129 .73 8 .4 0 214 214 0
7 . 00 128 .50 128 .73 0 .23 0 0 0 .27
*** E-SITE Reservoir
Invert - - - ---- - - ----- Maximum Flow Values - - -- - - - ---- -- - - - -
Link Up/Dn San Inf Sto Mis Design Cost
3 128 .50 DisChar_g� 0 0 98 0 _�8_ 0
127 .50 CStored 0 0 2240 0 __224-0
In=ming�� 0 0 401 0 401
-------------------- - - - - -- --------------------- - - - - -
Lateral length= 100 Upstream length= 200
,!
t
REQUEST FOR REVIEW FORM
CITY OF ARLINGTON -`�
DEPARTMENT OF PLANNING AND COMMUNITY DEVELOPMENT
FILE NO. SEPA 262 PROJECT NAME: CEMENT DIST
DATE OF CIRCULATION: APRIL 2, 1998
RETURN THIS FORM BY: APRIL 9, 1998
RESPONDING DEPARTMENT: BUILDING DAVE.
TYPE OF PROPOSAL: SEPA
APPLICANT: GORDON NIES CONTACT:
CEMENT DISTRIBUTORS, INC
815 OLIVIA PARK RD
EVERETT, WA 982-4
REQUEST: This request is for a SEPA. The applicant plans to operate a cement distribution company
on 59th Ave. NE that will consist of a new office (2492 sq. ft.) and a new mechanical shop
(7488 sq. ft.). The mechanical shop will be used for minor repairs to their vehicles and any
over haul of vehicles will be contracted out.
LOCATION: Property address - 15901 59th Ave NE
Legal description- SE 1/4 of SEC 22, T 31 N, R 5 E, W.M.
Tax Account# - 223105-4-017-0005
Nearest intersection- 59th Ave NE & 172nd St NE (SR 531)
COMMENTS FROM STAFF SHALL COME IN MEMO FORM. THE MEMO SHALL BE
ADDRESSED TO RYAN C. LARSEN.
IF YOU HAVE NO COMMENTS, PLEASE INDICATE BELOW BY MARKING THE BOX,
SIGNING AND DATING THE FORM. RETURN THIS FORM TO RYAN C. LARSEN.
❑ NO COMMENTS FOR THIS REVIEW
Department Signature/Title: Date:
h:\datamsof\current\procedur\sepa\0262\review.doc
�i
City of Arlington
Department of Planning and Community Development _
Master Permit Application
W 6 1996
yt aSTER PERNMIT APPT. ICATIQN
,FP! OF An!INGTCN
For Of&e Purposes Only
CITY OFtGTON DATE.RECEIED
} �. DATE ACCEPTED.'
238 North m
� P Ol f � ��
RECEIDY -
AT11IIbt0n,.wA 9 {
n k SEFA CHECKLIST -ATTACHED
YES .,NE)
.LXJQR FERMIT a�3
tiLliaRPERMIT �, FEES PAID
Sper- fe:Permit:Type CR odn}
PART I- GENERAL E' F� �TTnN
APPLICAN'_T_ CONTACT PERSON
1. Name CErIeNr DisT r2Rv4E wgaDEN o2 �oet�aN N��S
Address alS OL/viA ?,4itK Jest Sa�., c
City ,"YBRLr Ir
State,Zip w.a q S--26 -1
Phone-work i-u ZS- 3 SS S-o 9 Z
- home
2. Relationship of applicant to property(check one).,,4-owner contract purchaser lessee other
3. Name, mailing address and telephone number of property owner,if different from applicant.
4. General location of property,including nearest intersection:
IS4c>> ?
6. Street or known address of property: '� rq y� AVt N•C ?
1 Z S-o 1 a
6. Legal description of property: S e-e QTTQe W. 2 310 S — 24 —0 17 —CO O S
7. Description and purpose of proposal: 6 >x 'r 8 P oS T EZ4nid- S4010 w1 19 x 9 a' Pas?
LEAN—TD ,
8. List all property tax account numbers (all 14 digits): 7J 3 JS,5-44- D/`7- U ovS
masuper.doc
10/23/97
i
RECEIVEP
6w 6 1g4A
respectively. (;V'fY' OF AHLING- iC
SE---Pa awp
agso
A. BACKGROUND
1. Name of proposed project, if applicable:
CEMENT 0ISrR i Q4TORS INC.
2. Name of Applicant:
SAME'
3. Address/and phone number of applicant and contact person:
O
SIC f-/V)A R;QRIG Ape EYGRC-rr, wq�q$ Za4 !-142.S-35S-GSgts
4. Date checklist prepared: r3 R uc 6 WA L D FN OR 6o R ooN /V)F 5.
2-U-98
5. Agency requesting checklist:
C lry OF ARwN6ro►4
6. Proposed timing or schedule (including phasing, if applicable):
ASA P
7. Do you have any plans for future additions, expansions, or further activity related to or
connected with this proposal?
NOT- KNAowiv A7 T415 r)m>:.
8. List any environmental information you know about that has been prepared, or will be
prepared, directly related to this proposal.
PIM5E 2 FNYIRoNMENj�4L .4�cE55�1gHT- PkEP�4er0 G-2S-9G
9. Do you know whether applications are pending for governmental approvals of other
proposals directly affecting the property covered by your proposal?If yes, explain.
No.
10. List any governmental approvals or permits that will be needed for your proposal, if known.
/NoNC
11. Give brief, complete description of your proposal, including the proposed uses and the size
of the project and site. There are several questions later in this checklist that ask you to
NEW OFFICE— Z49 Z NEW SNoP- 7
8x 9(-- 7y88 s�
N�w FENcL:r ARwNp PE R)rnrrER .
GRAVGL P4RK/NG �orS
I
I
describe certain aspects of your proposal. You do not need to repeat those answers on this
page.
12. Location of the proposal. Give sufficient information for a person to understand the precise
location of your proposed project, including street address, if any, and section, township, and
range, if known. If a proposal would occur over a range of area, provide the range or
boundaries of the site(s). Provide a legal description, site plan, vicinity map, and topographic
map, if reasonably available. While you should submit any plans required by the agency, you
are not required to duplicate maps or detailed plans submitted with any permit applications
related to this checklist.
CORNER of 59r"AVE N.E. e 17ZN° -ST N.C.
Addret5 �
l7S()l S`if%
TO BE COMPLETED BY APPLICANT
Evaluation for Agency Use Only B. ENVIRONMENTAL ELEMENTS ! „IN-
suoxar roixrLill
LOCATION MAP
1. Earth i NO SCALE
i
a. General description of the site(circle one): Fla
rolling,hilly,steep slopes, mountainous, other.
b. What is the steepest slope on the site (approximate percent
slope)? I% .40 Z°/a
C. What general types of soils are found on on the site (for
example, clay, sand, gravel, peat, muck)? If you know the
classification of agricultural soils, specify them and note andy
prime farmland. 6 RAYEG €SA N D
d. Are there surface indications or history of unstable soils in the
immediate vicinity? If so, describe.
NO.
3
y
�I
1
e. Describe the purpose,type, and approximate quantities of any
filling or grading proposed. Indicate source of fill.
GR,4JP)NG OFC QRusy 0 69-4ss , APPL.9 CRusA
Rock Fog P,4RKnu` L..Or.
f. Could erosion occur as a result of clearing, construction, or
use? If so, generally describe. .No.
g. About what percent of the site will be covered with
impervious surfaces after project construction(for example,
asphalt orbuildings)? AFRR. ID- 1S°/b
h. Proposed measures to reduce or control erosion, or other
impacts to the earth, if any: ►JRA,NAGE sysrgm
2. Air
a. What types of emissions to the air would result from the
proposal(i.e.,dust, automobile, odors, industrial wood smoke)
during construction and when the project is completed? If
any, generally describe and give approximate quantities if
known. DIESEL EXHAUST GROm TRvGicS.-
b. Are there any off-site sources of emissions or odor that may
affect your proposal?If so, generally describe. NO.
C. Proposed measures to reduce or control emissions or other
impacts to air, if any: noNc--.
3. Water.
4
n
I
k
A. Surface:
1) Is there any surface water body on or in the immediate vicinity
of the site(including year-round and seasonal streams,
saltwater, lakes, ponds, wetlands)? If yes, describe.type and
provide names. If appropriate, state what stream or river it
flows into. /V O.
2) Will the project require any work over, in, or adjacent
to(within 200 feet) the described waters? If yes, please
describe and attach available plans. No
3) Estimate the amount of fill and dredge material that would be
placed in or removed from surface water or wetlands and
indicate the area of the site that would be affected. Indicated
the source of fill material. NONE.
4) Will the proposal require surface water withdrawals or
diversions? Give general description, purpose, and
approximate quantities if known. NO .
5) Does the proposal He within a 100-year floodplain? If so, note
location on the site plan. NO
6) Does the proposal involve any discharges of waste materials
to surface waters? If so, describe the type of waste and
anticipated volume of discharge.NO•
B. Ground:
1) Will ground water be withdrawn, or will water be discharged
to ground water? Give general description, purpose, and
NO.
5
approximate quantities if known.
None E
2) Describe waste material that will be discharged into the
ground from septic tanks or other sources, if any(for example:
Domestic sewage; industrial,containing the following
chemicals...; agricultural; etc.).Describe the general size of the
system, the number of such systems, the number of houses to
be served(if applicable), or the number of animals or humans
the system(s) are expected to serve. N 0..
C. Water Runoff(including storm water):
1) Describe the source of runoff(including storm water) and
method of collection and disposal, if any(include quantities,
if known). Where will this water flow? Will this water flow
into other waters? If so, describe. CArc,H a AS INS TO
A HOLD/NCB J DFTFNT►ON
2) Could waste materials enter ground or surface waters? If so,
generally describe. No
d. Proposed measures to reduce or control surface, ground, and
runoff impacts, if any:
SEE QoEsrioq u1 pat, <.
4. Plants
a. Check or circle types of vegetation found on the site:
_deciduous tree: alder,maple,aspen,other
10vergreen tree:fir,cedar,pine,other
_Eshrubs
Vrass
_pasture
_crop or grain
wet soil plants:cattail, buttercup,bulrush,skunk cabbage, other
6
water plants: waterlily, eelgrass,milfoil,other
other types of vegetation
b. What kind and amount of vegetation will be removed or
altered? Su R U P.S 0 (S RA SS
C. List threatened or-endangered species known to be on or near
site. No,v
d. Proposed landscaping, use of native plants, or other,measures
to preserve or enhance vegetation on the site, if any:
SNQUaS � FLowER QEDS ARouNc)
NEw pFFiCE BLO(, .
5. Animals
a. Circle any birds and animals which have been observed on or
near the site or are known to be on or near the site:
BIRDS: hawk,heron,eagle,songbirds,other: lVomE
MANIlVIALS:deer,bear,elk,beaver,other: NanIC
FISH: bass, salmon, trout, herring, shellfish, other: NoM G
b. List any threatened or endangered species known to be on or
near the site. NON E
C. Is the site part of a migration route?If so, explain. No
d. Proposed measures to preserve or enhance wildlife, if any:
005 S AJOT A PpL?.
6. Energy and Natural Resources
a. What kinds of energy (electric, natural gas, oil, wood stove,
solar) will be used to meet the completed project's energy
EcWdst
7/30/96 7
i
..
needs? Describe whether it will be used for heating,
manufacturing, etc.
GLEcrR ICAL NATuR4L 6.4s.
L 16I4TIW 6 € NEA-r
b. Would your project affect the potential use of solar energy by
adjacent properties? If so, generally describe. IVO
C. What kinds of energy conservation features are included in the
plans of this proposal? List other proposed measures to
reduce or control energy impacts, if any:
DOES NOT A PP[.y . Y
7. Environmental Health
a. Are there any environmental health hazards, including
exposure to toxic chemicals, rick of fire and explosion, spill or
hazardous waste,that could occur as a result of this proposal?
If so, describe. ND.
1) Describe special emergency services that might be required.
NONE.
2) Proposed measures to reduce or control environmental health
hazards, if any: N p .
b. Noise
EcMdst
7/30/96 8
1) What types of noise exist in the area which may affect your
project(for example: traffic, equipment, operation, other)?
NONE.
2) What types and levels of noise would be created by or
associated with the project on a short-term or a long-term
basis (for example: traffic, construction, operation, other)?
Indicate what hours noise would come from the site.
TRAFF)C_ EARLY MoRN)N(,S 4 LATE ASvxns.
TRuck RONNiNG 1N SHOP puKiv4- n.4w.
3) Proposed measures to reduce or control noise impacts, if any:
Ll r'"TEC) T)rne TRUalcs RUNNING Al- zme s
RGPA(R woRK To /3t r)ONE wlrylN crJN r-INES oP 9140P
8. Land and Shoreline Use
a. What is the current use of the site and:adjacent properties?
VACANT' 5/TP'.
A)RPoRT� &)�47- PLACE A)Ni STOR-46F-
b. Has the site been used for agriculture? If so, describe.
A10 .
C. Describe any structures on the site. NO NE.
d. Will any structures be demolished? if so, what? NO.
e. What is the current zoning classification of the site?
COMM&RIcAL/1-16HT 1NDuSrR/AL.
Eclkl.
7/30/96 9
f. What is the current comprehensive plan designation of the
site? UN KNOwm .
g. If applicable, what is the current shoreline master program
designation of the site? NO.
h. Has any part of the site been classified as an "environmentally
sensitive"-area? If so, specify.-ND
i. Approximately how may people would reside or work in the
completed project?
1Z People- fly OFFICES
Zy DR IUERS.
j. Approximately how many people would the completed project
displace? NON G.
k. Proposed measures to avoid or reduce displacement impacts,
if any: DOES NOT A pPL�p
1. Proposed measures to ensure the proposal is compatible with
existing and projected land uses and plan, if any:
DOES NOT ApPL?
9. Housing
EcWdst
7/30/96 10
a. Approximately how many units would be provided, if any?
Indicate whether high, middle, or low-income housing.
DOES NoT A PPL y.
b. Approximately how many units, if any, would be eliminated?
Indicate whether high, middle or low-income housing.
(I DES NOT 4 PPG V.
C. Proposed measures to reduce or control housing impacts, if
any: 006S NOT A PPL y,
10. Aesthetics
a. What is the tallest height of any proposed structure(s), not
including antennas; what is the principal exterior building
material(s) proposed? Z 6�- / F Ro m G RD a N p
rO R10660.F GI-D ,. COLORED M677AL .
b. What views in the immediate vicinity would be altered or
obstructed? 1VON e-.
C. Proposed measures to reduce or control aesthetic impacts, if
any: NO N c.
11. Light and Glare
a. What type of light or glare will the proposal produce? What
time of day would it mainly occur? N/GH T L I6 HT,
b. Could light or glare from the finished project be a safety
hazard or interfere with views? NO.
C. What existing off-site sources of light or glare may affect your
Echkist
7/30/96 I 1
r.
I
I
.;
proposal? )VO
d. Proposed measures to reduce or control fight and glare
impacts, if any: DOES NO T A PPG y.
12. Recreation
a. What designated and informal recreational opportunities are
in the immediate vicinity? DUES NOT A PPLy,
b. Would the proposed project displace any existing recreational
uses? If so, describe. A10,
C. Proposed measures to reduce or control impacts on `
recreation, including recreation opportunities to be provided
by the project or applicant, if any: GbES NOT A PPt,y,
13. Historic and Cultural Preservation
a. Are there any places or objects listed on, or proposed for,
national, state, or local preservation registers known to be on
or next to the site? If so, generally describe.No.
b. Generally describe any landmarks or evidence of historic,
archaeological, scientific, or cultural importance known to be
on or next to the site. DOES 140T A PPL- Y.
C. Proposed measures to reduce or control impacts, if any:
DOES NOr APPGT,
EcWdst
7/30/96 12
i
..
14. Transportation
a. Identify public streets and highways serving the site, and
describe proposed access to the existing street system. Show
on site plans, if any. 5 9r1* Aver A-E. � 1'7 Z 9 ST. N.F.
b. Is site currently served by public transit? If not, what is the
approximate distance to the nearest transit stop? NO.
AMR. VOpyds To TNF NoRT1+.
C. How many parking spaces would the completed project have?
How many would the project eliminate? 7 ro SO.
None.
d. Will the proposal require any new roads or streets, or
improvements to existing roads or streets, not including
driveways? If so, generally describe (indicate whether public
or private). /V O .
e. Will the project use (or occur in the immediate vicinity of)
water, rail, or air transportation? If so, generally describe.
NO.
f. How many vehicular trips per day would be generated by the
completed project? If known, indicate when peak volumes
would occur. A PR R. ioo O VC R z i4 14 R P 1E Rsoo.
NO P6AK TIMES.
g. Proposed measures to reduce or control transportation
impacts, if any: DOES NUT At PPL y
EcWdst
7/30/96 13
i
I
15. Public Services
a. Would the project result in an increased need for public
services(for example: fire protection, police protection, health
care, schools, other)? If so, generally describe.
F'IRE POLICE PROTECTION W/+SnN NEE DEfl.
b. Proposed measures to reduce control direct impacts on public
services, if any. DO /VO T 19'V6 W,
16. Utilities
a. Circle utilities currently available at the site; electricity, natural
gas, arefuse service, telephone, sanitary sewer, septic
system, other.
b. Describe the utilities that are proposed for the project, the
utility providing the service and the general construction
activities on the site or in the immediate vicinity which might
be needed. E1.Ec-TPiC1TY/ W.4rER, SaWFTR'
N.4TH RA L 6-46 .
C. SIGNATURE
The above answers are true and complete to the best of my
knowledge. I understand that the lead agency is relying on them
to make its decision.
Signature: Cq.r't.+,
Date Subn tted•
Echkts.
7r3o/96 14
PACIFIC MOBILE STRUCTU; 3), INC.
P.O. Box 1404
CHEHALIS, WASHINGTON 98532
DATE _ � JOB NO.9 ®,,? I
(360) 748-0121 ATTENTION
TO RE:
WE ARE SENDING YOU ❑ Attached ❑ Under separate cover via Ui Nfollowing items:
❑ Shop drawings ❑ Prints ❑ Plans ❑ Samples ❑ Specifications
❑ Copy of letter ❑ Change order ❑
COPIES DATE NO. DESCRIPTION
Z7,;- d
THESE ARE TRANSMITTED as checked below:
❑ For approval ❑ Approved as submitted 10 Resubmit copies for approval
XFor your use ❑ Approved as noted ❑ Submit copies for distribution
❑ As requested ❑ Returned for corrections ❑ Return corrected prints
❑ For review and comment ❑
❑ FORBIDS DUE(�� 19 ❑ PRINTS RETURNED AFTER LOAN TO US
REMARKS 3
4_/ G
oe,
I Ti GY�Iiel
y - wLIG GC �Gfl1 /- �C
COPY TO
I SIGNE���If enclosures are not as noted,kindly notify us of once.
:y
�r r -i r ` .. i r• r ���1 i 1211 ? i fIffh
lip I { — i +I If
1 � I
�� ��, yl� ■ — — - ■!V 7 ■ ■_ jam mm 1 1.0 I_ ■. w 1 1c tl■r r
INC L ON
' IL --Um try. lit
rn
"111 R r ■ n mill ■ 1 ■ 1 0 L r
11 1 '■
11111 ■ - ' '
- r I
v■�ti ■ i m WE II 1 ) 1 L.0 ■ _ - r 1- r
�y y . ■
36
1. 4ti-IN
t r
1 T
May 18, 1998
B&H P.C. #: 30100.00
PROJECT: Concrete Distributors
Cascade Surveying & Engineering
Cascade Surveying &Engineering
102 E Division P.O. Box 326
Arlington, Washington 98223
Attention: Randy Devoir
Re: Review of Drainage Report for Concrete Distributors
To the Applicant:
The City of Arlington is utilizing Berryman & Henigar for grading, drainage and flood plan review services; it is B&H's
goal to provide a quality review and minimize the impact of third party review on the applicant. Please note the items listed
below so you will better understand our role in the City review process and avoid delay in processing plans through
Berryman&Henigar.
1. Berryman&Henigar's review encompasses the grading, drainage and flood control portion of the City of Arlington's
Stormwater Management Ordinance(16.10),Flood Plain Ordinance(16.28),Flooding Hazards Ordinance (16.24), and
the Stormwater Management Manual for the Puget Sound Basin.
2. When addressing items on the correction list, please explain how the item was resolved in a response letter. Any new
or revised information,which relates to the correction items, should be referenced.
3. Please resubmit all information to Berryman&Henigar for further review purposes. The number of corrected drawing
sets should be in accordance with the City of Arlington submittal requirements. Once final approval is obtained, you
will be notified by the City on the status of the permit application.
If you have any questions regarding any of these items,please let us know. (Contacts: Mike Pawlak or Andy Law)
Berryman&Henigar
1215 Fourth Avenue, Suite 1400
Seattle,WA 98161
(206)505-3400
(206)505-3406
cc: Davc Anderson-City of Arlington
c:admi n:andy:doc:concdi s2:cp
1215 4ch Avenue, Suite 1400 • Seattle, WA 98161 • (206) 505-3400 • Fax(206) 505-3406
An Equal Opportunity Employer
-Tl
Letter to Cascade Surveying&Engineering 1
5/18/98
Page 2
DRAINAGE REVIEW COMMENTS: First Review
PROJECT- Concrete Distributors
Cascade Surveying &Engineering
A review of the stormwater management materials submitted to date indicates that all of the stormwater
management requirements are not yet satisfied. For the next submittal of stormwater management
materials, the items listed below should be included. The stormwater management measures will then be
reviewed again to determine whether all of the requirements are met.
A. Per the Stormwater Management Manual for the Puget Sound Basin (Technical Manual),
Minimum Requirements #1 through #11 shall be met, including the following:
MR#1:Erosion and Sediment Control
1. Stabilization and sediment trapping
Satisfied by TESC Note 7, General Note 13.
2. Delineate clearing and easement limits
Satisfied by TESC Note 3.
3. Protection of adjacent properties
Satisfied by TESC 6 for east boundary and by grading for the other boundaries.
4. Timing and stabilization of sediment trapping measures
Satisfied by TESC 4 and 5
Add: sediment shall not be discharged off-site. Stormwater shall be infiltrated
on-site.
5. Cut and Fill Slopes
Interior pond slopes should be no steeper than 3:1
6. Controlling Off-Site Erosion
NA
Berryman & Henigar
Letter to Cascade Surveying&Engineering—)
5/18/98
Page 3
7. Stabilization of Temporary Conveyance Channels
NA
8. Storm Drain Inlet Protection
Satisfied by TESC 15 and 16
9. Underground Utility Construction
NA or covered by others
10. Construction Access Routes
Satisfied by TESC Note 11 and Sheet 6 detail
11. Removal of Temporary BMPs
Covered by TESC Notes 14 and 1
12. Dewatering Construction Sites
Covered by M.R. #4
13. Control of Pollutants Other Than Sediment
Add note stating: "all pollutants other than sediment on-site during construction
shall be handled and disposed of in a manner that does not cause contamination of
site soils or stormwater (follow at least BMPs C 1.20, C 1.40, C 1.50, C 1.60, C 1.70,
C1.80, C2.00 in Technical Manual Volume III-3).
14. Maintenance
Satisfied by TESC Notes 2, 9, 10, and 13.
15. Financial Liability
To be provided prior to construction
MR#2:Preservation of Natural Drainage Channels
NA
MR#3: Source Control
Berryman & Henigar
�:
I
I
I
Letter to Cascade Surveying&Engineering
5/18/98
Page 4
The BMPs describW under Source Control of Pollutiori are actually treatment BMPs, not
source control BMPs. These BMPs should all be described under Runoff Treatment BMPs.
Required source control BMPs for Fleet Vehicle Yards include BMPs S 1.10, S 1.20, S 1.30,
S 1.40, S 1.50, S 1.80, S.200 and 52.20 per the Technical Manual, where applicable, and any
other source control BMPs that may be applicable for the site.
Review these BMPs to determine which structural facilities are required (e.g. fueling island,
vehicle wash area, liquid unloading dock, etc.). Details for structural source control BMPs
shall be submitted prior to construction.
Provide a narrative of source control BMPs for the site.
MR#4:Runoff Treatment BMPs
The selected runoff treatment BMP consists of wet ponds. These ponds do not have an
adequate permanent pool volume. The permanent pool volume must be equal to or greater
than the volume of the 6-month, 24-hour storm runoff, which is approximately 16,000 ft3 for
the 5.2 acre drainage area. The wet pond volume must be increased or a different treatment
BMP must be selected.
The oil/water separators for the frontage road will probably provide enough treatment if
adequately maintained. The oil/water separators should be type 2 catch-basins. The tees
should be as shown in City of Arlington Standard Plan No. SD8.
The two oil/water control catch-basins for the main site runoff are inadequate for oil/water
separation or sediment removal. Oil/water separators should be selected and designed in
accordance with the guidelines in the Ecology Technical Manual.
MR#5:Downstream Erosion Control
The infiltration pond design is adequate for controlling the 100-year storm flow, if the wet
pond volume is included. The interior pond slopes must be 3:1 not 2:1.
Provide the results of percolation testing for the infiltration trench area.
Describe on-site drainage control, for the east boundary in particular.
Describe on-site drainage routes, particularly from the on-site buildings.
Berryman & Henigar
Letter to Cascade Surveying&Engineering
5/18/98
Page 5
MR#6:Wetlands
Satisfied. No wetlands.
MR#7:Water Quality Sensitive Areas
None on-site and no discharge proposed from the site.
MR#8: Off-site Analysis and Mitigation
On the topographic map show the drainage route for overflow from the infiltration system to
Quilceda Creek.
MR#9:Basin Planning
NA
MR#10:Operations and Maintenance
Operations and Maintenance requirements were included in drainage report. An operation
and maintenance schedule shall be provided for the proposed stormwater facilities that
includes identification of the party or parties responsible for operation and maintenance. An
operations and maintenance agreement shall be signed and submitted for inclusion in the
Project Notebook at a later date. A copy of the city's standard agreement is attached.
MR#11: Financial Liability
This is to be provided as assessed by the City of Arlington. (To be added to project notebook
prior to construction).
B. Additional City of Arlington Stormwater Management Ordinance Requirements
1 In accordance with the City of Arlington Stormwater Management Ordinance No. 16.10.140,
Design Criteria and Construction Plans, please provide:
SUBMIT prior to beginning of construction
Construction Plans as per 16.10.140
Project Notebook
Berryman & Henigar
I
I
Letter to Cascade Surveying&Engineering
5/18/98
Page 6
Please ensure that the following items are included in the Project Notebook, which must be
submitted complete prior to beginning construction:
1. Stormwater Runoff and Drainage System Calculations.
2. Storm Drainage Report Narrative (include, at the least, Minimum Requirements #2, 4, 5, 6, 7, 8,
& 9).
3. Erosion and Sediment Control Plans (Minimum Requirement#1).
4. Grading and Drainage Plans.
5. Operation and Maintenance Plans for Erosion and Sediment Control(Minimum Requirement#1).
6. Operation and Maintenance Plans for Stormwater Management/Drainage System (Minimum
Requirement#10).
7. Financial Liability Instruments for Erosion and Sediment Control Facilities and the Stormwater
Management/Drainage System(Minimum Requirement#11).
8. Narrative concerning urban setting uses for development and applicable Source Control BMPs (if
applicable) (Minimum Requirement#3).
9. Copy of the filed signed Maintenance Agreement(to be provided later).
10. Legal descriptions of any property containing permanent stormwater management facilities to be
conveyed to a property owner association of the City.
11. Estimate of the construction cost of all permanent stormwater management facilities to be deeded
to the City or which are subject to a recovery contract under Chapter 18.08 of the City Code.
12. Inspection and construction control schedule to be enforced by the applicant.
The Project Notebook is simply a compilation of all required stormwater management submittals.
Documents will be added to the project notebook as the project is carried out (e.g. the signed Operations
and Maintenance Agreement). It will also be used to review the project history during future projects on-
site or related to the site. The notebook may be a three ring binder or similar item to which documents
may be added or removed.
Berryman & Henigar
ti ..1
CITY OF ARLINGTON
Building Department
May 23, 1998
Bruce Walden
Cement Distributors Inc.
815 Olivia Park Rd
Everett, WA 98204
RE; Building Permit application 98-2950
Dear Bruce,
The submitted drawings have been reviewed for compliance with the 1994 Edition of the
Uniform Building Code. The following applicable code data corrections and/or additional
requirement are necessary before the permit can be issued.
1. The applicant shall mitigate the cost of full improvement along 59th Ave in lieu of
constructing these improvements. A cost estimate of these improvement is required for review.
2. ? A no protest agreement in regards to the formation of an L.I.D. along 59th Ave NE.
(Y Dedication of right of way along 59th Ave is required.
✓4. Culverts at the driveways are required to the access of the property.
5. All driveways shall be paved to match existing edge of asphalt and shall have a minimum
of 30' radius on approaches.
6. The sanitary sewer grade will be .30%rather than the .40% indicated because its a 10"
line.
7. The sidewalks need to be moved to the property line to allow sufficient room for meters,
ect in the parking strip.
v S. Three hydrant assemblies are required and shall be installed along 59th, at the south end
that will also act as a blowoff for the south leg of the water system. The second hydrant will be
installed at the North end on the north leg of the tee. It will be on its own 8 X 6 valve for the
hydrant. The third hydrant will be required in the truck storage yard at the north property line
within 150 feet of all portions of the shop building.
238 N. Olympic Ave. • Arlington, WA 98223 • (360) 435-0724 0 FAX (360) 435-3906
_' {, � � '
I
:,
V'9. The 8"tee at station 1+63 needs to be fully valved, add an 8"on the north leg.
✓10. The ductile water main shall be class 52.
✓l 1. The hydrants shall be installed per City standard plan W 1. If the domestic water service is
larger than 1", a tee and valve will be required per standard plan W9.
✓12. The proposed water main location along 59th appears to be under the sidewalk. It should
be in the planter strip between the curb and the sidewalk. If the hydrant does not fit at the
standards location which is 2' from the face of the curb, it must be located behind the sidewalk in
a utility easement. By moving the sidewalk to the property line there should be sufficient room
for the water line. The hydrants will be behind the sidewalk.
✓ 13. There should be a 10' general utility easement along the property line on 59th Ave.
V 14. Although the building is classified as a S3/S1B occupancy which allows general
maintenance of vehicles without any welding or open flames, it could be construed that if any
welding or open flames and exchange of engine blocks or other major maintenance occurs in the
building it would be classified as an H4 occupancy. Therefore it is recommended that the
underground main fire line be installed to the shop building for future sprinklering of the
building . If a determination is made to change the occupancy based on violations in the building,
it would then be classified as an H4 occupancy which requires it to be sprinkled along with
additional requirements such as ventilation, and containment.
15. No open flames or welding is allowed within the shop building.
16. A one hour fire separation is required between the shop and the storage area. Doors shall
be 20 minute doors.
17. A one-hour fire separation is required between the storage and the lunch room area.
18. The boiler room shall have one-hour separation throughout the walls and the ceiling.
19. - Handicap accessibility is required throughout the building. This includes access to the
bathrooms in both the driver lunch room and the driver ready room.
S' elys
D vid W. Anderson
Building Official
PROJECT ENVIRONMENTAL MITIGATION AGREEMENT
Cement Distributors
4/27/98
SEPA #262
This agreement is entered into by and between the City of Arlington, a municipal corporation,
hereinafter referred to as the "City", and Cement Distributors hereinafter referred to as the
"Developer"
WHEREAS, this agreement is executed pursuant to Chapter 43.21 RCW, the State
Environmental Policy Act (SEPA), and Chapter VII of Arlington's Unified Development Code, to
provide for mitigation of existing and known environmental impacts associated with the development
hereinafter described. This agreement is a voluntary agreement entered into pursuant to the statutes of
the State of Washington. This agreement does not preclude any evaluation and determination by the
City upon later actions or proposals undertaken by the Developer which may require a determination of
significance and environmental review under SEPA and
WHEREAS, the Developer is proposing to construct a 78' x 96' (7,488 sq. ft.) shop and 2,492
sq. ft. office. The Developer is re-locating their current operation from Everett, WA to the Arlington
site, and
WHEREAS, the Responsible Official has made findings that the proposed development will
result in the following probable significant adverse impacts to the environment;
1. Storm water run-off resulting from impervious surfaces and related potential
contamination of ground water from automobile.
2. Traffic impacts of an estimated rate of 80 ADT per day for the new business.
3. Need for provision of water and sewer utilities, to and through the site, to serve this
project and those which may occur.
4. Need provisions of additional fire protection ability in conjunction with construction
and occupancy of Project.
NOW, THEREFORE, the City and the Developer agree that the following mitigation measures
shall be employed by the Developer to ensure that probable significant adverse environmental impacts
created by the proposed project are minimized or eliminated:
mitagre.doc
Page 1 of 5
Transportation
1. Full frontage lot improvements along 59th Ave. NE shall include, but not limited to,
curb, gutter, sidewalk, right turn lane for north bound traffic and storm drainage. The
Developer shall submit an engineered cost estimate of these improvements to the
Department of Planning and Community Development. The Developer shall pay for
the construction of improvements that are required as a condition of site development.
If a Street Improvement LID is formed in the next five years, the Developer has the
choice of contributing their fee towards the LID or being reimbursed the amount
contributed for frontage improvements. If the Developer chooses to be reimbursed,
then the Developer shall be required to pay their fair share of the LID improvements.
Payment of this fee shall be made prior to the issuance of a building permit.
2. Developer shall sign a Waiver of Protest for formation of a local improvement district
(LID) for any and all improvements that would benefit this property. The Waiver of
Protest shall be record at the Snohomish County Assessor's Office and recorded copy
submitted to the Department of Planning and Community Development, prior to the
issuance of a building permit.
3. The Developer shall dedicate right-of-way along 59th Ave NE to the City of Arlington
at 30' from center line of road. All dedications shall be completed prior to the issuance
of a building permit.
4. All street construction shall meet the standard City street requirements per the City of
Arlington Public Works Construction Standards and Specification Manual.
5. All areas frequent to street traffic shall be paved and meet the standard street
requirements of the City.
6. The Developer shall pay traffic mitigation fees, prior to the issuance of building permit
for the impacts to 172 St. NE (SR 531) at the following rates:
Transportation Mitigation Requirements
Project Total ADT Mitigation Per Total Mitigation
Trips $ Require $
Signalize SR 531 20 $19.12 $382.40
/67th Ave NE
I-5/SR 531 Interchange 60 $85.79 $5,147.40
Improvements -
Widening SR 531 80 $54.40 $4,352.00
43rd Ave to 67th Ave
TOTAL 160 $159.31 $9,881.80
mitagre.doc
Page 2 of 5
4
Utilities
1. Sanitary Sewer and Water lines shall be extended to the site by the developer at their
expense. The Developer shall submit construction drawings, drawn to City standards,
for review and approval prior to construction. The Developer shall pay the required
connection fees prior to the installation of the services.
2. Additional fire protection maybe required by the Arlington Fire Department. The City
of Arlington will inform the developer of their responsibility during the construction
review process. Fire protection systems shall meet adequate flow standards as required
by the Fire Chief and Director of Public Works.
Recreational
I. The Developer shall pay a parks mitigation fee of 50.05 per gross sq. ft. of total land
area of land being developed for a total of 59,487.37. This shall be paid at the
issuance of the building permit.
General
1. All construction drawings shall be submitted to the Department of Planning and
Community Development. This includes all on and off-site public facilities constructed
as part of this process.
2. Construction shall be limited to the hours between 7:00 a.m. and 7:00 p.m.
3. Approval of the building permit is subject to submittal of an engineered Storm
Drainage Plan and Temporary Erosion and Sediment Control Plan (TESCP) for review
and approval by the Building Department, prior to any site construction. These plans
shall be designed to the Puget Sound Water Quality Manual and AMC 16.10. The
Developer will be responsible for the cost of outside consultant review for the Storm
Drainage Plan.
4. A potential exists that high alkaline runoff will contaminate surface water during the
truck washing process. The developer will be required to implement Department of
Ecology Best Management Practice in order to mitigate this potential problem. Some
of these guidelines are included in DOE Stormwater Management Manual for the
Puget Sound, Chapters 2-3.8.5, 4-2.1.1, and 4-4.2.
5. Steps shall be taken to design and maintain the detention pond to discourage wildlife,
especially birds. Maintenance in the form of routine cutting of plant material that grow
in the pond is critical. The detention pond is a private facility, which the Developer is
required to maintain at their own expense.
6. The Developer shall coordinate with the City and the U.S. Department of Agriculture's
Animal Damage Control office should it appear in the future that hazardous wildlife are
habitating to the area. Also the City and/or U.S. Department of Agriculture's Animal
mitagre.doc
Page 3 of 5
Damage Control office may ask the Developer at any time to implement a program that
would discouraee wildlife.
7. Adequate measures shall be taken to mitigate noise and visual impacts on the
surrounding parcels. A landscaping plan shall be submitted to the Department of
Planning and Community Development for review and approval. Upon approval the
Developer shall landscape the site per the approved landscaping plans. All landscaping
requirements shall be completed, prior to final certificate of occupancy.
8. All development on this property shall conform to the requirements of the A.A
Investments Short Plat Auditor's File No. 9608015001 and any other conditions tied to
this plat from previous agreements.
9. This document shall be recorded with the Snohomish County Assessor's Office and a
recorded copy submitted to the Department of Planning and Community Development,
prior to the issuance of a building permit. The document shall be signed by all parties
before recording.
mitagre.doc
Page 4 of 5
J
Developer/Owner
State of Washington)
) ss
County of Snohomish)
On this day personally appeared before me LL 10'oo . to me known to be the individual
described in and who executed the within and foregoing instrument, and acknowledged that designed
the same as E 5 free and voluntary act and deed for the uses and purposes therein mentioned.
Given under my hand and official seal this 20 day of 1 W j998.
AN E. �c -
1Onj 4�F'o OT',kRYPUj3LlC in and for de Sta(e mf Washington
° NOTARY residing
`c —�0 My appointment expires
cf)� PUBLIC z
y 8-13-2000 �o
�OF WASN��C�
Ci y o Arlington
State of Washington)
) ss
County of Snohomish)
On this day personally appeared before me JA n W) R Usk►0(Jet to me known to be the individual
described in and who executed the within and foregoing instrument, and acknowledged that}LeLsigned
the same as free and voluntary act and deed for the uses and purposes therein mentioned.
Given under my hand and official seal this 20day of .1998.
FOP E. SyF,o "AY
ONQz � ��AR� No 1C in apd fo St to f Washington
residing t any
PUB�>,C oz My appoin nt expires 3 -a �GG
mitagre.doc
Page 5 of 5 F 1�t
�,:
r
9805200495
05/20/98 14:35
p .0005 Recorded COPY
Snohomish County ORIGINAL ON FILE IN THE
COUNTY AUJ)iTOn,'S OFFICE
Return Address: City of Arlington
238 N. Olympic Ave.
Arlington, WA 98223
Document Title: Project Environmental Mitigation Agreement
Reference Number: SEPA#262
Grantor: Bruce Walden
Grantee: Arlington, City of
Legal Description: Lot 4 of Short Plat recorded under No. 9608015001, records of
Snohomish County, Washington, being a portion of the Southeast
quarter of Section 22, Township 31 North, Range 5 East, W.M.
Assessor's Property Tax Parcel/Account Numbers: TAX ID #223105-4-017-0005
T ' SOS ' oaS --
' sapzs :� uo -29ae uado aog OOT pasUaaout -eaae aTq-eMoTTV
gaad 0 ' SE gaad 0 ' OL SuzpTzng ZSHM
'499d 0 ' 0iVE gaad O ' O'-�E auzT Agaadoad HMOS
gaad O ' SZZ gaad O ' SZZ auzT Agaadoad ZSVEI
gaad O ' OOT gaad O ' OOT auzT Agaadoad HZZION
NOIZOHZOEd HEId dSVEEDNI VSHV 2UdVCINfl0g NOIZOH2iIQ
NOIJ,V2d ddHS
•sT-eTDTgjo SuzpTzng 90 a0uaaa9uo0 T-euozgL-uaa-4ul
auq Jo uozsszwaad auq ugtM apoo SuzpTzng waogtun aqq woag
paonpoadaa aap wpa5oad stuq uz pau'Pquoo TUza9gUW auq Jo suozgaod
ZZ9S-66S (6TL) 'p '3 M q Aq aapmggos gskTPuV UPTd SUTsn pagpaao gaodaH
•apoo auq Jo suozgoas pagoaTas oq apzn5 P sz qI
'Ogfl L66T auq uz squawaaznbaa apoo aTgtssod TTP Jo SuzgsTT agaTdwoo
p aq oq papuaquz qou aap gaodaa szuq uz pagszT swage apoo aqy :HZON
SnKQ :gig ;aodaH
NSNIIHHZ 'N 'H :aaauzSuH N-n :uoTgonagsuoO
: goagzuoaV H'TS ' :VH :AoupdnooO
'THHIS NOSHIld SflgE :aogoPaquoa
RN HAV H16S TOSLT : ssaappV
SUOMEI-dISIQ ZNHWHO : aWPN qoa Coad
866T 'TZ DPW : @qPC OS6Z-86 :aagwnN goaCoad
apoo SuzpTzng waog?ufl L66T auq
uo paspq sts,�TPuP uPTd
t,ZLO-SEiv (09E)
EZZ86 uogSu"ISPM 'uogSuzTaV
anuaAV azdwATO LlgaoN 8 E Z
quawgapdac SuzpTzng
uogSu'TJV 90 AgTD
v
;LI,
I
Page # 2
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
FL NAME OCC MAX FLR AREA ALLOWED RATIO STATUS
- -- - - - - - - - - -- -- - - - - - - - - - - - - - - - - - - - - - -- - - --- - - - - - - - - -- - - - - - - -- - - - - - - - -
1 Repair Garage H4 ok 4032 10200 0 . 4 ok
1 Storage/Stock Room S1 ok 1080 16000 0 . 07 ok
1 Other Occupancy B ok 216 16000 0 . 01 ok
1 Other Occupancy B ok 216 16000 0 . 01 ok
1 Other Occupancy B ok 216 16000 0 . 01 ok
TOTAL FOR FLOOR 5760 11445 0 . 5 ok
BUILDING TOTAL 5760 11445 0 . 5 ok
-- Sec . 504 and Table 5-B
The actual height of this building is 27 . feet .
The maximum height of the building is 40 . feet . -- Table 5-B
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 5-A
NORTH
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
H4 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
EAST
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
H4 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
SOUTH
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
H4 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
WEST
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
i
1
f
Page # 3
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
H4 0 hour 0 hour None Any No
Sl 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
None - - No fire protection requirements for openings .
3/4 hour - - Openings are to be protected with 3/4 hr fire assemblies .
50% of the area of the wall maximum. -- Table 5-A,
Footnote 5 & Sec . 503 . 2 .2
Maximum single window size is 84 sq. ft . with no dimension
greater than 12 feet . -- Sec . 713 . 8
Not Allowed - - Openings are not permitted in this wall .
OTHER BUILDING ELEMENTS Table 6-A
ELEMENT MATERIAL RATING NOTES
Interior Bearing wall Any 0 hr
Interior nonbrg wall Any 0 hr
Structural Frame Any 0 hr
Exterior Struct Frame Any 0 hr See footnote #1
Floor/Ceiling Assembly Any 0 hr See Footnote #18
Roof/Ceiling Assembly Any 0 hr
Stairs Any None
FOOTNOTES :
1) Elements in an exterior wall located where openings are not permitted
or where protection of openings is required, shall be protected
against external fire exposure as required for exterior bearing walls
or the structural frame, whichever is greater. -- Table 6-A, footnote 1
9) In areas with vehicles or airplanes, the floor shall be of
noncombustible, nonabsorbent materials . -- Sec . 307 . 2 . 2
18) In areas containing hazaradous materials, the floor shall be of
noncombustible, liquid-tight construction. -- Sec . 307 . 2 . 2
C
Page # 4
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
PENETRATIONS OF FIRERESISTIVE ASSEMBLIES
WALLS ASSEMBLIES -- Sec . 709 . 6
Through penetrations :
1) Penetrations shall be installed as tested in the rated assembly.
-- Sec . 709 . 6 . 2
2) Penetrations shall be protected by an approved penetration
firestop system and shall have an F rating of not less than the
required rating of the wall penetrated. -- Sec . 709 . 6 . 3
Exception: When penetrating items are steel, ferrous or copper
pipes or steel conduits and the wall is concrete or
masonry, the annular space shall be permitted to be
grout or mortar. The minimum thickness is the
thickness required to maintain the fire rating. The
maximum size of the penetrating items is equivalent
to a 6-inch diameter and the opening is a maximum of
144 square inches . -- Sec . 709 . 6 . 1
Membrane penetrations :
The requirements are the same as for through penetrations .
-- Sec . 709 . 7
Exceptions :
1 . Steel electrical outlet boxes that do not exceed 16 square
inches provided that the area of such openings does not exceed
100 square inches for any 100 square feet of wall area.
Boxes on opposite sides of the assembly shall be
separated by a horizontal distance of not less than 24
inches .
2 . Sprinklers with metal escutcheon plates .
Noncombustible penetrating items shall not be connected to
combustible materials on both sides of the membrane unless it can
be confirmed that the fire-resistive integrity of wall is
maintained. -- Sec . 709 . 7
1
Page # 5
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES -- Sec . 710 .2
Through pentrations :
Through penetrations of fire-resistive horizontal assemblies shall
be enclosed in fire-resistive shaft enclosures . -- Sec . 710 . 2 . 1
Exceptions :
1 . When penetrating items are steel, ferrous or copper conduits,
pipes, tubes and vents through a single concrete floor, the
annular space shall be permitted to be grout or mortar.
The minimum thickness is the thickness required to maintain
the fire rating. The maximum size of the penetrating items is
equivalent to a 6-inch diameter and the opening is a maximum
of 144 square inches.
2 . Electrical outlet boxes that have been tested for use in
fire-assemblies .
The system shall have an F rating and a T rating of not less than
one hour but not less than the required rating of the floor system.
-- Sec . 710 . 2 . 3
Exception: Floor penetrations contained and located within the
cavity of a wall do not require a T rating.
Membrane penetrations :
The requirements are the same as for through penetrations .
-- Sec . 710 . 3
Exceptions :
1 . When penetrating items are steel, ferrous or copper
conduits, electrical outlet boxes, pipes, tubes and vents
through concrete or masonry and the annular space is
protected by an approved penetration firestop assembly or
protected to prevent the free passage of flame and
products of combustion. Such penetrations shall not
exceed an aggregate area of 100 square inches in any 100
square feet of ceiling area in assemblies without
penetrations .
2 . Electrical outlet boxes that have been tested for use in
fire-assemblies .
3 . Sprinklers with metal escutcheon plates .
Fire-resistive roofs may have unprotected openings . -- Sec . 710 .4
s
it
it
Page # 6
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
SMOKE and FIRE DAMPERS -- Sec . 713 . 10 and 713 . 11
Dampers shall be accessible for inspection and servicing:
1 . Penetrations through area separation walls .
Penetrations through occupancy separations .
2 . Penetrations of the fire-resistive construction of horizontal
exit walls or corridors serving as a means of egress .
Exception: Openings for steel ducts penetrating the required
fire-resistive construction of corridors are not
required to have smoke dampers when such ducts
are of not less than 0 . 019-inch thickness
(26 gage) and have no openings serving the
corridor.
3 . Penetrations of shaft enclosures .
Exceptions :
1 . Duct penetrations by steel exhaust air subducts
extending vertically upward at least 22 inches above
the top of the opening in a vented shaft where the
airflow is upward.
2 . Penetrations of a fire-resistive floor forming the
base of a shaft enclosure may be protected by fire
dampers listed for installation in the horizontal
position.
3 . Smoke dampers are not required when shaft is exhaust
only, and is used for continuously operating fans .
4 . Penetrations of the ceiling of fire-resistive floor-ceiling
or roof-ceiling assemblies .
Exception: Smoke dampers are not required.
5 . Penetrations of an atrium enclosure element .
Exception: Smoke dampers are not required.
6 . Penetrations of exterior walls where protection of openings
is required.
Exception: Smoke dampers are not required.
7 . Penetrations of areas of refuge .
Exception: Ventilation system designed to supply outside
air during an emergency.
8 . Smoke dampers are required in smoke barriers and elevator
lobbies .
_'
�-
I
Page # 7
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
OCCUPANCY SEPARATIONS -- Table 3-B
H4-S1 lhr
H4-B lhr
Si-B Ohr
HEATING EQUIPMENT SEPARATION:
FOR H4 OCCUPANCY:
A 2hr occupancy separation is required around rooms containing a
boiler or central heating unit . -- Sec . 302 . 5
FOR S1 OCCUPANCY:
A 1 hr. occupancy separation is required around rooms containing a
boiler or central heating unit greater than 400, 000 BTU input .
-- Sec . 302 . 5
FOR B OCCUPANCY:
A 1 hr. occupancy separation is required around rooms containing a
boiler or central heating unit greater than 400, 000 BTU input .
-- Sec . 302 . 5
ADDITIONAL SEPARATIONS :
A refrigeration machinery room shall be separated from the remainder
of the building as required for an H7 occupancy regardless of area. A
horizontal occupancy separation may be limited to the actual floor
area of the machinery room. Structural supporting elements shall be
protected for the type of construction only. -- Sec . 2802
A 1 hour separation is required from an H4 occupancy. -- Table 3-B
EXIT REQUIREMENTS :
FL NAME NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES
OCC EXITS WIDTH HDWR CORRIDOR SWING
- -- - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - -- - -- - - - - --- - - - - -- - - - - - - - - - - - - - - - - - - - - - -
1 Repair Garage 20 2 4 . 0 No N/A Out 8
1 Storage/Stock Room 4 1 0 . 8 No N/A N/R
1 Other Occupancy 2 1 0 .4 No N/A N/R
1 Other Occupancy 2 1 0 .4 No N/A N/R
1 Other Occupancy 2 1 0 .4 No N/A N/R
TOTAL 30 2 6 . 0 No N/A Out
In areas where 2 exits are required, the minimum separation is 1/2 of
the maximum diagonal of the area or floor. -- Sec . 1004 . 2 . 4
;.�:
�-
:w
I
Page # 8
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
When 2 exits are required, exits must be arranged so that it is possible
to go in either direction from any point in a corridor or hallway to a
separate exit, except for dead ends not exceeding 20 feet in length.
-- Sec . 1004 . 2 . 6
Exit signs are required from all areas where 2 or exits are required.
-- Sec . 1003 . 2 . 8 . 2 , Exception 2
No point to be more than 100 feet from an exit sign.
Main exterior exit doors which obviously and clearly are identifiable
as exits need not be signed when approved. -- Sec . 1003 . 2 . 8 .2 , Exception 1
Door swing is based on Sec . 1003 . 3 . 1 . 5 except as noted.
Occupant load factor is based on Table 10-A.
Number of exits is based on Table 10-A except as noted.
Exit width is in inches and based on Sec . 1003 . 2 . 3 and Table 10-B
Exit width is to be divided approximately equally among exits .
-- Sec . 1003 . 2 . 3 . 2
Width shown for all areas is based on other egress components .
Width shown for 1st floor is based on other egress components .
Width shown for other floors & basements is based on stairways .
-- Table 10-B
For the minimum width of doors, see Sec . 1003 . 3 . 1 . 3
For the minimum width of hallways, see Sec . 1004 . 3 . 3 . 2
For the minimum width of corridors, see Sec. 1004 . 3 . 4 .2
For the minimum width of stairways, see Sec . 1003 . 3 . 3 . 2
FOOTNOTES :
8) The number of exits is based on Sec . 1007 .4 . 1
FLUSH AND SURFACE BOLTS :
Manually operated edge- or surface-mounted flush bolts and surface
bolts or any other type of device that may be used to close or
restrain the the door other than by operation of the locking device
shall not be used. When automatic flush bolts are used, the door
leaf having the automatic flush bolt shall not have a door knob or
surface-mounted hardware . The unlatching of any leaf shall not
require more than one operation. -- Sec . 1003 . 3 . 1 . 8
LOCKS AND LATCHES :
Regardless of the occupant load served, exit doors shall be openable
from the inside without the use of a key or any special knowledge or
effort . -- Sec . 1003 . 3 . 1 . 8
f
I
Page # 9
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
LANDINGS AT DOORS :
1) A floor or landing shall be provided on each side of doors . When
access for persons with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum is 1 inch. -- Sec. 1003 . 3 . 1 . 6
2) Landings shall have a width not less than the width of the stairway
or width of the doorway, whichever is the greater. Where a landing
serves an occupant load of 50 or more, doors in any position shall
not reduce the landing dimension to less than one half it required
width. The minimum length in the direction of exit travel is 44 inches .
-- Sec . 1003 . 3 . 1 . 7
TRAVEL DISTANCE : (distance to an exit)
The maximum travel distance in this building is 200 feet . -- Sec . 1004 .2 . 5 .
Travel distance shall not be limited within an exit enclosure or exit
passageway. -- Sec . 1005 . 2 .2
BUILDING ACCESSIBILITY:
1) This building including each tenant shall be provided with at least
one entrance which complies with the accessible route provisions of
CABO/ANSI A117 . 1 . At least 50 percent of all entrances shall be
accessible . -- Sec. 1103 . 2 . 3
2) When more that one exit is required from any accessible space, each
accessible portion of the space shall be served by not less than two
accessible means of egress . -- Sec . 1104 . 1 . 1
3) When an exit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails . The stairway shall either incorporate an area of refuge
within an enlarged story-level landing or shall be accessed from
an area of refuge. -- Sec . 1104 . 1 .2
The area of refuge shall have direct access to the stairway that serves
it . -- Sec. 1104 . 2 . 1
4) Each area of refuge shall be sized to accommodate one wheelchair space
not less than 30 inches by 48 inches for each 200 occupants, or
portion thereof . -- Sec . 1104 .2 . 3
5) If the area of refuge is not within the stairway, it shall be separated
from the rest of the story by a smoke barrier having at least a one-
hour fire-resistance rating. Smoke barriers shall extend to the roof or
floor deck above . Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes . -- Sec . 1104 . 2 .4
•�
I
Page # 10
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
6) Two-way communications are required. -- Sec. 1104 .2 . 5
7) Each area must be identified by a sign stating AREA OF REFUGE and the
international symbol of accessibility. -- Sec . 1104 . 2 . 7
8) NOTE : Exit stairways in buildings protected throughout by an approved
automatic sprinkler system are NOT required to incorporate an area of
refuge . -- Sec . 1104 . 1 . 2 , Exception 2
ROOFING REQUIREMENTS :
1) The roofing on this building is required to be Class B or better.
-- Table 15-A
2) See section 1504 and ICBO research reports for requirements .
AUTOMATIC SPRINKLER SYSTEMS :
If openings are not provided in each 50 feet of exterior wall or there
is floor area more than 75 feet from an exterior opening, an automatic
sprinkler system is required. -- Sec . 904 . 2 . 2 Note : Openings shall have
a minimum dimension of 30 inches . There must be at least 20 sq. ft . of
opening in every 50 lineal feet of wall .
An automatic sprinkler system is required in an H4 occupancy more than
3000 square feet . -- Sec . 904 . 2 . 5 .2
STANDPIPE REQUIREMENTS :
There is no requirement for a standpipe . - - Table 9-A
FOOTNOTES :
FIRE ALARM SYSTEM:
A manual fire alarm system shall be provided in Group H Occupancies
used for the manufacturing of organic coatings . Smoke detection shall
shall be provided in rooms used for the storage, dispensing, use, and
handling of hazardous materials . -- Sec . 307 . 9
The alarm system is to be as set forth in the Fire Code .
.;
;..
I�
I
I
I
Page # 11
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
VENTILATION:
All areas customarily occupied by humans shall be provided with natural
ventilation by means of openable exterior openings with an area of not
less than 1/20 of the total floor area or shall be provided with a
mechanically operated ventilation system. Such system shall be capable
of supplying a minimum of 15 cubic feet per minute of outside air per
occupant . -- Sec . 1202 . 2 . 1
WALL AND CEILING FINISH:
1) Wall and ceiling finish materials are required to comply with
Sec . 804 . 1 and Table 8-B.
2) Carpeting on the ceiling is required to have a Class I flame
spread rating. -- Sec . 804 .2
3) Textile wall coverings shall have Class I flame spread rating.
and shall be protected by automatic sprinklers or meet the
acceptance criteria of U.B.C. Standard No. 8-2 -- Sec . 805
4) Toilet room floors shall have a smooth, hard nonabsorbent surface
that extends upward onto the walls at least 5 inches .
-- Sec . 807 . 1 . 1
5) Walls within 2 feet of the front and sides pf urinals and water
closets shall have a smooth, hard nonabsorbent surface .
-- Sec . 807 . 1 . 2
INSULATION NOTES :
1) All insulation material including facings are required to have a
flame-spread rating of 25 or less and a maximum smoke density of 450
unless it is in a concealed space and the facing is in contact with
a wall or ceiling. -- Sec . 707 . 3 exc . 2
2) Foam plastic insulations are required to be protected. - - Sec . 2602
�.
,j
i`t
I
it
Page # 12
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
ADDITIONAL REQUIREMENTS :
For H4 occupancy
1) If required by the Fire Code, storage areas for hazardous materials
shall be provided spill control and secondary containment .
-- Sec . 307 . 2 . 3 . 2
If an individual vessel has a capacity of more than 55 gallons or
the aggregate capacity of multiple vessels exceeds 1, 000 gallons,
floors shall be constructed to contain a spill from the largest
single vessel by one of the following methods :
1 . Liquid-tight sloped or recessed floors,
2 . Liquid-tight floors provided with liquid-tight rased or recessed
sills or dikes, or
3 . Sumps and collection system.
Except for surfacing, the floors, sills, dikes, sumps, and collection
systems shall be constructed of noncombustible material and the
liquid-tight seal shall be compatible with the material stored.
-- Sec . 307 . 2 . 3 . 2
2) Smoke and heat venting shall be provided as set forth in the
Fire Code . -- Sec . 307 . 2 . 5
For S1 occupancy
For B occupancy
-- `=
I
.�
I
I
Page # 13
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
ACCESSIBLE FACILITIES :
NOTE: Except as noted, section numbers listed below are from
CABO/ANSI A117 . 1 - 1992
WATER FOUNTAINS AND WATER COOLERS :
At least 50 percent of drinking fountains, but not less than one,
provided on every floor shall be accessible. -- UBC Sec . 1105 .4 . 1
Accessible units must comply with the following:
1) Spout is to be within 36 inches of the floor. -- Sec . 4 . 15 .2 . 1
2) Spout arranged for parallel approach shall be located 3 inches
maximum from the front edge . Spouts of cantilevered units with
knee and toe clearances shall be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
-- Sec . 4 . 15 . 2 . 2
3) Spouts shall provide a flow of water 4 inches height minimum.
-- Sec . 4 . 15 .2 . 3
4) Operable parts shall be located at or near the front edge of the
unit and shall comply with 4 .25 .4 -- Sec . 4 . 15 . 3
5) A cantilevered unit is required to extend 17 inches minimum from
the vertical support . Clear knee space must provide a clear area
of 8 inches in depth at 27 inches high and 11 inches at 9 inches
minimum above the floor. -- Sec. 4 . 15 . 4 . 1
6) Forward approach units shall comply with 4 . 2 . Units in alcoves
shall comply with 4 .2 . 4 .4 . Units not having the necessary knee
I
Page # 14
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
and toe clearance or clear space under them shall comply with
4 .2 .4 and have a clear floor space that allows a person in a
wheelchair to make a parallel approach. -- Sec. 4 . 15 .4 .2
TOILET FACILITIES :
1) A 60 inch diameter unobstructed turning space is required in
the toilet room. -- Sec. 4 . 16 . 3 , 4 . 2 . 3 & Fig. B4 . 2 . 3
2) Water closet shall be mounted adjacent to a side wall or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 in. Sec . 4 . 17 . 1
3) When the accessible water closet is not in a stall :
The clear floor space shall be 48 in minimum in front
of the water closet and 42 in from the center line of the
water closet on the side not adjacent to the wall .
-- Sec . 4 . 17 .2 & Fig. B4 . 17 . 2
4) When the accessible water closet is in a stall :
The stall shall be 60 in wide minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for floor
mounted water closets . -- Sec . 4 . 18 . 3 . 1
If the door swings into the stall, the required depth shall
be increased by 36 inches minimum. -- Sec . 4 . 18 . 3 . 2 &
Fig. B4 . 18 . 3 . 1
5) The bars are to be 33 to 36 inches above the floor and shall
be provided on the rear wall and on the side wall closest to
4
I
Page # 15
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
the water closet . -- Sec . 4 . 24 .2 . 2 & Figs . B4 . 17 . 3 , B4 . 17 . 4
and B4 . 18 . 3 . 1
a) Side grab bar is required to start within 12 inches of the
back wall and extend to 54 inches from the back wall . (The
minimum length of the bar is 42 in) -- Sec . 4 . 17 .4 . 1 &
Figs . B4 . 17 . 3 and B4 . 18 . 3 . 1
b) The rear bar shall be 24 in long minimum, centered on the
water closet . Where space permits, the bar shall be 36 in
long minimum, with the additional length provided on the
transfer side . -- Sec . 4 . 17 .4 . 2 & Figs . B4 . 17 . 3 , B4 . 17 .4
and B4 . 18 . 3 . 1
6) The top of the seat on the water closet is required to be 17
to 19 inches above the floor. -- Sec . 4 . 17 . 3 & Fig. B4 . 17 . 3
7) Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec . 4 . 19 . 2
8) A clear area of 30 X 48 inches minimum is required in front
of the urinal . Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart
minimum. -- Sec . 4 . 19 . 3
9) Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
-- Sec . 4 . 20 .2 . 1 & Fig. B4 . 20 . 3 . 1
10) It shall extend 17 inches minimum from the wall . The clear knee
space shall be 8 inches in depth minimum at 27 inches minimum
above the floor and 11 inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shall be ignored when
checking the clearances . -- Sec . 4 . 20 . 3 . 1 & Fig. B4 .20 . 3 . 1
11) A clear floor space of 30 X 48 inches minimum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4 .20 . 3 .2 & Fig. B4 . 20 . 3 . 2
12) Water supply and drain pipes under lavatories shall be
insulated or otherwise treated to protect against contact .
-- Sec . 4 . 20 .4
13) The bottom of mirror is required to be within 38 inches of
the floor. -- Sec . 4 . 16 . 6 & Fig. B4 . 20 . 3 . 1
:,
�I
I
Page # 16
Code review for:
Project Id. : CEMENT DISTRIBUTORS
Address : 17501 59TH AVE NE
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to be of safety
glazing material . -- Sec . 2406 . 3 & 2406 . 4
Locations :
1) Glazing in ingress and egress doors except jalousies .
2) Glazing in fixed and sliding panels of sliding door assemblies
and panels in swinging doors other than wardrobe doors .
3) Glazing in storm doors .
4) Glazing in all unframed swinging doors .
5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and showers . Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of the glazing is less than 60 inches above a standing surface
and drain inlet .
6) Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24-inch arc of
either vertical edge of the door in a closed position and where the
bottom exposed edge of the glazing is less than 60 inches above the
walking surface .
7) Glazing in an individual fixed or operable panel, other than those
locations described in items 5 and 6 above, than meets all of the
following conditions :
A. Exposed area of an individual pane greater than 9 square feet .
B. Exposed bottom edge less than 18 inches above the floor.
C. Exposed top edge greater than 36 inches above the floor.
D. One or more walking surfaces within 36 inches horizontally of
the plane of the glazing.
8) Glazing in railings regardless of height above a walking surface .
Included are structural baluster panels and nonstructural in-fill
panels .
9) Glazing in walls and fences used as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less than
60 inches above the pool side and the glazing is within 5 feet
of the pool or spa water' s edge .
10) Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edge is less
than 60 inches above the walking surface .
• r .
�, II
._ �
I
I
_ `
I
I
•
CITY OF ARLINGTON
• Building Department
May 23, 1998
Bruce Walden
Cement Distributors Inc.
815 Olivia Park Rd
Everett, WA 98204
RE; Building Permit application 98-2950
Dear Bruce,
The submitted drawings have been reviewed for compliance with the 1994 Edition of the
Uniform Building Code. The following applicable code data corrections and/or additional
requirement are necessary before the permit can be issued.
1. The applicant shall mitigate the cost of full improvement along 59th Ave in lieu of
constructing these improvements. A cost estimate of these improvement is required for review.
2. A no protest agreement in regards to the formation of an L.I.D. along 59th Ave NE.
3. Dedication of right of way along 59th Ave is required.
4. Culverts at the driveways are required to the access of the property.
5. All driveways shall be paved to match existing edge of asphalt and shall have a minimum
of 30' radius on approaches.
6. The sanitary sewer grade will be .30%rather than the .40%indicated because its a 10"
line.
7. The sidewalks need to be moved to the property line to allow sufficient room for meters,
ect in the parking strip.
8. Three hydrant assemblies are required and shall be installed along 59th, at the south end
that will also act as a blowoff for the south leg of the water system. The second hydrant will be
installed at the North end on the north leg of the tee. It will be on its own 8 X 6 valve for the
hydrant. The third hydrant will be required in the truck storage yard at the north property line
within 150 feet of all portions of the shop building.
238 N. Olympic Ave. • Arlington, WA 98223 • (360) 435-0724 • FAX (360) 435-3906
r
i
r
I
I
I
I
9. The 8"tee at station 1+63 needs to be fully valved, add an 8"on the north leg.
10. The ductile water main shall be class 52.
11. The hydrants shall be installed per City standard plan W1. If the domestic water service is
larger than 1", a tee and valve will be required per standard plan W9.
12. The proposed water main location along 59th appears to be under the sidewalk. It should
be in the planter strip between the curb and the sidewalk. If the hydrant does not fit at the
standards location which is 2' from the face of the curb, it must be located behind the sidewalk in
a utility easement. By moving the sidewalk to the property line there should be sufficient room
for the water line. The hydrants will be behind the sidewalk.
13. There should be a 10' general utility easement along the property line on 59th Ave.
14. Although the building is classified as a S3/S 1B occupancy which allows general
maintenance of vehicles without any welding or open flames, it could be construed that if any
welding or open flames and exchange of engine blocks or other major maintenance occurs in the
building it would be classified as an H4 occupancy. Therefore it is recommended that the
underground main fire line be installed to the shop building for future sprinklering of the
building . If a determination is made to change the occupancy based on violations in the building,
it would then be classified as an H4 occupancy which requires it to be sprinkled along with
additional requirements such as ventilation, and containment.
15. No open flames or welding is allowed within the shop building.
16. A one hour fire separation is required between the shop and the storage area. Doors shall
be 20 minute doors.
17. A one-hour fire separation is required between the storage and the lunch room area.
18. The boiler room shall have one-hour separation throughout the walls and the ceiling.
19. Handicap accessibility is required throughout the building. This includes access to the
bathrooms in both the driver lunch room and the driver ready room.
S' PW.
D�vderson 4
Building Official
I
I
4
CITY OF ARLINGTON
Planning and Community Development
May 20, 1998
Gordon E. Nies, CPA
Cement Distributors, Inc.
815 Olivia Park Road
Everett, WA 98204
RE: SEPA#262 Mitigated Determination of Nonsignificance for
Cement Distributors,Inc.
Dear Mr. Nies:
The City of Arlington is informing you that the seven day appeal period ended on May 19, 1998
for the Cement Distributors, SEPA#262.
It has been determined that the environmental impacts must be mitigated through certain actions
on your part, and that additional requirements were place on the project through staff and agency
comments. Enclosed is a copy of the Project Environmental Mitigation Agreement.
Please review the enclosed Mitigation Agreement, sign with a public notary present, and return
original copy to the City of Arlington by June 8, 1998. Once City staff has signed the Mitigation
agreement, the applicant shall recorded it with the Snohomish County Assessor's Office.
The applicant shall sign the attached Waiver of Protest for formation of a local improvement
district. This Waiver shall be signed in the present of a public notary and then recorded with the
Snohomish County Assessor's Office.
A recorded copy of both the Mitigation Agreement and Waiver of Protest shall be submitted to
the City of Arlington. Once these copies are received, your building permit maybe issued.
Sincerely,
W. Burkholder
Director of Planning and Community Devekopment
Enc
sepa\262\gordon.doc
238 N_Olvmoic Ave. • Adinaton.WA 98223 • (360)435-0361 • (360)435-0724
_ �.
T
I
Return Address: City of Arlington
238 N. Olympic Ave.
Arlington,WA 98223
Document Title: Project Environmental Mitigation Agreement
Reference Number: SEPA#262
Grantor: Bruce Walden
Grantee: Arlington, City of
Legal Description: Lot 4 of Short Plat recorded under No. 9608015001,records of
Snohomish County, Washington,being a portion of the Southeast
quarter of Section 22,Township 31 North,Range 5 East,W.M.
Assessor's Property Tax Parcel/Account Numbers: TAX ID#223105-4-017-0005
1
I
I
I
I�
PROJECT ENVIRONMENTAL MITIGATION AGREEMENT
Cement Distributors
4/27/98
SEPA #262
This agreement is entered into by and between the City of Arlington, a municipal corporation,
hereinafter referred to as the "City", and Cement Distributors hereinafter referred to as the
"Developer"
WHEREAS, this agreement is executed pursuant to Chapter 43.21 RCW, the State
Environmental Policy Act (SEPA), and Chapter VII of Arlington's Unified Development Code, to
provide for mitigation of existing and known environmental impacts associated with the development
hereinafter described. This agreement is a voluntary agreement entered into pursuant to the statutes of
the State of Washington. This agreement does not preclude any evaluation and determination by the
City upon later actions or proposals undertaken by the Developer which may require a determination of
significance and environmental review under SEPA and
WHEREAS, the Developer is proposing to construct a 78' x 96' (7,488 sq. ft.) shop and 2,492
sq. ft. office. The Developer is re-locating their current operation from Everett, WA to the Arlington
site, and
WHEREAS, the Responsible Official has made findings that the proposed development will
result in the following probable significant adverse impacts to the environment;
1. Storm water run-off resulting from impervious surfaces and related potential
contamination of ground water from automobile.
2. Traffic impacts of an estimated rate of 80 ADT per day for the new business.
3. Need for provision of water and sewer utilities, to and through the site, to serve this
project and those which may occur.
4. Need provisions of additional fire protection ability in conjunction with construction
and occupancy of Project.
NOW, THEREFORE, the City and the Developer agree that the following mitigation measures
shall be employed by the Developer to ensure that probable significant adverse environmental impacts
created by the proposed project are minimized or eliminated:
mitagre.doc
Page 1 of 5
1
I
I
I
Transportation
1. Full frontage lot improvements along 59th Ave. NE shall include, but not limited to,
curb, gutter, sidewalk, right turn lane for north bound traffic and storm drainage. The
Developer shall submit an engineered cost estimate of these improvements to the
Department of Planning and Community Development. The Developer shall pay for
the construction of improvements that are required as a condition of site development.
If a Street Improvement LID is formed in the next five years, the Developer has the
choice of contributing their fee towards the LID or being reimbursed the amount
contributed for frontage improvements. If the Developer chooses to be reimbursed,
then the Developer shall be required to pay their fair share of the LID improvements.
Payment of this fee shall be made prior to the issuance of a building permit.
2. Developer shall sign a Waiver of Protest for formation of a local improvement district
(LID) for any and all improvements that would benefit this property. The Waiver of
Protest shall be record at the Snohomish County Assessor's Office and recorded copy
submitted to the Department of Planning and Community Development, prior to the
issuance of a building permit.
3. The Developer shall dedicate right-of-way along 59th Ave NE to the City of Arlington
at 30' from center line of road. All dedications shall be completed prior to the issuance
of a building permit.
4. All street construction shall meet the standard City street requirements per the City of
Arlington Public Works Construction Standards and Specification Manual.
5. All areas frequent to street traffic shall be paved and meet the standard street
requirements of the City.
6. The Developer shall pay traffic mitigation fees, prior to the issuance of building permit
for the impacts to 172 St. NE (SR 531) at the following rates:
Transportation Mitigation Requirements
Project Total ADT Mitigation Per Total Mitigation
_ Trips $ Require $
Signalize SR 531 20 $19.12 $382.40
/67th Ave NE
I-5/SR 531 Interchange 60 $85.79 $5,147.40
Improvements
Widening SR 531 80 $54.40 $4,352.00
43rd Ave to 67th Ave
TOTAL 160 $159.31 $9,881.80
mitagre.doc
Page 2 of 5
i
��
i
i
i
Utilities
1. Sanitary Sewer and Water lines shall be extended to the site by the developer at their
expense. The Developer shall submit construction drawings, drawn to City standards,
for review and approval prior to construction. The Developer shall pay the required
connection fees prior to the installation of the services.
2. Additional fire protection maybe required by the Arlington Fire Department. The City
of Arlington will inform the developer of their responsibility during the construction
review process. Fire protection systems shall meet adequate flow standards as required
by the Fire Chief and Director of Public Works.
Recreational
1. The Developer shall pay a parks mitigation fee of $0.05 per gross sq. ft. of total land
area of land being developed for a total of $9,487.37. This shall be paid at the
issuance of the building permit.
General
1. All construction drawings shall be submitted to the Department of Planning and
Community Development. This includes all on and off-site public facilities constructed
as part of this process.
2. Construction shall be limited to the hours between 7:00 a.m. and 7:00 p.m.
3. Approval of the building permit is subject to submittal of an engineered Storm
Drainage Plan and Temporary Erosion and Sediment Control Plan (TESCP) for review
and approval by the Building Department, prior to any site construction. These plans
shall be designed to the Puget Sound Water Quality Manual and AMC 16.10. The
Developer will be responsible for the cost of outside consultant review for the Storm
Drainage Plan.
4. A potential exists that high alkaline runoff will contaminate surface water during the
truck washing process. The developer will be required to implement Department of
Ecology Best Management Practice in order to mitigate this potential problem. Some
of these guidelines are included in DOE Stormwater Management Manual for the
Puget Sound, Chapters 2-3.8.5, 4-2.1.1, and 4-4.2.
5. Steps shall be taken to design and maintain the detention pond to discourage wildlife,
especially birds. Maintenance in the form of routine cutting of plant material that grow
in the pond is critical. The detention pond is a private facility, which the Developer is
required to maintain at their own expense.
6. The Developer shall coordinate with the City and the U.S. Department of Agriculture's
Animal Damage Control office should it appear in the future that hazardous wildlife are
habitating to the area. Also the City and/or U.S. Department of Agriculture's Animal
mitagre.doc
Page 3 of 5
1
I
I
I
Damage Control office may ask the Developer at any time to implement a program that
would discourage wildlife.
7. Adequate measures shall be taken to mitigate noise and visual impacts on the
surrounding parcels. A landscaping plan shall be submitted to the Department of
Planning and Community Development for review and approval. Upon approval the
Developer shall landscape the site per the approved landscaping plans. All landscaping
requirements shall be completed, prior to final certificate of occupancy.
8. All development on this property shall conform to the requirements of the A.A
Investments Short Plat Auditor's File No. 9608015001 and any other conditions tied to
this plat from previous agreements.
9. This document shall be recorded with the Snohomish County Assessor's Office and a
recorded copy submitted to the Department of Planning and Community Development,
prior to the issuance of a building permit. The document shall be signed by all parties
before recording.
mitagre.doc
Page 4 of 5
i
i
"— 'f, 4��4L-
Developer/Owner
State of Washington)
) ss
County of Snohomish)
On this day personally appeared before me 1. 6-UCZ L OL-Oer1_, to me known to be the individual
described in and who executed the within and foregoing instrument, and acknowledged that j2e, signed
the same as h;S free and voluntary act and deed for the uses and purposes therein mentioned.
1 Fr
Given under my hand and official seal this 20 day of 1998.
AE. S �-
Iory f O P LIC in and for e Sta`ee f Washington
'I ° NOTARY 90 residing
--)-*E-- My appointment expires — 13 —aCCC
on PUBLIC =
-A 8-13-2000 �o
J
4Ci4Arllimngton
State of Washington)
) ss
County of Snohomish)
On this day personally appeared before me u S 0 Idec to me known to be the individual
described in and who executed the within and foregoing instrument, and acknowledged that '(� jsigned
the same as free and voluntary act and deed for the uses and purposes therein mentioned.
Given under my hand and official seal this 20 day of 1998.
E. SyFA
Q` �%ON E.�-A �
�9�o i Y� IC in and fo State f Washington
o NQ��R� residing V Z--L
�o�
P�g1.�C oz My appoin nt expires LL g-13 -A G
s ti3-2000 �;
mitagre.doc
Page 5 of 5 OF II p�j�\�
I
I
I
I
Return Address: City of Arlington
238 N. Olympic Ave.
Arlington, WA 98223
Document Title: Power of Attorney and Covenant Not to Protest Formation of
Improvement District
Reference Number: SEPA#262
Grantor: Bruce Walden
Grantee: Arlington, City of
Legal Description: Lot 4 of Short Plat recorded under No. 9608015001, records of
Snohomish County,Washington,being a portion of the Southeast
quarter of Section 22, Township 31 North,Range 5 East, W.M.
Assessor's Property Tax Parcel/Account Numbers: TAX ID #223105-4-017-0005
�I
I
I
P-QWEP OF—ATTORNEY AND COVENANT NQT TO PRQTE_ST
FO�LA'T'TON QF IMPROVEMENT DISTRIQT
The undersigned are the owners of the following described real
property in Snohomish County, Washington:
Lot 4 of Short Plat recorded under No. 9608015001, records of
Snohomish County, Washington, being a portion of the Southeast
quarter of Section 22, Township 31 North, Range 5 East, W.Mj.
The undersigned has filed and application for the following
permit, land use, or other development proposal :
CeMert—D� sr_siblit-org, Lnc (SEpA 11 262) -
FOR AND IN CONSIDERATION of approval of the above described
permit, land use, or proposal, the undersigned do hereby agree and
declare as follows :
(1) Power of Attorney— The undersigned hereby and make,
constitute and appoint the City of Arlington as their true and
lawful attorney in fact for the sole purpose of signing a letter,
notice, petition, or other instrument initiating, furthering, or
accomplishing the formation of a local improvement district under
RCW 35 . 43 as now enacted or later amended, for the purpose of the
following: Any-and all j=rovement thatwould benefit the proper v.
(2) Release of Power of Attorney Following installation of
the ultimate improvements contemplated by this agreement, this
City shall, on request of developer, deliver a signed release of
this power of attorney.
1
r
(3) Binding Effect _ The foregoing power of attorney and
agreement not to protest shall be binding upon the undersigned,
their heirs, successors and assigns, and shall constitute covenants
running with the above described property for a period of not more
than ten years from the date of its execution. Developer agrees
not to protest formation of said local improvement districts ,
provided that, however, this agreement shall not limit the rights
of an owner to object to said owner' s individual assessment or
determination of special benefits, or owner' s right to appeal to
the Superior Court the decision of the City Council affirming the
final assessment roll .
I
I
I
Bruce Walden
STATE OF WASHINGTON)
) ss
COUNTY OF SNOHOMISH)
On this day personally appeared before me Bruce Walden, to me known
to be the individual described in and who executed the within and
foregoing instrument, and acknowledged that II( signed the same as
` i17 free and voluntary act and deed for the uses and purposes therein
mentioned.
Given under my hand and official seal this__ day of 11 -U.
�A E. Sy
�Q ION
NOTARY/�N�o NOT P LIC in an r tl�e State of
--�°E Washington, residing at
PUBLIC o= My Appointment Expires - -
y,� 8-13-2000
�F
. �_
I
1
I
I
City of Arffiigt n
�3uEi7jg �e�artJri�n
Fax Cover Sheet
Date: Number of pages to follow: T_
Response needed As requested FYI /
TO: G
FERvl: S
FAQ: z1Z5- P en—? !? 7G
FROM:
RE:
Additional comments:
238 N. Olympic Ave. Arlington, WA. 98223 (360) 435-0724 FAX (360) 435-3906
`I � �'.
•.;��
�. � �. '
•�
,,
4
�. _ �
_ _.,
, :
• � �, �� .y
'�
n
�.
•
4 CITY OF ARLINGTON
Building Department
April 14, 1998
Bruce Walden
Cement Distributors Inc.
815 Olivia Park Road
Everett,WA 98204
RE; Required submittals for application for building permit.
Dear Mr.Walden,
I have reviewed your initial application for a building permit have determined it to be incomplete.The
following additional information is required before the review process can begin.Failure to comply wi&these
requirements may result in further delays or stopping the Sepa process until a completed application has been
submitted.
1 1. A Narrative of the storm drainage design.
✓2. Storm Drainage calculations of the proposed design.
6 The proposed site plan shows two buildings,only one has been submitted
✓4.Structural calculations for the building.
SA floor plan of the repair garage area showing any pits,ventilation requirements,overhead doors,man
doors,windows,bathrooms,offices,and any other misc.rooms.
,/6.If the buildings are to be heated,energy calculations are required as per the Washington State
Nonresidential Energy Code.
If you have any questions please give me a call at 360 435-0724.
eid
y,
n�.Anderson
Building Official
___ .. AA;— .+-- train 001)'�Pfl . earn Aq;;-f1794 • FAX (360) 435-3906
CITY OF ARLINGTON
Planning and Community Development
May 19, 1998
Ryan C. Zulauf
Washington State Department of Transportation
Aviation Division
8900 East Marginal Way South
Seattle, WA 98108-4024
RE: SEPA#262 Cement Distributors,Inc.
Dear Mr Zulauf:
Staff appreciates your comments on SEPA#262 for Cement Distributors, Inc.
Staff has taken into consideration your concern for the detention pond that is associated with the
development of the Cement Distributors, Inc. parcel. The applicant will be required to meet
standards that are acceptable to the routine maintenance of detention ponds that will help
discourage wildlife, especially birds. In the event the detention pond becomes an inhabited area
for wildlife in the future, the applicant will be required to meet standards set by the City and the
U.S. Department of Agriculture's Animal Damage Control Office.
These requirements are reflected in the final draft of the Mitigation Agreement.
If you have any questions,please feel free to contact myself or John W. Burkholder.
Sincerely,
Ryan C. Larsen
Staff Planner
zulauf.doc
238 N.Olympic Ave. - Arlington,WA 98223 - (360)435-0361 - (360)435-0724 - FAX(360)435-3906
1
,ti
I
I
CITY OF ARLINGTON
Planning and Community Development
May 19, 1998
Cayla D. Morgan
U.S. Department of Transportation
Federal Aviation Division
1601 Lind Avenue, S.W.
Renton, WA 98055-4056
RE: SEPA#262 Cement Distributors,Inc.
Dear Ms Morgan:
Staff appreciates your comments on SEPA#262 for Cement Distributors, Inc.
Staff has taken into consideration your concern for the detention pond that is associated with the
development of the Cement Distributors, Inc. parcel. The applicant will be required to meet
standards that are acceptable to the routine maintenance of detention ponds that will help
discourage wildlife, especially birds. In the event the detention pond becomes an inhabited area
for wildlife in the future, the applicant will be required to meet standards set by the City and the
U.S. Department of Agriculture's Animal Damage Control Office.
These requirements are reflected in the final draft of the Mitigation Agreement.
If you have any questions, please feel free to contact myself or John W. Burkholder.
Sincerely,
Ryan C. Larsen
Staff Planner
morgan.doc
238 N.Olympic Ave. • Arlington,WA 98223 • (360)435-0361 • (360)435-0724 • FAX(360)435-3906
r �i
I
CITY OF ARLINGTON
Planning and Community Development
May 19, 1998
Geoffery W. Crofoot
Environmental Health Division
3020 Rucker Avenue, Suite 104
Everett, WA 98201-3900
RE: SEPA#262 Cement Distributors, Inc.
Dear Mr Crofoot:
Staff appreciates your comments on SEPA#262 for Cement Distributors,Inc.
Staff has taken into consideration your concerns for potential high alkaline levels left from the
washing of trucks and equipment by Cement Distributors, Inc. The applicant will be required to
meet the standards of the Department of Ecology's Stormwater Manual for the Puget Sound
Basin. These requirements are reflected in the final draft of the Mitigation Agreement.
If you have any questions,please feel free to contact myself or John W. Burkholder.
Sincerely,
Ryan C. Larsen
Staff Planner
crofoot.doc
238 N.Olympic Ave. • Arlington,WA 98223 • (360)435-0361 • (360)435-0724 . FAX(360)435-3906
� � +'
I
V
CITY OF
C[*ARTRIENT0F COMMUNITY DE14 IPK8ENT
238 N. O|Vmpio, Arlington, VYA9&223
DATE JOB NO
q,,T'�oV��n� [] �n�nr P!an�"rw
Phone (2�f_7�} 435'0724 FAX (2D6) 4%5'30O6
TO
WE ARE SENDING YOU O Attached O Under separate cover via the following hems:
»
O Shop drawings O Prints O Plans O Samples O Specifications
O Copvof|otto, O Change order O
COPIES DATE NO. DESCRIPTION
THESE ARE TRANSMITTED oo checked below:
O For approval O Approved as submitted O Resubmit -copies for approval
O For your use O Approved an noted O Submit---------copies for distribution
OAsrequested O Returned for corrections O Return-------_corrected prints
�
[A For review and comment O
O FORBIDS DUE 19 ____-__- O PRINTS RETURNED AFTER LOAN T0US
REMARKS
^
�
COPY TO �
�� RECYCLED PAPER: �
��Contents:40m Pre-Consumer^,omPost-Consumer SIGNED:
If enclosures are not ao noted,kindly notify uoaxonce. |
4J/ r
1-f�1 �nt sa in�- -
April 21, 1998
Mr. David W. Anderson
Building Official
City of Arlington
238 N. Olympic Avenue
Arlington, WA 98223
Subject: Engineering Plan Review
Concrete Distributors, Inc. @ 591h Avenue N.E.
Dear Dave:
I am forwarding two copies of this letter confirming our agreement, whereby the City of Arlington
(CITY) requests that Berryman & Henigar (B&H) perform civil engineering plan review services on
the above referenced project. B&H will conduct the review for conformance to the ordinances and
requirements listed on the Jurisdictional Information Sheet, which we currently have on file. We will
conduct an initial review of the plans (for grading and stormwater), and storm drainage calculations,
plus up to two additional follow-up reviews. It is our understanding that the CITY will compensate
B&H in the amount of $1,600.00, on a lump sum basis. It is agreed that B&H will be compensated
for the review of system redesigns, submitted by the applicant after the initial review is underway, on
an hourly basis, at current B&H billing rates.
Please indicate your agreement by signing both copies of this letter, retaining one original for your
files and returning the other to our office. Our receipt of the signed documents shall constitute your
authorization for B&H to perform the work. Initial review comments will be forwarded to the applicant
within two weeks of work authorization. B&H in no way warrants or guarantees the accuracy of the
applicant's (Concrete Distributors, Inc.) design.
We are looking forward to this opportunity to provide engineering services to the City. If you have
any questions, please do not hesitate to call me at (206) 505-3400.
Sincerely, 1
Berryman & Henigar ACCE 7D:
� r
I
Michael A. Pawla , P.E. City of Arlin t
Vice President
Civil Engineering Division - Seattle Date: `
Attachment
Concrete Distributors,Inc.\File:A:\Conc Distr\AGMT0421.DOC
- �.
j,
1
04/22/98 WED 07:27 FAX 12065053406 BERRYMAN HENIGAR 191 001
s
r
INC. j
S
FAX TRANSMITTAL
DATE: April 22, 1998
TO: David W. Anderson, Building Official
FIRM: City of Arlington
FAX NUMBER: 1-360-435-6055
SUBJECT: Engineering Plan Review
FROM: Mike Pawlak
NUMBER OF PAGES (INCLUDING THIS COVER SHEET): 2
COMMENTS:
Dave, would you please sign this and fax it back. Two copies of the original
letter are in the mail. Thanks.
1215 41h Avenue, Suite 1400 • Seattle, WA 98161-1001 • (206)505-3400 • FAX(206) 505-3406
FORM M 0009 Revised May,1997
YF
N
1
16 -
1
M 1. Ll
-- • E - � -el
�� ti� tilt J u
- ' e one �� V
-
. - ■:7
04/22/98 WED 07:27 FAX 12065053406 BERRYMAN HENIGAR IM 002
B .., / ►ar
nI t ake nyl
April 21, 1998
Mr. David W. Anderson
Building Official
City of Arlington
238 N, Olympic Avenue
Arlington, WA 98223
Subject: Engineering Plan Review
Concrete Distributors, Inc. aGU 59th Avenue N.E.
Dear Dave: _.
r
I am forwarding two copies of this letter confirming our agreement, whereby the City of Arlington
(CITY) requests that Berryman & Henigar (B&H) perform civil engineering plan review services on
the above referenced project. B&H will conduct the review for conformance to the ordinances and
requirements listed on the Jurisdictional Information Sheet, which we currently have on file. We will
conduct an initial review of the plans (for grading and stormwater), and storm drainage calculations,
Plus up to two additional follow-up reviews. It is our understanding that the CH'Y will compensate
B&H in the amount of $1,600.00, on a lump sum basis. It is agreed that B&H will be compensated
for the review of system redesigns, submitted by the applicant after the initial review is underway, on {`
an hourly basis, at current B&H billing rates.
Please indicate your agreement by signing both copies of this letter, retaining one original for your
files and returning the other to our office. Our receipt of the signed documents shall constitute your
authorization for B&H to perform the work. Initial review comments will be forwarded to the applicant
within two weeks of work authorization. B&H in no way warrants or guarantees the accuracy of the
applicant's (Concrete Distributors, Inc.) design.
We are looking forward to this opportunity to provide engineering services to the City. If you have
any questions, please do not hesitate to call me at(206) 505-3400
Sincerely, -
Berryman & Henigrar _ _ ACCEPTED:
D
4-
R
Michael A. Pawlak, P.E. City of Arlington
Vice President
Civil Engineering Division- Seattle Date:
Attachment
Concrete Distributors,IncAFile:A:%Conc Distr\AGMT0421,DOC
.G
_sc
w
� � a
i = a
� F1 .t "
Al
_ MIN ■
� N 3 N y '0 �_��0 � �
� mV�'
fD '0 _� � �
:.
� lQ \ � T ��
N � �
� �. o.
� -� e
a
� � �� W
\ y � N � (�(V��\ � � a
V � �
I'u
y
� �
� � � " �
V
C
�� �
� � �
IT
r�
/\
(V(�A\ � G
YV Cv
C fi
ffl
C
`�t
L!�
..
�...
y �-r
(,V^
V' �
n
n
C�
�9
n
C
�G
4 4,
T :1r
t � i
r i i
r
i
i
Z
i�
i i
r, -
i t:
_ - f
r
i
i
�1
BUIZDIN�,x PERMIT APPLICATION �,=CKLIST
RES & DUPLEX CONIM & IND
APPLICATION ✓ APPLICATION
SITE PLAN ✓ SITE PLAN
ARCH. DRAWINGS ARCH. DRAWINGS
STRUCT DRAWINGS STRUCT DRAWINGS-►'�'`
LEGAL DESCRIPTION ✓ LEGAL DESCRIPTION
ENERGY CALCS ENERGY CALCS ,, nt,
STORM DRAINAGE ✓ STORM DRAINAGE N°
SEPTIC TANK DESIGN ✓ SEPA CHECKLIST(my kt'14
✓ UT11= DRAWINGS
STRUCT CALCS
Three ( 3 ) copies of each are required Four ( 4 ) copies of each are required
for at)plication for avplication
ZONING SETBACKS: FRONT
USE REAR
LOT COVERAGE SIDE
PERMIT TRACE ING
Name: U�r LME-K) Permit #:
Project Type: S Mp+ Leff -A o Date Received
DISTRIBUTED RETURNED DISTRIBUTED .." RETURNED
�� Public Works — 2-0 --9 9 Eng QAng
L — 19 Fire Dept John Farrens
Date returned for corrections
Date resubmitted with corrections I�� �C'� , �Qge
Date ready to issue: Date issued:
B u►1alfbrmslchecidst
.� - ..
� "
�
� -
s
.
/
|
|
/
|
/
.
CITY OF ARLINGTON
Building Department
PLANNING AND ZONING REVIEW
I. ZONING COMPLIANCE:
A. Zone Classification
B. Permit Use: Yes No
C. If no, extension of non conforming use:
D. Minimum lot size required:
Shown
E. Yard Requirements:
Required Shown
1. Front
2. Side
3. Rear
F. Height limitations, Maximum
G. Landscaping and plan required: Yes No
H. Parking:
1. Off street parking required: Yes No
2. Plan provided: Yes No
3. Adequate parking provided: Yes No
II. LOT COVERAGE:
A. Allowed: More/Less
Shown: Approved
DETERMINATION OF S.E.P.A. CATEGORICAL EXEMPTION
Action / Application Title: SFR Brief Description Of Action: EXEMPT
Code reference allowing exemption: W.A.C.197-11-800 1(b)
Person making determination:
Date:
ACCOUNT NO. FILE CITY OF ARLINGTON
WATE -"3, SEWER DEPARTMENT APPLICA' ')N
Application is hereby made by the undersigned property owner for all water and sewer service uir�sed f� an
purpose at !S�( ��` Ave �G in or near Arlington, Washington, for which gree in �gpnc ��
7'�X 7P 2 2310�— 4-017- 0005— �` !
and in accordance with existing ordinances and regulations of the City, the following estimated char the exact charges will J
be determined and payable immediately upon completion of the installation: r
Engineering Fees. . . . . . . . . . . . $
Water Main Extension. . . . . . . . . . . . . $
Fire Hydrant Installation . . . . . . . . . . . . . . . . . . . . . . . . $
Street Repairs. . . . . . . . .L`.� . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $
Tap-In Charge. . . . . . . . . . . . . . . $
Equalization Fee n . . . . . . . . . $
M Water Service Connection Charge (Metering Charge) . . . . .I $ " —
z O O Y
(�, H W Q U
= o I U 'n a Sewer Main Extension. . . . . . . . . . . . . . . . . . . . . . . . . . $= (n W -
in 0, U
NU) Z C Sewer Main Reimbursement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $
►— 0 cc ° C Zp
U
Side Sewer Permit(s). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $
C= OC Z J 7
o 4 _
Sewer Servic( . . . . . . . . .
to
DOD
� air •-.
m 'd W z C. Total. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $ 2_0
I further agree that al! rates and charges for water and sewer service to the above property shall be paid in accordance with
existing ordinances and regulations of the City, or any such ordinances and regulations passed hereafter. PS
I ea�ne.v►t �isfy�bu�svl to haveT u
I hereby authorize the following tenantE�( Acq kll�u alley' fAPdkdINGTOPI
kept in his name under Account No. with the understanding that water bills mailed to said tenant shall
not relieve the property from liability for water charges incurred.
I understand that the City will use all reasonable effort to maintain uninterrupted service, but reserves the right to shut off
the water at any time without notice for repairs, extensions, non-payment of rates or any other reason and assumes no liability
for any damage as a result of interruption of service from any cause whatsoever. V
3-Y/� �
OWNER DATE ADDRESS
C�ii
..
1 l '
i
1 City of Arlington Building Deli
PUBLIC WORKS DEPARTMENT CHECKLIST
�cj _5 C� DATE 9
�i
PERNII�# �t<. �--
ACCOUNT #
NAME: �1 . f_ L /��2�-44
ADDRESS: f 7.5—D/ 5-1 mk zv LEGAL:
BUILDING USE: # OF BUILDING UNITS:
TOTAL ERU DESIGN UNITS:
Item is inspected and complete
Eidsting Required SIGNATURE: Date
WATER METER REQUIRED:
HEALTH DEPT. APPROVAL:
SIDE SEWER PERMIT REQUIRED:
GARBAGE CONTAINER PAD:
CROSS-CONNECTION CONTROL:
BACKWATER VALVE:
SEWER REQUIRED: Off site
On site
CURBS: Off site
On site
SIDE WALK: Off site
On site
PAVING: Off site
On site
STORM DRAINAGE: Off site
On site
PRETREATMENT DISCHARGE PERMIT: YES NO
WATER/SEWER FEES PAID: YES NO
Build\fomis\u-check
7 •T . _ I
- 1JliT 1 ■'rNi 71'11�f 11111 `- F _ — — — Ap r um rL it •o
n
do's! Lb M LEI I■ 5 111
.Y 1N' Ir13 ' lil '"I R ■r No 1'il
1 ■ 1 1 ■ •
1 . • .I
■ r ! oI Ong, II r'mm, -
v Niel
.try It ' r'
1 ' r• a
1 '
I
or MY L10 VOU ` L J. V • 1• ■ 1i r
y _ _
erg, /00 ��l
City of Arlington Building Der. J
PUBLIC WORKS DEPARTMENT CHECKLIST
PERMIT # /Al DATE
ACCOUNT # ��}}
NAME: 1 1 _r/ P 4/
ADDRESS: LEGAL: _
BUILDING USE: # OF BUILDING UNITS:
TOTAL ERU DESIGN UNITS:
Item is inspected and complete
Existing Required SIGNATURE: Date
WATER METER REQUIRED:
HEALTH DEPT. APPROVAL:
SIDE SEWER PERMIT REQUIRED: 4r
GARBAGE CONTAINER PAD:
CROSS-CONNECTION CONTROL: '
BACKWATER VALVE: �.
SEWER REQUIRED: Off site —7� �✓r
On site
CURBS: Off site
On site
SIDE WALK: Off site
On site
PAVING: Off site //►► ' I
On site —' ,1, t1 RECEIVEL
STORM DRAINAGE: Off site APR 2 1999 z
On site r �-�- /43•-6 i
CITY OF ARLINGTON
PRETREATMENT DISCHARGE PERMIT: YES v/. NO
WATER/SEWER FEES PAID: YES NO �Z
I3uilcffonnsAj-check
- m m m
- - - WIN - - - -
1
I�
I I
11 L = C C = 7 Z 70 C I Q -
�- I
I
I
I I I
I
I
I
I
I
City of Arlington Building Dep
PUBLIC WORKS gj?6RTN[ENT' CHECKLIST
PERMIT # MAY 0 6 1998 DATE 9 �S
ACCOUNT # CITY of ARLINCITON
NAME: �'� _ r' f )XV L 1'41 &11v' &,o
ADDRESS: Al f'_. LEGAL:
BUILDING USE: # OF BUILDING UNITS:
TOTAL ERU DESIGN UNITS:
Item is inspected and complete
Eidsting Required SIGNATURE: Date
WATER METER REQUIRED: ✓
HEALTH DEPT. APPROVAL: If&
SIDE SEWER PERMIT REQUIRED: `/
GARBAGE CONTAINER PAD:
CROSS-CONNECTION CONTROL: p
BACKWATER VALVE:
SEWER REQUIRED: Off site ✓
/rwfl u/A-T%:VL- On site
CURBS: Off site
On site
SIDE WALK: Off site
On site
PAVING: Off site
On site
STORM DRAINAGE: Off site
On site
PRETREATMENT DISCHARGE PERMIT: YES ✓ NO
WATER/SEWER FEES PAID: YES NO
IIuild\forms\u-chtc:k #
• J
J 4
1 I R ,u•I
- 1�1� 111�1-Z �I 1�r _ ■ 1 11 1 1 1 ■
I
I
TL,n ■
• —_ — -yJrl ' } 1 1f1 I 111 1. I 1 �1 5t_ _ 1 ' I 1
u■1 I 11 - 1 1N' P O■ I_ 1 I _1 I
�• 1 1 1 1 1 T� ` L 11 -1 J 1 1
IS
'LLOMT-4- - 1111 L[I 1�
I
�J 11-- J I S I h
- I
IL1 1
I
I I I I 1
a � J
I IT 1 _ 11 1 IN 1'. - I 1 1
�.I1 1 `• 1 1 I IT I I
I
MEMO
To: Cristy Brubaker
From: Marc Hayes
Subject: CDI Construction Review
Date: May 5, 1998
1. Applicant shall mitigate the cost of full frontage improvements along 59th Ave. in lieu of
constructing these improvements. Please have an engineers cost estimate drafted for our
review.The improvements included curb,gutter,sidewalk,road widening and storm drainage.
2. The applicant shall sign a no protest agreement in regards to the formation of an L.I.D. along
59th Ave. N.E. Should an L.I.D. occur,the mitigation funds shall be credited towards the
proportionate share of the project.
3. The dedication of right of way along 59th Ave. still needs to occur.
4. Since the frontage improvements will not be constructed,the installation of culverts at all
driveways will be required.
5. All driveways shall be paved to match existing edge of asphalt and shall have a minimum of
30' of radius on approaches.
To: Dave Anderson
From: 'ferry Castle
Date: 4-23-98
Subject: Cement Distributors Building Permit
Having reviewed the construction drawings as subnutted dated 4-6-98,I have the following
comments:
The sanitary sewer grade will be .30%rather than the .40%indicated because it's a 10" line.
The sidewalks need to be inoved to the properly line to allow sufficient room for meters, etc in the
parking strip.
Two hydrant assemblies must be installed along 59th, one at the south end that will also act as a
blowoff for the south leg of the water system. The second hydrant will be installed at the north
end on the north leg of the tee. It will be on it's own 8x6 tee with 6" valve for the hydrant. These
locations will allow for water department use,flushing, and so on. There will probably be
additional hydrants required by the fire department.
The 8" tee at station 1+63 needs to be fully valved, add an 8" on the north leg.
The ductile water main shall be class 52.
The hydrants shall be installed per City standard plan W 1fIf the domestic water service is larger
than 1" a tee and valve will be required per standard plan.W9.
The proposed water main location along 59th appears
=t sidewalk. It should be in
the planter strip between the curb the sidewa%it i e standard location which is
2' from the face of the curbs
The hydrants will be behind the
sidewalk.
There should be a 10' general utility easement along the property line on 59th.
" -
1 �v A U4 t
WATER DEPARTMENT MEMORANDUM
TO: Bruce Walden(Cement Distributors Inc.)
FROM:' Karen Latimer
DATE: May 3, 1998
SUB7: Cross-Connection Control Review
Building Permit#98-2950
I have completed my review of the construction drawings submitted with building permit 498-
2950. Listed below are my comments and questions.
1. a. What size of water meter(s) is required?
b. Will one meter serve both the shop and office?
2. Will a fire sprinkler system be installed?
3. Will a landscape irrigation sprinkler be installed?
4. Complete and return the Cross-Connection Survey and Industrial/Commercial Waste
Discharge Permit Application. Complete one form for each building (mailed separately
May 4, 1998).
5. Attached is a copy of the procedures for New Water Main Construction and Backflow
Prevention Requirements for New Water Main Construction.
After I receive the requested information I will complete a final cross-connection control review
and notify you of all construction requirements.
Please do not hesitate to contact me at (360) 435-3811 if you have any questions.
r
New Water Main Construction
1. Backflow prevention requirements shall be completed prior to beginning construction.
See attached procedure.
2. Purity test must be completed prior to conducting pressure test.
3. Pump will not be hooked up to hydrant service or blow-off assembly until city water
inspector is present.
4. Barrels used to pump out of must be new or used only for this purpose (inspector's
discretion).
5. 200 psi must be maintained for 15 minutes.
6. Pressure will be bled off after testing.
7. Flush once more after pressure testing is complete.
Blocking:
Call for inspection before pouring.
Call for inspection after pouring.
-� r
• A.
Backflow Prevention Requirements for New Water Main Constniction
1. Install State approved Double Check Valve Assembly (DCVA) in location specified by
City water inspector.
a. Call City water department before installing DCVA to verify it appears on the state
approved list.
b. DCVA shall be installed in a temporary vault or other suitable configuration so no
portion of the DCVA is covered with dirt or other material.
C. Plugs shall be placed in all test cocks (4).
2. Contractor shall have DCVA tested by a State approved Backflow Assembly Tester. A
copy of the test report must be submitted to the City water department for review and
approval, prior to calling for inspection.
3. Call for inspection of the DCVA (after test report has been submitted). 24 hours
minimum notice required.
4. The DCVA shall not be removed from service without approval of the City water
inspector.
5. During the hydrostatic pressure test, the DCVA shall be removed, unless sterilization and
satisfactory bacteriological sampling has been achieved.
'---) City of Arlington Building Dep+---)
FIRE DEPARTMENT CH ECKL,� .
PERMIT # DATE: - / 9 9
NAME: �'u. (!F'_. L.J /a J ,01-4
ADDRESS: ,L ,� « / ..'S(f �Q' /�V� �-F' LEGAL:
BUILDING USE: OCCUPANCY CLASSIFICATION:
A B E F H
F172 12.1 131 4 1 1 2 = 1 1 2 1 1 2 1 3 1 4 1 5 1 6 1 7
I M R S U
1.1 L 1.2 1 2 1 3 1 1 1 3 1 1 1 2 3 4 1 5 1 2
TYPE OF CONSTRUCTION
I II III 1V V
F.R. F.R. ONE-HOUR N ONE-HOUR N H.T. ONE-HOUR N
Item inspected&completed
Site Plan: Approved Denied Signature & Date:
Access Requirements:
Required:
Fire lane:
Sprinkler system:
Alarm system:
Knox Box:
Fire extinquishers:
Hydrant:
#of hydrants required:
Location of Hydrant:
Location of Knox Box:
Location of Fire Extinquishers:
Fire Flow requirements:
Location of address on building:
FIRE DEPT: Date:
Signature
Build\focm\fdchecklist
IL
iL
t■ IJ J �I[ Ii r,#■ r 1 f 16. ■ ■ItI ]Im 'j�l■i u■ is
''
S m Jmmr�
T i I VI, IA I
F r �- [
I - T I, -)IJ."4 ergn -14i■ I
r I if I I I
IN L ■1 1 11 1 1 11 ` 1d[■ 'Ll I 4 jo l rf'n ik.I
■ I Rio ITWI AIV %MW 1 Il
III 1 +`� �_ ■ r
h 1 _LI
- JI I L��
' =1 J +,IL• w
■IrILM _ILrII
I tW
ti II 1
- II 1 11
1 ■ ■ ' 1 ,1 � 7 I
I T'4jr, Aril
iCity of Arlington Building Dept
TIRE DEPARTMENT CHECKL.h ,'
PERMIT # _ �� q .�_ DATE: _ /
7
NAME:
ADDRESS: ,L�7.`i(� 1 S �. t�IrG LEGAL: I Q _i—w1—Q 1 "7 —nr>rn .,;a:"
BUILDING USE: OCCUPANCY CLASSIFICATION:
A B E F H
F712 12.1131 4 1 1 2 1 3 1 2 1 1 2 3 ' 4 If 5 1 6 1 7
I M R S U
1.1 1 1.2 1 2 3 11 1 3 1 1 1 2 3 4 5 1 2
TYPE OF CONSTRUCTION
I II III 1V V
F.R. F.R. ONE-HOUR N ONE-HOUR. N H.T. ONE-HOUR N
Item inspected&completed
Signature & Date:
Site Plan: Approved 1^- Denied
Aeess Requirements:
Required:
Fire lane:
Sprinkler system: �►tL
Alarm system: C, ����v:� v4'/ '7-1isS j
Knox Box: r
Fire extinquishers:
Hydrant:
# of hydrants required:
Location of Hydrant: ; x �Ll y y vti a. ie ECE IV ED
Location of Knox Box: /4 4-IA-
Location of Fire Extinquishers: - i�'e ,r,Lry `
Fire Flow requirements:
Location of address on building:
FIRE DEPT: Date: < `
A-Signat"e
Bu i Id\form\fdchecklist
` i ` II _ - - - - -
III
pmI = - I -
I
I.
- - - - - - ■ mm' - i ■ &' -r ■ ■ - ■ - - _ -` it t -ice-
it
I I
ti
IN -
I�
I
r -
oil ■ ■I
■ _f - - . ■ - ■ - - - - r ■ ■ .
I
II
I
q -' I
1994 Washir__ n State Nonresidential Energy Code Cory 'ance orm
f Organizaflon of •
/ IQyt N'ashinpron Stare Enerpy Cooc Compliance Forms April,199a
This document introduces the forms to be used All projects should.complete the Summary forms
for showing compliance with the 1994 Nonresi- which apply (envelope, mechanical and/or light-
dential Energy Code (NREC). The following fig- ing). All projects should also review the Checklist
ure shows the overall organization of the form forms to make sure all necessary information on
set. For simple projects, only a few forms are compliance is provided. Applicable excerpts from
required; more complex projects will require addi- the General Requirements sections of the Code
tional forms. The forms explain the decision cri- are reprinted on the back of the Checklist forms.
teria for determining when a more complicated The need for other forms will be determined by
form is required. project specifics.
ENV Checklist
What goes on
plans?
Where it goes
Reprint of
ENV Summary General Reqmts.
Project information
Type of project
Compliance opts.
Glazing area% ENVSTD
Can use simple? r
Summ.o1 Req. Component
Performance
Worksheet
Target&Pro-
posed UA
Wid.Avg.SHGC
Area Adjustment
MECH Ckist
What goes on
plans?
Where it goes
MECH Reprint of RECEIVED
Summary General Reqmts.
Project information
Type of project MAY 111998
Compliance opts
Can use simple? Complex
systems CITY OF ARLINGTON
Basic equip
efficiencies Additional
Checklist and gy— �;L 9-5
decisionmaking
for Complex Motors
Systems Checklist
For any project
with motors cov-
ered by 1437 or
LTG Summary LTG Checkist 1511
Project information What goes on
Type of project plans?
Compliance opts. Where it goes
Can use most Reprint of
simple? General Reqmts.
Allowed and
Proposed Watts
1994 Washinaton State Nonresidential Energy Code Compliance Form
'Forms
The following is a list of the 1994 nonresidential compliance forms their use.
Envelope
ENV-SUM Envelope Summary - Use this form for all projects where envelope work is to be done;there are sepa-
rate versions for Climate Zone 1 and Zone 2. Show basic project information, compliance options chosen, summary
list of required insulation levels and U•factors. Back side has Decision Flowchart for Prescriptive Option and calcu-
lation to determine area weighted Heat Capacity for the ►Masonry Option. '
ENV-CHK Building Permit Plans Checklist-Comprehensive list of all information required on plans for all op-
tions, including the Component Performance and Systems Analysis Options. Also includes space for building de-
partment notes.
ENV-UA Envelope UA Calculations- Use this form if using the Component Performance Option; there are sepa-
rate versions for Climate Zone 1 and Zone 2. Summary calculations of Target UA and Proposed UA. Back side has
calculation of Target and Proposed SHGC, and calculation of glazing and opaque target area adjustments, if needed.
Mechanical
MECH-SUM mechanical Summary- Use this form for all projects where mechanical work is to be done. Show ba-
sic project information, compliance approach chosen, list of basic'.
asic equipment & efficiencies (else this information
goes on equipment schedules on the plans). Back side has Decision Flowchart for Simple System option.
MECH-CHK Mechanical Permit Plans Checklist-Comprehensive list of all information required on plans for all
options, including the Component Performance apd Systems Analysis Options. Also includes space for building de-
partment notes.
M, ECH-COMP.Mechanical - Complex Systems - Use this form if using the Complex Systems Option..Complex
Systems Checklist has additional information required on plans for this Option. Decision flowchart is provided for
determining which Complex Systems requirements apply to the project.
MECH-MOT Electric Motors Checklist for electric motors compliance and schedule of installed motors, both for
mechanical systems and other equipment.
Lighting
LTGSUMM_ Lighting Summary- Use this form for all projects where lighting work is to be done. Basic project in-
formation, compliance approach chosen, alteration exceptions. Calculations of Allowed and Proposed Lighting
Power for both Interior and Exterior Lighting if using the Lighting Power Allowance Option. Back side has questions
to determine if project qualifies for the Prescriptive Option. Also has Lighting Power Allowance table/footnotes.
LTG-CHK Lighting Permit Plans Checklist-Comprehensive list of all information required on plans for all op-
tions, including Component Performance and Systems Analysis. Also includes space for building department notes.
1994 Washington State Nonresidential Energy Code Compliance Form
• � Climate Zon�
1D'r[Wash-npton State Nonresidential Energy Code Compliance Forms Apnl.1PP[
Decision Flowchart Use this flowchart to determine if project qualifies for the optional Prescriptive Option.
for Prescriptive Option If not,either the Component Performance or Systems Analysis Options must be used.
l 1302 Space Heat Type:For the purpose of eetermrning building envelope Electric Resistance:Space hcsbnp systems which use electric resistance elements
requrtamonts.the lollowng two cateporirs compnse all space heating types: I as the pnmary heabnp system including baseboard.radiant and lotted air units
Outer:AV met space heating systems including gas,soled fuel,oil,and propane S`aA J where the tout electric tesrstance heal rapacity exceeds1'v'1.0rre of..me gross
space heating systems and those systems listed in the exception to elf-tne � condrboned floor area. Exception:Heat pumps and terminal electric resistanre
resrrance. (continued at right) y heating in vana ble air wlume distribulion systems.
Elecbie
Resistance
no\`Heat? . yes
All ,�• Masonry\ % WI
< walls R-11 11'aIl Creena OKi>4 ', walls R-19
wnsutsbont•'no \(bbelow)!' yes Ys�.(below) no
r
An Insulation Installed? I I ; All insulation installed? All Insulation Installed? All Insulation Inralied?
Opaque Walls R-11 Opaque walls R-11 (Opaque walls Rog Opaque Walls R-19
:Below grade walls(ext) R-10 :Masonry walls lint) U-0 19 Masonry walls(int) U-0.19 j Below grade walls(eat) R-10
Belo++grade wails(grit)R-11 :Masonry walls(clheh U-0.25 INasonrywalls(other) U-0.25 i,&Jl
Below grade walls(amr)R-19
]ROD%enter at,;s R-30 I Below grade walls(exl) R-10 IBelow grade walls(ext) R•10 Roos over otb� R-38
:AII other roofs R-21 tl Below grade walls(otter)R-11 I y Below grade walls(atnr)R-19 other roofs R-30
;Floors over uneond sp. R.19 Roes over an cs R•30 ;Roofs over aria R-38 Floors over uncond. R-30
;.Sias-0n gode R•11) , A JI Cher roo s I R-21 Al Met roots R-30 SlainDryyrade R-10
Radiant floors R-10 ;Floors over uncand.sp. R-19 �Floo:s over uncond. R•30 ]Radiant floors R-10
Opaque doors U-0 60 I IStabson-on R-10 Stnbson graae R•10 Opaque doors U-0 Ed
I I 'Radiant floors R-10 Ramantfloors R•1D
Opaque doors U-0 60 Opaque doors U-0 6D
Glaring Critma Met? l Glazing Cmeria Met?
I Glrin -Veit OH Glazing Vert OH
l 9 Glazing Cmera Met? I I Glazing Crrtena Met?
kea% U u SHGC I Area% U U SHGC
I OS75ab o 9D 1 e5 100 'Glazing Vert OH I Glazing Vert OH 00.2D% DAD 0 80 1 DD
I 15.20% 0.75 1[0 1 DD I j kea% u U SHGC kea% U U SHGC
l 2D-3^% 0 6D 130 06 t ml1 % 090 1 45 1 DD I 00-2m 0 40 0 60 1 DO yes I no
j 3D40e6 0.50 1.25 D[5 I 15 2JSG 075 1 40 1 DO
20.30% D 60 130 D 65 yes no
no I !yes 1 30-[D% 050 1.25 DO
r
1 } i no I i yes
I l 1 li Presenpv.ro
• j I 1 Pxtn,vlav+ed
J 1
3 r r +Carnp-rneny Ferforrranct or
1 Systems Analysis Required
Concrete/Masonry Option" Wall Heat Capacity (HC) 'If the area
weighted heat
Assembly Description Assy.Tag HC— Area(so HC x Area capacity(HC)of
the total above
grade wall is a
minimum of 9.0,
the Concrete
Masonry Option
may be used.
"For framed
walls,assume
HC=1.0 unless
calculations are
provided;for all
other walls,use
Totals Section 2DD9.
Area weighted HC:divide local of(HC x area)by Total Area
1994 Washinoton State Nonresidential Eneray Code Com fiance Form
April.IPP4
'PSs 1S'ashinpron Slte Nonresroent1al Enerpr Coce Compl,ance Forms
Project Info
Project Address Date
For Building Department Use
Applicant Name:
Applicant Address:
Applicant Phone:
Project Description New Building ❑ Addition ❑Alteration ❑ Change of Use
=(S&ei'si,,,
❑ Component Fertorrnance ❑ ENVSTD ❑ Systems
Compliance Option owchart(over)for qualifications) Analysis
Space Heat Tye ❑ Electric resistance All other (see over for definitions)
Total Glazing Area
Glazing Area Calculation (rough opening) Gross Exterior
Note:Below grade walls may be included in the (vertical 8 overhd) divided by Wall Area times 1 DO equals 'A Glazing
Gross Erclerior Wall Meg it they are insulated to _ �/ 00
the level required for opaque walls. I / X
v
v l
Concrete/I�iasonry Option ❑ Check here it using this option and it project meets all requirements for the ConcreieRJ.esonry Option. See
Decision Flowchart(over)for qualifi"tionz. Enter requirements for each qualifying assembly in the fable below.
I
Envelope Requirements(enter values as applicable) Opaque ConcreteJMasonry Wall Requirements
Fully heated/cooled space Insulation on interior-maximum U-factor is 0.19
Minimum insulation R-values Insulation on exterior or integral-maximum U-factor is 0.25
Roofs Over Attic If project qualifies for ConcreteJNasonry Option,list walls
with HC a 9.0 Btu/P,'•'F below(other walls must meet
All Other Roofs - Opaque Wall requirements). Use descriptions and values
Opaque Walls E—)q from Table 2D-5b in the Code.
Below Grade Walls Wall Description U-factor
Floors Over Unconditioned Space (including insulation R-value& position)
Slabs-on-Grade
Radiant Floors 2—le
Maximum U-facfors
Opaque Doors Q
Vertical Glazing
Overhead Glazing
Maximum SHGC(or SC)
VerticaVOverhead Glazing
Semi-heated space-
Minimum Insulation R.values
Roofs Over Semi-Heated Spaces' I )e_
'Refer to Section 1310 for qualifications and requirements
Noles:
1994 Washingn,, State Nonresidential Energy Codc ;,mpliance Form
Apnl.IPFd
Pr
1 PFA w,'aahmpMon State Eneipy Code Compnance Forma
oject Address Date
The following information is necessary to check a building permit application for compliance with the building envelope requirements in the
1%Iashington State Nonresidential Energy Code.
AppticzbdHy Code location Building Department
(circle one) Section Component Information Recuired on Plans Notes
GENERAL REQUIREMENTS Sections 1301-1314
1301 SCOpe Uncondflioned spaces identified on mans if allowed
1302 I Space heat pe
g
na. Electric resistance
n.z Other Indicate on plans that electric resistance heat is not allowed
n.a. 1310.2 Semi-healed spaces Semi-heated spaces identified on plans if allowed —.7
1311 I Insulation
yes o-n 2. 1311.1 1 Insul.installation Indicate denshies and clearances
no n.a. 1311.2 Roof/ceiling insul. Indicate R-value on roof sections for attics and other roofs;
Indicate clearances for attic insulation;
Indicate baffles if eave vents installed;
Indicate face stapling of faced balls
yes no n.a. 1311.3 Wall insulation Indicate R-value on v,all sections;
Indicate face stapling of faced barts;
Indicate above grade exterior insulation is protected;
Indicate loose-fill core insulation for masonry walls as necess;
Indicate heat capacity of masonrywalls
if masonry option is used or if credit taken in ENVSTD;
yes' no n.a. 1311.4 Floor insulation Indicate R-value on floor sections;
Indicate substantial contact with surface;
Indicate supports not more than 24"o.c.;
Indicate that insulation does not block
airflow throuah foundation vents
yes(fio;)n a. 1311.5 Slab-on-grade floor Indicate R-value on v.all section or foundation detail;
Indicate slab insulation extends down vertically 24"from top;
Indicate above orade exerior insulation is protected
ea o n.a. 1311.6 Radiant floor Indicate R-value on wall section or foundation detail;
Indicate slab insulation extends down vertically 36"from the top;
Indicate above grade exterior insulation is protected;
Indicate insulation also under entire slab where reo d.by Official
yes no n.a.l 1312 Glazing and doors Provide calculation of glazing area(including both vertical
vertical and overhead)as percent of gross wall area
yes no n.a. 1312.1 U-factors Indicate glazing and door U-factors on glazing and door
schedule(provide area-weighted calculations as necessary);
Indicate if values are NFRC or default,if values are default
then specify frame type,glazing layers,gapwidth,low-e
coatings,gas fillings
yes no n.a. 1312.2 SHGC 8 SC Indicate glazing solar heat gain coefficient or shading
coefficient on glazing schedule(provide area-weighled
calculations as necessary)
1313 Moisture control
ves no n.a.1 1313.1 Vapor retarders Indicate vapor retarders on Harm side
yes no n.a. 1313.2 Roof/ceiling tiap.ret. Indicate vapor retarder on roof section;
Indicate vao.retard.with sealed seams for non-wood strue.
ves no n.a. 1313.3 Wall vapor retarder Indicate vapor retarder on wall section
es no n.a.1 1313.4 1 Floor tiapor retarder Indicate vapor retarder on floor section
es no n.a. 1313.5 1 Crawl space vap,ret. Indicate six mil black po'yethvtene overlapped 12"on ground
1314 Airleakaoe
yes no n-a. 1314.1 Bldg.envel.sealing Indicate sezhng,caulking,gasketing,and weatherstripping
ves no n.a 1314.2 JGI.LzinprdDDr sealing Indicate weatherstripping
yes no n.a 1314 3 Assemb.as ducts Indicate sealino,caulking and casketin
PRESCRIPTIVE/COMPONENT PERFORMANICE (Sections 1320.23 or 1330-34
yy no Envelope Sum.Form Completed and attached.
Provide component performance worksheet if necessary
Provide ENVSTD screen 1 output if necessary
If no Is circled or any question, provide exp anatlon:
1994 Washington State Nonresidential Energy Code Compliance Form
M Apnl.'I PSG
f'PF<1YasrmQron Sare Enerst Coot Compliance Forma --
Unlabeled glazing and doors shall be assigned the default U-factor in
Envelope - General Requirements Section2DDs.
1311 Insulation 1312.2 Solar Heat Gain Coefficient and Shading Coefficient:Solar
1311.1 Ins W12lion Requirements: All insulation materials shall be Heal Gain Coefficient(SHGC),shall be determined,cc Need and labeled
clicns 10 achieve proper in accordance with the National Fenestration Rating Council(NFRC)
installed according to the mantfaclwefs instru
densities,mointoin cicoronces,and maintain uniform R•values,To the Standard by a certified,independent agency,licensed NFRC.
maximum extent pcssible,insulation shaf extend over the full component Exception: Shading coefficients(SC)shall be an acceptable
area to the intended R-value, alternate for compliance with solar heat gain coefficient
1211.2 RooflCeiling Insulation:open•blewn or poured loese-fill requirernenls. Shading coefficients for glazing shall be taken from
insubtion may be used in attic spaces where the slcpe of the ceiling is Chapter 27 of Standard RS-27 or from the manufacturer's lest
not more than 3112 and there is a1 least thirty inches of clear distance data.
from the top of the bottom chord of the truss or ceiling joist to the 1313 Moisture Control
underside of the sheathing at the roof ridge.When eave vents are
installed,baffling of the vent openings shall be provided so as to deflect side(i Vapor Retarders:Vapor retarders shall ec installed on the warm
the incoming air above the surface of the insulation. side(in winter)of insulation as required by this section.
V,'here lighting futes are recessed into a suspended or exposed grid Exception;Vapor retarder installed with not more than 113 01 the
x
cei'.ng,the foot/ceiling assembly shall be insulated in a location other than
nominal R-value be,,,een i and the conditioned space.
directly on the suspended ceiling. 1313.2 Roof/Ceiling Assemblies:Roo!keiling assembles where the
Exception Type IC rated recessed lighting fixtures. ventilation space above the insulation is lets than an average of twelve
inches shall be provided with a vapor retarder.Rooflceiling assemblies
Where installed in wood framing,faced batt insulation shall be face without a vented airspace,where neither the roof deck not the roof
stapled. structure are made of wood,shall provide s continuous vapor retarder
1311.3 Wall Insulation:Exterior wall cavities isolated during framing with taped seams.
shall be fully inn Malec to the levels of the surrounding walls.�%Ihen Exception'Vapor retarders need not be provided where all of
installed in wccc fit,ming,faced batt insulation shall be face stapled, the insulation is instated between the roof membrane and the
Above grade exterior insulation shall be protected. st`uctural roof deck.
1311.4 Floor Insulation: Floor insulz.an shall be installed in a 1313.3 Yjalls:Walls separating conditioned space from unconditioned
permanent manner in substantial contact with the surface being insulated. space shall be provided with a vapor retarder.
Insulation supports shall be installed se spacing is not mote than twenty- 1313.4 Floors:Floors separating conditioned space from unconditioned
four inches on center. Installed insulation shall not block the airflow t space shall be provided with a vapor retarder.
through foundation vents,
1313.5 Crawl Spaces:A ground[aver of six mil(0-D:6 inch thick)black
1311.5 Slab-On-Grade Floor: Stab on-grade insulation installed inside potyethytene or approved equal shall be laid over the ground within crawl
the foundation wall shall extend downward from the top of the slab a spaces.The ground cover shall be overlapped twelve inches minimum at
minimum distance of twenty-four inches or to the top of the focEng, the joints and shall extend to the foundation wall.
whichever is less. Insulation installed c:^side the foundation shall extend Exception:The ground cover may be cmitled in crawl spaces
downward a minimum of twenty-four inches or to the frostline,whichever if the crawl space has a -oncrele slab floor wr.)a minimum
is greater.Above grade insulation shall be protected. thickness of three and one-hag inches.
Exception:For mono!::is slzbs,the insulation shall extend 1314 Air Leakage downward from the tc ep of the slab to the bottom of the footing, g
1311.6 Radiant Floors(on or below grade): Slab-on-grade i-isu:ation
1314.1 Building Envelope:The reauuemena of this section shall apply
shall extend downward from the top of the slab a minimum distance of to building elements separating conditioned from unconditioned spaces.
thirty-six inches or downward to the top of the fooling and horizontal for an Exterior joints around windows and door frames,openings between walks
aggregate of not less than thirty-six inches. and founcation.between walls and roof and watt panels:openings at
penetrzbons of utility services through walls,fbors,and roofs:and all
If required by the building official where soil conditions warrant such other openings in the building envelope shall be sealed.caulked,
insulation,the entire area of a radiant floor shall be thermally isolated from gzsketed,or wealhersiripped to limit air leakage.
the soil. Where a soil cas control system s provided betew the radiant 1314.2 Glazing and Doors:Doors and operable glazing separating
Mot.which results in increased eonve.lir a flow below the radiant floor, conditioned from uneondr,ioned space shall be weatherstnpped.Fixed
the radiant floor shall be thermally isolated from the sub•f10ef gravel layer. windows shall be tight fitting with glass retained by stops with sealant or
1312 Glazing and Doors caulking all around.
1312.1 Standard Procedure for Determination of Glazing and Door Exception:openings that are required to be fire resistant.
U-Factors:U-factors for glazing and doors shall be determined,certified
1314.3 Building Assemblies Used as Ducts or Plenums:Building
and labeled in accordance wnh Standard RS-31 by a certified
independent agency 4:ensed by the National Fenestration Rating Council assemblies used as ducts or plenums shall be sealed,caulked,and
(NFRC).Compliance shall be based on Model Size AA or ES.Product gasketed to limit au leakage.
samples used for U-factor determinations shall be production line units or
representaitive of units as purchased by the consumer or contractor.
1994 Washino'1 State Nonresidential Energy Cod omDliance Form
-,PP<w'ashmyon Slate NomesedenhaI EneipyCDce Compfance Fc+mt April.1PPd
Project Address Dale
Space Heat Type ❑ Electric resistance All other For Building Department Use
Glazing Area as%gross exterior Hall area %
ConcreteAlasonry Option ❑ Yes ❑ No
Notes:If gazing area exceeds maximum allowed in Table,then calculate adjusted areas on back(over). If Concrete/Masonry Option is used,
Target U-factors,SHGC and Glazing%will be different than shown below. Refer to Table 13-1 for correct values.
Building Component Proposed UA Target 11A
List components by assembly ID 8 page# U-factor x Area(A) =UA(U x A) U-factor x Area(A) =UA(U x A)
U= Plan ID:
U= Plan ID: Glazing% Electric Resist. Other Heating
o, U= Plan ID: 0-15% 0.40 0.90'
c
d _
U= Plan ID: >15-20%, 0.40.
> C9 U= Plan ID: >20-30% not aliam�i
U= Plan ID: >3040% not a9mved 0.50:'
U= Plan ID: (see Table 13-1 for CorrWas.anry values)
U= Plan ID:
U= Plan ID: Glazing% EJectric Resist. Other heating
U= Plan ID: 0-15% .0.80 1.45
o c
r 'R U= Plan ID: >15.20% 0.80 1.40
d �
p U= Plan ID: >20-30% not alowed 1.30
U= Plan ID: >3D-4M not alowed 1.25
U= Plan ID: (see Table 13-1 for Conc.?lasonry values)
U= Plan ID:
a g JU= Plan ID: Electric ResisL Other Pleating
O U= Plan ID: 0.60 0.60
` R= Plan ID:
$ R= Plan ID: Eieciric Resist. Other heating
IR= Plan ID: 0.031 0.036
R= Plan ID:
d
s $ R- Plan ID: Electric Resist. Other hating
G Cr- R= Plan ID: 0.034 0.D5D
" R= Plan ID:
R= Plan 10:
R= Plan ID:
R= Plan ID: Electric Resist. Other heating
d
R= Plan ID: Odnary 0.052 0.14
R= Plan ID: Metal stud 0.11 0.14
R= Plan ID: Conc(int)• 0.19 0.19
R= Plan ID: Conc(oth)• 0.25 0.25
w R= Plan ID:
m
3 R= Plan ID: Electric Resist. Other Heating
m m- R= Plan ID: Ordinary 0.062 0.14
c9 R= Plan ID: Metal stud 0.11 0.14
d ci R= Plan ID:
O c R= Plan ID: Electric Resist. Other Heating
$ R= Plan ID: ; 0.029 0.D55
u- � R= Plan 10:
R= Plan ID:
V
R= Plan ID: Electric Resist Other Heating
A
N as R= Plan ID: F=0.54 F=0.54
R= Plan ID: (see Table 13-1 for radian floor►•akres)
.For CIAU walls,indicate core insulation material.
Totals Totals
For compliance:
1)Proposed Total Area shall equal Target Total Area,and 2)Proposed Total UA shall not exceed Target Total UA.
1994 Washington State Nonresidential Eneray Code Comr)liance Form
• • • •
IPPA Washington Slate Nomesioential EnelpyCode Comp. .e Fofms Apnl,1PE4
Vertical Glazing Proposed SHGC Target SHGC
List components by assembly ID 8 page# SHGC' x Area(A) =SHGC x A SHGC x Area(A) =SHGC x A
Plan ID:
Plan ID: Glazing% Electric Resist, Other Heating
e Plan 1D: 420% 1.00 1.00 .
z N >20-30% not allowed
d A Plan ID:
> 0 Plan ID: >30-40% not allayed 0.45
Plan ID: (see Table 13-1 for Conc/h'zsonry i alues)
'Note:Manufacturer's SC may be used in lieu of SHGC. I Totals
otals
For compliance:
1)Proposed total area shall equal Target Total Area,and 2)Proposed Total SHGC shall not exceed Target Total SHGC.
Overhead Glazing Proposed SHGC Target SHGC
List components by assembly ID 8 page# SHGC' x Area(A) =SHGC x A SHGC x Area(A) =SHGC x A
to Plan ID:
Glazing% Electric Resist. Other Heating
Plan ID:
0-20% 1.03 1.00
O Plan 1D: >2D-30% not arc,,:,d 0.65
s Plan ID:
d Plan ID: >301.0% not allowed 0.45
O Plan ID: (see Table 13-1 for ConcR.!zsonry values)
'Note:Manufacturer's SC may be used in lieu of SHGC.
Totals Totals
For compliance:
1)Proposed total area shall equal Target Total Area,and 2)Proposed Total SHGC shall not exceed Target Total SHGC.
• 1 ons
If the total amount of glazing area as a%of gross exterior wall area(calculated on ENV-SUM)exceeds the maximum allowed in Table 13-1,
then this calculation must be done. Use the resulting areas in the Target UA and SHGC calculations above.
Proposed Areas: Numbered values are used in calculations below.
Roofs over Attics Other Roofs Walls
2:OG= 3:VG= Note:
Glazing Area 1:OG= OG=overhead glazing
Opaque Area 4: 5: 6: VG=vertical glazing
Gross Exterior Wall Max Glazing Area Maximum Taroet
Area (Table 13.1) Glazing Area
X % - 100 = T
Target OG Area in Roofs over Attics Taroet OG Area in Other Roofs
1: Max OG Remaining 2' Target VG Area For Target OG's,circle
— and use the lesser
7
II lesser(circle) = e: `� lesser(circle) = 9: values both here and
7: 6: below.
Proposed Opaque Area Proposed OG Area Tar_oel OG Area W Target Opaque Area
Roofs over Attics 4: + 1: — 10: = 13:
Other Roofs 5: + 2: _ 11: _ 14:
Total Target OG Area(sum x10 4 1111) 12: -
Proposed Opaque Area Proposed VG Area Target VG Area Target Opaque Area
1Nalls 6: + 3: — 9: = 15:
Note: If there is more than one type of wall,the Target VG Area may be distributed among them,and separate Target Opaque Areas found.
Target values 9.12.13.14& 15(shaded boxes)are used in the applicable Taroet UA calculations on the front.
Target values 9 8 12 are also used in the applicable Target SHGC calculations above.
1994 Washington State Nonresidential Eneray Code Cain fiance Form
IPE<Wasmngron Stale Noniewennal Energy Code Compliance Forms April.IPP4
Project Info Project Address Date
For Building Deparlment Use
Applicant Name:
Applicant Address:
Applicant Phone:
Project Description -rU�,Q L 4',4r44:5;
Briefly describe mechanical system
type and features.
b Simple System ❑ Complex System ❑ Systems Analysis
Compliance Option (See Decision Flowchart(over)for qualifications)
Equipment Schedules The folloning information is required to be incorporated with the mechanical equipment schedules on the
plans. For projects without plans,fill in the required information below.
Cooling Equipment Schedule
Equip. OSA CF?vl SEER
ID Brand Name' Model No.' Capacity Total CFM Econo or EER IPLV' Location
r
I I
I I
I
I I I
Heating Equipment Schedule
Equip. OSA cfm
ID Brand Name' Model No.' Capacity Total CFM Econo Input Btuh Output Btuh Efficiency'
I
I �
Fan Equipment Schedule
Equip.
ID Brand Name Model No.' CFM SPI HP/BHP Flow Controls Location of Service
I
I
'If available. 2 As lesled according to Table 141.142 or 14-3. 'If required. 'COP.HSPF,Combustion Efficiency,or AFUE,as applicable.
s Flow control types:VAV,constant volume,or variable speed.
1994 Wa'shingio` hate Nonresidential Energy Code Cor--kliance Form
1454 WssRng.on Swl Navesioer6e'Energy CDO CWVI `t FW"d I lv�nl, 9Fd
System Description if HeatinglCooting ❑Conslanivol? ❑i4r cooled? ❑Pact:zged s�,s? El<54,000 Sluh?
See Section 1421 for tun description of or Cooling OnV- ❑Split system? ❑Economiser included?
Simple S�,Sicm qualifications. If Heating Only, <5DOO cfm? ❑<70%outside air?
Decision Flowchart Use this flowchart to determine if project qualifies for Simple System Option If not,either the
Complex Syslem or Systems Analysis Options must be used.
Sta rt
System T HeatinolCoolin onstan
y yPe or Cooling Only olume no
yes
Heating OnI
Ir Cooled.
no
<5000 cim
yes yes
4no Reference r
Sec.1421
ackace
<70%OA yes stems no
yes
no
54,000 Btu Split
no r 1900 cfm (stem no
yes
yes
Includes
Econo? Reference 54.000 Btu
no yes Sec.1423 r 1900 cfm no
yes
Simple System
AI'owed
j<
Reference
Sec. 1420
4Use Complex Reference
System Sec. 1430
Complex Systems Refer to MECH-COMP Mechanical Complex Systems for assistance in determining vfitch Complex
Systems requirements are applicable to this project
1994 Washingi—) State Nonresidential Energy Code (,ompliance Form
yp;4 ygsn,np,onSwe Ene,prCode Compla�ce Foams Rpnl,tpp�
Project Address Dafe� �
—, The folIDVAng information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the
Washington State Nonresidential Energy Code.
Applicabiliy Code Location Building Department
(circle one) 1 Section Component Information Required on Plans Notes
HVAC REQUIREMENTS (Sections 1401-1424)
1411 1 Eopmt performance
es. no -n a. 1411.4 Pko.elec.htq 8 cl . I List heat pumps on schedule
Veers no n.a. 1411.1 IJlinimum efficiency I Equipment schedule with type,capacity.efficiency
1 1412 1HVAC controls
es�no n a.1 1412.1 1Temperature zones I Indicate I>-atior.s on p.ar,s
es no n a.1 1412.2 1 Deadband control Indicate 5 decree deadband minimum
es no n a.1 1412.3 1 Humidify control I Indicate humidistat
Yes no n a.l 1412.4 IAvion-atic setback Indicate thermostat v,t,h nioht setback and 7 different da s
Yes no n.a. 1412.4.1 1 Dampers I Indicate damper location and automatic controls
yes no r,z 1 4125 Heat pump control I Indicate microprocessor on thermostat schedule
yes no n.a.1 1412.6 Combustion hi . Indicate modulating or staoed control
yes no n a.1 1412.7 Indicate balancing features on plans I
yes no n a 1 1422 Thermostat interlock Indicate thermostat inlerlock on plans
yes no n a.l 1423 Economizers I Equipment schedule 1
1 1413 Air economizers
Yes no n a.1 1413.1 Operation Indicate 100%capability on schedule
yes no n.a.l 1413.2 Control Indicate controls able to evaluate outside air
yes no n.a.l 1413.3 1 Integrated operation Indicate capability for partial coolin 1
1 1414 Duclinc sysiems
yes no n.a.l 1414.1 I Duct sealino Indicate sealing necessary
Yes no n a.l 1414.2 1 Duct insulation I Indicate R-value of insulation on duct
Yes no n.2.1 1415.1 1 Piping insulation I Indicate R=value of insulation on piping
Yes no n.e.l 1424 1 Separate air sys. I Indicate separate systems on plans
r_ no Mech.Sum.Form Completed and a;,ached. Equipment schedule with types,
input/oulout.efficiency,cfm,hp,a:onomizer
SERVICE WATER HEATING AND HEATED POOLS (Sections i4-0-i454
1440 1 Service water htg.
yes no n a.1 1441 1 Elec.rater heater I Indicate R-10 insulation under lank I
yes no n.a.1 1442 1 Shur-off controls Indicate automatic shut-off 1
1 1450 1 Heated pools
yes no n.a.l 1452 Pool eater heaters Indicate not electric resistance
yes no n.a.l 1453 Pool heater controls Indicate switch and 65 decree control
es no n.a.1 1454 Pool covers Indicate vapor retardant cover
es no n a.1 1454 Pools 90+degrees Indicate R-12 pool cover
I no is circled or any question, provide explanation:
1994 Washington State Nonresidential Energy uode 1,01TIp112ince corm
Aprd,1PPI
•.994 Wash.npron Sate E,py Cooe Compliance Forms
Mechanical - General Requirements economizers
shall
Operation: Building Heating Energy:Air
economizers shall be capable of prov.ding partial cooling even when
1412 Controls additional mechanical cooling is requited 10 meet the remainder of the
cooling load. Controls shall not preclude the economizer operation when
1412.1 Temperature Controls:Each sy,tern shall be provided with at mechanical cooling is tequited simultaneously.
least one temperature control device.Each zone shall be controlled by Exception: Economizers on individual,direct expansion,cooling
individual thermostatic controls responding to temperature whhin the zone, P
At a minimum,each floor of a building shall be considered as a separate systems with capacities not greater than 75.000 Btu/h may
include controls that limit simultaneous operation of the
zone. economizer and mechanical cooling for the purpose of preventing
1412.2 Deadband Controls:When used to control both comfort heating ice formation on cooling coils.
and cooling,zone thermostatic controls shag be capable of a deadband of at
least 5 degre-es F whin which the supply o!heating and cooling energy to 1414 Ducting Systems :
the zone is shut off or reduced to a minimum. 1414.1 Sealing: Duct work which is designed to operate 21 pressures
Exceptions: above V2 inch water column static pressure shall be sealed in accordance
1. Special occupancy,special usage,or code requirements where with Standard RS•18. Extent of sealing required is as folic vs:
deadband contro!s are not appropriate. 1- Static pressure: 112 inch to 2 inches;seal transverse pints.
2. Buildings complying with Section 1141-4.if in the proposed
_ 2. Static pressure: 2 inches to 3 inches;seal all transverse pints
buuding energy analysis.sis,heating and cooling
- thermostat setpoints are set to the same temperaturo and longitudinal seams.
between 10 degrees F and 75 degrees F inclusive, 3. Static pressure: above 3 inches;seal all transverse pints,
and assumed to be constant throughout the year. longitudinal scams and duct wag penetrations,
3. Thermos=That require manual changeover between heating 1414.2 Insulation: Ducts and plenums that are constructed as part of the
- and cooling modes. building envelope shall meet the requirements of Chaplet 13. Other ducts
1412.3 Humidity Controls:If a system is equipped wit a means for and plenums shall be thermally insulated per Table 14.5.
adding moisture,a humidistat shall be prcwded. Exceptions:
1412.4 Setback and Shut-Off:HVAC systems shall be equipped with 1 Within the HVAC equipment
automatic controls capable of accomplrshing a reduction of energy use
through control setback or equipment shutdown during periods of non-use 2, Exhaust air ducts not subject to condensation.
or alternate use of the spaces ser by the system.The autoratic controls
ved 3 Exposed ductwork within a space that serves that space only.
shall have a minimum seven-day clock and be capable of being set for
seven different day types per week. 1415 Piping Systems
Exceptions: 1415.1 Insulation:Piping shall be thermally insulated in accordance with
1. Systems serving areas which require continuous operation at the Table 14-6.
same temperature set;dlnt. Exception:Piping installed within unhary HVAC equipment
2. Equipment with full k:ad demands of 2 kW(6.E26 Blu.'h)or Ic=s
may be controved by readily accessible manual off- Water pines outside the n Szztoned space shall be insulated in
hour controls. accordance w h Wzshnon S�:e Plum bind Code p�'AC 51.26)
1412.4.1 Dampers:Outside air intakes,exhaust oute:s and relief outlets
serving conditioned spaces shag be equipped with dampers which close 1420 SIMPLE SYSTEMS(PACKAGED UNITARY EQUIPMENT)
automatically when the system is off of upon power failure. Stair shaft and
eievator shah smoke•relief Openings shall be equipped wGh normally open 1421 System Type:To qualify as a simple system,systems shall be one of
dampers. These dampers shall remain closed in normal Operation until the following:
activated by ne fire alarm syslem of other approved smoke detection a• Air cooled,constant volume packaged equipment which provide
system. heating,cooling or both,and require only external
connection to duct work and energy services.
Exceptions:
1. Systems serving areas which require continuous operation. b. Air cooled,constant volume split systems,which provide heating,
2. Combustion air intakes. cooling or both,with cooling capacity of 54.000 Btulh
1412.5 Heat Pump Controls:Unirry air cooled heat pumps shall include or less.
microprocessor conlro!s that minimbe supplemental heat usage during C. Heating only s)•slems which have a capacity of less than
start-up,set-up,and defrost conditions. These controls shall anticipate cfm or which have a minimum O=cir air suppllyyf o of
need for heal and use compression heating as the first stage of heat less than 70 percent of the total air elicitation.
ConL ols shag indicate when supplemental heating is being used through AA other systems shall comply with Sections 1430 through 1438.
visual means(e.g..LED indicators).
1422 Controls: In addition to the control requirement in Section 1412,
1412.6 Combustion Heating Equipment Controls:Combustion heating where separate heabng and cooling equipment sere the same temperature
equipment with a capacity over 225,ODD Btuth shall have modulating or zone,thermostats shall be interlocked to prevern simuGaneous heating and
staged combustion control. cooling.
Exceptions: 1423 Economizers: Economizers meeting the requirements of Section
1. Boilers. 1413 shal:be installed on packaged roof top fan-cooling units having a
2. Radium Heaters. supply capacity of greater than 1,900 cfm or a coal cooling capacity greater
1412.7 Balancing:Each air supply out'et or air or water terminal device than 54,ODD Btulh.
shall have a means for balancing,including but no;lirrtfed to,dampers. The total capacity of all units without economizers shag not exceed
temperature and pressure test connections and balancing valves. 240,0OD Bturn per building.
1413 Air Economizers 1424 Separate Air Distribution Systems:Zones with special process
1413.1 Operation: Au economizers steal:be of at.?omatically modulating tempetz!ure requirements and/or humidity requhemenis shall be served by
outside and relum air dampers 10 provide 1O0 percent of the design supply separate air distribution systems from those serving zones requiring only
air as outside air to reduce of eliminate the need for mechanical cooling• comfort conditions.
1413.2 Control: Air economizers shag be controlled by a control system
capable of determining if outside air can meet part or all of the building's
cooling loads.
1994 Washington State Nonresidential Energy Code Compliance Form
7flloMng
State EneivyCooe Compkince FoimsApnl,7PP�
s Cate
additional information is necessary to check a mechanical permit application for a complex mechanical For Building Department Use
system for compliance with the mechanical requirements in the Washington State Nonresidential Energy Code. Use
the checklist as a reference for notes added to the mechanical drawings(see the NIECH-CHK checklist for additional
system requirements). This information must be on the plans since this is the official record of the permit. Having
this information in separate specifications alone is NOT an acceptable alternative.
Applicability Code Location Building Department
(circle one) Section Component Information Required on Plans Notes
ADDITIONAL CHECKLIST ITEMS FOR COMPLEX SYSTEMS ONLY
es no n.a. 1431.1 Field essem.s s. 1 Provide calculations
1432 Controls
es no n.a. 1432.1 Setback 8 shul-off Indicate separate systems or show isolation devices on plans
1432.2 Temp.reset control
yes no n.a. 1432.2.1 Air systems I Indicate automatic reset
es no n.a.1 1432.2.2 Hydronic sysiems Indicate automatic reset
yes no n.a. 1433 Economizers Indicate economizer on equipment schedule or provide
calculations to iuslify exemption
es no n.a. 1434 1 Separate air sys. Indicate separate systems on plans
yes no n.a. 1435 Simul.hig.8 clg. Indicate that simultaneous heating and cooling is prohibited,
unless use of exception is justified
yes no n.a. 1436 1 Heat recovery Indicate heat recovery on plans:
complete and attach heat recovery calculations
ves no n.a.1 1437 1 Elec.motor effic. I MECH-MOT or Eauip.Schedule Mth"hp,rpm,efficient
yes no n.a.1 1438 1 Variable now sys. I Indicate variable flow on fan and pump schedules
I no is circled or any question, provide explanation:
I
Decision Flowchart Use this flowchart to determine how the requirements of the Complex Systems Option apply to the
project. Refer to the indicated Code sections for more complete information on the requirements.
Start
Here
I seeU.aun.1
Egmpment Fad.
Shall Metz Tables
i 141 thro
ugh 14.3
L
Sesbr 1431.1
Field• yes i C►1eu116ons od
' Assanbled- '—��Tout Cto•sne Enao•
Equipm=0. 114"k output
l i RtgL"
No j
I
S.Nr f 13L2 Capa,61.of FEW Att I Saed.�143=1
Ha WRIC Su Yes No S)stem Yes Supply 1_ Huvtg S.stem —� Supply A6Read
Tempennns Ream Chita Than $W°i; Controls
I Cortrob Requced oDUDD atuhli ` Multiple imes Requite
I
NO.�.
(continued on
U back)
1994 Washinoton State Nonresidential Enero Code Compliance Form
•
t pFa YJashinp,on SUIe Nonresidential Energy Code Conphanu Forme
(continued
from front)
/ OK '\ Multi- S.etl.n IU7
Moor Ef5cency�� No speed No Moron Must Meel
Included in Eq,apma j—fit Motor in Ef cieaein in
\ perforaunu ,/ \ wti-'peed Table 144
Ravry(1 \ 5)o,ern? f
Yee Yes
Yes , COOL,&\ 1b /Heao�E*`Electric Heating
�a > '�—1 DDO \Cooling in one /:�—�\ Fuel
Brute? , Pale?
1:on•Deeeie
No No
Seatl.n1111./ Seetle■1412.6
ODD Yes Modulatinl;or StMod
6rud Combustion
`•\"Mmrll: Controls
.� Requred
1
i 1 No
1 1412.3
Protide r
Mi=OProeesaor
Hear Pump
•, I Controls
Air> S"Pri 1 Ui
yOWcrmL \ Yes 5M,.Efrrmwe
Ouaide Air> - Hu,Rzro ry
?o•e? 5ve,em Requved
- \ i
f ,• ` ` '•� Tout Bldg\\. No
Cecy� Yea/'•PsekaFed I No Cooling No
RooSop �--� r' C►Pany 2, ' ,O,Op00 Bnh /4
No Y ea i v.. Yea
Sec-deb I433
Air-We
Eoonmrua
Required
r
�• Seed.■IUg
App6oenon Yu f Tani or Pumps\ Yes Vvuble Flow
lanal.ea '�► Deheu
Cansbk nws?.' 10 HP? Required
i
No i
No A�
Yea ran ■IUS Y'A�
r !
Fan Pow �
Termaul Unix Slslem?
Required X
No
Scab..1 U S
sirnu!umous
DoDe �= i HCA&4d
' 1 Cuol'vrE Aobbi,ed
1994 Washingtcn State Nonresidential Energy Code Compliance Form
t
-Ele
PU WoshmpIon Suit Envgv Coot cc,-;"4'.:r FoIns ipnl,iPF�
Project Address Dafe
Complete the following for all design A 6 B squirrel-sage,T-frame induction permanently wired polyphase motors For Building Department Use
from 1 hp to 2DD hp having synchronous speeds of 35D0,16aD or 12DO rpm(unless one of the exceptions belew
applies).
Motor Min.NOM.
No.or Type I Synch. Full load
Location HP (open or closed) es rat on of Application or Use Speed Efficiency
I �
I I I
I
I
I
I 1 I
Oa n Molors I cIcsec hholors Exceptions:
Symchronous I I I I 1. IVotors in systems designed to use more than one
Speed(n=!J1 3.6D0 1 6D0 1 200 3 5D0 1.6DD 1 2C)0 :peed of a murti•speed motor.
HP I [KI: n---v(°,o) I Efficiencv a°:) 2. Motors already included in the efficiency
1 0 I 62.5 1 80.0 I 6 5 I 825 I 80.0 reouirements for HVAC equipment(Tables 14_1 or
1.5 625 64.0 64 0 I E2 5 I 64-0 1 855 14-2)
2.0 I 640 I ik 0 1 65 5 $4 0 I 64.0 I 865 3. Motors that are an integral earl((e.not ersily
0 I 0 I 5. 5 I 6f.5 I E5.5 b7.5 67.5 removed and replaced of specialized process
5.0 65 5 I 67.5 I 67.5 ( 67.5 I 67.5 I 67 5 equipment(i.e.equipment which requires a special
75 57.5 I 6E5 I BE.5 I °E 5 89.5 1 E9.5 motor,such as an explosion-proof motor).
10 I 6E.5 I E9 5 I °:.2 E9 5 I E9.5 I 59.5 4. Motors integral 10 a listed piece of equipment for
15 E9 5 91 0 I 9D.2 1 9..2 I 91 0 I 90.2 which no qualifying motor has been approved(i.e.it the
20 9 .2 ( 91 0 I 91 D I 93.2 1 91 0 1 90.2 only U.L.listing for the equipment is vnth a less-efficient
25 91.0 1 91.7 I 91.7 I 91.0 1 924 1 91.7 motor and there is no energy-efficient motor option).
3D 91.0 224 9Z 4 9'. 0 2 4 I 91.7
40 I 91.7 I 93 0 1 930 1 91.7 I 930 I 93.0 For motors claiming an exception,list motor and note
50 1 92.4 I 93.0 I 930 I 924 93 0 I S3 0 which exception applies.
50 I 930 I 93 6 93 6 I 930 936 I 93 6
75 I 93 0 94.1 I 93.6 220 941 I 93 6
100 I 93.0 I E4.1 1 94.1 93.6 94 5 I <-1
125 93.6 1 94.5 94A I 94.5 I 94.5 941
150 1 93.6 95.0 l 945 I 94 5 95.0 1 95 0
2DD I 94.5 9 0 I 94.5 I 95.0 re5 0 95 0
� _
. .
f
y
>;.
.�: : --
.K• .J..�
%i~
... 4�/
w
.:
:•
1994 Washinctor State Nonresidential Energy Code C'=Dliance Form
.pN WaanmQon Stale NonlefooemlaI Enemy Coot Compliance For Rprtl,�Pc1
Project Info Project Address Date
For Building Department Use
Applicant Name:
Applicant Address:
Applicant Phone:
Project Description New Building ❑ Addition ❑ Alteration
Compliance Option Prescriptive ❑ Lighting Power Allowance ❑ Systems Analysis
(See Qualification Checklist(over).Indicate Prescriptive 8 LPA spaces clearly on plans.)
Alteration Exceptions ❑ No changes are being made to the lighting
(check appropriate box) ❑ Less than 60%of the fixtures are new,and installed lighting via"age is not being increased
Maximum Allowed Ligbtin I'Vattaoe (Interior)
Location Allowed
(floor/room no.) occupancy Description Wafts per tY" Area in f12 Allowed x Area
From Table 15.1 (over)-document all exceptions taken from footnotes Total Allowed Watts
Proposed Lighting Wattage (Interior) play not exceed Total Allowed Watts for Interior)
Location Number of Watts/ Watts
(floor/room no.) Fixture Description Fixtures Fixture Proposed
4=1L' CSG�
z - - o
Total Proposed Watts may not exceed Total Allowed Watts for Interior Total Proposed Watts
Maximum Allowed Lighting Ligbting Wattage (Exterior)
Allowed Watts Area in ftx Allowed watts
Location Description per fe or per If (or If for perimeter) x f(or x If)
Covered Parking 0.2 WIFe
Open Parting 0.2 W/ft'
Outdoor Areas 0.2 Me
Bldg.(by facade) 0.2-S W/ft
Bldg.(by Perim) 7.ilyltf
Note:for building exterior,choose either the facade area or the perimeter method,but ne,both) Total Alloyed Waits i 105
Proposed Lighting Ligliting Wattage (Exterior) (fJay not exceed Total Allowed Watts for Exterior)
Number of Watts/ Waits
Location Fixture Descriplion Fixtures Fxture Proposed
T .� _
!l
Total Proposed Watts may not exceed Total Allowed Watts for Exterior Total Proposed Watts i`77
1994 Washington State Nonresidential Energy Code Gompiiance corm -
s � e Apnl,ZPI;;
c c y,ashmg on Suit E�rrgt Coot Gompi.ance Fom s -
• tinter,p11D;oceE,or a eombir,ation Or timer and pholocct.Automatic time
Lighting - General Requirements, :whches shall atsp have prpgtam back-up capabilities.which prevent the
1513 Lighting Controls loss of program and time servings for al least 10 hours,a power is
interrupted.
1513A Local Control and Accessibility:Each space,enclosed by walls
nls loczted 1511.E Automatic Shut-011 Controls,Interior.O"'ce buiidings greater
a.,ceiling•heigh;parttions,shall be plaided wilt lighting co tro equipped wKh separate
witnin that space.The lighting controls,whether one or more,shall be than?S,OD�ftr and all school classrooms shall be
czpzble a!turning off at[;his within the space.The controls shall be zulors :contra's to shut off the ligh5ng during unoccupied hours.
readily access3k,al the point of entry/cxil,10 personnel occupying or Auforjbc controls may be an occupancy sensor,tone swr.ch,or other
dev::e capable of automatically shutting otf lighting.
using the space.
Exceptions:The following lighting controls may be central:ed in Exceptions:
remote locations: 1. Arers that must be continuously illuminated,of illuminated in a
manner requiring manual opera!lon of the I:ghting.
1- Lighting controls for spaces which must be used as a whole. 2. Emergency lighting zyslems.
2. Aulomatic controls. 3. Switching for industrial or manufacturinc process facilities as
may be required for production.
3. Controls requiring trained operators.
4• Controls for safety hazards and security. 1513.E.1 Occupancy Sensors: Occupancy sensors shall be capable of
1n autamz5czry turning off all the lights in an area,no more than 30 minutes
513.2 Area Controls:The maximum lighting power that may be
controlied from a single swtch or zutoraztic control shall not exceed t`at
oriel the area has been vacated.
which is provided by a twenty ampere circuit loaded to not more than 151?.E.2 Automatic Time Switches:Automate time swr hes shall have
eighty percent.A master control rnzy be installed provided the individual a min cum i day cloak and be cap Dle of Doing set for"e C'ierent day
switches retain their capabaityto function independently.CircuC breakers types per week and incorporate an :4 hour$ nC the,resumes
feature,
rr,zy not be use.zs the sole means o,switching, which lums all all loads for a!itzst 2<hours and then resumes normally
scheduled operations.Auromalic time switches shall also have program
Exceptions: back-up capabilfbtli.which prevent the loss of program and time semngs
1. Industrial or manufacturing process areas,as may be required for at least 10 hours,a power is interrupted.
for production.
2. Arers less than five percent of the building footprint for Anrdmatic time switches shall incorporate an over-ride switching device
fo tpnnts over 101000 tta. which:
1513,3 Daylight Zone Control:Ar daybghled zones,as defined in a. is readify accessible;
Chapter 12.bath under overhead pwzing and adjacent to vertical gt4-ling, b. is located so that a person using the de.i a car.see trth fights
or the areas controlled by the swr,ch.of so that the
shall be protdded with individual controls,or deyGght-of occupanl•sersing area being illuminated is annun-jve-d;
2utdrrabc controls,which control Vie I,ghts independent of generp!area a is manually operated:
lighting, d• alluws tilt lighting to remain on for no mnro"an two hours
1513.4 Display,Exhibition,and Specialty Lighting Controls:All when an over-ride is in tested:and
display,exhibe.ion,or specialty lighting shall be controlled independently of e, controls an area not exceeding 5,000 tr or 5 percent of
general area lighting, footprint for footprints over 100.000 te.whichever is
1513.5 Automatic Shutoff Controls,Exterior:Exterior lighting not greater.
intended for 24-hour continuous use shall be automatically switched by
TABLE IS-1
Unit Lighting Power Allowance (LPA)
LPA
Use, («'/f(2)
Painting, welding, ca ntry, machine shops 2.30
Barber shops, beauty shops 2.00
Hotel banquet/conference/exhibition hall 2.00
Laboratories 2.00
Aircraft repair hangars 1.50
Cafeterias, fast food establishmenisS 1.50
Factories, worksho s, handling areas 1 .50
Gas stations, auto repair sho s6 1.50
Institutions 1 .50
Librariess 1.50
Nursing homes 1.50
Wholesale stores (pallet rack shelving) 1 .50
Mall concourses 1.40
School buildings, school classrooms, 1.35
day care centers
Laundries 1 .30
Office buildings, office/administrative areas in 1.20
facilities of other use types (including but not
limited to schools, hospitals, institutions,
museums, hanks, churches)S,7_
Police and fire stations8 1.20
Atria (atriums) I •M
Assembly spaces , auditoriums, gymnasid, 1.00
theaters
Process plants 1 .00
Restaurants/harsS I .W
Retail A] 1 .00
Retail BI , retail hanking 1.50
Locker and/or shower facilities 0.80
WarehouseslI. storave areas 0.50
Aircraft storaee hangars 0.40
Parking garages See Section
1532
Plans Submitted for Common Areas Only?
Common area, corridors, lobbies 0.80
(except mall concourse)
Toilet facilities, washrooms 0.80
t
: , .
' �
,.►_r
1y' ''
G100 Series PACKAGED WATER GAS BOILER/BURNER UNIT
,._.,.___-_- ----r•^--•ram- _ •_____ ... t•�-r•. •-•-• -+ - -^---' "" _ �t r �,
�� ��y^{�i C: yt 4- -., F '_. _. X,, � ��,�'� �d� h� ;iiJ.t+3 #'it`ll � �+i.('• f
V 2,
k
��J
71� ;�4 t JJ y IV. 1 .•.r! _ � � 21' I.w��,�,�+ i'9�1'.7"- S �,L'1`� !' f.
•�� � �. +�r"r�^+tt�' a . y t'i a I r y ; 7�tA-77�.��r� 7f- w`y^: �`r#�.�' �, •� t�
...........,. ? s roll a[LIE2 VALY! _ srL -9r'I •
y�l
4111H , 1
� "
r I t• y n?' ,�'1 t ' t 1(-'_'.� .� t ! v •r TOPCLraNaur
�' .��S. -..• t�- ti� �Y.t o .'�. .i.. 1_1.:+.i.� �. t \, � SG,t - r� *.
} t
it
PLr •� ; \, I .3�. -C! > ��'S}rG
�
- � i�r�! - qZl.. •��`'` r•, wS'.'. ��.J � �'�i.•�t.'f''�L�`� _in 2�,$3r' VR. �(r '
+. a�E
' -4� 't!''Ir�� 4 a '''r �I t' '•rSt� �� �'� ��;. p; j � ;� ,�� Y �, � �, �. ,r �.����
' 6t
STANDApb EQUIPMENT NO, SECTIONS 3 4 5 8 7 8 9 10 11 12
Completeiy Packaged and Wired Gas -^- - - --- - -
Hot Water Boller "A" (IN.) 10'% 135/a 183/4 191/4 217/a 246A 27$/a 301/s 321/e 35%
• Cast iron sections _^ _
• Deluxe insulated metal Jacket "g" (IN.) '/a 4 41/: 4'/z 4'/2 5 5 bi%: 5'/: $'/:
• Burnel tray with high temperature
insulation board and burner tubes - - , "
• Non-combustible floor FLUE DIA. "C" ` : ' 5 6 6 6 7 7 8
® Integral flue collector and draft
diverter w/rlean out panel
® A,S.M•E. pressure reiief valve
(30 psi) NatuW'Gaas Propane Gals
• Taco"007"circulator
• Theraltlmeter Boller DAE, Net w D,O.E. Net
• Brass hose end drain cook Model A.G.A. ii`a. I.B=R A.G.A. HTG. I-BlaR EFPlclency
Thermostat Number Input Capftity Ratings Input Capaelty Ratings Steady
• Combination high limit and MBH MBH MOH MBH MBH MOH State A.F.U.E.•
circulator relay control -
• Oversized junction box G-100-3 50.0 41.0 y 357 50.0 41.0 35.7 82.1% 81.0%
r Constant Pilot Ignition W/combin- 0-1Q04 75.0 $7.6 53.6 75.0 81.8 63.6 82'.0% 80.9%
anon dual gas control including 3 G-100-5 100,0 02.2 71.5 10010 82.2 71.5 81.9% 80'e"
position gas-cock,pressure �.
regulator, 1001% pilot and main gas 0-100-6 125.0 10-8y1 89.4 125.0 102.8 89.4 81.8% 80.7%
shut-off for 24 volt. w/pilbt_durner G-100-7 -160:0 123.5! 107.4 150.0 1 123.5 107'.4 81.6% 80.6%
tubes and thermocouple. (4-12 Sect. G-100.8 166,0 156.7;° 118_9 168,0 1 136:7 118.9 81.e% K.7%
only) G•100-9 190.0 166.6 136.2 190.0 158.6 136.2 82t% 8018%
• High efficlency Stack Damper with G-100-10 216.0 1 .2 166.0 212,0 174.9 162.1 82.1.Wh 80.9%a
winng harness for mounting in -- -- --
breeching. (Packed in separate GT100.11 240M 1013.1 172.3 236.0 194.8 169.4 82:49ro., 81.6%
carton) G.lDD-121 2654 E 8:9 190.3 u26010 214.8 _ ll% 81,10/0
OPTIONAL EQUIPMENT Closet installation-3-79Wionslnatural gas only,
`With Stack Damper&Ha3.l. \ _
• Intermittent pilot systems providing Y 1998
electronic pilot ignition and flame ,,�;
sensing with IGO%shutoff: r/�+ .�
• Intermittent"pilotless"hot surface CITY®F�►R�IN�iTaPJ
ignition system, providing Ignition - 0
and sensing of main burner flame HBSmith
with 100% shutoff(std. on 3 Sect.) I B-
• Propane Gas (not available for R ,r.•.
closet installations) 26D NORTH ELM ST
• Tjernlund side-wall ventor(GPAK-J WESTFIELD MA 01085
and GPAK-1)for 3-11 section boilers. TEL.: (413)562-9631
-- FAX:(413)562-3799
A' !i
�4'
�� �l +�:� ���
.. .......... ... .................. .................... _ ........................................................................................................................... ...O ...
May-08-98 12 : 37P Mot �m 206-763-7234 P2
® PSG ,
Temp. Sensors, Preset & Adj.lSingle & Multistage
C� l
ACCTJTIEMP" ' Preset & Adjustable
Single & Multistage Temperature Sensors
Description:
PSG ACCUTEIv1P' sensors are preci- p
s•on accurate, hermetically sealed, '
temp sensors forACCUSTAT' Energy
Controls. ACCUTEMP; are .manufac-
tured in ,;reset, adjustable ano multi-
stage versions. Advantages of the
ACCUTEMPT sensor are: high accu-
racy fast response: no temp
draft. Unlike bimetal senscrs. j E`
ACCUTEMPI sensors have no fatigue a
factor are generally unaPected by vi-
oratior and will operate in any position
Theory of Operation:
Single stage ACCUTEMP Sen-
sors: ACCUTEMP"sensors are preci-
sion :emp switches in which platinum
vvires embedded in the glass coiurnc.
pass through a capillary containing a
temp. sensitive liquid
The psebumm wire
are the Common
tilultis:a Te Sensors:
and the Activating Contact The Com-
Specifications:
mon wire is located near the oaseof,he au sr_ le %t,:`.ri,rage
sensor and the activating Contact is ( Singlestage Sensors: aS�t C o-H)-a0"
ocatedabove theCommon.Asthe:emp. Preset Sensors "S"- series Range• +•40' to WF
increases,the liquid rises past the Com- Accuracy: .5'F Ambient Range:-20' to +110' F
mon contact then reaches the Activat- Temp. Drift: < 0.1°F per year Ac-_uracy +1-2.0' F
;ng Contact establisning an Ambient Range:-20° to +110° F. Temp Drift: < 0.25'F per vea:
electricai path These sensors are used Load: 100 milliamps
max. res, These sensors provide greater flex
tum heating or Cooling circuits ON or i
OFF X Preset sensors provide tamper- h ac i us in temp. selection. Simply re
; sensor knob for differe�
se
proof temp control.Standard temp. 1
Adjustable ACCUTEMP�+'Sensors: setpoints are. tooin s,
The adjustable sensors have a knot I 35°, 37 39-. 40', 45', 50', 55�. 60', g preset Multistage "SM" -series
which is used to adjust the setpon;t from 62 64 , 65°. 66'. 68', 7.". 72'. 74° curacy� + °F;-o°F
40°F to 90°F Turning the knob changes 75',76'.78',80 82',84'.86 88'F Temp �Dnft: Les_s!han0 t per;e�
trio displacement of the;emp sensitive msr r m; ^„a �,�,` ,e "5;.e•a, •.e ,rro er.Range 20° to +110 F
iquid, causing the sensor's setpoint c S:age Dfferenbai: Delta T of 4'
te~)p. to change U.S. Patent Ad-,usiablz Sensor ".�.5 ail' y
s 376 928 Range. +40 to 9G'F
=�,ese-_ ^iuitistage senscrs p',V,�E
° �110' F. tam�.e�-�rocf control.
Ambient Range 20 t0 S,andara:emp setpoints are
Multistage ACCUTEMRI Sensors: A.ccuraey t'-� `� F
,2 ,74° ,a,:�n
Preset a-id Adjustable multistage sen- Tem Drift'. < 0.2SF per year 63 •7' 'C°:;
1 P ;.; 73 78'80'F1
sors are also available These sensors load. 100 miliiamps
have two .Activating Contacts raith a 2° max. res.
Delta Temp Simply turning ,he knob changes Built-in Differential:
The ASNIH-90 adjustable Heating sen.- the setooint
son has a red knob The ASP,1G 90 RECEIVED As :nstaileo in ACCUSTA7 the-71,
adi staote cooling szrsor hips a blue slats. the ACCUTEMf' sensor
c'esianed to yield a roorn differen,ai
,Knob
TnePreset multistagesensc:s.l.he"SN-l" between t 5 anal 3'F
Brie �rW calibrated for vanGus Preset MAY 1 1998
CITY OF ARLINGTON S
r>,c r4 . r PPrkaSiP. Pp, 1894 - 1-800-782 8412 FAX f2":5i L57 42ts8
w 1. _ ��} _
J, � �.. _i ,r I
V I 1 *'
I L*
City of Arlington
Building Department
238 North Olympic Avenue
Arlington, Washington 98223
(360) 435-0724
Plan analysis based on
the 1997 Uniform Building Code
Project Number: 98-2950 Date : May 22, 1998
Project Name: CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
Contractor: BLUE RIBBON STEEL
Occupancy: S3 , S1,B Architect :
Construction: V-N Engineer: H. N. LEHTINEN
Report By: DAVE
NOTE : The code items listed in this report are not intended to be a
complete listing of all possible code requirements in the 1997 UBC.
It is a guide to selected sections of the code .
Report created using Plan Analyst software by b w & a. (719) 599-5622
Portions of the material contained in this program are reproduced
from the Uniform Building Code with the permission of the
International Conference of Building Officials .
SEPARATION
DIRECTION BOUNDARY AREA INCREASE FIRE PROTECTION
NORTH Property line 100 . 0 Feet 100 . 0 Feet
EAST Property line 225 . 0 Feet 225 . 0 Feet
SOUTH Property line 340 . 0 Feet 340 . 0 Feet
WEST Building 70 . 0 Feet 35 . 0 Feet
Allowable area increased 100 . % for open area on 4 sides .
-- Sec . 505 . 1
I�
I
Page # 2
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
FL NAME OCC MAX FLR AREA ALLOWED RATIO STATUS
- - - - - - - - - - - - - - - - -- - - --- -- - - - - - - --- - - - - - - - - - - -- - - - - - -- - - -- - - - - - - - - - -
1 Repair Garage S3 ok 5760 16000 0 . 36 ok
1 Storage/Stock Room S1 ok 1080 16000 0 . 07 ok
1 Other Occupancy B ok 216 16000 0 . 01 ok
1 Other Occupancy B ok 216 16000 0 . 01 ok
1 Other Occupancy B ok 216 16000 0 . 01 ok
TOTAL FOR FLOOR 7488 16000 0 .47 ok
BUILDING TOTAL 7488 16000 0 .47 ok
-- Sec . 504 and Table 5-B
The actual height of this building is 27 . feet .
The maximum height of the building is 40 . feet . -- Table 5-B
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 5-A
NORTH
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
S3 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
EAST
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
S3 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
SOUTH
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
S3 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
WEST
For Bearing Non-Bearing Opening Construction Parapet
Occupancy Wall Wall Protection Material Required
G
� r
I
1
I
Page # 3
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
S3 0 hour 0 hour None Any No
S1 0 hour 0 hour None Any No
B 0 hour 0 hour None Any No
None -- No fire protection requirements for openings .
3/4 hour -- Openings are to be protected with 3/4 hr fire assemblies .
50% of the area of the wall maximum. -- Table 5-A,
Footnote 5 & Sec. 503 . 2 . 2
Maximum single window size is 84 sq. ft . with no dimension
greater than 12 feet . -- Sec . 713 . 8
Not Allowed -- Openings are not permitted in this wall .
OTHER BUILDING ELEMENTS Table 6-A
ELEMENT MATERIAL RATING NOTES
Interior Bearing wall Any 0 hr,
Interior nonbrg wall Any 0 hr
Structural Frame Any 0 hr
Exterior Struct Frame Any 0 hr See footnote 41
Floor/Ceiling Assembly Any 0 hr See Footnote #9
Roof/Ceiling Assembly Any 0 hr
Stairs Any None
FOOTNOTES :
1) Elements in an exterior wall located where openings are not permitted
or where protection of openings is required, shall be protected
against external fire exposure as required for exterior bearing walls
or the structural frame, whichever is greater. -- Table 6-A, footnote 1
9) In areas with vehicles or airplanes, the floor shall be of
noncombustible, nonabsorbent materials . -- Sec . 307 . 2 . 2
e
Page # 4
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
PENETRATIONS OF FIRERESISTIVE ASSEMBLIES
WALLS ASSEMBLIES -- Sec . 709 . 6
Through penetrations :
1) Penetrations shall be installed as tested in the rated assembly.
-- Sec. 709 . 6 .2
2) Penetrations shall be protected by an approved penetration
firestop system and shall have an F rating of not less than the
required rating of the wall penetrated. -- Sec . 709 . 6 . 3
Exception: When penetrating items are steel, ferrous or copper
pipes or steel conduits and the wall is concrete or
masonry, the annular space shall be permitted to be
grout or mortar. The minimum thickness is the
thickness required to maintain the fire rating. The
maximum size of the penetrating items is equivalent
to a 6-inch diameter and the opening is a maximum of
144 square inches . -- Sec . 709 . 6 . 1
Membrane penetrations :
The requirements are the same as for through penetrations .
-- Sec . 709 . 7
Exceptions :
1 . Steel electrical outlet boxes that do not exceed 16 square
inches provided that the area of such openings does not exceed
100 square inches for any 100 square feet of wall area.
Boxes on opposite sides of the assembly shall be
separated by a horizontal distance of not less than 24
inches .
2 . Sprinklers with metal escutcheon plates .
Noncombustible penetrating items shall not be connected to
combustible materials on both sides of the membrane unless it can
be confirmed that the fire-resistive integrity of wall is
maintained. -- Sec. 709 . 7
!�
�:
�~
I
I
Page # 5
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES -- Sec . 710 . 2
Through pentrations :
Through penetrations of fire-resistive horizontal assemblies shall
be enclosed in fire-resistive shaft enclosures . -- Sec . 710 . 2 . 1
Exceptions :
1 . When penetrating items are steel, ferrous or copper conduits,
pipes, tubes and vents through a single concrete floor, the
annular space shall be permitted to be grout or mortar.
The minimum thickness is the thickness required to maintain
the fire rating. The maximum size of the penetrating items is
equivalent to a 6-inch diameter and the opening is a maximum
of 144 square inches .
2 . Electrical outlet boxes that have been tested for use in
fire-assemblies .
The system shall have an F rating and a T rating of not less than
one hour but not less than the required rating of the floor system.
-- Sec . 710 .2 . 3
Exception: Floor penetrations contained and located within the
cavity of a wall do not require a T rating.
Membrane penetrations :
The requirements are the same as for through penetrations .
-- Sec . 710 . 3
Exceptions :
1 . When penetrating items are steel , ferrous or copper
conduits, electrical outlet boxes, pipes, tubes and vents
through concrete or masonry and the annular space is
protected by an approved penetration firestop assembly or
protected to prevent the free passage of flame and
products of combustion. Such penetrations shall not
exceed an aggregate area of 100 square inches in any 100
square feet of ceiling area in assemblies without
penetrations .
2 . Electrical outlet boxes that have been tested for use in
fire-assemblies .
3 . Sprinklers with metal escutcheon plates .
Fire-resistive roofs may have unprotected openings . -- Sec . 710 .4
(`j
I
1
Page # 6
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
SMOKE and FIRE DAMPERS -- Sec. 713 . 10 and 713 . 11
Dampers shall be accessible for inspection and servicing:
1 . Penetrations through area separation walls .
Penetrations through occupancy separations .
2 . Penetrations of the fire-resistive construction of horizontal
exit walls or corridors serving as a means of egress .
Exception: Openings for steel ducts penetrating the required
fire-resistive construction of corridors are not
required to have smoke dampers when such ducts
are of not less than 0 . 019-inch thickness
(26 gage) and have no openings serving the
corridor.
3 . Penetrations of shaft enclosures .
Exceptions :
1 . Duct penetrations by steel exhaust air subducts
extending vertically upward at least 22 inches above
the top of the opening in a vented shaft where the
airflow is upward.
2 . Penetrations of a fire-resistive floor forming the
base of a shaft enclosure may be protected by fire
dampers listed for installation in the horizontal
position.
3 . Smoke dampers are not required when shaft is exhaust
only, and is used for continuously operating fans .
4 . Penetrations of the ceiling of fire-resistive floor-ceiling
or roof-ceiling assemblies .
Exception: Smoke dampers are not required.
5 . Penetrations of an atrium enclosure element .
Exception: Smoke dampers are not required.
6 . Penetrations of exterior walls where protection of openings
is required.
Exception: Smoke dampers are not required.
7 . Penetrations of areas of refuge.
Exception: Ventilation system designed to supply outside
air during an emergency.
8 . Smoke dampers are required in smoke barriers and elevator
lobbies .
Page # 7
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
OCCUPANCY SEPARATIONS -- Table 3-B
S3-S1 lhr
S3-B lhr A customer waiting room not exceeding 450 sq. ft .
with an exit to the exterior is not required to be
separated. -- Sec . 302 . 1 exc . 2 . 5
Si-B Ohr
HEATING EQUIPMENT SEPARATION:
FOR S3 OCCUPANCY:
A 1 hr. occupancy separation is required around rooms containing a
boiler or central heating unit greater than 400 , 000 BTU input .
-- Sec . 302 . 5
FOR S1 OCCUPANCY:
A 1 hr. occupancy separation is required around rooms containing a
boiler or central heating unit greater than 400 , 000 BTU input .
-- Sec . 302 . 5
FOR B OCCUPANCY:
A 1 hr. occupancy separation is required around rooms containing a
boiler or central heating unit greater than 400 , 000 BTU input .
-- Sec . 302 . 5
ADDITIONAL SEPARATIONS :
A refrigeration machinery room shall be separated from the remainder
of the building as required for an H7 occupancy regardless of area. A
horizontal occupancy separation may be limited to the actual floor
area of the machinery room. Structural supporting elements shall be
protected for the type of construction only. -- Sec . 2802
A 1 hour separation is required from an S3 occupancy. -- Table 3-3
EXIT REQUIREMENTS :
FL NAME NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES
OCC EXITS WIDTH HDWR CORRIDOR SWING
- - - - - - - - - - - - - - - - --- - - - - ---- - - - - - ---- - - - - ---- - -- - - - - - - - - - - - - - - -- - - - - - - -- --
1 Repair Garage 29 1 5 . 8 No N/A N/R
1 Storage/Stock Room 4 1 0 . 8 No N/A N/R
1 Other Occupancy 2 1 0 .4 No N/A N/R
1 Other Occupancy 2 1 0 .4 No N/A N/R
1 Other Occupancy 2 1 0 .4 No N/A N/R
TOTAL 39 2 7 . 8 No N/A N/R
In areas where 2 exits are required, the minimum separation is 1/2 of
the maximum diagonal of the area or floor. -- Sec . 1004 .2 .4
1
I
I
I
Page # 8
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
When 2 exits are required, exits must be arranged so that it is possible
to go in either direction from any point in a corridor or hallway to a
separate exit, except for dead ends not exceeding 20 feet in length.
-- Sec . 1004 . 2 . 6
Exit signs are required from all areas where 2 or exits are required.
-- Sec . 1003 . 2 . 8 . 2 , Exception 2
No point to be more than 100 feet from an exit sign.
Main exterior exit doors which obviously and clearly are identifiable
as exits need not be signed when approved. -- Sec. 1003 . 2 . 8 .2, Exception 1
Door swing is based on Sec . 1003 .3 . 1 . 5 except as noted.
Occupant load factor is based on Table 10-A.
Number of exits is based on Table 10-A except as noted.
Exit width is in inches and based on Sec . 1003 . 2 .3 and Table 10-B
Exit width is to be divided approximately equally among exits .
- - Sec . 1003 . 2 . 3 . 2
Width shown for all areas is based on other egress components .
Width shown for 1st floor is based on other egress components .
Width shown for other floors & basements is based on stairways .
- - Table 10-B
For the minimum width of doors, see Sec . 1003 . 3 . 1 . 3
For the minimum width of hallways, see Sec . 1004 . 3 . 3 .2
For the minimum width of corridors, see Sec . 1004 . 3 .4 .2
For the minimum width of stairways, see Sec . 1003 .3 . 3 .2
FOOTNOTES :
FLUSH AND SURFACE BOLTS :
Manually operated edge- or surface-mounted flush bolts and surface
bolts or any other type of device that may be used to close or
restrain the the door other than by operation of the locking device
shall not be used. When automatic flush bolts are used, the door
leaf having the automatic flush bolt shall not have a door knob or
surface-mounted hardware . The unlatching of any leaf shall not
require more than one operation. -- Sec . 1003 . 3 . 1 . 8
�:
�„
I�
- I
1
Page # 9
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
LOCKS AND LATCHES :
Regardless of the occupant load served, exit doors shall be openable
from the inside without the use of a key or any special knowledge or
effort . -- Sec . 1003 . 3 . 1 . 8
Key-locking hardware may be used on the main exit when the main exit
consists of a single door or pair of doors if there is a sign stating
THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS . When unlocked,
door (s) must swing without operation of any latching device . -- exc .
LANDINGS AT DOORS :
1) A floor or landing shall be provided on each side of doors . When
access for persons with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum is 1 inch. -- Sec. 1003 .3 . 1 . 6
2) Landings shall have a width not less than the width of the stairway
or width of the doorway, whichever is the greater. Where a landing
serves an occupant load of 50 or more, doors in any position shall
not reduce the landing dimension to less than one half it required
width. The minimum length in the direction of exit travel is 44 inches .
-- Sec . 1003 . 3 . 1 . 7
TRAVEL DISTANCE: (distance to an exit)
The maximum travel distance in this building is 200 feet . -- Sec . 1004 . 2 . 5 .
The travel distance for the major occupancy may be 300 feet .
-- Sec . 1004 .2 . 5 .2 . 5
Travel distance shall not be limited within an exit enclosure or exit
passageway. -- Sec. 1005 . 2 .2
:� ,.
�I
1
I
Page # 10
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
BUILDING ACCESSIBILITY:
1) This building including each tenant shall be provided with at least
one entrance which complies with the accessible route provisions of
CABO/ANSI A117 . 1 . At least 50 percent of all entrances shall be
accessible. -- Sec. 1103 .2 . 3
2) When more that one exit is required from any accessible space, each
accessible portion of the space shall be served by not less than two
accessible means of egress. -- Sec . 1104 . 1 . 1
3) When an exit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails. The stairway shall either incorporate an area of refuge
within an enlarged story-level landing or shall be accessed from
an area of refuge. -- Sec . 1104 . 1 .2
The area of refuge shall have direct access to the stairway that serves
it . -- Sec . 1104 . 2 . 1
4) Each area of refuge shall be sized to accommodate one wheelchair space
not less than 30 inches by 48 inches for each 200 occupants, or
portion thereof . -- Sec. 1104 . 2 .3
5) If the area of refuge is not within the stairway, it shall be separated
from the rest of the story by a smoke barrier having at least a one-
hour fire-resistance rating. Smoke barriers shall extend to the roof or
floor deck above . Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes . -- Sec . 1104 . 2 .4
6) Two-way communications are required. -- Sec. 1104 .2 . 5
7) Each area must be identified by a sign stating AREA OF REFUGE and the
international symbol of accessibility. -- Sec . 1104 .2 . 7
8) NOTE : Exit stairways in buildings protected throughout by an approved
automatic sprinkler system are NOT required to incorporate an area of
refuge . -- Sec . 1104 . 1 . 2, Exception 2
ROOFING REQUIREMENTS :
1) The roofing on this building is required to be Class C. -- Table 15-A
2) See section 1504 and ICBO research reports for requirements .
AUTOMATIC SPRINKLER SYSTEMS :
If openings are not provided in each 50 feet of exterior wall or there
is floor area more than 75 feet from an exterior opening, an automatic
sprinkler system is required. -- Sec . 904 .2 .2 Note: Openings shall have
a minimum dimension of 30 inches . There must be at least 20 sq. ft . of
opening in every 50 lineal feet of wall .
.[
1. �
I
Page # 11
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
STANDPIPE REQUIREMENTS :
There is no requirement for a standpipe. -- Table 9-A
FOOTNOTES :
VENTILATION:
All areas customarily occupied by humans shall be provided with natural
ventilation by means of openable exterior openings with an area of not
less than 1/20 of the total floor area or shall be provided with a
mechanically operated ventilation system. Such system shall be capable
of supplying a minimum of 15 cubic feet per minute of outside air per
occupant . -- Sec . 1202 . 2 . 1
WALL AND CEILING FINISH:
1) Wall and ceiling finish materials are required to comply with
Sec . 804 . 1 and Table 8-B.
2) Carpeting on the ceiling is required to have a Class I flame
spread rating. -- Sec . 804 . 2
3) Textile wall coverings shall have Class I flame spread rating.
and shall be protected by automatic sprinklers or meet the
acceptance criteria of U.B.C. Standard No. 8-2 -- Sec . 805
4) Toilet room floors shall have a smooth, hard nonabsorbent surface
that extends upward onto the walls at least 5 inches .
-- Sec . 807 . 1 . 1
5) Walls within 2 feet of the front and sides pf urinals and water
closets shall have a smooth, hard nonabsorbent surface .
-- Sec . 807 . 1 . 2
INSULATION NOTES :
1) All insulation material including facings are required to have a
flame-spread rating of 25 or less and a maximum smoke density of 450
unless it is in a concealed space and the facing is in contact with
a wall or ceiling. -- Sec. 707 .3 exc .2
2) Foam plastic insulations are required to be protected. -- Sec . 2602
i
Page # 12
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
ADDITIONAL REQUIREMENTS :
For S3 occupancy
1) In parking garages where any parking is located more than 5 feet above
the adjacent grade, vehicle barriers shall be provided. -- Sec . 311 . 2 . 3 . 5
2) The minimum clear height is required to be 7 feet . -- Sec . 311 .2 . 3 . 3
3) Parking garages require a ventilation system that exhausts 1 . 5
cfm per sq.ft . of floor area. -- Sec . 1202 .2 . 7
For S1 occupancy
For B occupancy
ACCESSIBLE FACILITIES :
NOTE: Except as noted, section numbers listed below are from
CABO/ANSI A117 . 1 - 1992
WATER FOUNTAINS AND WATER COOLERS :
At least 50 percent of drinking fountains, but not less than one,
provided on every floor shall be accessible . -- UBC Sec . 1105 . 4 . 1
Accessible units must comply with the following:
1) Spout is to be within 36 inches of the floor. -- Sec . 4 . 15 .2 . 1
2) Spout arranged for parallel approach shall be located 3 inches
maximum from the front edge . Spouts of cantilevered units with
knee and toe clearances shall be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
-- Sec. 4 . 15 .2 . 2
3) Spouts shall provide a flow of water 4 inches height minimum.
-- Sec . 4 . 15 .2 .3
4) Operable parts shall be located at or near the front edge of the
unit and shall comply with 4 .25 .4 -- Sec . 4 . 15 .3
5) A cantilevered unit is required to extend 17 inches minimum from
the vertical support . Clear knee space must provide a clear area
of 8 inches in depth at 27 inches high and 11 inches at 9 inches
minimum above the floor. -- Sec . 4 . 15 .4 . 1
6) Forward approach units shall comply with 4 .2 . Units in alcoves
shall comply with 4 . 2 .4 .4 . Units not having the necessary knee
I
Page # 13
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
and toe clearance or clear space under them shall comply with
4 . 2 .4 and have a clear floor space that allows a person in a
wheelchair to make a parallel approach. -- Sec . 4 . 15 .4 . 2
TOILET FACILITIES :
1) A 60 inch diameter unobstructed turning space is required in
the toilet room. -- Sec . 4 . 16 .3, 4 .2 .3 & Fig. B4 . 2 . 3
2) Water closet shall be mounted adjacent to a side wall or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 in. Sec . 4 . 17 . 1
3) When the accessible water closet is not in a stall :
The clear floor space shall be 48 in minimum in front
of the water closet and 42 in from the center line of the
water closet on the side not adjacent to the wall .
-- Sec . 4 . 17 . 2 & Fig. B4 . 17 .2
4) When the accessible water closet is in a stall :
The stall shall be 60 in wide minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for floor
mounted water closets . -- Sec . 4 . 18 . 3 . 1
If the door swings into the stall, the required depth shall
be increased by 36 inches minimum. -- Sec. 4 . 18 . 3 .2 &
Fig. B4 . 18 . 3 . 1
5) The bars are to be 33 to 36 inches above the floor and shall
be provided on the rear wall and on the side wall closest to
s
1
I
I
Page # 14
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
the water closet . -- Sec . 4 .24 . 2 . 2 & Figs . B4 . 17 . 3 , 34 . 17 . 4
and B4 . 18 .3 . 1
a) Side grab bar is required to start within 12 inches of the
back wall and extend to 54 inches from the back wall . (The
minimum length of the bar is 42 in) -- Sec . 4 . 17 .4 . 1 &
Figs . B4 . 17 . 3 and 34 . 18 . 3 . 1
b) The rear bar shall be 24 in long minimum, centered on the
water closet . Where space permits, the bar shall be 36 in
long minimum, with the additional length provided on the
transfer side. -- Sec . 4 . 17 .4 .2 & Figs . B4 . 17 .3 , B4 . 17 .4
and 34 . 18 .3 . 1
6) The top of the seat on the water closet is required to be 17
to 19 inches above the floor. -- Sec. 4 . 17 . 3 & Fig. B4 . 17 . 3
7) Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec . 4 . 19 . 2
8) A clear area of 30 X 48 inches minimum is required in front
of the urinal . Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart
minimum. -- Sec . 4 . 19 . 3
9) Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
-- Sec. 4 .20 . 2 . 1 & Fig. B4 . 20 .3 . 1
10) It shall extend 17 inches minimum from the wall . The clear knee
space shall be 8 inches in depth minimum at 27 inches minimum
above the floor and 11 inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shall be ignored when
checking the clearances . -- Sec . 4 . 20 . 3 . 1 & Fig. 34 . 20 . 3 . 1
11) A clear floor space of 30 X 48 inches minimum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4 .20 . 3 . 2 & Fig. 34 . 20 . 3 . 2
12) Water supply and drain pipes under lavatories shall be
insulated or otherwise treated to protect against contact .
-- Sec. 4 .20 .4
13) The bottom of mirror is required to be within 38 inches of
the floor. -- Sec. 4 . 16 . 6 & Fig. B4 .20 . 3 . 1
Page # 15
Code review for:
Project Id. : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to be of safety
glazing material . -- Sec . 2406 .3 & 2406 .4
Locations :
1) Glazing in ingress and egress doors except jalousies .
2) Glazing in fixed and sliding panels of sliding door assemblies
and panels in swinging doors other than wardrobe doors .
3) Glazing in storm doors .
4) Glazing in all unframed swinging doors .
5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and showers . Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of the glazing is less than 60 inches above a standing surface
and drain inlet .
6) Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24-inch arc of
either vertical edge of the door in a closed position and where the
bottom exposed edge of the glazing is less than 60 inches above the
walking surface.
7) Glazing in an individual fixed or operable panel, other than those
locations described in items 5 and 6 above, than meets all of the
following conditions :
A. Exposed area of an individual pane greater than 9 square feet .
B. Exposed bottom edge less than 18 inches above the floor.
C. Exposed top edge greater than 36 inches above the floor.
D. One or more walking surfaces within 36 inches horizontally of
the plane of the glazing.
8) Glazing in railings regardless of height above a walking surface .
Included are structural baluster panels and nonstructural in-fill
panels .
9) Glazing in walls and fences used as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less than
60 inches above the pool side and the glazing is within 5 feet
of the pool or spa water' s edge.
10) Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edge is less
than 60 inches above the walking surface.
i
City of Arlington
Building Department
238 North Olympic Avenue
Arlington, Washington 98223
(360) 435-0724
Plan analysis based on
the 1997 Uniform Building Code
Project Number: 98-2950 Date : May 22 , 1998
Project Name : CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
Contractor: BLUE RIBBON STEEL
Occupancy: S3 , S1,B Architect :
Construction: V-N Engineer: H. N. LEHTINEN
Report By: DAVE
NOTE : The code items listed in this report are not intended to be a
complete listing of all possible code requirements in the 1997 UBC.
It is a guide to selected sections of the code .
Report created using Plan Analyst software by b w & a. (719) 599-5622
Portions of the material contained in this program are reproduced
from the Uniform Building Code ( 1991 edition) with permission of the
International Conference of Building Officials .
# SHEET IDENTIFICATION CORRECTION REQUIRED
------------------ ------- --------
1 1 DOORS This is required to be a F hour assembly
since it is in an occupancy separation
wall . -- Sec. 302 . 3
2 1 STORAGE/SHOP This exterior wall is required to be a 1
hour assembly. -- Table 5-A
3 1 STORAGE/LUNCI RM This exteriorwall is required to be a
-
+I - hour assembly. - Table 5-A
4 1 ALL EXITS Provide a landing on both sides of door.
Note : The step & size requirements . -- Sec .
1003 . 3 . 1 . 6 -
5 1 MAIN EXIT Provide access to the building for the
physically disabled. -- Sec. 1103 . 0 & 1104 . 0
w
I I
S
i
I
M
Page # 2
Required corrections for:
Project Id: CEMENT DISTRIBUTORS INC.
Address : 17501 59TH AVE NE
# SHEET IDENTIFICATION CORRECTION REQUIRED
6 1 BOTH BATHROOMS At least one toilet for each sex is
required to comply with the accessibility
requirements . -- Sec . 1105 .2
CASCADE SURVEYING Surveyors
& E NGINEERNS9 INC.
ARLINGTON,WA Engineers
102 E Division•PO Box 326 98223
(360)435-5551 -(360)652-7572 — Planners
FAX(360)435.4012
PROJECT NOTEBOOK FOR
CONCRETE DISTRIBUTORS, INC.
Narrative
A review of city records included the Stormwater Management Plan for the City of Arlington. The SWP
clid not discuss this basin area.
Pollution from the proposed Cement Distributing facility will contribute both petroleum and metals
pollution and raise the ph of the stornmater. The treatment Best Management Plan selected for this site(Wet
Ponds and Infiltration Ponds)will provide a combination of two of the best approved methods for removing
pollutants from storinwatcr.
The pioject notebook is made up of the Construction Plans, and the Drainage Report. The following list indicates
where the required sections of the Project Notebook are located.
1. Storrnwater nu noff and Drainage System Calculations (See Drainage Report)
2. Slorrn Drainage Report Narrative (See Drainage RepoFrt)
3. Erosion and Sediment Control Plans (See Sheets ! & 5)
4. Gradi.iig and Drainage Plans (See Sheet 5)
5. Operation and Maintenance Plan for E.S.C. (See Report and Sheet 5)
6. Operation and Maintenance Plan for Storrnwater Systern (See Report, & sh. 4,5,5)
. Financial Liability Instruments (To be attached)
g. Source Control Narrative for urban setting uses (See Drainage Report)
9. Copy of the Filed Maintenance agreement (To be attached)
10. Legal Descriptions of SWM facilities to be deeded to the City (N/A)
11. Estimate of construction costs as per item 11. (N/A)
12. Inspection and Construction Control Schedule (See Report, & sh. 1)
k'9�
I7 A � �2
..-A. a
ft 61 A 12716
(,',ATV OF AAUNGI I ON ASS/ONAL
9 V EXPIRES 12122V 99
- � - - ��
1 � � i
I
C
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
ARLINGTON,WA Engineers
102 E Division•PO Box 326 98223 `
(360)435-5551 •(360)652-7572 - Planners
FAX(360)435-4012
DRAINAGE REPORT FOR
CONCRETE DISTRIBUTORS, INC.
BASIC ANALYSIS
The proposal is to construct a Cement Distribution facility on lot 4 of the A.A. Investments Short Plat
recorded under A.F.#9608015001. The site is zoned industrial by the City of Arlington. The proposed buildings
are approximately 7,500 sq. ft. and 2,775 sq. ft. and there will also be approximately 200,000 sq. ft. of parking,
driving, and other impervious surfaces. The site falls South of the Airport Basin of Arlington Stormwater
Management Plan,and the plan indicates that soil types in (lie area fall within the Lynnwood grouping(An SCS
Type"A" soil). The Soil Survey of Snohomish County describes typical Lynnwood deposits as follows"This very
deep, somewhat excessively drained soil is on terraces and outwash plains" "The surface layer is grayish brown
loamy sand about I" thick, the upper part of the subsoil is dark brown loamy sand about 14" thick. The substratum
to a depth of 60 inches or more is grayish brown sand." Actual soil types on site were loamy sands to a depth of 30
inches, then a gravelly medium sand to at least 80". The water table was encountered at 80 to 100 inches in depth.
Because of the lack of slope and high infiltration rates in the area of this site there is no off site flow.
There are no known ponding problems even during hcavy rains. There are no natural or constructed conveyences
within 300 yards that aflcct or are'affected by this site. (see U.S.G.S. quad map image below). Stormwater from
the proposed site will be managed with`Vet Ponds and Infiltration Ponds. Based on the above information no
drainage problems are foreseen.
0
A PO
� II
SITE
Edgecomi t
172ND 'Q+ ?� � •
K •+ '
1
1 �
1
SCALE: 1" = 1000' h
1
CASCADE SU FRVEYi NO urveyors
S� ENGINEERING, INC.
ARLINGTON,WA gineers
102 E Division•PO Box 326 98223
(360)435-5551 •(360)652-7572 1+1i
anners
FAX(360)435-4012
TEMPORARY EROSION AND SEDIiVIENTATION CONTROL
A variety of T.E.S.C. measures are being implemented on the constriction plans, these measures provide for the following
areas of concern:
1. Stabilization and Soil Trapping (See TESC Notes, Sh. 1)
2. Delineate clearing and easement limits (See Grading Plans, Sh. 5)
3. Protection of Adjacent Property (Silt Fence)
4. Timing and Stabilization of Sediment Trapping Measures (See TESC Notes, Sh. 1)
5. Cut and Fill Slopes (See Gen. Notes, Sh. 1)
6/ Controlling Off-site erosion (Infiltration Pond)
7. Stabilization of temporary convcyance channels and outlets (N/A)
8. Storm Drain Inlet Protection (See Details, Sh. 6)
9. Underground Utility Construction (See plans)
10. Construction Access Route. (See Grading Plan, Sh. 5) .
11. Removal of Temporary BMP's (See TESL Notes, Sh. 1)
12. Dewatering Construction Site (N/A)
13. Control-of Pollutants other than Sediment on Construction Site (Spill Control)
14. Maintcnance (See TESC Notes, Sh. 1)
15. Financial Liability (See Financial Liability
in this report)
PRESERVATION OF NATURAL DRAINAGE FEATURES
There are no natural drainage features on the site due to the high infiltration rate of the soil. There is no flow from the site
as the existing vegetation cover, and site soils are capable of absorbing a high amount of rainfall.
SOURCE CONTROL OF POLLUTION
The type of activity that is to be going on this site(Cement Distribution) falls into the DOE catagory of Fleet Vehicle Yard
(See DOE Stormwater Manual, IV-2.2.2). The Stormwater Manual for the Puget Sound Basin rccommends the following
for these activities.
"Stormwater from parking lots and maintenance areas where dripping oil or hydraulic fluids is likely to be occurring shall
be treated by an API or CPI-type oil/water separator(BMP RD.35 in Volume III, Runoff Control). Stormwater from
employees parking lots shall also be treated either in with or separately fromt the fleet vehicle parking areas using one of
the systems described in Volume III.
Storinwaler runoff from rooftops may be discharged to the storm drain system as long as the drainage requirements of the
local Public Works Dept. are met. If there is no stormwater drainage system(Storm Sewer) to disharge to, runoff from
rooftops should be disposed of through the use of an infiltration facility wherever possible(see BMP's RI.15 and RI.16 in
Chapter III-3 of the Runoff Control Volume)."
The source control BMP proposed for this site would be BMP RD.35 as detailed in Volume III of the Stormwater Manual for the
Puget Sound Basin. The stormwater from the site is being treated via a combination of an oil/water separator with a debris and two
stage oil control system, Wet Ponds and an Infiltration Pond. The oil/water separator with an installed two stage oil control system
(See attachments from Aqua Treatment systems)will provide a level of treatment capable of removing high percentages of spilled or
leaking pollutants from the stormwater associated with the fleet vehicle storage and maintenance. This system will directly target the
primary pollutants to the stornnvater and in combination with the wet ponds will provide adequate water quality treatment.
�. i�;u
� .,
C
CASCADE SURVEYING Surveyors
Sc ENGINEERING, INC.
ARLINGTON,WA Engineers
9 r
102 E Division•PO Box 326 96223
(360)435-5551 •(360)652-7572 — Planners
FAX(360)435-4012
SOURCE CONTROL OF POLLUTION (continued)
The Stormwaler from the frontage road improvements is being treated via an Infiltration Trench with oil/water separator and an
installed debris and two stage oil control system. The oil/water separator with an installed two stage oil control system(See
attachments from Aqua Treatment systems)will provide a level of treatment capable of removing high percentages of spilled or
leaking pollutants from the stormwater associated with vehicular traffic. This system will directly target the primary pollutants to
the stormwater and should provide adequate water quality treatment.
Alternative water quality treatment BMP's such as Bioswales or Wet Pond excel at lowering the storiTiwater PH, and removing heavy
metals from the stormwater. These are two types of pollution which will not be generated in appreciable amounts by the activities on
the frontage road, or the project site.
RUNOFF TREATMENT BMP'S
Runoff from all storm events from the site is being directed to the Wet Ponds,and thence to an Infiltration Pond. The Wet
Ponds are the water quality best management plan (bmp)while the infiltration Pond is the Streambank Erosion control
BMP: All flow entering the system from the parking lots passes through an oil/water separator before entering any of the
ponds both protecting the ponds sand providing additional wa:cr quality treatment.
Runoff from the frontage improvements is being tri.ated by a combination of a Debris and Two Stage Oil Control System
(by Aqua Treatment Systems, at(206) 343-5221) installed in a catch basin with an Oil/Water Separator also installed. This
system will provide waaerquality treatment to tl►e stormwatercollccled off the road. This management plan'dircctel3- targets
the most common type of pollutants for roads. After passing through one of these systems the stormwater enters an
infiltration trench which will provide streambank erosion control treatment.
STREAMBANK EROSION CONTROL
This requirement is met by discharging all runoff from the site to the Infiltration Pond, and all runoff from the frontage
improvements to the Infiltration trenches in the road right-of-way. See Calculations Section below for Pond and Trench
sizing calculations.
WETLANDS
There are no wetlands on the property.
WATER QUALITY SENSITIVE AREAS
No water quality sensitive areas have been identified on the site, and there is no stormwater discharge from the site to such
an area.
OFF-SITE ANALYSIS AND MITIGATION
There is no offsite discharge from the site, other than to groundwater. The discharge to groundwater from the site is being
treated via wet ponds, and an infiltration pond,while the discharge from the infiltration trenches is being treated via an
oil/water separator device installed in the inlet catch basins. These water quality BMP's wlien combined with Source
Control, and an emergency spill control plan, which is required by both state and federal regulations for any hazardous
materials stored or utilized on site, should be adequate to prevent or control the spills and discharge or liazerdous and
priority pollutants.
J� `w �r \' 'I I 1
�� • � -
• ►
1
- - • • - �• -1. - � -i •. • • . . • � _
7CA�SCADE SURVEYING =Engineers
NGINEERING, INC.ARLINGTON,WA 102 E Dlvislon-PO Box 326 98223 J(�*
(360)435-5551 -(360)652-7572
FAX(360)435-4012
BASIN PLANNING
There is no off-site stormwater discharge, so no Basin Planning issues are applicable.
OPERATIONS AND MAINTENANCE
The owners sliall be responsible for the operations and maintenance of the facilities. See following Maintenance
Requirements for Privately Maintained Drainage Facilities. The owner/applicant will record a binding
inspection/maintenance agreement for the City of Arlington as per AMC 16.10.210.
FINANCIAL LIABILITY
Financial Liability assurance will be provided as assessed by the City of Arlington.
CALCULATIONS
Drainage facilities were designed exclusively for-improvenrenls on-site and for improvements in the right-of-way. Because
of their lack of slope and high infiltration rates the adjacent lots will not contribute any flow to the site. The flow from the
parking, loading and driving surfaces will be treated by vvct ponds on its way to the infiltration pond. The infiltration pond
is designed to accornodate.the flow from the er.zirc site;:exceptihc frontage road. Tlic infiltration trencli in the road right-of
-way is designed to treat the frontage improvements.
I
Soils work performed on this site on February 6, 1999 indicate brown sandy loams (to 2' deep)overlaying gravelly medium
sands with a water table encountered at between 7' to 9' down. The proposal is to construct infiltration trench's and pond
bottom in the medium sands .
INFILTRATION TRENCH:
The infiltration trench will be 3 feet wide by 2.5 feet deep by 290 feet long. The trench will be divided into 2 parts
(separated by a catch basin) and located between the southerly 3 catch basins in the road right-of-way(see Site Plan). The
D.O.E. recommended rate of infiltration for medium sands is 8.27 inches per hour. We are proposing to contain all storm
events within the above mentioned trench. The dimensions of the trench will have a bottom width of 3 ft. and be 290 ft.
long. Using these variables the maximum infiltration from the trench may be calculated:
3.Oft x 290 ft. x 4.13 in x 1 hr. x 1 min. x 1 ft. = 0.083 c.f.s.
ft hr. 60 min. 60 sec. 12 in.
The Volume of the Trench can be calculated as follows:
290' x 3' wide x 2.5' high x 35% void space = 761 cu. ft. +
290' x 3.14(.33)2 x 65% = 64 cu. ft + 761 cu. ft. or 825 cu. ft. of trench storage
The storage calculations were performed using Hydra (Ver. 5.20),by Pizer, Inc. The calculation method used was a
modified(urban) Soil Conservation Service. The storm used was an SCS Type 1-A storm. Variables used in the '
calculations included vegetation cover, slope, percent impervious,basin sizes, and curve numbers for the soil type. The
curve numbers were taken from the Department of Ecology's Stormwater Manual for the Puget Sound Basin,Table III-1.3.
It is proposed to store all the storm events in the trench. At the peak of the 2 year storm event the total required storage will
be 116 cubic feet (link 3 page 5 of Hydra, 2 Year Storm). At the peak of the 10 year storm event the total required storage
will be 293 cubic feet (link 3 page 6 of Hydra, 10 Year Storm). At the peak of the 100 year storm event the total required
storage will be 596 cubic feet (link 3, page 7, Hydra, 100 Year Storrs)leaving 229 cf of storage remaining in the trench.
! .� ..
i .,
FCCAISCADE SURVEYING Surveyors
NGINEERING, INC. t
Engineers
ARLINGTON,WA
102 E Division•PO Box 326 98223 `
(360)435.5651 •(360)652-7572 — Planners
FAX(360)435-4012
CALCULATIONS (CONTINUED)
INFILTRATION POND:
The infiltration pond system will consist of 3 cells, a main infiltration cell bracketed by two smaller wet pond cells on the East and
West ends of the main cell (see Site Plan). The stage-storage relationship for the three cells is summarized in the following tables.
CELL ELEVATION AREA STORAGE
WEST WET CELL 127.5 641 0
WEST WET CELL 128.0 759 0/350 (WET)
WEST WET CELL 129.0 1020 890
WEST WET CELL 130.0 1313 2056
CELL ELEVATION AREA STORAGE
EAST WET CELL 127.5 638 0
WEST WET CELL 128.0 756 0/349 (WET)
WEST WET CELL 129.0 1016 886
WEST WET CELL 130.0 1308 2048
CELL ELEVATION AREA STORAGE
INFILTRATION CELL 128.0 7029 0
INFILTRATION CELL 129.0 8131 7580
INFILTRATION CELL 130.0 9259 15919
TOTAL STORAGE 130.0 20023
The storage calculations were performed using Hydra (Ver. 5.20), by Pizer, Inc. The calculation method used was a modified
(urban) Soil Conservation Service. The storm used was an SCS Type 1-A storm. Variables used in the calculations included
vegetation cover, slope, percent impervious, basin sizes, and curve members for the soil type. The curve numbers were taken from
the Department of Ecology's Storniwaler Manual for the Puget Sound Basin,Table 11I-1.3. A curve number normally associated with
paved surfaces was used for the gravel parking area to account for future paving potential.
It is proposed to store all the storm events in the pond system. At the peak of the 2 year storm event the total required
storage will be 3362 cubic feet(link 4 page 5 of Hydra, 2 Year S(orm). At the peak of the 10 year storm event the total
required storage will be 8889 cubic feet (link 4 page 6 of Hydra, 10 Year Storm). At the peak of the 100 year storm event
the total required storage will be 18062 cubic feet (link 4, page 7. Hydra, 100 Year Storm) leaving just over F of excess
storage remaining in the pond before overtopping occurs.
WET POND SIZING:
A Hydra caculation was performed to determine the required storage for the wet pond cells. The wet ponds are sized to
store at least the 6 mo. storm event. The required storage amount was determined to be 367 cf(Scc Link 4, page 8, Hydra,
6 Month Storm). The actual storage provided was approximately 700 cf, the larger volume will compensate for storage
volume lost to sedimentation during construction and on going usage.
Y � �. ,�
'_ '. .,
- i . . .�
CASCADE SURVEYING Surveyors
& ENGINEERING, INC.
ARLINGTON,WA engineers
102 E Division•PO Box 326 98223 ,,
(360)435-5551 •(360)652-7572 — Planners
FAX(360)435-4012
CDI February 2, 1998 JOB #12636 DOE Perc. Rate IN/HR
SOIL LOG 1: 0-12" Brown Sandy Loam 1.02
12-30" Tan loamy Sand 2.41
30-93" Gray Grav, med. Sand 8.27
93-96" Saturated. gray, Gray. med. Sand 0.00
96"+ Water table 0.00
SOIL LOG 2: 0-12" Brown sandy loam 1.02
12-20" Tan loamy Sand 2.41
'20-80" Gray gravelly rued. sand 8.27
80"+ Water table 0.00
SOIL LOG 3: 0-10" Brown sandy loam _ 1.02
10-24" Tan loamy sand 2.41
24-96" Gray gravelly medium sand 8.27
96-104" Saturated Gray,.Gray. med. Sand 0.00
104"+ Water Table
SOIL LOG 4: 0-8" Brown sandy loam 1.02
8-22" Tan Loamy Sand 2.41
22-91" Gray Gravelly med. sand 8.27
91-i0i" Saturated Gray, Gray. med. Sand 0.00
10111+ Water Table
MAINTENANCE AND OPERATIONS
CHECKLIST
�`
I
I
MAINTENANCE REQUIREMENTS FOR
PRIVATELY MAINTAINED DRAINAGE FACILITIES
PONDS
MAINTENANCE DEFECP CONDITIONS IVHEN MAINTENANCE IS RESULTS EXPECTED WIZEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH&DEBRIS :\,NY TRASH AND DEBRIS WHICH EXCEED 1 TRASH AND DEBRIS CLEARED
CUBIC FOOT PER 1,000 SQUARE FEET(THIS IS FROM SITE.
,\BOO TT EQUAL TO THE AMOUNT OF TRASH IT
WOULD TAKE TO FILL UP ONE STANDARD
SIZE OFFICE GARBAGE CAN). IN GENERAL,
THERE SHOULD BE NO VISUAL EVIDENCE OF
DUMPING.
i
POISONOUS ANY POISONOUS VEGETATION WHICH MAY NO DANGER OF POISONOUS
VEGETATION CONSTITUTE A HAZARD TO COUNTY VEGETATION WHERE COUNTY
PERSONNEL OR THE PUBLIC. EXAMPLES OF PERSONNEL OR THE PUBLIC
POISONOUS VEGETATION INCLUDE: TANSY MIGHT NORMALLY BE.
RAGWORT,POISON OAK,STINGING NETTLES, (COORDINATION WITH HEALTH
DEITLS CLUB. - DEPARTMENT).
POLLUTION OIL-GASOLINE,OR OTHER CONTAMINANTS NO CONTAMINANTS PRESENT
OF ONE GALLON OR MORE OR ANY AMOUNT OTHER THAN A SURFACE FILM.
FOUND THAT COULD: 1)CAUSE DAMAGE TO (COORDINATION WITH HEALTH
PLANT,ANIMAL,OR MARINE LIFE,2) DEPARTMENT).
CONSTITUTE A FIRE HAZARD;OR 3)BE
FLUSHED DOWNSTREAM DURING RAIN
STORMS.:
UJNNIOWED IF FACILITY IS LOCATED IN PRIVATE WHEN MOWING IS NEEDED,
GRASS/GROUND RESIDENTIAL AREA.MOWING IS NEEDED GRASS/GROUND COVER SHOULD
COVER WHEN GRASS EXCEEDS 18 INCHES IN HEIGHT. BE MOWED TO 2 INCHES HEIGIIT.
IN OTHER AREAS,THE GENERAL POLICY IS TO
JfAKE THE POND SITE MATCH ADJACENT
GROUND COVER AND TERRAIN AS LONG AS
THERE IS NO INTERFERENCE WITH THE
FUNCTION OF THE FACILITY.
RODENT HOLES ANY EVIDENCE OF RODENT HOLES IF RODENTS DESTROYED AND DAM
FACILITY IS ACTING AS A DAM OR BERM,OR OR BERM REPAIRED.
ANY EVIDENCE OF WATER PIPING THROUGH (COORDINATION WITH HEALTH
DANI OR BERM VIA RODENT HOLES. DEPARTMENT
INSECTS WHEN INSECTS SUCH AS WASPS AND INSECTS DESTROYED OR
HORNETS INTERFERE WITH MAINTENANCE REMOVED FROM SITE.
ACTIVITIES.
i �
v
_ i e: � i `i
� —
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE 1S RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
TREE GROWTH TREE GROWTH DOES NOT ALLOW TREES DO NOT HINDER
MAINTENANCE ACCESS OR INTERFERES WITH MAINTENANCE ACTIVITIES.
MAINTENANCE ACTIVITY(I.E.,SLOPE SELECTIVELY CULTIVATE TREES
MOVING,SILT REMOVAL,VACTORING,OR SUCH AS ALDERS FOR FIREWOOD.
EQUIPMENT NIOVENIENTS). IF TREES ARE NOT
INTERFERING WITH ACCESS,LEAVE TREES
ALONE.
SIDE SLOPES OF EROSION ERODED DAMAGE OVER 2 INCHES DEEP SLOPES SHOULD BE STABILIZED
POND WHERE CAUSE OF DAMAGE IS STILL PRESENT BY USING APPROPRIATE EROSION
OR WHERE THERE IS POTENTIAL FOR CONTROL MEASURE'(S);E.G.,ROCK
CONTINUE EROSION. REINFORCEMENT.PLANTING OF
GRASS,COMPACTION.
STORAGE.AREA SEDIMENT ACCUMULATED SEDIMENT THAT EXCEEDS SEDIMENT CLEANED OUT TO
10%OF THE DESIGNED POND DEPTH. DESIGNED POND SHAPE AND
DEPTH;POND RESEEDED IF
NECESSARY TO CONTROL
EROSION.
POND DIKES SETTLEMENTS ANY PART OF DIKE WHICH HAS SETTLED 4 DIKE SHOULD BE BLTIL"I'BACK TO
INCITES LOWER THAN THE DESIGN THE DESING ELEVATION.
IiI.E\'ATION.
EMERGENCY ROCK MISSING ONLY ONE LAYER OR ROCK EXISTS ABOVE REPLACE ROCKS TO DESIGN
OVERFLOW/ NATIVE SOIL IN ARE FIVE SQUARE FEET OR STANDARDS.
SPILLWAY LARGER,OR ANY EXPOSURE OF NATIVE SOIL.
2
i
.., _ _ ''
��
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES
MAINTENANCE DEFECT CONDITIONS WIIEN MAINTENANCE IS RESULTS EXPECTED NVIIEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
INFILTRATION
GENERAL, TRASH&DEBRIS SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. 1
POISONOUS SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. 1
VEGETATION
POLLUTION SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO. 1
UVMOWED GRASS/ SEE"PONDS"STANDARD NO.I SEE"PONDS"STANDARD NO.1
GROUND COVER
RODENT HOLES SEE"PONDS"STANDARD NO.I SEE"PONDS"STANDARD NO. 1
INSECTS SEE"PONDS"STANDARD NO.I SEE"PONDS"STANDARD NO. 1
STORAGE AREAS SEDIMENT A PERCOLATION TEST PIT OR TEST OF SEDIMENT IS REMOVED AND/OR
FACILITY INDICATES FACILITY IS ONLY FACILITY IS CLEANED SO THAT
WORKING AT 904•o OF ITS DESIGNED INFILTRATION SYSTEM WORKS
CAPABILITIES. IF TWO INCHES OR MORE ACCORDING TO DESIGN.
SEDIMENT IS PRESENT,REMOVE.
SHEET COVER(IF SHEET COVER IS VISIBLE.AND HAS MORE SHEET COVER REPAIRED OR
APPLICABLE) THAN THREE 1/4 INCH HOLES N IT. REPLACED.
SUMP FILLED WITII AIN Y SEDIMENT AND DEBRIS FILLING VAULT CLEAN OUT SUMP TO DESIGN
SEDMIMENT AND TO 10%OF DEPTH FROM SUMP BOTTOM TO DEPTH.
DEBRIS(IF BOTTOM OF OUTLET PIPE OR OBSTRUCTING
APPLICABLE) FLOW INTO THE CONNECTOR PIPE.
FILTER BAGS FILLED WITH SEDIMENT.AND DEBRIS FILL BAG MORE REPLACE FILTER BAG OR
SEDIMENT AND THAN 1/2 FULL. REDESIGN SYSTEM.
DEBRIS
ROCK FILTERS SEDIMENT:AND BY VISUAL INSPECTION,LITTLE OR NO REPLACE GRAVEL IN ROCK
DEBRIS WATER FLOWS THROUGH FILTER DURING FILTER.
HEAVY RAIN STORMS.
SIDE SLOPES OF EROSION SEE"PONDS"STANDARD NO.1 SEE"PONDS"STANDARD NO.1
POND
EMERGENCY ROCK MISSING SEE"PONDS"STANDARD NO. 1
OVERFLOW
SPILLWAY
SETTING PONDS SEDIMENT REMOVE WHEN 6"OR MORE.
AND AULTS
3
._ i�
n
I
l!
1
I
f
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
NOTE: SEDIMENT ACCUMULATION OF MORE THAN.25 INCHES PER YEAR MAY INDICATE EXCESSIVE EROSION IS OCCURRING
UPSTREAM OF THE FACILITY OR THAT CONVEYANCE SYSTEMS ARE NOT BEING PROPERLY MAINTAINED. THE CONTRIBUTING
DRAINAGE AREA SHOULD BE CHECKED FOR EROSION PROBLEMS OR INADEQUATE MAINTENANCE OF CONVEYANCE.SYSTEMS IF
EXCESSIVE SEDIMENTATION 1S NOTED IN AN INFILTRATION FACILITY.
CHECK TWICE A YEAR DURING FIRST 2 YEARS OF OPERATION; ONCE A YEAR THEREAF rER. CLEAN MANHOLES/CATCH BASINS.
REPAIR D.N\IAGED INLETS/OUTLETS,CLEAN TRASH RACKS.
4
,� �� ,: _
I
1
I
I
I
\ ti
MAINTENANCE REQUIREMENTS FOR
PRIVAELY MAINTAINED DRAINAGE FACILITIES
CONTROL STRUCTUREIFLOW RESTRICTOR
MAINTENANCE DEFECT CO3"ITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT NIA1N PENANCE IS NEEDED MAINTENANCE IS PERFORMED
GENERAL TRASH XNTD DEBRIS DISTANCE BETWEEN DEBRIS BUILD- ALI.TRASH AND DEBRIS REMOVED.
(INCLUDES 111';UND BOTTOM OF ORIFICE PLATE
SEDIMENT) IS LESS THAN 1 1/2 FEET.
STRUCTURAL STRUCTURE IS NOT SECURELY STRUCTURE SECURELY ATTACHED TO
DAMAGE ATTACHED TO MANHOLE WALL WALL AND OUTLET PIPE.
AND OUTLET PIPE STRUCTURE
SHOULD SITPPORT AT LEAST 1,000
POUNDS OF UP OR DOWN PRESSURE.
1
STRUCTURE IS NOT IN UPRIGHT STRUCTURE IN CORRECT POSITION.
POSITION(ALLOW UP TO 10%FROM
PLUMB).
C ONNF.CTIONS TO OUTLET PIPE.ARE CONNECTIONS TO OUTLET PIPE ARE
NOT N\'ATERTIGHT AND SHOW WATERTIGHT;STRUCTURE REPAIRED OR
SIGNS OF RUST. REPLACED AND WORKS AS DESIGNED.
ANY HOLES-OTHER THAN
DESIGNED HOLES-IN THE
STRUCTURE.
CLEANOUT GATE DAMAGED OR CLEANOUT GATE IS NOT GATE IS WATERTIGHT AND WORKS AS
MISSING WATERTIGHT OR IS MISSING DESIGNED.
GATE CANNOT BE MOVED UP AND GATE MOVES UP AND DOWN EASILY AND
DOWN BY ONE MAINTENANCE IS WATERTIGHT.
PERSON.
CHAIN LEADING TO GATE IS CHAIN IS IN PLACE AND WORKS AS
MISSING OR DAMAGED. DESIGNED.
GATE IS RUSTED OVER 504o OF ITS GATE IS REPAIRED OR REPLACED TO MEET
SURFACE:AREA. DESIGN STANDARDS.
ORIFICE PLATE DAMA(JED OR CONTROL DEVICE IS NOT WORKING PLATE IS IN PLACE AND WORKS AS
MISSING PROPERLY DUE TO MISSING,OUT OF DESIGNED.
PLACE.OR BENT ORIFICE PLATE.
6
i
. � -
MAINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAIN-1 E.NANCE IS NEEDED NLVNTF.\ANCE IS PERFORMED
OBSTRUCTIONS ANY TRASH,DEBRIS,SEDIMENT,OR PLATE IS FREE OF ALL OBSTRUCTIONS
VEGETATION BLOCKING THE PLATE. AND WORKS AS DESIGNED.
OVERFLOW PIPE OBSTRUCTIONS ANY TRASH OR DEBRIS BLOCKING PIPE IS FREE OF ALL OBSTRUCTIONS AND
(OR IfAVING THE POTENTIAL OF WORKS AS DESIGNED.
BLOCKING)THE OVERFLOW PIPE.
MANHOLE SEE"CLOSED DETENTION SYSTEMS" SEE"CLOSED DETENTION SYSTEMS"
STANDARD NO.3 STANDARD NO.3
CATCH BASIN SEE"CATCH BASIN"STANDARD NO. SEE"CATCH BASIN"STANDARD NO.5
5
7
I�
.I
i
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES
CATCH BASINS
MAINTENANCE DEFECT CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED M_AINTENANC'E IS PERFORIIIED
GENERAL TRASH&DEBRIS 'TRASH OR DEBRIS OF MORE THAN 1/2 NO TRASH OR DEBRIS LOCATED
(INCLUDES CUBIC FOOT WHICH IS LOCATED IMMEDIATELY IN FRONT OF
SEDIMENT) IMMEDIATELY IN FRONT OF THE CATCH CATCH BASIN OPENING.
BASIN OPENING OR IS BLOCKING CAPACITY
OF BASIN BY MORE THAN I00o.
TRASH OR DEBRIS(IN THE BASIN)THAT NO TRASH OR DEBRIS IN THE
EXCEEDS 1/3 THE DEPTH FROM THE CATCH BASIN.
BOTTOM OF BASIN TO INVERT T OF THE
t LOWEST PIPE INTO OR 01IT OF THE BASIN.
TRASH OR DEBRIS IN ANY INLET OR INLET AND OUTLET PIPES FREE.
OU"I'LET PIPE BLOCKING MORE THAN 1/3 OF OF TRASH OR DEBRIS.
ITS HEIGHT.
DEAD ANIMALS OR VEGETATION THAT NO DEAD ANIMALS OR
COT.LD GENERATE ODORS THAT WOULD VEGETATION PRESENT WITIIIN
CAUSE COMPLAINTS OR DANGEROLiS THE CATCH BASIN.
(_iASF.S(E.G._METHANE).
DEPOSITS OF GARBAGE EXCEEDING 1 NO CONDITION PRESENT WHICH
CUBIC FOOT IN VOLUME. WOULD A717RACT OR SUPPORT
THE BREEDING OF INSECTS OR
RODENTS.
STRUCTURAL CORNER OF FRAME EXTENDS MORE THAN FRANtE IS EVEN WITH CURB.
DAMAGE TO FRAME 3/4 INCH PAST CURB FACE INTO THE
AND%OR TOP SLAB STREET(IF.APPLICABLE).
TOP SLAB HAS HOLES LARGER THAN 2 TOP SLAB IS FREE OF HOLES AND
SQUARE INCHES OR CRACKS WIDER THAN CRACKS.
1/4 INCH(INTENT IS TO MAKE SURE AL.I,
MATERIAL IS RUNNING INTO THE BASIN).
FRAME NOT SITTING FLUSH ON TOP SLAB,I. FRAME IS SITTING FLUSII ON TOP
E..SEPARATION OF MORE THAN 3/4 INCH OF SLAB.
THE FRAMME FROM THE TOP SLAB.
CRACKS IN BASIN CRACKS WIDER THAN 1/2 INCH AND BASIN REPLACED OR REPAIRED
WALL&BOTI'O16I LONGER THAN 3 FEET,ANY EVIDENCE OF TO DESIGN STANDARDS.
SOIL PARTICLES ENTERING CATCH BASIN
THROI IGH CRACKS,OR MAINTENANCE
PERSON JUDGES THAT STRUCTURE IS
UNSOUND.
CRACKS WIDER THAN 1/2 INCH AND NO CRACKS MORE THAN 1/4
LONGER THAN 1 FOOT AT THE JOINT OF INCH WIDE AT THE JOINT OF
ANl Y INLET/OUTLET PIPE OR ANY EVIDENCE INLET/OUTLET PIPE.
OF SOIL PARTICLES ENTERING CATCH
BASIN THROUGH CRACKS.
8
• - - .. - • - � - - - _ - .� � 1
1
..
I
MAINTENANCE DEF F C.T CONDITIONS WHEN MAINTENANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
SETTLEMENT/ BASIN HAS SETTLED MORE THAN 1 INCH OR BASIN REPLACED OR REPAIRED
MISALIGNMENT HAS ROTATED MORE THAN 2 INCHES OUT TO DESIGN STANDARDS.
OF ALIGNMENT.
FIRE HAZARD PRESENCE OF CHEMICALS SUCH AS NO FLAMMABLE CHEMICALS
NATURAL.GAS.OIL,GASOLINE. PRESENT.
VEGETATION VEGETATION GROWING ACROSS AND NO VEGETATION BLOCKING
BLOCKING MORE THAN 10%OF THE BASIN OPENING TO BASIN.
OPENING.
VEGETATION GROWING IN INLET/OUTLET NO VEGETATION OR ROOT
PIPE JOINTS THAT IS MORE THAN SIX GROWTH PRESENT.
INCHES TALL AND LESS THAN SIX INCHES
APART.
POLLUTION NONFLAMMABLE CHEMICALS OF MORE NO POLLUTION PRESENT OTHER
THAN 1/2 CUBIC FOOT PER THREE FEET OF THAN SURFACE FILM.
BASIN LENGTH.
CATCH BASIN COVER COVER NOT IN COVER IS MISSING OR ONLY PARTIALLY IN CATCH BASIN COVER IS CLOSED.
PLACE PLACE. ANY OPEN CATCH BASIN REQUIRED
MAINTENANCE.
LOCKING \MECHANISM CANNOT BE OPENED BY ONE MECHANISM OPENS WITH
NIECH.AN[SNI NOT %MAINTENANCE PERSON WITH PROPER PROPER TOOLS.
WORKING TOOLS. BOLTS INTO FRAME HAVE LESS
THAN l/2 INCH OF THREAD.
COVER DIFFICULT TO ONE MAINTENANCE PERSON CANNOT COVER CAN BE REMOVED BY
REMOVE REMOVE LID AFTER APPLYING 80 LBS.OF ONE MAINTENANCE PERSON.
LIFT;INTENT IS KEEP COVER FROM
SEALING OFF ACCESS TO MAINTENANCE.
LADDER LADDER RUNGS LADDER IS UNSAFE DUE TO MISSING LADDER MEETS DESIGN
UNSAFE RUNGS,MISALIGNMENT,RUST,CRACKS,OR STANDARDS AND ALLOWS
SHARP EDGES. MAINTENANCE PERSON SAFE
ACCESS.
METAL GRATE (IF GRATE OPENING WIDER THAN 7/8 INCH. GRATE OPENINGS MEET'DESIGN
APPLICABLE) STANDARDS.
TRASH AND DEBRIS TRASH AND DEBRIS THAT IS BLOCKING GRATE FREE OF TRASH AND
MORE THAN 20%OF GRATE SURFACE. DEBRIS.
DAMAGED OR GRATE MISSING OR BROKEN MEMBER(S)OF GRATE IS IN PLACE AND MEETS
MISSING THE GRATE. DESIGN STANDARDS.
9
i
,,
i
MAINTENANCE REQUIREMENTS FOR PRIVATELY
MAINTAINED DRAINAGE FACILITIES.
CONVEYANCE SYSTEMS (PIPES AND DITCHES)
*MAINTENANCE DEFECT CONDITIONS WHEN iN.LAINTE.N ANCE IS RESULTS EXPECTED WHEN
COMPONENT NEEDED MAINTENANCE IS PERFORMED
PIPES SEDIMENT&DEBRIS AC'C ITNII?LATED SEDIMENT THAT EXCEEDS PIPE CLEANED OF ALL SEDIMENT
20no OF THE DIAMETER OF THE PIPE. AND DEBRIS.
VEGETATION VEGETATION THAT REDUCES FREE ALL VEGETATION REMOVED SO
MOVEMENT OF WATER THROUGH PIPES. WATER FLOWS FREELY THROUGH
PIPES.
DAMAGED PROTECTIVE COATING IS DAMAGED; RUST PIPE REPAIRED OR REPLACED.
1S CAUSING MORE THAN 50%
DETERIORATION TO ANY PART OF PIPE.
AiNY DENT TIfAT DECREASES THE CROSS PIPE REPAIRED OR REPLACED.
SECTION AREA OF PIPE BY MORE THAN
TRASH&DEBRIS TRASH AND DEBRIS EXCEEDS 1 CUBIC FOOT TRASH AND DEBRIS CLEARED FROM
PER 1.000 SQUARE FEET OF DITCH AND DITCHES.
SLOPES.
OPEN DITCHES SEDIMENT ACCUMULATED SEDIMENT THAT EXCEEDS DITCH CLEANED/FLUSHED OF ALL
20"o OF THE DESIGN DEPTH. SEDIMENT AND DEBRIS SO THAT IT
MATCHES DESIGN.
VEGET.Y\TION VEGETATION THAT REDUCES FREE WATER FLOWS FREELY THROUGH
MOVEMENT OF WATER THROUGH DITCHES. DITCHES.
EROSION DAMAGE SEE"PONDS—STANDARD NO. 1 SEE"PONDS"STANDARD NO. I
TO SLOPES
ROCK LINING OUT OF MAINTENANCE PERSON CAN SEE NATIVE REPLACE ROCKS TO DESIGN
PLACE OR MISSING SOIL BENEATH THE ROCK LINING. STANDARD.
(IF APPLICABLE)
CATCH BASINS SEE"CATCH BASINS"STANDARD NO.5 SEE"CATCH BASINS"STANDARD NO.
5
DEBRIS BARRIER E.G. SEE"DEBRIS BARRIERS"STANDARD NO.6 SEE"DEBRIS BARRIERS"STANDARD
TRASH RACK NO.6
f
14
�i
r
MAINTENANCE REQUIREMENTS FOR PRIVATELY MAINTAINED
DRAINAGE FACILITIES.
GROUNDS(LANDSCAPING)
\1AINTENANCE DEFECT CONDITIONS WHEN RESULTS EXPECTED WHEN
COMPONENT MAINTENANCE IS MAINTENANCE IS PERFORMED
NEL•'DED
WEEDS WEEDS GROWING IN WEEDS PRESENT IN LESS THAN 5%OF
(NONPOISONOI TS) ;MORE THAN 20%OF THE THE LANDSCAPED ARF,A.
LAND-SCAPED AREA
(TREES AND SHRUBS
ONLY).
GENERAL
SAFETY HAZARD ANY PRESENCE OF POISON NO POISONOUS VEGETATION PRESENT IN
IVY OR OTHER POISONOUS A LANDSCAPED AREA.
VEGETATION.
TRASH OR L11-FER. PAPER-CAN,BOTTLES, AREA CLEAR OF LITTER.
TOTALING MORE THAN I
CUBIC FOOT WITHIN A
LANNDSCAPED AREA
(TREES AND SHRUBS
ONLY)OF 1,000 SQUARE
FEET.
DAMAGE LIMBS OR PARTS OF TREES TREES AND SHRUBS WITH LESS THAN 546
OR SHRUBS THAT ARF, OF THE TOTAL FOLIAGE WITH SPLIT OR
SPLIT OR BROKEN WHICH BROKEN LIMBS.
AFFECT MORE THAN 25%
OF THE TOTAL FOLIAGE
OF THE TREE,OR SHRUB.
TREES AND
SHRUBS
TREES OR SHRUBS THAT TREE OR SHRUB IN PLACE I'RF:E OF
HAVE BEEN BLOWN DOWN INJURY.
OR KNOCKED OVER.
TREES OR SHRUBS WHICH TREE OR SHRUB IN PLACE AND
ARE OT ADEQUATELY ADEQUATELY SUPPORTED;REMOVE ANY
SUPPORTED OR ARE DEAD OR DISEASED TREES.
LEANING OVER,CAUSING
EXPOSURE OF THE ROOTS.
ill
i�
I
I
��
HYDRA CALCULATIONS
DEVELOPED STORM MODEL
III
- ►
1
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 1
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
Status of DEFAULTS at start of run. ( * May be reset by SET)
Command file : C:\HYDRA\CMD\12636.CMD
Input units are read as USA
� * Output sent to display Brief
� * Output sent to printer Off
� * Output sent to file Brief
Paper width in inches 8.000
String to reset printer 27 51 36 18
String to set printer to compressed 17 15
String to set printer to 8 lines/inch 8 27 51 27
Name of printer Epson, FX series
Print heading at top of page True
Number of steps in hydrograph 240
Step length in minutes 10
Significant flow in hydrograph 0.000
� * Maximum plot value Selected by HYDRA
Type of hydrographic plot Compact
Sanitary flow by Peaking Factor
Delay to start of actual storm 0.00
Rational Method computations Hydrograph
SCS computations Santa Barbara
Continuous simulation computations On
� * Maximum d/D for pipe design/analysis 0.900
� * Match point position on pipe 0.00 or Invert
� * Number of allowable diam drops 999
� * Mimimum drop thru manhole 0.000
Routing technique Quick
� * Calculate sanitary flows True
� * Calculate infiltration flows False
� * Calculate storm flows True
� * Calculate misc flows True
+--------------------------------------------------------------------
1: JOB 12636
2: TOT 1.8 (6mo=0.90 2yr=1.8,10YR=2.75, 25yr=3.2, 100yr=3.75)
3: STE 10
4: FIL SCS 1A.INC
------START OF SUB-FILE------
1: REM SCS Type 1A Distribution (100 year - 24 hour)
2: HYE 10 0.0040 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
3: 0.004 0.005 0.005 0.005 0.005 0.005 0.005 0.006 0.006 0.006 +
4: 0.006 0.006 0.006 0.007 0.007 0.007 0.007 0.007 0.007 0.0082
5: 0.0082 0.0082 0.0082 0.0082 0.0082 0.0095 0.0095 0.0095 +
6: 0.0095 0.0095 0.0095 0.0133 0.0133 0.0133 0.018 0.018 0.034 +
1
. - I
1
.,
I
. : _
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 2
------------------------------------------------------------------------------
------------------------------------------------------------------------------
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
7: 0.054 0.027 0.018 0.0133 0.0133 0.0133 0.0088 0.0088 0.0088 +
8: 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 0.0088 +
9: 0.0088 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 0.0072 +
10: 0.0072 0.0072 0.0072 0.0072 0.0072 0.0057 0.0057 0.0057 +
11: 0.0057 0.0057 0.0057 0.0057 0.0057 0.0057 0.0057 0.0057 +
12: 0.0057 0.005 0.005 0.005 0.005 0.005 0.005 0.005 0.005 +
13: 0.005 0.005 0.005 0.005 0.004 0.004 0.004 0.004 0.004 +
14: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
15: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
16: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
17: 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 0.004 +
18: 0.004 0.004 0.0006
Total in original hyetograph : 0.17 Inches
Total volume rain in production hyetograph : 1.80 Inches
Maximum intensity : 0.59 Inches/Hr
19: RET
------ END OF SUB-FILE ------
5: PDA 0.012, 6, 1, 0.5, 2, 0.004, 60
6:
7: NEW ROAD
8: SCS 0.06, 1, 98, 68, 20, 0.005, 70 BASIN (A)
Computed concentration time : 0.82 Minutes
9: PIP 150, 132.15, 132.60, 130.15, 128.15, 8
NOTE: No flow to inlet.
10: SCS 0.10, 1, 98, 68, 20, 0.005, 120 BASIN (B)'
Computed concentration time : 1.41 Minutes
11 : SCS 0.10, 1, 98, 68, 20, 0.005, 120 BASIN (C)
Computed concentration time : 1.41 Minutes
12: SCS 0.10, 1, 98, 68, 20, 0.005 120 BASIN (D)
Computed concentration time : 1.41 Minutes
13: RES 207 0/0 25/0.088 825/.083
NOTE: No flow to inlet.
14: REM CALCULATIONS BASED ON A 110' LONG TRENCH WITH A 6' BOTTOM.
15: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
16: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
17 : REM RATE: (290' X 3' WIDE X 4.13IN/HR / 43200 = 0.083 CFS)
18: REM VOLUME: (290' X 3' WIDE X 2.5' HIGH X 35% = 761 CU. FT.
I�I
I
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 3
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
19: REM + 290' x PI( .33)"2 x 65% = 64 CU. FT OR 825 CU. FT. TOTAL
20: HOL ROAD
21:
22: NEW SITE
23: SCS 0.47, 1, 98, 68, 20, .003, 600 (BLDGS AND PAVED PARKING)
Computed concentration time : 9.13 Minutes
24: SCS 5.27, .95, 98, 68, 15, .003, 600 (REST OF SITE)
Computed concentration time : 12.17 Minutes
25: RES 207 0/0 85/0.67 20023/0.885
NOTE: No flow to inlet.
26: REM CALCULATIONS BASED ON A 265' LONG POND WITH A 27' BOTTOM.
27: REM THIS INFILTRATION RATE IS BASED ON A PERC RATE OF 4.13 in/hr
28: REM WHICH IS 1/2 THE RECOMMENDED DOE RATE FOR SAND.
29: REM 0.01 ' DEEP: (7029 X 4.13 / 43200 = 0.67) VOL. = 85 CU. FT.
30: REM 2.00' DEEP: (9259 X 4.13 / 43200 = 0.885) VOL. = 20023 CU. FT.
31: END
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington Page 4
C:\HYDRA\CMD\12636.CMD
---------------------14:03 27-Feb-98
------ S U M M A R Y O F A N A L Y S I S ------
Run number on command file 34
Number of links 3
Number of hydrographs 46
Total sanitary population 0
Total sanitary area 0.00 Acres
Total storm area 6.10 Acres
Number of pumps 0
Number of reservoirs 2
Number of diversion structures 0
Number of inlets 0
Length of new pipe 150.00 Feet
Length of existing pipe 0.00 Feet
Length of channel 0.00 Feet
Length of gutter 0.00 Feet
Length of transport units 0.00 Feet
Length of pressure pipe 0.00 Feet
. . i
1
}
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 2 YEAR STORM Page 5
C:\HYDRA\CMD\12636.CMD 14:03 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.0 1.53 0.03 0
128.15 4.45 0.0 0.0 0.12
*** ROAD Reservoir
Invert --------- - ---- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge 0.00 0.00 0.09 0.00 0.09 0
207 .00 Stored 0 0 116 0 116
Incoming 0.00 0.00 0.19 0.00 0.19
------------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.71 0.0'0 0.71 0
Unknown Stored 0 0 3362 0 3362
Incoming 0.00 0.00 2.16 0.00 2.16
----------------------------------------------------
Lateral length= 0 Upstream length= 0
,�,
I
I
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 10 YEAR STORM Page 6
---------------------------------------------------------------------------
C:\HYDRA\CMD\12636.CMD 14:05 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.1 1.76 0.05 0
128.15 4.45 0.0 0.0 0.15
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge 0.00 0.00 0.09 0.00 0.09 0
207.00 Stored 0 0 293 0 293
Incoming 0.00 0.00 0.30 0.00 0.30
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values ----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.77 0.00 0.77 0
Unknown Stored 0 0 8889 0 8889
Incoming 0.00 0.00 3.41 0.00 3.41
----------------------------------------------------
Lateral length= 0 Upstream length= 0
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 100 YEAR STORM Page 7
C:\HYDRA\CMD\12636.CMD 14:06 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0.0133 2.00 1.28 0.0 0.1 1.88 0.07 0
128.15 4.45 0.0 0.0 0.17
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge 0.00 0.00 0.09 0.00 0.09 0
207 .00 Stored 0 0 596 0 596
Incoming 0.00 0.00 0.42 0.00 0.42
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.86 0.0'0 0.86 0
Unknown Stored 0 0 18062 0 18062
Incoming 0.00 0.00 4.74 0.00 4.74
----------------------------------------------------
Lateral length= 0 Upstream length= 0
i
��
�,
M
Cascade Surveying and Engineering, Inc. HYDRA Version 5.12
Arlington, Washington 6 MONTH STORM Page 8
C:\HYDRA\CMD\12636.CMD 14:07 27-Feb-98
12636
*** ROAD Pipe Design
Invert Depth Min San Sto Vel Design Estimated
Link Long Diam Up/Dn Slope Up/Dn Cover Inf Mis d/D CFS Cost
1 150 8 130.15 0. 0133 2.00 1.28 0.0 0.0 1.15 0.01 0
128.15 4.45 0.0 0.0 0.08
*** ROAD Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
2 128.15 Discharge 0.00 0.00 0.07 0.00 0.07 0
207 .00 Stored 0 0 18 0 18
Incoming 0.00 0.00 0.08 0.00 0.08
----------------------------------------------------
Lateral length= 150 Upstream length= 150
*** SITE Reservoir
Invert -------------- Maximum Flow Values -----------------
Link Up/Dn San Inf Sto Mis Design Cost
3 Unknown Discharge 0.00 0.00 0.67 0.00 0.67 0
Unknown Stored 0 0 367 0 367
Incoming 0.00 0.00 0.96 0.00 0.96
----------------------------------------------------
Lateral length= 0 Upstream length= 0
i
• :r � _:
.,r.,_ _ .
's7
:w
�?;;34z ♦ M A/ inn y � �r�tJ ���' b` ,N yt� ..tf„'��. I;I�',~ �(( st,l4`J
;:��, � ,•�� `i4-'1��.>i �,'. '�',,� � �' � AEs�r�'_.'fc;t.�77{•'' , ,r •t.v
. �' � � t 1 Y�'�� ..F •E7k
u3 f
•••-
e
• . - -•• • . •••- .. . . - - •••-
. ` �PA°`� d{�r41 `r�`'.�7 t ��'�!Y1{�4jv'�>r+ �j• ,p�;� w
� rr'• }�1_ � '�I�,.C/?.� •' } �iny��M� � �•c. eta
i _-
• _: � . .,
1
DEBRIS AND OIL CONTROL SYSTEM FOR TYPE I CATCH BASINS
18 gauge
stainless steel top
Stainless steel rivets
I -- - - - -— and washers
t
1 . Hydraulic bypass
16 gauge,galvanized,
= • � T
i X.
wire mesh
Oil selective polymer or
cellulose absorbent
F
Trapped oil
VM
4407
eyes
for lifting
Oil selective polymer
/ —or ceitul6se absorbent
pillow
/ Al
/ //• / �' / /' /'/
Stainless steel rivets
Suggested Applications:
1. Primary sto(mwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Reqular sweeping is
recommended for enhanced absorbent performance.
CC) 1997 Aqua Trealment Systems,Inc.
i
6 � _ _ .� _ ���., .., • _.
�, •, 2
DEBRIS AND TWO STAc7t OIL CONTROL SYSTEM FOR 1 APE I CATCH BASINS
18 gauge
stainless steel top - Stainless steel rivets
and washers
Hydraulic bypass - 16 gauge, galvanized,
plastic coated,
' 1/2"x1/2" wire mesh
_ Oil selective polymer
or cellulose filter pillow
Oil selective,
polymer
mini booms y� . •s �,-
,fie ,.ep, s
T ,
w;
-_Stainless pg-d-eyes -.
for lifting
• !' �' J• r � r � r' Oil selective polymer
or cellulose absorbent
/• /• /• / / / /- /,/ pillow
stainless steel rivets
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swoles of oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Regular sweeping is
recommended for eni-wnced absorbent performance.
U 1997 Aqua Treatment Systems,Inc.
l
3 DEBRIS AND OIL C`-NTROL SYSTEM FOR CB-42 OR "`3-42HBSS STEEL BASINS
18 gauge stainless
steel support funnel T- mrrrm Stainless steel
rivets and washers
Hydraulic
bypass
16 gauge, galvanized,
plastic coated,
1/2"x l/2"wire mesh
Oil selective polymer Outlet
or cellulose absorbent
i
.T�V ��•
C'
t tt
:yL •yet ,K*�*��, -
18 gauge stainless steel support funnel
Stainless steel rivets
.4
Stainless steel pad eyes for lifting
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swales or oil-water separators.
b. Existing catch basins are not connected to an oil-water separator.
2. Industrial pretreatment for sanitary sewers.
Maintain quarterly with cellulose absorbent or yearly with polymer absorbent. Requlor sweeping is
recommended for enhanced absorbent performance.
(r—) 1997 Aqua Treatment Systems,Inc.
S �•h
\' � ..� .
SEDIMENT TRAP BASKE' "FOR SELF CLEANING BASIN` *,,.ND DRY WELLS 4 '
18 gauyge stainless steel
Stainless pad eyes top (removable)
#1 brass snaps_
Double-wi[�.__.____.._ Hydraulic bypass ;
reinforcing c T
t •1
I 10.5 gauge, galvanized,
i plastic coated, 2"x2
' mesh wire
I
a
' 30 mesh stainless basket
4; or specify
I :I
I .I
to outfall
_Stainless pod eyes
for lifting
.. 30 mesh stainless _
:.....::. ......... ..:!':.... steel liner or specify
::•• ••-••• •• Stainless steel rivets
Suggested applications;
1. Removal of coarse sediments from stormwater under the following conditions;.
a. Existing basins are self cleaning and not connected to settling vault.
b. Basin is a dry well and the objective is to prolong infiltration.
c. Area is under construction.
2. Industrial pretreatment for sanitary sewers.
Maintain yearly or as needed for sites with heavy sedir-nent loading.
CC) 1997 Aqua Treatment Systems,Inc
��
• . . .
I
�:
I
5 SEDIMENT TRAP AND FILTER SYSTEM FOR SELF CLEF \NG BASINS AND DRY WELLS
18 gauge stainless steel top
(remo—vabiej '
Stainless pad eyes _ _
#1 brass snaps Hydraulic
--- ► bypass
Double wire reinforcing__ ► . —
A / /
a
10.5 gauge, galvanized,
plastic coated, 2"x2" -- f
wire mesh
Oil selective pglvmer _
or cellulose filter sock
r
4. /'% / .A
tz
Oil selective polymer
or cellulose filter pillow
i, _ � _ •1 'I l l f
to outfoll
Stainless steel pad
eyes for lifting
Wire spacer -
-- Stainless steel rivets
" -- f Oil selective filter. ilp IOW.
,J ,; ,' ,��,' ,' , �� , Oil selective filter sock
Suggested Applications:
1. Primary stormwater treatment for redevelopment and small site development under the following conditions:
a. Physical constraints or cost prohibits the use of bio-swoles or oil-water separators.
b. Existing catch basins not connected to an oil-water separator.
c, Existing catch basins not connected to a settling vault,
2, Industrial pretreatment for sanitary sewers.
Maintain monthly or until filter blinds. Note, regular sweeping is recommended for enhanced filter performance.
L�) 1997 Aqua Treatment Systems, Inc.
DEBRIS AND OIL C.JNTROL SYSTEM FOR TYPE II C,rATCH BASINS b
Support funnel
Stainless steel
Hydraulic bypass
rivets and washers _ •. �,_.__..,
16 gauge, galvanized,
- plastic coated 1/2"xl/2"
wire mesh
I fill
Polymer mink
Trapped oil
to outfall -- -.
. .u,�..•ma�yy ,y„{r-':, ::, y r,•,+,___ '.^�`fd3� :�
mn
WIN-
r� `�Q '�
h
'`�r c ♦ •Ii
4� I •..iri+r`o"3it
a+F fi^;�,^�•.'ti'.1 pR? ' �'F����"yr�� �r<,Y1 i`� f+-.1
=,� t�lf-'h w' "i'•'+�y_.6N, l.�rY�"f�d"�r^e+T' +,C7s'M.i,vi�`'y'F'�+.�+v.* ir••<<:
--F.�i�T�<J� t �':•'' 9 .a ro:h�`r'�ii'1`r,Y..r L. L. �`I r..�
,j�• € .. ryr ��+ hyZ>i.71a" ,T-..r+y p Fy� �`=7'�:r f.
v tr Y•
18 gauge stainless steel support
funnel for rectangular cast iron
w frames and grates or type I „.
catch basins with welded
steel grates, T.
i r
i�
0.080" 3003-Hl4 aluminum
support funnel for cast rings and
grates, Please call for specifications.
Suggested Applications:
1. Primary stcrmwater treatment for redevelopment and small site development under the following conditions:
a, Physical constraints or cost prohibits the use of bio-swales or coalescing plate oil-water separators.
2. Industrial pretreatment for sanitary sewers,
Maintain yearly or as needed with polymer absorbent. Regular sweeping is recommended for enhanced absorbent performance.
QC, 1997 Aqua Treatment Systems. Inc.
i � _.
I
r .
DEBRIS AND TWO STAG OIL CONTROL SYSTEM FOk TYPE it CATCH BASINS
Support funnel
H�raullc _ Stainless steel _
bypass rivets and washers
110111 Hydraulic ypass
Tee section gpJ,rdzed,
fllter cell plastic coated, 1/2'xl/2"
wire mesh
L,. Oil selective
polymer
mini bcorn
lf
Trapped al
to outfoll
1 P.62144
tc
•L •+.psi v �,' � s
/`s. �fsi. 5'W � }•.� 9i�.+r .ham a
Stainless steel screws-
Pad eye,cord and hook / 0.080'3003-H14
— for securing top pan / r• .` ��,� aluminum Paris 4
L'IfHna Coble a<Cambeoner
u. y ./. �
16 gouge,galvanized. ./ if
plastic coated, 1/2'AUT �10,/ f- J
Jir wire mesh /_• f
Stainless steel wire cloth
or plastic media netting
f Oil selective polymer
or cellulose absorbent Stainless steel
filter rivets and washers
Stainless steel support
pins or screws Filter cell plan view
PVC pipe stub
(optlonal)
Suggested Applications; Filter cell sectional view
1. Primary stormwater treatment for redevelopment and small site devolopment under the following conditions;
a. Physical constraints or cost prohibits the use of bio-swales or coalescing plate oil-water separators.
2. Industrial pretreatment for sanitary sewers.
Maintain yearly with polymer or cellulose absorbent. Note, confined space entry is required to install and maintain this system.
Specify oversize ring and grate or frame and grate for cell installation and removal. Special order item
C� 1997Aquo Treatment Systems, Inc.
. _ . .. � i
i
i
SAMPLE SPECIFICATION 8
Basket charged with melt blown polypropylene net bag absorbent
for CB42 OR CB42-HBSS steel catch basins
�e ►
18 gauge stainless — ►
steel support flmnel n 3/16'S5 rivers and
3/16'k 3/4.55 washers
M/ctrauliC — 10.
—
16 gauge,galvanized. bypass
plast c oat '
wire mesh
oil selective polymer i
or ce11u1ose absorbent '>i
4
i r• ri `e- c� j '7
�; Engineer specify minimum
funnel opening. Minimum
distances between basket
walls catch basin walls
_ should be specified as
needed for hydraulic bypass,
28' --—---...... -----A A
�4 �— B' —► Engineer specify minimum - - i 12' ►
hydraulic bypass cut-outs
Q _
t
r Anti-floatation cords /
' required for polypropylene IIIIIIII Ito
absorbents
12*
1 I. .. 1 I L, 1• r
6"x 16"x2l" melt blown polypropylene spaghetti net bag
1. � -� .•f. �• ,f !• j
�. �•�j- � �' Clean basket and replace absorbent minimum once per year.
/* j i i'�i Quarterly absorbent replacement recommended.
Gultywasher R1 (c) 1997 Aqua Treatment Systems, Inc.
i
i
I
i
t • 1 * _ .�,i.*Chi . _ � � '• 1':•1 .RYA Ma�� 't
GullywasherS Geotextile Catch Basin Inserts
SEDIMENT CONTROL FOR CONSTRUCTION SITES AND INDUSTRIAL YARDS
A gouge stainless
steel support funnel
Stainless steel bolts Easy to Install - One Person!
and wing nuts. Remove the catch basin grate. Place
Stainless support funnel on the grating ledge,
28" steel plates Hydraulic bypass Replace the catch basin grating. Support
(approximately 14 funnel prevents grate, workers and fully
rv,C'. square Inches per side loaded inserts from falling into the catch
28 square inches total)
basin during change out.
Easy to Maintain One Person!
Inserts can be removed, emptied, and
Double stitching reinstalled in a matter of minutes! No need
D
to disassemble, simply empty the insert
through the top of the funnel, Back flush if
Non Woven needle punched desired and place back in catch basin.
polypropylene geotextile
Easy to Assemble - One Person
Place funnel on the ground, bolt side up.
Stainless Remove wing nuts and plates. Center insert
0 steel support boot over funnel, Cut slits in geotextile
funnel where bolts protrude and slide geotextile ove
the bolts, Replace plates and tighten wing
nuts pinching the fabric between support
Stainless
.A funnel bottom and steel plates. Trim extra
t eel s b-Qb material as desired or leave and trim after
Lifting welded replacing grate to create a positive seal.
Strap
3.
Stainless Durable
0 steel Insert filters are manufactured
lifting with 8 ounce nonwoven needle
L pad eyes punched polypropylene geotextile and
Support funnels available in standard and custom sizes, double stitched for lasting quality,
Use with Gullywasher geotextile replacement inserts. Support funnels are fabricated with
Pre-trimmed filters with precut bolt holes available to fit your top! 18 gouge stainless steel.
(minimum order required) Reusable
Gullywasher inserts can be used again and
again. Simply replace the geotextile as
Geotextile Specifications desired.
Inexpensive
Property Test Method MARV Tired of paying too much? Call your local
Aqua Treatment System's dealer and ask
for Gullywasher inserts,
Grab Tensile,lbs, ASIVIT D 4632 200
Grab Elongation % ASTM D 4632 60 Distributed by:
Mullen Burst, psi ASTM D 3786 400
T,-;--.,ol:d Tear, lbs. ASTM D 4533 80
Puncture, lbs. ASTM D 4833 120
1 (g) 1997 Aqua Treatment Systems, Inc.
. i
� �,.� � �r - . _ � ,.'� .mow ,i �,. i l_.is !
•oul •swalsAS 4uawloail onby L661
OZ L gCev a Msv .sql 'aJnund
09 Ngv u W1Sd ' ql ',cal PiczadcJl
00v 98zc Cl AISb' lsd 'IsJng uallnW
/\q pa�nq!4sia 09 ZS9b a AJS`d % 1-10406u013 goJo
ON Zg9b a 1WSd 'sg1'a11sual goje
,pasul JaysomAlln Jol
asp pup Jaloap s,wals/\S luawlpoil onby
l000l JnoA IIoO 6Uonw ool bu!Aod to pail MVVw POulaW �Saj APad0Jd
anlsuadxaul
'paJlsap so luagJosgo suol,<ooljloadS all�xa�oa0
Ullm aUxaloa6 aapldaJ Aldw!S 'ulo6o
pup ulp6p pasn aq uoo siJasul JaysOmAjln0
algosna�j (pannbai iapio wnwlulw)
'!gals ssalulols aBnp6 g) Idol mo%1!1 of algoIiono saIoU 4loq anoaid ql!M s19414 pawwul-ajd
Ul!M palpaugpl aJo slauunl 4ioddnS sVasui luawaooldai apx9loa6 jagsomAIInE)L44!m am
'N!IrDnb fD-ullsol Jol palaalt)s algnop •sazis wolsno puo piopuols ui algollono slauunl lioddns
pup al!lxalo96 aualAdoJdAlod palaaund saAa pod
alpaau uanonnuou aouno g Ullnn 6u14!I
pamlapinupw aJp siallll lJasul laals a a
algolnQ ssalulolS
tt2 k k :tw d DJlS
!pas an!llsod p alpaJo of alpJ6 bu!ooldaJ paplaM
Jallo wlJ},.pup anoal Jo paJnsap so 1pualouJ ►0 �;�n9�, , tl` y . p
oJlxa wui 'salold laals pup wo4oq lauunl
lJoddns uaamlaq augol aUl bullaould slnu =
6u!n�u9l46!1 pup salold aao!da�j 'slloq ay)
JOAO al!lxalobb ap!ls pun apnJloid slloq aJaL m lauunl '
al!lxaloa6 ul sgs 4n0 'lauunl Jano looq lJoddns laals 0/ a
lJasu! JaluaO 'salold puo slnu bu!nn anowad PIS
•dn apls lloq 'punoib aUl uo lauunl aao!d
luosaad au0 - olguaassy q Aso
al!lxaloa6 aualAdoJdAlod
'u!soq laaloo ul �ooq aoold pup pansap paqound alpaau uanoM uoN
1! usnll �oo9 •lauunl aUl to dol aUl y6noJy1
ljasu! aql Ndwa Aldw!s 'algwassos!p of 6wl4olils algnoa
paau ON lsalnulw to Jallow p ul pallolsulaJ
pup 'palldwa 'panowaJ aq upa slJasul �� • ._... A
IuoSJad au0 -ulo�ulDA O� Aso]
�`'�• Mollld
- luagJosgo
'!no afiupgo (D-ulJnp ulsl)q
flo
laoloo aUl olui bu!Ilol wojj slJasu! papool
(loJoi sagoui ajonbs 6Z -
AIlnl pup s1a�JOM 'alpJ6 sluanaJd lauunl aps iad sagoui ajonbs Ii0
lJoddnS '6ulloib u!spq yoloa aUl aaolded b l 040w!x0jddo) u :l d�J I,SZ
ssoq oll dAnoJPAH p l
'a6pal 6ulloJ5 alai uo lauunl l oddns �� Ij '' ► salpld laals
aaold 'aloJ6 u!spq laaloa alai anowa�l slnu 6ulM puo �I~ " ssalu!olS
luoSaad au0 - Ilo�Sul O� AS03 sllog laals ssalu!olS
lauunl Vaddns leak _►
ssaluiolsabnoU g 1
SlOI ONIAdVd aMd sam ldl?llSn(INI dOJ IMNOD 1N3W1(13S (INd 110
�. i, s�asuj uisog uop:D E)gxajoaE) (8)aausiDmAjjnS
1 . I� ►-� _ .. q•r ra'.; 4 iw: �: J.V-
. .1r:.,.fir•� '_ _ . y - - . r . . _ - ' •�
~ [W •► �p�Q� �,x •Q ����' '•� 71 � t;•' �' •• ' Jew•
Ilb
_ - •-• _ • • _ • • r •�� ,�1„s"l�-:�� .»• •'�:.] � ..+ ` ..kr i�e'�h.} ,c ..may.
•- -• _• • � iV rar + Lt M ot"+aoee« ae�-
• S -<IT'y. •��`Mat . *t.•.i�-�.: .��A�.!�f4L'•►:��`:":�►.:•mot'':
so
•�� ;tn `,y'i',.S`* .ti ''� o.'P•t JtT•,t�(�1 d71a�11• .:.. •` .a!}+c• ., 7j •�:�!, , '� ""•
_•• • •• • • -- h''' ' ' ~� _�'': �r`�. !' ter , ¢ { �
•_ • •• •_ • •• _ • j�:• �,y. �z�t,;r yx•�<'�'•Jk�i .�!•�;�q> �'' .s'S,fre �`�:,,�'�
-rm
•_ •• • • •_ • •• 5 : : 4 .rtS:i �34'-r°k>r,V :i 3 1 • j .
`+'y'•'� '' �`,! w•�1 +.�Y !• - VIA'�wi'J.F'v '.��%•
i S^••:?j es, a �C f i�Y! r-
rf�.��,1�•'71.•'�~NY.��. i.�R',1;,;�•• :,1je'��.a 'ro• .•`�' � iiL'�r� � •�
• •• • •• _ • _• _ +S , '�� ,- ��:` fah.. � r p .: r _'
r 4 i't �A r. \�.sf( _�� t•C. ��t��,,�`� �`' aL. Hwy �9
• r y ' �}34ti/r:�.. �yl�.+t�s '+ � r sr';`Y7,,i��•�!�.R_ t•�.`-�,
• • •• • _ • • • • �a{7����•a'�.'�'.i, .�.e?i.� .":�++F. C�?�.t.1'•'•�r r � .w c .M��k+a�f�7ez •',�/r
ty�W;'•'f3v- •�- r ., `• tin�.i' '• h. ti Sri
n. t .' .•'*• t� t y •t a� t
i.!.�'y,;:,,��ft,1 i'-`t.w;t--,--w,: y �•��2,y...r.�,t,.4,>;�,• ,L,• ��+�13fia •
• • • • _ _ _ • - ' � 7 ; � •� i r � 'r` •^�J.�� • (tea ti-,t'��/�� y� v..
•_ i.; �.r,!,'� ,y��,1 •�lr.r• ,�p� t' y t. tN al'�"y •� '. ;;�Ks... .'
_ • •• • _•• • • • '„jtJ�� - .a tt1�t ;i3�r1.i�j\ t,�'�+<1';�x �--;.-t.<. �rr /YY•�.'Y
• " � +�j•`� t.''w�t t .^� (ra -�. v� 1�v�.{�. ��(���t S�K'�'�•t� �.�.F.nw ,
•� . _ • _ ..•,at:,•�t}��r •V• t L�� ` �`�.� _,..ra• ..�:tsL'a, 'r"�'1••�l<� <„�- sr 1
�fa"-'Gy,�l'yyyM�''�¢'� - ; �:� �,j\•:Vti-`ti'�•'!r�.`':�'`•�'•�tl't �Y�;`�y�f•.7y:y'�`'•»!�~�. kr''�„'�.:;-'�
it1�M �_••y-L: •a •`�. <�� •^�fat.�v-�/it7.a?t':' •'tl••,I..,y�;:'. r'•."��•:ti• tr..j•�� �''•�
• _ • `T'-. 1.��,r%•'_ -'�y�•y_ a. t:.J�.:'rr... �:A� ��~- '•!r t.:. •,V�,• :,tsi^ice �r\:.•�•e.
i
,;
i
.. _ _ .. _ r . � �
t �� � 'r N�
a
;�'x:
��
.............
............. ........... . .... .
....
........... ....
49 Im
.............
.... ...................
it...............
..............
af-
•
0,
w
FIT 0 1A.
Oft Jv
t'. ..f 1 aL
Ril
IN
ki.ot
j�n �N min
kv
qt: n
1
f
I I
ail .... i. ••irt'1ti 'i' .G, �• ..•:K•• 1�MZ �� 1 •ti � .r a•----• r� ►'�
. • II
'aul 'swajsAS juawloail onby 1661��1
1
`Ce i
D o aid:Ja aw i a
.P U �. S r:..
� I,8/8
,,9 :JalwDlp alOy adld
spunod V :I1461aM ak. . :L �> t \
,,8/L :Ssau�olgj IIDM ',, +r4 �_. ;A1`r�= n• a � ` ,. " ;
aual/,yja/\lod papow ,loua�Dtnl
,. •. � ,G� �
, W;st4, �• to l..... '` , 4 ,..� ~x,•.��i'•
suo!jcold!oadS _ '�,� "
•1no 14sc)m 4uanaid puD say!ds aye
01 aJGgPD 'uapJDy Illnn Juawao J!OS 9L41
'�uawao puDljJod qj!m Imp puD lauunj
a u� do saps a Ul PunoJD I!os aU� � d
•• . : . •
•saloU PaIIIJp-aid aUl y6noJy1 say!ds
al41 anlJp puD 'aoDld ul lauun; ay1 ssaid .e
' ` ,..� „' 4, i.`c �'•. tea_� ,• '
uawao puo od jo s unod inn
Aly6naJoy� xlw 'llos uasool 'lauunj aye p � , -. - - �•
U� U� I ICU I
uud oo a uD Ja6JD /� 6l s DaJD
uD ajDnDOx] 'juawao puDlVod puD
sallds .,Z L U1!m pallolsul sl lauun; ayl _ ,�
l+r ti'�•ao-i
-siaonpaJ Uj!M
adld uolsua�xa Ja4awDlp JallDws puD
s6u14!d PJDpuDjs U1lnn adld uolsua�xa ,,9 ` . , �s. `�''i• y, z�.��,'' x ��� ,..
ul alOy ay1 y6nojgl �j anaals puD
sa oul mej D qnjs adld eqj o pue � �� `f
aU1�!IS 'adld ollsDld pajobnJJoo ,,9
jo aoald goys D ono 'algwassD of �; ;'' a �� `� - T
;• , _ '� �" ,ref` p t.. � 1���}
'UOISOJa P!OnD pUD ��� r' ct •.
UOIJDnala JeMOJ D of jjouni 4Janlp 01
paau D sl aJay1 aJaynn soaJD JaylO ~
uD 'sin000 BuI auuD o aia m
P .I U U
sadols jo dol ay1 jo 'aoua� jps ul
sin000 gbnojq��oaiq aiaynn lauun� -
t
ay1 aoDld AldwlS 'aolnap IOJ4uoo ,
UDISOJa IIDjSUl-of-ASDa puD �olnb D sl qj
lauund JalDMwolg aJaL4sc)mAllnE) eqj
lauund Ja4DnnwiojS �JagsDnnAllne >��,y
L
15
I
'oul'swalsAS luawloaq onby 1661 (Z))
"slio paljlslnwa pup suaaUs Jo
6uu 6ugools
JIDAOUJaJ JCj IaUU,ij wO4oq dyj ui puaiq J---)luAlod
-uogJoo au1 aoold pub suogJpooJpAL4 jo uoljonpaJ
ssoib Joj lauunj dol au1 ul asolnllao auj omid im
-swnlpaw Japj yloq UIIM asn Joj pa�loots aq uoo Jo4Jodas Ja�pM-po aloos IIpws@JausomAlln0 ay1
"asn Jay.jnj Joj pualq JawAlod-uogJoo aye anowaJ
of lauun� /4dwa ay1 y6noJu1�opq slualuoo
aJljua auj Jnod "Iy6lUJano Moos 1a1 puo ja�onq suJnip
UOIlo6 9 p ui JajoM anplsaJ pup pualq JawAlod dot pasola
-uogJoo aoold 'lsisJad suaaUs jI 'pualq JawAlod U01106 g5'o; < 1
-uogJoo ay1 ybnoJy1 JapM anplsaJ au1 Jall1j lauunj II adAl
ueq� slio aU1 )o �lnq ay1 aoppaJ of asolnllao
aye asn pualq JawAjod-uogJoo anblun Jno Aj� I�
'suaaUs anowaJ of pjoLl puo slio paljlslnwa Jod T'
.Z�
"sl10 paljlslnwa anowaJ IOU ll!m asolnllao ay1 aPN Y_
.a1
"papJooslp uaaq aslMJayJo anon
pinoM Iou1 asolnilao puo 1l0 auk woJj /\FDJGUa s�axanq
6ulwiploaJ sallllloq buiss000Jd IpiJlsnpui puo U01106 s J01
lauunj I adAI ,ax>na a t•: `
sluold jjpydsp 'Sup luawao 'sJalioq aJnjoJadwal auaJ IaNPd
vaoow
-MOI panoJddo ui pauJnq Jo 1l1jpupi panoJddp up
ui paoold aq A= luagJosgp quads auj 'asn Jatjy 'I°"°"d°
suaa,xi
,K
y. elou PalUK7
"aaJj Isnp puo 'Iu6iaM 4Ubll 'uoaio aJp sJaglj ayl
'ono yopal jouuoo /\au1 a1auM sJaglj au1 uIU�IM daap spinbil sMoJp juagJos au1 'uoijoo /uollldoo
buizii!in -lonpoJd-Aq 5uunpojnuow Jadod puo dInd o 'sJaglj asolnilao pawlpoaJ sasn JopJodas
Ja,pM lio alpos-lbws ayi '6uiiGgj anuiluoo pup '/\IwJij Mood 'loualow Mau u1lM juagJosgo
juads aU1 aopldaJ /kiwis uay1 'JaloM paJallll aye jo dol uo uaas aq uoo uaays p pun lolJalow
luagJosgo auk asn 'silo 6ulnowaJ a11UM AIaaJj y6noJy1 sspd O� JapM sMollp asolnllao ay1 'lauunj
ay1 jo dol ayj olui sam�xiw JaloM-IIo Jno% Jnod je�onq Uoljp6 5 o JanO aoold pup tuagJosgp
oixol-uou 'ajps /',lajaldwoo aye u�IM lauunj ay1 Ig AIdwIS idous o saJn�xiw JajpM-lio A3Saw do
bulupalo sa�pw UoIUM lauunj asn-q-Asoa up si JopJodas JaloM-110 aloos Ilpws0aysDm/\IInO ayl
I
2 3ivm dNns 431VNIMIN00 SS300dd •
, 5c d3l`dM31SVM ividisnGNl lVM13dd •
�. K33dJ IiN' V oOdJ 110 3AON3d •
S111dS ll0 do Md313 •
d31dM 30119 AIIO d31113 •
2J31`dM dON AIIO d31113 •
IMN34NOD dOSSMdNO3 ld3dl •
t� L iopmdOS JOPM-lio V,-,)OS IIpwSgj@gsoM/\jjnS ,
•oui'swals/,S juawloail onbV L661(,� S3SVWVO 1V103dS do 1V1IN3n63SNO0'SIIdO21d 1SOl J,NV 60J 319V11 39
'ONI'SN31SAS 1N3NIV3di Vn6V IIIM 1N3A3 ON NI 'S1Dn0O21d '0NI 'SW31SAS IN3W1V3di Vn6V dO 1N3N3Z)V1d3d 39 I11M 1,03W3d 3lOS Sd3SVH0tJnd
'39CMS 031Vd3N39 0NV'V103W 1N39uO39V 1N3dS'd31VM 031V3M'631VM O3011H dO IVSOdS10 ONV 352JVH0SI0 3H1 9NINu3AO9 SMVI IV0032
ONV'3MS '1VD01 HUM 3DNb'I1dWOD 60d 3191SNOdS3d 1,131OS MV S1On0O21d'DNI 'SW3ISAS 1N3W1V3dI Vn6V d0 Msn ONV 03SVHO?Jnd
'1N3WNO?JAN3 3H1 JNIu31N3 S1NVlnllOd do INnOWV 3HU JNIOnO3d dO sNV3W 3AIsn10X3 3HU SV 3Sn dOd 030N31NI ION 3dv SI0n0oud
'DNI 'SMSAS IN3W1V3M Vn6V '9NINNVId NOLN3AMd N011nllod ONV'9NINNVId h13dVS ONV IMINOD 01d4Vdi'9NINNVId 3DNVN31N1VV4
1N39NR11S H11M NOl1OM NOD NI S1Dn0Odd'DNI 'SLN3.LS S 1N31N1b3a1 Vn6V 3sn '3sodund dyjn0uadd d d0J SS3N11d dO'Jk111119V1NVHOd3N
'3DNVNU0383d 2113H1 9NI0n1ON1 SiOnoodd S11 011O3dS3d H11M'O311dNI u0 SS3ddX3?J3H1!3 'S311Md21WM ON S3" 'DNI 'SW31SAS
M3W1V3u1 VnnV dIHSNVWN?JOM ONV WHIM NI 9103d3O INOW 33ud 39 Ol S1DnOO?Jd Sll S1NV?JdVM'DNI'SMISAS INgNIVM1 Vn6V
L
I
.LZ .0£
�Zl—► .b9
'sjallnd Ic_)uoljuanuoo .„o l ►
a�llun spuoy qpq loj dij6 o soU 11
'jallnd ajoj6 pjopuo�s mo Ail 2�
1 x.
'IDnowai ajoib uiaJp wj0js a ?, ? •f `� �,.w,� ,. � ""�,,ir.
joj paJlnbaJ lauuosjad aldijlnw puo
•-x�Mti; s -!•mac `�,�•�►�� _��` '.`"�
juawdinba Joi paau auk aIDUlwlP
sasc)o awos ui puc) Ain(ui jo Hsu s� ; ^`.. , ,.��.� �,+� ma c'►?
auI aonpai uoo 11 'salab pa40ls
a61c)l jo Mpay jol pap! sl jallnd aIJDJ6 01w0u06Ja,�Jaysc)mAjjnS aUl
-17
3W11 3ndS n wrNl 33nC13d
dLLn5
e61°43T.0>BJ°M uool 95ms
i3SdVH3SIa
paq 6uiNp of aUpnis uloJO'q
asnaJ JoJ JaloM JuD090 'b
21�1`dM�1S`dM (u!w Oe)9111as Jai puo Jax!w dolS'£
(salnuiw 9 xiw)JapMod
luawpajl ppo puo Jax!w JJD4s'Z
�
�lb'N I W Il UDJ luawPeJl Illd'1 XUDI 6'Pqw
:suoljonJIsul juawJoaJl "°e09C
JJax"
i Z 31dM puDIS�uol'9
Japmod JuawpaJl spunod OS'S
J811Id J910M P6406JI'b
dnoA Jiun 6uiJalDmeC]96pnlS'£
(AOZ 1)MIA J09us-U61H'Z JaJDM UJOJJ 018 '390d 's)DJauJ MDau 'JuauJ(pas
3sn3d (papnoul s5u1441l)xuol Juawpeil'1 '110 JO(DAOW9J JOJ WDISAS JUE)W,'DeJJ aJS'31 uIS
:sjuauodwoZ) WepAS
swea �Uew bawl aapm ajaaS ..,_))Ws . 9 L
i��
I
�� . �
" I
I
��...
•oul'swatsAS juawpal1 onby;o�towepott paiaisi6at o sl gJeLJsonMling
7£[96 u016UNSOM'ap1oaS
7092-£7£(90Z)xo j UJnoS anuany 10juap!aoO OOZ£
l ZZS-£7£(906)auoyd 'oul'swajsAS juawpeii onod
icinS N0I13111S (IN`d MIMIAO lo(1QOdd
1 ME
.�f ^a�' ., ..ykj,•�} ��tr F�fi:,1"'�F��sa'"�;.y'1.�z ,j.� •.4� F*��5
�� ����.,1-}� Vey M 'Y •�
9 l 960d jalInd 810Jg olwouo6i3 b l a60d iolomdaS jalnM-I!O
i
0 L -6 sa60d
sUasul u!s0g yo}oo alljxajoag
9 L sa60d sPasul uls09 y0400 aJ!M
fft
OCR ,
pu
�.
£l a60d lauun j jajDmwjojS Z I - t sa6od w04 W)KI
"(�y U��i." 4_ ~` ..�"v�i- �t '� ATE•'.
11Px ' �4t'.ytVr�'��9'1 "�l`� ����� •4'�Ir 4s a`
S4OnPOJd IOJJUOJ UOISOJ3 PUO JGIOM84SOM JeIOMWJ04$
.Ar
ti
Dul lgwQlsAS,uewpoil nnby 1661
-aouowiojjad luagjosgo paomo ua lo; papuawwooaJ
si buidaams iolnbad Iuegjosqo iaw/xlod L41!m AlioeA jo duaglosgo asolnpao L41!m/peponb uo}uroW
'siaMas Ajolpos joj juawpoiLaid loijlsnpu .Z
•lopiodas ja}oM-lio uo of pa}oauuoo you ajo suisoq y011Do builsix3 -q
•siopiodas japm-jp jo saloons-op jo asn ay;sligilaoid�soo jo sluioiisuoo jooisAL4J 'o
:suoilipuoo buimopoj ayj iapun juawdolanap aJis 11ows puo juawdojanapaJ col�uawLoaiI ialonnwJols AJowild •L
:suoilooilddy pajsa6BnS
slams 1991s ssaiuioic /. '.•`f•`�.-` '/ •`
/ /•.
Mollld
:o ;o
luagjosgp a4L0ao to -- -.i •/
jawAlod an1130jas lip
.__saAa pr�a ssa�uir�>.S - —�-►"' o ra, _ � :.
jio paddoil
f
luagjosgo asolnIIao 1
jo jawAlod an1100109 lip
ysaw GAM
Z/Lx, /L 'pepoo oilsold
'paziurJnlo6 'a6nn6 q L
ssbdAq oilnbJPAH }
sJE)gStD n pure
sJaniJ1aa1sssOJUID�S
dol jaa�s ssajuiop
a6n�69L
TI
SNIS` O HDIVO I ld)d ?JOJ AIISAS IOZllNOO 110 aN`d SM30 L
-oul'swelsAS luawloajl onby 1661 0
7�-uow!Qllad luegnsgo poou ill o lo;pap!�awwoc)ai
si buideems jojnbad -luegiosgo jawAlod UIIM Alic)eA io luegjosgo asojnpao Ul!m Alj;Dljonb upjuioW
•siamas Aioliuos jol luewpailaid Ioiilsnpul Z
'jopmodes japmgo uo of papauuoo lou ajo suisoq Uapa 6uilsix3 q
-siopiodas ialorn-lio jo saloons-op to asn ayl sligiyojd lsoo jo sluioilsuoo looisAUd 'o
:suoippuoo 6uimolIol aUl iapun luawdoIanap ells flows pup luawdolanapaJ iol luawloaJl JaloAnwiols AJowiJd I
:suoilooijddy palsabbnS
`e io,
s�ani� �aa�s ssa�uir��s- 1,•' r- r,�r�r t' f' i•
Mollid
juagjosgo asolnpao jo
jaw/\Iod aAI�O@Jes lip
6ui4!1 Joj
- saha pod-9 YWh - - fa-►�
�Yp.1ly.�lrt Y .+K 7KL4J Mt j* -1 .S -11,l".4
;x. .,"Gf•�rs ��4 c .� �Fyrtal �! f�STr•-Y
A. ^� � t swooq !ulw
jawAlod
aAi oa as i
.F
Mould aall!j asolnllao jo
aawAlod aAl�oalas I!0
gSGW aJlM ,Z/LX,,Z/
'pal000 ol�sold -
pazluonlofi 'ebnofi 9
_ � ssodAq olinoJpAH
_ s�ausoM puo-
sIanlI laa�s ssaluloIs do} laaIs ssalulp�s
afinofi g �
SNISV9 HOIVO 1 3& dOd MISAS 1OENOO 110 P/--)d1S OMl GNV S1�183a
Z
jul'swajbAS iudwiudil ui1L)y Z661 lJ)
-aouewiojiad auagiosgo paouoqua joj papuawwooai
si buidaams)ojnba�j 'ivagiosgo iawAlod L411nn ApoaA jo}uagjosgo asolnpao q�!m AIlauiJnb uiojuiow
'siannas Aioiiuos jol juawpaipid lopisnpul Z
'joloiodas ialoM-1p uo o}pajoauuoo jou ajo suisoq L40100 bUlISIx3 -q
-siopiodas jaloM-lio io sajonns-oiq jo asn aLa1 sj!q!Laoid Isoo io sauioJJsuoo IooisALUd 'p
:suoijipuoo buinnopoi aL41 japun luawdoIanap aIis flows puo juawdojanap9J ioI luaw}oaji ialonnwiop Aiowud 'L
:suoilooilddy pajseMnS
f)uitjli joj so/\a pod laals ssajuio�S
S�OAIJ 1001s ssaJuio�S
lauunj 4ioddns look ssaJuio�s abnob 9 — r f f/n/, —
juagiosgo asolniIa3 io
jallnp iawAIod 8N}a81as lip
ysaw Lx,Z/l
papoo oipold
'paziuoAIo6 'abnob 91
ssodAq -- --►
oilnopAH
siaLysorn pun s�anu
WJJ ty
laals ssaluioIs Lliifl lauunj uoddns laaJ
ssaluiols abno6 91
SNIS`d9 1131S SS9HzV-9' jO ZV-93 dOd W91SAS 10diNC 110 aNd M990
•oul'sways{g�uawloa�l onby L661 C��
)ulponl ��-iaWlpas Moay U1lM sails J01 oapaau so Jo MoaA uoiuloW
-siames Ajolluos joj juawloailaid loljlsnpul -Z
-uoljonijsuoo iapun sl oaiy -o
•uoljojjlldul 6uoloid o4 sl anlIoafgo ay1 puo llem/yip o sl ulsog q
•jlnon 6ul14as 01 pajoauuoo jou puo buluoap jlas aao sulsoq Bullslx3 •o
,suoljlpuoo 6uimolloj aU1 iapun ja�omwjojs wOJJ sjuaWlpas asJ000�o JIDAOWE)d 'I
:suolloollddo palsa66nS
sjanli ..._... ... ..... .
Nioads jo jaul polls
ssaluloIs Usaw p£
- sa�cid3geluit:)IS - --.,►•� ;o�
a
I
Ilogno o}
i,
I: i
is
Toads jo
ja�soq ssalulo�s ysau� pC—
a1IM gsaw I'
. .. . .. . .... . .. . ...
„o.Zx,,Z 'Pal000 ailsold
'paziuoAlo6'a6no6 5 p ;
6uloiojula
ssodAq ollnojpAH
sdous ssojq L#
(aigonowaj) doh ► - - saAa pod ssalulo�S
laa4s ssalulols a6Anob g
t7 S1I3M AdO ON\ _ /NISV9 ONINVII3 A13S dOd _J>1SV9 dVdl 1N3AIaIS .
'oul 'swalsAS luawloail onby L66 t P)
,aouowioljad lallll paouoqua jo;papuawwooai sl buldaanns joln5,- 'aloN 'spuliq jalp�Illun io Algluow ulolupow
-siannas A)olluos jo;luawloailaid loljlsnpul Z
'llnon 6ul149s o of paloauuoo lou sulsoq goloo kiullslx3 'o
•ioloaodas iepm-llo uo of paloauuoo lou sulsoq goloo bul4slx3 -q
•siolojodas jalDm-llo jo saloMs-op to asn aql s1ppoid poo jo sluioilsuoo loolsAgd •o
:suolllpuoo buimollo;aql iapun luawdolanap ells Mows puo luawdolanapaJ JOJ luaw}oaJl JalonnWJols AlowlJd 't
:suolloollddy palsabOnS
oos JGfl!j ant oa as l °
Mojlld 1ajlliaAlJoalas 1!0
r
s�anla laaIs ssalulDIS
r — -
r' r' /'
6u1411 ion saAa
pod leak ssaluio�S ► ... �o: '�
M.
Ilollno of
Mollld Jallll asolnllao Jo
jawu�a arujoatas lip
�'. /r /
Moos jallld asolnllao jo
l4saw aim
��
i x Z'pal000 ollsold
pazluonlo6 'ebnob 9-0 t
/ VrA., /
A
► u ojojulaj annn algnod
ssodAq ► sdous ssojq L#
ollno,pAH - -saAa pod ssaluloiS
__ (aIgbnowaJ)
dol laals ssalulols abnob g t
S113M Ado (INV SNIS` O ONIr 113 J13S dOd W31SAS d311Id T(' INV dVdi 1N3WIa3S
'z)ul 'swalsAS luawloail onby Z661 P)
-aounwlo}lad 4uaglosgD paouoyua Joj papuawwooaJ si BuldaaMs JDlnbad -}uaglosgo JawAlud y1IM papaau so Jo AIJoaA UIDIUIOV,
-dames AJo4Iuos Joj}uouipeilald Ioulsnpul 'Z
-sJolDJDdas laloM-IIo a}odd 6ulosal000 Jo saloMs-olq jo asn aye sIIglyad Isoo Jo sluloJ4suoo loolsAyd 'D
:suol}Ipuoo 6ulnnolloj ay1 Japun juawdolanap a4Is bows puo 4uawdol0n9paJ Jo;luawloaJl lajoMwlo}s AJowud 'I
:suolloollddy palsa66n$
'suol400lpads Joj Iloo asoald saIojb
pun sbuu Isc)o lol lauunj}Joddns
wnulwnlo b IH-EON .,090'0
.l
•Sa}oJ6laa}S ,
paplaM y4IM suisDq yojoo
I adAl Jo sapl6 puo sewoi;
uon Isoo Joln6uoloaJ Job lauun;
4Joddns loop ssalulols abnob 91
IID4no of ►
IIo paddoJl l /
wooq_
-lulu)JawAlod
XMIX
h
I
ysaw aJIM
Z/I x.Z/I p811Doo oI}sold
'pazlUOAID6 'a6no6 9I
SJay D SDM pU SIBNJ
sSDdAgyollnolpAH laajS SSaIUIr)I$
lauunj Uoddn$E I- I
i -11,,,,i, TTTrrrnQT=Ri Mmm-
9 SNISV9 H: "-1O 11 9dkL �Od AKSAS IOdlr �0110 aN`d S12J9]a
'oul 'swa}sAs}uaw}Dail onbVI66(
wall Japo goads 'IonowaJ pur)uoi}opoJsul llao Jo)810i6 puo awDJJ Jo a40J6 puo bull azlsJano A}pads
'WeISAs SIgI uloJwow pup po}sul of pannbaJ si AJJua goods pau!juoo 'aloN -IuagJosgo asoln1lao Jo JawAlod U11M AIJoaA wn}uloW
'sJaMas Aigpos Joj}uaw}oai}aid joii}snpul 'Z
'sJo}DJodas la}DM-1p aJold bulosal000 Jo saloMs-op p asn ay}sl!q!goJd).Soo Jo sjuIDJ}suoo looisAlld 'D
:suoj4!puoo Bul%ollo)ayJ Japun 4uawdojonap a}is pows puo JuawdolanapaJ JOI}uaw}oaJJ JaJDMWJO AJr)wud '
Ma!A louol}oas 110o Ja}pd :suoiloopddy pa}sa66nS
(louo!Ido)
qn}s adld 2Ad ►
MaIA uold pao Jag,l sMans Jo suld
}Joddns lagp ssalulo}S ►
SJaUsoM puo s}anu Je1111
► I * }uGq,osgo aso,njjao Jo
1aa}s sselu!o}S
JaWAlod aAildajas no
bui4Gu olpaw o1}sold Jo
r u}op aJ1M 1aa}s ssalu!o}s
r' jy
f , Usaw GJ1M
»Z tkZ/t 'Pa}000 ollsold
r. f• .t -poiluoA165 Wn 9I
JO apo IUl1 i
►\ wnuwno r� ! :f. uod dol 6uinoas Jol
V l H-£00£ ,020'0 r 5looq puo p1O3'GAG pod ►
-sMaJos 1aa}s ssaJu!o}S—
IIoJlno of
- 1io paddoJl � �
Woi NIW
JawAlod
anlJoalas 110
ysew anM
„Z/LXI Z/I 'Pa}Oo 311sold -- -► 1103 J011!J
'patlu3NoB 8M[-)69I uoi}oas gal
ssodAg oilnmpki ►
1
SJaysoM puo S19AIJ .. ssodAq
pals SsaJuloiS opnoiP HH
�auunJ uoddns
SNISd9 H01` O 11 IdKL �ir)d A31SAS ]0�11NOO 110 3�h'1S OMl aN`d S1�19�a
�
•oul 'swals/\S}uaw}oajl enby 1661 (-5) ��jaysonJu�ng
-papuawwooaj juawaor)ldai }uagjosgo Alja�on?�]) /' •/' ,/ ,/ / r//
•joeA jad aouo wnwlulw �uagjosgo aooldaj puo jo�mq ub913
t� t r�t� t f' t t•
6oq jau llpL45ods aualAdoidAlod uMolq klaw „IZx,,9lx,,9 �r •'rr•/ / //' /' / �
/ - zi ►
Tin
ol
t II
s�uagjosgo
T. aualAdadAlod jol pajlnbal '
spJoo u01�01001;-I�ud
8l
-I
s_no- no sstDdA oilnc)jpALA
zi ujnujlull u Toads laaul6u] �- �__ a _►
'ssodAq ollntDipAq jo} papaau
sc) paldloads aq pinous ,;� -
sllrDM ulsoq goloo sllom
a S1J uaa a Saom sl
� � a � a � p
wnwluiA 'buluado lauun�
wnwluiw /Toads laaul6u3 k
♦ I .
.L
luagiosgo asoinpao io
iawAlod amloalas Qo
BL 91
t USaw a11M
000
21
Ilsojd
ssodAq 'paZiuonIo6'a6no6 9 1
IF a+lnoapAH
sialasoM SS„q/£X&j/£- _ �auun��ioddns�aa�s
puo sIanii SS„9 V£ . __
II ssaIuiols 96no6 9
BL P.
suisr)q yoPo 100�s SSBH-ZVSO dO ZV80 JOI
�uogjosgo boq tau auelAdoidAlod uMolq �Iew q�!m pa6al)uo pa sou
NOIl`d3IJI3AdS 11MVS .
•z)ul 'swals/\S luawloail onby L66 l (J)
OZ L `v`r8lv a W1SV 'sql 'ainound
08 S99b a W1SV sqj 'goal plozadoal
00IV 99Lc a W1SV !sd Tsang uallnW
/\q pang jp(] 09 Z`r9p a W1SV % uo!pbuol3 goje
-s}Jasul laysoMApnO iq
ON ZS9ti a 1WSV 'sgl,,al!sual gDjS
Aso pub jaloap s,wals/\S luawloajl onby
l000l ino% Iloo 6yonw ool buiAod jo panl Add pOL40N �Saj /y..ladOad
anisuadxaul
pansap su i�x
oi�pOi�iOadS a� aPae
so a!!Valoab aye aoolda Aldw!S 'ulobo
puo ulobo pasn aq uoo s4jasul jausomAlln0
algosnad
(pajlnbai japio wnwlulw)
-laa}s ssaluiols abnob g[ idol mo%!ld of algollQno saloy Iloq�noad U11M sja;.11d pawwu4-a]d
ql!M pa�oougo; ajo slauunj �oddnS •sl,asul juaw000ldai agxajoa6 jaUsomAjjns Lgm asg
Agonb bullsol Jol payojljs algnop sazls woasno pup piopuols ul algoliono slauunj�joddnS
puo agxapab aualAdoidAlod payound saAe prod
alpaau uanoMuou aouno g Ul!M buly}l
panjoo;nuow ao sja�g�jasul lams
algojn(] ssalulnlS
d ojjS
logs an!llsod o aloao of aloab bulooldaj PaplaM ........ - -- 6u�yij
qo-
aa4o wu4 pub anoal Jo paJlsap so louaIowgl� - - ►p p
ave wul �safold lams puo wo4oq lauunj ssalulplS ' .-
�joddns uaaMjaq ougo� ay1 bulyould s}nu
bulM ualybll puo sa�old aoo!dad 's�loq aq�
ano allVa�oab aplis puo apnipad slloq ajayM lauunj
agxa�oab ul sips }n3 'lauunj Jano looq 4joddns lams
4jasul jalua0 -sajold puo s�nu bulM anowa�l
ssa}ulo�s
-dn apls Iloq 'punoib auj uo lauunj 000ld
uosiad auo - algwassy q Aso
'ulsoq gojoo ul �ooq aoold puo paalsap all�xaJnab eLlejAdo.idAlad
p9gound alpaau uanoM uoN
�! Usnll �mq 'lauunj ayt jo dol ayl ybnojy1
�jasul aye/�dwa Aldwls 'epwassoslp of bugojjl s algno4 J
paau ON lsa�nulw p ja4ow o ul pallolsulaj /
pub 'paljdwa 'panowa aq uoo sliasul - A
iuosaad auo -UlDpOW q ASD�
'Ino abuoyo buunp ulsoq (10}04 sayaul ajonbs gZ l
Uojoo ay1 olul bu!Ilod wojj s�asul papool apis iad sayaul ajnnbs I�
b l Ala;owixaddo)
AI!nd puo sja�joM 'aloJb sIuanad lauunj
4oddnS 'bullojb ulsoq uopo aye aoolda�l ssod/�q ollno�p/�H N � sa}qld lams 8z
.abpal bulloab aye uo lauunj lioddns
}; ssalulo�s
aoold 'alojb uwsoq y0103 ayj anowad 'slnu bulM puo
s�loq lams ssalulolS \�
i uosaad au0 - 110�SuI O� AS03
lauunj 4ioddns laa}s
-�
ssalulojs 95nD5 g t �
rt •,..
scmvA ivid1snaNl aNV S31lS NOuondlSNOD dOJ 10&N031N3WIa3S
r,.
s4iasul ulsa8 uapo agxapae ,��,aauso"IjnE)
6
•ouj 'swa�sAS juawpail onby L661
OZ L `✓S8ty Cl WlSV 'sql 'ainpund
09 CSgb a WlSd 'sql 'foal plozadpjl
00t7 99z� Cl MW lsd 'Ising uallnW
;Aq pe�ngpp(j 09 ZC9b a W1S`d % uolpbuo13 goj0
s�Jasul JaysonnApnO jo}
ON Z;CgV a 1WS`d sgl'el!suel goj0
also puo jaloap s,walsAS juewpail onby
l000l inoA Iloo Lgonw oof bulAod jo paill MVA POglOn Sal Apedoid
anisuadxaul
-pailsap so juagjosgo su01�0011i08dS aji�xa�oae
y1IM a14xa1oa6 aooldaj AldwlS 'upbo
puo upbo pasn aq uoo sVasul JaysoAnAlin
aIgbsna�j
(paiinbai iapio wnwiuiw)
-leak ssalulols abnob g L Idol moA jy o}algolionC)saloU lloq lnoajd Ul!M sJ94W pawwu4-aid
y1IM paloougol ajo slauun��joddnS •s�iasul 4uaw000ldaj agxaloa6 iaysc)mApnE)L41!m asn
-Agonb bullsol Jo; payol!ls algnop -sazis wolsno puo pjopuo}s ui algoIlono slauun;lioddnS
puo agxapab aualAdoidAlod payound saAa pod
alpaau uanonnuou aouno g qj!m 6u1411
pain}oojnuow ajo siallld pasul lae�s
aIgaanQ ssalulois
dDJjS
logs anlIlsod o apa�o o� a�o�6 6uloolda� pap!aM 6u! !1
JaJ4o wu� puo anoal Jo paJlsap so louaIow siIQ9Jaa}s- _ ►p 3' 0
ssalulo�s (. .l -
oj xa wul salold laaIs puo wolpq lauunj l� ,
jioddns uaaMlaq ougoj ayj bulyould s�nu
buim ualy6(l puo sa4old 000lded 'slloq aye ?
nano allValoa6 ap)ls puo apnipid slloq ajaynn lauunj
alpajoa6 ul sgs In0 'lauun�nano looq lloddns laa}s V
4lasul jalueD •sajold puo sfnu bulM anouuad
ssalulols i
•dn ap(s Iloq 'punoj6 ay1 uo lauunj aoold I
iuosaad auO - algwassd q /\sO�
•ulsoq Lobo ul �oog aoold puo pailsap alllxaloa6 aualAdoidAlod
i sn oo auun a o do a 6na payound alpaau uanonn uoN
�. y Id� 9 I yl 1 y1 y yl
liasuw ay1 Aldwe Aldu.ils 'algwE)ssoslp of buluojljs algnoa�
paau ON lsa4nulw p ja44ow o ul pallo�sulaj
puo 'palldwe 'panoWaJ aq uoo s�jasul
iuosaad auO -ui PDA O� Asp] Moll!d
'Ino abmgz) buunp ulsoq luagjosgo
yoIoo 8y1 olul bulpo; wa4 s�asul papool I I!O
(lojol saUoui ajonbs gZ
�Ilnd puo sJa�IJOM 'a1oJ6 sJuanajd lauun; apls iad sagoui aronbs II ISO
�joddnS 'builab ulsoq gojoo ay1 aooldad bl AlaJowixaddo) r „gZ
a6 a fiw o�fi a uo auun oddns ssodAq opno,pAH _ p��l
p I 1 y� I j ll :1 sa}old laa�s
aoold 'a4ojB ulsoq y01oo ay1 anowad 's}nu bu!M puo
s�!oq laa�s ssa!ulo�s \� ; ssalulolS
iu0saad au0 - jjO�suj 0� Asb]
lauunj�oddns laals
ssalulols a6nb g
` S101 ONl>iddd (INd scidvA lb'I?J1snCINl dO0 10diN031N3W1a3S aMd HO
s�jasl it uisae uap3 egxaar)aE) (8)aausr)mAjjne
0 _'
T,
r Y '; s r •ny� � 4 +��' �
•_• _ • • _ • • �.�'4 "ti _.;.1�,.1�yi���F�:,• •�� "P.`�}D�..• *fir' .•:'. � .�' .. x:
_ •_ _• _• • Y.n '.•`i{fir. �'a. `:�,f '1• "•tr a4b�Jg3.� � �1!!•. ?Tir
•. . _ • l y�•mil ,• A, •. �-+.lw � ��0: },� �_^ �• l �_
w.
77ii((,,,,,�i'- _'ems.• �" p�,�� j� _'•� �yL�.s, ✓�R
_ �''-•i 1. �;.
�`J+�,i r�Y.t�'�fi• .f BN��;,r �� �Ct�• �Q�j Fs:1.- J�:�)i Iyah c'r� � ,i.
• •• • •• _ • _• _ r~'.� '•n i�� n +" A.. * ."+ _ �'• _ �r Alt:
41,
• • •• • _ • • • • r .+�� r �iC4t�J! rw i.,. •n.�.�1r3T.�S��J• �%'
•• • _ • • •• 1 :,.. (,;�r.��y• R• '• ��as't.rA7^s�fh�rr` ^to +�7}
ZY
IM
L, p
'+ • + w �� ate,
_ •• • • _ _ • • •• .l•}•�rt � vP•�,�j.�+YY•'�2•�,"y'����V�".qy�a��., V� �,�f �
.-%��r y •i •`.O;r „� a Ywjk.,''t _ •aa ti t•t� -
r ,q
• • • • _ _ _ _ • v' w �•�+• ��• ' a�t�y�c+v>• ,� ' yr .a.
_ _ • •_ _ •• • • •+•bT �".ii1 r•,+,^ fir._ �.�)y.•k ,,t^��r �-' �• ..�Xnt�`ti" `•1Y
•. . _ • "F.-alK+.` '.•;'"'"'• a _ �y�'.r" `,��rYi ,` `�� •�.,'r '�v �=."'QiC
--Rr _ r�" �' .'.'r•n`^•;•.`�.,`.:�:', �._.l �-w.•'y''jn�.:� a; a1.�rtry �',
oul'swalsAS luawloafl onby 16610)
lop paAol wop yollp
l-ad/4 to M81A uold wop yollp l-adAl to MaIA uo9ona13 wop yollp l-ad/y to MaIA uoponal3
PC
it
.Pp .90 di rrTT t Zr ♦Y Y�f<' �, •[II
.901
loll paAol wop Uol!p
A-adA4 to Maln uold wop 4ollp A-adAl to MGA uollona13 wop yolip 6-adN to MGIA uollon913
•pal000 opsold puo panuonlo6 Jo
paziuonlo6'laals ulold ul algopony �j 'rs ►
�sawelM leek a6nob 91. Il_�%.Ul y" ♦
fo ysaw an.M laals a O V 1„1X,1 lulod lofluoo Mo 3 of ���
•aouafalaid ApoadS Usaw allm
•alpxaloab auaµdofdAlod
uanoM fo aualAdofdAlod pagound
alpaau uanoMuou ui algoliony _
�.rz ►
-sayol!p !Dp!ozadoil
Jodl adNPUD Sa O .P nJO ••;,.
4
a
A ad/4 sad/4 o M4 ul awoo s
swDQ yo�!p(JaysDMA!nE) ME =
_ne•
!no% Jo; si pnpoid s!y1 'alp
ssaom of l!no!lj!p D anDy
< 1
not j! 'S/\DM JO/4e[ Dn
D ui pa�oojs aq uDo
PUD 'Iyb!aM Iyb!! aJD
'Sa!Dq MDJ�S UDy1 aODds ;ia.
ssal yonw do a�oj Aayl
pa�JodsuoJj /\!!sDa aJD ; Y%t';,
swDQ yoj!Q(,OaysDM!!nE)
-sbu!J boy aJow A!ddD puo _u ;,. r
DaJD dD!JanO ay1 asDaJOU!
'y45ua4S JaIDaJb Job '' � ": `• "'
'IIZ L o� .9 wDP gOI!P aye
jo uo!�Jod aJ!M ay1 dD!Janp
'w04oq puD dol ayj buo!D
bu!J boy uay� 'a!pajoab
puo Emm ay4 dD!JanO A!dw!S
,suogDOI!ddD UDds ap!m JOB
jeL4ja5q pe uijA ISDa aJD
y
swDQ yoI!Q aJaysDMA!!nS , ;: ..' • _ `� .
7 I �'�1 `� r,�y 1 •��1
Lw
V L ••-• N \ �'T�1S3 �� Q�13 � �F � IL�i1t �-w
♦ ♦ Sul 'swaas/,S juawpail onby L661cj'l
Sj
c� ► "`emu 4'. Div+ � '. A
i
:�
��8/� :Jajawplp aloU a�IldS ,��- � •
lK
,,9 :Ja�wolp cloy add
spunod t7 :IgbieM
t tom•'•'
"g L :Ssau�olul IIpM
auE)IAL41GAlod paplow :lpuapA
suolpollloadS
ono ysoM juanaJd pup sa�lds auk
Jaypp 'uapJpU IIIM Juawao Ilos ayl
•�
,�,, • ; ,tip=� -p.,;
uawao pupllJod UIIM�snp pup lauun; �f•. �Q � y
Gq� jo sapls aU1 punaJp I!os OW�opd
sa o a u aid a
I U P !I P- U� UBnaU�sa�ilds a,..�.;; �.��G �' � ,��• � �,�> ``'� _ • ;� '
a'-II• an!JP puo 'aoold ui lauun; aUl ssaid
4LJawao puolliod jo spunod 01-9 U1!M
A1y6 xlw os uasoo 'auun a o ~�nOJOU� "l! I I 1 UI• � � M��=::�. � r•• ' ,• r �a'`�`P�'`
�UlJdjoq aU1 uogj Ja6Jpl Allgbils oaJp
ajpnoox3 •jueweo puopod pup .�.. �. tee•..
sa�l!ds Z L Uj!M Pallo�sul sl leuunj aUl
•sJaonpaJ U�!M � k, �, 3: •s�
Odld uolsue�xa iepwap Jallows pure ti0 ��:;.�Eat ..,:
S�U!44 PJppuols LPm adld uolsu94xe .9
01 joauuoD -leuund aUj do�ooq aye
ul eloy al41 L45noJy1 jI anaa S I PUD
sa oul Map n s adld a o ua �A �° '"�' �°` .�- �
a i •adld � so 6o d a nJJ � i
� `� :��*�� f.- � `�1`!;`'.1:,�•�j�•, ,t+�;.,; �„r a� =' ,
t r,ce w`
IM
jo eoald goys o ono 'aigwassp of
'uolsoJe plono pUp
I I jJ 1J P
vol ona a JaMo p o ounJ and o
FJaaU p sl aJay1 aJauM SCJ D eL410 G?c
pup 'sin000 Ijulleuupuo ejeL4m ,
sedols jo dol eq� jp 'eouad ll!s ul j� � `�;;;
sin000 UfinojgpiDaJq aJaUM lauun� yy.•�
aU1 eoold AldwiS aolnap loJ�uoo
voISOK) p Sul-of-ASDG pun�olnb D sl
vun3 JajpMwJojS ejaUsr)mAjjnE) aUl ,r. r l•, _-•�,
lauun3 JaloMwlolS JaUsoMAIlnE) r
• � ' �tl i�Ji. /•4.1!(i1� i� � �. .c:.'f'a'.21`'..►Sli''q$'"�i r.t,:.1....+..v.f...;, _ t',:,,"`
• C L
•ouj'swalsAS juawloaiJ onby 1661
-sl10 palJlslnwe puo suaaus Jo
FAMN bull 6wAoo1S _
lC.AC)LJaJ Joj IJuun; wo.4o:l au1 ul puelq JaujAliod
-uogJoo auj aoold pup suogJaooJp/\u Jo uoijonpaJ
ssoJfi JoJ lauunl doh au# uI asolnllao euj aoold
'swnlpaw Jallld uloq uIIM asn JoJ pe>loo�s eq uoo fix.
Joliodes JaJomgo eloos flows@JausomAlln0 au1 _
-asn JauJJnj Joj puelq JawAlod-uogJoo au1 enowaJ
of leuunl Mdwe au1 u6noJuJ>looq sjualuoo
eJl�ua au1 Jnod '�udluJano >lIDOS jal puo �e�onq swn,p
uollob 5 o ul JaloM anplsaJ pup puelq JawAlod do}pasolo
-uogJoo eoold 'IslsJad suaaus Jl 'puelq JawAlod Uoii°6 ss JoJ r:
-uogJoo auk.
uk ufinoJuJ Je�oM anplsaJ auk Jell!; IauunJ p adnl
uau j sllo au1 do �Inq euj aonpei q asolnllao °"'m�"
vsewroLs
141"6uUA Pam«Lids -
aw esfl puelq Jaw/\Iod-uogJoo anblun Jno AJ�
'suaaus anowaJ of pJou puo silo palJlslnwe Jod
-s io ai is nwa anowaJ ou inn eso n ao au aION
I. p ,d. I � II. III �
rft
'pepJooslp ueag aslMJau10 anon
pinoM lout asolnllao puo Ilo auJ woJj AfD'jaua sla)anq
6ulwloloeJ seRlllooj bulsseooJd IolJlsnpul puo uoiio6 5 Jo;
�auunj I adnl mm,
S�Uold JloudSo 'sull�l luewao 'sJalloq aJnjoJadwa�
-MoI penoJddo uI peuJnq Jo llljpuol panoJddo uo
{,:iN
uI peoold eq /pow luegJosgo juads auk asn Jajjy .�' �o ,d°ow -A -
.Yk�;Ft�Y wauod
yt cy'I. eloU PaliuO '
'aeJj Jsnp puo 'Iu6IeM Iudll 'uoalo aJo sJaq!j eul
'1no uooel louuoo AeL41 aJauM sJaglJ au1 uIUJIM deep spinbll sMOJp juegJos au1 'uoljoo AJollldoo
bulzinn '4onpoJd-Aq bulJnjoojnuow Jadod puo dlnd o 'sjeglj asolnllao pewloloaJ sesn JoloJodas
Ja�Dm Ilo eloos-flows aul 'buua111J anuiluoo puo AlwJll Blood 'louaJow Mau u11M juegJosgo
juads auJ eooldaJ Aldwls uegj 'JaloM paJa11!J au1 Jo dol uo uaas eq uoo uaaus o gun loijejow
luagJosgo au1 esfl 'sllo 6ulnowaJ alluM AIaaJJ ufinoJu1 ssod of JajoM sMollo asolnllao aul 'IauunJ
au1 Jo dol auk ojul saJn�xlw JaloM-llo Jno% Jnod 'je>lonq uollofi g o Jano aoold puo I'uagJosgo
olx01-uou 'ejos Alajaldwoo au1 u�!M leuun; auk Ig AIdwIS ldous o sejn xlw jepm-llo Assaw do
Buluoalo se>low uoluM leuunJ asn-of-Asoa uo sI JoloJodes jepm-llo eloos llows(�jausomAlln0 aul
d31b'M dNns a31dNIWb1N00 SS3 OW •
2J31VM]ISVM ividisnC1Nl IVEId dcl •
3ZIM:111Nd V\10d:1 110 3nOW3d •
SIIldS 110 cIn N`d310 .
2131` m 3O119 ATO d31lld -
' d31dM dOW Allo ZJ311ld •
31`dSN30N00 210SS3?JdW00lb'32J1 •
k aopiodeS aapM-!!o C,_. pS !lpwS,aaysoMA!!no
•ouI 'swadsAS Juawpail onbV L661�5) 'S39VWV4 1VI33dS do IV1NDmi SNOO 'Siliodd 1SOI ANV dOd 319VI1 39
'ONI'SW3ISAS 1N3W1V3di VnDV I1IM 1N9A3 ON NI 'S1OnaOdd 'ONI 'SW3ISAS IN3W1V3di Vnc3v dO 1N3W3OVld3t1 39 111M A03W3d 3lOs sd3SVH:Ddnd
304n1s 031Vd3N39(INV'VI43W IN39?JOS9V IN3dS'2131VM(131V3dI'd31VM CM3111d d0 MOAK](INV 3SdVH3SIa 3H1 JNINd3A09 SMVI 1VdD(13d
CNV'31VlS'lVOOl HIM 3ONVI1dWOO dOd 3191SNOdS3d A1310S 32JV sionaodd'ONI 'MKSAS IN3NIV3dI VnBV dO sd1 sn(INV S213SVH3dnd
1MAN02JIAN3 3HI 9NldDIN3 SINVInIIOd dO INnOWV 3HL JNIOn03d d0 SNV3W 3AISn1OX3 3H1 SV 3Sn 2JO3 a30N3INl ION 3dV SlonQOdd
'ON! 'SIN31SAS IN3WIV3dl VnOV 'ONINNVId NOIIN3A32Jd N011nliod(INV'JNINNVId A13dVS(INV lOdINOO OlddV I'JNINNVId 3ONVN3INIVW
INK )MIS HIM NOIIOWNOO NI S10(100W'ONI 'SW3ISAS 1N3MV3dI VnZ5V 3Sn '3SOddnd dV1nOIIdVd V dOd SSINIId dO'ALl1119VINVH0213W
'3ONVNdOd213d 2113H1 9NIOn1ONl SIOnC]Odd SII 011O3dS3d HlIM'a31ldAI dO SS32JdX3 d3H113 'S31INVddVM ON S3NVW 'ONI 'SMiSAS
1N3W1V321L Vnnv dlHSNVV0QJOM(INV lVld31VN NI 9103d3O NOW 3321d 39 Ol Slon0021d Sll 9INVddVM'3NI 'SA3ISAS IN3AX3d.1 Vn?5V
I _
♦ Imo. _�
.b9 —
'sJallnd louoljuanuoo •,ol ►
a�llun spuou uloq joj dlab o soy 11
'jallnd Glab piopuols ino Ail r�
'lonowai apic) uloJp wiols
J01 paJlnbaJ lauuosiad aldlllnw puo
luauidlnba joj paau aul a�oulwlla
sasoo awos ul puo /sinful jo �s1j
ayj aonpai uoo tl 'setab pa4ols /
ebic)l jo Moay Joj loapl sl aallnd
'E�)m6 Olwouo6ia -,jjausonnAllnS aUl „ PIT
�•
_..�
.ohs.,.
�All ]ndS sjimPN1 ioncid
i
dwnd dwnS
abow0sid,atom u0e0 6uuatoMa4 e6pnlS
,atPi
�b'H�SIa
paq 6ultitp of abpnls uloia-9
asnai JoJ iapm Juooap•b
1�/V�31Sb'M ('ulw 0£)al4es 191 puo jaxlw doJS'E
(saJnulw 9 xlw)JapMod
JuawJOaiJ ppo puo Jaxlw Dols'Z
WDI JuawlD84 II1d-1 >,Uol bulxlw
N I W I13 :suopni�sul juawpail u01100°91:
� �l`dM
puoJS Wol'9
iapnod Juawpail spunod og 'g
�j BOA JaJlH ialoM PaJoail'b
pun 6ulia}oMap a6pnlS'E
(AOZ 1)JaxI1nl Joays-U61H'Z Ja�DM uJOJj Oda 's93d 's(OIauJ MOau 'luauJ(pas
3 n 3 d (pepnpul sbulJ11J)�uol JuawJoail'1 '110 JO IDAOWGI Jot we,—sAs;uE)wjr)ejj 94S-51 u!S
:sjuauodwoo we�sAS
SWea S/_ �UGW�DeJl Je�DM elOOS-11. -US
�g wv
'tvntors 'V of t v
8Z9�y
SYM3��y .�'
uoo,,,,
9661 g
ioozf
- savO'l Q��Q
(13A13036 al�usr�s
08 ctnrrn�
MONs
N UOO'I1
—�� 5Qd0'I 3AI'I
�QOO
�'RI�L12i0 NOIS�Q
LNaI-lo
NOI L VOO'I
.LJar02id
2rwVN 'Dar011a
4Lf c ZSZ(9pZ)
IOZ&6 VM `-W-JaAJ
a.IOltlaahl 9I Z£ '
_ IlaIIljgarl
' I
I
I
t
r�
ND, IS30 CINIM
=1` Z ' Z ; 0 ' 1 x fold + 191 n � ' 1 k 29' 0 = s�
ca '/ (TCZ 'oN e1gE1) aoloel eouspodwl s I
-� '9I (d 9/, 'ON elgEl)
lAel EE to luble11 paepusls e41 la eanssead uolleubals pulM = sb
� (H-91 'ON elgel)
uolleaeplsuoo aepun uolpod jo inloruls eyl aol luelollleoo eanssead = bo
zL 'O ' L- 9.'0 " 7,90 (0.91 'ON e1gel)
lUelollleoo aoloel lsnb pue einsodxe 'Igbleq peulgwoo a e0
eanssead pulm ublsep a d
ISbb0a0 = d
:v,l wuo:j 'JNIMOi iOd 3Hl HIM 30NbOH000d
NI LHO13H kNv HOd 03NIWH3130 3A TIVHS S3unio 1diS
JO S1N3W313 HO S3Hniond1.S HOA S3Hf1SS3Hd ONIM NJIS30
��sz-zsz�9oz�
10Z86 VAI `paid^'
'and ajowpAl 914-
!a — — 'ON e6ed - ►
'ON Pf')Jd � Inlo / jojnpnj� '
saaaui� �, ,
a,e a 'As u a.0 4 q ea N H
------..�...�------------• -- ------- ------ -------- - . -�•--------- ._ ._ ����:-pus------- --- -
09
`5-1C)i
170
_ - - 107-86 `
Jp 'ON a6�d
•an d dJOUI1afl 9I ZF-
--- w n�
i 1
- 'ON 100.OJd Saaauibu] �ini3 / Ipanpna4S
ueu4g8] N H
i
I
��
/-7
�)0 ��1' xS'91 5
gxg -LISoc�
_y 0'86 y 7 I x go -
--
� -171
1.0 O 1 -3
j.S-Q d N7l 1
Tod
_ 10M VM `1lafan
artV dJ0ul;aM 9I U.
Jo -ON abed
ON »afoad sieeuibu] Iini::) / jDjnpna�S
�A8 - UeUIt`Ia] N- H•_
I
f
I
' I ~
sz Ar
7F 9171 >1
h 4 --'h CI--ri--_
o !
S8 'o - �I
-,o1/o Z•► .
097
c)b
�L�'Z'ZSZ(90Z)
IOM VAI `uaJan
-- jo ----_ 'OPT a62d �srnr..ra�r.�s
s19GuI U: I !Alo l Ipanpna�S
Oleo
ueu4qGTN HH
� - j i - 1
i
.t
i
.,
01
�d / �..
c'
pg/- Qi
0
I�r X Z /1
Q �I _ x C2� ) =
- �'L f'Z-ZSZ(90Z1 ,
IOZ86 Y'ihl
IIll 'and aaour;aAl 9I ZS
Io .0N eGL'd
_ . - Saaaulbu lni pan !ana
\ _ O D
O �
y rnco 0
e o cn o y rr-
L.. I U 0
N � N
U U O
D
(� � m
v
I� D
r
N O O O n n �
711 � n s
D
CO
s O a
C1 (I m r D
CL
r
re) -
D
z Z O
00 oo m Z
a o a m _
a
` re) O D
c�
r N prn
^; 5
f v\ 0
D C
O n m
r T
00
ro) D
r -�
> > FS
3 3
3 3,
m
cn cn C i
ti
n a a1
N W.
w
a n a
7� �
t
A INO rzvIlnzorn",ns
1
�j asy :.RE Q d V N Olsd OZVD
r
�'Ntdpj
9p
8Z96Z
y
SV* sUIdn 110s
Hooria
a —
smvorl GVHG
NOZ Ozwsias
0(9 UN LAX
d �cZ mONs
i
-doo-la
SQdO'I aATI
MOD
vI2Ia.LI2I0 NOISM
�1ff71,� Q e
NON I�
9661 t & rC119N l HW/f Nollvaorl
ddA$ 33 _ x�gwnN so�roxa
9 b XP)/ CV9�.�— 9-1 co 3wdN ioacoud
u rz-az(9oz)
IOZ96 VM `UalaAa
•aAV'0A0Mj;DM 9TZ£
jo ^_� .oN a$Bd s 1,99U1au:�J_ IAAID /Iunjan.I1S
akvc-v a��Q Z;fig llallllq.arl M H
i
Y ��
.. �
�, w f
r'
r�
Jd�► �3d Q f
Nl-JIS3CI GNIM
Z ,-H a '/ x Z- 910 = 0zd
cis '/ (TU 'ON agal) jopel eoulapodwl = I
-::iS-J + '91 (d-91. 'ON eIgE1)
feel EE to ly6leil piepusls eqj pa eanssaid uolllau6tls puler► = sb
f 9 '1 (H-91 'ON ejga_b
uo1lsaeplsuoo jepun uolpod jo mpruls eyl aol lueloUleoo eansseid - b0
G 9'0 Z90 (0-91 'oN epal)
lUelollleoo aoloel lsnD pus eansodxe 'Igbleq peulgwoo Q e0
=A'5d V 9 I eansseid puler► ubisep a d
Sb b.0 eO = d
:v-inWH03 JNIMO11Od 3Hl H11M 30NV00000V
NI 1HO13H ANV HOd Q3NIWd313a 39 11VHS S3LIniO1H1S
dO SIN3W313 HO S3Hf110(1H1.S HOzi S3Hf1Ss3Hd UNIM NOIS3a
I M6 V/f1 `y9j'9
•any dj0w;aM 910
jo — 'ON e6ed
'ON - foad SJeGlUIC•13 jin13 / Ioanpna�S
a,Eo —Ae. Jua.uING� N H
Y , , �-
Or-
Tj
4:
09
1�4
-ESV90j) :.cz FE.
IOE86 VAI
dj0w;dAi 9 IJE-
jo 'ON D;bL'd
.ON ),OdfoJJ
sAE)eul.bu3 I!AI'O jojnpnj�S
ueuPeTN HH
i
T_
11
� _r
t•
-D)o
• �-�=r fills;;'�-�la,�
Z/y o ' — >
g 1s c 'o
Od
x so S
i .
A 191 (���� ;
! � �7o� = ��
4 I 2�1x1 9�
r 1
� n IZ X 2 +�
s
Tod
W86 V1fl `ua�an
aced r , -an d dJ0W;0M 9I Z[-
_ .10 °N �.
. r
---- oN ,0aroJd saaauibu� Iini:D / Ipan �Dn4S.
ueuNOI N- H-11.
i
•.
J
zC ko_q . 9`-,�) >1 , 91 x /
9 a/
S 4701 - 4�
91
1�d 090 z 9g x (al 9 = gY
410- /
_T_�QZY M�d 0//,,o z)
_ x
�Z-ZSZ(90Z)
10Z86 `uaran-g
_ . ._ and dJ0W;d fl -91 U
10
— ON hefoid ,` . sJeegbd limo l joinpna�S
og
-� D _
_ i
I i D 'o I
913
-70
I � ,
( G _ o' x :�-- 91 L'Q x zq'o _ 11n
1-0 10
10M fy/H. `j�a�art
_ , _ •and OJOU 1aA. l 9I ZE
-- -ON. »erad ► saaaul�u� Ilnlo /: I_oin.! n,
alga Q
,
---- _. ..: �8. ,
_ uaullual N H
3 _ I O0 O
C. 7C
rn co O r
O cn O y r—
t7 O <
—1 I W
n n n
x x x
�} D
-.
m
M
I� D
v
(� z z Ago
co O O o me n
o x r,
(=r1
_ _ D
m �
C I i a o 0-
O D
ro m
re) � m r—
D. T
• _ CO O aV m � 7
CL
rp 0 D
J ^ �
lr a o a
fV �
r� O n m
A —� _
O O
a �
m
3 3 3
3 3_
m ;
a. a a\
ti cu cu c
i
S'
t
-9-�n-t� --��rv�(d Wiz//✓ e�
/�� c��l�✓J rr� ���5 vaQ'u�� ����.� z
,,. ����;
'ems.
'N
Ird
cc4-nyrV��/
�j�� yz/Y✓J rrJ y��s �aQ'��7 ��� z
r �t
-Z �-
0
� I
t
+,.
Mr° .��'�
NFL
_ __
����v
- -
�✓ I-- i
CITY OF ARLINGTON
CONSTRUCTION
PERMIT �-
❑ COMBINATION IR BUILDING ❑ MECHANICAL ❑ PLUMBING ❑ SIGN PERMIT NO. , 1,
j OWNER MAIL ADDRESS C17Y ZIP PHONE
BRuc.f L-04LDEN $!S ULIV/A PARK RD 4 YKePI n- 93Zay 647-S) -�S5-OS9Z
ARCHITECT OR DESIGNER MAIL ADDRESS CITY ZIP PHONE
GENERAL CONTRACTOR MAIL ADDRESS CITY ZIP PHONE LICENSE N
SL-w i?)2&6 ^ sT-5,t_ r3Lp6• N7 ACD R I-N, MT. VE2NOM 9RZ73 ,34&j07LI-'i G 21,ueRSb
MLCIIANICAL CONTRACTOR MAIL ADDRESS CITY ZIP ` PHONE LICENSE 1I
" Item—n .aG e /ate
PLUMBING CONTRACTOR MAIL ADDRESS CITY ZIP PHONE LICENSE N
3 CLASS Of WORK
O R NLW ❑AUDITION ❑ALTERATION ❑REPAIR ❑UEMOLI PION ❑BUILDING RELOCATION
QVALUATION OF WORK
z s 69 /66 1
IWyI ULSCRIBE WORK -�
3 x 9 PasTFqAM.9 SOOP w I x ' £E Pll r IPlqm G - O
m PROPOSED USE OF BUILDING
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLIC
w S OP Als LE - i TION AND KNOW THE SAME TO BE TRUE AND CORRECT ALL PRO)
z LLGAL DESCRIPTION 01 PROPERTY(SHOWN BELOW OR AT tA(-H k OUR COPIES) SIONS OF LAWS AND ORDINANCES GOVERNING THIS TYPE OF WOI
J
J LUI BLOCK OF WILL BE COMPLIED WITH WHETHER SPECIFIED HERIN OR NOT.T1
GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY
31OS-H--017— S VIOLATE OR CANCEL THE PROVISIONS OF ANY OTHER STATE (
j TA I MBER LOCAL LAW REGULATING CONSTRUCTION OF THE PERFORMANCE(
a FROM PROPERTY TAX STATEMENT CONSTRUCTION. PERMIT . CPRES 1 YEAR FROM DATE OF ISSUANC
S N•G . ? SIGNATURE OF CONTRACTOR O Ut1iOR)ZED AGENT DATE
O
0 IOB ADURISS
T I �so � x 3-G- q�
(O{'iICI?USE ONI.Y)
PLUMBING ECIIANICAL
NO. TYPE OF FIXTURE FEE x's FIXTURES NO. TYPE OF EQUIPMENT FEE x's FIXTURES
ATER CLOSET (TOILEI') TR COND.UNITS-H-P. EA. 3guip.list**
ATHTUB EFRIGERATION UNITS-H.P.EA. uip.list'•
VATORY(WASH BASIN OILERS-H.P.SA u .list••
BOWER AS FIRED A.C.UNITS-TONNAGEEA. 3guip.list**
TCHEN SINK&DISPOSAL TORCED AIR SYSTEMS-B.T.U. MEA
ISHWASHER NALL HEATERS-B.T.U. M
UNDRY TRAY NIT HEATERS-B.T.U. M
LOTHES WASHER 3VAPORATIVECOOLERS
ATER HEATER LOTHESS DRYERS
RINAL ENTILATION FAN
RINKTNG FOUNTAIN ANGE HOOD COMMERCIAL
LOOR DRAIN 1R HANDLING UNIT- CPM
VACUUM BREAKERS VE
OOF DRAINS-RAINLEADERS ETALFIREPLACE&CHIMNEY
INK SERVICE-BAR,E-IC.) WATER HEATER
AS PIPING *(up to 5=$3.00,add al.=$35
--**Equipment list must be provided
SUB TOTAL SUB TOTAL _
PERMIT PERMIT
TOTAL FEE TOTAL PEE
SIDE.YARD SE I BACK STRLLI SL TBACK REAR YARD S T PLAN CHECK NUM PLAN CHECK FEE
r� I )
�� C� FEE L10.533 IRECEIPTNOgggq
USE /o4 LOT ARk A VACANT SITE
5� �-7f Z]YES O 1 LLES VALUATION FEE
TYPL( ON.SIIf� OCCUP NCY R 11P NO.OF DWELLING UNITS PLAN CHECKING NG 'b
19 / 9 BU'LDING $ / 0 /
SILL 1 BLDt, NO.OF S ORILS MAX.OCC LOAD
PLUMBING
F IRE SPRINKLERS REQUIRED
❑YES NO MECHANICAL
STATE BLDG.CODE
COMMENTS ENERGY CODE SURCHARGE
{ R EC;EIVEP PENALTY U.B.C.
SEC 303(a)
I'll'R 6 1996 WATER/SEWER FEES
TOTAL
CITY OF ARLINGTON
PERMIT VALIDATION
WHEN PROPERLY VALIDATED TIN THIS SPACE)THIS IS YOUR PERMIT&RECEIPT
PAID CRIF BY
BUILDING OFFICIAL DATE
cc: ASSESSOR,APPLICANT,TREASURER, BLDG-DEPT, RECORDS COPY
I
City of Arlington N° 8937
238 N. Olympic
Arlington WA 98223 Clerk's Aeceipt
(360) 435-5785
Date '' 19
Received From: -�
For:
❑Cash XCheck Amount Received �4±)�
oU
By:
White-original Yellow-Cash Register Pink-File
CEMENT DISTRIBUTORS, INC. 226
VENDOR NO:
NAME: City Of Arlington CHECKDATE: 5-29-98
REFERENCE NUMBER I INVOICE DATE GROSS AMOUNT DISCOUNT TAKEN NET AMOUNT PAID
Permit # gq.r q
Bldg . Permit
17501 59thAve - NE
Arlington , A 98223
TOTAL t `3 0- r
J
22
CEMENT DISTRIBUTORS, INC. WESTERN BANK
815 OLIVIA PARK ROAD BELLEVUE BUSINESS BANKING CENTER
WA
EVERETT,WA 98204 BELL8-80 12 98004
9
PH.206-355-0592 8-807- 51 DATE
5-29-98
AMOUNT `���
c 13 �-�7
PAY ��
A- "41
TO THE
ORDER City of Arlington
OF
II'0 2 28 1 211' is 1 2 5 1080 713l:^20 1 0 19 70 20 1u1
a,.
i
ARL 'r ON
IOaW ST. t
x
c SUBJECT
a PROPERTY m
ti
172nd STRIiE(' NB m '
SMOKEY POINT
I
LOCATION MAP
I
NO SALE
SCALE: 1" = 100'
PROPOSED
DRIVEWAY
} _ j ENTRANCE `
TREES e di
S $
I I 2
!TREE
PROPOSED
' I• g �o SHOP I
J I �' PROPOSED 70, O1 /
it I i •�0•
1A�
y
�✓ I�,I �I I0 PROPOSED
1 0 1 J DRIVEWAY
' I r�
zzI ' EXIT C'ONCEtE'1'E DIS7'RI}1UT0RS } r!r
M. I I TREE ' r• I
q PROPOSED
' II .DRIVEWAY
ENTRAHCE-E817 ,\
SITE PLAN FOR:
CEMENT DISTRIBUTORS
Cl(
12636SP.M.
CASCADE SURVEYING Surveyors o
& ENGINEERING, INC. Engineers ; ¢
AL L
ARLINGTON, WA
102 E. Division •PO Box 326 98223 Planners
(360) 435-5551 • (360) 652-7572 XPiRES: 12-23-99
FAX (360) 435-4012 -