Loading...
HomeMy WebLinkAbout16415 Smokey Point Blvd_BLD4149_2026 � - CITY OF ARLINGTON ` 18204 59th Avenue NE,Arlington,WA 98223 INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551 BUILDING PERMIT 16415 SMOKEY POINT BLVD Permit#: 4149 Parcel#: 31052800201500 PERMIT EXPIRES 180 DAYS AFTER DATE OF ISSUANCE. Scope of Work: Kitchen hood and duct wet chemical fire suppression system Valuation: 7737.00 OWNER APPLICANT CONTRACTOR GRANDVIEW NORTH LLC All American Fire Protection Fire All American Fire Protection Inc PO BOX 159 P.O.Box 393 P.O. Box 393 ARLINGTON,WA 98223 Everett,WA 98201 EVERETT,WA 98062 4252683514 4252683514 LIC:ALLAMAF854QF EXP: 11/06/2021 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR All American Fire Protection Inc P.O.Box 393 EVERETT,WA 98062 4252683514 LIC#:ALLAMAF854QF EXP: 11/06/2021 LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: Fire Sprinkler CODE YEAR: 2018 STORIES: CONST.TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: OCC LOAD: PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid. The building official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation, guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City ordinance,regulation or order, state or federal law,or any order,proclamation,guidance or decision of the Governor. I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC 110/IRCI10. SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on your sales tax r turn form and coded City of Arlington#3101. i Print Name Da a Released By We CONDITIONS 1.Permit and set of approved plans to remain on site during installation.2. Final test and inspection witnessed by City of Arlington shall consist of the following: i. Orientation of nozzles shall be verified with the use of a nozzle aiming device. ii.A nozzle cap blow-off test shall be conducted. iii. Signage shall be provided on the exhaust hood or system cabinet,indicating the type and arrangement of cooking appliances protected by the automatic fire-extinguishing system. Signage shall indicate appliances from left to right,be durable,and the size,color, and lettering shall be approved.iv. Installation certification form to be completed and submitted to The Compliance Engine prior to project closeout.v.The hood suppression system shall be connected to the building fire alarm system. THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS, MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount 10/20/2021 Suppression System $200.00 10/20/2021 Processing/lechnology Fee $25.00 10/20/2021 Fire System Plan Review $148.67 Total Due: $373.67 Total Payment: $0.00 Balance Due: $373.67 CALL FOR INSPECTIONS Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon Permit#: 4149 Permit Date: 09/21/21 Permit Type: Project Name: Holman Recovery Center Company/Applicant Name: All American Fire Protection Fire Company/Applicant Address: P.O. Box 393 City, State, Zip: Everett, WA 98201 Contact: Kenny Graham Phone: 4252683514 Email: allamerican—fire@aol.com Permit Type: Fire Sprinkler Valuation: 7737.00 Square Feet: 0 Number of Stories: 0 Type of Construction: Occupancy Type: Scope of Work: Kitchen good and duct wet chemical fire suppression system MIC/Opportunity Zone: Permit Issued: Permit Expires: 03/20/2022 DNU: Status: IN PROCESS Assigned To: Ameresia Lawlis Property Parcel# Address Legal Description Owner Name Owner Phone Zoning 31052800201500 16415 SMOKEY POINT GRANDVIEW 230 COMMERCIAL BLVD NORTH LLC /SERVICES Contractors Contractor Primary Contact Phone Address Contractor Type License License# All American Fire Kenny Graham 4252683514 CONTRACTOR Construction ALLAMAF854QF Protection Inc Contractor Plan Reviews Date Review Type Description Assigned To Review Status 09/21/2021 Fire Suppression BUILDING In Review Fees Fee Description Notes Amount Suppression System Pre-engineered or Custom $200.00 Processing/Technology Fee $25.00 Fire System Plan Review Table 4-2 or 4-10 $148.67 Total $373.67 Uploaded Files Date File Name 09/21/2021 9729553-4149 Application.pdf 09/21/2021 9729552-4149�ystem Drawings.pdf 09/21/2021 9729551-4149 Email.msg 09/21/2021 9729550-4149 CwSheets.pdf 09/21/2021 9729549-4149 Certification.pdf FIRE SPRINKLER PERMIT APPLICATION \-ZJN6" O Department of Community&Economic Development City of Arlington• 18204 59th Ave NE• Arlington,WA 98223• Phone(360) 403-3551 THIS APPLICATION MUST BE ACCOMPANIED BY TWO (2) SETS OF COMPLETE AND SCALED PLANS, TWO (2) SETS OF HYDRAULIC CALCULATIONS, TWO (2) SETS OF EQUIPMENT SPECIFICATIONS FOR EACH FIRE SPRINKLER PERMIT APPLICATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO INCLUDE SPECIFICATION SHEETS, WIRING DIAGRAMS (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON ALL EQUIPMENT TO BE INSTALLED PRIOR TO INSTALLATION. Type of Permit: ❑ New Fire Sprinkler ❑ Fire Sprinkler Add/Alt + ❑ Underground Fire Line Project Address: 16400 SMOKEY POINT BLVD. Parcel ID#: 31052800201500 Project Valuation: W66.06 - 13, Number of Heads: 9 Building Area(Sq Ft):NA Owner: GRANDVIEW NORTH LLC Phone Number: 360-435-7171 PO BOX 159 ARLINGTON WA 98223 Address: City: State: Zip Code: Contact Person:KENNY GRAHAM - ALL AMERICAN FIRE Phone Number: 425-268-3514 Cell Phone: 425-268-3514 Email: allamerican_fire@aol.com Address: PO BOX 393 City:EVERETT State: WA Zip Code:98206 Contractor: ALL AMERICAN FIRE PROTECTION INC Phone Number: 425-268-3514 Address PO BOX 393 City:EVERETT State: WA 98206 Zip Code: Contractor's License Number:ALLAMAF854QF Expiration:11/21 Contact Person: KENNY GRAHAM Email:allamerican-f ire@ aol.com I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the above- described ropeerty will be in accordance with the laws,rules and regulation of the State of Washington. Cr( racr/r,���-ter/raorr -Y,.,e.».-,,...�o�,,,.e.a", ,,. 09/21/2021 Applicants Signature Date Kenneth L. Graham Print Applicants Name FOR STAFF USE ONLY Permit# Accepted By Amount Received Receipt# Dale Received WEB Forms—131 Page 1 of 1 6/16LP :/ " VI I V Ameresia Lawlis From: Jeremy Manning <permitallamericanfireprotection@yahoo.com> Sent: Tuesday, September 21, 2021 10:10 AM To: CED Main Line Subject: 16400 Smokey Point Blvd. Fire system application Attachments: HOLMAN RECOVERY CENTER SYSTEM DRAWING.pdf; Pro Tex II Cert (1).pdf [NOTICE: This message originated outside the City of Arlington mail system.-- DO NOT CLICK on links or open attachments unless you are sure the content is safe.] I uploaded an application to you this morning for the Holman Recovery Center. I need to amend the application with the following information and documents. 1. Job valuation is NOT $5000. It is $7737. 2.The job is NOT for a sprinkler system, but a KITCHEN HOOD AND DUCT WET CHEMICAL FIRE SUPPRESSION SYSTEM built to UL300 testing standards. 3. Attached are the system drawing and manufacturer certification. Thank you for your assistance. i I 0 Z = w in aw I-� W } >> a d o a �Oy m '� Z� 'c v cuuLL C/) z 0. Z¢ Z 0 Q `\ _U � O O Z = W I m Z=m J rn, e C a U a aX Z toO o N i � N o O J z, Z = m a ~ q - O H ? j IA z 3 3 ® W O Q x n >_ N Z Z J W Ncc N d O W O N W p N H LLJ W A a F d Z e o : ui LU w �Wa �" oN Z z O V1 M 00 W o " ° C7 O p z d o, �o °o z 6 " -i W M N W x � O J �4e4 W LLI m a W O ♦ h W (Au ua aao W o co x a = p a W N Mm � 4 N soft N H N Y ♦ _, z x Z_ Z II w iO a J N N Z 1'A h'AW iD O I C y Q N O ? cc m `tiN Q A d ~ I W v_ a a 2 a Q z ui uw W Q a1 .v m EVON 1 0: a Q x r a Y w O¢ ih�'.•� r W LL N�aC7 O Z z a a a Z a ;0 kD iP d M ei M J c v � R � r r-- Aa -� is 1� ;v Lys 3 O � y v p z U �► v Go JIM GoA IS bm Win c •N WN d O a � v x i i I I I t.1.rpR*2�4i�wtaiw CHAPTER II COMPONENTS CYLINDERS B;VALVE ASSEMBLY 'Itw Pro"ree 11 Re*wumis r rt 9uppewtioniel"ann h"4VAlmw focirdiQamesuecyWd={1'1N`tLi oosLmo,1.46W,and Le4M Cybn&rdw%dreetp•oedeittrmetfartiRaa�trr� e•IN ape(itfiit.tiw 1Jm* wr* A r tie rr me"g$aitl'Mccpiltden are marafacturad,wderd. N atd met DOT reslrarmana C�llindemcwneFwt4A 3wth ' 00 — vt 0%mm Aging eVnr arid aft dtr rgrd r+eth d n nil nVen to a prewnreof21S plat;02rF-Chinder and rah* Awmmv dimenwmi an ebnwn to 2-1 and T"2-1 1 "wrw♦ - /irbe !&r- urI-_11fL�_ lava, Host l ee �uut' t ti tt ' 13 itelktt�n asM *1.W ILW tm lk"111. ._ rare 2-2 �a,e trcw Sectrtm 'tali@ 24 VALVE REBUILDING EQUIPMENT I.WET VALYE RIM UD Im H IT 4 WX 060,r.va ARQ*"an dreherEe.IN valve aranblP mom N n%sbl to 15T r*ryw pn or 60we tfprtwi us Tht Noe V&"Robuildiag IGt c i t !FNN i.• i''• I dr,dd be used.h lm%L ca di awnpamrna necessary w p"e*robudd The.the See IiRse 2-.1 and'IAk 2-} Pm-r to amerw0r-43 arp dmid be bkommed wah 0-nug h+briwtt F#Avm 2-1-CyWd;and%Wwr Amwtr*h A L �� t WN'Jlllr�. II r e pe+e.w,re ceded pappa tote.Y1.e detrMywd tr ptvNtderapbdaofaaMoemrddladtia, cis:is,It uamerwelha Pawm� Rapid**fNNlSM51ibalm4wodimAr, ptt.wre �-�-� ID Io"p See Firm 2.2 and The 2.1 E: -$ rm nNi t►.wt'rr Pgm*2-A Vahw RoWildorg Kill • WA 4tia swv t *A V .%m 1*.rrH7 ter few K*wv" V4h* *mj _ I RYA V*Iw 4m�.mHv * rok4ham* na* a A*wtW LWvr*rfm t "mtmruf 111Ar0aI" 4 k"w"ia IN e(),W1 A •,itN1 r►••*�er4*yr — 4 wnnrn ►wa.n( bas r 40ommnu VAvCyA.ubk 'F11W23 N SaMPrM reeafAOflt� p sap^ w.tu�ea*strt�t 1YIir 2,2 2n15 Irw L fee.U UI F.%�12t t Yen•PlFA1+L' owfow 2 CAAv d+rn M PU NSURE REGULATOR ASSEMBLY VIM (.)it rider in.r lldoon initnicso tt are protrided In ifhc►nlalLo wn 'M 1wame RrBtsWw Aewembll(WN i f was w nh the ardicm of tits manual$ae Purr 2.7 tybuderVahe Asemtbly(P!N SM1751 and isawffA k ifthe comFiete prtaaraer re;tshlor rvgmiet rgiaeennnl le aF'- thNeddamelpi Sae F*vtr2-4. Pure 2•4 11more Repittoe A+twmtiy PRWSURIlREGULATOR [if fit ILDINGKITWXMIfti1 Ala tfllan dlrchrrtie aed hydeerrttttc teM sttemtlr the Presrma ftu Recur dPlN illplBSf ntiM brnbrrM to enrar grope fusee opnikm TM P+wurr H:x-sw RoWhiltns 0 WN SifDill a=-7:l.Tkntter Mounting Ilrrsiet dwuldbe+red fl 1n ladetolmtttpemaA,aedirrleuc aeu 01% 1 McCreary topoperty rob"id the pierrore negabilor. Mtn, her` _ im FigaoeI-3.. mi Ws .,1 su ttrnx� _- •��+i A o— WET CHF.MWAl.lt1131AFAik AULN'l �,awe. (PINS RL1600&RL3000) O � - _ast.AexV '�wetchemtcslir�d+arw�etttt:srdtnthePraTexllRerAaurarM ttrnivat tanirrici:.. ++ Pi ,rrwanSplrmi•s patr..Mrrn crarMnselr.rd.ianrr Fthat is enurmoelyeffretttr for peare'aired laden firer,`I?as tgwv ree 2tY Rag+rbelor Rebrid Ktt n rttprtlratl ytrYN�atno'.��: fes.yfinds rrd�asrlttnR m I 0 and WET VALVE TOOL(PFN N'T1l ►o pRun�u ineraa f PVN i RL Iet10 and R 1 Jil10l AfMr+}arwn Ilse V'll Wd Vahg`tbdisdognedtoitahtaetAe ,buildinged diechaW.tlre coin,.. inge6womustbe.leanedap the cybmder+aka an m* h*mwld be need to hold the prim anmafirly wth hate,m4y water to pieeett cmtarcet ed allecied whir anamiring the cr and imen tervotbly- ear ha+Sre IF 2 i See Iirn 24L 1 Fgare2-oo Watt Salta Tsai CY UNDER MO NTINGBRACKETS P%wre2-s WetChamkalR,achaewA#mt (PM'S M 015&M 01) Fw SDS in4lrmawn cargact Hebw L o Wkt of YW Verwalbra4e-egcfdwLliOo.LwD0amd L4eooirpn»-wird lq wwwousim trrean the M fp S Cyioder MntaAinS A radaet Vernal bradueen8 of for LOW it prew;dre by ice MR I Cybo4dir MawAmq firaclrl Aew f (:ill"T ION 1 brads mum be ordered apsa W y w,:h tab elt der_ Ste TA& 2; f<a carld whan hslydfWlRend �aniniop,�w,gtiM.firawe lbry art caosec IMear to all -ML Ifyae,Set my agent buss yore eye flash Mann vah cium moor for 15 minuooa a rid 4;00&18 pftrysietai. 9 Tow go eo T a A'-.'art T*W Ain.6046 0 wah sold mier on prey"trraa*m TW agent is elecataly candwirm You mwl dean if All q Mtdadtagedaround Aviricrldpowraetbrfnre Ina otrn0*perarrb&kon. 2o� i -L Pe.[t Lit F%4321 i itrrr•Pb1AN2 0aFolff2-4. . MECHANICAL CONTROL HEAD 16 GRAM CO2 CARTRIDGE(PIN C0]6) (PIN MCH2) 'Thr tX126*pam(Xn C'srtrid i requirrdt+prrrumt,l:orlt The Mechsrtal Corwol Hard CP1N MCJ{li r a mechrtawl acuaw the cllerder tahe down6ll.'nw mnrk*is rwialed in aonaolhaldwhichoanhe.aanar�dbtlrrl.11401.1000IAbdo the MC Ill WdunkalCoeAral Hadar n6tENMCUIMaswr err the L6000cylirda mire arembllc.'nwMCNI Nedunic-al Erwin fee hlgwv 1.11 Control Had wd suMam adRacum Istic a RPSM Bemm-t l. dosowulPaH%*woaandamecfarnicalevelkwA;rc+acecll 04fto garralre khlra�ISwrtirs$R�H`sMliPfYfLfdSUNl1hL )^MYT2.or MMPl1T21 can Nordead oo"ratelf and idd T�tas 2-ll Is gramt.(�2 Crrlrxiji rIstIIYd Thaw ihtolncalnanadactudsw Ito 4heM4:H1 CONTIIOLHEADMO[TNTINGBRACKET MedhanuelC:ca•rd FleWd'Ilse MCH2 Ma&antral6wsrul Head can aciusiea m urntimotlne(Sl clindestlilhthe (PIN M0P2) M26 161pam CAl2 carlr+dp Sot lure 21 11re MRP2(:amid Hard Moaners Ruches nwo be uidd Ica mcvn the MC ILl MacMrnal Control I laid it the omwil hard 11 mrwutad d`eall Fon 4 cyli rdr r.ahv a we milt' .%,o F*ure 2.12. IWAUiIANot f1R/fNPPBiffiON f1'fT[ifl Pswe 2-91 M•cloocal Control IEeM Pvure 2.12•Control Head Mounting lIn4et MASTER ENCLOSURE ON ENMCU2) PNEUMATICACTUATING CYLINDER At PNMCUI Mate Enclo tow sediatenalmomang (PM PAC1001 via aingk 1,1600,1.1000or IA6W;yindw 'T*FNMt:1J2 d.o enclWaa swam nicalcontrolan .thminaingrlw need for 71re Promo Pnramaa Azinang tondo canactmle a an MCHIMrclumalCxmwd Had TUE?IWUIMaw r^art'"umodlenElOicfildesamoAnevullrTtlePACIbO Pedarmreanac4orirrmaairnamof�it,ofSlcTilydert,tall indrrd • f1(YI'�M340cTtlnd•Tp�anratdwltlldrTn'rc>pen 1heCt)2Alr,pamC42Can1Ie eSeel arc=1 11eL6000 toA0P94P70'F. aberankewrlhpreawncgaugeardan•l chador cannot be mom s-d in an ENMC U2 Maler fackarae moattltng hrocial, Sae Ptgtae 212. AK;iIYMleyIAYK:A 1 • t;tTITtM Ill a. • +7iiM n a Mt,1T!rt r • K tl•r[71Alii 1[!t7 1s li! KHrrM.rRl:GA4J[=I if In, ll►ea� lllfml saw a 14Q Maur Eardoaure - t- fart 1N M11T61 Pigure 2•Ik Prrrranatic A sualingC]llr der SLAVE ENCLOSURE(PIN ENS) The ENS Enekantr a toed tar radical mrrartngod a or*L16M (3C00M 1.46g0 e>Af<dw wh•n :uwd as a+rKwidnR cY1�1. in awymesn_Unit lti ad, thta@meaaire 11NNC:U2 W*wr A U012 NedmnhadCortrd Haider ENM[Y12 Maser E.ndoeane Sae Pigtae 240, The ENS Enaicwune hat,no cortrd Cn9osaroe mtwe!n purdrsed wpardtaIlp,and cowword w the unit,and ma•1la ward in ecu"w0on with an FKN(.'U2 Mawli PAC:100 Pritumove wlre endosmle err an MC H2 Mrdaniml Coard Hard The Low climdar cannot hr mounted in an ENS Sure Bndkretre 20t9 f1Nf: L Rer D U I.FXatd I Part a PM A N2 Y40 0 TAURAKT FIRE SUMIRES8IOM OVOT/Y Ikti•ember 1.2017 BulWn Nx AutM►ri?vd PmTex tl Restaurant Fire System Dioribulor.s From Kevin Muv%xk,Vice Pretldent.Technical In-itruct kin Sufo,ket- Stainless Steel Sc I.oso,r linkage and Fusible Linkc in the Pi,,1:x 11 Restaurant Fire Suppression System Reference. Pyro-CAittn Bulletin No, 2016122,dated May 20,2016 and No. 2017120 dated In no 5,2017 Ii, MAY 2ot6,Pyro-Chem released Bu11et in No,2016122,which offered the uw of the Slakik--Steel Sciswr Linkage and Brackets in their Fire Suppression Systems The allowanve of sci«ir linkap! provides an additional means for easier instillation of the detection line while usinga continuous run of cAk. Bulletin. No_N16122 als,t allo % for the use of St style Fu.,,IW links to be used After additional testing, a second bulletin was rcicawd In June 2017, Bulletin No.20P120,antxsuncing that the Stainless Steel Sctimir linkage could also he used in existing Pyro-Chem It"and UY'detector brackets. 'this additinnal option allows for easier rel ro-fitting ofexisting systems and easier maintenance Heiser is now pleased to announce that the Prol'ex U Re#aurant Fine Suppremion System has adopted these added options using the approved parts listed below: 435547 Sails Link Housing Dewcter Kit 10 9tsialoen Shad Scisoor Link 435546 Terminal Link housing Detour Kit w/Stainles Stord Seisaa Linkage 4390 &a ink,,SW Sdow L nk-ist In,9411 the — Nla inlr+rj titarl �{►t t 4istir I ulicege �. hetrntt+r Nruirt++nd uihnA-n Stain"tiled ki,.ur 1upsidc-AlM11l linkage ire nurkeJ a, in the hAH(4 Mown Ia nukrfe the the drtedar stu rk ing"A K7 h rirt funhem fnrnw the SIC112 f Meehan k al(milnil He;iO m NOIKr Ill STtt Fer •S4 tTt So CAN'AKnAIGUA,NF.w YORK 14424 FAX, 585-919,69,?01 tkio.78L19.s7 Tou-/'nee C)tr and t;tofohtcr.Servrre: 1.8l{1,828,938 k�l GCi�tt v t'aa,aI'MAND TAURINT 4r* Heiser FIRE SUPPRESSION f�lTFY 110163 Globe Model K 165OF Fusible Link 100"F 110212 ("ic Modti K 212"1°F-udhlc Link 150"1: 110290 Globe Model K 2WF Pu dble Link 22 S"P HOW (Ab Model K WIF=Fusible Link aril"F 110450 (:k lx Model K 4WF 1=udble Link 37ST rtt1L (Aube Model K Pus We Lin la atc0NLY4vprovW for im with the Stair&%Sted Scivor LinkAge 349H Lhtk Flouting Debedw Bnclret-10' fth*mdolf.Sted 2255H Link liuuning Detwor Kit 21061 Link I IonOng Detocbor 10t llx titainkss 5te+cl ticisurrl.inkage olicrs the folowing limitation,+when used with either deiectorhrarket upl Fun- Maximum a ofdetecl rs. 20 MAxImum lengh ofcable. 150 Maximum s of pulleys: 40 The Pyre-Chem Budetirn mWenced above are to be considered a temporary supplement to the ProTex Il 1 Tech niial Man ua)dated lkeccmbe r 1,2D I S. For further inf4v malionAnd inquiries,pleasre contact vour Sa6 Manager or Kevin Mrnwk,Vkv Prc*kki%t, Technical Fr�tncdiun at(tK10)828-Sttt}�itl or enuilus at srla�hrberusaxom_ Hie to L"1.fXai:t �g Nil aI'MANO Qrpaa 2-t'."r. FLEXIBLE CONDUIT REMOTE MI E7C HA NIC AL PULL STATION fie&tiet:mdtar,nnbetredwlththcRemreeMe3fan►atPUN (PMRPSM) S9atrcm A.wmtbir W N R PSMI afrd Mr,llanteal4;as Yal+ea Remote rmmnual omttol for the MCIU MeclwnKal R"m*wA Ifead ,!koF/Rvre2-ec RwnIPer PMI'"304 lin6tm&h"wJ1F%AlOwl,"nandRa11vaktIkwf MedhLnt\nlPullgaam.�isla�asneaedtfalie+}aenMc:1[2 tand"Fatf"Ong ile orwal tnNal6tm em Sev'I'abk 1-6 MedmrtulCc"rd ftwdcv ENWIll Moms bnduwutabT reaidvmMrdcAle 7tirarbloocvw W bn4'FMl(:LwiuA web-�wnar pulk?iorflaAk omdnw veil tfmda4n&cv waver 14M. IMvwrwr — — puhrsateachdlaliemdMeQlatt 'f'heRPSMRernwsM*.hamQl _-�I.r1 Nebkl awlwlts MI: y.-- .,�„ Ilallk•u.lu�;.,.. P.�ttrllcen firaihrs kaY.tsdatthrpalrA�eitvl.l S.r P�cPI(Ir:.� �Syy; NabkCl>•IW-wo'wd(iM. wr �tv� Nebk(:.wlwwwom$dl.r/.w.9a.kr Mq N',.NN4raIl Yl Iraq, •t raw 2-& fy}are 2-M Ilamov Mvd"n"l Il.il Swoom GAS VALVES ME[:KAN ICAL CAS VALVES A(a+Va by o,re gtn trd cm Al sTile im,a fled t o"c t a W, ford .,eiatg4"wn,vinAWPoa flow rn*laawrf®Of■y,*m acxw®on Sot ljux 2,3 A meAunruf gaa wha can be uwed l atie1•IS:Pla.tbkConduIt wiohthrMCMMehreualComolFledorI'NMCU2h4j1*t CABLE Et..fitwwv It;swnrrrctedtn*I#W.1il M&JmTrcull'Av"wi Hlad asPNMf112k owtfa&-ourebTvwankaaandcAkwfiakk Pi.'dtameerSettnklaValt;tNrmuxbeu.ed►rohaaurmra. oondnrl 111 •wlktaer�ie,edfnk'RMTf vdmtwMh.(Irrrrr dotedom and pwvohvcmW4.vme,ngwrrrgamWccatrievoat► pm"atnoL ye(1nAui1^ilhtwn b4"4*w :' =Troan.at 'N ielinlew lave!Cow 1%"fjAMd in W 2 W`,5W,dtd 10 0' each dhaip in dweoum 'nw raha ate nerd fro na od and kigitw See P*uc 1-ry and`Wbk 1-T llrbes to thei:o(rlpcmlals LP 11a(am likir 1•i) Mectionkal lw ra"are awiatit in the LwinrpaanuiT6wsonc3impw.tcipala vr.ardS)wcAA [ik++Ar�ntrwt . .. Marw+l Atirllsw - -- 11C�1 twwrs. AH 9� thwwar sl..dl 1 111w Nw. 11\- 1 NI IbNe2 7 .IL1H la fn. awu � 1\.1 �IMat 11 11�. aml stun ON%*M..Taiwan wr!IM.AIi.G.. thbv and.amTn/irmq"arn `� labk 2 f*'ure3,lf Glk f*vtv 1-Ii-tow Strw5 Mac hnmc416al rahti 200 f1w 1_Rev 11 V1.P.X4S2b Pars a Ph1AN3 (Butte 2 c'.�vft PJ.21I:TRIC119012 1130 GAS VALM Sartcb lit WN MSI)PDTL Tbrtc swish Ka PIN MSIPUT2,4nd AChasWvowrrgtd•dsmAll"rrsapedrap"4p 44,sus Four SwrldhK .PINM54PPT2 Eachaw,d°bpsasetofanghe fudedcoakmgapplbnxiofAcppraflnwnlieewmafslrem P'ig.doA -4hnwrcnnq&b"w4ar2l+rmp,IHK121k,15Q277 ad®`on See f*wre 2-U A UL 1.64tdelecirk gas why can VAC tw 1 HP.250.277 VA(' M~ ,ig hardware and 12'ware bit wwd wtli die Mf H2 MrckfrwW1CrnarcA Has!cw F2'II,Ot:IP2 areenliesAm prandedwilhaidh kA See hgwras 2.14and 2.24b Murex Hndwore'llk rages at raad fur narUnl And L Pga: YalvaarearalAkn110VA' fkdricp%valwsa, aradablein the fr&awinRviarrc,par'l-Ak 2-'° pgwre 244 Ekafkal lOomch NOTE I°elgwre 2-21 Ekaric fSdeicrdlGaaValve 0 xda4cRiahpannadii9i�rlai !w mode at<:dethw A4C:H2 Mrdh.niailCoatrolHaadartbe ENAlC:U2MaraPrwkwre A viK:r am]waxer%shall etatllveow9fal head lirawolie L„rzie•aa carithr ridavf liebouE AlekcriaioonnreFcna mumbemade in an grsawdeleancalboa .ar PO �w 4Pk sFbi Tibia 2-0 p l; asw . • NOTE c A Ul,1,4ua4 manwrl raw rely it rvgwhrd when ping an t6evic ps wake Rest RAV(PIN&ZI may be used for b purpawe See pear 121. IgwreA214 E1r AialCemwsion RESET RELAY(PIN 035) Pkc Ic gaarake wvteig Eir#aAioelr ape prorded n ibe ALARM 1 NnUTI NG SW ITCH (PIN S?0077) inrYiketmovabndll&mr>MIl UoFi prr2.23 The Alarm inlam"Swbchipm 4ia"714inbefild•mnmltrd within lie MC MnhaaicalCwwd Headce the ENW.U2 Maas r Endwo m 71w aw ak h an be Dead to dcse a sWervi aid cttvait to the bu/dirp main fire rl nin panel"tarn Ile WWI kve ENMf U2 a males.lllis a�lioa wihi aipsil lke/re alarm pand ` IWOlbene vat awrtan actodwo nlhe knd►enarm The wAkh +., knxin ,ins ail newourymgrtairigenrt"Aratsh"-RhA moan`rrwnwam shut`llw m&h is mud 3amA.2si V, Sea ptgare 2-24c. FWve 241 ResA Refar ELECTR[CAL SWITCHES e s 11w Electncal Swndua Are imerded for war wob elactric xrlw*.alarm►.<mwarkics,10 irwcmorm%*wMAOdd"Ric pawa thus-idderiata And atwehacirimlderkatbatawe ftwe2-31r AlwrnI m ONO u%Swikh deagnedto Amcdfar turn ar when tbeaptan aaduawd Swatcbm aft Available in knit One SwachKa.P!N)&SPCYT2 Tim JOM IWI L Re+11 Ul.EX4411 A FW"a PlI A w c ulpow 1 t;owl ww vmm PIPE AND FITTINGS RUBBER NOZZLE BLOW-OFF CAPS Pete and fatawfitumbefumbslsedbydtrbswtier.ieleddtc40 (PINSM016) mumks ded.dams pYdd.m Nre4 ppe and fatlttp moss be Th IWbber Mat*INnw-ctlf Qp(P)N S100161 lwlirt kdolt tk wdCralaaalsd*0604 fttbvan ago ria,.ml aatlictaftbenosaieivedgaeaaecaatksrsobtdon4vs6.ta<wid tserltsie ttdAa�all dts�tbottrn►A •IaIlArptsrapaNackeaite N0/1I I-A bkm-affear10 the nook Ile�aNatollepksw-c$Cirp.(p�N Ncrosks i dvv been de►doped fcx aponncc pkmn_and duce �o0ldt sne sad to pots al ll See Pt arc 2 3t, tprba iwm A aml o tavvs%w tFK flan ptArn raise and ate sappiad>r A mtxd!narde Eiann-adlcapa 4 Pf N?OS•2os11!to "w"Ick EacAttmAtaatampedwilltbemodt•lnumber Saal*rea2.31aaA'PaW2-ll Applkalimshmmatirntare I*MN2.32Atd*rr Blow 0(fc4p pwovi ed m the demp ua iw adtto manta! Wul nunke Nbst off amp iNN J4 4DWIcanbe purckmsW eparaleiraadam ... SWIVEL ADAPTER(PIN 423572) In pa kwcdl4 - t1w"%wndAdtpotr(PAWWDmw.cda�Irstst.++rnel 1cd/.snd atriaalbrtl A�atetlaCans-pktard Ilte StaheE rldalaaa elk»a the am*obe noted dppaalmm4*rJO`mall bkearcm,c ,w Wad• u P4.01. Sea Pf#wv 2-a tr tttnl� t r Nvd► , a1R411dFA MIAM t"I c 4(1 t�M�t+Ww11t �l1AitV Pili RltlMi iC ll li � lir d IL 40O � we+Etta stun �u snafus �G. �towams I'iKsae I3S Swirtl Adsplrr NOZZLE AIMING DEVICE(PIN 551265) Tls NtmAt Aimug tltrrtx(PIN 5$kWf i ampm ed in Para jamcwh nook to 6tawrattatmtn`room,The dericecknpato QenooieardertnMra arnr YserlepMtkalrefttctronthrsntita 1717 6d iliadamirldl Tkvnamektdnikan batsadW opaila d A praddammed aanttg"sand iben i%howd to b4A Out a q*. Tfieaim igde"mrapirsanadarta(PJN21092e1oaNadtw v1w In tlw t wAr 'f le ddap t vsw l bd ardaeed rrlsrsldr%to F*v" Fisav3-31' Ntmk* 2"34. NOTE �. P>'oTeill Naml4asre mY,rid adtown omeadtlba ward ` IVY I(r F qwt Z34 Moak Aiming Mrix IIIIX�UI 14 Rev it) C1Nwi VAIAX)t clt►,�r3-�7'�Ucsaga CHAPTER III SYSTEM DESIGN GENERAL 0"rigW Alietipkcated0.6°into*it du:topenin&and TNPrct'lirtllly[ ttrit11 5u{gstw sn icmmaykviiwdm aimeddirectirumothedua See f*,arce3.1. a mmlber of dtfieaettt tnva of remmura rn oAAft applunoesund hood and duct comfigurao ms.'rfm deagninform:miam Wood in tha kaai€ro dvOS WO the umicAkas a nd r4ramas's of Ih°prc, rngmand,l..xm 'I'ta.te rrdartdtuk res+puntbk L,r tfre deagln of the Nci lF t I I%Taem m tm tw I w rued a rod hold a as rent I It t.•r RIiC:LLl:tkt73fwa1¢in a I'roI'as I I Arantin pdytr.rfit a"t n 'ITaN+e+:t am>.Al tare the p r-.Ta FAX)CUE?Lt desKn of tAi Prc�l'ee I I \1T Rt sit tua to hm suigavt+a n SrAwn It a d n-sded arlo kru r(a 1 s•r an"W21 c seslioru .C1q inch r Sd rp .Noxadc(:overage and Pk emerl as w w Piping I.nnmalicau .I?+errasr Rttltta�nraula m�s t I1.ahadiheww tionsnmatx txmijMly tmdct m..,lbesa. at1m(Ainiii;any imalbliou NEU rc 3 1 SYSTEM CYLINDER SIZING oNt:r•Low uuc:'r iwmc'ritm want ft.NcrME Path ofthe rimiks m the sti 4kn"Norsk Caverage and IIhM NLill 11acemwm'has Ax own flk w pc•m1 valw each of the knar difacm .ltirrdeftt:m supportjmairmumnuri6eradfiow"to..buwd ThcILNonk4NNNI.IL11%a one 111 flow naakA*119k11. on she mkmaeofilmpipeusedSdeallrenswmclhraderfsPEq raarrdeNcapaNeafptokctarKatllalteOrreAanguludtatYAwish e4kA46%Ow"A numbw ad fknrp.dma N rviued wirA Plan a malimum pertiraamw ad30"Walmium sglr of 16►i.nflA ON •ppWiscoy(tl.pknum..mddtwtiphslAelcal piping tv&ane diigurulhcmgam.nimomof1XV hwnAsoproleaarourd ductNrlha TrammnmdiaTelerof 16",See Ptgwcs 3•i&3.3. NOZZLECOVERAGE AND PLACEMENT 1fih xa>oticaa will pranidrt fiuidrliraax ferdaarninaagncr�sk Iffi4. 1ype.pcdNkaur#,and quan1hy fen dual.plcauni,and apphance pror oc U on tiuc'r P1tlYt'6t:noN 11 ix not ragtrnrd that Iho fail be xibtm dow m•ae e.thauA duct bredoarred fur lhcsymarn4iiopmakprcgrerlr_Each noakif mane1-1AbxirnrannunplarduApenmdeof3 .approved to",:i e<lwsi dugs cd u rh m med kng/a Al dud ptosedion is UL bated wAod 11miuvom admaairnum dual kngih 4rmkmiled kr>plth}.This includes A rarkties cd aka i m-aks bola hauom al aid rwr%;A t m kacA tilt disc at Our au n at t 6 angles to Ow homoMal and dm-gswgh dtnxtkowl bench tiara protwlkm regrtirea that a ncmmk bx p marikmod to disdFw%o moo she do t'No trades at aralakk fca dutl prateaion I*stm 3--k Maximum qlti ndriml dud etstmaw of W 'nw no AeOl corm kriosmatlad m Ihega.mum*arrmrrofihrdws. 1GL9=L`DC,L Pier Lt till FA 3d1 13 Part+NklkNJ �:•er J•Symm N SW FWt)HAM PUCT PRtYCecrION WITH ID NlYME CRANSII'ION DUCCS•SMALL VIA)LARGER Tsar 11)drgt oozrla d 1'+N N1.1DIis a Iwo 421 flow noaAe.A siing+le 11) In 4*0"her. cpeadmg is.1vulkw than rnazsle is cc mbk of pn-Qctir j nMuDgtiv dmb with a maximum the final eahaum duct,measure the penrnc*wdiametcr of IN grid perimeter cd W',rash The diagonal l+eag a nmitimmn 417W,le exhaust duos.The noa'M4 u to be lapsed wilnin 0'-4"cd the&W 4an alarm moms a T4'wlrrd dwi"ilh a ma timum dnanidlw of RV fikmum a»faae,4ealtarod in the coin .See Figvae 34. Wlxn Two 411 NL2DD dote nomles are rimed to proleol a is a dm-C .v+we 1tY.ircnN gllkwulim.dlhe duct mim b.dn ukd tM11 IWI9kpUI Is '[U rL=k mtwl Tlren l,e ins lliA in The cemternf The area it pn:aectsand aimedamdyimIN dmiopernu* TRANSI'CION DUCI•S Ism plow li-411 of i o*'dkfp ON rutharn03+rrwgiw�L.i►_wn Iiru,ru�n.luci.stwndJbepnxeceed as follldynws frlgurc 3 5-`Prwts9lioan LxLi-3maker to urger MULTIPLE RISERS In q*m e4MA plc A indiwidrml ducT-See Ngurc 3.i .,t,w rrurwi +�ww MS9 1 � Ll lJLC1 figure 3-4c`I'rarteiiiom Lkid Larpr Tn Smaller I 1 'CRANSI'CION DUCI'S-L%itcFRTOSMALLFR PO IN+u Insaaesrwhero Thed,t4tlplentlrnira���+erdrngirlarr�rThar! The final edhatnt dummamuz the peru ewelirmder of Ile duos 1 tt1>x 3 fc J4LuWpk Rises halfway between The latgcd and srnallat mom¢or IN aw ige ELECTRfOM ATIC PRF:CIInCTATOR lveritiletw,d�rmetaa}.'1'hv mmlleiawbe k-poqgd woW W r 6"41flhe duccTlenum interlace Onaa al The pokm rhQe The meamutmem way 11ucls utilizes electrostatic pracipatamrs must be pmwdad lakeml,cenkmd ender lne final CAh]UA duct gMATIK Sae 1*11x aborc and below The unit Standard duel noulm are used m this 3.4 rpplwalkar Soo Iiip m 1.7 NILY F E >JJ W I2I E N-_vsleswpa W1dumwith4Irnsit*MOutism.nVthan4 in Night.will be regrured to be pcaan„ne<i in The opening cd INgrarlmtiomfn-mi the hood2'toS'iT*D the gmmngusing mm4ird dr►:t n k dw.ggn paaremat PI klirF it]NG\1212 \\ I*UFV-3.7-Ii We 066 15oe4**W 2ll l3.11IV,L kew D U L FA4Q 1 1 I Pail-a PMA M i <L4rea I sy.eren Ikvw, P1.9m UM PKIT WITION Clan V bank pianans,6c nonWO mina be kaaamd at the canter of the V bed wndlb.K d the rdmxat ltt*t c f the!lien On TV* tN mo*(PIN KI,Ml a ore(11 fbm twAomood kw knot(aortankpWmmtitte not At nnwltm kuetrd t'( mOw fieemanproteatton.AytngieINnomkcanprouctaflnum(wek badedgeodthe(Awc4sdawnfromOwww cakhtiSaFweshm regk of V tank ibenf IQ'5mg br 4'wide f*nclrngtlar kng4h ap*diwo,tlw nmik mut be located wttbtn V of tht and of the moireltmeegwllnakrrs that, to'snkengttrandpA*Luirga prMorokomodmk(rude.meddiwilldmm low ker%lhCON nook oinbadooetoproidkosm plenum-11mnotAtsmTpoertl noM)mmtdtneettomjmkaVah flearane the camimpksumaneaup"dcted.dad the nolornratnori nrn ee.;ardrd Saw Fv".I•• w 1,2 w v i T I M Wk IT r.�r• gPd >s tlMt a PTO% tM1tM1Aa to"jai MANNINO �R¢t tti 1r•�AN( IIIlI��1 SINGLE BWK _ aemm u001ttMC Figaal# PkeumProtasan APPLIANCE PROTECTION �,i ► 11 When pnxmcting o fglnnarowWdh are Ia"then sretrgk nonkwvvn e.mdttpk MwAoaanbe wed. I,arprr epplianao wn be di+ided smo w"rd modals►tar h egad b ON rt>&I that 0000 Untie**map Qaoepaaom Fmn m m rot aceeda maiwmtam aftirl a4 n. Far tfndnkraeegfr�era. Aiw to'Pemaing IseV Files le►thvidingThate Aeea Iona Aindtrlft:Page U 200-D : L Rev It U L Ex4 t21 16 Ike n A I'M A Ti' L,1► *1f3 .Svs*em I3ewn Cksign Index Chart and Nuzzk: Coverage Summary Shot lets Meg Am ma. Max Nasihc Nouk Noaete Iuw 1"4b Lemglr Am HNIr1 Ik/KV1 Apet owr ,tlamml It— 7}rs PdW Me Wklt 010 0k7 4w Mao 061 4W Ity.ac wwx[INV R)wd H }'3 NLZi 2 ty% IV 24 41 Hym wlwe INV hard L 14 NUI 2 Iy h 19 13 N Imm w!11oWo RWaad H 3-1 N 12H 2 Day%I v% 324 A 48 QCoadd-1) (NcwUCnukmVArm 18 snn 24 48 Rye w IxT Ikhyrd H 3 9 N 1-11-1 2 Ikea Sag N�i n I Al 491 (t-..JAO"m21 43rmltCuukryAma 25.% 443 24 44 *LT es W+r[Is q Rwrd L 311 NL2L 2 Dav VaI Is 324 13 N Oca.d.buw III chmOOR40%Arqw v% inn 14 34 l.yc^wI wr lb).x,l 1. 3=5 NI21 !. 1we WR 19!h .37I 1..1 A 1Cuadn l*21 OvgmIlC'*1kayl Arrim % 4)1 1.1 2.1 7&skiibdMtm"P6m H 3.7 N11H 2 27M son 24 48 Tkk*k .Albr.a.m"l'am 11 1-0 'WjI1 2 2714 IN 11 .1-1 Sratl Brrye H 3.9 NUN t 12 28 336 40 50 I-F peaF AVA 3113 N1aL 2 29 m 144 34 4H S MB llaagb wWrRech" L Ili NU I. 1 L2 28 336 13 34 NAM W 'mma$CImw n•�Ihr�k4uo H a 114 MW 11 2 12 ,91 lift1 15 Pam.w1m S"wok H 3-12 NllH 1 IN Dotxux 6 A 48 ti"d4 V" 11 3-11 1j U I, 1 m Dww,nn►1is 0 1 1 24 Loge Wak H 3.14 NL2H 2 30 Dimmmraw Max 8 24 48 kww vA,k I. + li an„1, 2 D..kvw,,a.x H 11 :.1 s mum calkia. H 3•16 N11H 1 36 L08d 24 48 5au11tlyddie L. 3317a W,11. 1 36 1040 10 24 Samsco.I& L Il7h XUL 2 36 land L3 24 LargeGmWMly 14 3.18 ti12H 2 A 14.10 24 44 Lmge c"Hlc 1. 3-L9 M.N. 2 48 L440 In 24 Rama Char=Il.rrlln 11 113) VIM 1 25 624 Ai 44 BdmsChar-louder L 3.21 NU 1 26 624 13 24 tr* Law&dbam Char, li J- NI-111 2 3s 464 )6 43 Laago16rd1aac Chat-llnalas L 3.23 NI21. 2 36 864 13 36 LOM Rink Chor 14,1lrr 11 3• l HI.21. 2 26 624 -11 35 I.An 16rck(haw.lku4t L 3.23 NIA, 2 26 624 0 24 5u11.31udc_A.w Hots 11 JIM Nil 11 1 .1 4:I0 24 jrj (mare,tic!dcydo 6'I SolalFwdCbm bmtw L 3.27 NLLL t 24 480 1s 24 id4sL rlarlkWka VA 3 30a N1174 1 JL IakS 16 14 Ujxv'jh1.5daau4d. 1Rudw VA 3.306 M AL 1 36 28 Bus Edge IIcwwy IM..y FAY"Mow&A "LA 3A V-11] 2+2 5m5pe ui Isiccua c +N I.2F W-ay N-sty Ftym Dvd LIB VA 3.32 NL2H :+2 SerSl+ccWal lyd wwwma .N1a Nefldjdrm.mum MPH VA 3.33 NI.21. 2 9mimd lm9omLarra WA Qmil A 06t'1 NwV11aldmmvmove IV�A 1134 Nun 2 sg*spas41adgwou r Ekanc buAm w.k ea0o13m "empvsleBaWtc+ XIA 3 3i NU 2*2-1 5tc5p'Nwj IImnw%'wK 13 35 wih 5maka Dos ChmrBm4d(hWa&IC:h.mImI )1rA 3.31 NLIL L A htme Edge 1" i' ahuve the chain i%mww 4a.ylr Hmmk;V I►.+k H Nll li I fl 120 rl-f'in. _j4 liravm Not Mum Dkamem �k f*-4%myJa0 w;yI4T U4c# Imw IUQ 3t 4 Nxi mgutwommme Iba N11 L 1 17 S0 w 200-PLC L,Rev 11 llI,FX4 W1 t7 Nila Phi AN2 Fryer% With Drip 11(mrd (Nigh Niuunt Nozzle) CmmpdrlrTNom* XUR Plots Parrs herNmeir 14711m) M6rfiedNim*sRmumed 1Opel A4amlm Alec al prolrcwn hedp VM Co*b*Mies 37a sgmre rldlas wtfl a maitmum stlie danen iml od ieadds dslp bmrdl O.adl Cm*irg Arm cdM" indwa deft bmidl Glasiilise l Ckqp Val Co*kgArles 171 stun&mclwsvo&amaunumkmom ldedomemcmof194' feaddal drip timsdl (rrrdl CAat Arm 4"tsgare Indus w*b a mmzmwn kopm wile demisnamod Iir" on ." a drV beesdl Wok I.aawn A"WhM VWI .eirsad wuiaea Neuls 1+ I4'•4V Ams Ow h sird w rism Not*Aiftrg Aimedallowom soflhrhsrredaarfs4 r 1 Muzzle►nut!8114w aced wipivi m II &M Ow ahoW ow Ir111loMat d Aw cowrolaW lwwed su►furr j sw Is ALL OY!ALA 1 COGUM•ar I. C9MMMi iru IIiN�r�10)1 N�Illh e1MIrM1ta®1` /N(NM „y« N�sYirlll „ti• - � // L1AI;MIM 1 , 1 1 1 1 t -•sue- � j - ! I Ile v11 u l 1 Lel ytlu um 1 N'ill♦ I tvt7M Ia Irk ����t, � 1<fngNi lNUlM/uu _ LtMIQ111 u/1T 7 �M nr.u�.ipa) UN1lh�a0lV IatfVAfi rlt►r UT) •, Ysl/ IsallYiW 2 Pile 5-&Pryen wtl!VM Bmtd 4Ho Mom NcwW 200 W l PAY 1) UI.EX41i 1 3o Nei 8 PMAM ru"a s s"am flesw Sm&B Range with or without Ii wkshelf Protection (I ow Mount Nozzle) NOTE OmnrAwrrNot* Ntit Plow Pcdm1 Pair NLuric I ooel fire.rye hmu w Aww dmp, Nun6a of Nae*e R"utred 1 One) JAW.mW'*kaa Matmam Alva efP"eew,n 1.16 square maw$Wia4Impel odedlmeierceiat26, lobe 0"W loot Iwo" Notate Walloon 11`fMmlheayfaawwtd#tdibebi asdvadaceandamleredy*Wic JAW Ae1&0 latl Oje they,v NcvaM ►{ 1 1)° '1i'�rnv IM h tr 1 ni >� Av kY►4r Ait"IM unr Neade Ammlrg Amiadala pomlogw1snamballcidw mwller hw0A4"d0w oyl JAW r W* applreK a and AmS ibe rtN ie fl c amali ne Ar ydmr fmmpk, fj Aw mak swr marwrd 1-r oboov dv howM rw*4 rAr wwu►t;ps,WI mwAd ke 114'f—JAW°1P1P-Aoq**4f#M oppliarrm aw u+Mich Ae rrak to Arosiel Sae AW smomos t'uarIt I wW @aan*1 iWA '' Graphic Rapvowwwnn 5w Parel-H Nat zk awe hr lanes(h rtoew{tiirJ anywhere wethn Al%r eharted arm, - #04IowMddWNIkft-rfjkC~NOW&&DWAebwwnt►0r uw Boole`I VAN •fit ;r -11;, ; at r+s sa rile h ham[ almcda 'feom AAAGM , •! 4C+a4 ddlpr d AND lramrclrka iEaAldlffa "' NrrQM iali' oll �) got" a abeime alrlace .rut � metiYdllK" ;,�r� �— aen lvmr a( lrzardd snriuce 'Zi��! 1 � Aprel It%mrl Name {taw Main!Neairl 100 111X-'•C Nee 11 1i 1,NX4 U 1 lA Pd rl m PM A M l:YK�r r J ��f►era SmaI GrWdk (Low Mount Nozzle) VbmpAwsTNoede NLII.orNLlL Floor Pearma Per Ncade I N1nel N LLL or 2 Owl WIL NambaciNcEdrs Pagmwrd I KMeINLLL cc 1 40m1NUL My mmmAraaalPrc4ecion Wo qua"Ind* waabm:01We4hmmm ofje Noah lacown NLIL Attmvanr owner d de beard smdwe NL21.-Or-Ch ms lrwc46v 4v44& drlubrasrdrmrilar Kroda HOOO NLIL Io'-Ws"Ibbaledwrila NUI.-U, •IT abaw 64b1sad amllare NcodrAamirs KLII:Aid"Il2'insndll'cmorkewllwq:n rrbsiaw600006 KUL AN ilr am•,ddw bags rdamifrw Ura}inc Ildporeamirfan So Pigvm I-rh&3-17b MUL AWrde a> a.larattddfi�ldJr.6aMr ah�mmw of N!r fwsard smrJaar a arr.d it NrI Ml11MrtM�1 12"j•am each sidref&r deNm frill w Mb mask NLX wr::k mlui belarattd r•d*fhamr eths of d wafbohf sida qfdr Tram rd surf ur aaef alrhred of Nr rrnarr rI�14 baaand srrrJmr r � NOMICAP la0 VqU uu IN OIDMTtb teak Awawl ul N861 M 171 ilI11 1.(KI�iV(4 ANA NB IAOUHTIP Al" in 1 1 1 f 1 1 1 1 1 1 1: 1 it "law I.it • MUM F�mr+e3 17Y NLeL Nasde Fgae M7b NUL Noada lob -Mc LIlerA UI.Px4VI IS Per+aPirlAw �y��•��m Items Larne Radiant/Elect rk Char-Bw ikr O f i gh ,\count Nuzzle) 4k,-miAIA,TNolzk NL-1H Flaw Pe"s PerNrutzt Z¢'hwi1 Nunka of Noaties R"wed I one) MatiummAneaodPmocuoa dtl spurt orchswvibaknigestm&dtmen%mn-.4 Nock lio-moon ,4box anycornerofIN htmtdaurim Nca* Ilc-%N W•dW 3,o►c the hasard wurfaoe NCMAe AaTmng Atmed al the QWItr ad IN twotla <.;raphk kopte-ensaton Sot Pip rts-12 No=lr tntrsf be ludaOrd direrrtly abu ue duty corner of fheha.-anf surface, dud aitrad at lhecenfer dVI&harasld surfs w. i �-� N(1TI1 Ff.AN!E Mon 4TILDA MI ANY CON" � 1 � t Lam Eff S ae.\ `�er#SauAFIE DIM EM MM I M Ifs C4KIN W46 AMA I=�ttre 3•Z2 I�rgt Had►tm!FEbcalclTar 16n�ier SIl trh M.muat NcQ�dcl 2415.11UC Rev n UL VX4Qt 40 NosPMAM cZyrrr 1-3+radem Iki:� PIPING LIMITATIONS Omit this ix**Cnqma"d<ttafa*faf.;j*n4W$h*becn GEN1%RAI.PIPING REQUIREMENTS dckrmtm&it ismcoes wy4odetermine tic Mrlf[ocatfiguratlons between dbecyimders and dwnaalmTlisse.tm cont ainsOR s .1.)O aTOL.dwtruthipq�r�ar<Eti�lharcrNaf,.■ri guiddmraandhmAdianxlkrtck *JIM ,IheJMnlwAkmPq■ingw I.IeU�?.i.1400andL•Ib?:)+r torn. tMl the eslurtu►40fktukv fit NIaJ1*durpfnunIN.Mvder,aa •L 1AWO.riumsmu.tu.<�#npipi Sig.vir.with no proler%mrate I'hc bnuudumnnivlj6Lbercfermdoowhen romtielamtedbefore tie%T4n,artdwithamatirnumofld �Sdkc jtig the mmutting I%rati%rm irar Ow q#inArrx Iktw pt*Mit pvf side !4`minimttart Wfig,ntuoft by d0ad lathe f3rstVail The niallTrmm pre kngdhsarebased ori internal pgv%-Atmte. 3 M4A Sim 1"10Imm0fof!4-ppab01Na¢n anorA1; F*h AXIS criindei i*ask'•wrt)a fnimimtma sand masimmm%oral and the pwodug din is 410 mk volumeofpgung,cAmliatal inmitimem d Masirnum(knrnumbvr.(of Wpga @.b TOwiv i%no mod to df>,%isiA Nirmomii what partiom dlke py,, 3, Maxanum Mrntbcr ofebaws beIweem a rrootie and Is i1appaT11M and whit porliam is brnrtch lint Onlfdhe said the pm mAf%tee is a vontimeofth<.xnopklepgnngnelmvih.satolse:on%idered 6, )bum!runol13c1bomaiea low edinIhebda9 Ilind'"li a T. Mamm um difieamcc in ek-"dim betwatn the Volume Chart cl#rrderotalA arrdav nc Ag i+14' W pipe-:t7aSm6d(t .l No trams ore Actwod m the pgmtg rtetwotk %"p ie-37.5 mis)k % Pipe Iergths are met armed frorn cenlar to oerwer oaf •PVC=ins misfll. (mine Fox mace Pipe�oiume 3tlr,sae pas: 10. 'Ilk- iinanal ecprr@akM krtgAr rabtrrr►e of fnbrty,. does nal hne to be oansackmd as pi it of the Idyl pip< Aperil Diskibueiom f(ote=dOOmDhose ralumv CYLINDCRCH.4RT 11. When tailinng eb 'excnlsueepipein the gAem,the 1a.fr s1 ww must s1W t fvA:md tA:add rexi it pipe mu.1 MMMMn it approahea ttav nm*' MaMbMM s>! Abwdsdwen 12. L'Jltcnt�sl 9a'swind adapdrs It.�olaxl ad the rtataies A" %Wert@ iGd Mzdma Lad C}Wdrstr. Mwhd. trndf*ftn.t Mum*}nrw.,i do no hary so by eols mod in the S vkcnr maximirm 3 ,6 GdAbm 1 ■Wan ft4f rdamsement Litt 13 RWwd%t%S4isng;arvab.+wd Own aduci%to a i.a cNhw p rdna m r srruller pg+e>�e 4WO s+damn tw y.t.o ioM 1.1. Addoxusd p,pir%requm:nw m.„W n vf.s..11114 1 t46W ra rtge.Neat.or a fryer e44k20r 4 s10109 moo I.1ty70• httmm%rmof1l9m1andon<01fkn. 1+6aa ��crm■ ro aas iartA'id* namibcr>.te�rnd in t<rpil�aair%Cl(that � minimum,NOml and out WfbwrnumbeTsmusl LAG 0.od➢Alb■ in ice. V.V.1Wr be at alhcl at Cif b+fane the rl rlxl•.NCaa.Orff'(vr t.Aom • L IWO- himmttsm of 100 ml add lour 01 fkmv `AMritfrriscbdWM nuakd@nl@,nrd seiicltd■d td tltr number regrdrod in tool qwm CN that minimum,1M m1 and Iwo Of flow nundters musl by sA ii tad at or bvfmv At rargv,waft.o r f rya • (.•Ie�O•Minimumoft660mlandlmiplli.»@ Mirad may H P t tt 4taarat Mxx seas numbers recpd rod In tuul sTstem Od%tat Rtcr cs,IL%atri&A nn WOC minimum.M m1 and two Rd(krw mt rdv rs nnrst Cyitdr bvaeiitedatorbticiteOw rarge.woit.orfirm M* tow*ant Am a.9@Ew offbwc* I.6000•Minimum 4960 ad and foa nwootl•N Laeluo A"d-■Amn ■sumi-■ilbwn fkrw numbers ryuned in Vital symew exthal 10200 yaa d-431a.140 sypRtl-s 15"PIN mrrartmn,130 ml and i flow nurdstrs must be L40oo 660we-pro@.fit a■sett-t a."►.■ attilaeded at or bek-uv the ta%cwol%.or frier. t.evw 9400111_y Lamm sr na 411-2 Am rM :t7Ct•IIUC•L ker1? VL HUM 1 NwisP UM. r OFFICE COPY • Hydraulic Calculations CITY OF ARLINGTON FOR: BUILDING DEPARTMENT APPROVED Holman Recovery Center DATE_q/&JO�� BY 16400 Smokey Point BLVD L d &__0 Marysville,WA NO CHANGES AUTHORI?En UNLESS APPROVED BY BUILDING INSPF,--- Main Floor Dining Room (NFPA 13) Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13 Density: 0.10 GPM per SF Area of application: 1,176 SF(quick response heads) Coverage of sprinklers: 172.6 SF Number of sprinklers calculated: (8)Heads Total Sprinkler Demand at Source: (including Hose) 249.2 GPM @ 36.9 PSI Flow&Pressure Available at Source: 249.2 GPM @ 50.6 PSI Sprinkler make& model: Viking model VK302 Quick Response,Recessed Sprinkler Thread: '/2"NPT Sprinkler "K" Factor: 5.6 Design Layout: D.F. Date: August 19,2020 WASHINGTON STATE CERTIFICATE OFCOWETENCV PIRE PROTECTION SPRINKLER SYAT j Khosrow(David)Farahanl 1 1 7325-0195-C Level Nor-Tech Fire Protection,Inc. NORTEFPO 6 � 1 b � i xp` rgnutum 12l31/20 ; �..........a...........r�..../ w M7fu►g3Q Wit" I CI3VOFlg9A SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMzN\HLMN-DNG.SDF JOB TITLE: Holman Recovery Center Dining Room Light Hazard CPVC WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS . PRESS . Q PRESS . ® DEMAND PRESS . MTAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2555 . 0 50 . 6 249 . 2 36 . 9 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 249 . 2 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 149 . 2 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 11 . 0 K= 5 . 60 10 . 3 18 . 0 2 11 . 0 K= 5 . 60 11 . 1 18 . 7 3 11 . 0 K= 5 . 60 10 . 8 18 .4 4 11 . 0 K= 5 . 60 11 . 5 19 . 0 5 11 . 0 K= 5 . 60 13 .4 20 . 5 6 11 . 0 K= 5 . 60 9 .4 17 .2 7 11 . 0 K= 5 . 60 10 . 1 17 . 8 8 11 . 0 K= 5 . 60 12 .4 19 . 7 9 11 . 0 - - - - 15 . 7 - - - 10 11 . 0 - - - - 16 .2 - - - 11 11 . 0 - - - - 16 . 5 - - - 12 11 . 0 - - - - 14 . 9 - - - 13 11 . 0 - - - - 15 . 9 - - - 14 11 . 0 - - - - 15 . 7 - - - 15 11 . 0 - - - - 16 . 3 - - - Ml 11 . 0 - - - - 17 . 0 - - - M2 11 . 0 - - - - 17 . 1 - - - M3 11 . 0 - - - - 17 .4 - - - M4 11 . 0 - - - - 23 . 7 - - - FDM 11 . 0 - - - - 24 . 8 - - - TOR 11 . 0 - - - - 27 . 2 - - - WHD 2 . 0 - - - - 32 . 3 - - - DHD 2 . 0 - - - - 32 . 3 - - - BFO 2 . 0 - - - - 32 . 3 - - - BFI 2 . 0 - - - - 36 . 3 - - - BOR 1 . 0 - - - - 36 . 9 - - - UGE -3 . 0 - - - - 38 . 6 - - - CC 1 . 0 SOURCE 36 . 9 149 . 2 - . � ° � | | | U Y | � - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMkN\HLMN-DNG.SDF JOB TITLE: Holman Recovery Center Dining Room Light Hazard CPVC PIPE DATA PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe : 1 -18 . 0 1 . 101 PL 14 . 00 PF 0 . 8 1 11 . 0 5 . 6 10 . 3 18 . 0 6 . 1 150 FTG - - - - PE 0 . 0 2 11 . 0 5 . 6 11 . 1 18 . 7 0 . 056 TL 14 . 00 PV 0 .2 Pipe: 2 -36 . 7 1 . 101 PL 11 . 80 PF 4 . 5 2 11 . 0 5 . 6 11 . 1 18 . 7 12 .4 150 FTG 2E PE 0 . 0 9 11 . 0 0 . 0 15 . 7 0 . 0 0 . 209 TL 21 . 80 PV 1 . 0 Pipe : 3 -36 . 7 1 . 394 PL 8 . 29 PF 0 . 5 9 11 . 0 0 . 0 15 . 7 0 . 0 7 . 7 150 FTG - - - PE 0 . 0 10 11 . 0 0 . 0 16 .2 0 . 0 0 . 066 TL 8 . 29 PV 0 .4 Pipe: 4 -36 . 7 1 . 598 PL 9 . 71 PF 0 . 3 10 11 . 0 0 . 0 16 .2 0 . 0 5 . 9 150 FTG - - - - PE 0 . 0 11 11 . 0 0 . 0 16 . 5 0 . 0 0 . 034 TL 9 . 71 PV 0 .2 Pipe : 5 -36 . 7 1 . 598 PL 6 . 88 PF 0 . 5 11 11 . 0 0 . 0 16 . 5 0 . 0 5 . 9 150 FTG T PE 0 . 0 Ml 11 . 0 0 . 0 17 . 0 0 . 0 0 . 034 TL 14 . 88 PV 0 .2 Pipe: 6 -18 .4 1 . 101 PL 12 . 05 PF 0 . 7 3 11 . 0 5 . 6 10 . 8 18 .4 6 .2 150 FTG ---- PE 0 . 0 4 11 . 0 5 . 6 11 . 5 19 . 0 0 . 058 TL 12 . 05 PV 0 .3 Pipe : 7 -37 .4 1 . 101 PL 9 . 00 PF 1 . 9 4 11 . 0 5 . 6 11 . 5 19 . 0 12 . 6 150 FTG ---- PE 0 . 0 5 11 . 0 5 . 6 13 .4 20 . 5 0 . 216 TL 9 . 00 PV 1 . 1 Pipe: 8 -57 . 9 1 . 394 PL 9 . 62 PF 1 . 5 5 11 . 0 5 . 6 13 .4 20 . 5 12 .2 150 FTG ---- PE 0 . 0 12 11 . 0 0 . 0 14 . 9 0 . 0 0 . 154 TL 9 . 62 PV 1 . 0 Pipe: 9 -57 . 9 1 . 598 PL 12 . 00 PF 0 . 9 12 11 . 0 0 . 0 14 . 9 0 . 0 9 . 3 150 FTG ---- PE 0 . 0 13 11 . 0 0 . 0 15 . 9 0 . 0 0 . 079 TL 12 . 00 PV 0 . 6 Pipe : 10 -57 . 9 1 . 598 PL 7 . 58 PF 1 .2 13 11 . 0 0 . 0 15 . 9 0 . 0 9 . 3 150 FTG T PE 0 . 0 M2 11 . 0 0 . 0 17 . 1 0 . 0 0 . 079 TL 15 . 58 PV 0 . 6 Pipe : 11 -17 .2 1 . 101 PL 12 . 04 PF 0 . 6 6 11 . 0 5 . 6 9 . 4 17 .2 5 . 8 150 FTG ---- PE 0 . 0 7 11 . 0 5 . 6 10 . 1 17 . 8 0 . 051 TL 12 . 04 PV 0 .2 Pipe: 12 -35 . 0 1 . 101 PL 12 . 08 PF 2 . 3 7 11 . 0 5 . 6 10 . 1 17 . 8 11 . 8 150 FTG - -- - PE 0 . 0 8 11 . 0 5 . 6 12 .4 19 . 7 0 . 191 TL 12 . 08 PV 0 . 9 Pipe : 13 -54 . 6 1 . 394 PL 12 .25 PF 3 .4 8 11 . 0 5 . 6 12 .4 19 . 7 11 . 5 150 FTG 2E PE 0 . 0 14 11 . 0 0 . 0 15 . 7 0 . 0 0 . 138 TL 24 . 25 PV 0 . 9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-DNG.SDF JOB TITLE: Holman Recovery Center Dining Room Light Hazard CPVC PIPE DATA (cont . ) PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 14 -54 . 6 1 . 598 PL 8 . 83 PF 0 . 6 14 11 . 0 0 . 0 15 . 7 0 . 0 8 . 7 150 FTG ---- PE 0 . 0 15 11 . 0 0 . 0 16 . 3 0 . 0 0 . 071 TL 8 . 83 PV 0 . 5 Pipe: 15 -54 . 6 1 . 598 PL 6 .42 PF 1 . 0 15 11 . 0 0 . 0 16 . 3 0 . 0 8 . 7 150 FTG T PE 0 . 0 M3 11 . 0 0 . 0 17 .4 0 . 0 0 . 071 TL 14 .42 PV 0 . 5 Pipe: 16 -36 . 7 2 . 423 PL 11 . 00 PF 0 . 0 M1 11 . 0 0 . 0 17 . 0 0 . 0 2 . 6 150 FTG - - - - PE 0 . 0 M2 11 . 0 0 . 0 17 . 1 0 . 0 0 . 004 TL 11 . 00 PV 0 . 0 Pipe: 17 -94 . 5 2 .423 PL 11 . 00 PF 0 . 3 M2 11 . 0 0 . 0 17 . 1 0 . 0 6 . 6 150 FTG -- - - PE 0 . 0 M3 11 . 0 0 . 0 17 .4 0 . 0 0 . 026 TL 11 . 00 PV 0 . 3 Pipe : 18 -149 .2 2 . 003 PL 41 . 58 PF 6 . 3 M3 11 . 0 0 . 0 17 .4 0 . 0 15 .2 150 FTG - - - - PE 0 . 0 M4 11 . 0 0 . 0 23 . 7 0 . 0 0 . 152 TL 41 . 58 PV 1 . 6 Pipe: 19 -149 .2 2 .423 PL 6 .42 PF 1 . 1 M4 11 . 0 0 . 0 23 . 7 0 . 0 10 .4 150 FTG T PE 0 . 0 FDM 11 . 0 0 . 0 24 . 8 0 . 0 0 . 060 TL 18 .42 PV 0 . 7 Pipe: 20 -149 . 2 2 . 423 PL 16 . 33 PF 2 .4 FDM 11 . 0 0 . 0 24 . 8 0 . 0 10 .4 150 FTG 2E PE 0 . 0 TOR 11 . 0 0 . 0 27 . 2 0 . 0 0 . 060 TL 40 .33 PV 0 . 7 Pipe: 21 -149 .2 2 .423 PL 7 . 00 PF 1 .2 TOR 11 . 0 0 . 0 27 .2 0 . 0 10 .4 150 FTG TG PE 3 . 9 WHD 2 . 0 0 . 0 32 . 3 0 . 0 0 . 060 TL 20 . 00 PV 0 . 7 Pipe: 22 -149 . 2 4 . 310 PL 2 . 00 PF 0 . 0 WHD 2 . 0 0 . 0 32 . 3 0 . 0 3 .3 120 FTG - - - - PE 0 . 0 DHD 2 . 0 0 . 0 32 . 3 0 . 0 0 . 005 TL 2 . 00 PV 0 . 1 Pipe: 23 -149 .2 4 . 310 PL 0 . 50 PF 0 . 0 DHD 2 . 0 0 . 0 32 . 3 0 . 0 3 . 3 120 FTG - - - - PE 0 . 0 BFO 2 . 0 0 . 0 32 . 3 0 . 0 0 . 005 TL 0 . 50 PV 0 . 1 Pipe: 24 FIXED PRESSURE LOSS DEVICE BFI 2 . 0 0 . 0 36 . 3 0 . 0 4 . 0 psi, 149 .2 gpm BFO 2 . 0 0 . 0 32 . 3 0 . 0 Pipe: 25 -149 .2 4 . 220 PL 2 . 00 PF 0 . 1 BFI 2 . 0 0 . 0 36 . 3 0 . 0 3 .4 140 FTG E PE 0 .4 BOR 1 . 0 0 . 0 36 . 9 0 . 0 0 . 005 TL 20 . 00 PV 0 . 1 Pipe: 26 -149 .2 6 . 280 PL 4 . 00 PF 0 . 0 BOR 1 . 0 0 . 0 36 . 9 0 . 0 1 . 5 140 FTG E PE 1 . 7 UGE -3 . 0 0 . 0 38 . 6 0 . 0 0 . 001 TL 28 . 00 PV 0 . 0 t SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-DNG.SDF JOB TITLE: Holman Recovery Center Dining Room Light Hazard CPVC PIPE DATA (cont . ) PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 27 -149 .2 6 .280 PL 45 . 00 PF 0 . 1 UGE -3 . 0 0 . 0 38 . 6 0 . 0 1 . 5 140 FTG T PE -1 . 7 CC 1 . 0 SRCE 36 . 9 (N/A) 0 . 001 TL 97 . 00 PV 0 . 0 NOTES : (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc . 4792 LaVista Road Tucker, GA 30084 (2) The system has been balanced to provide an average imbalance at each node of 0 . 003 gpm and a maximum imbalance at any node of 0 . 075 gpm. (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 15 .2 ft/sec at pipe 18 . (4) PIPE FITTINGS TABLE Pipe Table Name : CUSTOM. PIP PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 .220 18 . 00 36 . 00 11 . 00 39 . 00 22 . 00 4 . 00 36 . 00 6 .280 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T R C B G A D Ell Tee T-RUN 1 . 101 5 . 00 5 . 00 1 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 394 6 . 00 6 . 00 1 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 598 7 . 00 8 . 00 1 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 003 9 . 00 10 . 00 1 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 .423 12 . 00 12 . 00 2 . 00 19 . 00 10 . 00 1 . 00 18 . 00 13 . 00 PAGE: H MATERIAL: Bullms HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-DNG.SDF - JOB TITLE: Holman Recovery Center Dining Room Light Hazard CPVC 4 . 310 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 I I - � SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-DNG.SDF JOB TITLE: Holman Recovery Center Dining Room Light Hazard CPVC WATER SUPPLY CURVE 60+ 55+ 50+0\ 45+ \ \ \ P 40+ \ R \ E X \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi ® 2555 gpm Flow Test Point 15+ 10+ LEGEND " X = Required Water Supply " 36 . 94 psi Q 249 . 2 gpm " 5+ " 0 = Available Water Supply " 50 . 58 psi Q 249 .2 gpm " 0++-+---+----+-----+------+--------+--------+---------+-----------+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) v J o Hydraulic Calculations FOR: Holman Recovery Center 16400 Smokey Point BLVD Marysville, WA Main Floor East Wing(NFPA 13) Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13 Density: 0.10 GPM or per MFG listing Area of application: 998 SF(quick response heads) Coverage of sprinklers: 178.5 SF (17.85 GPM per head) Number of sprinklers calculated: (9)Heads Total Sprinkler Demand at Source: (including Hose) 268.6 GPM @ 44.5 PSI Flow&Pressure Available at Source: 268.6 GPM @ 50.5 PSI Sprinkler make& model: Viking model VK302 1 Quick Response,Recessed Sprinkler Thread: '/2"NPT Sprinkler "K" Factor: 5.6 Design Layout: D.F. Date: August 20,2020 WASHINGTON STATE a 1 CERTIFICATE OF COWETMOV a _ I FIRE PROTECTION SPREIKLER SYST Khosrow(David)Farahanl N 7325-0195-C Level Nor-Tech Fire Protection,Inc. NOR'IEFPO 6 I I � slynYtrr• 1 1170 F � 7r� � - Y _ � `^ SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 Date: 08/21/2020 C: \HASS64\DATA2020\HOLMAN\EAST-13 .SDF JOB TITLE: Holman Recovery CTR Main Floor East per NFPA 13 WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'p NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2555 . 0 50 . 5 268 . 6 44 . 5 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 268 . 6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 168 . 6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 11 . 0 K= 5 .60 10 . 6 18 .2 2 11 . 0 K= 5 . 60 10 . 6 18 .2 3 11 . 0 K= 5 . 60 11 . 7 19 . 2 4 11 . 0 K= 5 . 60 10 .2 17 . 8 5 11 . 0 K= 5 . 60 10 . 5 18 . 1 6 11 . 0 K= 5 . 60 10 . 2 17 . 8 7 11 . 0 K= 5 . 60 10 . 5 18 . 1 8 11 . 0 K= 5 . 60 13 . 5 20 . 6 9 11 . 0 K= 5 . 60 13 . 2 20 . 3 A 11 . 0 - - - - 11 . 5 - - - B 11 . 0 - - - - 13 . 0 - - - C 11 . 0 - - - - 14 . 3 - - - D 11 . 0 - - - - 21 . 0 - - C9 11 . 0 - - - - 23 .2 - - - Ml 11 . 0 - - - - 25 .4 - - - M2 11 . 0 - - - - 26 .2 - - - M3 11 . 0 - - - - 27 . 0 - - M4 11 . 0 - - - - 30 . 2 - - - FDM 11 . 0 - - - - 31 . 6 - - - TOR 11 . 0 - - - - 34 . 6 - - - WHD 2 . 0 - - - - 39 . 8 - - - DHD 2 . 0 -- - - - 39 . 8 - - - BFO 2 . 0 - - - - 39 . 8 - - - BFI 2 . 0 - - - - 43 . 8 - - - BOR 1 . 0 - - - - 44 .4 - - - UGE --3 . 0 - - - - 46 . 1 - - - 'CC 1 . 0 SOURCE 44 . 5 168 . 6 A I SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: 08/21/2020 C: \HASS64\DATA2020\HOLMAN\EAST-13 .SDF JOB TITLE: Holman Recovery CTR Main Floor East per NFPA 13 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 1 -18 .2 1 . 101 PL 11 . 25 PF 0 . 9 1 11 . 0 5 . 6 10 . 6 18 .2 6 . 1 150 FTG T PE 0 . 0 A 11 . 0 0 . 0 11 . 5 0 . 0 0 . 057 TL 16 . 25 PV 0 . 3 Pipe : 2 -18 . 2 1 . 101 PL 11 .25 PF 0 . 9 2 11 . 0 5 . 6 10 . 6 18 .2 6 . 1 150 FTG T PE 0 . 0 A 11 . 0 0 . 0 11 . 5 0 . 0 0 . 057 TL 16 .25 PV 0 . 3 Pipe: 3 -36 . 5 1 . 101 PL 1 . 00 PF 0 . 2 A 11 . 0 0 . 0 11 . 5 0 . 0 12 . 3 150 FTG - - - - PE 0 . 0 3 11 . 0 5 . 6 11 . 7 19 .2 0 .207 TL 1 . 00 PV 1 . 0 Pipe: 4 -55 . 6 1 . 394 PL 8 . 83 PF 1 . 3 3 11 . 0 5 . 6 11 . 7 19 .2 11 . 7 150 FTG - - - - PE 0 . 0 B 11 . 0 0 . 0 13 . 0 0 . 0 0 . 143 TL 8 . 83 PV 0 . 9 Pipe: 5 -17 . 8 1 . 101 PL 6 . 00 PF 0 . 3 4 11 . 0 5 . 6 10 .2 17 . 8 6 . 0 150 FTG - - - PE 0 . 0 5 11 . 0 5 . 6 10 . 5 18 . 1 0 . 055 TL 6 . 00 PV 0 . 2 Pipe : 6 -36 . 0 1 . 101 PL 7 .42 PF 2 . 5 5 11 . 0 5 . 6 10 . 5 18 . 1 12 . 1 150 FTG T PE 0 . 0 B 11 . 0 0 . 0 13 . 0 0 . 0 0 .202 TL 12 .42 PV 1 . 0 Pipe: 7 -17 . 8 1 . 101 PL 6 . 00 PF 0 . 3 6 11 . 0 5 . 6 10 . 2 17 . 8 6 . 0 150 FTG PE 0 . 0 7 11 . 0 5 . 6 10 . 5 .18 . 1 0 . 055 TL 6 . 00 PV 0 .2 Pipe: 8 -36 . 0 1 . 101 PL 7 . 42 PF 2 . 5 7 11 . 0 5 . 6 10 . 5 18 . 1 12 . 1 150 FTG T PE 0 . 0 B 11 . 0 0 . 0 13 . 0 0 . 0 0 .202 TL 12 . 42 PV 1 . 0 Pipe: 9 -127 . 6 2 . 003 PL 4 . 54 PF 0 . 5 B 11 . 0 0 . 0 13 . 0 0 . 0 13 . 0 150 FTG ---- PE 0 . 0 8 11 . 0 5 . 6 13 . 5 20 . 6 0 . 114 TL 4 . 54 PV 1 . 1 Pipe : 10 -148 .2 2 . 003 PL 5 .29 PF 0 . 8 8 11 . 0 5 . 6 13 . 5 20 . 6 15 . 1 150 FTG - - - - PE 0 . 0 C 11 . 0 0 . 0 14 . 3 0 . 0 0 . 150 TL 5 .29 PV 1 . 5 Pipe: 11 -20 . 3 1 . 101 PL 11 . 25 PF 1 . 1 9 11 . 0 5 . 6 13 . 2 20 . 3 6 . 8 150 FTG T PE 0 . 0 C 11 . 0 0 . 0 14 . 3 0 . 0 0 . 070 TL 16 .25 PV 0 . 3 Pipe: 12 -168 . 5 2 . 003 PL 35 .42 PF 6 . 7 C 11 . 0 0 . 0 14 . 3 0 . 0 17 . 2 150 FTG ---- PE 0 . 0 D 11 . 0 0 . 0 21 . 0 0 . 0 0 . 190 TL 35 .42 PV 2 . 0 Pipe : 13 -168 . 5 2 .423 PL 29 . 21 PF 2 . 2 D 11 . 0 0 . 0 21 . 0 0 . 0 11 . 7 150 FTG ---- PE 0 . 0 C9 11 . 0 0 . 0 23 .2 0 . 0 0 . 075 TL 29 . 21 PV 0 . 9 v SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 08/21/2020 C: \HASS64\DATA2020\HOLMAN\EAST-13 .SDF JOB TITLE: Holman Recovery CTR Main Floor East per NFPA 13 PIPE DATA (cont . ) PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 14 -168 . 5 2 .423 PL 28 .42 PF 2 . 1 C9 11 . 0 0 . 0 23 . 2 0 . 0 11 . 7 150 FTG ---- PE 0 . 0 M1 11 . 0 0 . 0 25 . 4 0 . 0 0 . 075 TL 28 .42 PV 0 . 9 Pipe: 15 -168 . 5 2 .423 PL 11 . 00 PF 0 . 8 M1 11 . 0 0 . 0 25 .4 0 . 0 11 . 7 150 FTG ---- PE 0 . 0 M2 11 . 0 0 . 0 26 .2 0 . 0 0 . 075 TL 11 . 00 PV 0 . 9 Pipe: 16 -168 . 5 2 .423 PL 11 . 00 PF 0 . 8 M2 11 . 0 0 . 0 26 . 2 0 . 0 11 . 7 150 FTG ---- PE 0 . 0 M3 11 . 0 0 . 0 27 . 0 0 . 0 0 . 075 TL 11 . 00 PV 0 . 9 Pipe: 17 -168 . 5 2 .423 PL 41 . 58 PF 3 . 1 M3 11 . 0 0 . 0 27 . 0 0 . 0 11 . 7 150 FTG ---- PE 0 . 0 M4 11 . 0 0 . 0 30 . 2 0 . 0 0 . 075 TL 41 . 58 PV 0 . 9 Pipe: 18 -168 . 5 2 .423 PL 6 .42 PF 1 .4 M4 11 . 0 0 . 0 30 . 2 0 . 0 11 . 7 150 FTG T PE 0 . 0 FDM 11 . 0 0 . 0 31 . 6 0 . 0 0 . 075 TL 18 .42 PV 0 . 9 Pipe: 19 -168 . 5 2 .423 PL 16 . 33 PF 3 . 0 FDM 11 . 0 0 . 0 31 . 6 0 . 0 11 . 7 150 FTG 2E PE 0 . 0 TOR 11 . 0 0 . 0 34 . 6 0 . 0 0 . 075 TL 40 . 33 PV 0 . 9 Pipe: 20 -168 . 5 2 . 705 PL 7 . 00 PF 1 . 3 TOR 11 . 0 0 . 0 34 . 6 0 . 0 9 .4 120 FTG TG PE 3 . 9 WHD 2 . 0 0 . 0 39 . 8 0 . 0 0 . 067 TL 20 . 00 PV 0 . 6 Pipe: 21 -168 . 5 4 . 310 PL 2 . 00 PF 0 . 0 WHD 2 . 0 0 . 0 39 . 8 0 . 0 3 . 7 120 FTG ---- PE 0 . 0 DHD 2 . 0 0 . 0 39 . 8 0 . 0 0 . 007 TL 2 . 00 PV 0 . 1 Pipe: 22 -168 . 5 4 . 310 PL 0 . 50 PF 0 . 0 DHD 2 . 0 0 . 0 39 . 8 0 . 0 3 . 7 120 FTG ---- PE 0 . 0 BFO 2 . 0 0 . 0 39 . 8 0 . 0 0 . 007 TL 0 . 50 PV 0 . 1 Pipe: 23 FIXED PRESSURE LOSS DEVICE BFI 2 . 0 0 . 0 43 . 8 0 . 0 4 . 0 psi, 168 . 5 gpm BFO 2 . 0 0 . 0 39 . 8 0 . 0 Pipe: 24 -168 . 5 4 .220 PL 2 . 00 PF 0 . 1 BFI 2 . 0 0 . 0 43 . 8 0 . 0 3 . 9 140 FTG E PE 0 .4 BOR 1 . 0 0 . 0 44 .4 0 . 0 0 . 006 TL 20 . 00 PV 0 . 1 Pipe: 25 -168 . 5 6 . 280 PL 4 . 00 PF 0 . 0 ,BOR 1 . 0 0 . 0 44 . 4 0 . 0 1 . 7 140 FTG E PE 1 . 7 UGE -3 . 0 0 . 0 46 . 1 0 . 0 0 . 001 TL 28 . 00 PV 0 . 0 Pipe: 26 -168 . 6 6 . 280 PL 45 . 00 PF 0 . 1 UGE -3 . 0 0 . 0 46 . 1 0 . 0 1 . 7 140 FTG T PE -1 . 7 CC 1 . 0 SRCE 44 . 5 (N/A) 0 . 001 TL 97 . 00 PV 0 . 0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/21/2020 C: \HASS64\DATA2020\HOLMAN\EAST-13 .SDF JOB TITLE: Holman Recovery CTR Main Floor East per NFPA 13 NOTES : 4 (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc . 4792 LaVista Road Tucker, GA 30084 (2) The system has been balanced to provide an average imbalance at each node of 0 . 006 gpm and a maximum imbalance at any node of 0 . 156 gpm. (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 17 .2 ft/sec at pipe 12 . (4) PIPE FITTINGS TABLE Pipe Table Name: CUSTOM.PIP PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 .220 18 . 00 36 . 00 11. 00 39 . 00 22 . 00 4 . 00 36 . 00 6 .280 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T R C B G A D Ell Tee T-RUN 1 . 101 5 . 00 5 . 00 1 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 394 6 . 00 6 . 00 1 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 003 9 . 00 10 . 00 1 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 .423 12 . 00 12 . 00 2 . 00 19 . 00 10 . 00 1 . 00 18 . 00 13 . 00 PAGE: H MATERIAL: Bullms HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 2 . 705 6 . 00 12 . 00 6 . 00 19 . 00 10 . 00 1 . 00 14 . 00 4 . 00 4 .310 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 i SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 08/21/2020 C: \HASS64\DATA2020\HOLMAN\EAST-13 .SDF JOB TITLE: Holman Recovery CTR Main Floor East per NFPA 13 WATER SUPPLY CURVE 60+ 55+ 50+0\ \ \ \ 45+X \ \ \ P 40+ \ R \ E \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi Q 2555 gpm Flow Test Point 15+ 10+ LEGEND " X = Required Water Supply 44 .49 psi Q 268 . 6 gpm " 5+ " 0 = Available Water Supply " 50 . 52 psi ® 268 . 6 gpm " 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) �J i Hydraulic Calculations FOR: Holman Recovery Center 16400 Smokey Point BLVD Marysville,WA Main Floor SW Corner (NFPA 13) Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13 Density: 0.10 GPM per SF Area of application: 968 SF(quick response heads) Coverage of sprinklers: 98.0 SF Number of sprinklers calculated: (12)Heads Total Sprinkler Demand at Source: (including Hose) 293.6 GPM @ 42.0 PSI l Flow&Pressure Available at Source: 293.6 GPM @ 50.4 PSI Sprinkler make& model: Viking model VK302 Quick Response,Recessed Sprinkler Thread: 1/2"NPT Sprinkler "K" Factor: 5.6 Design Layout: D.F. Date: August 19,2020 WASHIN®TON STATE I CERTIFICATE OF COMPETENCY FIRE ■ PROTECTION SPRM M"SrST! j Khosrow(David)Farahanl j 1 7325.0195-C Level Nor-Tech Fire Protection,Inc. t ■ NORTEFPOas t I t ■ i �• N►*o a I sgn.twr 12/31/20 1 I R r' ' SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-SW.SDF JOB TITLE: Holman Recovery CTR - SW Corner NFPA13 Light Hazard WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAII4. TOTAL REQ'D NODE PRESS . PRESS . Q PRESS . Q DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2555 . 0 50 .4 293 . 6 41 . 9 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 293 . 6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 193 . 6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 11 . 0 K= 5 . 6'0 7 . 0 14 . 8 2 11 . 0 K= 5 . 60 7 . 3 15 . 2 3 11 . 0 K= 5 . 60 8 . 6 16 .4 4 11 . 0 K= 5 . 60 9 .2 17 . 0 5 11 . 0 K= 5 . 60 7 . 5 15 . 3 6 11 . 0 K= 5 . 60 7 . 8 15 . 7 7 11 . 0 K= 5 . 60 9 . 1 16 . 9 8 11 . 0 K= 5 . 60 8 . 1 15 . 9 9 11 . 0 K= 5 . 60 8 . 6 16 .4 10 11 . 0 K= 5 . 60 10 .4 18 . 1 11 11 . 0 K= 5 . 60 8 . 0 15 . 8 12 11 . 0 K= 5 . 60 8 .4 16 . 3 M4 11 . 0 - - - - 25 . 8 - - - M5 11 . 0 - - - - 10 . 5 - - - M6 11 . 0 - - - - 11 . 3 - - - FDM 11 . 0 - - - - 27 . 6 - - - TOR 11 . 0 - - - - 31 . 6 - - - WHD 2 . 0 - - - - 37 .2 - - - DHD 2 . 0 - - - - 37 .2 - - - BFO 2 . 0 - - - - 37 .2 - - - BFI 2 . 0 - - - - 41 .2 - - - BOR 1 . 0 - - - - 41 . 8 - - - UGE -3 . 0 - - - - 43 . 5 - - - CC 1 . 0 SOURCE 41 . 9 193 . 6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-SW.SDF -f JOB TITLE: Holman Recovery CTR - SW Corner NFPA13 Light Hazard PIPE DATA PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 1 -14 . 8 1 . 101 PL 8 . 75 PF 0 . 3 1 11 . 0 5 . 6 7 . 0 14 . 8 5 . 0 150 FTG - - - - PE 0 . 0 2 11 . 0 5 . 6 7 . 3 15 .2 0 . 039 TL 8 . 75 PV 0 .2 Pipe: 2 -30 . 0 1 . 101 PL 8 .42 PF 1 . 2 2 11 . 0 5 . 6 7 . 3 15 .2 10 . 1 150 FTG ---- PE 0 . 0 3 11 . 0 5 . 6 8 . 6 16 .4 0 . 144 TL 8 .42 PV 0 . 7 Pipe: 3 -46 .4 1 . 394 PL 6 . 00 PF 0 . 6 3 11 . 0 5 . 6 8 . 6 16 .4 9 . 7 150 FTG ---- PE 0 . 0 4 11 . 0 5 . 6 9 . 2 17 . 0 0 . 102 TL 6 . 00 PV 0 . 6 Pipe: 4 -63 . 3 1 . 394 PL 1 . 33 PF 1 . 3 4 11 . 0 5 . 6 9 . 2 17 . 0 13 . 3 150 FTG T PE 0 . 0 M5 11 . 0 0 . 0 10 . 5 0 . 0 0 . 182 TL 7 . 33 PV 1 .2 Pipe: 5 -15 . 3 1 . 101 PL 7 . 75 PF 0 . 3 5 11 . 0 5 . 6 7 . 5 15 . 3 5 .2 150 FTG ---- PE 0 . 0 6 11 . 0 5 . 6 7 . 8 15 . 7 0 . 042 TL 7 . 75 PV 0 .2 Pipe: 6 -31 . 0 1 . 101 PL 8 . 33 PF 1 . 3 6 11 . 0 5 . 6 7 . 8 15 . 7 10 .4 150 FTG - - - - PE 0 . 0 7 11 . 0 5 . 6 9 . 1 16 . 9 0 . 153 TL 8 . 33 PV 0 . 7 Pipe : 7 -47 . 9 1 . 394 PL 7 . 00 PF 1 .4 7 11 . 0 5 . 6 9 . 1 16 . 9 10 . 1 150 FTG T PE 0 . 0 M5 11 . 0 0 . 0 10 . 5 0 . 0 0 . 108 TL 13 . 00 PV 0 . 7 Pipe: 8 -111 . 2 2 . 003 PL 8 . 83 PF 0 . 8 M5 11 . 0 0 . 0 10 . 5 0 . 0 11 . 3 150 FTG - - - - PE 0 . 0 M6 11 . 0 0 . 0 11 . 3 0 . 0 0 . 088 TL 8 . 83 PV 0 . 9 Pipe: 9 -15 . 9 1 . 101 PL 12 . 25 PF 0 . 5 8 11 . 0 5 . 6 8 . 1 15 . 9 5 .4 150 FTG - - - - PE 0 . 0 9 11 . 0 5 . 6 8 . 6 16 .4 0 . 044 TL 12 . 25 PV 0 .2 Pipe: 10 -32 . 3 1 . 101 PL 10 . 92 PF 1 . 8 9 11 . 0 5 . 6 8 . 6 16 .4 10 . 9 150 FTG ---- PE 0 . 0 10 11 . 0 5 . 6 10 .4 18 . 1 0 . 165 TL 10 . 92 PV 0 . 8 Pipe: 11 -50 .4 1 . 394 PL 1 . 33 PF 0 . 9 10 11 . 0 5 . 6 10 .4 18 . 1 10 . 6 150 FTG T PE 0 . 0 M6 11 . 0 0 . 0 11 . 3 0 . 0 0 . 119 TL 7 . 33 PV 0 . 8 Pipe: 12 -15 . 8 1 . 101 PL 10 . 75 PF 0 . 5 11 11 . 0 5 . 6 8 . 0 15 . 8 5 . 3 150 FTG -- -- PE 0 . 0 12 11 . 0 5 . 6 8 .4 16 . 3 0 . 044 TL 10 . 75 PV 0 .2 Pipe: 13 -32 . 1 1 . 101 PL 12 . 33 PF 2 . 8 12 11 . 0 5 . 6 8 .4 16 . 3 10 . 8 150 FTG T PE 0 . 0 M6 11 . 0 0 . 0 11 . 3 0 . 0 0 . 163 TL 17 . 33 PV 0 . 8 !k SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date : 08/20/2020 C: \HASS64\DATA2020\HOLM�kN\HLMN-SW.SDF JOB TITLE: Holman Recovery CTR - SW Corner NFPA13 Light Hazard PIPE DATA (cont . ) -PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 14 -193 . 7 2 . 003 PL 49 . 16 PF 14 . 6 M6 11 . 0 0 . 0 11 . 3 0 . 0 19 . 7 150 FTG T PE 0 . 0 M4 11 . 0 0 . 0 25 . 8 0 . 0 0 . 246 TL 59 . 16 PV 2 . 6 Pipe: 15 -193 . 7 2 .423 PL 6 .42 PF 1 . 8 M4 11 . 0 0 . 0 25 . 8 0 . 0 13 . 5 150 FTG T PE 0 . 0 FDM 11 . 0 0 . 0 27 . 6 0 . 0 0 . 097 TL 18 .42 PV 1 . 2 Pipe : 16 -193 . 7 2 .423 PL 16 . 33 PF 3 . 9 FDM 11 . 0 0 . 0 27 . 6 0 . 0 13 . 5 150 FTG 2E PE 0 . 0 TOR 11 . 0 0 . 0 31 . 6 0 . 0 0 . 097 TL 40 . 33 PV 1 .2 Pipe: 17 -193 . 7 2 . 705 PL 7 . 00 PF 1 . 7 TOR 11 . 0 0 . 0 31 . 6 0 . 0 10 . 8 120 FTG TG PE 3 . 9 WHD 2 . 0 0 . 0 37 .2 0 . 0 0 . 086 TL 20 . 00 PV 0 . 8 Pipe: 18 -193 . 7 4 . 310 PL 2 . 00 PF 0 . 0 WHD 2 . 0 0 . 0 37 .2 0 . 0 4 . 3 120 FTG - - - - PE 0 . 0 DHD 2 . 0 0 . 0 37 .2 0 . 0 0 . 009 TL 2 . 00 PV 0 . 1 Pipe: 19 -193 . 7 4 . 310 PL 0 . 50 PF 0 . 0 DHD 2 . 0 0 . 0 37 .2 0 . 0 4 . 3 120 FTG ---- PE 0 . 0 BFO 2 . 0 0 . 0 37 .2 0 . 0 0 . 009 TL 0 . 50 PV 0 . 1 Pipe : 20 FIXED PRESSURE LOSS DEVICE BFI 2 . 0 0 . 0 41 .2 0 . 0 4 . 0 psi, 193 . 7 gpm BFO 2 . 0 0 . 0 37 .2 0 . 0 Pipe: 21 -193 . 7 4 .220 PL 2 . 00 PF 0 . 1 BFI 2 . 0 0 . 0 41 .2 0 . 0 4 .4 140 FTG E PE 0 .4 BOR 1 . 0 0 . 0 41 . 8 0 . 0 0 . 007 TL 20 . 00 PV 0 . 1 Pipe: 22 -193 . 7 6 . 280 PL 4 . 00 PF 0 . 0 BOR 1 . 0 0 . 0 41 . 8 0 . 0 2 . 0 140 FTG E PE 1 . 7 UGE -3 . 0 0 . 0 43 . 5 0 . 0 0 . 001 TL 28 . 00 PV 0 . 0 Pipe: 23 -193 . 6 6 .280 PL 45 . 00 PF 0 . 1 UGE -3 . 0 0 . 0 43 . 5 0 . 0 2 . 0 140 FTG T PE -1 . 7 CC 1 . 0 SRCE 41 . 9 (N/A) 0 . 001 TL 97 . 00 PV 0 . 0 NOTES : (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc . 4792 LaVista Road Tucker, GA 30084 (2) The system has been balanced to provide an average imbalance at each node of 0 . 004 gpm and a maximum imbalance at any node of 0 . 093 gpm. Y SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-SW.SDF JOB TITLE: Holman Recovery CTR - SW Corner NFPA13 Light Hazard (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 19 . 7 ft/sec at pipe 14 . (4) PIPE FITTINGS TABLE Pipe Table Name: CUSTOM.PIP PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 .220 18 . 00 36 . 00 11 . 00 39 . 00 22 . 00 4 . 00 36 . 00 6 . 280 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T R C B G A D Ell Tee T-RUN 1 . 101 5 . 00 5 . 00 1 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 394 6 . 00 6 . 00 1 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 003 9 . 00 10 . 00 1 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 .423 12 . 00 12 . 00 2 . 00 19 . 00 10 . 00 1 . 00 18 . 00 13 . 00 PAGE: H MATERIAL: Bullms HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 2 . 705 6 . 00 12 . 00 6 . 00 19 . 00 10 . 00 1 . 00 14 . 00 4 . 00 4 .310 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 r, SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-SW.SDF f JOB TITLE: Holman Recovery CTR - SW Corner NFPA13 Light Hazard WATER SUPPLY CURVE 60+ 55+ 50+0\ \ \ \ 45+ \ \ X \ P 40+ \ R \ E \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi Q 2555 gpm Flow Test Point 15+ 10+ LEGEND " X = Required Water Supply " 41 . 92 psi Q 293 . 6 gpm " 5+ " 0 = Available Water Supply " 50 .43 psi @ 293 . 6 gpm " 0++-+---+----+-----+- - - -- -+- - - - -- - -+- - - -- ---+- - - - - - - - -+- - - - - - - - - - -+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) Y Hydraulic Calculations FOR: Holman Recovery Center 16400 Smokey Point BLVD Marysville,WA Attic North Wing Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13 Density: Per MFG listing Area of application: 7 heads per MFG Coverage of sprinklers: 260 SF per head Number of sprinklers calculated: (7)Heads Total Sprinkler Demand @ Source: (including hose) 286.4 GPM @ 45.0 PSI Flow&Pressure Available at Source: 286.4 GPM @ 50.4 PSI ,I Sprinkler make&model: Viking model V-BB l Viking Attic Heads Sprinkler Thread: '/a"NPT Sprinkler "K" Factor: 5.6 Design Layout: D.F. Dale: August 19,2020 MIASHINOTON'STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION arRWNLER SrST" Khosrow(David)Farahanl 1 7325-0195-C Level Nor-Tech Fire Protection,Inc. NORTEFP 8 1 � j Otpina � U slEnatw■ 1Z/31120 ; R r• i v i r � r ., I _ � • _ __ SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 --, Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-N.SDF JOB TITLE: Holman Recovery Attic North Win (Dry System) north wing WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2525 . 0 50 .4 286 .4 45 . 0 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 286 .4 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 186 .4 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 15 17 . 0 K= 5 . 60r' 18 .4 24 . 0 16 17 . 0 K= 5 . 60/ 19 . 7 24 . 8 17 17 . 0 K= 5 . 604, 21 . 0 25 . 6 18 17 . 0 K= 5 . 600 22 . 3 26 .4 19 17 . 0 K= 5 . 60d`' 24 . 6 27 . 8 20 17 . 0 K= 5 . 60e 25 . 7 28 .4 21 17 . 0 K= 5 . 60 -1' 27 . 3 29 . 3 J2 17 . 0 - - - - 30 .4 - - - FDM 17 . 0 - - - - 33 . 0 - - - TDR 17 . 0 - - - - 33 . 3 - - - DPV 5 . 0 - - - - 38 . 6 - - - DHD 2 . 0 - - - - 40 . 2 - - - BFO 2 . 0 - - - -- 40 . 3 - - - BFI 2 . 0 - - - - 44 . 3 - - - BOR 1 . 0 - - - - 44 . 7 - - - UGE 0 . 0 - - - - 45 . 3 - - - CC 1 . 0 SOURCE 45 . 0 186 .4 R SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-N.SDF JOB TITLE: Holman Recovery Attic North Win (Dry System) north wing PIPE DATA ,,PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 1 -24 . 0 1 . 083 PL 5 . 92 PF 1 . 3 15 17 . 0 5 . 6 18 .4 24 . 0 8 .4 100 FTG - - - - PE 0 . 0 16 17 . 0 5 . 6 19 . 7 24 . 8 0 . 219 TL 5 . 92 PV 0 . 5 Pipe: 2 -48 . 8 1 .418 PL 5 . 92 PF 1 .3 16 17 . 0 5 . 6 19 . 7 24 . 8 9 . 9 100 FTG - - - - PE 0 . 0 17 17 . 0 5 . 6 21 . 0 25 . 6 0 . 219 TL 5 . 92 PV 0 . 7 Pipe: 3 -74 . 5 1 . 654 PL 5 . 92 PF 1 . 3 17 17 . 0 5 . 6 21 . 0 25 . 6 11 . 1 100 FTG ---- PE 0 . 0 18 17 . 0 5 . 6 22 . 3 26 .4 0 .226 TL 5 . 92 PV 0 . 8 Pipe: 4 -100 . 9 1 . 654 PL 5 . 92 PF 2 . 3 18 17 . 0 5 . 6 22 . 3 26 .4 15 . 1 100 FTG ---- PE 0 . 0 19 17 . 0 5 . 6 24 . 6 27 . 8 0 . 396 TL 5 . 92 PV 1 . 5 Pipe: 5 -128 . 7 2 . 123 PL 5 . 92 PF 1 . 1 19 17 . 0 5 . 6 24 . 6 27 . 8 11 . 7 100 FTG - - -- PE 0 . 0 20 17 . 0 5 . 6 25 . 7 28 .4 0 . 184 TL 5 . 92 PV 0 . 9 Pipe: 6 -157 . 1 2 . 123 PL 5 . 92 PF 1 . 6 20 17 . 0 5 . 6 25 . 7 28 .4 14 .2 100 FTG PE 0 . 0 21 17 . 0 5 . 6 27 .3 29 . 3 0 . 267 TL 5 . 92 PV 1 .4 Pipe: 7 -186 .4 2 . 705 PL 15 . 92 PF 3 . 1 21 17 . 0 5 . 6 27 . 3 29 . 3 10 .4 100 FTG T PE 0 . 0 J2 17 . 0 0 . 0 30 .4 0 . 0 0 . 112 TL 27 . 92 PV 0 . 7 Pipe: 9 -186 . 4 3 . 334 PL 48 . 50 PF 2 . 6 J2 17 . 0 0 . 0 30 .4 0 . 0 6 . 8 100 FTG T PE 0 . 0 FDM 17 . 0 0 . 0 33 . 0 0 . 0 0 . 041 TL 63 . 50 PV 0 . 3 Pipe : 10 -186 . 4 4 . 310 PL 12 . 50 PF 0 .3 FDM 17 . 0 0 . 0 33 . 0 0 . 0 4 . 1 100 FTG E PE 0 . 0 TDR 17 . 0 0 . 0 33 . 3 0 . 0 0 . 012 TL 22 . 50 PV 0 . 1 Pipe: 11 -186 .4 4 . 310 PL 5 . 67 PF 0 . 1 TDR 17 . 0 0 . 0 33 . 3 0 . 0 4 . 1 100 FTG - - -- PE 5 .2 DPV 5 . 0 0 . 0 38 . 6 0 . 0 0 . 012 TL 5 . 67 PV 0 . 1 Pipe: 12 -186 .4 4 . 310 PL 2 . 00 PF 0 .4 DPV 5 . 0 0 . 0 38 . 6 0 . 0 4 . 1 100 FTG TGD PE 1 . 3 DHD 2 . 0 0 . 0 40 .2 0 . 0 0 . 012 TL 34 . 00 PV 0 . 1 Pipe: 13 -186 .4 4 . 310 PL 2 . 00 PF 0 . 0 DHD 2 . 0 0 . 0 40 .2 0 . 0 4 . 1 120 FTG ---- PE 0 . 0 BFO 2 . 0 0 . 0 40 . 3 0 . 0 0 . 008 TL 2 . 00 PV 0 . 1 Pipe: 14 FIXED PRESSURE LOSS DEVICE BFI 2 . 0 0 . 0 44 . 3 0 . 0 4 . 0 psi, 186 .4 gpm BFO 2 . 0 0 . 0 40 .3 0 . 0 .�: I I .. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-N.SDF JOB TITLE: Holman Recovery Attic North Win (Dry System) north wing PIPE DATA (cont . ) •PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 15 -186 .4 4 .220 PL 4 . 00 PF 0 . 0 BFI 2 . 0 0 . 0 44 . 3 0 . 0 4 . 3 140 FTG - - - - PE 0 .4 BOR 1 . 0 0 . 0 44 . 7 0 . 0 0 . 007 TL 4 . 00 PV 0 . 1 Pipe : 16 -186 .4 4 .220 PL 4 . 00 PF 0 .2 BOR 1 . 0 0 . 0 44 . 7 0 . 0 4 .3 140 FTG E PE 0 .4 UGE 0 . 0 0 . 0 45 . 3 0 . 0 0 . 007 TL 22 . 00 PV 0 . 1 Pipe: 17 -186 .4 6 .280 PL 45 . 00 PF 0 . 1 UGE 0 . 0 0 . 0 45 . 3 0 . 0 1 . 9 140 FTG T PE -0 .4 CC 1 . 0 SRCE 45 . 0 (N/A) 0 . 001 TL 97 . 00 PV 0 . 0 NOTES : (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been balanced to provide an average imbalance at each node of 0 . 009 gpm and a maximum imbalance at any node of 0 . 145 gpm. (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 15 . 1 ft/sec at pipe 4 . (4) PIPE FITTINGS TABLE Pipe Table Name: CUSTOM. PIP PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 . 220 18 . 00 36 . 00 11 . 00 39 . 00 22 . 00 4 . 00 36 . 00 6 . 280 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PAGE: G MATERIAL: EddyTr HWC: 100 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee LngEll i SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-N.SDF JOB TITLE: Holman Recovery Attic North Win (Dry System) north wing 1 . 083 2 . 00 5 . 00 2 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 418 3 . 00 6 . 00 2 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 654 4 . 00 8 . 00 2 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 123 5 . 00 10 . 00 3 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 705 6 . 00 12 . 00 4 . 00 14 . 00 7 . 00 1 . 00 10 . 00 10 . 00 3 . 334 7 . 00 15 . 00 5 . 00 16 . 00 10 . 00 1 . 00 13 . 00 10 . 00 4 . 310 10 . 00 20 . 00 6 . 00 22 . 00 12 . 00 2 . 00 20 . 00 10 . 00 PAGE: H MATERIAL: Bullms HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 4 . 310 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 .: I I SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-N.SDF JOB TITLE: Holman Recovery Attic North Win (Dry System) north wing WATER SUPPLY CURVE 60+ 55+ 50+0\ \ \ \ 45+X \ \ \ P 40+ \ R \ E \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi @ 2525 gpm Flow Test Point 15+ 10+ LEGEND " X = Required Water Supply " 44 . 97 psi @ 286 .4 gpm " 5+ " 0 = Available Water Supply 50 .45 psi @ 286 .4 gpm " 0++-+---+----+-----+- - - - - -+- - - - - - - -+---- -- --+- - - - -- - --+- - ------- --+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) N .• 1 1 I G NOR-rECH" Hydraulic Calculations FOR: Holman Recovery Center 16400 Smokey Point BLVD Marysville, WA Attic South Wing Design Data: Oceup>incy Classification: Light Hazard Standard: NFPA 13 Density: Per MFG listing Area or application: 7 heads per MFG Coverage of sprinklers: 260 SF per head Number of sprinklers calculated: (7)Heads FT—otal Sprinkler Demand @ Source: (including hose) 283.3 GPM @ 45.3 PSI Flow & Pressure Available at Source: 283.3 GPM @ 50.5 PSI Fl) ioker make&model: Viking model V-BB ^ Viking Attic Heads Sp �ii1' 'cr Thread: '/3"NPT Sl;ri11 Icr "K" Factor: 5.6 Dcsi, I_,ayout: D.F. D,T!c: August 19,2020 1 WASHIN®TON STATE CERTIFICATE OF CONOrETENOr 1 FIRE PROTECTION SPRINKLER SYST 1 1 Khosrow(David)Farahanl 17325-0195-C Level i Nor-Tech Fire Protection,Inc. 1 � NOt2TEFP 6 � � of 1 f I 1 I ExplrM � � Slgna tlti 14/31/2t1 � .............................� f� I .:.:_ � r■ i 1 � _ i � SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-S .SDF JOB TITLE: Holman Recovery CTR Attic South Wing (Dry System) WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2525 . 0 50 . 5 283 . 3 45 . 3 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 283 . 3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 183 . 3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 8 17 . 0 K= 5 . 60 18 .4 24 . 0 9 17 . 0 K= 5 . 60 19 . 6 24 . 8 10 17 . 0 K= 5 . 60 20 . 9 25 . 6 11 17 . 0 K= 5 . 60 22 .2 26 .4 12 17 . 0 K= 5 . 60 22 . 9 26 . 8 13 17 . 0 K= 5 . 60 23 . 9 27 .4 14 17 . 0 K= 5 . 60 25 .4 28 .2 J1 17 . 0 - - - - 28 .2 - - - J2 17 . 0 - - - - 30 . 5 - - - FDM 17 . 0 - - - - 33 . 0 - - - TDR 17 . 0 - - - - 33 . 6 - - -- DPV 5 . 0 - - - - 38 . 9 - - - DHD 2 . 0 - - - - 40 . 5 - - - BFO 2 . 0 - - - - 40 . 6 - - - BFI 2 . 0 - - - - 44 . 6 - - - BOR 1 . 0 - - - - 45 . 0 - - - UGE 0 . 0 - - - - 45 . 6 - - - CC 1 . 0 SOURCE 45 . 3 183 . 3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-S .SDF JOB TITLE: Holman Recovery CTR Attic South Wing (Dry System) PIPE DATA •PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe : 1 -24 . 0 1 . 083 PL 5 . 79 PF 1 . 3 8 17 . 0 5 . 6 18 .4 24 . 0 8 .4 100 FTG - - - - PE 0 . 0 9 17 . 0 5 . 6 19 . 6 24 . 8 0 . 219 TL 5 . 79 PV 0 . 5 Pipe : 2 -48 . 8 1 .418 PL 5 . 79 PF 1 . 3 9 17 . 0 5 . 6 19 . 6 24 . 8 9 . 9 100 FTG - - - - PE 0 . 0 10 17 . 0 5 . 6 20 . 9 25 . 6 0 .219 TL 5 . 79 PV 0 . 7 Pipe : 3 -74 .4 1 . 654 PL 5 . 79 PF 1 . 3 10 17 . 0 5 . 6 20 . 9 25 . 6 11 . 1 100 FTG - _ - PE 0 . 0 11 17 . 0 5 . 6 22 .2 26 .4 0 .226 TL 5 . 79 PV 0 . 8 Pipe : 4 -100 . 8 2 . 123 PL 5 . 79 PF 0 . 7 11 17 . 0 5 . 6 22 .2 26 .4 9 . 1 100 FTG -- - - PE 0 . 0 12 17 . 0 5 . 6 22 . 9 26 . 8 0 . 117 TL 5 . 79 PV 0 . 6 Pipe: 5 -127 . 6 2 . 123 PL 5 . 79 PF 1 . 1 12 17 . 0 5 . 6 22 . 9 26 . 8 11 . 6 100 FTG - - - - PE 0 . 0 13 17 . 0 5 . 6 23 . 9 27 .4 0 . 181 TL 5 . 79 PV 0 . 9 Pipe: 6 -155 . 0 2 . 123 PL 5 . 79 PF 1 . 5 13 17 . 0 5 . 6 23 . 9 27 .4 14 . 0 100 FTG - - - PE 0 . 0 14 17 . 0 5 . 6 25 .4 28 .2 0 . 260 TL 5 . 79 PV 1 . 3 Pipe : 7 -183 .2 3 . 334 PL 55 .42 PF 2 . 8 14 17 . 0 5 . 6 25 . 4 28 .2 6 . 7 100 FTG T PE 0 . 0 J1 17 . 0 0 . 0 28 .2 0 . 0 0 . 039 TL 70 .42 PV 0 . 3 Pipe: 8 -183 .2 3 . 334 PL 37 . 00 PF 2 . 3 J1 17 . 0 0 . 0 28 . 2 0 . 0 6 . 7 100 FTG ET PE 0 . 0 J2 1_7 . 0 0 . 0 30 . 5 0 . 0 0 . 039 TL 59 . 00 PV 0 . 3 Pipe: 9 -183 .2 3 . 334 PL 48 . 05 PF 2 . 5 J2 17 . 0 0 . 0 30 . 5 0 . 0 6 . 7 100 FTG T PE 0 . 0 FDM 17 . 0 0 . 0 33 . 0 0 . 0 0 . 039 TL 63 . 05 PV 0 .3 Pipe : 10 -183 .2 4 . 310 PL 11 . 67 PF 0 . 6 FDM 17 . 0 0 . 0 33 . 0 0 . 0 4 . 0 100 FTG 2ET PE 0 . 0 TDR 17 . 0 0 . 0 33 . 6 0 . 0 0 . 011 TL 51 . 67 PV 0 . 1 Pipe : 11 -183 .2 4 . 310 PL 5 . 67 PF 0 . 1 TDR 17 . 0 0 . 0 33 . 6 0 . 0 4 . 0 100 FTG - - -- PE 5 . 2 DPV 5 . 0 0 . 0 38 . 9 0 . 0 0 . 011 TL 5 . 67 PV 0 . 1 Pipe : 12 -183 .2 4 . 310 PL 2 . 00 PF 0 .4 DPV 5 . 0 0 . 0 38 . 9 0 . 0 4 . 0 100 FTG TGD PE 1 . 3 DHD 2 . 0 0 . 0 40 . 5 0 . 0 0 . 011 TL 34 . 00 PV 0 . 1 Pipe : 1-3 -183 . 2 4 . 310 PL 2 . 00 PF 0 . 0 DHD 2 . 0 0 . 0 40 . 5 0 . 0 4 . 0 120 FTG -- - - PE 0 . 0 BFO 2 . 0 0 . 0 40 . 6 0 . 0 0 . 008 TL 2 . 00 PV 0 . 1 G SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-S .SDF JOB TITLE : Holman Recovery CTR Attic South Wing (Dry System) PIPE DATA (cont . ) •PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (TT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe : 14 FIXED PRESSURE LOSS DEVICE BFI 2 . 0 0 . 0 44 . 6 0 . 0 4 . 0 psi, 183 . 2 gpm BFO 2 . 0 0 . 0 40 . 6 0 . 0 Pipe : 15 -183 . 2 4 . 220 PL 4 . 00 PF 0 . 0 BFI 2 . 0 0 . 0 44 . 6 0 . 0 4 .2 140 FTG - - - - PE 0 .4 BOR 1 . 0 0 . 0 45 . 0 0 . 0 0 . 007 TL 4 . 00 PV 0 . 1 Pipe : 16 -183 .2 4 .220 PL 4 . 00 PF 0 . 1 BOR 1 . 0 0 . 0 45 . 0 0 . 0 4 .2 140 FTG E PE 0 .4 UGE 0 . 0 0 . 0 45 . 6 0 . 0 0 . 007 TL 22 . 00 PV 0 . 1 Pipe : 17 -183 . 3 6 . 280 PL 45 . 00 PF 0 . 1 UGE 0 . 0 0 . 0 45 . 6 0 . 0 1 . 9 140 FTG T PE -0 .4 CC 1 . 0 SRCE 45 . 3 (N/A) 0 . 001 TL 97 . 00 PV 0 . 0 NOTES : (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been balanced to provide an average imbalance at each node of 0 . 009 gpm and a maximum imbalance at any node of 0 . 150 gpm. (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 14 . 0 ft/sec at pipe 6 . (4) PIPE FITTINGS TABLE Pipe Table Name : CUSTOM. PIP PACE : B MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 . 220 18 . 00 36 . 00 11 . 00 39 . 00 22 . 00 4 . 00 36 . 00 6 . 280 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PACE : G MATERIAL : EddyTr HWC: 100 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee LngEll SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-S .SDF JOB TITLE : Holman Recovery CTR Attic South Wing (Dry System) 1 . 083 2 . 00 5 . 00 2 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 418 3 . 00 6 . 00 2 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 654 4 . 00 8 . 00 2 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 123 5 . 00 10 . 00 3 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 3 . 334 7 . 00 15 . 00 5 . 00 16 . 00 10 . 00 1 . 00 13 . 00 10 . 00 4 . 310 10 . 00 20 . 00 6 . 00 22 . 00 12 . 00 2 . 00 20 . 00 10 . 00 PAC'3 : iI MATERIAL: Bullms HWC: 120 DiE!:neter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 4 . 310 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 I I I .: SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 03/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-S .SDF JOB TITLE: Holman Recovery CTR Attic South Wing (Dry System) WATER SUPPLY CURVE 60+ 55+ 50+0\ \ \ \ 45+X \ \ P 40+ \ R \ E \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi @ 2525 gpm Flow Test Point 15+ 10+ LEGEND " X = Required Water Supply " 45 .26 psi @ 283 . 3 gpm " 5+ " 0 = Available Water Supply " 50 .46 psi @ 283 . 3 gpm " 0++-+---+----+-----+------+-----11--+--------+---------+-----------+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) I Hydraulic Calculations FOR: Holman Recovery Center 16400 Smokey Point BLVD Marysville, WA Attic East Wing Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13 Density: Per MFG listing Area of application: 7 heads per MFG Coverage of sprinklers: 260 SF per head Number of sprinklers calculated: (7)Heads Total Sprinkler Demand @ Source: (including hose) 286.3 GPM @ 46.8 PSI Flow&Pressure Available at Source: 286.3 GPM @ 50.4 PSI Sprinkler make& model: Viking model V-BB Viking Attic Heads Sprinkler Thread: ''/Z"NPT Sprinkler "K" Factor: 5.6 Design Layout: D.F. Date: August 19,2020 WASHINGTON STATE CERTIFICATE OF COMPETENCY 1 I FIRE PROTECTION SPRMIKLER SrSTN Khosrow(David)Farahanl V 1 17325-0195-C Level i Nor-Tech Fire Protection,Inc. NOfi FEFPOExpiros 8 O •; 1 / 1 Ignster. 12131/20 ; r. . ------_..----a I I IL SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 Date : 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-E .SDF JOB TITLE: Holman Recovery CTR Attic East Wing (Dry System) WATER SUPPLY DATA -SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS . PRESS . @ PRESS . @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2525 . 0 50 .4 286 . 3 46 . 8 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 286 .3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 186 . 3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 17 . 0 K= 5 . 60 18 .4 24 . 0 2 17 . 0 K= 5 . 60 19 . 7 24 . 8 3 17 . 0 K= 5 . 60 20 . 9 25 . 6 4 17 . 0 K= 5 . 60 22 . 3 26 .4 5 17 . 0 K= 5 . 60 24 . 6 27 . 8 6 17 . 0 K= 5 . 60 25 . 7 28 .4 7 17 . 0 K= 5 . 60 27 .2 29 .2 Jl 17 . 0 - - - - 29 . 9 - - - J2 17 . 0 - - - - 32 . 3 - - - FDM 17 . 0 - - - - 34 . 9 - - - TDR 17 . 0 - - - - 35 . 1 - - - DPV 5 . 0 - - - - 40 .4 - - - DHD 2 . 0 - - - - 42 . 1 - - - BFO 2 . 0 - - - - 42 . 1 - - - BFI 2 . 0 - - - - 46 . 1 - - - BOR 1 . 0 - - - - 46 . 6 - - - UGE 0 . 0 - - - - 47 . 2 - - - CC 1 . 0 SOURCE 46 . 8 186 . 3 r + I _ � ' SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-E.SDF JOB TITLE: Holman Recovery CTR Attic East Wing (Dry System) PIPE DATA .PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe: 1 -24 . 0 1 . 083 PL 5 . 88 PF 1 . 3 1 17 . 0 5 . 6 18 .4 24 . 0 8 .4 100 FTG -- - - PE 0 . 0 2 17 . 0 5 . 6 19 . 7 24 . 8 0 . 219 TL 5 . 88 PV 0 . 5 Pipe: 2 -48 . 8 1 .418 PL 5 . 88 PF 1 .3 2 17 . 0 5 . 6 19 . 7 24 . 8 9 . 9 100 FTG - - - - PE 0 . 0 3 17 . 0 5 . 6 20 . 9 25 . 6 0 . 219 TL 5 . 88 PV 0 . 7 Pipe: 3 -74 . 5 1 . 654 PL 5 . 88 PF 1 . 3 3 17 . 0 5 . 6 20 . 9 25 . 6 11 . 1 100 FTG PE 0 . 0 4 17 . 0 5 . 6 22 . 3 26 .4 0 . 226 TL 5 . 88 PV 0 . 8 Pipe: 4 -100 . 9 1 . 654 PL 5 . 88 PF 2 . 3 4 17 . 0 5 . 6 22 . 3 26 .4 15 . 1 100 FTG -- - - PE 0 . 0 5 17 . 0 5 . 6 24 . 6 27 . 8 0 . 396 TL 5 . 88 PV 1 . 5 Pipe: 5 -128 . 7 2 . 123 PL 5 . 88 PF 1 . 1 5 17 . 0 5 . 6 24 . 6 27 . 8 11 . 7 100 FTG ---- PE 0 . 0 6 17 . 0 5 . 6 25 . 7 28 .4 0 . 184 TL 5 . 88 PV 0 . 9 Pipe : 6 -157 . 0 2 . 123 PL 5 . 88 PF 1 . 6 6 17 . 0 5 . 6 25 . 7 28 .4 14 .2 100 FTG PE 0 . 0 7 17 . 0 5 . 6 27 .2 29 .2 0 . 266 TL 5 . 88 PV 1 .4 Pipe: 7 -186 . 3 3 . 334 PL 43 . 92 PF 2 . 7 7 17 . 0 5 . 6 27 .2 29 .2 6 . 8 100 FTG ET PE 0 . 0 J1 17 . 0 0 . 0 29 . 9 0 . 0 0 . 041 TL 65 . 92 PV 0 . 3 Pipe: 8 -186 . 3 3 . 334 PL 37 . 00 PF 2 .4 J1 17 . 0 0 . 0 29 . 9 0 . 0 6 . 8 100 FTG ET PE 0 . 0 J2 17 . 0 0 . 0 32 . 3 0 . 0 0 . 041 TL 59 . 00 PV 0 . 3 Pipe: 9 -186 . 3 3 . 334 PL 48 . 50 PF 2 . 6 J2 17 . 0 0 . 0 32 . 3 0 . 0 6 . 8 100 FTG T PE 0 . 0 FDM 17 . 0 0 . 0 34 . 9 0 . 0 0 . 041 TL 63 . 50 PV 0 . 3 Pipe: 10 -186 . 3 4 . 310 PL 12 . 50 PF 0 . 3 FDM 17 . 0 0 . 0 34 . 9 0 . 0 4 . 1 100 FTG E PE 0 . 0 TDR 17 . 0 0 . 0 35 . 1 0 . 0 0 . 012 TL 22 . 50 PV 0 . 1 Pipe: 11 -186 . 3 4 . 310 PL 5 . 67 PF 0 . 1 TDR 17 . 0 0 . 0 35 . 1 0 . 0 4 . 1 100 FTG -- -- PE 5 .2 DPV 5 . 0 0 . 0 40 .4 0 . 0 0 . 012 TL 5 . 67 PV 0 . 1 Pipe: 12 -186 . 3 4 . 310 PL 2 . 00 PF 0 .4 DPV 5 . 0 0 . 0 40 .4 0 . 0 4 . 1 100 FTG TGD PE 1 . 3 DHD 2 . 0 0 . 0 42 . 1 0 . 0 0 . 012 TL 34 . 00 PV 0 . 1 Pipe: 13 -186 . 3 4 . 310 PL 2 . 00 PF 0 . 0 DHD 2 . 0 0 . 0 42 . 1 0 . 0 4 . 1 120 FTG ---- PE 0 . 0 BFO 2 . 0 0 . 0 42 . 1 0 . 0 0 . 008 TL 2 . 00 PV 0 . 1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-E.SDF JOB TITLE: Holman Recovery CTR Attic East Wing (Dry System) PIPE DATA (cont . ) -PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe : 14 FIXED PRESSURE LOSS DEVICE BFI 2 . 0 0 . 0 46 . 1 0 . 0 4 . 0 psi, 186 .3 gpm BFO 2 . 0 0 . 0 42 . 1 0 . 0 Pipe : 15 -186 . 3 4 .220 PL 4 . 00 PF 0 . 0 BFI 2 . 0 0 . 0 46 . 1 0 . 0 4 . 3 140 FTG - - - - PE 0 .4 BOR 1 . 0 0 . 0 46 . 6 0 . 0 0 . 007 TL 4 . 00 PV 0 . 1 Pipe: 16 -186 . 3 4 .220 PL 4 . 00 PF 0 . 2 BOR 1 . 0 0 . 0 46 . 6 0 . 0 4 .3 140 FTG E PE 0 .4 UGE 0 . 0 0 . 0 47 .2 0 . 0 0 . 007 TL 22 . 00 PV 0 . 1 Pipe : 17 -186 . 3 6 .280 PL 45 . 00 PF 0 . 1 UGE 0 . 0 0 . 0 47 .2 0 . 0 1 . 9 140 FTG T PE -0 .4 CC 1 . 0 SRCE 46 . 8 (N/A) 0 . 001 TL 97 . 00 PV 0 . 0 NOTES : (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc . 4792 LaVista Road Tucker, GA 30084 (2) The system has been balanced to provide an average imbalance at each node of 0 . 010 gpm and a maximum imbalance at any node of 0 . 177 gpm. (3) Velocity pressures are printed for information only, and are not used in balancing the system. Maximum water velocity is 15 . 1 ft/sec at pipe 4 . (4) PIPE FITTINGS TABLE Pipe Table Name: CUSTOM. PIP PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 . 220 18 . 00 36 . 00 11 . 00 39 . 00 22 . 00 4 . 00 36 . 00 6 .280 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PAGE: G MATERIAL: EddyTr HWC: 100 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee LngEll I 1� SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-E.SDF JOB TITLE: Holman Recovery CTR Attic East Wing (Dry System) 1 . 083 2 . 00 5 . 00 2 . 00 5 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 .418 3 . 00 6 . 00 2 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 654 4 . 00 8 . 00 2 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 123 5 . 00 10 . 00 3 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 3 . 334 7 . 00 15 . 00 5 . 00 16 . 00 10 . 00 1 . 00 13 . 00 10 . 00 4 . 310 10 . 00 20 . 00 6 . 00 22 . 00 12 . 00 2 . 00 20 . 00 10 . 00 PAGE: H MATERIAL: Bullms HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D Ell Tee 4 . 310 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-E.SDF JOB TITLE: Holman Recovery CTR Attic East Wing (Dry System) WATER SUPPLY CURVE 60+ 55+ 50+0\ 1 \\ X \ 45+ \ \ \ P 40+ \ R \ E \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi @ 2525 gpm Flow Test Point 15+ 10+ LEGEND " X = Required Water Supply " 46 . 83 psi @ 286 . 3 gpm " 5+ 0 = Available Water Supply 50 .45 psi @ 286 . 3 gpm " 0++-+---+----+-----+- - - - - -+- - - - - - -+- - - - - - - -+- - - - - - - - -+- - - -- -- - - - -+ 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) Hydraulic Calculations FOR: Holman Recovery Center 16400 Smokey Point BLVD Marysville, WA Attic West Wing Design Data: Occupancy Classification: Light Hazard Standard: NFPA 13 Density: Per MFG listing Area of application: 7 heads per MFG Coverage of sprinklers: 260 SF per head Number of sprinklers calculated: (7)Heads Total Sprinkler Demand @ Source: (including hose) 382.8 GPM @ 44.6 PSI Flow&Pressure Available at Source: 382.8 GPM @ 50.0 PSI Sprinkler make& model: Viking model V-1313 Viking Attic Heads Sprinkler Thread: '/Z" NPT Sprinkler "K" Factor: 8.0 Design Layout: D.F. Date: August 19,2020 WASNIN®TON STATE CERTIFICATE OF COMPETENCY / FIRE PROTECTION SPRINKLER SYST j Khosrow(David)Farahanl 1 1 7325-0195-C Level i Nor-Tech Fire Protection,Inc. Q NOR FEFP 6 i �• xPlr�s i � IOnacun �s�auzo � , I I , , , SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 Date : 08/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-W.SDF JOB TITLE : Holman Recovery CTR Attic (Dry System) W Wing 8 . OK WATER SUPPLY DATA --SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS . PRESS . Q PRESS . Q DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CC 51 . 0 20 . 0 2525 . 0 50 . 1 382 . 8 44 . 6 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 382 . 8 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 282 . 8 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) T1 17 . 0 K= 8 . 00 22 . 6 38 . 0 T2 17 . 0 K= 8 . 00 23 . 3 38 . 6 T3 17 . 0 K= 8 . 00 24 . 6 39 . 7 T4 17 . 0 K= 8 . 00 25 .4 40 . 3 T5 17 . 0 K= 8 . 00 26 . 9 41 . 5 T6 17 . 0 K= 8 . 00 27 . 5 42 . 0 T7 17 . 0 K= 8 . 00 28 . 5 42 . 7 FDM 17 . 0 - - - - 30 . 7 - - - TDR 17 . 0 - - - - 32 . 0 - - - DPV 5 . 0 - - - - 37 . 3 - - - DHD 2 . 0 - - - - 39 . 5 - - - BFO 2 . 0 - - - - 39 . 5 - - - BFI 2 . 0 - - - - 43 . 5 - - - BOR 1 . 0 - - - - 44 . 0 - - - UGE 0 . 0 - - - - 44 . 8 - - - CC 1 . 0 SOURCE 44 . 6 282 . 8 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 Date: O8/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-W. SDF JOB TITLE : Holman Recovery CTR Attic (Dry System) W Wing 8 . OK PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe : 1 -38 . 0 1 .418 PL 5 .42 PF 0 . 7 T1 17 . 0 8 . 0 22 . 6 38 . 0 7 . 7 100 FTG - - - - PE 0 . 0 T2 17 . 0 8 . 0 23 . 3 38 . 6 0 . 138 TL 5 .42 PV 0 .4 Pipe : 2 -76 . 6 1 . 654 PL 5 .42 PF 1 . 3 T2 17 . 0 8 . 0 23 . 3 38 . 6 11 .4 100 FTG - - - - PE 0 . 0 T3 17 . 0 8 . 0 24 . 6 39 . 7 0 .238 TL 5 .42 PV 0 . 9 Pipe : 3 -116 . 3 2 . 123 PL 5 .42 PF 0 . 8 T3 17 . 0 8 . 0 24 . 6 39 . 7 10 . 5 100 FTG - - - - PE 0 . 0 T4 17 . 0 8 . 0 25 .4 40 . 3 0 . 153 TL 5 .42 PV 0 . 7 Pipe : 4 -156 . 6 2 . 123 PL 5 .42 PF 1 .4 T4 17 . 0 8 . 0 25 . 4 40 . 3 14 .2 100 FTG -- - - PE 0 . 0 T5 17 . 0 8 . 0 26 . 9 41 . 5 0 .265 TL 5 .42 PV 1 .4 Pipe : 5 -198 . 1 2 . 705 PL 5 .42 PF 0 . 7 T5 17 . 0 8 . 0 26 . 9 41 . 5 11 . 1 100 FTG -- - - PE 0 . 0 T6 17 . 0 8 . 0 27 . 5 42 . 0 0 . 126 TL 5 .42 PV 0 . 8 Pipe : 5 -240 . 1 2 . 705 PL 5 .42 PF 1 . 0 T6 17 . 0 8 . 0 27 . 5 42 . 0 13 .4 100 FTG - - - - PE 0 . 0 T7 17 . 0 8 . 0 28 . 5 42 . 7 0 . 180 TL 5 .42 PV 1 .2 Pipes : 7 -282 . 8 4 . 310 PL 26 . 58 PF 2 . 2 T7 17 . 0 8 . 0 28 . 5 42 . 7 6 .2 100 FTG 4ET PE 0 . 0 FDM 17 . 0 0 . 0 30 . 7 0 . 0 0 . 025 TL 86 . 58 PV 0 . 3 'pe : 9 -282 . 8 4 . 310 PL 11 . 67 PF 1 .3 FDM 17 . 0 0 . 0 30 . 7 0 . 0 6 .2 100 FTG 2ET PE 0 . 0 TDR 17 . 0 0 . 0 32 . 0 0 . 0 0 . 025 TL 51 . 67 PV 0 . 3 Pipe: 10 -282 . 8 4 . 310 PL 5 . 67 PF 0 . 1 TDR 17 . 0 0 . 0 32 . 0 0 . 0 6 .2 100 FTG - - -- PE 5 . 2 DPV 5 . 0 0 . 0 37 . 3 0 . 0 0 . 025 TL 5 . 67 PV 0 . 3 Pipe : 11 -282 . 8 4 . 310 PL 2 . 00 PF 0 . 9 DPV 5 . 0 0 . 0 37 . 3 0 . 0 6 .2 100 FTG TGD PE 1 . 3 DHD 2 . 0 0 . 0 39 . 5 0 . 0 0 . 025 TL 34 . 00 PV 0 . 3 Pipe : 12 -282 . 8 4 . 310 PL 2 . 00 PF 0 . 0 DHD 2 . 0 0 . 0 39 . 5 0 . 0 6 .2 120 FTG ---- PE 0 . 0 BFO 2 . 0 0 . 0 39 . 5 0 . 0 0 . 018 TL 2 . 00 PV 0 . 3 Pipe : 13 FIXED PRESSURE LOSS DEVICE .BFI 2 . 0 0 . 0 43 . 5 0 . 0 4 . 0 psi, 282 . 8 gpm BFO 2 . 0 0 . 0 39 . 5 0 . 0 Piny : 14 -282 . 8 4 .220 PL 4 . 00 PF 0 . 1 BFI 2 . 0 0 . 0 43 . 5 0 . 0 6 . 5 140 FTG - - - - PE 0 .4 BOR 1 . 0 0 . 0 44 . 0 0 . 0 0 . 015 TL 4 . 00 PV 0 . 3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 Date: 08/;'0/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-W.SDF JOB TITL:. : Holman Recovery CTR Attic (Dry System) W Wing 8 . OK PIPE DATJ� (cont . ) PPIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) F.L. /FT (PSI) Pipe : 15 -282 . 8 4 .220 PL 4 . 00 PF 0 . 3 BOR 1 . 0 0 . 0 44 . 0 0 . 0 6 . 5 140 FTG E PE 0 .4 UGE 0 . 0 0 . 0 44 . 8 0 . 0 0 . 015 TL 22 . 00 PV 0 . 3 Pine : 1_6 -282 . 8 6 .280 PL 45 . 00 PF 0 .2 UGE 0 . 0 0 . 0 44 . 8 0 . 0 2 . 9 140 FTG T PE -0 .4 CC 1 . 0 SRCE 44 . 6 (N/A) 0 . 002 TL 97 . 00 PV 0 . 1 NOTES : (1) Calculations were performed by the HASS 6 .4 . 0 computer program under license no. 4 C1324A granted by HRS Systems, Inc . 4792 LaVista Road Tucker, GA 30084 (2) The s-�3tem has been balanced to provide an average imbalance at each node of 0 . 006 gpm and a maximum imbalance at any node of 0 . 086 gpm. (3) Veloc ' 1__y pressures are printed for information only, and are no{,, u: -d in balancing the system. Maximum water velocity is 14 . 2 ft/sec at pipe 4 . (4) PIPE ?,=CTTINGS TABLE Pine "'-able Name : CUSTOM.PIP P'-,-,E : ') MATERIAL: DIRON HWC: 140 Diame' r Equivalent Fitting Lengths in Feet (in' E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 4 . 22c 18 . 00 36 . 00 11 . 00 39 . 00 22 . 00 4 . 00 36 . 00 E . 28r' 24 . 00 52 . 00 16 . 00 55 . 00 17 . 00 5 . 00 52 . 00 PT ,E : MATERIAL : EddyTr HWC: 100 Di_.ame; r_ Equivalent Fitting Lengths in Feet (in; E T L C B G A D Ell Tee LngEll 1 . 41� 3 . 00 6 . 00 2 . 00 7 . 00 6 . 00 1 . 00 10 . 00 10 . 00 1 . 65G 4 . 00 8 . 00 2 . 00 9 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 12;- 5 . 00 10 . 00 3 . 00 11 . 00 6 . 00 1 . 00 10 . 00 10 . 00 2 . 70`- 6 . 00 12 . 00 4 . 00 14 . 00 7 . 00 1 . 00 10 . 00 10 . 00 r SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 Date: 08/" )/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-W.SDF JOB TIT'JE : Holman Recovery CTR Attic (Dry System) W Wing 8 . OK 4 . 31C 10 . 00 20 . 00 6 . 00 22 . 00 12 . 00 2 . 00 20 . 00 10 . 00 PAGE : 'i MATERIAL: Bullms HWC: 120 Diame' ,,r Equivalent Fitting Lengths in Feet (in; E T L C B G A D Ell Tee ;',1C' 13 . 00 26 . 00 8 . 00 29 . 00 16 . 00 3 . 00 26 . 00 13 . 00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 Date: 03/20/2020 C: \HASS64\DATA2020\HOLMAN\HLMN-A-W.SDF JOB TIT!-JE : Holman Recovery CTR Attic (Dry System) W Wing 8 . OK WATER S'TPPLY CURVE t 60+ 1 55+ I 50+0\ \ \ \ 45+X \ \ \ P 40+ \ R \ E \ S \ S 35+ \ U \ R \ E \\ 30+ \ P \ S \ I 25+ \ \ \ 20+ * <-20 . 0 psi ,@ 2525 gpm Flow Test Point 15+ 10+ LEGEND " _, = Required Water Supply " 44 . 56 psi @ 382 . 8 gpm " 5+ IT 0 = Available Water Supply " 50 . 05 psi @ 382 . 8 gpm If 0+-1--+---+----+-----+------+--------+- - ---- - -+- --- ---- -+- - - - - - - - -- - -+ ''001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) ,. .. e I I .. . M i .aes " es• DC ��gqCKFLOW ��/ Double Check Valve 61REGT • The Deringer 20(x) Double Check Valve Assembly is designed to prevent non-health hazard pollutants from entering the potable water supply system caused by backpressure and/or backsiphonage conditions. V E Sizes: 21/2", 3", 4"1 6", 8" T '1 Working Pressure: 10-175psi (0.7-12.1 bar) I Temperature Range: 339-140°F(1°-60°C) C End Connections A -ITS Groove for Steel Pipe: AWWA C606 - - HORIZONTAL L -Flange Adapters: ANSI B16.1 Class 125 ►�aNS m ,�, �+ AwwA P ULCENnFIED U FM O U.7�. cs»-0r Lead Free: 0.25%Maximum by Weight LE"FaF . ,&WWF„ o„ APPROVED ccrruuur Integral Shut-Off Valves Dual Actioffk4 Check Modules Prewired Supervisory Indoor/Outdoor Application •Poppet Action at Low Flow Switches -Swing Action at High Flow -Patent Pending Silicone Elastomer ` Check Discs aor._ - 100%Stainless fir... Flange Adapters Steel Housing L Available i IPS Grooved f Ends 1 :.V, Tamper Resistant Test Cocks I COPY �agisseesi�g Spec�ca>esio� The Deringer 20(x) Double Check Valve shall utilize two independent Dual Action Check modules and two integral resiliently seated shut-off valves all of which shall be contained within a single rigid valve housing constructed entirely of 304 stainless steel. Both integral shutoff valves shall include pre-wired supervisory tamper switches contained within a weatherproof actuator housing approved for both indoor and outdoor use.Dual Action Check modules shall operate as a "poppet style" check under low flow conditions, operate as a "swing style" check under high flow conditions and • utilize replaceable silicone elastomer sealing discs. Assembly test cocks shall - resistant actuator.Assembly shall have a single full access service port and cove vtitffii � � seal. Assembly shall be serviceable without special tools and approved for bot honzo��yL� WX Job Name: Contractor: APPROVED Job Location: Approval: Engineer: Contractor's P.O No: Approval: Representative: nv Kict PI III nlf\lr-- 1K1C0r_r'TnQ Backtlow Direct, LLC - 2484 Mercantile Drive• Rancho Cordova- Califuru - Phone: 916-7604524 Website: www.backflowdirect.cont.__—.---_— - .RowPerformance 379 757 _ 1514 2271 2650 18 124 16 2 '/z" (20) t 10 g 14 . 3" (20)-•- 4„ (20) 96 cn 12 63 0 10 69 8 D 6 4; u 4 28 a 2 � 0 (kPa) 0 100 200 300 460 500 600 700 800 - Rated Flow ♦ - UL Tested O - 15 fps Rate of Flow (gpm) Horizontal Orientation Iipm) i{14 3026 4542 6056 7571 9065 16 110 v 14 _ g„ (20) 96 a 12 N 10 6" (20x)_ 69 8 - 5� QL) 6 - 41 4 - 6 2 14 0 {kF?aJ 0 400 800 1200 1600 2000 2400 'Specific orientation&agency flow characteristics avadable on website Rate of Flow(gpm) NaF izrsntal Orientation 71 Sc ' H Ht D r Ec Hb L -� - W-size Model Ht Hb L EC 0 H W Weight 3c In mm in mm in mm in mm in mm In mm in mm In mm Ibis kg NPT 2% 65 20 7.1 180 2.9 74 18.7 475 2% 65 0.0 0 10.0 254 11.0 279 38 17 W 3 80 20 7.4 188 2.9 74 18.7 475 3 80 0.0 0 10.3 262 11.0 279 40 18 Y2" 4 100 20 7.9 201 3.1 79 18.7 475 4 100 0.2 5 11.0 279 11.0 279 42 19 Y�" 6 150 20K 8.7 221 4.8 122 28A 721 6 150 1.0 25 13.5 343 13.8 351 122 55 'A* r, 8 200 20 10A 264 5.4 137 30.7 780 8 200 1.8 46 15.8 401 13.8 351 141 64 W Valve Housing: 304 Stainless Steel SOV Bearings: Teflon/Bronze Check Springs: 17-7 Stainless Steel Valve Cover: 304 Stainless Steel Non Wetted Bolts: Grade 8 Zinc Plated Check Fins: 17-7118-8 Stainless Steel SOV Disks: EPDMI304SS Wetted Fasteners: 18-8 Stainless Steel Check Seats: Noryl Polymer(NSF) SOV Shafts: 304 Stainless Steal Cheek Disks: Silicone(NSF) O-Rings: Bnna-N(NSP) Backnow Direct, LLC - 2484 Mercantile Drive• Rancho Cordova -California -95742- United Slates or America Phone: 916-7604524 Website: www.backtlowdirect.com tqC0 Fire & Building Products Technical Services: Tel: (800) 381-9312/Fax: (800)791-5500 Model BFV-N Butterfly Valve Grooved End 2-112 Inch - 10 Inch (DN65 - DN250) General Technical Description Data The Model BFV-N Grooved End But- Model terfly Valves(Ref. Figure 1)are indicat- BFV-N C� ing type valves designed for use in fire Sizes:ANSI Inches/DN protection systems where a visual in- 2-1/2(DN65),3 (DN80), dication is required as to whether the 4 DN100),5 DN125), valve is open or closed.They are used, 6�DN150),8�DN200), 10(DN250) for example, as system,sectional,and A rovals pump water control valves. They have The 2-1/2 through 10 inch (DN65 - cut groove inlet and outlet connections DN250) Model BFV-N Grooved End that are suitable for use with grooved Butterfly Valves are UL and C-UL List- end pipe couplings that are listed and ed and FM Approved. approved for fire protection systems. In addition,the Model BFV-N Grooved For applications requiring supervision End Butterfly Valves are listed by the of the open position of the valve, the California State Fire Marshall under Gear Operators for the Model BFV-N Listing No.7770-1670:100. Butterfly Valves are provided with two sets of factory installed internal All laboratory listings and approvals are switches each having SPDT contacts. for indoor and outdoor use. Friction Loss The supervisory switches transfer their The approximate friction loss, based p y Maximum Working Pressure on the Hazen Williams formula and ex- electrical contacts when there is move- •2-1/2 -8 Inch(DN65- DN200): pressed in equivalent length of pipe ment from the valve's normal open po- 300 psi(20,7)bar with C= 120, is as follows.The data is sition during the first two revolutions of . 10 Inch (DN250): based on friction loss information col- the handwheel. 175 psi(12,0 bar) lected at a typical flow rate of 15 feet WARNINGS Materials of Construction: per second. The Model BFV-N Grooved End But- Body •6.9 feet of 2-1/2 inch Sch. 40 pipe terfly Valves described herein must be Ductile iron conforming to ASTM A-395 for the 2-1/2 inch valve. installed and maintained in compliance Body Coating •8.7 feet of 3 inch Sch. 40 pipe for with this document, as well as with the Polyamide the 3 inch valve. applicable standards of the National Disc •4.5 feet of 4 inch Sch. 40 pipe for Fire Protection Association, in addition Ductile iron conforming to ASTM A-395 the 4 inch valve. to the standards of any other authori- Disc Seal •6.6 feet of 5 inch Sch. 40 pipe for ties having jurisdiction. Failure to do Grade EPDM"E"encapsulated rubber the 5 inch valve. so may impair the performance of conforming to ASTM D-2000 • 11.1 feet of 6 inch Sch. 40 pipe for these devices. the 6 inch valve. Upper&Lower Stem The owner is responsible for maintain- Type 416 Stainless Steel conforming • 10.2 feet of 8 inch Sch.30 pipe for ing their fire protection system and de- to ASTM 582 the 8 inch valve. vices in proper operating condition. Lower Plug •12.1 feet of 10 inch Sch.30 pipe for The installing contractor or sprinkler PVC the 10 inch valve. manufacturer should be contacted with any questions. Operator Gear operator with iron housing Page 1 of 4 MAY, 2007 TFP1510 Page 2 of 4 TFP1510 Nominal Nominal Installation Dimensions in Inches and(mm) Weight Valve Pipe Sizes O'D' A B C D E F G H Ik9) 2-1/2" 2.88 3.85 11.71 3.25 5.43 6.00 7.81 2.50 22 DN65 (73,0) (98,0) (297,4) (83,0) (137,9) (152,4) (198,4) (63,5) 0 (10,0) 3" 3.50 3.85 12.25 3.54 5.68 6.00 7.81 2.50 23 DN80 (88,9) (98,0) (311,1) (90,0) (144,2) (152,4) (198,4) (63,5) 0 (10,4) 4" 4.50 4.56 13.95 4.35 6.58 6.00 7.81 2.50 28 DN100 (114,3) (116,0) (354,3) (110,0) (167,1) (152,4) (198,4) (63,5) 0 (12,7) 5" 5.56 5.86 14.93 4.84 7.07 6.00 7.81 2.50 31 DN125 (141,3) (149,0) (379,2) (123,0) (179,6) (152,4) (198,4) (63,5) 0 (14,1) 6" 6.63 5.86 17.31 5.93 8.35 6.00 7.81 2.50 0.67 41 DN150 (168,3) (149,0) (439,7) (151,0) (212,0) (152,4) (198,4) (63,5) (17,0) (18,6) 8` 8.63 5.26 19.20 6.87 9.29 6.00 7.81 2.50 5.86 53 DN200 (219,1) (134,0) (487,7) (174,0) (236,0) (152,4) (198,4) (63,5) (148,8) (24,1) 10" 10.75 6.29 25.11 9.17 11.50 9.00 7.68 3.00 7.41 88 DN250 (273,1) (160,0) (637,8) (233,0) 1 (292,1) (228,6) (195,1) 1 (76,2) (188,2) (40,0) G F HANDWHEEL INDICATORFLAG 1/2"NPT CONDUIT CONNECTION GEAR _ OPERATOR E O BODY D B DISC H C 4 A FIGURE 1 MODEL BFV-N GROOVED END BUTTERFLY VALVE -NOMINAL DIMENSIONS- TFP1510 Page 3 of 4 Installation The Model BFV-N Grooved End But- r — — — — — — - terfly Valves may be installed with flow I SUPERVISORY in either direction and can be posi- I I SWITCH tioned either horizontally or vertically. The grooved end pipe couplings used SWITCH SHOWN g p pL _ — J WITH VALVE with the Model BFV-N must be listed FULL OPEN or approved for fire protection service and installed in accordance with the 2 2 Z z manufacturers instructions. > > o 0 The Model BFV-N Butterfly Valve may be installed with any schedule of pres- sure class of pipe or tubing that Is list- END OF LINE PANEL ed or approved for fire protection. RESISTOR As applicable, refer to Figure 2 for the internal switch wiring diagram. r — —— — — — -� Conduit and electrical connections AUXILIARY are to be made in accordance with I GND I SWITCH the authority having jurisdiction and/ or the National Electrical Code. With SWITCH SHOWN reference to Figure 2, the "supervi- L J WITH VALVE sory switch" is intended for connec- — — W FULL OPEN Z tion to the supervisory circuit of a fire o w U) alarm control panel in accordance with ° " m o NFPA 72. The "auxiliary switch" is in- Z tended for the unsupervised connec- tion to auxiliary equipment in accor- - + I BELL dance with NFPA 70, National Electric Code. POWER + NOTE For outdoor applications with inter- nal supervisory switches, it is recom- mended that wiring connections be CONTACT RATING .... 1/2A @ 125 VDC made at a temperature above 150F 1/4A®250 VDC (-9°C),in order to insure sufficient flex- 15.1A/12HP @ 125,250 VAC ibility of the wire lead insulation. 5A®125 VAC"L" Care and FIGURE 2 MODEL BFV-N BUTTERFLY VALVE Maintenance -INTERNAL SWITCH WIRING DIAGRAM- The owner is responsible for the in- spection,testing,and maintenance of their fire protection system and devic- NOTE es in accordance with the applicable Before closing a fire protection system standards of the National Fire Pro- control valve for maintenance or in- tection Association (e.g., NFPA25), in spection work on either the valve or fire addition to the standards of any au- protection system which it controls, thority having jurisdiction.The install- permission to shut down the affected ing contractor or product manufac- fire protection systems must be ob- turer should be contacted relative to tained from the proper authorities and any questions. Any impairment must all personnel who may be affected by be immediately corrected. this decision must be notified. It is recommended that automatic sprinkler systems be inspected, test- ed, and maintained by a qualified in- spection service. Page 4 of 4 TFP1510 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Grooved End Butterfly Valves: & Building Products (TFBP) are war- Specify: (specify inch size) Model ranted solely to the original Buyer for BFV-N Grooved End Butterfly Valve ten(10)years against defects in mate- with internal supervisory switches, rial and workmanship when paid for P/N(specify). and properly installed and maintained Valve Size Valve Part Number under normal use and service. This 2-1/2 .....59-300-F-025N warranty will expire ten(10)years from 3..........................59-300-F-030N date of shipment by TFBP. No warran- 4..........................59-300-F-04oN ty is given for products or components 5..........................59-300-F-050N manufactured by companies not af- 6..........................59-300-F-060N filiated by ownership with TFBP or for 8••••••••••••••.•••••••••••59-300-F-080N products and components which have 10.........................59-300-F-010N been subject to misuse, improper in- stallation,corrosion,or which have not been installed,maintained,modified or repaired in accordance with applicable Standards of the National Fire Protec- tion Association, and/or the standards of any other Authorities Having Juris- diction. Materials found by TFBP to be defective shall be either repaired or re- placed, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other ob- ligation in connection with the sale of products or parts of products. TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,ex- press or implied including warranties of merchantability and fitness for a par- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products,materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale Pennsylvania 19446 r Bulletin 350 Rev.R Model D Relmiabi Dry Pipe W Valve 411(100mm) - 6"(150mm) Instructions for Valve With Installation, Operation, Model D Trimmings Listed by Underwriters Laboratories,Inc.Approved Care and Maintenance er M Approvals',and other fire insurance and gov- ernmental agencies in the United States and foreign countries. O Sp 4, 'a QH�R C01� s asarn-e The Reliable Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523 ` General Reliable Model D Dry Pipe Valves are installed in the • Threaded openings per ANSI B 1.20.1. vertical position in the main supply to the dry pipe system. • Reliable's standard trim sets are compatible The basic trim set, priming chamber attachment and fill with US Flanged and Grooved Valves. line attachment are described below and are separately • Color- Black. ordered and supplied. Additional items such as air maintenance devices, air compressors, alarm switches, c. Metric Flanged Inlet and Outlet: etc. are described and installed in accordance with their Flanges mate with E N 10 9 2-2 8.6 6, respective product bulletins. NF-E-29-282 and BS 4504 PN 16 Flanges. Valve Description Metric Flange Dimensions in Millimeters 1. Rated working pressure- 175 psi (12,1 bar). Valve Bolt Bolt Flange Flange No. 2. Factory hydrostatic test pressure - 350 psi(24,2 bar). size Circle Hole Outside Thickness Bolts 3. End and trim connections-Three valve connection Dia. Dia. Dia. styles are available: loomm 180 18.3 229 23.8 8 a. US Standard Flanged Inlet and Outlet: 150mm 241 22.2 279 1 25.4 8 U.S. Flange Dimensions in Inches • Threaded openings per ISO 7/1-R. Valve Bolt Bolt Flange Flange No. • Reliable's standard trim sets may be used with size Circle Hole Outside Thickness Bolts metric valves providing trim is assembled Dia. Dia. Dia. carefully and extra thread sealant is applied to 4" (100mm) 71/2 3/4 9 15/16 8 connections between valves and trim. 6" (150mm) 91/2 7/6 11 1 8 • Color- Red. • Threaded openings per ANSI B 1.20.1. 4. Face to Face Dimension: • Reliable's standard trim sets are compatible • The 4" (100 mm) valve - 16" (406 mm). with Flanged Valves. • The 6" (150 mm) valve - 1911 (482 mm). • Color- Black. 5. Friction Loss-Expressed in Equivalent Length b. US Standard Flanged Inlet and Grooved Outlet of Pipe, Based on Hazen-Williams formula with (Fig. A C=120: )� • Inlet flange mates with ANSI B 16.1 (125 lb.) Equiv. Length Flange. • The 4" (100 mm) 28' (8.51 m) • Outlet groove dimensions per ANSI/AWWA . The 6" (150 mm) 47' (14.29m) C606. 6. Installation Position: Vertical. U.S.Groove Dimensions in Inches Valve Installation Valve Outlet Groove Groove Outlet Face When the dry pipe valve is to be placed on top of an OS&Y Size Dia. Dia. Width to Groove gate valve,the use of 4 stud bolts and 4 nuts is needed to 4" (100mm) 4.500 4.334 3/6 5/6 connect the bottom flange of the Dry Pipe Valve to the top 6" (150mm) 6.625 6.455 3/6 5/6 flange of the OS&Y gate valve. Dry Pipe Valve Stud Bolt Size Dia. Len th 1998 4" (100mm) 5/" 3" " 6"(150mm) %" 31/z" 4 INCH MoDEL DRY ° Insert the 4 stud bolts in the top flange holes of the OS&Y PIPE VALVE gate valve.Push stud bolts up through flange holes of dry A pipe valve and attach nuts.Complete bolting with uniform RELIABLE• AUTOMATIC tightening. SPRINKLER co. Assembly of Model D Trim "r.vExrlo" CO NEW rats MODEL o �.+"'9r`4e LISTED , K 706A All valves are Listed by Underwriters Laboratories, Inc. wn1 ®4FMD and Approved by'FM Approvals'only when used with the D O uV 173 P' valve manufacturer's trim sets. q Basic Trim " 175 PSI The assembled basic trim set is shown in Figures B and C. TEW 1. Install 1/4" Nipple (42) in tapped opening marked TEST 350F1 M S/N and attach half of 1/4" Union (26). Figure A 2. 2. Install/"Nipple(47)in tapped opening marked ALARM Hydrostatic Testing of Dry Pipe System and connect parts in proper order through Check Valve When conducting hydrostatic test of system piping at (12)to Union(26). pressures in excess of 50 psi (3.44 bar), be sure the dry Note: Check Valve(12)must allow flow from the dry pipe pipe valve clapper is either latched in wide open position valve to the alarm line. or removed from valve.Otherwise, injury to the valve may 3. Connect balance of trimming parts in any desired order. occur. 4. A Model B Strainer must be installed as shown, when Operation ever a Model C Mechanical Water Motor Alarm is used. The normal position of the dry pipe valve parts is shown in The strainer must be in a horizontal line to protect the nozzle in the water motor, and it must be accessible for Figure E. cleaning. When air pressure in the system drops due to the 5. Drain pipe from Drip Cup(2)should be run as directly as opening of one or more sprinklers, the Clapper possible to an open drain. If it is absolutely necessary to Assembly(5), through the greater force exerted on its connect itto the 21'main drain line, install a check valve in underside by the water supply pressure, moves the drip cup drain line at least 4 feet below the drip cup upward rotating to its open position and is held in this so as to give proper head for discharge of water into the position by the Latch. Water from the supply instantly main drain line.See NFPA 13 for additional requirements. flows through the dry pipe valve into the sprinkler Priming Chamber and Fill Line Attachments system piping. Water also flows through the alarm The assembled priming chamber and fill line attachments outlet to the electric alarm switch and water motor are shown in Figure D. causing alarms to be sounded. Installation Dimensions For 4" (100mm)Valve&6"(150mm)Valve 2J" [63.5mm] 6$" [165.1 mm] 8J" [212.7mm] QQ �Y006�0 oOQ I M ruK O 16" [406.4mm] 19" [482.6mm] ® � ® n n rn i i 5" [127.Omm] 1 3#" [88.9mmJ 10" [254.0mm] 6J" [168.3mmJ 3}" [88.9mmJ 11 " [295.3mm] 11" [279.4mmJ 4J" [1 14.3mm] 17" [431.8mmJ 15" [381.0mm] 1 1" [279.4mm] 4 " [1 14.3mmJ 181" [473.fmm] 15J" [403.2mm] 350DIM 35 TDIM_A 707PGIIIC NOTE.TOP DIMENSION LINE APPLIES TO 4" VALVE. BOTTOM DIMENSION LINE APPLIES TO 6" VALVE. 3. TO SYSTEM 31 WHEN MECHANICAL SPRINKLER ALARM IS NOT USED 45 I F� Y ?2 WHEN ELECTRIC SPRINKLER 39 ALARM IS NOT USED J 21 43 9 IJ 39 32 39 REMOVE THIS PLUG 28 20 Y'A j4 TO CONNECT TO AN (� ACCELERATOR PER 39 39 BULLETIN 322 29 22 17 \ 5 �28 r� f. 1 40 I I J9 7A J J7 18 29 i /39 78 36 J9 47 42 1 12 26 10 37 1 / 16 41 39 JJ 21 1 44 J 3 43 /25 2 44 14 r9 44 J JI TO 10 44 48 REMOVE THIS PLUG DRAIN 1-1/4" NPT 78 TO INSTALL AN ELECTRIC NON-SILENCEABLE ALARM JJ FROM PRESSURE SWITCH 350FOB-D SUPPLY Figure B 4 16 J6 Jb 8 rJ S6 30 2J REMOVE THIS PLUG WHEN CONNECTING A VALVE ROOM SPRINKLER LINE OR AN 81 ACCELERATOR ACCORDING TO BULLETIN J22 36 83 15 62 J5 S- Q \ 83 I o JSOFiGC-A I JSOFCO-A 8b Figure C Figure D 4. Reliable Model D Dry Pipe Valves—Model D Basic Trim (See Figures B&C) (Trim Parts Without Priming Chamber & Fill Line Attachments) P/N 6501050100 Item te 'd Item No. No. Part No. Description No. Part No. Descri tion Re 'd 1 75000050 Primin Cu ,112" 25 98174404 Elbow, '/a"Galv. 1 2 71010471 Dri Cu Assembl 26 98815201 Union,Malleable Iron GJ,'/4" 1 3 78653100 Mechanical Ball Dri Valve,'/2" 27 98815202 Union,Malleable Iron GJ 3/4" 1 4 988401901 Relief Valve Bronze,1/2" 1 28 198164406 101.Brass,Male Comp.Type,%6"x'/a' 2 5 98840105 Ball Valve,112" 1 29 98768005 Tubing,Copper,3/16"x 15"Lg. 2 6 98840100 Valve,Angle,Bronze,2" 1 30 98604405 Plug, 1" 1 7 98840101 Valve,Angle,Bronze 1/4" 2 31 98614401 Plu ,3/4" 1 8 98840170 Valve,Globe,Bronze,3/4" 1 " 3 9 98840171 Valve,Globe,Bronze,1/2" 1 32 98604401 33 98614406 Plu ,'/Plu ,'/2" 3 10 98840160 Valve Gau e Bronze,Three Wa 1/4"' ' 2 34 98543238 Nipple,2"x Close 1 11 98840180 Valve Horiz.,Check,Bronze,3/4" 1 35 98543222 Nipple. 1"x 31/2" 1 12 98840181 Valve,Horiz.,Check,Bronze,'/2" 1 36 98543215 Nipple,3/4"x 11/2" 4 13 98248000 Gau e,Pressure,Air 1 37 98815200 Union,1/2" 1 14 98248001 Gaucle,Pressure,Water 1 38 98543209 Nipple,1/2"x 2" 1 15 96606602 1"x 3/a"x 1"Galv. 1 39 98543223 Nipple,'/2"x 11/2" 11 16 96606604 3/4"x 3/4"x'/2"Galv. 1 40 98543224 Nipple,'A"x 41/2" 1 17 96606603 1/2'x'/2"x 3/4"Galv. 2 41 98543210 Nipple,1/2"x 21/2" 1 18 98761651 1/2"x 1/2"x 1/2"Galv. 3 42 98543225 Nipple,'/a"x 21/2' 1 19 198761649 '/2"x 1/a"x 1/2"Galv. 1 43 98543244 Nipple,'/4"x 2" 2 20 96606607 1/2"x'/2"x 1/4"Galv. 1 44 198543226 Nipple,'/4"x 11/2" 5 21 96606608 '/4"x'/4"x'/4"Galv. 3 45 198543279 Nipple,3/4"x Close 2 22 98048000 BushinCj Reducer,1/2"x 1/4" 1 1 46 - 23 98174402 1 Elbow, 3/4"Galv. 1 47 98543207 Ni le,1/2'x 4" 1 24 98174401 Elbow, '/2" Galv. 1 48 98543241 �14pple,'/4"x 5" 1 I Priming Chamber Attachment (See Fig-D) Fill Line Attachment (See Fig.D) P/N 6501080100 P/N 6501070100 Item Item No. Part.No. Description No. Req. No. Part.No. Description No. Req. 81 71010432 Priming Chamber 1 84 1 98840101 Valve, Angle, Bronze, 1/4" 1 82 98840171 Valve, Globe, Bronze, 1/2" 1 85 98543226 Nipple. Steel, 1/4"x 1'/2" 1 83 98543223 Nipple, Steel, 1/2"x 11/2" 2 86 98164406 Ell, Brass, Male Comp.Type, 1 3/16"x 114" 87 98768001 1 Tubing, Copper, 3/,6"x 42" 1 Table 2 -Water/Air Pressure Water Pressure Air Pressure Water Pressure Air Pressure in Supply Line To be Pumped into System in Supply Line To be Pumped into System psi bar psi(bar) psi(bar) psi(bar) Maximum Not less than Not more than Maximum Not less than Not more than 20(1,38) 10(0,68) 20(1,37) 125(8,62) 30(2,06) 40(2,75) 50(3,44) 15(1,03) 25(1,72) 150(10,34) 35(2,41) 45(3,10) 75(5,17) 20(1,37) 30(2,06) 175 12,06 40(2,75) 50(3.44 100(6,89) 25(1,72) 35(2,41) Note:41,(100mm)and 6"(150mm)Model D Dry Pipe Valves are identical in general design and operation. Maximum water pressure to which the system is liable to be subjected should be taken instead of normal pressure.Fire pumps usually provide pressure in excess of 125 psi(8,62 bar). Maintenance Dry pipe systems, as a minimum, shall be tested and • Quarterly main drain flow test. maintained in accordance with NFPA 25, which • Quarterly water flow and low air alarm test. provides minimum inspection,testing and maintenance • Draining of all low point drains as frequently as necessary. requirements. These requirements include: • Annual dry pipe valve trip test, inspection, cleaning, parts renewal as required and valve reset. 5. Resetting the Model D Dry Pipe Valve Figures B, C and E show the trim and valve parts in Observe if water leaks through Ball Drip Valve(3)into their normal positions. Drip Cup (2). If no leak occurs, the air seat is tight. 1. Close valve controlling water supply to dry pipe Note: If an Automatic Air Pressure Maintenance Device valve. is used,Valve(8)should be left open. See Bulletin 251 2. Open Main Drain Valve(6),Fig C,and drain system. for information on this device. 3. Open all drain valves(remove plugs)and open vents 12. Open slightly the valve controlling the water supply to at low points throughout the system, closing them the dry pipe valve,closing Main Drain Valve(6)when when flow of water has stopped. water flows. Observe if water leaks through Ball Drip 4. Push in plunger of Ball Drip Valve(3), Fig. B,to force Valve (3) into Drip Cup (2). If no leak occurs, the air ball from its seat. and water seats are tight. Open slowly, but fully,the 5. Release Cover (3) and raise Clapper Assembly (5), valve controlling water supply to the dry pipe valve Fig. E, to wide open position by lifting under the and seal in the OPEN position. rubber facing. Thoroughly clean air and water seats Tests in making certain that they are free from scale, dirt, To test the operation of the dry pipe valve and its lint,etc. Inspect and clean or replace rubber facing. alarm equipment, open the inspectors test Never apply grease, compound, shellac, or any oily connection which should cause the mechanical and substances to seats or rubber facing. electric alarms to sound. This test connection is Note: If replacement is necessary, see parts removal. usually located on the end or top line of the system 6. Release Lever Latch by holding clapper slightly and is equivalent to the operation of one sprinkler. above the top latch stop in the body. Push the front The main control valve must be completely open to tip to the latch down and hold the latch in this tipped allow sufficient flow for the clapper to latch open. position. Lower the clapper onto the seat. Following this test, the system must be drained and 7. Center the locating diameter of the Clapper Rubber the dry pipe valve reset. Facing (6), around the water seat. The Clapper As- To test the operation of the alarm equipment only, sembly (5) should sit flat and with a minimum of without operating the dry pipe valve,open Valve(713), movement when the seating is correct. Figure B. Should the mechanical sprinkler alarm fails 8. Replace Gasket (4) and Cover (3) and uniformly to operate, inspect Valve (25) for complete opening tighten Cover Bolts (2). and the stainer for clogging. 9. Open Valve(9), Fig. B. Fill body of dry pipe valve by Parts Removal pouring water through Priming Cup (1) until water Refer to Figure E. flows into Drip Cup (2) from open Valve (7A), To remove the Clapper Assembly(5)and the Seat(9), indicating that priming water is at the proper level. proceed as follows: Close Valves(9)and(7A). If priming water continues 1. Clapper Assembly: With the cover removed, the to flow out of the ball drip valve, this means that the Hinge Pin (12) can be slipped out of its rubber facing is not sealing at the air(outer)seat. To bushings. Prior to this operation, a piece of correct this, return to Step"5", remove the cover and heavy cardboard or rubber should be placed on re-inspect the rubber facing. Replace the facing if the Seat (9) to protect its sealing surfaces. required. If the facing appears acceptable,it may be Put the Clapper Assembly (5) on the upper latch deformed. Pull the outer edge of the rubber down, stop, and push clapper to left so that the latch away from the clapper, so that the rubber contacts moves to the downward position. Then rotate the the air seat when the clapper is reset. clapper until the bearing legs are at the front of the Note: When Dry Pipe Valve is equipped with Priming valve. The clapper can then be removed through Chamber Attachment(Fig. D), follow same procedure, the cover opening. but open and close Valves(9)and (82). Note: If replacement of the rubber facing is 10. Open Valve (8) and admit a few pounds of air required do not over tighten clamping ring bolts. pressure into the sprinkler system. Close Valve(8). Tighten to 30 in-lbs. (3.39N.m). If a torque wrench Open separately all drain valves(see Step "3")to is not available, tighten bolts finger tight, and then force any water from low points of the system. an additional 1/8 of a turn only. Close these valves when dry air appears and 2. Seat: With the clapper removed, the seat can be replace plugs in valve outlets. easily unscrewed from the body with the use of 11. Open Valve(8)Fig.C,and admit sufficient air into the the Reliable Model D Dry Valve Seat Wrench sprinkler system to hold the dry pipe valve closed [P/N 6881340000 for the 4" (100mm) size; P/N 1 against the water supply pressure in accordance with 6881360000 for the 6" (150mm) size]. 1 Table 2,Water-Air Pressure. The level of air pressure Be careful not to damage the seat during this operation. is adjusted by removing the cap nut on the top of the Prior to replacing the seat, the threads on the body Relief Valve(4), and turning the now exposed,slotted and the seat should be cleaned and lubricated, and adjusting screw clockwise to increase pressure or new lubricated "O"-rings (10) and (11) should be counterclockwise to reduce it. Replace the cap, nut used. White petroleum jelly is an effective lubricant. and close Valve (8) after the correct air pressure setting has been made according to NFPA 13. 6. I t {-----------f- r-1-----------1-' I i l 1 I I I 1 I I 5 RELIABLE* AUTOMATIC 2 WT. SPRINKLER CO.YORK I \•, 3 MODEL D 9Y 40 ®USTED rasa 706A N 4 Ixcx ®K 4 F M 12 DRY rIrE 13 V 175 PSI 6 9 I 7 8 11 I 10 I I L---T- ----- -----T-T--� _ I C \ � 350FGE-B Flanged Inlet & Grooved Outlet Flanged Inlet & Outlet Figure E Item Part No. Part No. Description No. Required No. 4"Size 6"Size Dry Pipe Valve Parts 4"Size 6"Size 91006225 91006227 Body Flanged 1 91006214 91006216 Flanged and Grooved 1 1 91006222 91006223 Metric 100 mm 150 mm 2 91106124 91106126 Cover Bolts 7 8 3 92116224 92116226 Cover 1 1 4 93706224 93706226 Cover Gasket 1 1 5 71010423 71010623 Clapper and Latch Assembly 1 1 6 93406224 93406226 Clapper Rubber Facing 1 1 7 95306224 95306226 Clamping Ring 1 1 8 95606224 95606224 Clamping Rino Screws 8 8 9 96016224 96016226 Seat 1 1 10 95446224 95446226 Seat"0" Ring 1 1 11 95436224 95436226 Body"0" RinQ 1 1 12 95006224 95006226 Hinge Pin 1 1 13 1 98614402 98614402 1/2"Pipe Plug 1 1 Contact the installing contractor or Reliable if any difficulties are experienced. Should replacement parts be needed, use only Reliable manufactured parts.When ordering, specify part number, name, size, model and serial number of the unit. 7. Reliable . . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and propertyfrom fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connections The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances,whenever applicable. Products manufactured and distributed by RELIABLE have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co.,Inc. Recycled Paper (800)431-1588 Sales Offices Printed in U.S.A. �" ' ( )8 - 051 Sales Fax (914914)82929-2042 Corporate Offices Revision lines indicate update or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A. 12/11 PN 9999970044 Ammw AIR PRODUCTS OL Plus Series - Single Phase Riser Mount Air Compressors for Dry Pipe Sprinkler Systems A-O s This oilless riser mounted air ' ° compressor is UL1450 listed Y L p for use in sprinkler systems. Series - Oil Less Piston Compressor - Integrated Air Intake Filters - UL Listed Pressure Switch - Customized Motor Windings - Riser Mounting Kit included - Fully automatic, direct drive - Bubble tight air check valve - 60 Hz (cycle) - Permanently lubricated bearings - Max Pressure: 50 PSI - Specifically designed to fill the system to 40 PSI in 30 minutes System Model Average Motor Minimum Dimensions Weight Wire Capacity"* Number CFM* HP Size + L W H (Ibs) 125 gal. OL12516AC 1.52 1/6 12 16" 12" 12" 30 250 gal. OL25033AC 3.03 1/3 12 16" 12" 12" 31 365 gal. i OL36550AC 4.43 1/2 12 16" 15" 10" 38 430 gal. OL43075AC 5.21 3/4 10 17" 15" 10" 48 615 gal. OL615100AC 7.46 1 6 17" 15" 10" 48 915 gal. OL915150AC l 11.10 1 1/2 6 1 23" 15" 10" 60 1225 gal. 01-1225200AC l 14.85 2 10 24" 15" 11" 70 Accessories Required By Code: Magnetic Line Starters - Thermal Overload Protection `7 H Single Phase 115V 2081230V Size Model 4 w 1/3 HP 1 HP 00 MGOOA Maximum 1 HP 2 HP 0 MGXOA VOLTAGE:All Units 115 or 208-230 Volt except HP 2 HP 3 HP 1 MG01A OL1225200AC which is 208-230 only. 3 HP 5 HP 1P MG15A When Ordering a Motor Starter you must specify *Average CFM is the average free air delivery HP Voltage and Phase that is supplied to the motor. from 0 to 40 PSIG. + Based on 100 foot run at weakest electrical supply. Air Maintenance Device Consult Factory for longer or shorter runs. Part#AMD-1 **Based on 70 degree F system temp. Our UL Listed / FM Approved AMD-1 air maintenance device is recommended For other conditions consult factory for pump up times. for all riser mounted compressor ++OLRTK Riser Tank Kit may be required, consult factory. installations++. I www.generalairproducts.com 1-800-345-8207 Oil Worldwide wwwtyco-fire.com Contacts Model RM-1 Riser Manifold Commercial and Residential Optional Pressure Relief Kits feature a General 175 psi pressure relief valve and trim Description components for convenient integration f 1 into commercial and residential riser ; J The TYCO commercial and residential manifold assemblies. Model RM-1 Riser Manifold provide The pressure relief valve, installed in the necessary waterflow alarm, pres- manifold assemblies above the nor- p sure gauge, alarm test orifice, drain, mally closed test and drain or drain A and sight glass equipment in a single valve, automatically bleeds system assembly for use in NFPA 13 com- pressure exceeding 175 psi through a 1li1 - mercial sprinkler systems and in NFPA flexible hose connected to the mani- 13D/13R residential sprinkler systems fold drain outlet(Ref. Figure 5), reduc- as follows: ing system pressure to 175 psi. NFPA 13" • 1-1/2 in.(DN40) MUM Male Thread x Female Thread The Model RM-1 Riser Manifolds • 2 in.-6 in. (DN50-DN150) described herein must be installed f 1 Groove x Groove and maintained in compliance with this document,as well as with the applica- NFPA 13D ble standards of the NATIONAL FIRE • 1 in. (DN25) PROTECTION ASSOCIATION (NFPA), Female Thread x Female Thread in addition to the standards of any other NFPA 13R authorities having jurisdiction. Failure / • 1-112 in. (DN40) to do so may impair the performance Male Thread x Female Thread of these devices. • 2 in. (DN50) The owner is responsible for main- Groove x Groove taining their fire protection system and devices in proper operating con- Although the Riser Manifold described in this techni- dition. Contact the Installing contrac- cal data sheet is intended for NFPA 13 sprinkler sys- tems,it may be used for NFPA 13D or 13R residential p y sprinkler systems,where a test orifice of 2.8K or 4.2K questions. is acceptable. The variety of sizes and grooved end Technical connections allow cost effective and easy transition to check valves,control Data valves, and system piping. The Model RM-1 Riser Manifolds may be installed Approvals either horizontally (flow switch on top) UL and ULC Listed or vertically(flow going up)orientation, FM Approved for both single sprinkler rises and floor Listed by California State Fire Marshall control in high-rises. Maximum Working Pressure 300 psi(20,7 bar) Test Orifice 1 in.-3 in.(DN25-DN80)Manifolds:2.8K 4in.-6 in.(DN100-DN150)Manifolds:4.2K Finish Red Painted IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Page 1 of 8 AUGUST 2018 TFP963 TFP963 Page 2 of 8 Nominal NO DESCRIPTION P/N Nominal Dimensions Drain 1 300 psi/2000 kPa Nominal End Inches Size Water Pressure Gauge..90050001 Riser Connections Size (mm) Inches 2 Test and Drain Valve, Inches (DN) Model TD-1: (DN) 1-1/2-3 Inch Inlet Outlet A B C D E F G H (DN40-DN80) 1-1/2 Thread Thread 10 15-1/2 2-1/4 5-5/8 8-3/8 15 4-3/8 1-1/4 Size Manifolds, 40 MNPT FNPT (254) (394) (57) (143) (213 (381) (111 (32) 1-1/Inch KOrifice.....A61G0420 ( ) ) ) 4-6 Inch 2 13 18 2-1/16 5-5/8 8-3/8 15-1/4 4-3/8 1-1/4 (DN100-DN150) (50) Groove Groove (330) (457) (53) (143) (213) (388) (111) (32) Size Manifolds, 2",4.21K Orifice........A61G0601 2-1/2 Groove Groove 13 18-1/16 2-1/16 5-5/8 8-3/8 15-1/4 4-3/8 1-1/4 3 Flow Switch,VSR-M: (65) (330) (460) (53) (143) (213) (388) (111) (32) 1-1/2"(DN40).........91144815 3 13 18-1/16 2-1/16 5-7/8 8-5/8 15-3/4 4-3/8 1-1/4 2"(DN50) ............91144802 (80) Groove Groove (330) (460) (53) (150) (219) (400) (111) (32) 2-1/2"(DN65).........91144825 3"(DN80) ............91144803 4 13 20-1/4 4-1/4 6-3/4 10-3/4 18-3/8 5-3/16 2 4"(DN100)...........91144804 (100) Groove Groove (330) (514) (108) (172) (273) (467) (132) (50) 6"(DN 150)...........91144806 6 13 20-1A 4-1/4 7-3/4 11-3/4 21 6-3/4 2 4 Field Replaceable (150) Groove Groove (330) (514) (108) (197) (300) (533) (172) (50) Retard/Switch.........91144800 OUTLET 1 OPTIONAL PRESSURE ° RELIEF TRIM CONNECTION O o 3,4 B A 2 O O � � o INLET C G H D E F FIGURE 1 MODEL RM-1 COMMERCIAL RISER MANIFOLDS 1-112-6INCH(DN40-DN150) TFP963 Page 3 of 8 OPTIONAL PRESSURE RELIEF TRIM 1"NPT 1 CONNECTION (FEMALE) NO DESCRIPTION P/N 2 T 1 300 psi/2000 kPa 10" � 11 Water Pressure Gauge..90050001 (254 mm) 0 (280 mm) 2 Ball Valve,1"(DN25)....97111603 C 3 Flow Switch,VSR-M, 1"(DN25) ............91144801 4 Field Replaceable 1 Retard/Switch.........91144600 2-1/2" (64 mm) NPT DRAIN 3-3/4" 3-7/8" (96 mm) 1"NPT 3,4 (100 mm) 4-5/8" (FEMALE) (118 mm) 10-1/8" (257 mm) FIGURE 2 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1 INCH(DN25) OPTIONAL PRESSURERELIE 1 ONNFT IO (FEMALE) NPT CONNECTION (FEMALE) 1 0 13-1/4" (337 mm) NO DESCRIPTION P/N 1 300 psi/2000 kPa 10" t Water Pressure Gauge..90050001 (254 mm) 2 Ball Valve,1"(DN25)....97111603 2 3 Flow Switch,VSR-M, 1-1/2"(DN40).........91144815 4 Field Replaceable 7/16" Retard/Switch .....91144800 (11 jmm) _I 3-7/8" 3-7/8" 3,4 (100 mm) 1« (100 mm) 1-1/2" NPT NPT 4-3/4" (MALE) DRAIN r—(121 mm) 11-3/8" (290 mm) FIGURE 3 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1-1121NCH(DN40) TFP963 Page 4 of 8 1 2" (GROOVED) FA OPTIONAL PRESSURE o RELIEF TRIM CONNECTION 1 m 16" *0 (406 mm) NO DESCRIPTION P/N 13" / 1 300 psi/2000 kPa (330 mm) Water Pressure Gauge..90050001 2 Ball Valve,1"(DN25)....97111603 3 Flow Switch,VSR-M, 2"(DN50) ............91144802 2 4 Field Replaceable Retard/Switch.........91144800 1/2" 4 (13 imm) 1 i � 1 3-7/8" I 4-1/8" 3,4 (100 mm) 1• (105 mm) 2" NPT 5" (GROOVED) DRAIN (127 mm)~ 11-7/8" (300 mm) FIGURE 4 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 2 INCH(DN50) Notes: Step 1. Install the manifold body with Manifold Where applicable pipe thread sealant the flow arrow pointing in the down- Installation is to be applied sparingly. Use of a stream position using threaded con- non-hardening pipe thread sealant is nections and/or listed mechanical TYCO Model RM-1 Riser Manifold recommended. grooved connections,as applicable. must be installed in accordance with Never remove any piping component Step 2. Connect the drain line and on this section. nor correct or modify any piping defi- commercial manifolds set the Model The Model RM-1 Riser Manifold may be ciencies without first depressurizing TD-1 Test and Drain Valve to the OFF installed either horizontally(flow switch and draining the system. position or on residential manifolds on top)or vertically(flow going up).The close the drain valve. Residential Models must be made. inlet of the Riser Manifold may be con- Provisions for an alarm test flow e. Step 3. Refer to Figure 6 for wiring wiring nected directly to a shut-off control The alarm test flow is to be through guidance.All with the must be performed an orifice having a flow capacity equal accordjurisdiction and/or the National ity having ni- to or smaller than the smallest orifice cal Code. sprinkler in the system. One of two options can be considered. The first Step 4. Refer to Figure 5 for Optional option is to temporarily install a test Pressure Relief Trim installation. orifice in the outlet of the drain line Step 5. Place the system in service prior to performing the alarm test. The by filling the system with water. When second option is to install an Inspec- filling the system, partially open the tor's Test Connection downstream of control valve to slowly fill the system. the Waterflow Alarm Switch. Filling the system slowly will help avoid damaging the waterflow alarm switch. After the system is fully pressurized, completely open the control valve. Step 6.Secure all supply valves open. TFP963 Page 5 of 8 Commercial Riser Manifolds Residential Riser Manifolds NO DESCRIPTION P/N NO DESCRIPTION P/N 1 Pressure Relief Valve, 1 Pressure Relief Valve, 175 psi,1/2"NPT.... ..1001184-01 175 psi,1/2"NPT..........1 001 1 84-01 2 1/2"x Close Nipple ........1001023-01 MODEL RM-1 2 1/2"x Close Nipple,Oty 2...1001023-01 3 Flexible Hose: COMMERCIAL 3 Flexible Hose,1/2"x 16"....1001266-03 1-1/2-3 Inch(DN40-DN80) RISER MANIFOLD 4 Figure 815 Threaded Size Manifolds, 2 Reducing Tee, 1/2"x 24..................1001266-02 1 1"x 1"x 1/2"NPT.........1001259-07 4-6 Inch(DN100-DN150) `� 5 1"x Close Nipple..........1001025-01 Size Manifolds, i 1/2"x 30..................1001266-01 4 Figure 323 Reducing Tee, MODEL RM-1 Grooved x NPT Threaded: I RESIDENTIAL 1-1/2-3 Inch(DN40-DN80) RISER MANIFOLD Size Manifolds, 2 1-1/4"x 1-1/4"x 1/2".......3231305GS 4-6 Inch(DN100-DN150) a = 1 1 Size Manifolds, 2"x 2"x 1/2.. .............3232005GS / 5 Figure 577 Rigid Grooved 3 Coupling: 5 I 1-1/2-3 Inch(DN40-DN80) 4 Size Manifolds, 1-1/4.....................57713AGCP 3 4-6 Inch(DN100-DN150) Size Manifolds, 2 ' \ 2" ......................57720AGCP 5 4 FIGURE 5 MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLDS OPTIONAL PRESSURE RELIEF TRIM INSTALLATION Optional Commercial Manifolds Residential Manifolds Refer to Figure 1 for commercial riser Refer to Figures 2, 3 or 4 for residen- Pressure manifold features and Figure 5 for pres- tial riser manifold features and Figure sure relief trim components described 5 for pressure relief trim components Relief Trim in this procedure. described in this procedure. Installation Step 1. Remove 1/2 in.pipe plug from Step 1. Remove 1/2 in.pipe plug from manifold tee. Inspect exposed female manifold tee. Inspect exposed female Model RM-1 commercial and resi- tee threads, remove thread sealant tee threads, remove thread sealant dential riser manifold assemblies are remnants or debris as necessary. remnants or debris as necessary. designed to accommodate an optional Step 2. Install Pressure Relief Valve(1) Step 2. Install Pressure Relief Valve(1) pressure relief valve and trim compo- in manifold tee, orienting valve outlet in manifold tee, orienting valve outlet nents(Ref.Figure 5). port perpendicular to and facing away port perpendicular to and facing away Optional pressure relief trim must be from manifold body. from manifold body. installed in accordance with the follow- Step 3. Install 1/2 in. x Close Nipple Step 3. Disconnect drain piping from ing procedures. (2)in pressure relief valve outlet port. threaded outlet of manifold drain valve Notes: Step 4. Disconnect drain piping from as applicable and install 1 in. x Close For assembly in Riser Manifolds grooved outlet of manifold TD-1 test Nipple(5)in valve outlet. installed and in service, verify the fire and drain valve as applicable and install Step 4. Install Figure 815 Reducing protection system is de-pressurized Figure 323 Grooved Reducing Tee (4) Tee(4)onto 1 inch x close nipple,align- and drained. Close the system supply on valve outlet by securing with Fig- ing tee branch outlet parallel with pres- control valve,set commercial manifold ure 577 Grooved Coupling (5), align- sure relief valve outlet port. Reconnect test and drain valve to DRAIN or open ing tee threaded branch outlet parallel drain piping to Figure 815 tee drain out- residential drain valve to relieve resid- with pressure relief valve outlet port. let as necessary. Reconnect drain piping to Figure 323 Ste 5. Install 1/2 in. x Close Nipples ual pressure and drain system. Make P PP tee drain outlet as necessary. 2 in pressure relief valve outlet port - certain that drainage water will not ( ) P cause any damage or injury. Note: Refer to Technical Data Sheet and in Figure 815 reducing tee branch Refer to Care and Maintenance section G901 for Figure 577 Grooved Coupling outlet. for other requirements when closing a installation and assembly instructions. Step 6. Install Flexible Hose (3) by fire protection system control valve and Step 5. Install Flexible Hose (3) by threading female ends onto 1/2 in. x placing system in service. threading female ends onto 1/2 in. x close nipples installed on relief valve Apply thread sealant or TEFLON tape close nipple installed on relief valve outlet port and Figure 815 reducing tee on all threaded connections, with the outlet port and onto Figure 323 reduc- branch outlet. exception of internally sealed flexible ing tee branch outlet. Note.Assure Flexible Hose is not sus- hose connections. Note:Assure Flexible Hose is not sus- ceptible to being caught or snagged by ceptible to being caught or snagged by other moving equipment. other moving equipment. TFP963 Page 6 of 8 SWITCH TERMINAL CONNECTIONS UNINSULATED CLAMPING SEVERED LOOPED SECTION CAUTION: PLATE STRIPPED SINGLE An uninsulated section of a TERMINAL ENDS CONDUCTOR single conductor is not � SEPARATE permitted to be looped around CONDUCTORS CLAMPING the terminal and serve as two PLATE \ separate connections.The TERMINAL \�`��\� wire must be severed to serve INCOMING \ as two separate connections, thereby providing supervision of the connection in the event that the wire becomes dislodged from the terminal. OUTGOING IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD WIRE NUT LOCAL WIRE NUT FIRE PANEL OR AUDIBLE/VISUAL ADDRESSABLE ANNUNCIATOR MODULE NEUTRAL ¢ WHITE WHITE BLACK M Lu j� U� ¢ JJl M co Oa¢ (iJ BLACK H D O (LINE/HOT) j S Q 0 0 J z OEZ Q¢ O OO OO CONTACT RATINGS: 00 Two sets of SPDT(Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min.at 24VDC q0 NC C M I Oto NC mop -�NOTE: When connecting to a UL Listed control panel, use panel resistor rating for circuit supervision NOTE: For supervised circuits,see"Switch Terminal Connections"above.The Waterflow Alarm Switch has two switches,one can be used to operate a central station,proprietary or remote signaling unit,while the other contact is used to operate a local audible or visual annunciator. FIGURE 6 MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLD WIRING GUIDANCE TFP963 Page 7 of 8 7000 0W00 0 0� 0_4 0 0 3!0 531 Nn OFF MARKING TEST MARKING DRAIN MARKING ON HANDLE ON HANDLE ON HANDLE 0 POSITIONED POSITIONED POSITIONED ON DETENT ON DETENT ON DETENT MODEL TD-1 0 0 0 O O O O TEST AND DRAIN I VALVE O O Q O O O O --�_ SIGHT �� FLOW 0 C t O O O O DRAIN SET TEST CONNECTION DRAIN FRONT CONDITION CONDITION CONDITION VIEW FIGURE 7 MODEL RM-1 COMMERCIAL RISER MANIFOLD TD-1 TEST AND DRAIN VALVE OPERATION Care and tion to the standards of any authority of the NFPA,and any impairment must having jurisdiction.Contact the install- be immediately corrected: ing contractor or product manufacturer Alarm/Flow Test Procedure Maintenance with any questions. Step 1.Place the Model TD-1 Test and TYCO Riser Manifolds RM-1 must be It is recommended that automatic Drain Valve in the TEST position (Ref. serviced and maintained in accordance sprinkler systems be inspected,tested, Figure 7). On residential assemblies with this section. and maintained by a qualified Inspec- without a test orifice,temporarily install Before closing a fire protection system tion Service in accordance with local a test orifice in the drain outlet and fully control valve for inspection or main- requirements and/or national codes. open the Drain Valve. Make certain tenance work on the fire protection Note: No attempt is to be made to that drainage water will not cause any system that it controls, permission to repair any Riser Manifold component damage or injury. shut down the effected fire protection in the field. Only the pressure gauge, Step 2.Verify operation of associated system must first be obtained from waterflow alarm switch, or relief valve alarms. the proper authorities and all person- can be replaced.If any other problems Step 3. Verify that the residual (i.e., nel who may be affected by this action are encountered the entire riser mani- flowing)pressure indicated by the pres- must be notified. fold must be replaced. sure gauge is no less that originally After placing a fire protection system The alarm/flow test procedure will recorded for the system when it was in service,notify the proper authorities result in operation of the associated first installed. and advise those responsible for moni- alarms. Consequently, notification Step 4. Close the Drain Valve on the toring proprietary and/or central station must be given to the owner and the fire Residential models and the Test and alarms. department, central station, or other Drain valve on commercial models. The owner is responsible for the signal station to which the alarms are inspection,testing,and maintenance of connected, and notification must be Step 5. Verify that the static (i.e., not their fire protection system and devices given to the building occupants. flowing)pressure indicated by the pres- in compliance with this document, as The following inspection procedure sure gauge is less that originally well as with the applicable standards must be performed as indicated, in recorded for thea system when it was first installed. of the NATIONAL FIRE PROTECTION addition to any specific requirements ASSOCIATION(e.g.,NFPA 25),in addi- TFP963 Page 8 of 8 Limited Orderinry Optional 175 psi Pressure Relief Kit 7 Specify: Pressure Relief Kit, Model Warrant Procedure RM-1 Riser Manifold,(specify Commer- ,Y cial or Residential application),(specify For warranty terms and conditions,visit Contact your local distributor for avail- size range), P/N(specify): www.tyco-fire.com. ability. When placing an order, indi- Commercial cate the full product name, including 1-1/2 in.-3 in.(DN40-DN80) 40721 description and part number(P/N). 4in.-6 in.(DN100-DN150) 40731 Residential Riser Manifolds 1 in.-2 in.(DN25-DN50) ............ .40711 Specify:Size(specify)Connection Type Replacement Parts (specify inlet x outlet)Model RM-1 Riser Specify: Model RM-1 Riser Manifold Manifold, P/N(specify): (specify part description), P/N (specify Commercial from Figures 1,2,3,4 or 5) 1-1/2 in.(DN40)MT x FT..............40551 2 in.(DN50)G x G ...................40601 2-1/2 in.(DN65)G x G ................40611 3 in.(DN80)G x G ...................40621 4 in.(DN100)G x G ..................40651 6 in.(DN150)G x G...................40661 Residential 1 in.(DN25)FT x FT........... ......40671 1-1/2 in.(DN40)MT x FT..............40571 2 in.(DN50)G x G ...................40591 1400 Pennbrook Parkway,Lansdale,PA 194461Telephone+1-215-362-0700 0 2018 Johnson Controls.All rights reserved.All speoificalions and other information shown were ourrent as of document revision data and are subject to change without notice. Johnson ,' NATIONAL FIRE PROTECTION A OOIATION and NFPA ere reglatered trademarks of National Mrs Pmtacdan Association; Controls TEFLON Is a registered Iredemark of DuPont FOR SMALL PIPE VSR—S (OPOTTER . VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL,ULC,CSFM Listed and NYMEA Accepted Service Pressure: Up to 300 PSI(20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive 1 OmAmps min.at 24 VDC Conduit Entrances:Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic,copper and schedule 40 iron pipe. Fits pipe sizes-V(25mm), 1 1/4"(32mm), 1 1/2"(38mm) and 2"(50mm) Stock No. 1144440 Note: 12 paddles are famished with each unit,one for each pipe size of threaded and sweat TEE,one for 1"(25mm)CPVC, one for 1"(25mm)CPVC(Central),one for 1"threaded Nibco +. �`�hh/� p CPVC,and one for 1 1/2"(38mm)threaded(Japan). YYQf1N�NG Environmental Specifications: • NEMA-4/IP54 Rated enclosure suitable for indoor or outdoor Installation must be perfomed by qualified personnel and in use with factory installed gasket and die-cast housing when used accordance with all national and local codes and ordinances. with appropriate conduit fitting. Shock hazard. Disconnect power source before servicing. Temperature range:400 F to 1200 F,(4,50 C to 490 C)UL Serious injury or death could result. Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NFPA-13 injury or death could result. One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional:Cover Tamper Switch Kit,Stock No.0090148 (See Fig.7 for terminations) Replaceable Components:Retard/Switch Assembly,stock no.1029030 The Model VSR-S is a vane type waterflow switch for use on wet Installation sprinkler systems that use 1"(25mm), 1'/4"(32mm), 1'/z"(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On (50mm)pipe size.The unit may also be used as a sectional waterflow horizontal pipe they should be installed on the top side of the pipe where detector on large systems. they will be accessible.The units should not be installed within 6"(15 cm) The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the waterflow. an adjustable, instantly recycling pneumatic retard. The switches are Select the proper paddle for the pipe size and type of TEE used see Fig. actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The unit has a 1"NPT bushing downstream of the device.The flow condition must exist for a period of for threading into a non-corrosive TEE.See Fig.2 for proper TEE size, time necessary to overcome the selected retard period. type and installation.Use no more than three wraps of teflon tape. Enclosure Screw the device into the TEE fitting as shown in Fig.2.Care must be The VSR-S switches and retard device are enclosed in ageneral purpose, taken to properly orient the device for the direction of waterflow. die-cast housing.The cover is held in place with two tamper resistant The vane must not rub the inside of the TEE or bind in any way.The screws which require a special key for removal.Afield installable cover stem should move freely when operated by hand. tamper switch is available as an option which may be used to indicate The device can also be used in copper or plastic pipe installations with unauthorized removal of the cover. See bulletin number 5401103 for the proper adapters so that the specified TEE fitting may be installed installation instructions of this switch. on the pipe run. • Note:Do not leave cover off for an extended period of time. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG #5401206-REV G PAGE 1 OF 3 12/08 FOR SMALL PIPE VSR—S (E) POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig.1 Fig.2 Retard Adjustment IX)NOT LEAVE COVER OFF FOR FXTENDED PERIOD OFTIME FL�w "u'� ArrRu. y The time delay is factory set at 30±10 seconds. COVER TAMPER SWITCH The delay can be adjusted by rotating the retard — adjustment knob from 0 to the max setting(60- 90 seconds).The time delay should be set at the minimum required to prevent false alarms. Screw the device into the tee fitting as shown. Care must be taken to properly orient the DIRECTION OF MOUNT SO device for the direction of waterflow.On sweat WAFER FLOW ARROW ON HUSHING POINTS tees,no threaded bushings,inserts,or adapters IN DIRECTION OF WATERFOW are permitted,unless they comply with the dimensions listed in the chart below. °WQtl"'" TFIREA ED Important-The depth to the inside bottom of FITTING ON the tee should have the following dimensions: ALL AWARNING OF TES o RUN OF THE TEE Appro.imalc Deplh Requirement MAY HE Them are 12 paddles fim ished with each unit THREADED OR T.Sire Threadcd Sweat CPVC SWEAT PIPE One for each size of threaded,sweat or plastic IRECTION OF 2 u16• 1 3/4" 2 7/16" TEE as described in Fig.2.These paddles have DWA ERF OW 1 1/4"z 11/4"s I" 2 7/16" 2 7/16" N/A raised lettering that shows the pipe size and type t,ar�• 1 1/2"..1 1/2",1" 2 11/16" 2 1/4' N/A of TEE that they are to be used with.The proper 2•.2".,V 3 3/16" 2 3/4" N/A paddle mustbe used.Thepaddlemustbeproperly Shown with optional Cover Tamper Switch Kit. attached(see drawing)and the screw that holds A WARNIN the paddle must be securely tightened Do not use more tha7three wraps ofteflon t;qc Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring (Shown with cover in place) A ARNING An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections.The wire + o1�'o „,,,,.,, must be severed,thereby providing supervision of the connection in �o C N.O. N.C. c the event that the wire become dislodged from under the terminal. (V,WHT) (RED) (BLK) Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. DWGN 8810019-2 Fig.4 Typical Electrical Connections Fig.5 Fig.6 To remove knockouts: Breakout thin section ofcoverwhen wiring ® O NEcnTIVE Dc oR Place screw g driver at edge of both switches from one conduit entrance. Rk7.L NI:uTRA1.Ac knockouts,not in the center. _ POSITIVE DC OR HOT AC 7 7HREPAN17.1. ATF,RFLOW ZONE.ON ® M'J� Notes: 1. The Model VSR-S has two switches,one can be used to operate a a� central station,proprietary or remote signaling unit,while the other is used to operate a local audible or visual annunciator. 2. For supervised circuits see"Switch Terminal Connections"drawing and caution note(Fig.3). PRINTED IN USA MFG.#5401206-REV G PAGE 2 OF 3 12/08 FOR SMALL PIPE VSR—S (E) POTTER VANE TYPE WATERFLOW • The Symbol of Protection ALARM SWITCH WITH RETARD Testing Removal The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should associated protective monitoring system should be in accordance with be shut tight and the system completely drained before waterflow applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced. jurisdiction(manufacturer recommends quarterly or more frequently.) • Turn off electrical power to the detector,then disconnect wiring. An inspector's test valve(usually located at the end ofthe most remote branch • Use a wrench on the flats of the bushing.Turn the switch line)should always be used for test purposes.If there are no provisions for counterclockwise to disengage the pipe threads. testing the operation of the flow detection device on the system,application • Gently lift with your fingers,roll the vane so it will fit through the of the VSR-S is not recommended or advisable. hole while continuing to lift the waterflow detector. A minimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe. Please advise the person responsible for testing of the A CAUTION fire protection system that this system must be tested in accordance with the testing instructions. Waterflow switches that are monitoring wet pipe sprinkler systems Maintenance shall not be used as the sole initiating device to discharge AFFF, Inspect detectors monthly for leaks. If leaks are found, replace the deluge,or chemical suppression systems.Waterflow switches used detector.The VSR-S waterflow switch should provide years of trouble- for this application may result in unintended discharges caused free service.The retard and switch assembly are easily field replaceable. by surges,trapped air,or short retard times. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Mounting Dimensions 3.50" 5.56" GROUND SCREWS (89.0 mm) (141.2 mm) C 2.00' (50.8 mm)� _ 1 2.34" (59.4 mm) 1 4.89" f + (52.3 mm) ROW O 1"-I1 I/2 NPT DWGS 1206-5 PRINTED IN USA MFG.95401206-REV G PAGE 3 OF 3 l2/08 (E.) POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and]0"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm r General Signaling Burglar Alarm Environment: Indoor or outdoor use(See Note 1) -400 to 150OF(401 to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires u 0 0 rw DC Bells-Terminal strip *O Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-I deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(IOlmm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-I Standard 464. UL temperature range is-30'to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 ;1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC M13A-10-12 1750060 1 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* 1 .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection.*Does not have ULC listing. WARN! ARN In outdoor or wet installations,bell must be mounted with • weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC St. Louis, MO, Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.95400776-REV Y-1 PAGE I OF 2 01/13 (E) POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC Bells Dimensions Inches(mm) Wiring(rearview) Fig. 1 Fig.3 A.C.BELLS I0 WHITE I INI WHITE(OUT) $ FROM CONTROL (200) 6' PANEL OR (150) �7 ( PRECEDING BELL 1 0 RLACKONI C."".. ) CAUTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. 2 l l/l6" (68) DWG#T76-1 NOTES: I.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELYAFTER LAST BELL. 2,END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. OWM 114-1 Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"conduit entrance ° 5 3/4' O _ 3 3/8" 5" To Next (146) (86) (127) Device or — End si Line Rsto esi r 1,27 3 3/8" I5/S" (86) (Q D A I/4" 1108) Installation DWG#776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. 0 2. Remove the gong. o 3. Connect wiring(see Fig.3). ° 4. Mount bell mechanism to backbox(bell mechanism must be mounted with the striker pointing down). 0 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). 0 6. Test all bells for proper operation and observe that they can ^'`4\1 BBx-I be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). FA WARNING "Failureinstall striker down will prevent bell from operating. PRINTED IN USA MFG.#5400776-REV Y-l PAGE 2 OF 2 01/13 • June 28, 2013 Sprinkler 41g ® STANDARD/QUICK RESPONSE ' CONCEALED PENDENT SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Standard/Quick Response Concealed Pendent Sprinklers are thermosensitive glass bulb spray sprinklers pre-assembled with a threaded adapter for installation with a domed cover that provides up to '/2" (12.7 mm) of vertical adjustment. The •'`,- cover plate is available with several decorative finishes to meet design requirements. The Electroless Nickel PTFE (ENT) finish has been investigated for installation in corrosive atmospheres and is listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: FM Global approves ENT finish as corrosion resist- ant.) The ENT finish is only available for the sprinkler assembly, the cover plate is not plated. The two-piece design allows installation and testing of the sprinkler prior to instal- f �: Iation of the cover plate. The "push-on", "thread-off" design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled,allowing temporary removal of ceiling panels without taking the sprin- kler system out of service or removing the sprinkler. •-'' 2. LISTINGS AND APPROVALS r@os cULus Listed: Category VNIV FM FM Approved: Class 2015 VdS Approved: Certificate G4080014 vds Refer to Approval Chart 1 and Design Criteria on pages 41 i-j for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 41k for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 2003. Minimum Operating Pressure: 7 psi (0.5 bar) Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread sizes: Sprinkler VK302: 1/2" (15 mm) NPT, Sprinkler VK352: 3/4" (20 mm) NPT Nominal K-Factors: Sprinkler VK302: 5.6 U.S. (80.6 metric*), Sprinkler VK352: 8.0 U.S. (115.2 metric*) *Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65°F (-55°C) Overall Length(sprinkler body): Sprinkler VK302: 2-1/4" (57 mm), Sprinkler VK352: 2-5/16" (59 mm) Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinkler VK302. Brass UNS-C84400 for Sprinkler VK352. Deflector: Phosphor Bronze UNS-051000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Ejector Spring (Sprinkler VK352): 17-7 Stainless Steel Compression Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Cover Assembly Materials: Viking Technical Data may be found on Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 The Viking Corporation's Web site at Spring: Beryllium Nickel http:/Iwww.vikinggroupinc.com. Solder: Eutectic The Web site may include a more recent Ordering Information: (Also refer to the current Viking price list.) edition of this Technical Data Page. • Viking Standard/Quick Response Concealed Pendent Sprinklers VK302 and VK352 and Cover Plate Assembly must be ordered separately: Sprinkler: Base Part Nos. 12979A-X, 18021A-X, or 06666BA-X for brass finish, and 12979JN-X or 06666BJN-X for ENT finish (in- cludes sprinkler and adapter pre-assembled,with a protective plastic cap covering the unit) Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number: Temperature Suffix: 155°F (68 °C) = B, 175°F (79*C)= D, 200°F(93°C)= E For example, concealed sprinkler VK302 with a 155°F (68 °C)temperature rating = 12979ABX. Form No. F 070803 Replaces page 41g-I, dated June 5, 2013. (ENT finish is now approved as corrosion resistant.) • Sprinkler 41 h June 28, 2013 STANDARD/QUICK RESPONSE TECHNICAL DATA I CONCEALED PENDENT SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Note:When ordering this sprinkler using the SIN,add suffix-D. For example,concealed sprinkler VK302=VK302-D. Cover Plate Assembly: Base Part No. 12381 Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number: Finish Suffix: Polished Chrome= F, Painted White= M-AN, Painted Ivory= MA, Painted Black= M413 Temperature Suffix: 135°F(57°C) =A (for use with 155°F(68°C)rated sprinklers only), 165°F (74°C)= C(for use with 175°F (79°C)or 200°F(93 °C) rated sprinklers). For example, cover 12381 with a Polished Chrome finish and a 135°F (57 °C)temperature rating = 12381 FA. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories"section of the Viking data book.) Sprinkler Wrench: Part No. 13577W/B**(available since 2006) a. **A W ratchet is required(not available from Viking). — Sprinkler Cabinet: Part No. 01731A(available since 1971) t 4. INSTALLATIONo�oho Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions,when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the ' exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,forming o a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. 7. AVAILABILITY The Viking Quick Response Concealed Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Figure 1: Concealed Sprinkler VK302 and Cover 12381 Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Ordinary 155 °F(68°C) 100°F (38°C) Red Intermediate 175°F (79°C) 150°F(65°C) Yellow Intermediate 200 °F(93°C) 150°F (65°C) Green Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black Sprinkler Finishes: Brass or ENT(See Ordering Information section page 33K) Corrosion-Resistant Coatings': ENT Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments.Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers,the ENT coating is applied to all exposed exterior surfaces, including the waterway.For ENT coated sprinklers the belleville spring is exposed. June 28, 2013 Sprinkler 41 i STANDARD/QUICK RESPONSE ' ' ' CONCEALED PENDENT • SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 1 (UL) Spgpkjor Ternpuratum Rai)2 Standard/Quick Response Concealed Pendent Sprinklers +;Cam PLIlu Temperature Rabmg Maximum 175 PSI(12 bar)WWP awl•Cara�PtatetltuM KEY Sprinkler NPT Thread Nominal Overall Length Listings and Approvals' Base Part SIN Size K-Factor (Sprinkler Body) (Refer also to Design Criteria on page 41j.) Number' Inch mm U.S. metric- Inches I mm cULus° NYC VdS- LPCB Quick Response Applications 12979A-X VK302 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 18021A-X VK302 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 — 12979JN-X8 VK302 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 I See Footnote 5 — — 06666BA-X VK352 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 — — 06666BJN-X8 VK352 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 — Standard Response Applications 12979A-X VK302 1/2" 15 5.6 80.6 2-1/4" 57 — — — 18021 A-X VK302 1/2" 15 5.6 80.6 2-1/4" 57 — — AW1, CX1 12979JN-X8 VK302 1/2" 15 5.6 80.6 2-1/4" 57 - — — — 06666BA-X VK352 3/4" 20 8.0 115.2 2-5/16" 59 — — — 06666BJN-XI VK352 1 3/4" 20 8.0 115.2 2-5/16" 59 — — — — Sprinkler Temperature Ratings Cover Plate Assembly Temperature Ratings' Finishes of the Cover Plate Assembly' A-155 OF(68°C) W- 135 OF(57°C)cover 12381' 1 - Polished Chrome, Painted White, Painted B-175°F(79°C)and 200 OF(93°C) C-200 OF(93°C) X-165 OF(74°C)cover 12381' Ivory, or Painted Black Footnotes Part number shown is the base part number.For complete part number,refer to current Viking price list schedule. -Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 9 This chart shows the listings and approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any additional approvals. Listed by Underwriter's Laboratories for use in the U.S.and Canada. 5 Meets New York City requirements,effective July 1,2008. 8 VdS Approved,standards VdS 2344:2005-12,VdS 2100-25:2008-01,and EN 12259-1:1999+A1:2001 +A2:2004+A3:2006,Certificate G4080014 'The 135 OF(57°C)cover has an orange label.The 165 OF(74°C)cover has a white label. 8 cULus Listed as corrosion-resistant. 'Standard painted finishes consist of Polyester Baked Enamel.Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer.Contact Viking for additional information. NOTE:Custom colors are indicated on a label inside the cover assembly.Refer to Figure 3. Sprinkler41j June 28, 2013 ® STANDARD/QUICK RESPONSE A A CONCEALED PENDENT SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com _- ��p CUSTOM 2-5/8' (66.7 mm) ;—— diameter opening l Q 9y required in J ', the ceiling. —— O v y NIKING Sprinkler Identification of Custom Paint Color: Wrench Sprinkler and All custom color painted cover plates will Part No, Adapter Assembly have an identifying label affixed to the 13577W/Bxw (Protective Shell inside of the cover that indicates custom x KA 1/2' ratchet Removed for color and will have a representative sample is required (not Installation.) (a paint dot) of the paint on the (abel. available from Viking). Figure 3: Figure 2: Sprinkler Installation and Correct Use of Wrench Identification of Custom Paint Color for Concealed Covers DESIGN CRITERIA - UL o refer to Approval Chart 1 on page 41 ' cULus Listing Requirements: Viking Concealed Pendent Sprinklers VK302 and VK352 are cULus Listed quick response as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.Maximum spacing allowed is 15 ft.(4.6 m). • Minimum spacing allowed is 6 ft.(1.8 m)unless baffles are installed in accordance with NFPA 13. • Minimum distance from walls is 4 in.(102 mm). • Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. • The sprinkler installation and obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed. • DEFLECTOR POSITION: Install Concealed Pendent Sprinklers VK302 and VK352 with the deflector 3/8"(9.5 mm)to 7/8"(22.2 mm)below the ceiling.Refer to Figures 4 and 5. NOTE:Concealed sprinklers must be installed in neutral or negative pressure plenums only. VdS Approval Requirements: a)The sprinkler can be installed in a concrete ceiling(massive ceiling)or in a false ceiling made of light materials. b)This sprinkler is deflector fixed type and can be only activated by heat.The housing is not tight. c)Follow installation guidelines of current standards,CEA4001VdS and EN12845.These sprinklers can only be installed in LH and OH occupan- cies,except in OH4. NOTES: Due to the design the sprinkler type'Domed-CCP'shall not be installed in false ceilings in which the false ceiling space is protected by a water extinguishing system. Due to the design the sprinkler type'Domed-CCP'shall not be installed in false ceilings in which during a fire the pressure above the false ceiling may be assumed to be higher than the pressure below the false ceiling. The criterion for the dropping of the cover relevant for this approval is heat. Steps of installation: 1. Prepare the sprinkler key. 2 Remove the plastic cover. 3. Hold the sprinkler with the wrench and fasten it. 4 Replace the plastic cover and do not remove until the cover is installed. IMPORTANT:Always refer to Bulletin Form No.F 091699-Care and Handling of Sprinklers.Also refer to page QR1-3 or SR1.3 for general care, installation, and maintenance information.Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes,ordinances,and standards, whenever applicable. June 28, 2013 Sprinkler 41 k ® STANDARD/QUICK RESPONSE ' ' ' CONCEALED PENDENT SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com r Approval Chart 2 (FM) sw nw��Tamp 4ire RAtl-57 Standard Response Concealed Pendent Sprinklers „—CoverPlm*lrempo?euroRaung Maximum 175 PSI (12 bar)WWP Aw1.cc*lwFla+.Fin" KEY Sprinkler NPT Thread Size Nominal K-Factor Overall Length 3 Base Part SIN (Sprinkler Body) Approvals � (Refer alsoo t to Design Criteria below.) Number Inch mm U.S. metricz Inches I mm 12979A-X VK302 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 18021A-X VK302 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 12979JN-X6 VK302 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 06666BA-X VK352 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 06666BJN-X6 VK352 I 3/4" 20 8.0 115.2 2-5/16- 59 AW1, BX1 Sprinkler Temperature Ratings Cover Plate Assembly Temp. Ratings' Finishes of the Cover Plate Assembly' A-155°F(68°C) W- 135°F(57'C)cover 12381' 1 - Polished Chrome, Painted White, Painted B-175°F(79°C)and 200°F(93°C) X-165°F(74°C)cover 12381' Ivory, or Painted Black Footnotes Part number shown is the base part number.For complete part number,refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any ad- ditional approvals. "The 135°F(57°C)cover has an orange label.The 165°F(74°C)cover has a white label. 5 Standard painted finishes consist of Polyester Baked Enamel.Other paint colors are available on request with the same listings as the standard paint colors.Listings and Approvals apply for any paint manufacturer.Contact Viking for additional information. 6 FM approved as corrosion resistant. NOTE:Custom colors are indicated on a label inside the cover assembly.Refer to Figure 3. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Reauirements: eking Concealed Pendent Sprinklers VK302 and VK352 are FM Approved as standard response Non-Storage concealed pendent sprinklers as indi- cated in the FM Approval Guide.For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply require- ments, hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes,ordinances,and standards,whenever applicable. _1 Sprinkler 411 June 28, 2013 ® STANDARD/QUICK RESPONSE a CONCEALED PENDENT SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1/2' NPT (15 mm) 1 2-1/4' (573 mm) 1-3/8' (35.1 mm) 0 Minimum o 1" (25.4 mm) (80 mm) i 1�9�16\ `-r-- 7/8' (22.2 mm) 3/8" Maximum (9,5 mm) Minimum 1-7/8" (47,8 mm) Maximum 0 0 Figure 4: Concealed Sprinkler VK302 Dimensions and Cover Installation June 28, 2013 Sprinkler 41 m ® STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLERS(VK302&VK352) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 3/4' NPT (20 mm) � — 1 I I 2-5/16' (59.2 mm) 1-7/16' (37 mm) Minimum 0 1" (25.4 mm) 3-1/8' (80 mm) I I (22.2 mm) 3/8" Maximum (9.5 mm) 1-15/16" Minimum (49.7 mm) 1 0 Maximum T � � 7� 0 Figure 5: Concealed Sprinkler VK352 Dimensions and Cover Installation THIS PAGE INTENTIONALLY LEFT BLANK Form No. F 070803 Replaces page 41g-I, dated June 5, 2013. (ENT finish is now approved as corrosion resistant.) Material Specification for VK300 Head June 28, 2013 Sprinkler 51a ® MICROFAST®AND MicrofastHP° QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Microfase and MicrofastHP®Quick Response Upright and Conventional(Old Style)Sprinklers are small,thermosensitive,glass-bulb spray sprinklers available in several different finishes,temperature ratings,and K-Factors to meet design require- ments.The special Polyester,Polytetrafluoroethylene(PTFE),and Electroless Nickel PTFE(ENT)coatings can be used in decorative applications where colors are desired. In addition,these coatings have been investigated for installation in corrosive atmos- pheres and are listed/approved as corrosion resistant as indicated in the Approval Charts.(Note: FM Global approves the ENT coating as corrosion resistant.FM ,. Global has no approval classification for PTFE and Polyester coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS u� �s cULus Listed: Category VNIV FM FM Approved: Classes 2002 and 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984B-PDA vds VdS Approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 twice LPC Approved: Ref. No. 096e/03, TE30401, and TE30872 C E CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, 0786-CPD-40171, and 0786-CPD-40278 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Viking Technical Data may be found on Available since 1987. The Viking Corporation's Web site at Minimum Operating Pressure: 7 psi (0.5 bar)` http://www.vikinggroupinc.com. Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for The Web site may include a more recent use with water working pressures ranging from the minimum 7 psi(0.5 edition of this Technical Data Page. bar) up to 250 psi (17 bar) for high-pressure systems. High-pressure (HP)sprinklers can be identified by locating "250"stamped on the de- flector.All other Part Nos. not mentioned above are rated to a maximum 175 psi (12 bar)wwp. Factory tested hydrostatically to 500 psi (34 5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65°F (-55°C) Overall Length: Refer to the Approval Charts "cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12978, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978, 06764B, and 12281. Copper UNS-C19500 for Sprinklers 06665B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Form No. F_080488 Replaces page 51a-e, dated June 11, 2013. (ENT finish is no approved as corrosion resistant.) Material Specification for VK300 Head Sprinkler 51b June 28, 2013 MICROFAST®AND MicrofastHP® QUICK NC4 RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap-ENT plated. Ordering Information: (Also refer to the current Viking price list) Order Microfast®and MicrofastHP®Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome = F, White Polyester= M-/W, Black Polyester=M-/B, and Black PTFE = N, ENT=JN Temperature Suffix(°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286'/141° =G For example, sprinkler VK300 with a 1/2"thread, Brass finish and a 155°F/68°C temperature rating = Part No. 12978AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories"section of the Viking data book) Sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000) Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B.Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements 7. AVAILABILITY The Viking Microfase and MicrofastHP®Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color ClaSS LtQn Tempo_ turp._ _"n ' Ceilin Tem erature' Ordinary 135°F (57°C) 100°F (38°C) Orange Ordinary 155°F(68°C) 100°F (38°C) Red Intermediate 175°F (79°C) 150°F(65°C) Yellow Intermediate 200°F (93°C) 150°F (65°C) Green High 286°F (141 °C) 225°F (107 °C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings': White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C) Footnotes The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compatible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only.Note that the spring is exposed on sprinklers with Polyester,ENT,and PTFE coatings. For ENT coated automatic sprinklers,the waterway is coated. Material Specification for VK300 Head June 28, 2013 Sprinkler 51c MICROFAST®AND MicrofastHP° QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com - - pprovzl a T�motiu� KEY Finish Microfast"and MicrofastFiP�Quick Response :TT� Upright and Conventional Sprinklers AT EocuuxealUlapplicanlo] Maximum 175 PSI(12 bar)W VP Base Part SIN Thread Size Nominal K-Factor Overall Length Listings and Approvals' (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metricz Inches I mm cULus4 NYC8 VdS LPCB (E O Upright-Standard Orifice 12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al2 B4 See Footnote 7 - - - - 07060 VK345 - 15 mm 5.6 80.6 2-3/16 56 - - A2 A2 B212 B215 Conventional-Standard Orifice 067666 VK310 1/2" 15 mm 5.6 80.6 1 2-3/16 1 56 A2 A2 - A2 B212 B215 Upright-Large Orifice 06665B VK350 3/4" - 8.0 115.2 2-5/16 59 Al, B4 Al A2 A2 B212 -- 14817 VK350 - 20 mm 8.0 115.2 2-5116 59 A11 B4 Al A2 A2 B212 - 06764616 VK350 1/2" 15 mm 8.0 115.2 1 2-5/16 59 Al. B4 Al A2 - A213 - Conventional-Large Orifice 06768B VK354 3/4" 20 mm 8.0 115.2 1 2-5/16 1 59 Al A2 - A2 B212 Upright-Small Orifice" 067171311 VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Al - - - - 06719611 VK327 1/2" 15 mm 4.2 57 2-3/16 56 Al Al 06931 B11 VK327 - 10 mm 4.2 57 2-3/16 56 - A2 C314 - Maximum 250 PSI(17 bar)WWP Upright-Standard Orifice Base Part SIN Thread Size Nominal K-Factor Overall Length Listings and Approvals' Refer also to Desi n Criteria on page 51d. Number' NPT BSP U.S. metricz Inches rem cULus4 NYC- VdS LPCB (E � 12281 VK315 1/2" 15 mm 5.6 1 80.6 2-3/16 56 Al Al -- - - Upright-Small Orifice10 1228611 1 VK340 1/2" 15 mm 2.8 1 40.3 1 2-3/16 56 Al Al - Approved Temperature Ratings Approved Finishes A- 135 OF (57 °C), 155 OF (68 °C), 175 OF (79 °C), 200 OF (93°C), and 1 - Brass, Chrome, White Polyester. , Black Polyesters 6, and Black PTFES 286 OF(141°C) 2-Brass,Chrome,White Polyesters.6,and Black Polyester'A B- 155 OF(68°C), 175 OF(79°C), 200 OF(93°C), and 286 OF(141°C) 3-Brass and Chrome C-155°F(68°C) 4-ENT' Footnotes 1 Base part number is shown.For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0 3 This table shows the listings and approvals available at the time of printing.Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 6cULus Listed as corrosion resistant. 8 Other colors are available on request with the same Listings and Approvals as the standard colors. Meets New York City requirements,effective July 1,2008. 6 Accepted for use,City of New York Board of Standards and Appeals,Calendar Number 219-76-SA. 9 Accepted for use,City of New York Department of Buildings,MEA 89-92-E,Vol.16. 10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only Exception:4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized 7he sprinkler orifice is bushed. Certified,Standard EN 12259-1,EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. " Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40278. 4 ((Certified,Standard EN 12259-1,EC-certificate of conformity 0786-CPD-40131. 5 $MED Certified,Standard EN 12259-1,EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. 6The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only Material Specification for VK300 Head Sprinkler 51d June 28, 2013 ® MICROFAST®AND MicrofastHP®QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com DESIGN CRITERIA - UL (Also refer to Approval Chart 1 on page 51c) cULus Listing Reauirements: Microfase and MicrofastHP®Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers,or old style(conventional)sprinklers. • Designed for use in Light and Ordinary Hazard occupancies(exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style(conventional)sprinklers. IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information.Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Protective Wrench Sprinkler Flat Cap C=W:= Figure 1: Standard Sprinkler Wrench 10896W/B Material Specification for VK300 Head June 28, 2013 Sprinkler 51e MICROFAST®AND MicrofastHPO QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Approval Chart 2 (FM) —Temparatu+a KEY Microfast'-Quick Response Upright Sprinklers rriah Escutax-on td appitcab:ni Maximum 175 PSI 12 bar)WWP Base Part SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Number' NPT BSP U.S. I metres Inches mm (Refer also to Design Criteria below.) Standard Orifice 12978 VK300 1/2-7 15 mm 5.6 80.6 2-3/16 56 A2, B3 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2 Large Orifice 06665E VK350 3/4" 8.0 115.2 2-5/16 59 A2, B3 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2, B3 06764B7 VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 A2, B3 Small Orifice _ 06717B6 VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Approved Finishes Approved Temperature Ratings 1 -Brass and Chrome A- 135°F(57°C), 155°F(68°C), 175°F(79°C),200°F(93 °C), and 286°F(141°C) 2 - Brass, Chrome, White Polyesters, and Black B-155°F(68°C), 175°F(79°C), 200°F(93°C), and 286°F(141°C) Polyesters 3-ENT' Footnotes 'Base part number is shown. For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3This table shows the FM Approvals available at the time of printing.Check with the manufacturer for any additional approvals. " FM Approved as quick response Non-Storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets(including Data Sheet 2-0). s Other colors are available on request with the same Approvals as the standard colors. 6 The sprinkler orifice is bushed. The 1/2"NPT Large Orifice Sprinkler is Listed and Approved for retrofit only e FM approved as corrosion resistant DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above) FM Approval Reauirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-Storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes,ordinances,and standards,whenever applicable. THIS PAGE INTENTIONALLY LEFT BLANK Form No. F_080488 Replaces page 51a-e, dated June 11, 2013. (ENT finish is no approved as corrosion resistant.) Page 1 of 15 MODEL V-BB SPECIFIC APPLICATION 4 I KjATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION The Model V-BB (Back to Back) is a Specific Application Attic Sprinkler designed to provide superior fire protection in combustible and non-combustible sloped attic spaces when compared to standard spray attic protection. With specific application criteria for use with Model V-SD (Single Directional) and VK696 Attic Upright Specific Application Sprinklers, Viking attic sprinklers provide an extended coverage spacing alternative to standard spray sprinklers.They make it possible to use a single line of piping at the attic peak,eliminating the need for branch lines and greatly reducing the number of required sprinklers and associated material and installation costs. Model V-BB sprinklers also have lower minimum flow and pressure requirements than competitive products. Viking Attic Sprinklers can be installed with either steel or CPVC piping(CPVC allowed on wet pipe systems only), and are available in brass or with corrosion-resistant Electroless Nickel PTFE (ENT) coatings where salt water and other corrosive elements are a consideration. They are cULus Listed with specific application guidelines for use as special sprinklers as defined by the National Fire Protection Association (NFPA), and are cULus Listed for extended coverage in combustible and non-combustible construction.The cULus Listing was achieved using full-scale fire tests within wood truss construction. The Model V-BB Attic Sprinkler provides a reduced response time due to its narrow ridge spacing of 6 ft. (1,8 m) and long throw pattern (up to 30 ft. in each direction measured horizontally), and is offered in three different slope ranges and two different orifice sizes (K=5.6 or 8.0). Listed for specific pitches 4:12<7:12, 7:12<10:12, and 10:12:512:12; and V-BB Sprinkler spans of 60 ft. and 40 ft.The 8.OK can protect up to 80 ft.span when used along with the Model 8.0K 5.61K Pitch Attic Upright VK696. VK681 VK684 4:12<7:12 VK682 VK685 7:12< 10:12 2. LISTINGS AND APPROVALS VK683 VK686 10:12<_12:12 O cULus Listed: Category VNIV ' WARNING:Cancer and Reproductive Harm- US OS Refer to the Approval Chart on page 4. wmyP6swarrnngs.ca.gov 3. TECHNICAL DATA Viking Technical Data may be found on Specifications: The Viking Corporation's Web site at Minimum Operating Pressure: See Design Criteria-UL http://www.vikinggroupinc.com. Rated to 175 psi (12 bar)water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) The Web site may include a more recent Thread size: 1/2" (15 mm)or 3/4" (19 mm) NPT edition of this Technical Data Page. Nominal K-Factor: 5.6 U.S. (80.6 metric*) or 8.0(115.2 metric*) *Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65 of (-55°C) Overall Length: 2-5/8" (67,6 mm) Covered by the following US Patent No.: 9,149,818 Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Brass UNS-C23000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Ordering Information: (Also refer to the current Viking price list.) To order the Attic Sprinkler, add the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, ENT=JN Temperature Suffix: E =200°F(93.3*C) Form No. F 042915 18.10.25 Rev 16.2.P65 Replaces Form F_042915 Rev. 16.2 (Added P65 Warning.) Page 2 of 15 MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Available Finishes And Temperature Ratings: Refer to the approval chart on page 4. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking website under Technical Data) Sprinkler Wrench: Standard Wrench: Part No. 10896W/13 Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A B. Twelve-head capacity: Part No. 01725A 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 6. OPERATION During a fire condition, the heat sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern to extinguish or control the fire, and protect the piping in the interstitial space. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Model V-BB Specific Application Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Intermediate 200 °F (93.3 °C) I 150 °F (65°C) Green Sprinkler Finishes: Brass, ENT' Footnotes The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 cULus Listed as corrosion resistant. Form No. F 042915 18.10.25 Rev 16.2.P65 Page 3 of 15 ® MODEL V-BB SPECIFIC APPLICATION 4 I KjATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com _Protective Sprinkler Clip Wrench Flat O �wM »,-A I �r 'D�=10896 CD Figure 1: [Standard Sprinkler Wrench 10896W/B 1-1/8" (29 mm) (29 mm) 1 1 2-1/4" 12 2-5/8" (57 mm) O (67 mm) (62-5/8" O (76 mm) 1 —_ 7/16"(11 mm) — Nominal Pipe " 15 mm) Engagement 7/16"(1 1/2 1 mm) NPT �J 3/4"(19 mm) Nominal Pipe Engagement NPT Figure 2a: Figure 2b: Sprinkler Dimensions -5.6K Sprinkler Dimensions -8.OK Form No. F 042915 18.10 25 Rev 16.2.P65 Page 4 of 15 ® MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com pproval C-MRI Tampbrurura KEY Viking V-BB Specific Application Sprinkler rinsh Non-Combustible Sloped Attic Spaces A;XF Exutcr:.wni,�ncic��e, Thread Size Nominal Overall Length Listings and A rovals' Part � SIN Maximum K-Factor g g pp Number Pressure NPT BSP U.S. metric- Inches mm cULus4 FM LPCB E Q 19627 VK684 175 psi 1/2" 15 mm 5.6 80,6 2-5/8 68 Al,A2 - - - - 19801 VK685 175 psi 1/2" 15 mm 5.6 80,6 2-5/8 68 Al,A2 19754 VK686 175 psi 1/2" 15 mm 5.6 80,6 2-5/8 68 Al,A2 - - 19626 VK681 175 psi 3/4" 20 mm 8.0 115,2 2-5/8 68 Al,A2 - - 19798 VK682 175 psi 3/4" 20 mm 8.0 115,2 2-5/8 68 Al,A2 - 19751 VK683 175 psi 3/4" 20 mm 8.0 115,2 2-5/8 68 Al,A2 - - - Approved Temperature Rating Approved Finishes A-200°F(93.3°C) 1 -Brass,2-ENT5 'Also refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing.Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc for use in the United States and Canada. 5 cULus Listed as corrosion resistant. DESIGN CRITERIA - UL Cha = fA!so refer to Approval Chart 1) Allowab!e. flow,pressure a'nd s!ope for attic protechcri using Viking V-BB Sprinkle Thread Size Nominal Allowable Roof Minimum Minimum Dry Pipe System Sprinkler K-Factor - Flow Pressure Maximum Water Base Part SIN Type Span Pitch Delivery Time3 Number NPT BSP U.S. metric ft.(m) GPM LPM PSI BAR (in seconds) 19627 VK684 V-BB 1/2" 15 mm 5.6 80,6 <40(12,2) 24 91 18.4 1,3 4:12<7:12 See footnote 3 19801 VK685 V-BB 1/2" 15 mm 5.6 80,6 <40(12,2) 24 91 18.4 1,3 7:12<10:12 See footnote 3 19754 VK686 V-BB 1/2" 15 mm 5.6 80,6 <40(12,2) 24 91 18.4 1,3 1 10:12<-12:12 See footnote 3 19626 VK681 V-BB 3/4" 20 mm 8.0 115,2 <60(18,3) 38 144 226 1,5 4:12<7:12 See footnote 3 19798 VK682 V-BB 3/4" 20 mm 8.0 115,2 <60(18,3) 38 144 22.6 1,5 7:12<10:12 See footnote 3 19751 VK683 rV-BB 3/4' 20 mm 8.0 115,2 <60(18,3) 38 144 22.6 1,5 10:12 512:12 See footnote 3 Pitch and slope indicate the incline of a roof,expressed as a proportion of the vertical to the horizontal. • 2 Refer to the Viking Attic Upright VK696 data sheet for roof spans over 60 ft(18,29 m)up to 80 ft(24,38 m)wide. 3 Refer to NFPA 13,2013,Section 7.2.3. IMPORTANT: Always refer to Bulletin Form No. F_091699 -Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data,the appropriate standards of NFPA, LPCB,APSAD,VdS or other similar organizations,and also with the provisions of governmental codes,ordinances,and standards,whenever applicable. Form No. F 042915 18 10.25 Rev 16.2.P65 f Page 5 of 15 ® MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-946-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com ADDITIONAL DESIGN CRITERIA - UL Chart 2 (Also refer to DESIGN CRITERA Chart 1) Allowable roof span,flow,pressure and slope for attic protection using Viking V-BB Sprinklers Design Criteria: Flow and Pressures refer to Design Chart 1. System Type: Wet systems and dry systems. Piping Types: Steel (wet and dry)CPVC(wet systems only). Occupancy Classification: Light hazard only. Viking V-BB Sprinkler Spacing Maximum Coverage Area: 400 ft2(37,16 m2)as measured along the slope. Coverage area is determined by the twice the maximum distance thrown measured along the slope, multiplied by the distance along the branch line. Example: 60'(18,3 m)span with a 10:12 slope,when measured along the slope provides a distance of approximately 39'-1" (11,9 m).This number must be multiplied by 2 to equal the overall span, which would be approximately 78'-2" (23,8 m). 400 ft2 divided by 78'-2" (23,8 m)allows a maximum spacing along the branchline of 5'-1" (15,5 m). Along the Branch Line: Minimum Spacing: 4'-0"(1,2 m)between V-BB's and from V-SD's.T-0"(2,1 m)from Viking Attic Uprights. 6'-0"(1,8 m)from Standard Spray Sprinklers Maximum Spacing: 6'-0"(1,8 m)between V-BB's and from V-SD's. Measured Down the Slope: Minimum Spacing: 26'-0" (7,9 m)from Viking Attic Uprights and Standard Spray Sprinklers. Deflector Position below Peak, Ridge,or Deck: For all roof pitches as per the listing from 4:12 — 12:12 the maximum deflector distance down is 22" (560 mm), and the minimum deflector distance down is 16" (405 mm). Deflector Position above Scissor Truss: For all roof pitches as per the listing from 4:12— 12:12 the minimum distance above a scissor truss is 18" (458 mm). Maximum distance from center line of the ridge: 6" (152 mm)on either side of the center line. Minimum distance from Truss: 6" (152 mm)from nearest edge of the truss. Draft Curtains: Where used to allow Attic Upright Sprinkler installation shall be constructed to contain heat, may be constructed of minimum YZ" (13 mm)plywood or equivalent. Continues on next page. Form No. F 042915 18.10.25 Rev 16.2.P65 Page 6 of 15 MODEL V-BB NIKJNG* SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Continued from previous page. Use of UL Listed CPVC Blazemaster Piping (Wet Systems Only): Can be used to supply the sprinklers protecting the floor below the combustible concealed space when covered with 6" (152 mm) of non-combustible insulation over the horizontal or vertical piping, and extending 12" (304 mm) on both sides of the center line of the piping. If the piping is located in the joist, the width of the joist channel must be entirely covered to 6" (152 mm)above the top of the piping. The area above the piping must be protected with the Model V-BB's, V-SD's, or the Attic Upright Sprinklers. Listed CPVC Blazemaster piping may also be used exposed to feed wet systems using Viking V-BB sprinklers in accordance with the following requirements, and in accordance with Figure 15: Risers are vertical and protected by V-BB or V-SD sprinklers located a maximum of 12(304 mm)"away from the riser centerline. Model V-BB or V-SD sprinklers are mounted directly to the branchline. Model V-BB or V-SD sprinklers are installed on arm-overs a maximum of 6"(152 mm)laterally from the center line of the branch line. Model V-BB or V-SD sprinklers are installed on Vertical Sprigs attached to the branchline. Model V-BB or V-SD sprinklers are installed on angled sprigs a maximum of 6"(152 mm)laterally from the centerline of the branchline. Installed with a minimum lateral distance of 18"(456 mm)from any device that produces and releases heat, i.e. attic furnace, kitchen or bathroom exhaust fan,flue vents, heat lamps, and other such devices. Insulation requirements are provided solely for Fire Protection purposes and not for freeze protection. Non-combustible insulation being used needs to be verified for chemical compatibility with the CPVC piping at www.lubrizol.com Obstruction Criteria: Refer to Figures 4-14 Refer to Sections 8.8.5.2.1.3 and 8.8.5.2.1.7 of NFPA 13, 2013 for requirements if installed on greater than 2-1/2" (64 mm)diameter piping. Hydraulic Requirements: Viking V-BB Sprinklers must be calculated in accordance with the following figures and guidelines. The design area shall include the most hydraulically demanding sprinklers, and in certain cases may require more than one set of calculations to verify the system's design. The following figures cover Hydraulic Requirements for Viking V-BB Sprinklers only, and when installed with Attic Upright or Standard Spray Sprinklers. For areas using Viking V-SD Sprinklers refer to the applicable data sheets. Refer to Figures-unless otherwise noted,all Figures portray a 60'(18,3 m)roof span: Figure 16—V-BB Sprinklers Figure 17—V-BB Sprinklers &Attic Upright or Standard Spray Sprinklers Beyond an Obstruction Figure 18—V-BB Sprinklers &Attic Upright or Standard Spray Sprinklers at the Hip Figure 19—V-BB Sprinklers &Attic Upright or Standard Spray Sprinklers in a Dormer, at a Hip, or at an Ell. Figure 20—V-BB Sprinklers&Attic Upright or Standard Spray Sprinklers separated by compartmentalization. V-BB(Back to Back) V-SD(Single Directional) Attic Upright Top Side Top Side Top Side Form No. F 042915 18.10.25 Rev 16.2.P65 Page 7 of 15 ® MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER -NIIQNG* IN The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Refer to figures 4 and 5 below-unless otherwise noted, all Figures portray a 60'(18,3 m) roof span. Maximum 6" (152 mm) obstruction allowed provided it sits at least 36"(914 mm)vertically below the Viking V-BB Sprinkler. Larger or closer obstructions require an additional sprinkler on the opposite side of the obstruction. This criteria only limits the obstructions that run across the trusses or rafters, not the top chord of the trusses or the depth of the rafter. 36"Maximum Minimum air space (914 mm) 33-1/2"(89 mm) Any distance 6"Maximum >6'(152 mm) (152 mrn) required re tea`—�=�� a - No additional sprinklers / Additional Attic Upright or p q standard spray sprinklers required 60'(18,3 m)roof span I 60'(18,3 m)roof span Figure 4: Figure 5: Obstruction Criteria 1 Obstruction Criteria 2 Refer to Figures 6 and 7 below where the maximum spacing for Attic Upright Sprinklers is 12 ft. (3,7 m) and standard spray sprinklers is 15 ft(4,6 m).Any horizontal obstruction that is 4 ft. (1,2 m) or less in width requires minimum 6" (152 mm) clearance over the top to allow for sufficient water flow over and under.The clearance must be measured perpendicular to and from the bottom of the rafter. If the clearance is less than 6"(152 mm), an additional sprinkler is required on the opposite side of the obstruction. If the obstruction is more than 4 ft. (1,2 m)wide, an additional sprinkler is required underneath. 36"Minimum 36"Minimum (914 mm) 6"(152 mm) (914 mm) Minimum - <6"(152 mm) i 4 (1,2 m)Maximum j' >4'(1,2 m) f No additional sprinkler required Additional Attic Upright or 60'(18,3 m)roof span standard spray sprinklers required I— 60'(18,3 m)roof span Figure 6: Figure 7: Obstruction Criteria 3 1 Obstruction Criteria 4 Form No. F 042915 18.10.25 Rev 16.2.P65 Page 8 of 15 ® MODEL V-BB SPECIFIC APPLICATION 4j -E ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Refer to Figure 8 below For vertical obstructions, the maximum dimension of the obstruction is the width and the horizontal distance is measured horizontally. TABLE 2: OBSTRUCTION CRITERIA Additional Sprinklers Required Beyond Dimension X Distance Y Obstruction Maximum Horizontal Dimension of Obstruction Minimum Horizontal Distance to Obstruction All vertical obstructions <6" (152 mm) YES 1/2"- 1" (13 mm -25 mm) 6" (152 mm) NO 1"-4" (25 mm - 102 mm) 12" (305 mm) NO 4"-8" (101 mm-203 mm) 24" (610 mm) NO 8"- 10" (203,mm -254 mm) 5'-0" (1,5 m) NO 10"-20" (254 mm -508 mm) 10'-0" (3,0 m) NO 20"-30" (508 mm -762mm) 15'-0" (4,6 m) NO 30"-40" (762 mm - 1016 mm) 20'-0" (6,1 m) NO 40"-48" (1016 mm- 1219 mm) 25'-0" (7,6 m) NO >48" (1219 mm) Any distance YES X� Y�I Additional Attic Upright or standard spray sprinklers required 60'(18,3 m)roof span Figure 8: Obstruction Criteria 6 Form No. F 042915 18 10.25 Rev 16.2.P65 Page 9 of 15 ® MODEL V-BB SPECIFIC APPLICATION .NIKJNG* IN ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com If a V-BB Sprinkler is 36" (914 mm) or greater avove the space, 36"(914 mm) and 36" (914 mm)or greater clearance above the space is present, 36"(914 mm)or more additional sprinklers are not needed. or more iMech cai sp Additional sprinklers are not required. L 60'(18,3 m)roof span Figure 9: Obstruction Criteria 6 If a V-BB sprinkler is 36"(914 mm)or greater above the space, and a 12" - 36" (304 -914 mm) clearance above the space is present, 4"(102 mm)TO intermediate level standard sprinklers are required. 6"(152 mm) 36"(914 mm) 12"(305 mm)TO or more — a � � 36 (914 mm) d — 0 Mechanical) — s ace mm)TO 6"(152 mm) Intermediate level sprinklers II 60'(18,3 m)roof span Figure 10: Obstruction Criteria 7 Otherwise,the area outside the mechanical space is to be protected as shown using standard spray sprinklers as necessary or by building a shear wall and installing V-SD Sprinklers. <12"(304 mm) Mechanical space 1 Protect with standard OR Add a shear wall and protect spray sprinklers with V-SD Sprinklers Figure 11: Obstruction Criteria 8 Form No F 042915 18.10.25 Rev 16.2.P65 Page 10 of 15 ® MODEL V-BB PECIFIC APPLICATION 11111LS 4lKjw4j ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com If a V-BB Sprinkler can be installed below or between stiffeners and 16"(406 mm)TO 16 to 22" (404 to 559 mm) distance to peak can be maintained, as 22"(559 mm) Stiffeners well as A and B clearances to the stiffeners, no additional sprinklers are required. Bottom plane _ of stiffener B A _ A ,' I Top of denector VK681 VK682 VK683 VK684 VK685 VK686 0" 0" 0' 0 A>p" A+15" A+10" A+8" B E 60'(18,3 m)roof span Figure 12: Obstruction Criteria 9 When the stiffeners are located a minimum of 12" (305 mm) below the V-BB Sprinkler, the stiffeners are 7-12" (190 mm) maximum Minimum70%open area wide, the openings are 12" (305 mm) minimum, and there is 70% 12"(305 mm) minimum open area, no additional sprinklers are required. Minimum ` stiffeners Minimum air space 3-1/2" -= (89 mm) 7-1/2"(190 mm) 12"(305 mm) Maximum Minimum 60'(18,3 m)roof span Figure 13: Obstruction Criteria 10 Otherwise, additional sprinklers are required as shown. <70%open area, openings less than 12"(305 mm),m re or stiffeners more than wide m U Install draft curtain or full wall 60'(18,3 m)roof span Figure 14: Obstruction Criteria 11 Form No. F 042915 18.10.25 Rev 16.2.P65 Page 11 of 15 ® MODEL V-BB - SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com X= 6" (150 mm) MAXIMUM Y= 12" (300 mm) MAXIMUM X X Vertical sprig Branchline �Armover sprig Armover Vertical riser Branchline `Direct mount Vertical riser Y Y Figure 15: Exposed CPVC with V-BB Sprinklers Wet Systems:Calculate the most demanding 5 sprinklers c Dry Systems:Calculate the o most demanding 7 sprinklers. RIDGE,. 0 r9 NOTE:Wet system shown. Figure 16: V-BB Sprinklers Form No. F 042915 18.10.25 Rev 16.2.P65 zA Page 12 of 15 MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email:techsvcs@vikingcorp.com Wet Sytems:Calculate the most demanding 5 V-BB sprinklers and add up to 2cc of the most demanding Attic y Upright or Standard Spray - g Sprinklers. A RiocE Dry Sytems:Calculate the Obstruction most demanding 7 V-BB sprinklers and add up to 2 =•% °i !' of the most demanding Attic Upright or Standard Spray Sprinklers. NOTE:Wet system shown. Figure 17: IV-BB and Attic Upright or Standard Spray Sprinklers Beyond an Obstruction Form No. F 042915 18.10.25 Rev 16.2.P65 Page 13 of 15 ® MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER .N41vjw*j IN The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Wet Sytems:Calculate the most demanding 5 V-BB sprinklers plus the 2 most demanding Attic Upright Sprinklers,and then calculate the most o; demanding area up to 1500 ft2(137m2) having Attic Upright sprinklers.Use the m most demanding calculation. • 0- a - °o RIDGE Wet Sytems:Calculate the most R E demanding 5 V-BB Sprinklers and Cli add up to 2 of the most demanding t` Standard Spray Sprinklers,then ,' calculate the most demanding remote m design area(including ALL sprinkler types)per NFPA 13 For example,area reduction for quick response and 30% NOTE:Wet system shown. increase for sloped ceilings.Use the most demanding calculation. Dry Sytems:Calculate the most demanding 7 V-BB sprinklers plus the 2 most demanding Attic Upright sprinklers,and then calculate the most demanding area up to 1950 ft2(181 m2) having Attic Upright sprinklers.Use the most demanding calculation. a O Dry Sytems:Calculate the most ` demanding 7 V-BB Sprinklers and M add up to 2 of the most demanding ' `'` ;1 m Standard Spray Sprinklers,then o calculate the most demanding remote design area(including ALL sprinkler :! :! types)per NFPA 13.For example,30% increase for sloped ceilings and 30% NOTE:Wet system shown. increase for dry systems. Use the most demanding calculation. Figure 18: FV-BB and Attic Upright or Standard Spray Sprinklers at the Hip Form No. F 042915 18.10.25 Rev 16.2.P65 Page 14 of 15 ® MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 0 Where the quantity of Attic Upright or Standard Spray sprinklers in each dormer,cross,or ell is 4 or less and all of the dormers, crosses and ells meet the maximum 4 standard sprinkler criteria, calculate the V-BB demand as shown in Figures 16 and 17,and add up to 2 of the most demanding Attic Upright or Standard Spray sprinklers in the dormer,cross,or ell that is adjacent to the Attic Upright Sprinklers that are bing included in teh demand calculation. Where the quantity of Attic Upright or Standard Spray sprinklers in any dormer,cross,or ell is greater than four,refer to Figure 18. It >N t(t »? Standard Spray Sprinklers(4 or less) '0 0) Kt )8 • ((t ») Standard Spray Sprinklers(4 or less) llt 1U 60'(18,3 m)roof span Figure 19: FvBB Sprinklers and Attic Upright or Standard Spray Sprinklers in a Dormer, at a Hip or at an E11 Form No. F 042915 18 10.25 Rev 16.2.P65 Page 15 of 15 ® MODEL V-BB SPECIFIC APPLICATION 411aATTIC SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Wall Calculate the V-BB demand as t described in Figures 16 and 17,then calculate the Attic Upright or Standard n Spray Sprinklers per NFPA 13.use the ••. c�; most demanding calculation. o ■ ■ ■ ■ _ RIDGE_ E ZM pp CD N 6 O _ RIDGE_ E Cd 0 m Dormer on top of roof or sheating. Figure 20: Fv-1313 Sprinklers and Attic Upright or Standard Spray Sprinklers Separated by Compartmentalization Form No. F 042915 18.10.25 Rev 16.2.P65 Replaces Form F_042915 Rev. 16 2 (Added P65 Warning.) 1y •� FIRE SPRINKLER PERMIT APPLICATION ItNIGV Department of Community & Economic Development City of Arlington • 18204 59th Ave NE• Arlington, WA 98223• Phone(360) 403-3551 THIS APPLICATION MUST BE ACCOMPANIED BY TWO (2) SETS OF COMPLETE AND SCALED PLANS, TWO (2) SETS OF HYDRAULIC CALCULATIONS, TWO (2) SETS OF EQUIPMENT SPECIFICATIONS FOR EACH FIRE SPRINKLER PERMIT APPLICATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO INCLUDE SPECIFICATION SHEETS, WIRING DIAGRAMS (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON ALL EQUIPMENT TO BE INSTALLED PRIOR TO INSTALLATION. Type of Permit: ❑ New Fire Sprinkler ❑ Fire Sprinkler Add/Alt ❑ Underground Fire Line Project Address: 16400 SMOKEY POINT BLVD. Parcel ID#: 31052800201500 Project Valuation: 5000.00 Number of Heads: 9 Building Area (Sq Ft): NA Owner: GRANDVIEW NORTH LLC Phone Number: 360-435-7171 PO BOX 159 ARLINGTON WA 98223 Address: C ty: State: Zip Code: Contact Person:KEN NY GRAHAM - ALL AMERICAN FIRE Phone Number: 425-268-3514 Cell Phone: 425-268-3514 Email: allamerican_fire@aol.com Address: PO BOX 393 City: EVERETT State: WA Zip Code:98206 Contractor: ALL AMERICAN FIRE PROTECTION INC Phone Number: 425-268-3514 Address: PO BOX 393 City: EVERETT State: WA Zip Code:98206 Contractor's License Number: ALLAMAF854QF Expiration:11121 Contact Person: KENNY GRAHAM Email:allamerican—f ire@ aol.com hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the above- described property will be in accordance with the laws,rules and regulation of the State of Washington. e,es=3oeo,9eseeoe =ea4�eoa�d 09/21/2021 Applicants Signature Date Kenneth L. Graham Print Applicants Name FOR STAFF USE ONLY Permit# Accepted By Amount Received Receipt# Date Received WEB Forms—131 Page 1 of 1 6116LP Zs- �' _ A A �Ca � ram. v♦, � ` J O p k ° !�i• ITI c Oiq A co W �• r) Z O. � a IOU 0 c n Al � A co O o tp p A � Cco n N H CHAPTER II COMPONENTS CYLINDERS&VALVE ASSEMBLY )w I'r.fiss11 Rexumirrt FireSupFvow.mcptem lux a.v�•hle bur di fferen i we c 1linden(P1 N's LI600•I_1000.L 4600,and LN1001 <:filrslersaesanal;•resredmtemsa(atmgsmhrr�c -owto 6e.1er I IM%we•10Kc11t1ce1•�dwAckgrrwyl es n r#%u hhMg igentl The c y wdas An ma nldact weed.tested. �r • andmatllnl'regwcwncres Cyliodencomepreldledwth rs 111%in-hMIL-Karl and are Ju/pd with dry rdtn m las pressure of—,psg 4D V*F.Cylinder and Mahe assembly chmernums me.en$rn in I*ure 2-1 and Table 2.1 M•e flow ""*am ---Q mr fade• N N_ A_ 6 C U_ C•ae.eltr 1t O' U and I.w$• •uu' -r$' c�$•' �,N' r }•Ib. t1sa1_ • 1 � l a wu.' cue' m•� ur ' � •.Ib. Mr• t•om i.•.... •46' •...e' gp�' m 11416 .Na. Ptp n 2-2 Val e:ross secuom 'IuNv 2-1 VALVE REBUILDING EQUIPMENT Tw 1.WET VALVE REBU UDtXG KIT (P,x 4+6420MI Apa"an dw harge.the nlve ame bly most tv rebaN to em.we pnjer f owv 4wrawm *Mc Nbl N'Ahv R•b l&rg K11 e o 6 (k'N 490.120 61 sAcmili be used It itsA►Ics Al oompum ms ne«rarr,to propalr reblid the.-ahY see r g.we 2.3 and Uble 2-3 P own to asw nk*r_O n tgs dKmId!a IUtvrcated with 0�n rK IeR.nurA P*setn 2-I-C,Wa and Milve Aawn6 i I AR cyind•r•at a 4w rho vsme dr"nt Valw A.remmy L_J (P)N S117S1.I1s a pressure sealed poppet type webs des�ned provide npd aclmbn and ducharp cispo.M comes with a Pro"ar R•8slietar(PIN 3�o09V1ilOh•o mama d$ wjw prawrc nQ to IN". See Fig wet-2rni'l'.bie 2-1 —•L��Q, Ism FM a•w+t0• Prawns 2-3s Valor ReblddrnR Knt e VA V•b.andv c %l.A V•1.a51em A•ww"y (� IIN O•a.,�e e us.Nnn �'•M.7p•ne WA \••Iw 7iem Aw•nMV • r�.•,nv7 Mrs a fA•su)w1 1L.rp�g1 — %^4wrc• %1d.e04k1ea 1 611,61r714, V•ve0a.all • a1$IA 11w•1•►eiM�t • 0"sure$ Ieeu•U1Lne_ •M•usyl VoiwvCy Aeed.b 'table 23 .•.won Raw"ORife n a..vn 1►s•u•erepeM.• T•b1.2-2 200 11C L Re.V UI.EX4Q1 3 Nn a MAW (2,VAW 2 kAngkvw ens PR ES SUR E R FGIJLA'I'UR ASSLIKUY(N N 3349931 Cyb ride r art stallatbm cost ru:tKvas are provided in the 1 mtalla c s:In 'M 14c..ury V4%mkm.w,t+,wmlj(PrN;i0W1.tImc i.ehlho wdvonci Cis mAnsut See f7gune2.7. Cylinder Yahe Awcmb4-(P1N SSi17SI and isawlable mfthe 0orrtlieto pre%sure tegvkltca requiems refi,iemad be.,posit* Ihrv:nl.lanulcl See FgLvne 2-4. Figure 2,4 Ptomure Roe gtialm Aswn*4y PRESSURE REGULATOR REBUILDINGKIT114NS310611 After s7acm drOurge and hipdroslatic test mtervah the Pressure Repilaox(N N SISO"Id51 mum by rebm 1t to enwne proper f m ure cgvrA1 vn *M Pro mine 14gsksun RoN iklmK KA(1'!N SSM11 Kure 2-T t:ffader A4xlrAarag Ilradet should be used It uKludes al aumptmenis and irwuv:aueu I" A n t: neoesadrr io pmgerty r&wid the prrfwre regulawIr w,. Sa I--%vre 2-S VIUVI MmT 1 %/xnN4 lath 2 , EXTEaNA I. WET CHE M IC A L R EC:I I A 14G E AGENT C5 (P/N'S RL1600&RL3000) O O The wetc hem Ica I ra:harpr.gent used In the ProTet II R&Aaurato HDIHNQ SK"W Fin SuppMv.K.n Sircarm 1.4 1%144muunm rarAv)Aelu+Kal tidutaal u tour, that as exvvmeh effectoe kir grease-related btdwn fares. 11m Figure 23 Regulllar Rebwid Kt exaagtnshing agent a armUmbe kv c►ionder redurgmg in 1.6 and WET VALVE TOOL(PPN S'Tl I 3 0 Aaiun avapmas(P,IN's R1.1600 and R I30001, Aflerrrplenl The Y'll Wet Yahe'lod n downed to 6cibtate the ebw di"arge.the attmgua.hmgagen t must be.leaned up the comder rake areembb It-3K-IIld be used to hold the p Immedattdt with bat.xup water to prerrnt corrc..K,n,-f acted whim rm"'WwIng the,4P Mid.t.,newntl► ArLeo^ SteFgure 2-& See I*ure2-6. Fguty 2-6 Wei Yalw'Pool + CYLINDER MOUNTING BRACKETS Figure 2 a WtiChemtcal RahnAgent (P/NSMBIS&MBI) IwSl)smixmat&-vLc0etla:tIlenerI.agtm sor►ast Pero:albra4eargoftheL*W.1-3000ard1.46001%p"-%,,Wby wwwhetscrusacom the M B15 Cyhnda Mounting 11radel Vertical bradlearg of the 16000 i,prcnidrdbT!Ie MRI C:timdre A4wlnlmgBndlet Tbow I CALrI-ION I brades mum be ordered sepa rad y with ea:h.Yil nler. See'I'Aie Re<anfdul wh hrndlulg,andtranr.frmngwA gernA kv.a.l.e 2 the f are causba Wear Vales at all aims. If l-ou get an►agent into rcour eTek Mob Can wth c lean wa le t fcv I l m mints and konl&la ptq,.i.tan V Tc.I1 geland 4"nil Isar AIM Hush A wtb wad mwr w prcvcw arreatun '11r agent fa electrlwh ccwdaKttre You must dean up ail agent duchaageda"id ekt'Wc+E:lpiiur►.aly/nc xna Rlnrlhe laments.►..n 190 I a c L K.�+11 III F.X4S21 41!rn�1't,IAT:: C y goer: C.>mf,�rwrm MECHANICAL CONTROL HEAD 16 GRAM CO2 CARTRIDGE(PIN COW (P/N MC H2) ITw w26*ttv m(X)2 C'a ri ndier im,nevu rmd a,p nou rtu l"W? 11wMahim-mlCon4wolHmd MIN MCIL'K amalurocrl Aclulwtte.livalurahea ablyAWQanrsgelsuwriedm onnortrlhadwhich can I*k,wuookwdtotheI.WQ1.1000.Id6r4 the MCI 1:Medlnn Kai Coo rdIleodaormtoe[NMCU2 Mask r Lm the 1.6000c1dwdervalrc metrl+llc'1lreMC!{:Med"mial Fmk-wim Sev reltwe2-11 C.omol lldd will anppoal a detect m hne-a RPSM Iletttote Modtwnwl hill 1.1so m and a nrdanwil.w rirc'trw(rrirra A gas T&IM Fke:trts2l SW&hs(Pt N's M%P DT2.MSUI'D'1'Z MSJPDT2.oo MS4PDT21 cal be arderod sgmratetrand bdd I yztr. 2-11 b Rram C:<):<�nr.c>Xc onawlied now in nn kxal nutawl a<tu,a►m fart the MC:H2 MeduawAl(:.moral"Old The MCH2M0&1Am AlC antral IIt Aj CONTROL HEAD MOUNTING BRACKET can a:tumeartummumoffrreOlcylindemwahthe (PIN MBP2) W26 I6Kram CA)2 caR"p Sm F-Sviv 2-9 Ile MOP:C:onerd!laid w uroug Oradet must be used to mcnmt the MCIll Matetool Canal Hard d tleooaltrd hmd ����" 2 n n..l tncnmtod i1111tOlir ana sT/itldrr.ahtr italrtrlNr.So*F�.ar 12 !'dare 2-0 Mahrrocal Comrd head err 2.11 Coraroi Head MouramIt 0rJ&et MASTER ENCLOSURE(PIN ENMCU2) PNEUMATIC ACTUATING CYLINDER The EN MC'U:Mato Enckmme s deed for nerocal mounting (PIN PACI00) ala wnI&1.16M LWWan Id6404;!under 'Ilw FNMCll2 t+.c. ul3tadesa med►Innticoollyduna-efanutJtmgthe rrodfctr 'Itr PM:lOo Pneumro: hwatrlfC:rUndercJnJ.t►sIc J anMCILMechlrnaiCcwltrciHatdAeENMCU2Mamw murmumofkn(IOlcl6ndesomulbrlewesk'fhcP,1C1t7) F.nclrisurr.anJ.lwlcamJsmntrnrrlfne(+Ic)finrtd&r%er+.wvtt meluda.aflC)1'�OA1iO.�londaprrwwordwehAr�ner.�e+t the(U2616gromC:U2C:Jnrw ie See l�turc2.1vA6o0o to 350PsIC;0 'U"F.-abrars valve With pfasuregruge.and a wul clluider cannot be moankd to an I NMCU2 Maser Prwkwwv motuamg bratet. See I 1 1} MC:t12MQc]IANtcili M C[TtTIL[II DOW' w OtCKlltiilARATIIII ••... I19*31A LC2 ICMT at WrMIA- r[MrcY�Qr1 Ci Ai'C21 12 SS" IA W IaetY F%mT saw f�tue 2 1. 1•la+aa L'rldhstlrc amr IN AMR"A Ftgure2.13 Piwamxx htuxmngCrlmdcr SI.AVE F.NCL0SURF(P/N ENS) The INS E•Ric Imwe is uwd ka reseal mcatnmgod a sato 1.16W. NOTE L7000ar 1.46M c 11 ruder w hen a A u+nl as a mm an&ry c rWw w asTstem Ulmertskvls ae the lanicastte FNMCU2 Master A MC H2 Medun*AlC:aaard IWdor ENMC:U2 Master L'ruiostue See I�Etme 2 1• The ENS EndmuTe ha no ooeard E'n3owrc mu.t be purchased scryradr and ccm ecled b the unit.:utdnat�.Itr.e.edmanMtte�kcmwlhanFNM(;ll2Ma..art PrK:10014tatnub:A.tuaur�<:►4mclrrt..�anlhraRK Frlioxae.v an AK:lI:Medl►tntcal CmNrd Hetd'Itte 4600t) cltmder cannot be mcwmkd in an INS Sim End-mu re .oLl IIOC: L key U III FX41VI ; h1rtaP161A142 TSUPPRESSWAI RANT FIRE SYSTEM December 1.2017 BuIWn To- Authoro�ed ProTex 11 Restaurant Fire System Distributors From Kevin Mu&wk,Vice President,Technical Instruction Subject- Stainless Steel Scissor Linkage and Fusible Links in the ProTex 11 Restaurant Fire Suppression System Reference- Pyro-Chem Bulletin No.2016122,dated May 20,2016 and No.2017120 dated tune 5,2017 IN MAY 2016.Pyro-Clem released Bulletin No.2016122.which offered the use of the Stainless Steel Scissor Linkage and Brackets in their Fire Suppression Systems. The allowance of scissor linkage provides an additional means for easier installation of the detection line while usinga continuous run of cable. Bulletin N-i.2016122 alsoallows far the use of SL style Fusible links to be used After additional testing, a second bulletin was released in June 2017.Bulletin No.2017120.announcing that the Stainless Steel Scissor Linkage could also be used in existing Pyro-Chem 8"and 10"detector brackets. This additional option allows for easier ret ro-fit ling of existing systems and rasirr maintenance. Heiser is now pleased to announce that the ProTex 11 Restaurant Fite Suppression System his adopted these added options using the approved parts listed below. 435547 Series Link"owing Detector Kit wd Stainless Steel Scissor Linkage 4-15546 Terminal Link Housing Detector Kit w.Stainless Steel Scissor Linkagr 435545 Stainless Steel Scissor linkage NOTE Install the t, Stainless S14r1 NOTE Scismr Linkage Dakota Ilra.iorts end as shown Stainless Sted Scissor lupside-down) LIAW are traAced as in the half of drown to Intksde the the detedw nurihing"A.PC*- bradha futdheat ` from the MCH2 {Mechanical Control Heady ti 35 Notrr a S'rtt Li!:r •SL I f L• 90 CAKANDAic,m NEW YORK i44z4 FAX:585,919.69"1 800.782.3937 Toll free Order and C1tsto►nerServrce: 1.gM.828.9638 20cs 08C 1 Ho It UI.FA4841 • Part a MIAMI Tex ll, �� Heiser JLP AUIUNT SUPPRESSION sysrE� 110165 Globe Model K 165"F Fusible Link 100"I 110212 (,k.he SI<xlel K 2121:Fusible Link 150"F 110290 Globe Model K 200OF Fusible Link 225OF 110360 Globe Muriel K 360T Fusible link 3(10"F 110450 Globe Model K 450"F Fusible Link 375°F 'Still robe Model K Fusible Lin la are ONLY approved for use with the S tat nkis Stec)Scissor Linkage 349H Link Housing Detector Bracket - l0" High Stand-ofi,Steel 225SH Link Homing Iktector Kit 210SH Link Housing Detedor Kit the Stainless Steel Scissor 1.inkape offers the following Iimital0nswhrn rtsed with either detectorbrackef optisrn: M aximum •ofdetectors: 20 MaxLnum length ofcablC 150 Maximum sofpdkys: 40 The Pyio-Chem Bulletins trtcrcnced above are to be considemd a temporary supplement to the ProTex 11 Tech tucal Man ual dated Detembe r 1,2015. Frr further in formation and inqui rim please conta0 your'Sales Manager or Kevin Mussack.Vice President, Technical Instruction at(SW828-9638 or emAilus at salewheberusaxo - 20t3,DW-1 Rev tl t11,Ii Wl n PenaPMAM C2irpter 2-coagwtrns FLEXIBLECONDUIT REMOTE MECHANICAL PULL STATION Neibk C'axtdun an be uwd wNb the Nemute Meattanwd ruG (PM RPSM) StatKm Amemltl7(PJN ItPSMI and Mechanwal Gas Vales Remote manatl oarlaol far be MC It2 Meths n:al Contrd(lead Sto F*nre 2-Y Fk—xoW(inrtdwtd ins mata.tlw nwd Lx npd ltrd FMQt2 Ma,Arr Frkiceurtr rt,prtnxled hl the 1411W Rrrrtta- E M'1'Cimdwt m*w mechuucal pol suoon and gas rake Ilse Medunnal Pu)1 Mawn-it as wa amaed to the aTsterst M012 sagrlrft�ntl►mivang/ieamerr�tmCaLitK.nnme 5«Tabie2.b Sledunxall:oaertillmdorCNMCU2AiastrCm3asiircl+� sta<ri:�,tad�aNe 'ITn■W bio w e n kwtl m��'F M-C Ca.tr.ltl n w ah aw na pu4�o r flea>bie s.n.AM rn fl b.erld►a rM�ur svn. ps Mwlwew tby n.. Na bk t.."hy-Iw t.Jl- w' pu4►s at each dwntyem dtrcaKan 'f he Ilr�1<l Nemote Ma htru.., ter. Rabkt.unlut biu Put54A&m 4usbte h.ledat the ptwn aAtlts.�w Sw FAll 2-20 aww Nwbk<:.r.lut-ym n.At�le.-yn t. I}yy Nnbkt:.u6lueW.,a Wlrtrr,a7rckl oy- NnbIsCnowwl,.01-P.,PukI e.&k t10Jk6t4LlNrrt,A7ackl 1, rclL'ry`g441 1N S[Of n„t�l n't.no..ru,t:untaWr Tathk 2-6 h4law 2-10 Nttmae W turlustl Pull Wbnn GAS VALVES MF.(:HANICAI.CA%VAl-VF-5 A Css Vake is regtu ed vis all%T stems u atd to pmtec t a pis fm*d4.%W►ulkappla my h..tas,ra.fkmm ttCgwillatf.l.tem aawoon See Fgue 2.21 A meduntatl gas mAecanbe maJ Fgure 2.Y.limbk Cortdu a wah the MC If2 Meclu meal Cn rarol Head or E NMCU 2 Mask r CABLE FrbAw urtr II�6.cmra+ctadtuttoMc_:H:Mabrrowlli,npdHu.! ax ENMCU2 Master Fndasure bq statnks&%wd cA*or flex"- ",.'tlumtter Su lnlem Mori C abk m ust be umd ry rh as w", aorniuN 1bMtaNetsarkeednM'FJtITCcmduNwNhctms•- deteaanandppsrahecortgoetmeregarvga.Ybkcatmadon pub„c,tllrttdo:ttrduNwahhrtd.arll�n.turgtpuh.ar 'Itre Stamktw yawl C';alie*�.tlppited m it)',2-W.i00',and 1000' er'h dlan�al titnea,an.'11te rakes are rated Cu n.aural at►d krgthk see Fgue 2•bAndUbk2-T 11efertotheCorTortertts LPda(6ee Ubk2-6) M«htm al gorahesarearatlabie tot*. I.w(forpatnuniben ors crmtps.stop sAmre►and Shobs killovorg,wase Ir N fr►Y law hl aw,w AMtrwww Wk. Or a we Wbtr or*&" ttMaw .t. wu. . TAV Atw PI-0. FY flit. ►i..w. .,nN =,oWl , ap■ i ..1. 7bbk2-7 .,rJt a�Swt,.<ir llM.rrrmdrre.w o/•gna]srt.fr ` Vaks and aim Ty Krti?,ti 6 oll labk 24 0 '1 f*ute2-19 Cis I'ifure 2-21 d000 Serves mechanical GM Valre 20Li IN1t L Rev I UL FX49JI Pats s Pit A t_ugw 2 canx lr m LLlil:'Title:isotkNoj LN GAS VALVES with KaL ON UNDPI)UL llvee Switch Km.PIN Ms3Pl)'1.2.and A(imxVahee.rerawd.vnall*?,*nau+a%ftopr%*ctapis I..nrr Switch Krl.P)NNSPDT: Each swmchhaa&vtofungk- fuded cooking applunx it-map gaaf"in 6tew mof%Timm i'Ae•ci**r-Mu m4r nmae.raid41.1amp,I HK12i.250277 aatutmn See fegwe 2-22 A UL Lilted electric gas sake can VAC cx 2 HP-250.277 VAC-Masmong lurdware and I2'wve by w,xt)wl+r ale MCH2 Ma he in;itCtmenra Head sr FN Mt:U.' asrembbesxv provided with mch km See figums 2-24 and 2-2 lb Master Pncitsuft.'flee valves are rated im natural and 1.P gas Vahvs are asaAkk to 120 VAC Ekarw pps vales are araitMe in the fcvlow aug ai vex,pa'PAk 2-9 • Kure 124 liearical Switch NOTE Pgm 2.21 Elearic 6cimcndl Gas Valve Nn elKwial aulne"ll straI by nude.wid e thr Me;H2 AlecistnicalContrul thud or the ENMe:U2Mama Enksaae mmmumn y � AN electruml winig 4ml exit the ommrd head through the �r tL..sa. tlx�rr. hock-cwm cmttw"at#ovbnt AlekttriaelunrmrrcOmx w•rt r ,•,�. mum be made in an apprumdelearicalbm wan ' i P Ott •. itlll •>v P. i PI 111.1wra1 Ric Ih' i P• r lot Tab&2-1 NOTE C A UL IA#*d manual edwet sv6rf M rvgunvd whnl cs n)t an t5winc gas rah a head II.day(PIN 9331 amy be used for th o. purporee See 1*tme:21) RESET RELAY (PIN 935) I xllre 2-2dlr Flxtridyieneuerct�m Ekxtrwga•rahewtetrgmArw�tcrosare pmrtdedm the ALARM INITIATING SWITCH (P/N 550077) inaY14innrAieaedIhismurmexl Seeligun2-23 1Tu• ALumInsu.mrtrXtwRh(NN rAW771canbefield-mrsmid within the A((:lt2 Me:lun►al Conud Head ar the ENNICU2 Maste r ITdicdv m 'fhe swan h mu sat tse rased to drm a%Wem w%l a nsl m to the bu ekl ergx tee n f vv akersn(urvl wMn the MCH2 FN)A(:U2 actumes.'flera aawn wil signal the fire alarmpand that that wasasTstem actumicm in the kmciaenateo The swatch ►m amp enx aN rw%vvw rl mou ran erg a,nr unm x a►ug w m h a eea�g mounting erestrawtransheet'ller sww:h a raid 50mA.2s1'I>r See I•*are 2-2*. dt,urr 2 2J k. -• N,�-i ELECTRICAL SWITCHES o e Ilse Electncal Swatcho are trmetded fcsr use with elmnc gas L' muses.ilia mu...wo&ax,c boobs.c arm n►►u xuppkvd Aec Ma puwaslmtoBdiev►xa and cxhaelatrumlderkextlutare Fipvc,2-2ic AlurnlmraetalXSwAh desagnedto Onsoffmiurno•ewhenthesrAem aaotuid Swt�hesareavatlbie in kni ontsw&hKet.PIN M��PI)'I'L'1'seo 20ts LIM L New D Ul.EXISl1 a Pan a PM AM e]w.a 2 -cking ooem PIPE AND FITTINGS RUBBER NOZZLE BLOW-OFF CAPS 11pe and fntm*%,mint be furnnhed by the atsuller.Sched&fro (P/N 550016) wink„+x3 dlrmwFU ed.a bla-k M itnifeulpmusth 'MItuMaKwA Itk»wallCapf PIN;ID01eihe11%kcpIhc twJ Gabsaitad pipe and(*I imp am not In 4e■wt oedice odthe nozzle free of grease cs dherwbwnss hi omki mlaferc wab agent dt stnbtn tart A wta m ng strap attaches the NOZZLES Ww-aff tap itI the ntwk. Kohler N,arale Rkn.+.Ir Caps(P!N Ncwks have been derdoped for V i once-pie run.and dud MWI61 are wU in purls ed 1-See F rgure 2-32 gtplimaws. A/ntwles irrre a Isar dw'flew plasm rakw and are �t�pllad wtth maal ttort�e bbw off.q+a S PI N lOi-120b211 u prcrenl ck V*:t* Each n mAt to clamped writ!te model m nbet SLvFvAurc2-.Nsn1'rable2-11 Applkat►vtlrmowavaare rigure2.32RubberOkn+OffCap prv►taiedmltedesgnacannt7�tltismanwl Alculnomrlebionlr- o$aps MN 303J206111canbeplrclus-edwFuratAr and are SWIVEL ADAPTER (P/N 423572) to pschul ed 10 71re Swnd,ldtpkr(P!N i23S?2].most,.�f a swtael nil.swrtel ltnd►,rncl rwrwllr/ A/ares:hnnno-p4►d "Iltr S►►i►rl Aclipter YUIN& 11""swas flaw No Jima the nm*to be rutted apprauimatay Win all dueatk-m* RLI■ In NDmir 1 !!tt IILIL IL 1,6.01. 1 Sec r tae 2-D- sur tr%­aI, L X.bf N YNt. 1 AI-IN DOT ,IRA 1 Dl1 "AM IF fll NMI R'DI S21/01110I UTA1NNGN."000UP Itmv - II O :11 �I <IP N 1OSe fIN)�I s1A LL TtItlAat CA 11 c►x rrrxlowt rs h%mm 2,U Swiwh Adg4w NOZZLE AIMING DEVICE (P/N 551265) The Navnfte AimrrqL 1)o+tue(P N 55120i1 o.retluwW§Lv"wl► acmeach nozzle so*womrataunmgp%mm-1lydmicecVrl�to Menouleardemtea satul6xrltXhtthatrcflectsonthewrfaa Plat n w simtrlL.� The natiGrk:sn IhNt hse tattslt+d b paten st a peedetermined aiming fkmi and then tomened to hold that angle. I 'nw a my%der wi r"wes an adarvin(PIN SS0t 1e1 to aNa it it tPthf nLWz1e 'f1!a,lilht muwlbe In.►Ke.1.,fanJdt Sec I utc hpa 2-ll N.aak,I 2' NOTE P4oTea11 Mcmksarc nurked asslw�wn tomdu tie the s+card TY RM 1 igure 2.34 NctaItAxnInjMv-oe 2013 MC L Rev 11 UL U031 tit Part a PhIA NI C►pter3 -5tsioem Down CHAPTER III SYSTEM DESIGN GENERAL .pcfwf*Wm met{r4-A0d0 e'Irtn fle.i.,,.a,f rfu 'Ilw 14. 1.t 11 R.•.uunnl lm%I., anS3rlsnl m,n hr goosed an juneddmaly mlotledua See iligwe.11 a number of different types of rcsu mart ctceofttng applmnaesand bond ani.iu i cxmfigtt ftm%The desagn mfonmatam listed in 1 ha w o win dcak.with the lml Aat were.•rd Pa rommAun of l hs.jinn engineered slomm.'I'haae anLvadwh resportubk for the dewgn of the ProTexIIsyskmmustbe trained and hold acuim Ilaser R H�:1.U:�en Aw ate i n a I'nil'n 1I triining Iwryn m r n Cu- This seittom will Dower the pn,per dc+*n ofthe ProTa II Renuunnt Frrc SuVM�.w.to Syaarr i It o,dwided won lour WI a�.ro ranuic se a aarw. .t:?I wde or%in n% .NcuAe Ccwerage and Pl►anew .PrprnIt I.uneatrue. .11teb.t ur 14�pt rr.�rn.TrA �' Each cdthese sea worts muss tv..cmtpklh understood befcene amlanlp61gany ewulabcut ! urn 3 1 SYSTEM CYLINDER S123NG LINE FLOW VUC I PROI'LC I'ION WI I'll IL NOME Encodthe rwmnlesinthe sectwwL'NovkCowrage and WX NLI11 IlA,enleam*hwA+own Arm fwmt►,tlue Fandt�a�nrr.lM.r.�rl c0 and encan safuta tow xrnutwn nunberofflow puen to,lu.ed Ile ILNauklPtN NIAIJ saorte(11 Soiwnoale Awrgk IL on the vo bum e of the pipe used Sdea be sy win cybndetta by nor At a capabk of protecbrot sglure or recta rtgvlar dime witIt :A-Wiw%the"A number cs Mmpnm%A.w-,mwdwiththe ynstamrumjow"i claufW(maamlum%odeafl6%.withthe applsances{tl_plenum.and ducts,pM the tout ptpag volume cl gonal beinga maximum of l64'. It can also pmva a round ductweha nu atrnumdumeleroIb*SeeFWms W-l&1.3- NOZZLE COVE RAGE AND PLACEMENT 'Ilio.%%Iamwil in.nwinKtiskbnC.IurdclernsmmXn..uI Ib0' trope.pce.n rw+g-and qu an got y hu dui.pknu in.ard apphtt►r prat e,b not twou'1'PMIYCECTION it a ma fvq mrd thtt thr(an hr 4mom down or!Ie r ah.es t d u.t beciart4eered lot the systeme operate property.E.achnoukrs FKvrelI Masuntun recurgulirdt►I;v run e4erof kW approe cd to pro tec t a hau so dui s of a rdi in*d length AN dua"dim 4 UL bswd wallou t 1tmwbon of maxmlinn ductkrlgth(unbmrtedkrtgthl Thmom3tldmalvaraebesof duc'1worltabutrherv.m/alandsaat alir~katltnitdun'Atha1ninaI 1e' argks to the horizontal and ducts with darataon ds al ben . I INwtPmo:1ticon w fv ro,glut anortlrhr foomAimedtoasdlnrve nutheduct'Ibonuzksat"adabk for ductprotamon Fgtuto.I~1 MAs root room cyhrdtwaIJuoduno coo et.dla' lyu III It Timm I%Im1Ala)al 0irX.III 1Arw .rrr4r III llw:ItwI. 2015 UIlC L Kew 1) VI.EK491 11 Pan a M A N2 Curler l-S,rsse m 11e skm TWO F LOW DUCT PRtYI'lCTIONINI'llf 2DNOLLLE TRANSITION DUCI'S-SMALLER'1'OLAIM&K 'Ile2DAtwinonlOP,INH11Dli.ylwn(2l flow ncwAr AtrinSk21) In.a.awhm the dwl,rienumrnkrukvg nmlt8%,mnierthan rwut;e ac4mbkof proteoongrecsrrgtltrdwisWitha mislmum :-.e final eshaut dwt.measur the perrmeky.1dumeterofthe Brad perimeterofM*.with the dugoml being anummumd)7`' It %hauoduo Thenoarle(dis lobe located within 0'-6'cdtheduo! .mdsnprcACAymunddswlwAhamatmrsanddmAaa(11�' rnttnttltrkr�Y,�R11rrMAinlhrc�Itrin� "we F*urc3-S. When two(A NL2D duct mordes are used to protect a urigh do.: Iht crcwh rrrClinral arw tithe ck►.t rnuhA bt di„iArd pact Iwo esph�l """„s"'"" area•7Le swulemuht then bemstalladln the centerofthearea a protecuand amrddhrectlr1ntothe dwwtorenu* 'rkANSI'!'ION DUCTS 71e prenit<Iirm Aram-.0 n.L rsl ckr:b rlhcwld be res u-►w sl h? the authortt7ho-ng iunsd.00n'Ihtnaitlonduts 4&vAd be protected as f Alowc Figure 3•5 Tra nutw,n D wt smaler to Larger MU U1'1PLE RISERS In<nm d mukq*ruin,mob riser is preswaad as an indiridwl duct-Ste Pi/we 3•t< DUCT tuba KM VAA/�rMrVT 19 14M tNl:j "Woo ~ OIJCT Ftsslrc 3.4'1'ramatauuh lhla I.argr u S.mala 'I'R AN&i,r ION DUCT S-LA R1i ER'I'O SMA L L ER awh.n A1NM Int,.asawtere the dhwtllhterehrnamrlatsctjserunXr Lhr)arthan the fin cit w du t.me suw the Is du of the duct Ptgvrc l t AlulmFie llhsen ha halfway bttwmniheLa"andsmaleol aect son(or the arerage ELECTROSTATIC PRECIPITATOR 1<rvuelerklunwtrd The tscutltit.lobrkviledwrltan0'-6'd1he dwwt.Tknumuhterboe octat the point where the meaaurementwaa lhac as,ualaigck%vortatic pro;".aoramustbe protected t.Aen1.cente red urderthe fin deOuuA du t opt mrig See 1'-*vie above and twkwthe unit St,mdrrddu:tnouln ire used mhos i 4 a"Au;a sm See IiSwa 3-7 N(YI'E lD ar: I Nowksto pia«i duaa with»tarwAim that is mm t iban 4' in bcigk wtl be re"ved to be ptamoned an the opt rang d the tranataorl k mt the bocd Y to d'h rao the opening uong Plitt gtAii7lt rtancbrddut:tncutlede%%ti its r.hmea-r. in I NUM 20 NUM Fyttte .1.-7 Fkctoatrtic Preeirt111ew 2015 IJIC L Ref Lt 111.F:R4S21 14 Part a PXIAM -;�trr 1 �Kxm 11r+�1 I'1 I♦C'M Pittil'lic'CIoN On N'hank pier cons The nou kt r1 must be kx-awd at the center of the Y ivnk wl<ith t-,of she mttcal lteghlcdthe filkrs On fie Ili ravdr WIN Nl.IHI is a cnr ill Arm nm&ustd lnr ungk Hta bon►pbnumRthe nm&nmm bo kwted i kawn tht *mun pru accal Autgk lllaomkcan potecta pkmm(w,., bud edit of to The r.Kdown fi m Iherertkalhetgirt Fmtobw %inOtor V h1n►sherd IVkn*by 4'wtde Dmdmgthe knp* apsbcattcm.the nowAt must beb atedwtltm e•ofthe end of the MOO W-7ransapultoorkrr.thin Win lrrgthsrtdPcwm..tnIVA-1 pirrwms4mnsoMelond awned dw%%ol►down she lw%%hcrlshe nazilea the starof cut wc"can be Jane topnra►ager plenum 'Ilerloatfesrrn�pwrtttnop¢recrtedsntw►cas4vgas ;ae Dunk the a ro oe pkrttl m area a prcaec led and the to'I tmsttton a nM aceedtd 114.r l;g.00.1-9 w 17 w -v ",o tut l�tT1 >rRatrp yIT tO R(lt 1 no wB,ANK IIAI11111M SOFT a.tW4 N MQUMUAI s' f ?l0 R 1 oor �M wN I� :I r MCOtrtt'.'L'r FIDE We.14 1'krnr Ill l'nrl4%ts.n APPLIANCE PROTECTION NOTE When puutatag app6tnmswlodl are larger thin sogk nololkoomeryte_muhq*nmAts.:tnbe u+ed I.arXe+appM:msr..anhecfi.wle►1nrl��wrerJm�.dukr.raCh,• .�� to or settler than mn#e nozAc omerage. kscepwin Freers nM etceeda masunum 4864 sq In For mc4uhruingfrl'es. rpf w t n-I'mMd rn X.I.1 rite Fr 1e to b►hn I del K 1'lay r &n is I fe p.gc=4 100 111C L Rev 11 1I I\till hsrtsI'MAN: C6"r3 -S►s>ten Dc n Design Index Chart and Nozzle- Coverage Summary Sheet ki. s,o 31n Mn kla Nbadr Waft Weak new Ilgeb toMb Ana Hd01 Hftw Aplbaa klsaml Ftfart 7y/a Fdmbr 31a Waft 410 dal Aral drr 4101 061 krala WARM DrV g6ad N !) NLM 2 11% Iv 4 4a ky.s wAm;Prip guard L 314 MIL 2 19 11 14 11 11 k7m w.117ny lkwd H 3•5 NL7H IIwP Vat 7% U4 4 48 `r""IA-M II Ora>.QC_ouhmV Afar la S00 4 48 kyon VOIkv NI.Vd H 1.4 N1.2H DOW WI Iv+'a IT :I 414 ((Mdrd>•1) OrawUC. Amo;Afa.'J 261.4 40S 4 4A gryas MOrop Board L 3.5 N1.2L 2 De V%I 11 324 U 11 OC4dlmua II (lrnarfookmagAm 27% 700 13 4 NY to WlVV guard L 3 5 SUL 2 Dccr Vat 19% rl U 11 (CordrMas 21 OrAYCmAong Anal am "'I Is .4 71kAkdki.MrmamegP&a H 3.7 NL2H 2 r% S00 21 4a TIlt*dl.e'gram"114■ I. 1-8 N1.11. 2 r% 100 II kI SrJI R■SW H 3.9 N U H 1 12 21 136 40 M law R zw VA 3-10 N1.11- 1 4 4 784 34 48 im dl low mW w!lb.krkd( L 3.11 N U L 1 L2 IN 136 U 24 P AM man �>rl Raa w rrlgaa*d%.lf I/ I Ilb N1.11 12 4 Ila 4 M N,wv Was S•f Wok )1 3 U Null 1 24 D6rmam kka 6 14 48 �adl VMk I III V U 1 1 H 1)rrAw kAra 6 I I 4 Larr Wok H 3-l4 N I VH 2 A Dammam Abs 8 4 48 Ijww%%A I I H 141.11 21 Daowm kArx 8 11 14 Saw/Gmlrlk H 3-l6 NUN I 36 1080 4 48 Sall(ifddk L 1 17a NLI L 1 36 IOAO 10 1 1 111101111111� some Grldk L 3-lb NU 2 36 1080 U 14 1arw(Axille H I Ia VI-III 1 a 1110 11 la LaryG Mk L 3.19 NI-11. 1 41 1440 10 14 aad"a Char DEAN )1 1 4 VIM 1 26 624 11 4a Radaechaphadw L 3.21 NI.IL I 26 614 13 24 Lrpr RoJt6t Wr grata H 122 N1111 2 36 461 16 la Lear lydmnWrlkulm L 3-23 M-2L 1 36 864 13 36 Lon%XA cur Ira er II 1 4 NI1.21- 2 4 611 11 1. I.anaMma(hop 11mvllw 1. 1-A N121. 2 2s 624 IS 14 SuW FodClar grollci H 1 26 Nil 11 1 24 1a0 2 1 1i (MM.fed deplt 6*1 SoidfirlCba•lbiba L 3-r N1.11. 1 4 480 IS 14 Sals6lamdergrutla MA 3110a V1311 1 31 1: 16 la UprrklSJraalea Hrtrla NSA 3-30b Nl.l 1. l 36 21 Prue Edrr rbax lle lratr llaaar Ptiy 111erl1uao Rod NVA 1 11 N1111 2.1 scespold latrlaMas .N 1-11 "ew Pew Fneff DaW LA MA 3 32 MU 11 2.1 Scespwad lrltnags .N41.21 NuawgaahoMaldWit VA 3.13 NI-11. 1 Scwsp"lardrML`as WA otaht omlp Nrarn galkmAtritO P -11 )YA V$4 MI-21-1 2 $"%Fw d Imtnctama Ekasa grunt alma Cawlr.l saka.Pride sadae VA 11; mill 2Q.2 SMSM111atrwams w ad1 S"cf gut Cho agallm(ImarasICbsombaal N4A 3.31 NLIL 1 31 hue Edre 1'.3' ADW f or'baa I%Mma Snrb Ib rk!V Ilak H N U H 1 4a 1211 II-6•i.ar wsd at 00— Dlwt Pala D6rmKmm lint mmolo rl 0 avla r Drcr N 1.2D 2 14 an balm 100 5111, Mm mpWOwdarOw NUL 1 17 so 16 20119•DOC•LRaD UL EX4S21 17 Pan a PMA)G Casa l S"m 13emp Fryers %ith Drip Bogard (High Mount Nozzle) CAM1P.t:rif)-Ncu* NUH Fk»f Pctmts PerNca* 2('llto1 NuriberofNmrksRequired 1Klnel Mmmmm AraaofPolco&wn fnmL Ilon Ueep Via GoAmg Arm 3-14*quieemd,eswlth imasunum kmgoA slded,menAmncd vt 4esdieda drip bmrdl OresJ1Con11ugArm MOm*urv►ricbmwAha nustinxim kltges1-Me dlmemsim cd274' Gnlwc^dry"rd1 C*"Lnti 1 Deep YaC'.oA wegAral 311"we uwbe%wiC amnunumkmgat tidedunemicmc.419W 4e%J ladrepbmrd1 Ora 411ContngArs► •143sgiliremdwswithamastmllmk'igemWedlmenomo(2�►►' On4Wea drip bmrdl WIVIC Is+01ann Anyw10 n e►mr Owe harafd,.place Nearb H.*M 24'.411'AKwv IN hvtilyd muffim N�.rri Alttur% •tmwOAiOwmenert,,flhbarinlmatilx Nt►:.lr/nu,u be ltr aeJ an vwhem wl dll tl die Ah adral au a i a testae tmd a l der cai ler o f tll a lrt:af J:eu tfat r- (►v nLu I ov 1rLu I (AM►10M1 A93A (AM6]M:AII.tA 1(NII:hTMIn I(V*;1%7%IU f 4" 1►1M1?(!fA(N f _ dt71El. I►t ITNNI(rt H- ' 1`1(:11 ,' MM1V<i f <<N►AN<6 AREA � tiR!1 1 � t t I 1 1 I 24' 24' 1f4"' !4 T _ 1 vI(gt:AM /% 1 14011-S I N('31IS MtLiMUM i 1 �� 1,44A2M11N F*IP%'f,T la' 111K' 1111 PPAI Oil � �IeNOB\ 1►Rlr1p(►.ARIt -'0� 1,(M{Q3T SO fit StiE l►MUMMO t 11tiMINlION �E11'ATI 4"ilp AT) lenldltbu 1 liur/ubri: Figme 3.5 Frjen with Msp Owed!Ilglh W,um Naukl 1011 IM1C: L key 11 1 4i:l :o he"aPMAHI e3ipter J- S?aem IlesW Small Range with or without Backshelf Protection (Low Mount Nozzle) NOTE. lamPLlwr♦Ncu* N1.11. Fiuw Palms PerNare* 1"Cl 11 the rases kei a hn-AeAWQ. Number edNaz*s Required 1 4Ont! the no. kha' MauunumArcacdP"cc oon 1k%%WjrealdwswlCrk-nLwstmde&nrriwm% ls' tole A7rrr) Irrprlvlew NnakLowoon :1'fmmlhec"ionkedge-.4lhehmardwrf.weandoenkredrrg)n; IAV bri*W of ml Ike Awl end Nateir ti.y114 13' 2a'yhrnr the here•r.1 Mrr 6cr 1Y Ni*its Jmivattomr NWAC 1j till fig Mmadala Iannlr"IOLi omhdfolfft r*uek twiXMArnrlho o)the no: ap pium e a nd akmg the r*td k A ce merh ne Ar 4w fiarmplr!f tAk.resxL nu,wnu,•kd 2.Y alvry AAe Aaarrd emr*t:tAr atarlsvpalal sWM U lle tt W fromr Ame op'plajmV edge q►tke apphame on rrkick he rouk b A -a1ed See ►Vuarrl+mr Exampk 1 and Exano;* Wn GriF*W Rermmmawa Sm (;k(urtl-11 Nark rRwrt for lusted Owightwar)anywhere wither the Aliened area, and luta ird tut Iht Vt-riSk a ruler 6n►ester ve bt hwa roll an r fifer F X A MPIF.1 Nock a 11' >r -� ACftCwr Ad,rAll vAatll��EE ✓ , ' Ir armed6k'irum 14 Vlll AI W!K. / 44 1* i lxA t t�(t cd AND / � �� ipratcl�snLcr EiAN/lE� ci • ` 1r :! D Q kXAAlPlk2 Q __ ter• Ncurk rr:t' milt T above muiatt E! - 51IrE (R amrd 11 c'i 1 IL in,no marl cd 1 Aua>rdsurLce r �J \ ( P24114 r Fegure l•I SmalI Rerge (Law Mom NorAel 100 1*C-L Rev 11 lILMil is PertrI'MAN2 Small Griddle (Low Mount Nozzle) I:vnlalswryNeaAe NLILorNL2L Flaw PourMa Nee Norte 1"el N LIL or 2 Owl NL2L Nurnt+a cif NarhesReyu sure d IQOnelNLILarI One INL2L NaxunumArraalPmAabon IMsquareindwswAakmp!-4%%Jcdsrmmkno(Ie' NoukLocawn KUL•Atkweinyavrtaofflefurarcisurfsce N1.21.'0'-67(TOM CdFwn..I*IV Ihclucrr.l.urtrw Ncurfe "e%M NI.11: 10r-2{'ADcne dw Iucrr.l nurlr.e N1.2L7 W-2.f gram tfie)art:rtl Inrrfic KcaAt .L nos rt NI 11, AI o"1 12'rn:rai 12'.nee h sno Ihe.orner Isirnr tee note. N1.21 .0•re.r rAer arl I Ire lure rd err rte�e (;t,r ldn. Il.-pte wI tr tarn Sae 1*u race 1-t7r t)-17U NL1 L Na:,Ir moist[r located dfnrdl y above any mrnerof the hazard surface amf ainsed atthe inreraro ring point 12"Awrr each sideof ke Corner Irluw 111r nook. NL2L Na-Jr roust be located 0" 6'•jroat either of the shori side of door haatrd surfiIa. and aintrd at the 4rntrr ay the haarnt sue stir 1407112 C AN luau SQCAU "MOttmTtb NCHS AT tIMA MAY tM UW 1 N U COOMG AMA MCNINTU),41110M I �YY tY►Rr t a � I 1 1 1 :c ur 1 se tr I - I � 1 I= I I 1 1 r 6' JONGIST twit I1ISn Vc X014 - �• 91QT S"M HAZARD AIR FACE I,i.iic 1 Inc N1:I 5.:_c I.q.aw A 17% 1LZ1 `. •..a UL EXMS2I I Put a PMA N2 C�Q J- 5�srem 11es�/I LarW Rad Wit/Electric Char-Bmiler (Nigh Mount Nozzle) 6.unptj6uryNww N1111 F law KUM%PCINcuZ.� 24'5o Nunber of Ncades Rap wed I OOnel MmummAnacdPrctecbon W s turelndhawnha k-agat s;k*dunensscmof Jp Norock"wn Abcw anyccwwrcdthe lurardsur6ee Nar de I feghl le'-49'Aw"the him rd w r6.Y Node Alrrorig Avnedatthe omwrcdthebroier Graltn; Rq+"SmUuon See rvvrc 1-n I#Ao=k must be loco Ord direrrly above Bury canna of 1hehazwd surface. acld AIM41 I rllecelder of the hazarsf surfllte. i { ND721 E GN" i MO14TIEVAt101'E ANY Coot" ~+� r I I 1 I !!r 1[MM1 ES4 ttI DE '11 M�cr��c{ 11ttHE1�ION MAIM 11 M N�F NII:N C(KIL PI(i 4M 4 PipK 3-12 lame RadmmIEJwvnc Ch:-Renter 010 NImi l Na Ael VI.F14MI 40 CJAqvoa 3-S"m tkupl PIPING LIMITATIONS Oia:ethr nmAr placement and Quantal►ofcy%ndushatabyn GLNLRAL PIPING REQUIREMENTS derrmrmed■!s neoessa7toderrmrae finepep�uoa(galratioems between the c>r6tmders and the noulea no section coarlats the L *A pringand mrairlt pVNS are bah al awal on Ruiddows and lmilations kw drxigning thr dwtrf,ution pipmjl.t. LI600.L1000 and L io0o s7slem■ that the extin`ul"Eig arm win dis3nrp from the nornfes at a 2- Lb00oquans must use spin ptpling onil.wnlh no proper flow raw.TWst limitations naolabbe nekrredtowhen node kxardbeiore the.pin,and wnha maximum of 14 malei4 ante mcwaninp kusicn ix thr gfindrm Mm points per aids Wminim{mi piping mumt he%"mp to the Arm 41 it The nt unm in Fpt kingihs are booed on wmrnol F%v ralane 3. bl.r a,raaarn lobme hr%,pipe betw.•Cfl a nocile F,ach sire cylindrr w a0omrd s minimum and masimum total and the praadlnt tee is 410 mis volume of pgin`,cakvLvcd to m111aem 4 M.a l,mtmr flow numbers(cw W papa a 6 71ureisno need todsirguabbrbernwhotparemcilhoF S S. M.rxmmumnumbercdekvow%betweenancedeand is orgplyllne and wont poruon a branch lone Oolrthe total Ihr prrcrdaroi WC w i •cilmme cd 6t ocvm 1c prpmg nci vKA has to be catodmed ^ Mixanum c+f 2S d om are allcrwed m n the ta4 p`q fit x?aae nl 7 Maxarnum dlfferencx mekraam baxweenthe Volume Chart c}Imdrr.wniki andant ntV*w IIY Wrpa-205m64t a. No traps arealknr,d in the plpmgnetwoet ta'peps-37.5 nliilft 4 Ihpe kengthA are measured from center to cxmer of fit'p>Fe= Spa mkAt. (inmjpi �'ppa- gSAmblft few terse Pipe V�dame data.see par 9D ID '11w moomalo"pahm Wigth laiunw of(stir*. date not lore to be consadmd as pan of die total pope Apat Dentition Hose=JOOmVbose .dame H. WhenaLsing,dill'a ntstreppeinthesTacm.*w CY LI N DE R C HART brpsl use rem st start two and the additional peat mot .%I&.mw.n msaa..mv-d a... dr%weae aw A approwhes fee iacvnfn Aluumm Pa• Alorcdntv... New Velon, part!kWou a l— 12. ERvw(d or sword adapters located at the noa Ae, c:rl..d,•ems ?%**a s maWlrrat Somek rmaYalsev do not have to be ccwud in thr is eRaaw ma aimunm one requwement ban, I RducinjlMslatrta..rrra love alwheaadW"to8 (;"= ., ..., ar" mullea pipe site I N.,n ♦a cal.4 ,4 t.m poi N Mdthaewl plpirmR agum nl.•aA.,►!wnpnAa'1Itg1.a 1.sm range.wdL or a(ryv: .s(.lu■ tow sow L WW- )k mmmum of 2"ml and one(1)flow ..,40ne numbws raquirad in total sTsilrm Of tliait mt mien.MO ml and one(1)flow mn*w rs must soc.ua. w r�sl ,),pYd. bit aisrdsoorbeire ohr argawdLer(rysr 1.um L 3000-Minimum o(300 Wand low 441 flow YI P,^a...Y dr a.r.1�J rvP..mr•Ac..1a J,d.mar n alnb m regd ad in octal spasm Of flaw nr�ac.i..tas.a. mtrnnnun.2M ml and two 0)flaw numbers most beaiudsoocbeiewthr argawdLor(gaw. • L4600-Minimum d660 ml and tan ODI(km M1%tt.u sl P I Pr Ybru sa n s tat A members rrgared in total span Of fro fat i t.RA M i.A N n W arc mi nnmali.1160 ml and two 0)flow made is rimot r:road. borwobsidsoerrbr(ortl1w argawcLor(rpr %so tam m.oil Anne b.a..O WN.* • L6000-Minimum of%0 ml and(orlAtea(141 t4400 eyed-I Now N aamd-a11o.R (law numbers reglltrcd ti told s*tatJll-Of tint tsouo pod-sfbmRe "got-a now A miraintm.l2Dml and 2 flow minWn must be 1*.s, seal-aNmA 0.at-a now A uilkeda1orbdtovtawarW.wc1Lor(rwr. 11om rtod-yNmSPIN m.o-aamft 2015-DDC•L Rev Ul.Fx4U I I %to a PMAM CITY OF ARLINGTON 18204 59th Avenue NE,Arlington,WA 98223 INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551 BUILDING PERMIT 16415 SMOKEY POINT BLVD Permit#: 4149 PERMIT EXPIRES 180 DAYS AFTER Parcel#: 31052800201500 DATE OF ISSUANCE. Scope of Work:Kitchen hood and duct wet chemical fire suppression system Valuation: 7737.00 OWNER APPLICANT CONTRACTOR GRANDVIEW NORTH LLC All American Fire Protection Fire All American Fire Protection Inc PO BOX 159 P.O.Box 393 P.O.Box 393 ARLINGTON,WA 98223 Everett,WA 98201 EVERETT,WA 98062 4252683514 4252683514 LIC:ALLAMAF854QF EXP: 11/06/2021 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR All American Fire Protection Inc P.O. Box 393 EVERETT,WA 98062 4252683514 LIC#: ALLAMAF854QF EXP: 11/06/2021 LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: Fire Sprinkler CODE YEAR: 2018 STORIES: CONST.TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: OCC LOAD: PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation, guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City ordinance,regulation or order,state or federal law,or any order,proclamation,guidance or decision of the Governor. I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY;NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC 110/IRCI10. SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on your sales tax r•turn form and coded City of Arlington#3101. i Print Name Da a Released By EKtc CONDITIONS 1.Permit and set of approved plans to remain on site during installation.2.Final test and inspection witnessed by City of Arlington shall consist of the following:i.Orientation of nozzles shall be verified with the use of a nozzle aiming device.ii.A nozzle cap blow-off test shall be conducted.iii. Signage shall be provided on the exhaust hood or system cabinet,indicating the type and arrangement of cooking appliances protected by the automatic fire-extinguishing system. Signage shall indicate appliances from left to right,be durable,and the size,color,and lettering shall be approved. iv.Installation certification form to be completed and submitted to The Compliance Engine prior to project closeout.v.The hood suppression system shall be connected to the building fire alarm system. THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS, MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount 10/20/2021 Suppression System $200.00 10/20/2021 Processing/Technology Fee $25.00 10/20/2021 Fire System Plan Review $148.67 Total Due: $373.67 Total Payment: $0.00 Balance Due: $373.67 CALL FOR INSPECTIONS Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon " CITY OF ARLINGTON N ` 18204 59th Avenue NE,Arlington,WA 98223 INSPECTIONS: 360-403-3417-Permit Center:360-403-3551 BUILDING PERMIT 16415 SMOKEY POINT BLVD Permit#:4149 PERMIT EXPIRES 180 DAYS AFTER Parcel#: 31052800201500 DATE OF ISSUANCE. Scope of Work:Kitchen hood and duct wet chemical fire suppression system Valuation: 7737.00 OWNER APPLICANT CONTRACTOR GRANDVIEW NORTH LLC All American Fire Protection Fire All American Fire Protection Inc PO BOX 159 P.O.Box 393 P.O.Box 393 ARLINGTON,WA 98223 Everett,WA 98201 EVERETT,WA 98062 4252683514 4252683514 LIC:ALLAMAF854QF EXP: 11/06/2021 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR All American Fire Protection Inc P.O.Box 393 EVERETT,WA 98062 4252683514 LIC#: ALLAMAF854QF EXP: 11/06/2021 LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: Fire Sprinkler CODE YEAR: 2018 STORIES: CONST.TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: OCC LOAD: PERMIT APPROVAL The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation, guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City ordinance,regulation or order, state or federal law,or any order,proclamation,guidance or decision of the Governor. I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/IRC110. SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on your sales tax return form and coded City of Arlington#3101. lD Signature Print Name Date Released By to CONDITIONS 1.Permit and set of approved plans to remain on site during installation.2.Final test and inspection witnessed by City of Arlington shall consist of the following:i.Orientation of nozzles shall be verified with the use of a nozzle aiming device.ii.A nozzle cap blow-off test shall be conducted.iii. Signage shall be provided on the exhaust hood or system cabinet,indicating the type and arrangement of cooking appliances protected by the automatic fire-extinguishing system. Signage shall indicate appliances from left to right,be durable,and the size,color,and lettering shall be approved.iv.Installation certification form to be completed and submitted to The Compliance Engine prior to project closeout.v.The hood suppression system shall be connected to the building fire alarm system. THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS, MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount 10/20/2021 Suppression System $200.00 10/20/2021 Processing/Technology Fee $25.00 10/20/2021 Fire System Plan Review $148.67 Total Due: $373.67 Total Payment: $0.00 Balance Due: $373.67 CALL FOR INSPECTIONS Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon HOLMAN RECOVERY CENTER INSTALLED BY ALL AMERICAN FIRE PROTECTION INC 16400 SMOKEY POINT BLVD. P.O. BOX 393 EVERETT WA 98206 ARLINGTON, WA 98223 PHONE: 425-268-3514 FAX: 360-631-5146 LINK TEMPERATURE TO BE DETERMINED AT TIME OF TRIP TEST DUCT 12 FT. HOOD 2DNOZZLE 12"X 12" PROTEX GALLON 4.6 1H NOZZLE 1H NOZZLE Appliances 6" 2H NOZZLE 2H NOZZLE �► inside hood 24"-4a" y 36"-48" Appliances 6" inside hood Connection Fires stem to electrical intertied to shut down buildiing alarm upon system. 1L NOZZLE �1L NOZZLE 1L N022L activation MECHANICAL 1 13"-24" 13"-24" 13"_24" 1L NOZZLE AUTOMATIC 10"-24" GAS SHUTOFF o � o CLASS X WET CHEMICAL EXTINGUISHER SHALL BE INSTALLED �48'ABOVE FL THE FINISHED FLOOR QD e (D o (J)o 42"—48" J - L—b _Tf I� REMOTE PULL STATION 6 BURNER GAS RANGE GAS GRIDDLE GAS FRYER GAS CHAR BROILER SHALL BE INSTALLED 42-48'ABOVE THE FINISHED FLOOR AND A DISTANCE OF AT LEAST IOFT FROM THE HAZARD BUT 36"X 24" 24"X 24" 18"X 24" 36"X 24" NOT MORE THAN 2OFT.IT SHALL BE INSTALLED IN THE PATH OF EXIT AND REQUIRE A MAXIMUM FORCE OF 40 LBS AND A MAXIMUM MOVEMENT OF 14'FOR ACTUATION PIPING SIZE UL 300 COMPLIANT SYSTEM 3/8" PIPING \�Texii STAURANT SYSTEM MFG: PROTEX II 4.6-GALLON TANK SUPPRESSION 1/2" PIPING SYSTEM CAPABLE FLOW POINTS: 15 ACTUAL FLOW POINTS USED: 12 3/4" PIPING FIRE SYSTEM AND APPLIANCE DRAWING WILL BE DISPLAYED AT OR NEAR THE SYSTEM MANUAL PULL STATION Permit#: 4149 Permit Date: 09/21/21 Permit Type: FIRE SPRINKLER Project Name: Holman Recovery Center Applicant Name: All American Fire Protection Fire Applicant Address: P.O. Box 393 Applicant, City, State, Zip: Everett,WA 98201 Contact: Kenny Graham Phone: 4252683514 Email: allamerican fire@aol.com Scope of Work: Kitchen hood and duct wet chemical fire suppression system Valuation: 7737.00 Square Feet: 0 Number of Stories: 0 Construction Type: Occupancy Group: ID Code: Permit Issued: 01/05/2022 Permit Expires: 03/20/2022 Form Permit Type: Status: COMPLETE Assigned To: Ameresia Lawlis Property Parcel# Address Legal Description Owner Name Owner Phone Zoning 31052800201500 16415 SMOKEY POINT GRANDVIEW 230 COMMERCIAL BLVD NORTH LLC /SERVICES Contractors Contractor Primary Contact Phone Address Contractor Type License License# All American Fire CONSTRUCTION COA Business Protection Inc Kenny Graham 4252683514 P.O.Box 393 CONTRACTOR License 602865777 All American Fire CONSTRUCTION Construction Protection Inc Kenny Graham 4252683514 P.O.Box 393 CONTRACTOR Contractor ALLAMAF854QF Inspections Date Inspection Type Description Scheduled Date Completed Date Inspector Status R20.ACCESSORY 01/18/2022 STRUCTURE Commercial Kitchen Hood 01/14/2022 01/14/2022 Approved FINAL approved by Fire FS07.FIRE Kitchen hood and duct wet Not 01/04/2022 SPRINKLER FINAL chemical fire suppression 01/06/2022 01/05/2022 BUILDING Completed system Final Plan Reviews Date Review Type Description Assigned To Review Status 1.Permit and set of approved plans to remain on site during installation.2.Final test and inspection witnessed by City of Arlington shall consist of the following:i. Orientation of nozzles shall be verified with the use of a nozzle aiming device.ii.A nozzle cap blow-off test shall be conducted.iii.Signage shall be provided on the exhaust hood or system cabinet,indicating the type and 09/21/2021 Fire Suppression arrangement of cooking appliances protected by the BUILDING automatic fire-extinguishing system.Signage shall indicate appliances from left to right,be durable,and the size,color,and lettering shall be approved.iv.Installation certification form to be completed and submitted to The Compliance Engine prior to project closeout.v.The hood suppression system shall be connected to the building fire alarm system. Fees Fee Description Notes Amount Suppression System Pre-engineered or Custom $200.00 Processing/Technology $25.00 Fire System Plan Review Table 4-1 $148.67 Total $373.67 Attached Letters Date Letter Description 10/20/2021 Building Permit Payments Date Paid By Description Payment Type Accepted By Amount 10/25/2021 Aaron Graham 89330547 $373.67 Outstanding Balance $0.00 Notes Date Note Created By: 01/13/2022 Pinky&Kevin onsite Ameresia Lawlis Uploaded Files Date File Name 01/05/2022 10411756-4149 Issued Permit.pdf 09/21/2021 9729549-4149 Certification.pdf 09/21/2021 9729550-4149 CutSheets.pdf 09/21/2021 9729551-4149 Email.msg 09/21/2021 9729552-4149 System Drawings.pdf 09/21/2021 9729553-4149 Application.pdf