HomeMy WebLinkAbout20227 77th Avenue NE_BLD1195_2026 FIRE PROTECTION, INC. PO BOX 12642 MILL CREEK,WA 98082 14251 290-9600 OR 1-800-681-1125 FAX (4251353-4546 October 20,2016 City of ARLINGTON - PLAN REVIEW RE; FIRE ALARM SYSTEM Please find enclosed plans for a FIRE ALARM SYSTEM.The FACP will be located in building 17 ( lower floor of this building is the site community building) , all residential buildings will have their own individual fire alarm annunciator and remote power supply. All residential buildings sprinkler systems will be tied to and monitored by the FACP located in building 17 . The site electricians (Express Electric) are providing building linking conduit/wiring as shown on the included site building linking plan. The SLC and SBUS will be run in a Class A loop as shown. When a Waterflow, Smoke Detector or Pull-station is activated in a residential building, it will annunciate at the annunciator in that specific building and also at the FACP located in building 17 . Residential building occupant notification devices will only activate when an initiating device in that building is triggered, no other building' s occupant notification devices will active. The system has been designed per NFPA 72 , 2013 edition requirements as well as WAC, IBC, IFC 2012 , NEC current and your additional requirements . The building is fully-sprinkled. The system shall monitor by zone activation as well as separate trouble signals . Monitoring shall be provided via UL listed Central Station, The Alarm Center LACEY, WA. Audibility shall be in compliance with NFPA standards . Interior DB shall be 75 DB minimum throughout, (LOW FREQUECNY NOTIFICATION DEVICES TO BE INSTALLED IN RESIDENTAL SLEEPING AREAS . A full service and monitoring agreement is in force for the proper service and maintenance per NFPA requirements . A full pre-test and NFPA form shall be conducted and completed prior to calling the AHJ for acceptance testing. INSTALLATION COMPANY Fire Protection, Inc. 1730 Gibson Rd. Everett, WA 98204 WSCL# FIREPI*021ML UL CERT #608242-002 JOB SITE Park 77 Apartments *Building ll* 20201 77th Ave Ne Arlington , WA APPROVED UL MONITORING COMPANY Alarm Center, Inc. /FPI 4300 3rd Ave. SE Lacey, WA 800-429-0991 UL CERT #902799-02 CONTRACTUAL RESPONSIBLE PARTIES Installation; Monitoring; Service; Testing; Fire Protection, Inc. AMBIENT TEMPERATURES No area with alarm service equipment shall fall below 40 degrees, common areas shall be at 68 degrees per builder AMBIENT NOISE RANGE All areas serviced by the Fire Alarm Control and notification system will be as listed for per UBC listings, per builder. SEQUENCE OF OPERATIONS All Alarm and Trouble conditions shall enunciate at FACP as well as remote notify UL listed Central Station. Zones of alarm shall cause for all notification circuits to activate, send alarm zone to CS, re-dispatch to Fire and dispatch FPI runner service. Trouble and supervisory signals shall transmit to CS which will dispatch FPI runner service to site, (no notification circuits shall activate. ) On site emergency contact personnel shall be notified. Wet Waterflow ALARMS shall be retarded by a period of not more than 45 seconds . Low air shall activate at 25lbs, causing for a supervisory signal . A short on FACP smoke, Waterflow Switches, (wet and dry) and pull station shall cause a alarm. Shorts on PIV, tamper and Hi-low air zones shall cause a Supervisory condition. Opens on any zones shall cause for a trouble signal . Should you have any further questions, please feel free to contact me directly. David Mow VP of Operations/Designer NICET-3 #120904 CITY OF REDMOND D.O.R. #16-B-141 WA JOURNEYMAN LICENSE #MOW**DDE957M6 FACP FOR ALL BUILDINGS LOCATED IN BUILDING 17 @POTTER P 3 00 P/uS Fire Alarm Control Panel Features • 127 expandable to 381 Analog Addressable Points.Any combination of detectors/modules • 5 Amp Power Supply.Expandable to 315 amps • 2 NAC circuits rated at 3 amps maximum,expandable to 188. • 2 Input/Output(1/0)Circuits for system flexibility rated at 1 Amp . �• each _ • Built-in UL Listed IP Communicator • Built-in email event notification and report capability. • Optional Dual Line Digital Alarm Communicator • System wide synchronization of Potter/AMSECO,Gentex, Cooper/Wheelock,and System Sensor signals. • No twisted or shielded wiring required. • Cabinet will accommodate up to 18AH batteries.Panel will charge up to 55AH. • Capable of Class A or Class B wiring configurations • Built-in NFPA 72 compliant smoke detector sensitivity test • Dead-front cabinet design '' �. • 1000 Event History Buffer V` i NYC Fire Dept. Certificate of Approval Potter/Nohmi Protocol Features S735 7165-0328:0195 6156 • Less than 4 second polling time Product includes a 5 year warranty • LED's visible from 360' • Adjustable Smoke Detector Sensitivity • Adjustable Heat Detector Temperature annunciators,intelligent power supplies and other optional modules. • High Temperature Heat Detector as fixed temp The P-Link will support 31 accessories in any combination.The RA- Drift6075 is a 2 x 16 LCD annunciator.The RA-6500 offers a larger 4 x • Compensation 40 line LCD display that allows points and descriptions to be shown • Maintenance Alerts simultaneously.Intelligent remote power supplies repeat the P-Link data • Day/Night Mode and can be mounted 6,500 feet from reach other.P-Link devices such as the RLY-5 relay module,SPG-1000 serial parallel gateway and DRV-50 Description LED driver can be mounted anywhere in the chain of communication with a maximum of 31 of each P-Link devices.A total of two(2) The P300 is a mid-sized analog/addressable fire alarm control panel SLCE-127 Signaling Line Circuit Expanders(loop cards)may be with a total of 381 points.The points may be any combination of smoke installed in the P300 enclosure,in a remote enclosure such as the AE-8 sensors,heat detectors or modules.This panel has a 5 amp power supply or with a PSN-1000E remote intelligent power supply. that is distributed across two Notification Appliance Circuits(NACs) and two Input/Output(1/0)Circuits. The entire system,including the SLC,NACs and P-Link may be converted with a CA-6075 Class A module.The entire system is The NAC circuits are rated at a maximum of 3 Amps each and the 1/0 programmed using a Windows based computer software and requires circuits are rated for a maximum of 1 Amp each.All of the outputs may the use of a software programming software key. be configured for notification or auxiliary power.In addition,each NAC and Output can be programmed for strobe synchronization and utilizes The P300 can communicate to a monitoring station using the on board Quadrasync for strobe synchronization across circuits of various brands. Ethernet connection to an IP communicator or using optional UL listed The 1/0 may also be programmed for a dry contact input such as a water UD-1000 traditional two line alarm communicator.The UD-1000 flow switch or pull station. connects to the main board and has two phone line jacks provided. The IP communicator uses a RJ-45 connection and when connected The cabinet will hold two 12 volt,8 amp/hour batteries or two 12 volt, to the intemet may be programmed to E-mail system status,history 18 amp/hour batteries.The system when fully loaded will charge 55 reports,reminders and the configuration file.The panel may be updated amp/hour batteries.Anything larger than 18 amp/hour will require an remotely using the LTD-1000.If the Ethernet connection is needed external battery cabinet the SSU-00050. remotely,the FCB-1000 fire communication bridge may be installed to The panel has the Potter P-Link connection for expansion with remote allow the Ethernet connection to be installed in a rack. Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • wwpottersignal.com P'�O�IUsJ w. #8830035-REV A PAGE 1 OF 4 08/12 (E) POTT ER P 3 00 Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 381 addressable devices or modules in any combination.The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PSA Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PSHA Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135'Fahrenheit heat detector FHA Analog Fixed Temperature Heat Detector that is selectable from 135'F to 185°F RHA Analog Rate or Rise Heat Detector that has a fixed temperature selection from 135°F and 174°F and also will alarm if the temperature increase 12-15°F in one minute DDA Addressable Duct Smoke Detector AB-6 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors AB-4 4"round base that may be mounted to an electrical box and wired for connection to the above sensors AIB Isolater base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop ARB Addressable Relay Base that contains two relays controlled by the SLC.One relay is rated at 8 amps at 240 VAC/30VDC and the other is rated at 2 amps 240 VAC/30 VDC ASB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. Modules Device Description MCM Miniature Contact Module provides a small foot print contact module for mounting inside an enclosure. APS-SA Single Action Addressable Pull Station APS-DA Dual Action Addressable Pull Station SCM-4 Single Contact Module is a standard contact module with an LED that mounts into a 4"square electrical box. DCM-4 Dual Contact Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. TRM-4 Twin Relay Module provides two form C relays that simultaneously active when the module is triggered by the control panel. Each relay is rated for 2 amps at 24VDC or 0.5 amps at 125VAC. MOM-4 Monitored Output Module is a power switching module that monitors the circuit that is controlled by the control panel. CIZM-4 Conventional Input Zone Module is used to connect conventional smoke detectors to the system that receive their power from the module.This module is like a conventional zone on the SLC. SCI Short Circuit Isolater interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • www.pottersignal.com P"�O�A'SP v #8830035-REV A PAGE 2 OF 4 08/12 (E) POTT ER P 3 00 Fire Alarm Control Panel SLC Features RA-6075—2 x 16 LCD annunciator with a key pad in a locked metal enclosure. The Potter/Nohmi protocol is a digital protocol with a proven design for reliability and noise immunity.The system does not require special RA-6500—4 x 40 LCD annunciator with a key pad in a locked metal cable or conductors for connection of the Signaling Line Circuit as enclosure long as the cable is compliant with NFPA 70 and NFPA 72.The system LED-16—16 LED annunciator with common indicators in a locked allows for Class A or Class B installations as well as"T-Taps." metal enclosure The total polling time for the protocol is about four(4)seconds which PSN-1000(E)—10 amp,remote intelligent power supply with 6 NACs, allows two polling cycles in the ANSUUL 864 requirement of alarms 2 I/Os and a P-Link repeater reporting in less than ten seconds.Each loop is capable of 127 points with the exception of the P100 and P200. CA-6075—Class A convertor that converts the SLC,NACs and P-Link connection Sensor Features UD-1000—UL listed,Dual line telephone alarm communicator The sensors through the fire alarm control panel provide a real DRV-50—LED driver expander,used to connect up to 50 LEDs in a time status as to the condition of the system.The smoke detector graphic display sensitivity,heat detector temperature level and drift compensation FCB-1000—Fire communication bridge,provides remote mounting of as all programmable options.The system also allows for a day/night the Ethernet connection mode where the panel automatically adjusts the sensitivity depending on the time of day.To assist in the reduction of false alarms,the smoke FIB-1000—Fiber interface module,used to extend P-Link to multi- detectors also have a maintenance warning that sends a trouble signal mode fiber(2 required) when a detector is dirty to the point that it can no longer maintain the RLy--5—Relay module,provides 5 form C relay contacts rated at 3.0 programmed sensitivity. amps 24VDC/125AC User Interface SPG-1000—Serial parallel gateway,allows for the connection to a serial or parallel printer The fire alarm control panel has a 4 x 40 LCD display to provide information to the system status.The keypad has navigation keys The FIB-1000,FCB-1000 and the SPG-1000 maybe installed in the t stacker bracket or ordered with the optional rack mount enclosure.o allow manipulation of the Menu on board the panel.The panel is shipped standard with the following LEDs: AE-8—Eight card expansion cabinet • AC Power—Green AE-14—Fourteen card expansion cabinet • Alarm—Red Ethernet/I.P. Connection • Earth Fault—Amber The P300 is shipped standard with an Ethernet connection.This • Supervisory-Amber connection is the programming port and may be connected to a building • Silenced-Amber Wide Area Network(WAN)or Local Area Network(LAN).Once connected to the Internet,the panel may be selectively programmed to • Trouble-Amber e-mail alarm conditions,trouble conditions,supervisory conditions,test, The common buttons include a Silence,Reset,Acknowledge and Drill. Event History and detector status.An e-mail may be sent to the panel All of the buttons are accessible once the locked door is opened. and the panel will e-mail the event history,detector status,configuration file or server status to an authorized E-mail account.In addition, P-Link reminders may be set to send an e-mail for service,testing or other The P300 has a proprietary communication protocol that communicates conditions. through a RS-485 connection to field devices.Up to thirty-one In addition,the Ethernet connection is UL listed as an IP communicator. (31)devices may be connected to a single P-Link connection.The The IP communicator is listed to report to the UL listed Sur-Gard III P-Link includes the communication terminals and regulated 24 VDC IP receiver.The IP communicator replaces the traditional less reliable connection for the field devices.The field devices may be any of the alarm communicator transmitter that utilized telephone lines.The IP following: communicator is an active method of connection and communication to SLCE-127-Analog/Addressable loop expansion module(maximum of 2 the monitoring station. per P300) Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • wwpottersignal.com P'��PlusZ* w. #8830035-REV A PAGE 3 OF 4 08/12 (E) POTT ER P 3 00 Fire Alarm Control Panel Specifications 18.91" 17.60" Electrical Specs:AC Mains O O TOP o 3.0 Amps @ 120 VAC 50/60 HZ 2.0 Amps @ 240 VAC 50/60 HZ 4.41" 3.75" DEPTH Battery p 0 130 mA Standby 220mA Alarm b • 5 Amps power for NACs,I/O and P-Link • 3 Amps per NAC,regulated a • 1 Amp per I/O circuit,regulated �e c7 O • Battery Charger range 8-55 Ah • Battery Charger voltage 27.3 VDC • P-Link maximum current of 1 Amp • Panel holds(2)8AH or(2) 18AH batteries LEFT SIDE RIGHT SIDE Cabinet • 16 gauge cold rolled steel with removable BOTTOM ` locked door • Dimensions—18 15/16"W x 27 5/16"H x 4 7/16"D • Dead front to cover all electronics • Lexan viewing window Temperature and Humidity This fire alarm control is listed and approved for operation in an indoor application with temperature range fluctuations of 32'to 120'(0°C to 49°C) with a maximum humidity of 93%non-condensing.The ideal temperature is 77°F +/- 10°F(25°C+/-5°C). Standards The P300 series fire alarm control panel complies with the following standards and codes. • NFPA 13,70 and 72 • ANSI/UL 864 0 Local(L),Remote Station(RS),Central Station(CS),Propriety(PPU),Auxiliary(AUX) 0 Type of Service:Automatic(A),Manual(M),Water flow(WF)Sprinkler Supervisory(SS) 0 Type of Signaling:Digital Alarm Communicator(DAC),March Time(March),Non Coded(NC),Reverse Polarity(Rev Pol),Other Technologies(OT) • IBC 2000,2003,2006,2009,2012 Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • wwpottersignal.com P'h�T PUF'J w. #8830035-REV A PAGE 4 OF 4 08/12 POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Features Standby Current 20 mA Alarm Current 25 mA Operating Temperature 0°C-49°C(32°F-120°F) 10%-93% @ 30°C(86°F)non-condensing 0 © humidity Maximum Wire Length 6500 FT ® © Maximum Annunciators 31 - Dimensions(WxHxD) 8"x 6-1/4"x 1-5/8"(Cabinet) Wire Gauge 14 AWG-22 AWG Display 2 lines x 16 characters Product includes 5 year warranty U� LISTED S2930 7165-0328:0195 Description Installation The RA-6075 is a LCD remote annunciator for the PFC-6075 and The RA-6075 is connected to the PFC-6075 using a four wire RS-485 PFC-6030 addressable fire control panel.The RA-6075 communicates connection.The connection is power limited and supervised.Up to using a RS-485 connection to the main panel providing common thirty-one(31)RA-6075 LCD annunciators can be connected using indication of Alarms,Supervisory,Trouble and other system status and Class B or Class A wiring.Class A wiring requires an optional Class A control functions. Expander. The RA-6075 features a 32 character, 16x2 LCD display with LED's for Power,Alarm,Supervisory,Trouble,and Silenced conditions. , It can be mounted on a single gang electrical box or a four square electrical box.The annunciator is enclosed in a sheet metal enclosure Instal!inac!cord!anc!e with compatib7fir,alarm panel. and has a Potter lock securing the keypad. Figure 1:RA-6075 Class B Wiring Example Figure 2:RA-6075 Class A Wiring Example To the next annunciator 4CA-60775 + m + a P-LINK + a + A B + + + + Panel + + + + + + Panel + + Connection Remote -LIN + Annunciator Connection + Remote -LIN< Annunciator m Q m Oa O a + Q O Remote O Remote Annunciator Annunciator Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5406077-REV B-1 PAGE 1 OF 2 9/11 (E) POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Address Settings The RA-6075 address is set by dip switch S 1 located on the back of the RA-6075.The address must be set in the range of 1 to 31 to be recognized by the control panel. Figure 3:RA-6075 Class A(back panel view) O ❑ 0 0 OWWWW .-9. O 0 © A on ® 9 ® + Al O o Dip Switch Settings Refer to the table below for dip switch settings per Annunciator Address. Annunciator Dip Switch Settings Annunciator Dip Switch Settings Address SW-1 SW-2 SW-3 SW-4 SW-5 Address SW-1 SW-2 SW-3 SW-4 SW-5 1 On Off Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Off On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Off On On On 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On PRINTED IN USA MFG.#5406077-REV 13-1 PAGE 2 OF 2 9/11 CPOTTER PSN-1000(E) The Symbol of Protection POWER EXPANDER Features 10 Amp Power Supply • 3 Amps,regulated per NAC • 6 NACs Class B or 3 NACs Class A • 2 dry contact inputs • Fully programmable and monitored through control panel _ I Isolated P-Link repeater connection,Class A or B • Up to 31 power supplies per control panel with system wide sync • Quadrasync feature synchronizes strobes from Potter/AMSECO, Gentex,Cooper-Wheelock and System Sensor. ®RPOTTFR PSN-1000 Compatible with all Potter PFC-6000 series fire alarm control panels. Ines➢pool of Frowpon P.—Supply --. Electrical Specs • 120/240 VAC Input at 50/60 HZ • 5.1 Amps/3.0 Amps max draw • Standby Current 60 mA • Alarm Current 200 mA U` S2930 7165-0328: 0195 Product includes a 5 year warranty Description The PSN-1000 series is a UL listed intelligent 10 amp notification power supply and P-Link(RS-485)repeater.The power supply connects to the P-Link bus from the control panel and is operated and supervised from the panel.The power supply may be installed 6,500 feet from the control panel.The PSN-1000 then repeats the P-Link communication for another 6,500 feet. The power supply has six(6)Class B or three(3)Class A power outputs.Each output is regulated and power limited with a 3 Amp maximum rating.In addition,the PSN-1000 has two(2)programmable dry contact inputs.The dry contact inputs are Class B,supervised inputs. The power supply operates on either 120 or 220 VAC power and has a regulated 24 VDC output.In addition,the panel can charge up to 55 AH batteries and will house 18 AH batteries.The cabinet is constructed out of 18 gauge cold rolled steel with a durable red powder coat finish.A standard Potter key lock is provided for securing the door.Electrical conduit knockouts are provided on the sides and top providing installers with multiple options for installing conduits and providing proper power separations. The PSN-1000 is a self contained intelligent power supply/P-Link repeater complete with cabinet.The PSN-1000E is the intelligent power supply/P-Link repeater with additional cabinet room for the exclusive Stacker Bracket for SLCE-127 loop expanders.Both cabinets include space for 18 AH batteries. The power supplies are programmed and controlled through the main control panel P-Link bus.The panel displays any troubles or off normal conditions of the power supply and the events are stored in the panel history buffer. Each output can be independently configured to provide one of four synchronization patterns,constant power,ANSI temporal Code 3 or Door Holder power.The panel can be configured to synchronize Potter/AMSECO®,Gentex®,Cooper Wheelock®and System Sensor®. Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830032-REV B PAGE 1 OF 2 09/14 (E) POTTER PSN-1000(E) The Symbol of Protection POWER EXPANDER 18.91" 17.60" 4 0 0 TOP w 0 4.41" 3.75" DEPTH O O 0 0 0 N O O O 0 LEFT SIDE RIGHT SIDE BOTTOM Dimensional drawings showing the cabinet in all three planes. Knock out locations. PRINTED IN USA MFG.#8830032-REV B PAGE 2 OF 2 09/14 4, �� SYSTEM � SENSOR t 41, Photoelectric Smoke Detectors System Sensor i3-series smoke detectors represent significant advancement in conventional detection. 3 The i3 family is founded on three principles:installation TM ease,intelligence,and instant inspection. Features Installation ease.The i3 line redefines installation ease with its •Plug-in detector line,mounting base included plug-in design.This allows an installer to pre-wire bases(included with heads).The large wire entry port and in-line terminals provide Large wire entry port ample room for neatly routing the wiring inside the base.The base •In-line terminals with SEMS screws accommodates a variety of back box mounting methods as well as •Mounts to octagonal and single-gang back boxes,4-square back direct mounting with drywall anchors.To complete the installation,i3 boxes,or direct to ceiling heads plug into the base with a simple Stop-Drop'N Lock'action. •Stop-Drop'N Lock attachment to base Intelligence.i3 detectors offer a number of intelligent features •Removable detector cover and chamber to simplify testing and maintenance.Drift compensation and •Built-in remote maintenance signaling smoothing algorithms are standard with the i3 line to minimize nuisance alarms.2-wire i3 detectors can generate a remote LED- indicated maintenance and smoothing algorithms indicated maintenance signal when connected to the 2W-MOD2 •Simplified sensitivity measurement loop test/maintenance module or a panel equipped with the i3 •Wide-angle,dual-color LED indication protocol.The SENS-RDR,a wireless device,displays the sensitivityof i3 Loop testing via EZ Walk feature detectors in terms of percent-per-foot obscuration. • •Built-in test switch Instant inspection.The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition:normal standby,out-of-sensitivity,alarm,or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol,the EZ Walk loop test feature is available on 2-wire P detectors.This feature verifies the initiating loop wiring by providing LED status indication at each detector. T istin s M MEA MSFMTPROVED approved approved cC I,us I W6 7272-1653:152 290-01-_ 3C93? (-L3)Smoke Detector Specifications Smoke detector shall be a System Sensor i3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The detector shall be a photoelectric type(Model 2W-B,4W-B)or a combination photoelectric/thermal(Model 2WT-B,4WT-B)with thermal sensor rated at 1357 (57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal,single-gang,and 4-inch square back boxes with a plaster ring,or direct mount to the ceiling using drywall anchors.Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual- color LED indication that blinks to indicate power up,normal standby,out of sensitivity,alarm,and freeze trouble(Model 2WT-B,4WT-B)conditions.When used in conjunction with the 2W-MOD2 module,2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24V non-polarized Minimum: 8.5 V Maximum:35 V Maximum Ripple Voltage 30%peak to peak of applied voltage Standby Current 2-wire:50 NA maximum average;4-wire:50 NA maximum average Maximum Alarm Current 2-wire:130 mA limited by control panel;4-wire:20 mA @12 V,23 mA @ 24 V Peak Standby Current 2-wire:100 uA;4-wire:n/a Alarm Contact Ratings 2-wire:n/a;4-wire:0.5 A @ 30 V AC/DC Physical Specifications Dimensions(including base) 5.3 inches(127 mm)diameter;2.0 inches(51 mm)height Weight 6.3 oz(178 g) Operating Temperature Range 2W-B and 4W-B:32°F to 1207(0°C to 49°C);2WT-B and 4WT-B:327 to 1007(0°C to 37.8°C) Operating Humidity Range 0 to 95%RH non-condensing Thermal Sensor 1357(57.2°C)fixed Freeze Trouble 2WT-B and 4WT-B only:417(5°C) Sensitivity 2.50/o/ft nominal Input Terminals 14 to 22 AWG Mounting 3'/2-inch octagonal back box 4-inch octagonal back box Single-gang back box flinch square back box with a plaster ring Direct mount to ceiling LED Modes Power-Up Sequence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal(standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max.limited by control panel 2WT-B Yes 2-wire 130 mA max.limited by control panel 4W-B No 4-wire 20 mA @ 12 V,23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V,23 mA @ 24 V Accessories 2W-MOD2 2-wire loop test/maintenance module RT Removal/replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket,6.6 inch(16.76 cm)diameter f_ SY TE� m2cha system Sensor. �/ 3825 Ohio Avenue•St.Charles, L 60174 Product specifications subjec[to009 System Sensotice.Vsit rystemsensoccom for SENSOR Phone:800-SENSOR2•Fax:630-377-6495 urrentproductinformat5-03180i7-6/09 latest version okhis data sheet. A06-0318-007.6/09•#2169 PULL STATION SERIES (E) POTTER DIE-CAST METAL The Symbol of Protection MANUAL PULL STATIONS • UL and cUL Listed,FM Approved,CSFM Listed,MEA ' Approved,ADA Compliant • Single or Dual Action • Terminal connectors PULL UOWN Big . 10 Amp Snap Action Switch Gold plated SPST contacts Optional auxiliary contacts Mounts on standard single gangbox • Surface backboxes available • High-gloss red enamel finish • Glass breakrod DUs FMo �5 Made in the U.S.A. LISTED Description Engineering Specifications The Potter Pull Station Series offers a complete line of die-cast pull The contractor shall furnish and install the Potter series of pull stations for a variety of applications focusing mainly on fire alarm stations as indicated.The pull station shall be die cast construction systems.The pull stations are available in single or dual action with a"T"type pull handle that is ADA compliant.Single action pull models.All of the pull stations have a 10-amp snap action switch and stations shall be a P32-lT.Dual action pull stations shall be the Potter a dedicated terminal block for the ease of wire connections.All of P32-1T-LP.Any manual pull station installed in an outdoor or wet the metal is completely coated to inhibit corrosion and provide for a location shall be a RMS-IT--WP weather proof unit.The contact shall uniform and quality finish. be a single pole,single throw switch rated at 1 amp 30V DC/125V The standard models have a hex key reset,however a key reset is also AC.The device shall have a terminal block for ease of wiring.Once available.The models are available with shallow and deep surface activated,the pull station shall be reset by opening the front cover. mount back boxes and as a weatherproof version. Opening of the cover in a normal state shall initiate an alarm. Operation Specifications The Potter single action series of pull stations operate by pulling Switch Rating: 1 Amp @ 30 VDC the white operating handle straight down and the handle will lock 10 Amps @ 125 VAC into place.The dual action stations require the lifting of the front Pull Station Dimensions: 4-3/4"H x 3-1/4"W x 7/8"D cover and then pulling the white operating handle straight down.The Color:Red with raised white letters,white pull bar with raised red letters stations are reset by opening the front and placing the handle in the For special application manual stations see bulletin#8910014. normal position. For explosion proof manual stations see bulletin#8880014. Ordering Information Type Model Number Stock Number Contact Type P32-1T 1000447 SPST RMS-2T 1000477 DPST Single Action RMS-6T 1000478 DPDT RMS-1 T-KL 1000451 SPST RMS-IT-KO 1000450 SPST,key operated,no pull Weather Proof RMS-1 T-WP 1000401 Dual Action P32-1 T-LP 1000476 SPST Weather Proof Dual Action RMS-IT-WP-LP 1000403 Accessories Notes Dual Action RMS-LP 1000480 Converts single action to dual action Back Box P32-BB 1000444 Surface mount back box Back Box P32-DBB 1000445 Deep surface mount back box Glass Rods RMS-GB 1000470 Replacement glass rods(10 per pkg) Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-1211•Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8900097-REV L PAGE 1 OF 1 9/10 P POTT ERS A ka-"Wl' DCM-4 ® The Symbol of Protection Dual Contact Module Features • Single module with dual contact monitoring inputs • Two(2)Class B or one(1)Class A monitoring inputs • SLC Class A(Style 6,7)&Class B(Style4) • Mounts in a standard 4"or double gang box s- S. • Wiring terminals accessible when mounted in box ©E�►•■-�+•�.+o • All wiring terminals accept 22 to 14 AWG li wsiar • Product includes a 5 year warranty ee _.. NOTE: This addressable module does not support 2-wire smoke f zz1,1" zi ;, ci detectors. Stock Number: 1430822 LISTED �zw� S2930 7165-0328:0196 Application Technical Specifications The DCM-4 is compatible with Potter's PFC-6000 series and PFC- Operating Voltage 22.0-24.OV 8500 addressable fire alarm control panels.The DCM-4 is an interface Max SLC Standby Current 325 µA module used to monitor dry contact devices such as sprinkler water Aux Power Required 1mA flow,valve tamper switches,or conventional pull stations.The module is capable of monitoring two separate Class B or one Class A circuits. Max Wiring Resistance of IDC I 100 S2 Max Wiring Cpacitance of IDC 1 µF EOL Resistor 5.lK S2 Description Operating Tempurature Range 32 to 120°F(0 to 49°C) The DCM-4 uses two (2) consecutive SLC loop addresses when Operating Humidity Range 0 to 93%(non-condensing) monitoring two(2)Class B circuits or one(1)address when monitoring 127 units(Class A)or 63 units a single class A(Style D)circuit.The module mounts on either a 4" Max no.of Module Per Loop (Class B) square or double gang box.The module is capable of monitoring two (2)separate class B circuits making it ideal for monitoring sprinkler Dimensions 4.17"(106mm)L X 4.17" waterflow and valve tamper switches when they are located in the same (106mm)W X 1.14"(29mm)D proximity.The DCM-4 includes one red LED to indicate the modules Standard 4"Square or status.In normal condition,the LED flashes when the device is being Mounting Options Double Gang Box polled by the control panel.When a contact is activated,the LED will Shipping Weight 0.6 lbs light continuously and in case of an open circuit,the LED will turn off. Potter Electric Signal Company,LLC • St.Louis,MO • Tech Support: 866-956-0988/Customer Service: 866-572-3005 • www.pottersignal.com 8830008-REV B • 7/14 PAGE 1 OF 2 P POTT ERS OHM/® DCM-4 ® The Symbol of Protection Dual Contact Module Setting the Address Each addressable module, smoke sensor,heat detector and combination sensor/detector must be assigned an address prior to installing the device.The address is set using either the hand held device programmer or the addressing feature on the PFC 6000/PFC 8500 Series control panels.When the DCM- 4 is used to monitor two individual Class B circuits a single device address is assigned,with the second address number assigned automatically by the module assuming the next consecutive address.For example,if the first address number is assigned as"2",the second address number will automatically be assigned as SLC device address"3". Before connecting a device to the SLC loop,take the following precautions to prevent potential damage to the panel or device verify the following: 1.Power to the device is removed 2.Field wiring is correctly installed. 3.Field wiring has no open or short circuits. Installation Using Compatible Electrical Box O e ° ° o e Wiring Diagrams DCM-4 With One Class ACircuit NOl FROM FACP OR C 1 PREVIOUS MODULE S+ ZI S- NO2 TO THE NEXT MODULE F 1 C2 SELECT STYLE D 0000 LED Q Z2 NOTE:END-OF-LINE RESISTOR IS NOT REQUIRED DCM-4 With Two Class B Circuits NOl FROM FACP OR C 1 PREVIOUS MODULE S+ Zl "OHM1/2W S- NO2 TO THE NEXT MODULE ppH1pC2 �000 LED O Z2 SELECT STYLE B 5.1K OHM 1/2W Potter Electric Signal Company,LLC St. Louis,MO • Tech Support: 866-956-0988/Customer Service: 866-572-3005 www.pottersignal.com :so 9001:2008 1 DESIGNING,MANUFACTURING, 8 DISTRIBUTING QUALITY SYSTEMS 8830008-REV B • 7/14 PAGE 2 OF 2 GENTEX CORPORATION Low Frequency Audible Signal GHLF Applications 24 V D C The GHLF is a high quality, low profile, low frequency audible appliance that offers a dependable audible alarm with a low current draw. The GHLF is ideal for any S E R I E S occupancy that requires notification appliances. The GHLF horn offers a 520 Hz square wave,temporal 3 tone. A jumper selection is available for normal or loud decibel tone. A temporal 4 pattern is available when used with the Gentex GTSM Synchronization Control Module. The GHLF is shipped with a standard 4" metal mounting plate which incorporates the popular Super-Slide°feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The GHLF also features the patented Checkmate°- Instant Voltage Verification feature which allows the installer to check the voltage drop and match it to the blueprint. The GHLF horn is listed to ANSI/UL 464 and CAN/ULC S525, is listed for use with fire Product Listings protective systems and is warranted for three years from date of purchase. SIGNALING Standard Features � • Nominal voltage 24 VDC • Input terminals accept 12 to 18 AWG C&uS :U0= O Unit Dimensions:6-1/8"(15.55 cm)high x • Produces a 520Hz square wave,temporal 3 LISTED 5-1/2"(13.97 cm)wide x 1-5/8"(4.13 cm) tone deep • Jumper selection for normal or loud dBA • ANSI/UL 464 Listed • Super-Slide®Bracket-Ease of Supervision • Temporal 4 pattern available when used • CAN/ULC S525 Listed Testing with Gentex GTSM Synchronization Module • CSFM: Pending • Checkmate°-Instant Voltage Verification • Temporal 4 520Hz measured per Product Compliance • Synchronize horn with Gentex GTSM ANSI/UL 2075 • NFPA 72 Synchronization Control Module • Tamperproof re-entrant style grill and • IBC/IFC/IRC • Prewire entire system,install mounting locking screw(optional use) • Quality Management System bracket,then install signals • Faceplate available in red or off-white is certified to:ISO 9001:2008 Model Number Part Number Nominal Voltage Model Designations: �i •j ' = R=Red Faceplate MEMBER •� GHLFW 904-0530-002 24 VDC W=White Faceplate ASSEMBLED IN GHLFR 904-0531-002 24 VDC All units are plain(no lettering) THE USA Horn Decibel Levels: 24VDC Nominal Horn Horn Current Ratings Reverberant Room Current Ratings(mA) Over Input Voltage Range of 16-33V(mA) Minimum SPL Minimum SPL 24VDC 24VDC 24VFWR 24VFWR Regulated Regulated Regulated Regulated at 10Ft.Per at 10Ft.Per Operating Operating Operating Operating 24VDC Max. 24VDC Max. 24VFWR Max. 24VFWR Max. Horn Mode Operating Operating Operating Operating ANSI/UL 464 ANSI/UL 464 Current Current Current Current Current Current Current Current (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) Temporal 3 520 Hz I 77.8 dBA 1 79.8 dBA 72.1 mA 120.1 mA 104.6 mA 158.4 mA 99.4 mA 155.8 mA 152.1 mA 213.5 mA Temporal 4 520 Hz*1 81.5 dBA 1 83.4 dBA 75.9 mA 116.0 mA 108.1 mA 182.0 mA 100.1 mA 157.2 mA 163.1 mA 235.2 mA O Temporal 4 520 Hz measured per ANSI/UL 2075 NOTES: • Operating temperature:32 to 120 F(0 to 49 C).The GHLF is not listed for outdoor use. • For nominal and peak current across ANSUUL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. RMS current ratings are per ANSUUL average RMS method. ANSUUL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units). For unfiltered FWR ratings,see installation manual. GHLF 24 VDC S E R I E NOTES: UL Listed • THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR Control Signal Signal PULSING SIGNALING CIRCUITS Panel S+ s- s- H+ H- S+ s+ s- H+ H- • THE FOUR PULSE TEMPORAL PATTERN(TEMPORAL 4)CAN ONLY BE Supervised 0 0 0 0 OBTAINED ON THIS PRODUCT WHEN USED IN CONJUNCTION WITH Signal Circuit THE GENTEX GTSM SYNCHRONIZATION MODULE 1 + ENO LINE • SEE GTSM CONTROL MODULE MANUAL(550-0632,MANUAL ISSUE RESISTOR DATE(02-01-15)FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. S GTSM MANUAL CAN BE OBTAINED AT WWW.GENTEX.COM/FIRE OR CALL GENTEX CORPORATION AT 1-800-436-8391. DOIMIW x o Lt LOCKING 0 0 o SCREW 0 " (optional) Cho H+ logo RED WIRES �- H! Q BLACK WIRES 6- � O o H- U a O o 00 NORMAL-LOUD o c �`f/ DECIBEL JUMPER. 0 0 FOR LOUD DECIBEL CEED INSTALL JUMPER. SLIDE ONTO BRACK Gentex Checkmate® Gentex Super-Slide® LOCKING Instant Voltage Verification: Mounting Bracket: SCREW It is often necessary to confirm the voltage drop Allows the installer to pre wire the system, (optional) along a line of devices.The access holes are test for system supervision,remove the provided in the back of the terminal block to signal head until occupancy,switch out allow the voltage to be measured directly without Gentex signals without changing removing the device.Typically this would be done mounting brackets and has locking edge at the end of the line to confirm design criteria. connector for snap-in-place installation. Most measurements will be taken using the S+ and S-locations although access is provided to other locations. NOTICE:CARE SHOULD BE TAKEN TO NOT qM SHORT THE TEST PROBES. Architect & Engineering Specifications The alarm horns shall be Gentex model GHLF.The appliance shall be listed with Underwriters Laboratories(ANSI/UL)for use with fire protective signaling systems (ANSI/UL 464) and with CAN/ULC S525 with intended use in fire alarm systems. The GHLF will produce a peak sound output of 88.3 dBA as measured in an anechoic chamber. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. 24 units per carton Important Notice: GHLF-01 GENTEX These materials have been prepared Gentex Corporation Gentex')for informational purposes only,are O necessarily summary,and are not purported to serve as legall advice and should not used s such. Gentex makes no representations and warranties,express or implied,that these materials are complete and CORPORATION accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to Fire Protection Products Group•www.gentex.com particular fact patterns.Each persons activities can differently affect the obligations that exist under applicable laws,regulations or rules.Therefore,these materials should be used only for informational 10985 Chicago Drive •Zeeland, Michigan 49464 purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. CPOTTER MHT 1224 SERIES The Symbol of Protection LOW CURRENT MINI-HORN Features • Single unit is capable of 12 or 24 VDC determined by the input I voltage - Y I I IEI I Unit Dimensions:4.48"(11.38cm)high x 2.84"(7.21 cm)wide x F I 0.5"(1.27 cm)deep Jumper selectable temporal 3 or continuous tone I I I i Horn frequency is 3100Hz I I I I Terminal blocks(12 AWG to 18 AWG) • Low current consumption • Variety of mounting options for new construction and retrofit E applications • Synchronize using the AVSM Series control module • ANSUUL 464 listed for fire protective service • Textured finish high impact plastic faceplate,available in red or off-white Ordering Information Operating Temperature(indoor use only) Stock Number Model Number Model Designations 320 to 120OF(00 to 49°C) 4890001 MHT-1224R R=Red facepalte 4890002 MHT-1224W W=Off-White faceplate 4890003 MHT-1224PR P=Plain 4890004 MHT-1224PW SIGNALING U� LISTED Product includes a 5 year warranty Description The MHT-1224 Series mini-horn is a high quality remote The MHT-1224 can be used on the same sync circuit(AVSM audible signaling appliance that offers dependable remote annunciation. Series Control Module)as other Potter signals.The MHT-1224 Series The MHT-1224 is ideal for applications where a dependable audible is ANSUUL 464 listed for use with fire protective systems. alarm signal is required in applications such as hotels, dormitories, and apartments.The MHT-1224 is listed for use with both filtered and unfiltered power and a jumper is provided to select either temporal 3 or continuous tone. Architect&Engineering Specifactions The alarm horns shall be Potter model MHT-1224.The appliance shall be listed with Underwriters Laboratories(ANSUUL)for use with fire protective signaling systems(ANSUUL 464)and produce a peak sound output of 90dBA or greater as measured in an anechoic chamber.The appliance shall be of solid-state construction and be polarized to operate from 8-33VDC with a 22mA current drain at 24VDC.The appliance shall be provided with 2 terminals,and mount to a variety of single-gang back boxes. Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830065-REV A PAGE 1 OF 2 06/13 (E) POTTER MHT 1224 SERIES ® The Symbol of Protection LOW CURRENT MINI-HORN Mini-Horn Wiring UL MHT-1221 MHT-I I 1151I I; WIRING DIAGRAM FOR DUAL CLASS B CIRCUITS WITH A SINGLE AVS"CONTROL MODULE CONTROI PANtI + — + SYNCODULAl10N F A C P MUrAIIE 1MT•t7H ANT•t!N h• lu M SIJI>f kV F.I 'NU IT I INr SIGnn•. tE51STDR CIRI'I ' EOI R SIGNAL CIRCUITS wr-Tti+ rrtfar 1_4Cf< B:-ALK Et,-ACK BLAf,R a., Wiring Diagram EOLR Mini-Horn Wiring Use a screwdriver to break the jumper for a continuous tone. O DO NOT BREAK m JUMPER IF TEMPORAL 3 TONE IS NEEDED. Horn Mode Minimum SPL at 10 Minimum SPL at 10 Reverberant dBA at 10 In Anechoic MHT-1224 Current Ratings feet per ANSI/UL feet per ANSFUL feet per ANSI/UL 464 Room dBA @ I 24 VDC 22 mA 464 at 24 VDC 464 at 12 VDC 10 ft. 24 VDC UL Max 18 mA Temporal 3 81 dBA 78 dBA 78-86 90 12 VDC UL Max 13 mA Continuous 86 dBA 1 83 dBA 78-86 90 NOTES:The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. 1 RMS current ratings are per ANSFUL average RMS method.ANSFUL max current is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units)(8-17 VDC for 12 VDC units).For strobes,the ANSFUL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units)(8 VDC for 12 VDC units).For audibles,the max current is usually at the maximum listed voltage.For unfiltered FAIR ratings,see installation manual. PRINTED IN USA MFG.#8830065-REV A PAGE 2 OF 2 06/13 Effective June 2014 Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Description ••�• �.�•�.••� � Eaton's Cooper Notification business has developed the Wheelock . •.•:•;...;•.•;••. Exceder LED Low Frequency Sounder Strobes and Sounders to ;••: meet the new National Fire Protection Association (NFPA) low •:•:;:•:•••• •' frequency sounder requirements for sleeping rooms -NFPA 72 for fire alarm and NFPA 720 for Carbon Monoxide (CO)alarm. In a single ••' device,the Exceder LED Low Frequency Sounders can provide alarm ••.•;:•:;�:�;:•:'•;: signals for dual applications-T3 (Fire)and T4(CO)tones. It is the � first product in the industry to be listed to the audibility requirements �'•:;;;;;:�'• X;�����:;�.� of UL 2034 and UL 2075 for CO applications. H ,., fib :;:;:::,•:•;••;; The Exceder LED Low Frequency Sounder Strobes and Sounders feature multiple 520 Hz modes of operation:T3 (fire),T4(CO), •: �••�••��••�.�.•.�. Continuous,T3/T4 Sync Control. The 520 tone is generated within the appliance itself. When '.•;:;:;:;;;:�;:•.;• the selector switch is set forT3 orT4,the sound pattern is also •.•.••...••.•; generated within the appliance. When the selection switch is set to continuous,the product is listed for coded operations. TheT3,T4 pattern or other pattern must be generated by the FACP according to ....... •.�•..•. •� the alarm condition sensed by the panel (fire or CO alarm). . . . . . When the device is set toT3/T4, the appliance can switch fromT3 to '�' '•"'�'•'•'�' T4 based upon the condition sensed by the FACP and passed to the %•% Wheelock DSM module. ••••.••••.••• 0 0 •. Like the entire Wheelock Exceder LED product line, the Low �.�.•�•.;�;.����; Frequency Sounder Strobes will utilize Light Emitting Diode (LED) N ••;.;•:;;;:•; as the light source—a breakthrough optical design, resulting in best- in-class efficiency that enables material and system cost savings, allowing for a greater number of appliances on the notification appliance circuit and fewer power supplies. All LLFHS strobe models include a 110 candela setting. Providing a sleek aesthetic appearance, the Exceder LLFHS and LLFHN models feature one of the industry's smallest footprints and a sleek, modern, low-profile design. Installers will benefit from its comprehensive feature list, multiple 520 Hz modes of operation, lowest current draw, no tools needed for setting changes, and convenient mounting options.These products are suitable for indoor wall-mount applications.The Sounder and Sounder Strobe models are for 24V operation. Exceder LED Sounder Strobes may be synchronized when used in conjunction with the DSM Sync Modules,Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol.Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. The Exceder LED Low Frequency Sounders and Sounder Strobes are UL Listed for indoor use under Standard 1971 and 464 and ULC under S525 and S526. The appliances are Restriction of Hazardous Substances (RoHS)compliant and contain no mercury or other F AIkT* N hazardous substances. Powering Business Worldwide Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Effective May 2014 Features Drawings • Meets dual low frequency sounder codes for sleeping rooms in a 4.56 1.29 single device • NFPA 72 for fire alarm • NFPA 720 for CO alarm "'eeeeeaeo • 4 Settings in 1 device 000000000000000 • T3 (fire) o°omoo°o°00000°0°0°°0 o°o mo 000000000000 oo°om • T4(CO) °000°o°o°000°o°o°o°o0 m°m°o°Oo°Oo°O°o°o°o°o°m°u • Continuous (Coded) moeo°o°o°o°o°o°0000°oo°° 6. 10 • T3/T4 °o om o0 00°0°00000 o°°a o o eoo °o0 000 o • Energy efficient °ooaooeoo°0o0000o00° eeeee • Patented LED technology provides industry's lowest current O000000es°o draw • Low-profile design • Smallest footprint with sleek, modern aesthetics • --- t 11 • 110 candela setting I.40-I • Easy-to-install • Finger slide switches—No tools needed for setting changes • Built-in level adjustment feature and snap-on grille cover Figure 1.Wall Low Frequency Sounder Strobe • IN/OUT screw terminals using#12 to#18 AWG wires • Mounting Options include Exceder LSPKBB _ backboxes and 4" square backboxes o°000°0000°o 0o0o0aes°°a°o°0 • Strobe synchronization components o o ¢ 00000 0 0 0 Y p o o°o°OpOo°o°o°0°a°o o • Meet synchronizing standards with Wheelock's DSM Sync mom 00 oaop0°o°o°o°°o m Modules or PS-6/8 Power Supplies ®000000°°000°°o$00000 pP m0m0o0o00000000o0o00° m o 0 0 0 0 0 0 0 0 0 m o0 o°o00 o°o°o°o°o°o°o° • Compliance o°m°000°000°0°00000 • UL 2034, UL 2075, UL 1971, UL 464, ULC S525, ULC S526 °o°m o°°o°Op°o°00000°®oo° °aooee000000oee0000 • California State Fire Marshal (CSFM) o o eeeee o o o°aoeeeeeepe0o • ADA/NFPA/ANSI/OSHA 000 • RoHS Note: All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION Figure 2.Wall Low Frequency Sounder INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT.VISIT WWW.000PERNOTIFICATION.COM OR CONTACT Table 1. Horn Strobe Current Draw COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. ULIULC Max Current a FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR Exceder LED Sounder Strobes 24VDC WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, 16-33 Volts WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR Model Horn Setting 110 cd DEATH TO YOU AND/OR OTHERS. LLFHS Continuous 0.292 Code 3 0.292 Code 4 0.292 General Notes Code 3/Code 4 0.292 • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range:' Note that NFPA-72 specifies a Table 2. Horn Only Current Draw flash rate of 1 to 2 flashes per second and ADA Guidelines specify ULIULC Max Current a a flash rate of 1 to 3 flashes per second. Exceder LED Sounders 24VDC • All candela ratings represent minimum effective Strobe intensity Model Horn Settings 16.0-33.0 based on UL 1971. LLFHN Continuous 0.113 Code 3 0.113 Code 4 0.113 Code 3/Code 4 0.113 2 EATON www.eaton.com Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Effective May 2014 Table 3. Sound Output (SPL)- UL Table 4. Sound Output (SPL)- ULC LLFHS/LLFHN 24V LLFHS/LLFHN Reverberant dBA per UL 464 dBA per ULC S525-07c Description 16.OV 24.OV 33.OV Description 16.OV 24.0V 33.OV Continuous 80 80 80 Continuous 80 80 80 Code 3 76 76 76 Code 3 80 80 80 Code 4 b 85 85 85 Code 4 80 80 80 Code 3/Code 4 76 76 76 Code 3/Code 4 80 80 80 Table 5. Specification &Ordering Information Sync w/DSM or Model Strobe Candela Red White Lettering Wheelock Power Supplies Sounder Strobes LLFHSR 110 X FIRE X LLFHSW 110 X FIRE X LLFHSR-AL 110 X ALERT X LLFHSW-AL 110 X ALERT X LLFHSR-CO 110 X CO X LLFHSW-CO 110 X CO X LLFHSR-N 110 X No Lettering X LLFHSW-N 110 X No Lettering X Sounders LLFHNR-AL X ALERT X LLFHNW-AL X ALERT X LLFHNR-CO X CO X LLFHNW-CO X CO X LLFHNR-N X No Lettering X LLFHNW-N X No Lettering X Accessories Description Red White LSPKBB-R 0756 Exceder LED Backbox X LSPKBB-W 0757 Exceder LED Backbox X Table 6. Specifications Physical Material Red or white textured UV stabilized,colored impregnated engineered plastic. Exceeds 94V-0 UL flammabil- ity rating Weight 1.10 lbs. Lens Light Emitting Diode(LED)in a rugged Lexan lens Dimensions 6.1"H x 4.56"W x 1.4" D Operating Temperature Indoor:33.8°F to 120.2°F WC to 49°C)and maximum humidity of 85% Mounting&Wire Connections Mounting(indoor only) Wall-mount applications only. Exceder LSPKBB backboxes or to 4" square backboxes Wire Connections #12 through#18 AWG Power&General Operating voltage 24 VDC: 16-33 VDC Strobe Output Rating UL 1971: 110 candela output Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies, using Wheelock patented sync protocol Temporal Audible Pattern Continuous, Code 3, Code 4 or Code 3/Code 4 Sync Control. The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. The Code 4 temporal pattern (four cycles of 100 milliseconds 10 percent"on"and 100 milliseconds 10 percent"off;'followed by 5 seconds 10 percent"off) is specified by NFPA 720. a RMS current ratings are per UL maximum RMS method.UL max current rating is the maximum RMS current within the listed voltage range(16-33A. For strobes the UL max current is usually at the minimum listed voltage. For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation instructions. b Code 4 setting rated per UL 2075, UL 2034. c For dwelling use only. 3 EATON www.eaton.com Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes & Sounders Effective May 2014 Architects and Engineers Specifications backboxes and to standard 4" square backboxes. The sounder and The low frequency sounders and sounder strobes appliances shall sounder strobe shall incorporate a mounting plate with a snap-on be Wheelock® ExcederTm LED Series LLFHN Sounder and LLFHS grille cover and shall mount to standard electrical hardware requiring Sounder Strobe for wall-mount applications with a low-profile design no additional trimplate or adapter. Removal of an appliance shall or approved equals.The sounders shall be UL Listed under UL 464 result in a supervision fault condition by the Fire Alarm Control Panel (FACP). All notification appliances shall be backwards compatible. for Fire Protective Service and to the requirements of UL 2034/UL 2075 for CO applications and ULC S525. Sounders equipped with The Series LLFHN wall model shall have a low profile measuring strobes shall be listed under UL 1971 for Emergency Devices for the 6.1" H x 4.56"W x 1.29" D.The Series LLFHS wall model shall have Hearing-Impaired and ULC S526.The Series shall be Restriction of a low profile measuring 6.1" H x 4.56"W x 1.4" D. Finish shall be Hazardous Substances (RoHS) compliant and contain no mercury or red or white. Special lettering,ALERT, CO and No lettering, shall be other hazardous substances. In addition, the sounder strobes shall available. meet the requirements of FCC Part 15.All inputs shall be compatible When synchronization is required, the appliance shall be with standard reverse polarity supervision of circuit wiring by a Fire compatible with Wheelock's DSM Sync Modules, PS 6/8 Power Alarm Control Panel (FACP)with the ability to operate from 16 to 33 Supplies,or other manufacturer's panels with built-in Wheelock VDC. Patented Sync Protocol.The strobes shall not drift out of synchro- nization at any time during operation. If the sync protocol fails to The Series LLFHS Sounder Strobe shall produce a flash rate of one operate,the strobe shall revert to a non-synchronized flash-rate and (1)flash per second over the Regulated Voltage Range and shall still maintain (1)flash per second over its Regulated Voltage Range. incorporate a Light Emitting Diode (LED)as the light source with a The appliance shall also be designed so that the audible signal may rugged Lexan®lens.The Series shall be of low current design.The be silenced while maintaining strobe activation when used with strobe intensity shall have a 110 candela for wall mount applications. Wheelock patented sync protocol. The audible shall have a minimum of four(4) 520 Hz modes of operation:T3 (fire),T4(CO), Continuous,T3/T4 Sync Control. UL 1971, UL 464, ULC S525, ULC S526, CSFM, FCC, RoHS The Series LLFHS and LLFHN shall be designed for indoor surface or flush mounting. Mounting options shall include LED speaker Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. 111=11A WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eaton.com Cooper Notification 273 Branchport Ave. Long Branch,NJ 07740 CooperN otif i cation.com ©2014 Eaton All Rights Reserved Eaton is a registered trademark. - Printed in USA Publication No.TDO01009EN All other trademarks are property Powering Business Worldwide June 2014 of their respective owners. pp- 000 COOPER Notification EJCED _ Strobe, Horn Strobe, and Horn Notification Appliances - Ceiling Wall Description: The Wheelock°Exceder`Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. - Save up to 14% cost of installation** The Wheelock°ExcederTm Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single U Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. C40 Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock° ExcederTm Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before ' the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a 90,95,99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings *** it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra Universal Mounting Base *** secure installation, while the ceiling models provide a captivated Ceiling and Wall screw to prevent the screw from falling during installation. UU Mounts to 5 Backbox Types Compliance Environmentally Friendly -UL 1971, UL 464, ULC, CSFM, FM Low Current Draw -ADA/NFPA/ANSI/OSHA -RoHS Compatibility and Requirements -Synchronize using the Wheelock°Sync Modules or panels with built-in Wheelock°Patented Sync Protocol -Compatible with UL"Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage" range Compared to competitive models ""Patented Compared to previous models NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 1207(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 1971). Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = FewerPower • • Strobe Ratings per UL Standard 1971 UL Max Current* 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &Anechoic at 24 VDC AnechoicUL Max Current*at •• •:A 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 10.125 AnechoicUL Max Current*at •:A 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122 AnechoicUL Max Current*at •• •:A 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL Anechoic Model Regulated Voltage 99 dB 95 dB 90 dB Range VDC HN 16-33.0 0.064 0.044 0.022 HNC 16-33.0 0.084 0.044 0.022 HN 8.0-17.5 0.047 0.026 0.017 HNC 8.0-17.5 0.047 0.026 0.017 *UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Sync w/ Model Strobe DSM or 12/24 VDC* Mounting Candela Wheelock Power Options Supplies HSR 15/1575/30/75/95/110/135/185 X X UMB** ' HSW 15/1575/30/75/95/110/135/185 X X UMB** H S RC 15/30/60/75/95/115/150/177 X X UMB** ' HSWC 15/30/60/75/95/115/150/177 X X UMB** STIR 1511575/30/75/95/110/135/185 X X UMB** STW 15/1575/30/75/95/110/135/185 X X UMB** STRC _ 15/30/60/75/95/115/150/177 X X UMB** STWC 15/30/60/75/95/115/150/177 X X UMB** HNR X X UMB** HNW X X UMB** HNRC .. X X UMB** HNWC 117 X X UMB** *12 VDC models feature 15&15/75 settings **UMB=Universal Mounting Base Model Legend HN = Horn A =Agent Lettering - ST = Strobe (Strobes only) 4r HS = Horn Strobe AL=Alert Lettering C = Ceiling Mount (Strobes only) W =White N = No Lettering R = Red (Strobes only) Example 1: STRC=Strobe,Red,Ceiling Mount / Example 2: HSR=Horn Strobe, Red,Wall Mount / Example 3: HSW=Horn Strobe,White,Wall Mount ' r Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering ■ p g Example. Example: HSWC • 1 *UMB Contact Cover NOTE: Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock° ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. Where Multi-Candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68"x 1.50" D. When synchronization is required,the appliance shall be compatible with Wheelock®'s DSM Sync Modules,Wheelock®Power Supplies or other manufacturer's panels with built-in Wheelock®Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1) flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock®synchronization protocol. Wall Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS Ceiling Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS W WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder- Spec Sheet 5/13 NJ Location 273 Branchport Ave. Long Branch, NJ 07740 800-631-2148 www.coopernotification.com Cooper Notification is Wheelock' MEDC SAFEPATH® WAVES { COOPER Notification S-24 & HS-24 CPOTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Features • 24VDC units have field selectable candela options of 15,30,60, 75,& 110 • Super-Slide®Bracket-Ease of Supervision Testing • Checkmate®-Instant Voltage Verification • Synchronize strobe and/or horn with AVSM Control Module • Prewire entire system,install mounting bracket,then install - signals f, _ — Documented lower installation and operating costs Input terminals accept 12 to 18 AWG Switch selection for high or low dBA Switch for chime,whoop,mechanical and 2400Hz tone Tamperproof re-entrant style grill R I I I I I I I I Switch for continuous or temporal 3 tone(not available on whoop tone) • Surface mount with the AVBB(Surface Mount Back Box) • Silence audible while visual appliance will remain flashing(for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature • 320F to 120OF(0°C to 49°C).The HS and S Series are not listed for outdoor use. Unit Dimensions • 5"(12.7 cm)high x 4.5"(11.43 cm)wide x 2.5"(6.35 cm)deep U� LISTED S3247 Description The S-24/HS-24 Series is a low profile strobe and horn/strobe This Series is shipped with a standard 4" metal mounting combination that offers dependable audible and visual alarms and the plate which incorporates the popular Super-Slide®feature that allows absolute lowest current available. the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without The S-24 & HS-24 Series 24VDC offers tamperproof field any screws showing. selectable candela options of 15,30,60,75,and 110 candela. The S-24/HS-24 also features the patented Checkmate® - The Strobe and Horn/Strobe offers a continuous or sync Instant Voltage Verification feature which allows the installer to check temporal three in 2400Hz and mechanical tone, a chime and whoop the voltage drop draw and match it to the blueprint. tone.All tones are easy for the professional to change in the field by the use of switches. The S-24&HS-24 Series appliances are ANSI/UL 464 and ANSI/TJL 1971, listed for use with fire protective systems and are The S-24 & HS-24 Series has a minimal operating current warranted for three years from date of purchase. and has a minimum flash rate of 1 Hz regardless of input voltage. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 1 OF 4 06/13 S-24 & HS-24 (E) POTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Tone Switch Locations TONE SWITCH POSITION 3 4 5 ®o Mechanical Temporal 3 ON ON ON �® 1, Mechanical-Continuous OFF ON ON 2400Hz-Temporal 3 ON OFF ON ® S+ 2400Hz-Continuous OFF OFF ON S- Chime-Temporal 3 ON ON OFF -® H+ � Chime-Continuous I OFF ON OFF Whoop I ON OFF OFF Whoop OFF OFF OFF NOTE: • Switch Positions 1 and 2 in the OFF position to select isolated horn and strobe power inputs • Switch Position 6 ON=HIGH dBA • Switch Position 6 OFF=LOW dBA Super Slide®Mounting Bracket Checkmate®Instant Allows the installer to pre-wire Voltage Verification the system,test for system It is often necessary to confirm the voltage supervision,remove the signal drop along a line of devices.The access head until occupancy,switch holes are provided in the back of the out signals without terminal block to allow the voltage to be changing mounting brackets measured directly without removing the and has locking edge connector device.Typically,this would be done at the for snap-in-place installation. end of line to confirm design criteria.Most - measurements will be taken using the S+ and S-locations althouhg access is provided to other locations. NOTE:Care should be taken to not short the test probes. Candela selection slider switch. Depress center and slide switch to desire brightness level. r- T Break off pin and insert l S into hole at the bottom of .a the selector to lock candela setting.Signal must be removed from bracket and pin pushed forward from backside out of hole to change candela. To remove bezel,grip both sides of bezel and pull in a download and outward motion. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 2 OF 4 06/13 S-24 & HS-24 CF POTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES S-24 24 VDC Selectable Candela,Low Profile Evacuation Strobe Model Part Nominal Candela Number Number Voltage (ANSI/UL 1971) S-24WR I 4890010 24 VDC 15,30,60,75, 110 S-24WW 4890011 24 VDC 15,30,60,75, 110 HS-24 24 VDC Selectable Candela,Low Profile Evacuation Horn/Strobe Model Part Nominal Candela Reverberant dBA at In Anechoic Room Number Number Voltage (ANSFUL 1971) 10 ft.,per ANSI/UL 464 dBA at 10 ft. HS-24WR 4890030 24 VDC 15,30,60,75, 110 62-82 100 HS-24WW 4890031 24 VDC 15,30,60,75, 110 62-82 100 S-24&HS-24 Product Strobe Current Ratings(mA) 24 VDC(16-33 Volts) Model Designations: W=Wall Mount Candela 24 VDC UL Maxi R=Red Faceplate W=White Faceplate 15 cd 30 mA 42 mA 30 cd 35 mA 58 mA All units are available in plain(no lettering). Plain units are non-returnable. 60 cd 66 mA 97 mA 75 cd 80 mA 116 mA ALERT bezel available for order. 110 cd 103 mA 161 mA ALERT bezel available for order. S-24&HS-24 Product Horn Current Ratings Horn Decibel Levels Horn Current Ratings Minimum SPL Minimum SPL Regulated 24 VDC Horn Mode at 10 ft.,per at 10 ft.,per Max.Operating @ ANSI/UL 464 ANSI/UL 464 High Setting(mA) (HIGH) (LOW) Temp 3 2400 Hz 78 dBA 71*dBA 28 mA Temp 3 Mechanical 76 dBA 70*dBA 25 mA Temp 3 Chime 70*dBA 66*dBA 15 mA Continuous 2400 Hz 81 dBA 74*dBA 28 mA Continuous Mechanical 80 dBA 72*dBA 25 mA Continuous Chime 70*dBA 66*dBA 15 mA Whoop 82 dBA 69*dBA 56 mA NOTES: • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified]) power,see installation manual. • Potter does nto recommend usign a coded or pulsing signaling circuit with any of our strobe products. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use.Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 3 OF 4 06/13 S-24 & HS-24 (E) POTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Architect&Engineering Specifications The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 horn/strobe Series or approved equal and shall be listed by Underwriters Laboratories,Inc.per ANSI/UL 1971 and/or ANSI/UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM)and the California State Fire Marshal(CSFM). The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage.The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. Conventional Wiring Diagrams for Emergency Notification Evacuation Series UL Listed UL Listed Control Control Panel signal signal Panel Signal Signal g+ S+ S- H+ H- S+ S+ S- H+ H- s+ S+ S- H+ H- S+ S+ S- H+ H. Supervised Supervised 0 B 0 B Signal Circuit Signal Circuit \ + \ + END LINE END OF LINE RESISTOR RESISTOR \ + 7D END OF LINE RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage.Strobes should not be used on coded or pulsing signaling circuits.However,use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe,horn,and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION,REFERENCE AVSM CONTROL MODULE DATA SHEET(8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 4 OF 4 06/13 GENTEX CORPORATION GOE OUTDOOR ENCLOSURE Applications A C C E S S O R I E S The Gentex GOE Outdoor Enclosure is ANSI/UL 464 listed for use in indoor and P A G E outdoor applications when used with the Gentex GEH Series horn and WGE Series strobe and horn/strobe. Standard Features • ANSI/UL 464 listed • Back box with side mount tabs • Made of clear Lexan°- providing maximum visibility and reliability • Unit Dimensions: 5.75" (14.61 cm) high x 4.75" (12.10 cm)wide x l •�,''- 4.18" (10.62 cm) deep • 3/4"conduit knockouts l'llll� • Reinforcement steel hardware --- R • Outdoor resistant gasket • Available in red or off-white GOE-R GOE-W GOELP OUTDOOR ENCLOSURE Applications The Gentex GOELP Low Profile Outdoor Enclosure that creates a surface mount look, is ANSI/UL 464 listed for use in indoor and outdoor applications when used with the Gentex GEH Series horn and WGE Series strobe and horn/strobe. Standard Features • ANSI/UL 464 listed • Back box with outdoor resistant seal for mounting to wall GOELP GOE • Made of clear Lexan°- providing maximum visibility and reliability • Unit Dimensions: 5.75" (14.61 cm) high x 4.75" (12.10 cm)wide x 3.25" (8.255 �+- cm) deep • 3/4"conduit knockouts • Reinforcement steel hardware • Outdoor resistant gasket • Available in red or off-white GOE AND GOELP NOTES: • Product does not meet ANSI/UL 1971 light distribution requirements • To allow for drainage, the seal on the bottom edge is not water tight GOELP-R GOELP-W GBLP OUTDOOR BACK BOX Applications f ►'� The Gentex GBLP Outdoor Back Box is constructed of durable plastic is ANSI/UL _ •, 464 listed for use indoor and outdoor applications when used with the WSSPK Series speaker and speaker/strobe. Gl Standard Features o' v • ANSI/UL 464 listed ,.. • 1/2"conduit knockouts with metal washer reinforcements i • Wiremold knockouts for 500, 700 Series and pendulum mount • Unit Dimensions: 6.20" (15.75 cm) square x 2.04" (5.18 cm) deep • Reinforcement steel hardware GBLP-R GBLP-W • Outdoor resistant gasket • Available in red or off-white ACCESSORIES PAGE GSB SURFACE BACK BOX Applications The Gentex GSB Surface Back Box is constructed of durable plastic and is fully compatible with the Commander' (GE)and Commander'(GE3) Series horns, strobes and horn/strobes. Standard Features • ANSI/UL listed for indoor use • 1/2" conduit knockouts with metal washer reinforcement • Wiremold knockouts for 500 and 700 Series • Unit Dimensions: 5.57" (14.15 cm) high x 4.55" (11.56 cm) wide x 1.47" (3.73 cm) deep • Screw heads hidden GSB-R • Available in red or off-white ALERT & AGENT BEZELS Applications The Gentex ALERT and AGENT bezels are constructed of durable plastic and is q fully compatible with the Commander (GE)and Commander' (GE3) Series horns, l strobes and horn/strobes. E Standard Features R T • Easy to install I • ALERT or AGENT wording on both sides of bezel • Available in red or off-white ALERT-W AGENT-R GCSB CEILING SURFACE BACK BOX Applications The Gentex GCSB Surface Back Box is constructed of durable plastic and is fully compatible with the Commander (GC) Series strobes and horn/strobes. Standard Features • ANSI/UL listed for indoor use • 1/2"conduit knockouts with metal washer reinforcement • Wiremold knockouts for 500, 700 Series and pendulum mount • Unit Dimensions: 6.2" (15.75 cm) round x 1.67" (4.24 cm) deep • Screw heads hidden • Available in red or off-white GCSB-R GCSB-W Important Notice: 551-0031-02 G E N T E X These materials have been prepared Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and arere not purported to servee as legal advice and should not be used as such. Gentex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws, CORPORATION regulations and rules. The materials do not address all legal considerations as there is inevitable Fire Protection Products Group•www.gentex.com uncertainty regarding interpretation of laws,regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the 10985 Chicago Drive •Zeeland, Michigan 49464 obligations that exist under applicable laws,regulations or rules. Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. 9 8 7 6 5 4 3 2 1 HRE PROTECTION INC- 1730 Gibson Road Everett,WA.g8204 DEVICE INSTALLATION REQUIREMENTSPARK 77 PARTMENTS VICINITY MAP 425-290-9600 DAVID MOW mxc wear CEIUNG MOUNTED 3' YIN osruvx NOT PERMITTED SMOKE/HEAT+ iF&I HFRE DETECTOR + CJUNG 1' T �' /ll% 120904, AUoIO/MSUAL L x• a VISUAL DEVCES 4- NOT LEVEL III PERM,TIED ERMHE 'r HERE HERE BUILDING'�'I _:;9�44 PERMITTED, HERE McDowr NFPA D FRCP ME P= - 000805173 B nclrlEa ncBtn IE,y rao�a tuvnsEr x $ex �aw " FIRE ALARM _ u'wix ey-p ROY L CATS sas•x tAT'R �, HSD zs B —� � ; - QPO7ECr P�■^■ �`,, ■■9 n•AR W., WArr WAN, FIRE tMANUAL i ...,. (° �AirMiN N.0-st PHDNE PULL Aerospace a JACK STATION nufacwnngTech° 6 NFPA yC d� ti ARLI N GTO N, WA CFPS 46'MAX r FINISHED iL00R CITY OF REDMOND DAVID MOW - ...sea INSTALLATION NOTES Fire Alarm Symbol Legend 204TH STREET N.E. o 1) Prior to calling for inspection,the installer shall provide SYMBOL DESCRIPTION PART NUMBER MFG QTY BACKBOX REQUIREMENTS MOUNTING REQIXREMENTS lu 2 documentation to the local AHJ stating that the system has been � w C I^^' LCD REMOTE ANNUNCIATOR RA-6075 POTTER 1 v H n installed,tested,evaluated and confirmed to be in accordance with all governing codes and the approved plans.The Fire Alarm System PS INTELLIGENT 10 AMP REMOTE POWER EXPANDER PSN-10W POTTER , AREA OF WORK U Re Z y N C installer shall complete an NFPA72 Record of Completion(NFPA72 Ts SPRINKLER TAMPER BY OTHERS BY OTHERS Z 01 U = 01 10.18.2.1.1). The completed Record of Completion shall be provided to BUILDING 11 0 0 DUAL INPUT CONTACT MODULE DCM-0 POTTER 1 BBOX-0.Standard backbox..4 - f C- -t7� the AHJ inspector at the time of inspection(NFPA72 10.18.2.1.2.4). ® BLDG.13 o z'o w«a ❑F PULL STATION SINGLE ACTION P31-IT POTTER 1 BBOX-2.Standard backbox.2 4W AFF _ — — ——— Q O tY G J^ 2) Instructions for the operating,testing and maintenance of the ? o�to W a t o>.W o (xS) SMOKE,PHOTO,2-WIRE 2W-B SYSSENSOR , BBOX-2,Standard backbox,2 I >W O a N system,along with record drawings otherwise referred to as �� = I m rc W W$ ("as-built")and equipment specifications shall be provided at an LF LED,LF,HORN/STROBE,MC,WH LLFHSW WHEELOCK 9 BBOX4,Standard backbox,4 ffi AFF BLDG.12' BLDG.11 j 3 o $ o approved location(NFPA72 10.18.2.3). _W W m tr a FUI wD STROBE,EXCEDER 24V M-C,WALL,WHITE STW WHEELOCK 7 BBOX-2,Standard backbox,2 82"AFF BLDG.14 _ _ I U N 4r� W `-------J REVISION RECORD 3) All systems and devices shall be installed and tested per the = �' manufactures listing and the authority having jurisdiction(NFPA72 wco HORNSTROBE,EXCEDER 24V.M-C.WALL,WHITE HEW WHEELOCK 4 BBOX-2,Standard backbox.2 82"AFF - DATE/DESCRIPTION 10.14.2.1).Label all device locations containing EOL resistors. c BLDG. 17 �_ I LF HORN LOW FREQUENCY,WH GHLFW GENTEX 16 BBOX4,Standard backbox,4 82"AFF /� w 4)FRCP&all Remote Power Supplies REQUIRE a DEDICATED 120VAC ca / Building m BLDG-15 �BLDG.9 a 20amp circuit.A notice placed in the FRCP shall direct personnel to the MINI HORN,WH MHT-1224W POTTER 8 BBOX-2.Standard backbox.2 62-AFF BLDG.10 — location of the electrical panel that is supplying DEDICATED power to wP 'Z, --r = SHEET LIST „edb HORN/STROBE,2WIRE,M-C,RED,WALL HS-24WR POTTER , BBOX.2,Standard backbox,2 82"AFF —����� N the system(NFPA72,Section 10.5.5.1). The DEDICATED circuit breaker I `� R FA 0.0 FA DETAILS that serves the fire alarms stem shall be Labeled and Secured against Fa WATERFLOW SWTICH BY OTHERS BvorHERs I BLDG.8 y g BLDG.16 I _ D FA 1.0 FIRE ALARM tampering with a RED breaker lockout(NFPA72,Section 10.5.5.2). _ FgCP FRCP LOCATED IN BUILDING 17 P3o0 POTTER E _ r'z rBLDG.6 BLDG.?_ I � -� FA 2.0 RI$ER/CALC$ OUTDOOR HIS WEATHERPROOF ENCLOSURE GOELP POTTER I L i(= -BLDG.5 I , - B 5)This property will have one FACP located in the Community Building. ' Each residential building will have a Remote Power Supply and a - --�-- - Remote Fire Alarm Annunciator connected to the main FACP in the Community Building.The FACP will monitor each buildings fire sprinkler system via SLC,the occupant notification devices in each the building will only activated when a fire alarm device from that BLDG.2 f BLDG.3; BLDG.4 speck building(waterflow,smoke detector,pull-station) is activated. __ J L. ter Lr� 6) Wall mounted strobes shall be placed 80"minimum to 9611 maximum above floor level.(NFPA72 18.5.4.1&2).Wall mounted strobes shall be SITE PHASING PLAN sized in accordance with(NFPA72 Table 18.5.4.3.1(a).Ceiling mounted SYSTEM OUTPUTS strobes shall be placed and sized in accordance with(NFPA72 Table Required Fire Safety Control 18.5.4.3.1(b). cormol Unit Annuncia on ti c /// 0; SCALE: 1/8"=1' c DATE: 10/10/16 7) When MORE than two notification appliances are visible at the same o o c.c . time whether they are in the same room or adjacent space within the h o'Coy; PROJECT NAME field of view,the flash of those strobes shall be synchronized(NFPA72, �° `y s° y Section 18.5.4.3.2(3)&(4). z yc°"°��2 CIRCUIT LINE TYPE Circuit Legend w a O o s.o 8) Pull stations shall be placed between 42 and 48 inches above floor a« o a ; Z Z Q level.Devices shall be red in color(ICC A117.1 309&NFPA 72 17.14.5) F yo`` o Q = A Abbreviation Type Name w 9 Outdoor strobes required fora approaching Emergency Vehicles to d Qe�> `y F y� ---- u U #18/4 FPLR SLC-SIGNAL LINE CRKT H Q Z q o pp g g y a e a as A #1614 FPLR TWISTED PAIR NAC-NOTIFICATION CRKT O Z A be located in the upper 25/o of the building(at a serviceable height), Q Q 4 y o+3 y ry Q — = O and to be clearly visible from the emergency vehicle approach path. , , q e e;g; e B #18/4 FPLR SBUS d 0 n U A Z 10)Fire Alarm circuits to be installed/securedherminated in accordance SYSTEM INPUTS A B C D E F G H O J h CD —C) J with NEC,NFPA 72,IFC and Local AHJ requirements&standards. 1 Manual Fire Alarm Boxes ♦ ♦ ♦ ♦♦ 1 Y C4 Q -L Smoke Detectors ♦ ♦ ♦ ♦♦ 2 N 11)The means of communication to the central stations for the fire 8 Waterflow ♦ ♦ ♦♦♦♦ s Fire Alarm Device Numbering d 4 alarm system is to be provided by a Potter UD-1000 DACT as per plan. Sprinkler Control Valve ♦ ♦ 4 6 Fire Alarm AC Power Failure ♦ 7 . ♦ 6 (SLC)ADDRESSABLE DEVICES NOTIFICATION DEVICES System requires 2 x POTS telephone lines,1 of these lines is required 6 Fire Alarm System Low Battery ♦ ♦ 6 to be DEDICATED to the FACP.The FACP is located in building 17. 7 Open Circuit ♦ ♦ . 7 CIRCUIT CIRCUIT 8 Ground Fault ♦ - ♦ g DEVICEADDRESS DEVICEY SHEET DESCRIPTION 12)All building linking conduit&wiring to be provided/installed by 9 Notification Appliance Circuit Short ♦ ♦ 6 CANDELA 5Lc•uRM /L^1 FIRE ALARM 10 Remote Power Supply Trouble ♦ ♦ 10 `�V.7// ' DETAILS others. ABC0E FOH I J OPERATIONAL MATRIX SMOKE DETECTOR SHOWN AS EXAMPLE C[ SHEET NUMBER FA 0.0 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE PROTECTION INC. 1730 Gibson Road Everett,WA.98204 425-290-9600 DAVID MOW e m J LEVEL III D - UNIT B-11 1 n UNIT B-10 �--- UNIT B-9 sly I j- I UNIT B42 p H NFPA 614 FPLR SIG S 000805173 PS IN RISER ROOM t I I J I H ---- O_ ROY L CATS I A i I� i �QPOTECTjO �1 l i I O I = I A _- - i- --- #1473 IJ 1 -J STAIR/ j STAIRI _— sirso�, A I •.,,� ENTRY -L.I I ENTRY sicsaro I 7 DN I�_ `- —- DN —Ia. CITY OFREDMOND DAVIVIDo MOW R sacs ooz na#16-B-141co O W H m U q W 2 N z F 6 3RD FLOOR - f O J H V J 3OCOo ZOW p 9YWFW OmzFO Y WDu.mY m�W W6K 3 H W 0 R'0: 614 THHN'BUILDING THE FAC 0 U 2:H-+a u: (LOCATED IN BUILDING 17 REVISION RECORD 61 FPLR SIG 3 — 6/2 THHN SLC TO THE FAC O PS IN RISER ROOM - I OCATED IN BUILDING t7 DATE I DESCRIPTION 17614 FPLR SIG 2 O PS IN RISER ROOM /— --- F ZNhW1 �r Z S,zN _ _ — SHEET LIST - I -. _ FA 0.0 FA DETAILS sici•a,aam — � UNIT B-7 _ - - FA 1.0 FIRE ALARM k-� UNIT B-2 UNIT BJ UNIT B-1 I ' Type A sicaaas Type A =� Ts Fs UNIT B-6 srr% FA 2.0 RISER/CALCS I—D --- ZN]•001 2Ni•Wt I B Type A I I °oc° I UNIT B 4 UNIT B-5 sct•u o F� sr----- ----- UNIT 68 7 ,, sxo-------- -- O' I SIG— �s°r°oo. I Type A '. - F _.� r I 1614 PLR SIG 4 I SIG-3AL J I -- \- A I O PS IN RISER ROOM ---- -- r------ - _�� I I -- __ T I TI I sr*001 I 1614 FPLR SIG( I A - I( I -�iJrx° I I�tss cc3r cos IrJv�s_oo: sIlI�x�°�III •— I I ,-rI -------I --- �° nI�- -T -rntaa-w° 'f�rsc -- _- Gz STAIR! If STAIRr:-� cv � SCALE 1/8"=1' L6TAIw l SAIw ENTRY ENTRY ENTRY r ENTRY -- r -- UP - I DATE: 10/10/16 uP_ EaSN.° --i-- -�,� I rc•aae PI RJR, sr� PROJECT NAME A y J _ ` dl I li \ /-I - i s •ma s' I .. sir..ms T ttOC° 11aC° -- w wt. Z � 5 G3 005 � _ --- w � t9QZ — —�-- = O A � a. CL a UP q UP Q Jn � _ r Z 1ST FLOOR -N 2ND FLOOR N ^ m CD 11714 � N Q a SHEET DESCRIPTION FIRE ALARM SHEET NUMBER FA 1 .0 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 �'�� Aw FIRE PROTECTION INC. 1730 Gibson Road Everett,WA.98204 Battery Calculations for Panel:PS BUILDING 11 425-290-9600 Part No:PSN-1000-INTELLIGENT 10AMP REMOTE POWER EXPANDER DAVID MOW Part No. Qty. Description Standby Total Standby. Alarm Total Alarm ('N Panel Equipment PSN-1000_MB 1 10AMP POWER EXPANDER MB 75.000OmA 75.000OmA 215.000Omh 215.0000mATotal Panel Stby 75.000OmA TotalPanel Ale 215. �' Peripheral Devices 2W-B 1 SMOKE,PHOTO,2-WIRE(Initiefing) 0DIO0.4 0.0100mA 6.5000mA 6.5000mA 120904 P31-1T 1 PULL STATION SINGLE ACTION(Initiafing) 0.0000mA O.000DMA 000ODrrA 0.0000mA ILEVEL III LLFHSW 9 LED,LF,HORNISTROBE,MC,WH(Notification) 0.000OmA 0.000OmA 292.0000mA 2628.000OmA STW 7.STROBE,EXCEDER 24V M-C,WALL,WHITE(Notification) 0.0000mA M000DmAj 57.0000mA 399.ODOOmA HSW 4 HORNISTROBE,EXCEDER 24V,MC,WALL, A WHITE(Notification) 000WmA 0.0000.A 102.0000nA 408.0000mA D GHLFW 16 HORN LOW FREQUENCY,WH(Notification) O.aooOmA O.a000mA 99.40aomA 159D.4600m MHT-1224W MINI HORN,WH(Notification) 0.0000mA 0.000OmA 22.0000mA 176.000OmA HS-24WR 1 HORNISTROBE.2 WIRE,M.C.RED,WALL(Notification) O.00DDMA 0.0000mA 1860000.A 186.0000MAD Total Peripheral Stby 0.0100rr1A Total Periph Alarm 5=3.90001M NFPA Total Standby Amps 75.01ODmA Total AlarmAmps 56D8.9000mA 000805173 Standby time:24 Hm ISM ROYL CATS Alarm time:5 Min 0.467M Q9DTECj� Battery requirement: 226BAh 0F' dy Compensation Factors-Standby:12 Alarm:1.2 Requirement with compensation: 2.721M y NF1 a PA' S ''o y Circuit Calculations Panel:PS Card:00 Circuit:SIG1 Circuit Calculations Panel:PS Card:00 Circuit:SIG2 Circuit Calculations Panel:PS Card:00 Circuit:SIG3 CFP6 Clrcuit "a SIGT Circuithlame:SIG2 CircultName:SIG3 #1473 CimuitType:Notification Terminal Voltage:20.4V:DC Amperage:3.000DA Cimuit Type:Notification Terminal Voltage:20.4V:DC Amperage:30DDOA Circuit Type:Notification Terminal Voltage:20AV:DC Amperage:3.00DOA Cable:1614C TWISTED FPLR#16 Cable:1614C TWISTED FPLR 016 Cable:1614C TWISTED FPLR#16 Calculations based on Running Total Length. Calculations based on Running Total Length. Calculations based on Running Total Length. Design Criteria:Ambient temperature:1STF Max.operatingvoltagedrop:15% Design Cdteria:Ambiemtempemtum:16TF Max.operatingwitagedrop:l5% Design Criteria:Ambient temperature:1677 Max.operating voltage drop:15% Device Part No Appliance Desc Distance Current Voltage Voltage Drop Device Part No Appliance Desc Distance C_urreM Voltage Voltage Drop Device Part No Appliance Desc Distance Current Voltage Voltage Drop CITY OF REDMOND PSN-1000 Panel 20AV PSN-1000 Panel 20.4V PSN-10DO Panel 20AV DAVID MOW 001 HSW HORN/STROBE,EXCEDER 24V,M-C,WALL,WHITE,30CD 39-01 102. 19 (0.4165V)i Out LLFHSW LED,LF.HORN/STROBE,MC,WH,11DCD 4& 292.0000mA 19.812 (0.5873V) 001 STW STROBE,EXCEDER 24V M-C,WALL,WHITE,15GD 102'-0 57. 19.310 (1.0693V) na arcs..or as a 002 STW STROBE,EXCEDER 24V MC,WALL,WHITE,I5CD Z-O 57.00DDmA 19.9641 (0.019414) 002 STW STROBE,EXCEDER 24V M-C,WALL,WHITE,I5CD 15 57oDD0mA 19. (0.1407V) 002 HSW HORN/STROBE,EXCEDER 24V,MC,WALL,WHITE,30CD 2T-0 102.000OmA 19.0981 (0.212 #16-B-141co STW STROBE,EXCEDER 24V MC,WALL,WHITE,I5CD 2V-0 57.0000mA 19. _(0.19161n OD3 STW STROBE,EXCEDER 24V M-C,WALL,WHITE,I5CD 1T 57.0DD0mA 19.5221 (0.15V) om STW STROBE,EXCEDER 24V M-C,WALL,WHITE,I5CD 16 5T0000mA 18.9521 (0.146V) 004 LLFHSW LED,LF,HORNISTROBE,MC,WH,110CD 7-0 292.00DOnA 19.7564V J0 1 1 DD4 HSW HORNISTROBE,EXCEDER 24V,MC,WALL,WHITE,3DCD 21 102.0000m 19.348 (0.1735V) 004 LLFHSW LED,LF,HORNISTROBE,MC,WH,110CD 19-0 292.DDDOmA 18. (0.1628V) 005 LLFHSW LED,LF,HORNISTROBE,MC,WH,IIDCD 26--0 292-00DOmA 19. -(0.148M 005 LLFHSW LED,LF,HORWSTROBE,MC,WH,110CD T-0 292.DDDOmA 19.2977V to 0509u) 005 LLFHSW LED,LF,HORNISTROBE,MC,WH,IIOCD V-0 292.0000 18.7 (0.0228V) O ODS LLFHISW LED,LF,HORNISTROBE,MC,WH,110CD 7'0 292. 19aD1 (0.IXI57V) HSW HORWSTROBE,EXCEDER 24V MC,WALL,WHITE,30CD 19 102.ODDOmA 19.21 (0.0838Vj LLFHS LED,LF,HORN/STROBE,MC,WH,110CD 14' 292.ODDOmA 18.7 to 9" w C 92'-0 1092 o90DmA 007 LLFHSW LED,LF,HORNISTROBE,MC,WH,110CD V D 292.0D00 19.2 (0.0137V) 179-01092DWOmA - > a Total Current 1092.000DmA 008 STW STROBE,EXCEDER 24V M-C,WALL,WHITE.I5CD 29 57 0000.A 19.7 (0.0162V) Total Current 1092.0000mA w Dial VDr Percent:3.92%) Trial Voltage Dr 0.7988V IW_o 1251.Oo00mA (Total VDr Percent82D%) Total Voltage Drop:1.6735V m U W w (r oP Drop: oP P w ro_m a C Total Current:lzst.txllXhoA U m q Vl (Total vorop Percem:5.96%) Total Voltage Drop:1.21. Z odo# l2 0uO ut H Q CC1 J� Circuit Calculations Panel:PS Card:00 Circuit:SIG4 Circuit Calculations Panel:PS Card:00 Circuit:SIG5 e e m w 5 o CircuitName:SIG4 CimuilName:SI(35 Circuit Type:Notification Terminal Voltage:20AVDC Ampemge:3.0000A Circuit Type:Notification Terminal Voltage:20AV'DC Amperage:30000A =LL w J<w Cable:1614C TWISTED FPLR#16 Cable:16/4C TWISTED FPLR#16 3 TO Q O= Calculations based on Running Total Length. Calculations based on Running Total Length. Design Criteria:Ambienttempmatum:167°F Max.operating voltage drop:15% Design Criteria:Ambienttampmtum:167°F Max operating voltage drop:15% DU2:V) au. Device Part No Appliance Desc Distance Current Voltage Voltage Drop Device Part No Appliance Desc Distance Current Voltage Voltage Drop REVISION RECORD PSN-1000 Panel 20AV PSN-1000 Panel 20.4 DATE/DESCRIPTION 001 GHLFW HORN LOW FREQUENCY,WH 44'-0 99.4000mA 19.8971V (p.5029V) 001 GHLFW HORN LOW FREQUENCY,WH 66-0 99.4000mA 19.6941V (0.5059V) 002 HT-1224W MINI HORN,WH 6.0 22.0000 19.a44 (OD52311) 002 GHLFW HORN LOW FREQUENCY,WH 13'-0 99A00DmA 19.8071 (0.087V) OW HS-24WR HORNISTROBE,2 WIRE,MC,RED,WALL,110CD 21' 186.000OmA 19.6299V (0.2151V) MHT-1224W MINI HORN,WH Y-0 22.000OmA 19,7899V (0.0172V) GHLFW HORN LOW FREQUENCY,WH 11' 99.40DD.A 19.5371V (00926V) 0154 GHLFW HORN LOW FREQUENCY,WH 39-0 99.4000rnA 19.591 (0.1982V) 005 GHLFW HORN LOW FREQUENCY,WH 3'-0 99.40DOmA 19.5148 (OD224V) MHT-1224W MINI HORN,WH 31'-0 22.0000mA 19.4511 (0.1406V) DDSMHT-1224W MINI HORN,WH 56-0 22.00DOmA 19.152V (0.3628V) ON GHLFW HORN LOW FREQUENCY,WH 6499.4000rM 19A295V (0.0216V) SHEET LIST 007, GHLFW HORN LOW FREQUENCY,WH 6-0 99.4000mA 19.1207V (0A313V) 00 MHT-1224W MINI HORN,WH 3T-O 22.0000mA 19.3191 (0.1104V) 008 GHLFW HORN LOW FREQUENCY,WH 37-0 99.4000mA 18.951 (0.169310 008 GHLFW HORN LOW FREQUENCY.WH 9-0 99.4000mA.19.3M4 (0.0157V) FA 0.0 FA DETAILS 009MHT-1224W MINI HORN,WH 49-0 22.0000mA 18.7527V (0.1987V) 009GHLFW HORN LOW FREQUENCY,WH 34'-0 99.4000mA 18.23V (OD734Vj FA 1.0 FIRE ALARM D1 GHLFW HORN LOW FREQUENCY,WH 5-0 99.40DOmA 18.7322 (0.0205V) 01 GHLFW HORN LOW FREQUENCY,WH 14'-0 99.40 A 19.2134 (0.O166V) 011 GHLFW HORN LOW FREQUENCY,WH 42'-0 99.4000mA 18.6007V (0.1315V) O11 MHT-1224W MINI HORN,WH 4'-0 22.00DOmAl 19.2125V (0.0009V) FA 2.0 RISERICALCS 012 GHLFW HORN LOW FREQUENCY,WH V-0 99.4000mA 18.592V (0 1 244'-0 783-8OD0mA 13 013 GHLFW HORN LOW FREQUENCY,WH 26-0 99AODOmA 18.5623V (0.029M Total Current:783.80DOmA 01 MHT-1224W MINI HORN,WH Y-0 22.0000mA 18.5617V (0.0006V) (Total VDrop Percent5.82%) Total Voltage Drop:1.1875V 302'-0 1165.6000mA Total Current:116BS000mA (Total VDrop Percent:9.01%) Total Voltage Drop:1.8383V SCALE:1/8"=1r H H LF LF LF FHj LF FHj LF H LF LF DATE: 10/10/16 A9 Sao h YYK q5 PROJECT NAME LF LF LF LF H LF LF H LF LF H LF V, Z LLI a �a Jr W Z � T loco ; noCo +1x0 nsc0 15co O 15cp Q Z LF LF LF /r( [t Z = O A 5cJR a _j ^ Z A 30CD -D i5c0 11.0 ¢ 110cD b 10 15CD 'Iwo J r = m CD LF LF JD Cj L,F¢ F Y 01,11 0L0 BLDG 11 11000PS 1f000 7-VI t5C0 r5C0 p� LF LF LF � tt � W �� >g e ' 4icrn TS SHEET DESCRIPTION FACP FS a� FS FIRE ALARM IN CALCS/RISER BUILDING 17 ANN SHEET NUMBER FA 2.0 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE PROTECTION INC. 1730 Gibson Road Everett 98204 425-290-90-9800 INSTALLATION NOTES ONDUIT WITH �g L D G. 1 � \ DAVID MOW 1 CONDUIT ROUTES ARE FOR REFERENCE, EXACT 6x THHN#16 1 x RED,1 x BLACK ROUTE TO BE DETERMINED BY THE ELECTRICIAN. 1 x BLUE,1 x WHITE \ BUILDING LINKING MUST BE DONE AS SHOWN FOR 1 xGREEN 1 xYELLOW \ A CLASS A LOOP AND PROJECT PHASING. 120904, \ \ / LEVEL III p 2)JUNCTION BOXES SHOWN ARE TO BE LOCATED IN THE FIRE SPRINKLER RISER ROOM OF EACH / \ \ BLDG 12 �� �� n BUILDING OR ON THE EXTERIOR WALL OF EACH . SPRINKLER RISER ROOM WITH A MINIMUM OF 16 J \\ \\ 4 f BLDG. 11 _ NFPA AWG WIRE AS SHOWN. JUNCTION BOX LOCATIONS 000sos173 SHOWN ARE BASED ON INDIVIDUAL BUILDING \ ROYL CATS ONDUIT WITH ONDUIT WITH Qaoreo> PLANS. i x THHN#16 x THHN#16 1 x RED 1 x BLACK 1 x RED,1 x BLACK ONDUIT WITH w 1 x BLUE,1 x WHITE 2 X THHN#16 L'1►J BLDG. 14 1XBLUE,IXWHITE 3) BUILDING LINKING CONDUITS/WIRING TO BE RUN 1 x GREEN,1 x YELLOW � 1x GREEN,1xYELLOW �' ,J 2xRED,2xBLAC b�JNFPAyyc TO A GUTTER IN THE ELECTRICAL/MECHANICAL `� \ 2x BLUE,2x WHIT E CFPS ROOM IN BUILDING 17 THE SITE FACP IS LOCATED 2x GREEN,2xYELLOW #1473 IN BUILDING 17). \\ \� / I I I I �& 4 ALL FIRE SPRINKLER RISER ROOMS REQUIRE 1 x ONDUIT WITH I I I CITY OF REbMOND DEDICATED 120VAC 20AMP CIRCUIT FOR EACH \ xTHHN#16 ONDUITWITH - C .,abnswo MO o BLDG. 17 xTHHN#16 1 x RED,1 z BLACK o.#16-B-141 w REMOTE POWER SUPPLY. 1 x DEDICATED 120VAC J- �� 1 x BLUE,1 x WHITE 1 x RED,1 x BLACK 20AMP CIRCUIT IS REQUIRED AT THE MAIN FACP IN \, 1 xGREEN,1 xYELLOW 1 x BLUE,1 x WHITE I 1 1 1 cn Community w 1 x GREEN,1 x YELLOW Q BUILDING 17 ( SEE FIRE ALARM DRAWINGS FOR oNDu1TWITH GEC ROOM II I T. d� w BUILDING FIRE ALARM DETAILS). -ONDUIT WITH xTHHN#16 Building �. _��� W x THHN#16 1 x RED,1 x BLACK G —m W N y w,oVm 'wx 1 x RED,1 x BLACK 1 x BLUE,1 x WHITE y � z#H a C 1 x BLUE,1 x WHITE t x GREEN,1 x YELLOW 1X GREEN,IX YELL OW oo� pS2 -BLD . 15� �� BLDG. 9 2 CI_ FilEXTERIOR OUTDOOR RATED JUNCTION BOX `� \ ® J ,,. _ __ N p o m a ONDUIT WITH __�� 1 a W p W a. x THHN#16 \ _ � , W 3o� a ` W 1 x RED,1 x BLACK N >a o a ELEC.GUTTER TO BE LOCATED IN ELEC RM OF BUILDING 17 \ J w La;; z a 1 x BLUE,1 x WHITE ����_ p O w N M w 1 x GREEN,1 x YELLOW \ g L D G. 10 ONDUIT TH REVISION RECORD \ WI x THHN M6 ^ DATE/DESCRIPTION 1 x RED,1 x BLACK {+� ONDUIT WITH 1 x BLUE,1 x WHITE x THHN ON WITH 1 x GREEN,1 x YEL I x LOW BLDG. 8 1 x RED, x BLACK x THHNHHN#16 r ` 1 x BLUE,1 x WHITE 1 x RED,1 x BLACKSHEET LIST r 1 x GREEN,1 x YELLOW 1 x BLUE,1 x WHITE 1 �.nnnnn�I I ' 1 x GREEN,1 x YELLOW Wuu BLDG. 16 N �� ONDUIT WITH o x THHN#16 B WI!® — 's—� f 1 x RED,1 x BLACK N J 1 x GREEN,1'xYETLLOW B _ BLDG. 5 ; J BLDG. 6, J BLDG. 7 a � N — ONDUIT WITH ONDUIT WITH x THHN#16 tu x THHN#16 1 x RED,1 x BLACK (� = 1 x RED,1 x BLACK _ t x BLUE 1 x WHITE \1 1 x BLUE,1 x WHITE 1 x GREEN,1 x YELLOW DATE: 10/10/16 ONDUITXTHH WITH 1 xGREEN 1 xYELLO e J� PROJECT NAME 2 X THHN#16 a 2 x RED,2 x BLACK 2 x BLUE,2 x WHITE 2 x GREEN,2 x YELLOW ~ LU I W Z Q BLDG. 1 ��BLDG. 2 BLDG. 3_ BLDG. 4 Q Z A Boa p� N ONDUIT WITH ONDUIT WITH d x THHN#16 x THHN#16 t x RED,1 x BLACK 1 x RED,1 x BLACK 1 x BLUE,1 x WHITE 1 x BLUE 1 x WHITE 1 x GREEN 1 xYELLOW 1 x GREEN,1 x YELLOW SHEET DESCRIPTION N FIRE ALARM SITE BUILDING 41 LINKING PLAN SITE BLDG LINKING PLAN E SHEET NUMBER 9 1 8 1 7 1 6 1 5 1 4 1 3 1 2 1 1 \ FIRE PROTECTION, INC. PO BOX 12642 MILL CREEK,WA 98082 14251 290-9600 OR 1-800-681-1125 FAX (4251353-4546 October 20,2016 City of ARLINGTON - PLAN REVIEW RE; FIRE ALARM SYSTEM Please find enclosed plans for a FIRE ALARM SYSTEM.The FACP will be located in building 17 ( lower floor of this building is the site community building) , all residential buildings will have their own individual fire alarm annunciator and remote power supply. All residential buildings sprinkler systems will be tied to and monitored by the FACP located in building 17 . The site electricians (Express Electric) are providing building linking conduit/wiring as shown on the included site building linking plan. The SLC and SBUS will be run in a Class A loop as shown. When a Waterflow, Smoke Detector or Pull-station is activated in a residential building, it will annunciate at the annunciator in that specific building and also at the FACP located in building 17 . Residential building occupant notification devices will only activate when an initiating device in that building is triggered, no other building' s occupant notification devices will active. The system has been designed per NFPA 72 , 2013 edition requirements as well as WAC, IBC, IFC 2012 , NEC current and your additional requirements . The building is fully-sprinkled. The system shall monitor by zone activation as well as separate trouble signals . Monitoring shall be provided via UL listed Central Station, The Alarm Center LACEY, WA. Audibility shall be in compliance with NFPA standards . Interior DB shall be 75 DB minimum throughout, (LOW FREQUECNY NOTIFICATION DEVICES TO BE INSTALLED IN RESIDENTAL SLEEPING AREAS . A full service and monitoring agreement is in force for the proper service and maintenance per NFPA requirements . A full pre-test and NFPA form shall be conducted and completed prior to calling the AHJ for acceptance testing. INSTALLATION COMPANY Fire Protection, Inc. 1730 Gibson Rd. Everett, WA 98204 WSCL# FIREPI*021ML UL CERT #608242-002 JOB SITE Park 77 Apartments *Building ll* 20201 77th Ave Ne Arlington , WA APPROVED UL MONITORING COMPANY Alarm Center, Inc. /FPI 4300 3rd Ave. SE Lacey, WA 800-429-0991 UL CERT #902799-02 CONTRACTUAL RESPONSIBLE PARTIES Installation; Monitoring; Service; Testing; Fire Protection, Inc. AMBIENT TEMPERATURES No area with alarm service equipment shall fall below 40 degrees, common areas shall be at 68 degrees per builder AMBIENT NOISE RANGE All areas serviced by the Fire Alarm Control and notification system will be as listed for per UBC listings, per builder. SEQUENCE OF OPERATIONS All Alarm and Trouble conditions shall enunciate at FACP as well as remote notify UL listed Central Station. Zones of alarm shall cause for all notification circuits to activate, send alarm zone to CS, re-dispatch to Fire and dispatch FPI runner service. Trouble and supervisory signals shall transmit to CS which will dispatch FPI runner service to site, (no notification circuits shall activate. ) On site emergency contact personnel shall be notified. Wet Waterflow ALARMS shall be retarded by a period of not more than 45 seconds . Low air shall activate at 25lbs, causing for a supervisory signal . A short on FACP smoke, Waterflow Switches, (wet and dry) and pull station shall cause a alarm. Shorts on PIV, tamper and Hi-low air zones shall cause a Supervisory condition. Opens on any zones shall cause for a trouble signal . Should you have any further questions, please feel free to contact me directly. David Mow VP of Operations/Designer NICET-3 #120904 CITY OF REDMOND D.O.R. #16-B-141 WA JOURNEYMAN LICENSE #MOW**DDE957M6 FACP FOR ALL BUILDINGS LOCATED IN BUILDING 17 @POTTER P 3 00 P/uS Fire Alarm Control Panel Features • 127 expandable to 381 Analog Addressable Points.Any combination of detectors/modules • 5 Amp Power Supply.Expandable to 315 amps • 2 NAC circuits rated at 3 amps maximum,expandable to 188. • 2 Input/Output(1/0)Circuits for system flexibility rated at 1 Amp . �• each _ • Built-in UL Listed IP Communicator • Built-in email event notification and report capability. • Optional Dual Line Digital Alarm Communicator • System wide synchronization of Potter/AMSECO,Gentex, Cooper/Wheelock,and System Sensor signals. • No twisted or shielded wiring required. • Cabinet will accommodate up to 18AH batteries.Panel will charge up to 55AH. • Capable of Class A or Class B wiring configurations • Built-in NFPA 72 compliant smoke detector sensitivity test • Dead-front cabinet design '' �. • 1000 Event History Buffer V` i NYC Fire Dept. Certificate of Approval Potter/Nohmi Protocol Features S735 7165-0328:0195 6156 • Less than 4 second polling time Product includes a 5 year warranty • LED's visible from 360' • Adjustable Smoke Detector Sensitivity • Adjustable Heat Detector Temperature annunciators,intelligent power supplies and other optional modules. • High Temperature Heat Detector as fixed temp The P-Link will support 31 accessories in any combination.The RA- Drift6075 is a 2 x 16 LCD annunciator.The RA-6500 offers a larger 4 x • Compensation 40 line LCD display that allows points and descriptions to be shown • Maintenance Alerts simultaneously.Intelligent remote power supplies repeat the P-Link data • Day/Night Mode and can be mounted 6,500 feet from reach other.P-Link devices such as the RLY-5 relay module,SPG-1000 serial parallel gateway and DRV-50 Description LED driver can be mounted anywhere in the chain of communication with a maximum of 31 of each P-Link devices.A total of two(2) The P300 is a mid-sized analog/addressable fire alarm control panel SLCE-127 Signaling Line Circuit Expanders(loop cards)may be with a total of 381 points.The points may be any combination of smoke installed in the P300 enclosure,in a remote enclosure such as the AE-8 sensors,heat detectors or modules.This panel has a 5 amp power supply or with a PSN-1000E remote intelligent power supply. that is distributed across two Notification Appliance Circuits(NACs) and two Input/Output(1/0)Circuits. The entire system,including the SLC,NACs and P-Link may be converted with a CA-6075 Class A module.The entire system is The NAC circuits are rated at a maximum of 3 Amps each and the 1/0 programmed using a Windows based computer software and requires circuits are rated for a maximum of 1 Amp each.All of the outputs may the use of a software programming software key. be configured for notification or auxiliary power.In addition,each NAC and Output can be programmed for strobe synchronization and utilizes The P300 can communicate to a monitoring station using the on board Quadrasync for strobe synchronization across circuits of various brands. Ethernet connection to an IP communicator or using optional UL listed The 1/0 may also be programmed for a dry contact input such as a water UD-1000 traditional two line alarm communicator.The UD-1000 flow switch or pull station. connects to the main board and has two phone line jacks provided. The IP communicator uses a RJ-45 connection and when connected The cabinet will hold two 12 volt,8 amp/hour batteries or two 12 volt, to the intemet may be programmed to E-mail system status,history 18 amp/hour batteries.The system when fully loaded will charge 55 reports,reminders and the configuration file.The panel may be updated amp/hour batteries.Anything larger than 18 amp/hour will require an remotely using the LTD-1000.If the Ethernet connection is needed external battery cabinet the SSU-00050. remotely,the FCB-1000 fire communication bridge may be installed to The panel has the Potter P-Link connection for expansion with remote allow the Ethernet connection to be installed in a rack. Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • wwpottersignal.com P'�O�IUsJ w. #8830035-REV A PAGE 1 OF 4 08/12 (E) POTT ER P 3 00 Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 381 addressable devices or modules in any combination.The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PSA Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PSHA Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135'Fahrenheit heat detector FHA Analog Fixed Temperature Heat Detector that is selectable from 135'F to 185°F RHA Analog Rate or Rise Heat Detector that has a fixed temperature selection from 135°F and 174°F and also will alarm if the temperature increase 12-15°F in one minute DDA Addressable Duct Smoke Detector AB-6 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors AB-4 4"round base that may be mounted to an electrical box and wired for connection to the above sensors AIB Isolater base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop ARB Addressable Relay Base that contains two relays controlled by the SLC.One relay is rated at 8 amps at 240 VAC/30VDC and the other is rated at 2 amps 240 VAC/30 VDC ASB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. Modules Device Description MCM Miniature Contact Module provides a small foot print contact module for mounting inside an enclosure. APS-SA Single Action Addressable Pull Station APS-DA Dual Action Addressable Pull Station SCM-4 Single Contact Module is a standard contact module with an LED that mounts into a 4"square electrical box. DCM-4 Dual Contact Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. TRM-4 Twin Relay Module provides two form C relays that simultaneously active when the module is triggered by the control panel. Each relay is rated for 2 amps at 24VDC or 0.5 amps at 125VAC. MOM-4 Monitored Output Module is a power switching module that monitors the circuit that is controlled by the control panel. CIZM-4 Conventional Input Zone Module is used to connect conventional smoke detectors to the system that receive their power from the module.This module is like a conventional zone on the SLC. SCI Short Circuit Isolater interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • www.pottersignal.com P"�O�A'SP v #8830035-REV A PAGE 2 OF 4 08/12 (E) POTT ER P 3 00 Fire Alarm Control Panel SLC Features RA-6075—2 x 16 LCD annunciator with a key pad in a locked metal enclosure. The Potter/Nohmi protocol is a digital protocol with a proven design for reliability and noise immunity.The system does not require special RA-6500—4 x 40 LCD annunciator with a key pad in a locked metal cable or conductors for connection of the Signaling Line Circuit as enclosure long as the cable is compliant with NFPA 70 and NFPA 72.The system LED-16—16 LED annunciator with common indicators in a locked allows for Class A or Class B installations as well as"T-Taps." metal enclosure The total polling time for the protocol is about four(4)seconds which PSN-1000(E)—10 amp,remote intelligent power supply with 6 NACs, allows two polling cycles in the ANSUUL 864 requirement of alarms 2 I/Os and a P-Link repeater reporting in less than ten seconds.Each loop is capable of 127 points with the exception of the P100 and P200. CA-6075—Class A convertor that converts the SLC,NACs and P-Link connection Sensor Features UD-1000—UL listed,Dual line telephone alarm communicator The sensors through the fire alarm control panel provide a real DRV-50—LED driver expander,used to connect up to 50 LEDs in a time status as to the condition of the system.The smoke detector graphic display sensitivity,heat detector temperature level and drift compensation FCB-1000—Fire communication bridge,provides remote mounting of as all programmable options.The system also allows for a day/night the Ethernet connection mode where the panel automatically adjusts the sensitivity depending on the time of day.To assist in the reduction of false alarms,the smoke FIB-1000—Fiber interface module,used to extend P-Link to multi- detectors also have a maintenance warning that sends a trouble signal mode fiber(2 required) when a detector is dirty to the point that it can no longer maintain the RLy--5—Relay module,provides 5 form C relay contacts rated at 3.0 programmed sensitivity. amps 24VDC/125AC User Interface SPG-1000—Serial parallel gateway,allows for the connection to a serial or parallel printer The fire alarm control panel has a 4 x 40 LCD display to provide information to the system status.The keypad has navigation keys The FIB-1000,FCB-1000 and the SPG-1000 maybe installed in the t stacker bracket or ordered with the optional rack mount enclosure.o allow manipulation of the Menu on board the panel.The panel is shipped standard with the following LEDs: AE-8—Eight card expansion cabinet • AC Power—Green AE-14—Fourteen card expansion cabinet • Alarm—Red Ethernet/I.P. Connection • Earth Fault—Amber The P300 is shipped standard with an Ethernet connection.This • Supervisory-Amber connection is the programming port and may be connected to a building • Silenced-Amber Wide Area Network(WAN)or Local Area Network(LAN).Once connected to the Internet,the panel may be selectively programmed to • Trouble-Amber e-mail alarm conditions,trouble conditions,supervisory conditions,test, The common buttons include a Silence,Reset,Acknowledge and Drill. Event History and detector status.An e-mail may be sent to the panel All of the buttons are accessible once the locked door is opened. and the panel will e-mail the event history,detector status,configuration file or server status to an authorized E-mail account.In addition, P-Link reminders may be set to send an e-mail for service,testing or other The P300 has a proprietary communication protocol that communicates conditions. through a RS-485 connection to field devices.Up to thirty-one In addition,the Ethernet connection is UL listed as an IP communicator. (31)devices may be connected to a single P-Link connection.The The IP communicator is listed to report to the UL listed Sur-Gard III P-Link includes the communication terminals and regulated 24 VDC IP receiver.The IP communicator replaces the traditional less reliable connection for the field devices.The field devices may be any of the alarm communicator transmitter that utilized telephone lines.The IP following: communicator is an active method of connection and communication to SLCE-127-Analog/Addressable loop expansion module(maximum of 2 the monitoring station. per P300) Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • wwpottersignal.com P'��PlusZ* w. #8830035-REV A PAGE 3 OF 4 08/12 (E) POTT ER P 3 00 Fire Alarm Control Panel Specifications 18.91" 17.60" Electrical Specs:AC Mains O O TOP o 3.0 Amps @ 120 VAC 50/60 HZ 2.0 Amps @ 240 VAC 50/60 HZ 4.41" 3.75" DEPTH Battery p 0 130 mA Standby 220mA Alarm b • 5 Amps power for NACs,I/O and P-Link • 3 Amps per NAC,regulated a • 1 Amp per I/O circuit,regulated �e c7 O • Battery Charger range 8-55 Ah • Battery Charger voltage 27.3 VDC • P-Link maximum current of 1 Amp • Panel holds(2)8AH or(2) 18AH batteries LEFT SIDE RIGHT SIDE Cabinet • 16 gauge cold rolled steel with removable BOTTOM ` locked door • Dimensions—18 15/16"W x 27 5/16"H x 4 7/16"D • Dead front to cover all electronics • Lexan viewing window Temperature and Humidity This fire alarm control is listed and approved for operation in an indoor application with temperature range fluctuations of 32'to 120'(0°C to 49°C) with a maximum humidity of 93%non-condensing.The ideal temperature is 77°F +/- 10°F(25°C+/-5°C). Standards The P300 series fire alarm control panel complies with the following standards and codes. • NFPA 13,70 and 72 • ANSI/UL 864 0 Local(L),Remote Station(RS),Central Station(CS),Propriety(PPU),Auxiliary(AUX) 0 Type of Service:Automatic(A),Manual(M),Water flow(WF)Sprinkler Supervisory(SS) 0 Type of Signaling:Digital Alarm Communicator(DAC),March Time(March),Non Coded(NC),Reverse Polarity(Rev Pol),Other Technologies(OT) • IBC 2000,2003,2006,2009,2012 Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • wwpottersignal.com P'h�T PUF'J w. #8830035-REV A PAGE 4 OF 4 08/12 POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Features Standby Current 20 mA Alarm Current 25 mA Operating Temperature 0°C-49°C(32°F-120°F) 10%-93% @ 30°C(86°F)non-condensing 0 © humidity Maximum Wire Length 6500 FT ® © Maximum Annunciators 31 - Dimensions(WxHxD) 8"x 6-1/4"x 1-5/8"(Cabinet) Wire Gauge 14 AWG-22 AWG Display 2 lines x 16 characters Product includes 5 year warranty U� LISTED S2930 7165-0328:0195 Description Installation The RA-6075 is a LCD remote annunciator for the PFC-6075 and The RA-6075 is connected to the PFC-6075 using a four wire RS-485 PFC-6030 addressable fire control panel.The RA-6075 communicates connection.The connection is power limited and supervised.Up to using a RS-485 connection to the main panel providing common thirty-one(31)RA-6075 LCD annunciators can be connected using indication of Alarms,Supervisory,Trouble and other system status and Class B or Class A wiring.Class A wiring requires an optional Class A control functions. Expander. The RA-6075 features a 32 character, 16x2 LCD display with LED's for Power,Alarm,Supervisory,Trouble,and Silenced conditions. , It can be mounted on a single gang electrical box or a four square electrical box.The annunciator is enclosed in a sheet metal enclosure Instal!inac!cord!anc!e with compatib7fir,alarm panel. and has a Potter lock securing the keypad. Figure 1:RA-6075 Class B Wiring Example Figure 2:RA-6075 Class A Wiring Example To the next annunciator 4CA-60775 + m + a P-LINK + a + A B + + + + Panel + + + + + + Panel + + Connection Remote -LIN + Annunciator Connection + Remote -LIN< Annunciator m Q m Oa O a + Q O Remote O Remote Annunciator Annunciator Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5406077-REV B-1 PAGE 1 OF 2 9/11 (E) POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Address Settings The RA-6075 address is set by dip switch S 1 located on the back of the RA-6075.The address must be set in the range of 1 to 31 to be recognized by the control panel. Figure 3:RA-6075 Class A(back panel view) O ❑ 0 0 OWWWW .-9. O 0 © A on ® 9 ® + Al O o Dip Switch Settings Refer to the table below for dip switch settings per Annunciator Address. Annunciator Dip Switch Settings Annunciator Dip Switch Settings Address SW-1 SW-2 SW-3 SW-4 SW-5 Address SW-1 SW-2 SW-3 SW-4 SW-5 1 On Off Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Off On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Off On On On 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On PRINTED IN USA MFG.#5406077-REV 13-1 PAGE 2 OF 2 9/11 CPOTTER PSN-1000(E) The Symbol of Protection POWER EXPANDER Features 10 Amp Power Supply • 3 Amps,regulated per NAC • 6 NACs Class B or 3 NACs Class A • 2 dry contact inputs • Fully programmable and monitored through control panel _ I Isolated P-Link repeater connection,Class A or B • Up to 31 power supplies per control panel with system wide sync • Quadrasync feature synchronizes strobes from Potter/AMSECO, Gentex,Cooper-Wheelock and System Sensor. ®RPOTTFR PSN-1000 Compatible with all Potter PFC-6000 series fire alarm control panels. Ines➢pool of Frowpon P.—Supply --. Electrical Specs • 120/240 VAC Input at 50/60 HZ • 5.1 Amps/3.0 Amps max draw • Standby Current 60 mA • Alarm Current 200 mA U` S2930 7165-0328: 0195 Product includes a 5 year warranty Description The PSN-1000 series is a UL listed intelligent 10 amp notification power supply and P-Link(RS-485)repeater.The power supply connects to the P-Link bus from the control panel and is operated and supervised from the panel.The power supply may be installed 6,500 feet from the control panel.The PSN-1000 then repeats the P-Link communication for another 6,500 feet. The power supply has six(6)Class B or three(3)Class A power outputs.Each output is regulated and power limited with a 3 Amp maximum rating.In addition,the PSN-1000 has two(2)programmable dry contact inputs.The dry contact inputs are Class B,supervised inputs. The power supply operates on either 120 or 220 VAC power and has a regulated 24 VDC output.In addition,the panel can charge up to 55 AH batteries and will house 18 AH batteries.The cabinet is constructed out of 18 gauge cold rolled steel with a durable red powder coat finish.A standard Potter key lock is provided for securing the door.Electrical conduit knockouts are provided on the sides and top providing installers with multiple options for installing conduits and providing proper power separations. The PSN-1000 is a self contained intelligent power supply/P-Link repeater complete with cabinet.The PSN-1000E is the intelligent power supply/P-Link repeater with additional cabinet room for the exclusive Stacker Bracket for SLCE-127 loop expanders.Both cabinets include space for 18 AH batteries. The power supplies are programmed and controlled through the main control panel P-Link bus.The panel displays any troubles or off normal conditions of the power supply and the events are stored in the panel history buffer. Each output can be independently configured to provide one of four synchronization patterns,constant power,ANSI temporal Code 3 or Door Holder power.The panel can be configured to synchronize Potter/AMSECO®,Gentex®,Cooper Wheelock®and System Sensor®. Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830032-REV B PAGE 1 OF 2 09/14 (E) POTTER PSN-1000(E) The Symbol of Protection POWER EXPANDER 18.91" 17.60" 4 0 0 TOP w 0 4.41" 3.75" DEPTH O O 0 0 0 N O O O 0 LEFT SIDE RIGHT SIDE BOTTOM Dimensional drawings showing the cabinet in all three planes. Knock out locations. PRINTED IN USA MFG.#8830032-REV B PAGE 2 OF 2 09/14 4, �� SYSTEM � SENSOR t 41, Photoelectric Smoke Detectors System Sensor i3-series smoke detectors represent significant advancement in conventional detection. 3 The i3 family is founded on three principles:installation TM ease,intelligence,and instant inspection. Features Installation ease.The i3 line redefines installation ease with its •Plug-in detector line,mounting base included plug-in design.This allows an installer to pre-wire bases(included with heads).The large wire entry port and in-line terminals provide Large wire entry port ample room for neatly routing the wiring inside the base.The base •In-line terminals with SEMS screws accommodates a variety of back box mounting methods as well as •Mounts to octagonal and single-gang back boxes,4-square back direct mounting with drywall anchors.To complete the installation,i3 boxes,or direct to ceiling heads plug into the base with a simple Stop-Drop'N Lock'action. •Stop-Drop'N Lock attachment to base Intelligence.i3 detectors offer a number of intelligent features •Removable detector cover and chamber to simplify testing and maintenance.Drift compensation and •Built-in remote maintenance signaling smoothing algorithms are standard with the i3 line to minimize nuisance alarms.2-wire i3 detectors can generate a remote LED- indicated maintenance and smoothing algorithms indicated maintenance signal when connected to the 2W-MOD2 •Simplified sensitivity measurement loop test/maintenance module or a panel equipped with the i3 •Wide-angle,dual-color LED indication protocol.The SENS-RDR,a wireless device,displays the sensitivityof i3 Loop testing via EZ Walk feature detectors in terms of percent-per-foot obscuration. • •Built-in test switch Instant inspection.The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition:normal standby,out-of-sensitivity,alarm,or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol,the EZ Walk loop test feature is available on 2-wire P detectors.This feature verifies the initiating loop wiring by providing LED status indication at each detector. T istin s M MEA MSFMTPROVED approved approved cC I,us I W6 7272-1653:152 290-01-_ 3C93? (-L3)Smoke Detector Specifications Smoke detector shall be a System Sensor i3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The detector shall be a photoelectric type(Model 2W-B,4W-B)or a combination photoelectric/thermal(Model 2WT-B,4WT-B)with thermal sensor rated at 1357 (57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal,single-gang,and 4-inch square back boxes with a plaster ring,or direct mount to the ceiling using drywall anchors.Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual- color LED indication that blinks to indicate power up,normal standby,out of sensitivity,alarm,and freeze trouble(Model 2WT-B,4WT-B)conditions.When used in conjunction with the 2W-MOD2 module,2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24V non-polarized Minimum: 8.5 V Maximum:35 V Maximum Ripple Voltage 30%peak to peak of applied voltage Standby Current 2-wire:50 NA maximum average;4-wire:50 NA maximum average Maximum Alarm Current 2-wire:130 mA limited by control panel;4-wire:20 mA @12 V,23 mA @ 24 V Peak Standby Current 2-wire:100 uA;4-wire:n/a Alarm Contact Ratings 2-wire:n/a;4-wire:0.5 A @ 30 V AC/DC Physical Specifications Dimensions(including base) 5.3 inches(127 mm)diameter;2.0 inches(51 mm)height Weight 6.3 oz(178 g) Operating Temperature Range 2W-B and 4W-B:32°F to 1207(0°C to 49°C);2WT-B and 4WT-B:327 to 1007(0°C to 37.8°C) Operating Humidity Range 0 to 95%RH non-condensing Thermal Sensor 1357(57.2°C)fixed Freeze Trouble 2WT-B and 4WT-B only:417(5°C) Sensitivity 2.50/o/ft nominal Input Terminals 14 to 22 AWG Mounting 3'/2-inch octagonal back box 4-inch octagonal back box Single-gang back box flinch square back box with a plaster ring Direct mount to ceiling LED Modes Power-Up Sequence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal(standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max.limited by control panel 2WT-B Yes 2-wire 130 mA max.limited by control panel 4W-B No 4-wire 20 mA @ 12 V,23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V,23 mA @ 24 V Accessories 2W-MOD2 2-wire loop test/maintenance module RT Removal/replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket,6.6 inch(16.76 cm)diameter f_ SY TE� m2cha system Sensor. �/ 3825 Ohio Avenue•St.Charles, L 60174 Product specifications subjec[to009 System Sensotice.Vsit rystemsensoccom for SENSOR Phone:800-SENSOR2•Fax:630-377-6495 urrentproductinformat5-03180i7-6/09 latest version okhis data sheet. A06-0318-007.6/09•#2169 PULL STATION SERIES (E) POTTER DIE-CAST METAL The Symbol of Protection MANUAL PULL STATIONS • UL and cUL Listed,FM Approved,CSFM Listed,MEA ' Approved,ADA Compliant • Single or Dual Action • Terminal connectors PULL UOWN Big . 10 Amp Snap Action Switch Gold plated SPST contacts Optional auxiliary contacts Mounts on standard single gangbox • Surface backboxes available • High-gloss red enamel finish • Glass breakrod DUs FMo �5 Made in the U.S.A. LISTED Description Engineering Specifications The Potter Pull Station Series offers a complete line of die-cast pull The contractor shall furnish and install the Potter series of pull stations for a variety of applications focusing mainly on fire alarm stations as indicated.The pull station shall be die cast construction systems.The pull stations are available in single or dual action with a"T"type pull handle that is ADA compliant.Single action pull models.All of the pull stations have a 10-amp snap action switch and stations shall be a P32-lT.Dual action pull stations shall be the Potter a dedicated terminal block for the ease of wire connections.All of P32-1T-LP.Any manual pull station installed in an outdoor or wet the metal is completely coated to inhibit corrosion and provide for a location shall be a RMS-IT--WP weather proof unit.The contact shall uniform and quality finish. be a single pole,single throw switch rated at 1 amp 30V DC/125V The standard models have a hex key reset,however a key reset is also AC.The device shall have a terminal block for ease of wiring.Once available.The models are available with shallow and deep surface activated,the pull station shall be reset by opening the front cover. mount back boxes and as a weatherproof version. Opening of the cover in a normal state shall initiate an alarm. Operation Specifications The Potter single action series of pull stations operate by pulling Switch Rating: 1 Amp @ 30 VDC the white operating handle straight down and the handle will lock 10 Amps @ 125 VAC into place.The dual action stations require the lifting of the front Pull Station Dimensions: 4-3/4"H x 3-1/4"W x 7/8"D cover and then pulling the white operating handle straight down.The Color:Red with raised white letters,white pull bar with raised red letters stations are reset by opening the front and placing the handle in the For special application manual stations see bulletin#8910014. normal position. For explosion proof manual stations see bulletin#8880014. Ordering Information Type Model Number Stock Number Contact Type P32-1T 1000447 SPST RMS-2T 1000477 DPST Single Action RMS-6T 1000478 DPDT RMS-1 T-KL 1000451 SPST RMS-IT-KO 1000450 SPST,key operated,no pull Weather Proof RMS-1 T-WP 1000401 Dual Action P32-1 T-LP 1000476 SPST Weather Proof Dual Action RMS-IT-WP-LP 1000403 Accessories Notes Dual Action RMS-LP 1000480 Converts single action to dual action Back Box P32-BB 1000444 Surface mount back box Back Box P32-DBB 1000445 Deep surface mount back box Glass Rods RMS-GB 1000470 Replacement glass rods(10 per pkg) Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-1211•Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8900097-REV L PAGE 1 OF 1 9/10 P POTT ERS A ka-"Wl' DCM-4 ® The Symbol of Protection Dual Contact Module Features • Single module with dual contact monitoring inputs • Two(2)Class B or one(1)Class A monitoring inputs • SLC Class A(Style 6,7)&Class B(Style4) • Mounts in a standard 4"or double gang box s- S. • Wiring terminals accessible when mounted in box ©E�►•■-�+•�.+o • All wiring terminals accept 22 to 14 AWG li wsiar • Product includes a 5 year warranty ee _.. NOTE: This addressable module does not support 2-wire smoke f zz1,1" zi ;, ci detectors. Stock Number: 1430822 LISTED �zw� S2930 7165-0328:0196 Application Technical Specifications The DCM-4 is compatible with Potter's PFC-6000 series and PFC- Operating Voltage 22.0-24.OV 8500 addressable fire alarm control panels.The DCM-4 is an interface Max SLC Standby Current 325 µA module used to monitor dry contact devices such as sprinkler water Aux Power Required 1mA flow,valve tamper switches,or conventional pull stations.The module is capable of monitoring two separate Class B or one Class A circuits. Max Wiring Resistance of IDC I 100 S2 Max Wiring Cpacitance of IDC 1 µF EOL Resistor 5.lK S2 Description Operating Tempurature Range 32 to 120°F(0 to 49°C) The DCM-4 uses two (2) consecutive SLC loop addresses when Operating Humidity Range 0 to 93%(non-condensing) monitoring two(2)Class B circuits or one(1)address when monitoring 127 units(Class A)or 63 units a single class A(Style D)circuit.The module mounts on either a 4" Max no.of Module Per Loop (Class B) square or double gang box.The module is capable of monitoring two (2)separate class B circuits making it ideal for monitoring sprinkler Dimensions 4.17"(106mm)L X 4.17" waterflow and valve tamper switches when they are located in the same (106mm)W X 1.14"(29mm)D proximity.The DCM-4 includes one red LED to indicate the modules Standard 4"Square or status.In normal condition,the LED flashes when the device is being Mounting Options Double Gang Box polled by the control panel.When a contact is activated,the LED will Shipping Weight 0.6 lbs light continuously and in case of an open circuit,the LED will turn off. Potter Electric Signal Company,LLC • St.Louis,MO • Tech Support: 866-956-0988/Customer Service: 866-572-3005 • www.pottersignal.com 8830008-REV B • 7/14 PAGE 1 OF 2 P POTT ERS OHM/® DCM-4 ® The Symbol of Protection Dual Contact Module Setting the Address Each addressable module, smoke sensor,heat detector and combination sensor/detector must be assigned an address prior to installing the device.The address is set using either the hand held device programmer or the addressing feature on the PFC 6000/PFC 8500 Series control panels.When the DCM- 4 is used to monitor two individual Class B circuits a single device address is assigned,with the second address number assigned automatically by the module assuming the next consecutive address.For example,if the first address number is assigned as"2",the second address number will automatically be assigned as SLC device address"3". Before connecting a device to the SLC loop,take the following precautions to prevent potential damage to the panel or device verify the following: 1.Power to the device is removed 2.Field wiring is correctly installed. 3.Field wiring has no open or short circuits. Installation Using Compatible Electrical Box O e ° ° o e Wiring Diagrams DCM-4 With One Class ACircuit NOl FROM FACP OR C 1 PREVIOUS MODULE S+ ZI S- NO2 TO THE NEXT MODULE F 1 C2 SELECT STYLE D 0000 LED Q Z2 NOTE:END-OF-LINE RESISTOR IS NOT REQUIRED DCM-4 With Two Class B Circuits NOl FROM FACP OR C 1 PREVIOUS MODULE S+ Zl "OHM1/2W S- NO2 TO THE NEXT MODULE ppH1pC2 �000 LED O Z2 SELECT STYLE B 5.1K OHM 1/2W Potter Electric Signal Company,LLC St. Louis,MO • Tech Support: 866-956-0988/Customer Service: 866-572-3005 www.pottersignal.com :so 9001:2008 1 DESIGNING,MANUFACTURING, 8 DISTRIBUTING QUALITY SYSTEMS 8830008-REV B • 7/14 PAGE 2 OF 2 GENTEX CORPORATION Low Frequency Audible Signal GHLF Applications 24 V D C The GHLF is a high quality, low profile, low frequency audible appliance that offers a dependable audible alarm with a low current draw. The GHLF is ideal for any S E R I E S occupancy that requires notification appliances. The GHLF horn offers a 520 Hz square wave,temporal 3 tone. A jumper selection is available for normal or loud decibel tone. A temporal 4 pattern is available when used with the Gentex GTSM Synchronization Control Module. The GHLF is shipped with a standard 4" metal mounting plate which incorporates the popular Super-Slide°feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The GHLF also features the patented Checkmate°- Instant Voltage Verification feature which allows the installer to check the voltage drop and match it to the blueprint. The GHLF horn is listed to ANSI/UL 464 and CAN/ULC S525, is listed for use with fire Product Listings protective systems and is warranted for three years from date of purchase. SIGNALING Standard Features � • Nominal voltage 24 VDC • Input terminals accept 12 to 18 AWG C&uS :U0= O Unit Dimensions:6-1/8"(15.55 cm)high x • Produces a 520Hz square wave,temporal 3 LISTED 5-1/2"(13.97 cm)wide x 1-5/8"(4.13 cm) tone deep • Jumper selection for normal or loud dBA • ANSI/UL 464 Listed • Super-Slide®Bracket-Ease of Supervision • Temporal 4 pattern available when used • CAN/ULC S525 Listed Testing with Gentex GTSM Synchronization Module • CSFM: Pending • Checkmate°-Instant Voltage Verification • Temporal 4 520Hz measured per Product Compliance • Synchronize horn with Gentex GTSM ANSI/UL 2075 • NFPA 72 Synchronization Control Module • Tamperproof re-entrant style grill and • IBC/IFC/IRC • Prewire entire system,install mounting locking screw(optional use) • Quality Management System bracket,then install signals • Faceplate available in red or off-white is certified to:ISO 9001:2008 Model Number Part Number Nominal Voltage Model Designations: �i •j ' = R=Red Faceplate MEMBER •� GHLFW 904-0530-002 24 VDC W=White Faceplate ASSEMBLED IN GHLFR 904-0531-002 24 VDC All units are plain(no lettering) THE USA Horn Decibel Levels: 24VDC Nominal Horn Horn Current Ratings Reverberant Room Current Ratings(mA) Over Input Voltage Range of 16-33V(mA) Minimum SPL Minimum SPL 24VDC 24VDC 24VFWR 24VFWR Regulated Regulated Regulated Regulated at 10Ft.Per at 10Ft.Per Operating Operating Operating Operating 24VDC Max. 24VDC Max. 24VFWR Max. 24VFWR Max. Horn Mode Operating Operating Operating Operating ANSI/UL 464 ANSI/UL 464 Current Current Current Current Current Current Current Current (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) Temporal 3 520 Hz I 77.8 dBA 1 79.8 dBA 72.1 mA 120.1 mA 104.6 mA 158.4 mA 99.4 mA 155.8 mA 152.1 mA 213.5 mA Temporal 4 520 Hz*1 81.5 dBA 1 83.4 dBA 75.9 mA 116.0 mA 108.1 mA 182.0 mA 100.1 mA 157.2 mA 163.1 mA 235.2 mA O Temporal 4 520 Hz measured per ANSI/UL 2075 NOTES: • Operating temperature:32 to 120 F(0 to 49 C).The GHLF is not listed for outdoor use. • For nominal and peak current across ANSUUL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. RMS current ratings are per ANSUUL average RMS method. ANSUUL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units). For unfiltered FWR ratings,see installation manual. GHLF 24 VDC S E R I E NOTES: UL Listed • THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR Control Signal Signal PULSING SIGNALING CIRCUITS Panel S+ s- s- H+ H- S+ s+ s- H+ H- • THE FOUR PULSE TEMPORAL PATTERN(TEMPORAL 4)CAN ONLY BE Supervised 0 0 0 0 OBTAINED ON THIS PRODUCT WHEN USED IN CONJUNCTION WITH Signal Circuit THE GENTEX GTSM SYNCHRONIZATION MODULE 1 + ENO LINE • SEE GTSM CONTROL MODULE MANUAL(550-0632,MANUAL ISSUE RESISTOR DATE(02-01-15)FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. S GTSM MANUAL CAN BE OBTAINED AT WWW.GENTEX.COM/FIRE OR CALL GENTEX CORPORATION AT 1-800-436-8391. DOIMIW x o Lt LOCKING 0 0 o SCREW 0 " (optional) Cho H+ logo RED WIRES �- H! Q BLACK WIRES 6- � O o H- U a O o 00 NORMAL-LOUD o c �`f/ DECIBEL JUMPER. 0 0 FOR LOUD DECIBEL CEED INSTALL JUMPER. SLIDE ONTO BRACK Gentex Checkmate® Gentex Super-Slide® LOCKING Instant Voltage Verification: Mounting Bracket: SCREW It is often necessary to confirm the voltage drop Allows the installer to pre wire the system, (optional) along a line of devices.The access holes are test for system supervision,remove the provided in the back of the terminal block to signal head until occupancy,switch out allow the voltage to be measured directly without Gentex signals without changing removing the device.Typically this would be done mounting brackets and has locking edge at the end of the line to confirm design criteria. connector for snap-in-place installation. Most measurements will be taken using the S+ and S-locations although access is provided to other locations. NOTICE:CARE SHOULD BE TAKEN TO NOT qM SHORT THE TEST PROBES. Architect & Engineering Specifications The alarm horns shall be Gentex model GHLF.The appliance shall be listed with Underwriters Laboratories(ANSI/UL)for use with fire protective signaling systems (ANSI/UL 464) and with CAN/ULC S525 with intended use in fire alarm systems. The GHLF will produce a peak sound output of 88.3 dBA as measured in an anechoic chamber. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. 24 units per carton Important Notice: GHLF-01 GENTEX These materials have been prepared Gentex Corporation Gentex')for informational purposes only,are O necessarily summary,and are not purported to serve as legall advice and should not used s such. Gentex makes no representations and warranties,express or implied,that these materials are complete and CORPORATION accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to Fire Protection Products Group•www.gentex.com particular fact patterns.Each persons activities can differently affect the obligations that exist under applicable laws,regulations or rules.Therefore,these materials should be used only for informational 10985 Chicago Drive •Zeeland, Michigan 49464 purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. CPOTTER MHT 1224 SERIES The Symbol of Protection LOW CURRENT MINI-HORN Features • Single unit is capable of 12 or 24 VDC determined by the input I voltage - Y I I IEI I Unit Dimensions:4.48"(11.38cm)high x 2.84"(7.21 cm)wide x F I 0.5"(1.27 cm)deep Jumper selectable temporal 3 or continuous tone I I I i Horn frequency is 3100Hz I I I I Terminal blocks(12 AWG to 18 AWG) • Low current consumption • Variety of mounting options for new construction and retrofit E applications • Synchronize using the AVSM Series control module • ANSUUL 464 listed for fire protective service • Textured finish high impact plastic faceplate,available in red or off-white Ordering Information Operating Temperature(indoor use only) Stock Number Model Number Model Designations 320 to 120OF(00 to 49°C) 4890001 MHT-1224R R=Red facepalte 4890002 MHT-1224W W=Off-White faceplate 4890003 MHT-1224PR P=Plain 4890004 MHT-1224PW SIGNALING U� LISTED Product includes a 5 year warranty Description The MHT-1224 Series mini-horn is a high quality remote The MHT-1224 can be used on the same sync circuit(AVSM audible signaling appliance that offers dependable remote annunciation. Series Control Module)as other Potter signals.The MHT-1224 Series The MHT-1224 is ideal for applications where a dependable audible is ANSUUL 464 listed for use with fire protective systems. alarm signal is required in applications such as hotels, dormitories, and apartments.The MHT-1224 is listed for use with both filtered and unfiltered power and a jumper is provided to select either temporal 3 or continuous tone. Architect&Engineering Specifactions The alarm horns shall be Potter model MHT-1224.The appliance shall be listed with Underwriters Laboratories(ANSUUL)for use with fire protective signaling systems(ANSUUL 464)and produce a peak sound output of 90dBA or greater as measured in an anechoic chamber.The appliance shall be of solid-state construction and be polarized to operate from 8-33VDC with a 22mA current drain at 24VDC.The appliance shall be provided with 2 terminals,and mount to a variety of single-gang back boxes. Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830065-REV A PAGE 1 OF 2 06/13 (E) POTTER MHT 1224 SERIES ® The Symbol of Protection LOW CURRENT MINI-HORN Mini-Horn Wiring UL MHT-1221 MHT-I I 1151I I; WIRING DIAGRAM FOR DUAL CLASS B CIRCUITS WITH A SINGLE AVS"CONTROL MODULE CONTROI PANtI + — + SYNCODULAl10N F A C P MUrAIIE 1MT•t7H ANT•t!N h• lu M SIJI>f kV F.I 'NU IT I INr SIGnn•. tE51STDR CIRI'I ' EOI R SIGNAL CIRCUITS wr-Tti+ rrtfar 1_4Cf< B:-ALK Et,-ACK BLAf,R a., Wiring Diagram EOLR Mini-Horn Wiring Use a screwdriver to break the jumper for a continuous tone. O DO NOT BREAK m JUMPER IF TEMPORAL 3 TONE IS NEEDED. Horn Mode Minimum SPL at 10 Minimum SPL at 10 Reverberant dBA at 10 In Anechoic MHT-1224 Current Ratings feet per ANSI/UL feet per ANSFUL feet per ANSI/UL 464 Room dBA @ I 24 VDC 22 mA 464 at 24 VDC 464 at 12 VDC 10 ft. 24 VDC UL Max 18 mA Temporal 3 81 dBA 78 dBA 78-86 90 12 VDC UL Max 13 mA Continuous 86 dBA 1 83 dBA 78-86 90 NOTES:The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. 1 RMS current ratings are per ANSFUL average RMS method.ANSFUL max current is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units)(8-17 VDC for 12 VDC units).For strobes,the ANSFUL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units)(8 VDC for 12 VDC units).For audibles,the max current is usually at the maximum listed voltage.For unfiltered FAIR ratings,see installation manual. PRINTED IN USA MFG.#8830065-REV A PAGE 2 OF 2 06/13 Effective June 2014 Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Description ••�• �.�•�.••� � Eaton's Cooper Notification business has developed the Wheelock . •.•:•;...;•.•;••. Exceder LED Low Frequency Sounder Strobes and Sounders to ;••: meet the new National Fire Protection Association (NFPA) low •:•:;:•:•••• •' frequency sounder requirements for sleeping rooms -NFPA 72 for fire alarm and NFPA 720 for Carbon Monoxide (CO)alarm. In a single ••' device,the Exceder LED Low Frequency Sounders can provide alarm ••.•;:•:;�:�;:•:'•;: signals for dual applications-T3 (Fire)and T4(CO)tones. It is the � first product in the industry to be listed to the audibility requirements �'•:;;;;;:�'• X;�����:;�.� of UL 2034 and UL 2075 for CO applications. H ,., fib :;:;:::,•:•;••;; The Exceder LED Low Frequency Sounder Strobes and Sounders feature multiple 520 Hz modes of operation:T3 (fire),T4(CO), •: �••�••��••�.�.•.�. Continuous,T3/T4 Sync Control. The 520 tone is generated within the appliance itself. When '.•;:;:;:;;;:�;:•.;• the selector switch is set forT3 orT4,the sound pattern is also •.•.••...••.•; generated within the appliance. When the selection switch is set to continuous,the product is listed for coded operations. TheT3,T4 pattern or other pattern must be generated by the FACP according to ....... •.�•..•. •� the alarm condition sensed by the panel (fire or CO alarm). . . . . . When the device is set toT3/T4, the appliance can switch fromT3 to '�' '•"'�'•'•'�' T4 based upon the condition sensed by the FACP and passed to the %•% Wheelock DSM module. ••••.••••.••• 0 0 •. Like the entire Wheelock Exceder LED product line, the Low �.�.•�•.;�;.����; Frequency Sounder Strobes will utilize Light Emitting Diode (LED) N ••;.;•:;;;:•; as the light source—a breakthrough optical design, resulting in best- in-class efficiency that enables material and system cost savings, allowing for a greater number of appliances on the notification appliance circuit and fewer power supplies. All LLFHS strobe models include a 110 candela setting. Providing a sleek aesthetic appearance, the Exceder LLFHS and LLFHN models feature one of the industry's smallest footprints and a sleek, modern, low-profile design. Installers will benefit from its comprehensive feature list, multiple 520 Hz modes of operation, lowest current draw, no tools needed for setting changes, and convenient mounting options.These products are suitable for indoor wall-mount applications.The Sounder and Sounder Strobe models are for 24V operation. Exceder LED Sounder Strobes may be synchronized when used in conjunction with the DSM Sync Modules,Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol.Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. The Exceder LED Low Frequency Sounders and Sounder Strobes are UL Listed for indoor use under Standard 1971 and 464 and ULC under S525 and S526. The appliances are Restriction of Hazardous Substances (RoHS)compliant and contain no mercury or other F AIkT* N hazardous substances. Powering Business Worldwide Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Effective May 2014 Features Drawings • Meets dual low frequency sounder codes for sleeping rooms in a 4.56 1.29 single device • NFPA 72 for fire alarm • NFPA 720 for CO alarm "'eeeeeaeo • 4 Settings in 1 device 000000000000000 • T3 (fire) o°omoo°o°00000°0°0°°0 o°o mo 000000000000 oo°om • T4(CO) °000°o°o°000°o°o°o°o0 m°m°o°Oo°Oo°O°o°o°o°o°m°u • Continuous (Coded) moeo°o°o°o°o°o°0000°oo°° 6. 10 • T3/T4 °o om o0 00°0°00000 o°°a o o eoo °o0 000 o • Energy efficient °ooaooeoo°0o0000o00° eeeee • Patented LED technology provides industry's lowest current O000000es°o draw • Low-profile design • Smallest footprint with sleek, modern aesthetics • --- t 11 • 110 candela setting I.40-I • Easy-to-install • Finger slide switches—No tools needed for setting changes • Built-in level adjustment feature and snap-on grille cover Figure 1.Wall Low Frequency Sounder Strobe • IN/OUT screw terminals using#12 to#18 AWG wires • Mounting Options include Exceder LSPKBB _ backboxes and 4" square backboxes o°000°0000°o 0o0o0aes°°a°o°0 • Strobe synchronization components o o ¢ 00000 0 0 0 Y p o o°o°OpOo°o°o°0°a°o o • Meet synchronizing standards with Wheelock's DSM Sync mom 00 oaop0°o°o°o°°o m Modules or PS-6/8 Power Supplies ®000000°°000°°o$00000 pP m0m0o0o00000000o0o00° m o 0 0 0 0 0 0 0 0 0 m o0 o°o00 o°o°o°o°o°o°o° • Compliance o°m°000°000°0°00000 • UL 2034, UL 2075, UL 1971, UL 464, ULC S525, ULC S526 °o°m o°°o°Op°o°00000°®oo° °aooee000000oee0000 • California State Fire Marshal (CSFM) o o eeeee o o o°aoeeeeeepe0o • ADA/NFPA/ANSI/OSHA 000 • RoHS Note: All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION Figure 2.Wall Low Frequency Sounder INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT.VISIT WWW.000PERNOTIFICATION.COM OR CONTACT Table 1. Horn Strobe Current Draw COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. ULIULC Max Current a FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR Exceder LED Sounder Strobes 24VDC WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, 16-33 Volts WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR Model Horn Setting 110 cd DEATH TO YOU AND/OR OTHERS. LLFHS Continuous 0.292 Code 3 0.292 Code 4 0.292 General Notes Code 3/Code 4 0.292 • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range:' Note that NFPA-72 specifies a Table 2. Horn Only Current Draw flash rate of 1 to 2 flashes per second and ADA Guidelines specify ULIULC Max Current a a flash rate of 1 to 3 flashes per second. Exceder LED Sounders 24VDC • All candela ratings represent minimum effective Strobe intensity Model Horn Settings 16.0-33.0 based on UL 1971. LLFHN Continuous 0.113 Code 3 0.113 Code 4 0.113 Code 3/Code 4 0.113 2 EATON www.eaton.com Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Effective May 2014 Table 3. Sound Output (SPL)- UL Table 4. Sound Output (SPL)- ULC LLFHS/LLFHN 24V LLFHS/LLFHN Reverberant dBA per UL 464 dBA per ULC S525-07c Description 16.OV 24.OV 33.OV Description 16.OV 24.0V 33.OV Continuous 80 80 80 Continuous 80 80 80 Code 3 76 76 76 Code 3 80 80 80 Code 4 b 85 85 85 Code 4 80 80 80 Code 3/Code 4 76 76 76 Code 3/Code 4 80 80 80 Table 5. Specification &Ordering Information Sync w/DSM or Model Strobe Candela Red White Lettering Wheelock Power Supplies Sounder Strobes LLFHSR 110 X FIRE X LLFHSW 110 X FIRE X LLFHSR-AL 110 X ALERT X LLFHSW-AL 110 X ALERT X LLFHSR-CO 110 X CO X LLFHSW-CO 110 X CO X LLFHSR-N 110 X No Lettering X LLFHSW-N 110 X No Lettering X Sounders LLFHNR-AL X ALERT X LLFHNW-AL X ALERT X LLFHNR-CO X CO X LLFHNW-CO X CO X LLFHNR-N X No Lettering X LLFHNW-N X No Lettering X Accessories Description Red White LSPKBB-R 0756 Exceder LED Backbox X LSPKBB-W 0757 Exceder LED Backbox X Table 6. Specifications Physical Material Red or white textured UV stabilized,colored impregnated engineered plastic. Exceeds 94V-0 UL flammabil- ity rating Weight 1.10 lbs. Lens Light Emitting Diode(LED)in a rugged Lexan lens Dimensions 6.1"H x 4.56"W x 1.4" D Operating Temperature Indoor:33.8°F to 120.2°F WC to 49°C)and maximum humidity of 85% Mounting&Wire Connections Mounting(indoor only) Wall-mount applications only. Exceder LSPKBB backboxes or to 4" square backboxes Wire Connections #12 through#18 AWG Power&General Operating voltage 24 VDC: 16-33 VDC Strobe Output Rating UL 1971: 110 candela output Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies, using Wheelock patented sync protocol Temporal Audible Pattern Continuous, Code 3, Code 4 or Code 3/Code 4 Sync Control. The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. The Code 4 temporal pattern (four cycles of 100 milliseconds 10 percent"on"and 100 milliseconds 10 percent"off;'followed by 5 seconds 10 percent"off) is specified by NFPA 720. a RMS current ratings are per UL maximum RMS method.UL max current rating is the maximum RMS current within the listed voltage range(16-33A. For strobes the UL max current is usually at the minimum listed voltage. For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation instructions. b Code 4 setting rated per UL 2075, UL 2034. c For dwelling use only. 3 EATON www.eaton.com Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes & Sounders Effective May 2014 Architects and Engineers Specifications backboxes and to standard 4" square backboxes. The sounder and The low frequency sounders and sounder strobes appliances shall sounder strobe shall incorporate a mounting plate with a snap-on be Wheelock® ExcederTm LED Series LLFHN Sounder and LLFHS grille cover and shall mount to standard electrical hardware requiring Sounder Strobe for wall-mount applications with a low-profile design no additional trimplate or adapter. Removal of an appliance shall or approved equals.The sounders shall be UL Listed under UL 464 result in a supervision fault condition by the Fire Alarm Control Panel (FACP). All notification appliances shall be backwards compatible. for Fire Protective Service and to the requirements of UL 2034/UL 2075 for CO applications and ULC S525. Sounders equipped with The Series LLFHN wall model shall have a low profile measuring strobes shall be listed under UL 1971 for Emergency Devices for the 6.1" H x 4.56"W x 1.29" D.The Series LLFHS wall model shall have Hearing-Impaired and ULC S526.The Series shall be Restriction of a low profile measuring 6.1" H x 4.56"W x 1.4" D. Finish shall be Hazardous Substances (RoHS) compliant and contain no mercury or red or white. Special lettering,ALERT, CO and No lettering, shall be other hazardous substances. In addition, the sounder strobes shall available. meet the requirements of FCC Part 15.All inputs shall be compatible When synchronization is required, the appliance shall be with standard reverse polarity supervision of circuit wiring by a Fire compatible with Wheelock's DSM Sync Modules, PS 6/8 Power Alarm Control Panel (FACP)with the ability to operate from 16 to 33 Supplies,or other manufacturer's panels with built-in Wheelock VDC. Patented Sync Protocol.The strobes shall not drift out of synchro- nization at any time during operation. If the sync protocol fails to The Series LLFHS Sounder Strobe shall produce a flash rate of one operate,the strobe shall revert to a non-synchronized flash-rate and (1)flash per second over the Regulated Voltage Range and shall still maintain (1)flash per second over its Regulated Voltage Range. incorporate a Light Emitting Diode (LED)as the light source with a The appliance shall also be designed so that the audible signal may rugged Lexan®lens.The Series shall be of low current design.The be silenced while maintaining strobe activation when used with strobe intensity shall have a 110 candela for wall mount applications. Wheelock patented sync protocol. The audible shall have a minimum of four(4) 520 Hz modes of operation:T3 (fire),T4(CO), Continuous,T3/T4 Sync Control. UL 1971, UL 464, ULC S525, ULC S526, CSFM, FCC, RoHS The Series LLFHS and LLFHN shall be designed for indoor surface or flush mounting. Mounting options shall include LED speaker Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. 111=11A WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eaton.com Cooper Notification 273 Branchport Ave. Long Branch,NJ 07740 CooperN otif i cation.com ©2014 Eaton All Rights Reserved Eaton is a registered trademark. - Printed in USA Publication No.TDO01009EN All other trademarks are property Powering Business Worldwide June 2014 of their respective owners. pp- 000 COOPER Notification EJCED _ Strobe, Horn Strobe, and Horn Notification Appliances - Ceiling Wall Description: The Wheelock°Exceder`Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. - Save up to 14% cost of installation** The Wheelock°ExcederTm Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single U Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. C40 Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock° ExcederTm Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before ' the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a 90,95,99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings *** it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra Universal Mounting Base *** secure installation, while the ceiling models provide a captivated Ceiling and Wall screw to prevent the screw from falling during installation. UU Mounts to 5 Backbox Types Compliance Environmentally Friendly -UL 1971, UL 464, ULC, CSFM, FM Low Current Draw -ADA/NFPA/ANSI/OSHA -RoHS Compatibility and Requirements -Synchronize using the Wheelock°Sync Modules or panels with built-in Wheelock°Patented Sync Protocol -Compatible with UL"Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage" range Compared to competitive models ""Patented Compared to previous models NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 1207(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 1971). Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = FewerPower • • Strobe Ratings per UL Standard 1971 UL Max Current* 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &Anechoic at 24 VDC AnechoicUL Max Current*at •• •:A 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 10.125 AnechoicUL Max Current*at •:A 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122 AnechoicUL Max Current*at •• •:A 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL Anechoic Model Regulated Voltage 99 dB 95 dB 90 dB Range VDC HN 16-33.0 0.064 0.044 0.022 HNC 16-33.0 0.084 0.044 0.022 HN 8.0-17.5 0.047 0.026 0.017 HNC 8.0-17.5 0.047 0.026 0.017 *UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Sync w/ Model Strobe DSM or 12/24 VDC* Mounting Candela Wheelock Power Options Supplies HSR 15/1575/30/75/95/110/135/185 X X UMB** ' HSW 15/1575/30/75/95/110/135/185 X X UMB** H S RC 15/30/60/75/95/115/150/177 X X UMB** ' HSWC 15/30/60/75/95/115/150/177 X X UMB** STIR 1511575/30/75/95/110/135/185 X X UMB** STW 15/1575/30/75/95/110/135/185 X X UMB** STRC _ 15/30/60/75/95/115/150/177 X X UMB** STWC 15/30/60/75/95/115/150/177 X X UMB** HNR X X UMB** HNW X X UMB** HNRC .. X X UMB** HNWC 117 X X UMB** *12 VDC models feature 15&15/75 settings **UMB=Universal Mounting Base Model Legend HN = Horn A =Agent Lettering - ST = Strobe (Strobes only) 4r HS = Horn Strobe AL=Alert Lettering C = Ceiling Mount (Strobes only) W =White N = No Lettering R = Red (Strobes only) Example 1: STRC=Strobe,Red,Ceiling Mount / Example 2: HSR=Horn Strobe, Red,Wall Mount / Example 3: HSW=Horn Strobe,White,Wall Mount ' r Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering ■ p g Example. Example: HSWC • 1 *UMB Contact Cover NOTE: Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock° ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. Where Multi-Candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68"x 1.50" D. When synchronization is required,the appliance shall be compatible with Wheelock®'s DSM Sync Modules,Wheelock®Power Supplies or other manufacturer's panels with built-in Wheelock®Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1) flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock®synchronization protocol. Wall Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS Ceiling Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS W WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder- Spec Sheet 5/13 NJ Location 273 Branchport Ave. Long Branch, NJ 07740 800-631-2148 www.coopernotification.com Cooper Notification is Wheelock' MEDC SAFEPATH® WAVES { COOPER Notification S-24 & HS-24 CPOTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Features • 24VDC units have field selectable candela options of 15,30,60, 75,& 110 • Super-Slide®Bracket-Ease of Supervision Testing • Checkmate®-Instant Voltage Verification • Synchronize strobe and/or horn with AVSM Control Module • Prewire entire system,install mounting bracket,then install - signals f, _ — Documented lower installation and operating costs Input terminals accept 12 to 18 AWG Switch selection for high or low dBA Switch for chime,whoop,mechanical and 2400Hz tone Tamperproof re-entrant style grill R I I I I I I I I Switch for continuous or temporal 3 tone(not available on whoop tone) • Surface mount with the AVBB(Surface Mount Back Box) • Silence audible while visual appliance will remain flashing(for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature • 320F to 120OF(0°C to 49°C).The HS and S Series are not listed for outdoor use. Unit Dimensions • 5"(12.7 cm)high x 4.5"(11.43 cm)wide x 2.5"(6.35 cm)deep U� LISTED S3247 Description The S-24/HS-24 Series is a low profile strobe and horn/strobe This Series is shipped with a standard 4" metal mounting combination that offers dependable audible and visual alarms and the plate which incorporates the popular Super-Slide®feature that allows absolute lowest current available. the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without The S-24 & HS-24 Series 24VDC offers tamperproof field any screws showing. selectable candela options of 15,30,60,75,and 110 candela. The S-24/HS-24 also features the patented Checkmate® - The Strobe and Horn/Strobe offers a continuous or sync Instant Voltage Verification feature which allows the installer to check temporal three in 2400Hz and mechanical tone, a chime and whoop the voltage drop draw and match it to the blueprint. tone.All tones are easy for the professional to change in the field by the use of switches. The S-24&HS-24 Series appliances are ANSI/UL 464 and ANSI/TJL 1971, listed for use with fire protective systems and are The S-24 & HS-24 Series has a minimal operating current warranted for three years from date of purchase. and has a minimum flash rate of 1 Hz regardless of input voltage. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 1 OF 4 06/13 S-24 & HS-24 (E) POTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Tone Switch Locations TONE SWITCH POSITION 3 4 5 ®o Mechanical Temporal 3 ON ON ON �® 1, Mechanical-Continuous OFF ON ON 2400Hz-Temporal 3 ON OFF ON ® S+ 2400Hz-Continuous OFF OFF ON S- Chime-Temporal 3 ON ON OFF -® H+ � Chime-Continuous I OFF ON OFF Whoop I ON OFF OFF Whoop OFF OFF OFF NOTE: • Switch Positions 1 and 2 in the OFF position to select isolated horn and strobe power inputs • Switch Position 6 ON=HIGH dBA • Switch Position 6 OFF=LOW dBA Super Slide®Mounting Bracket Checkmate®Instant Allows the installer to pre-wire Voltage Verification the system,test for system It is often necessary to confirm the voltage supervision,remove the signal drop along a line of devices.The access head until occupancy,switch holes are provided in the back of the out signals without terminal block to allow the voltage to be changing mounting brackets measured directly without removing the and has locking edge connector device.Typically,this would be done at the for snap-in-place installation. end of line to confirm design criteria.Most - measurements will be taken using the S+ and S-locations althouhg access is provided to other locations. NOTE:Care should be taken to not short the test probes. Candela selection slider switch. Depress center and slide switch to desire brightness level. r- T Break off pin and insert l S into hole at the bottom of .a the selector to lock candela setting.Signal must be removed from bracket and pin pushed forward from backside out of hole to change candela. To remove bezel,grip both sides of bezel and pull in a download and outward motion. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 2 OF 4 06/13 S-24 & HS-24 CF POTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES S-24 24 VDC Selectable Candela,Low Profile Evacuation Strobe Model Part Nominal Candela Number Number Voltage (ANSI/UL 1971) S-24WR I 4890010 24 VDC 15,30,60,75, 110 S-24WW 4890011 24 VDC 15,30,60,75, 110 HS-24 24 VDC Selectable Candela,Low Profile Evacuation Horn/Strobe Model Part Nominal Candela Reverberant dBA at In Anechoic Room Number Number Voltage (ANSFUL 1971) 10 ft.,per ANSI/UL 464 dBA at 10 ft. HS-24WR 4890030 24 VDC 15,30,60,75, 110 62-82 100 HS-24WW 4890031 24 VDC 15,30,60,75, 110 62-82 100 S-24&HS-24 Product Strobe Current Ratings(mA) 24 VDC(16-33 Volts) Model Designations: W=Wall Mount Candela 24 VDC UL Maxi R=Red Faceplate W=White Faceplate 15 cd 30 mA 42 mA 30 cd 35 mA 58 mA All units are available in plain(no lettering). Plain units are non-returnable. 60 cd 66 mA 97 mA 75 cd 80 mA 116 mA ALERT bezel available for order. 110 cd 103 mA 161 mA ALERT bezel available for order. S-24&HS-24 Product Horn Current Ratings Horn Decibel Levels Horn Current Ratings Minimum SPL Minimum SPL Regulated 24 VDC Horn Mode at 10 ft.,per at 10 ft.,per Max.Operating @ ANSI/UL 464 ANSI/UL 464 High Setting(mA) (HIGH) (LOW) Temp 3 2400 Hz 78 dBA 71*dBA 28 mA Temp 3 Mechanical 76 dBA 70*dBA 25 mA Temp 3 Chime 70*dBA 66*dBA 15 mA Continuous 2400 Hz 81 dBA 74*dBA 28 mA Continuous Mechanical 80 dBA 72*dBA 25 mA Continuous Chime 70*dBA 66*dBA 15 mA Whoop 82 dBA 69*dBA 56 mA NOTES: • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified]) power,see installation manual. • Potter does nto recommend usign a coded or pulsing signaling circuit with any of our strobe products. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use.Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 3 OF 4 06/13 S-24 & HS-24 (E) POTTER SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Architect&Engineering Specifications The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 horn/strobe Series or approved equal and shall be listed by Underwriters Laboratories,Inc.per ANSI/UL 1971 and/or ANSI/UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM)and the California State Fire Marshal(CSFM). The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage.The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. Conventional Wiring Diagrams for Emergency Notification Evacuation Series UL Listed UL Listed Control Control Panel signal signal Panel Signal Signal g+ S+ S- H+ H- S+ S+ S- H+ H- s+ S+ S- H+ H- S+ S+ S- H+ H. Supervised Supervised 0 B 0 B Signal Circuit Signal Circuit \ + \ + END LINE END OF LINE RESISTOR RESISTOR \ + 7D END OF LINE RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage.Strobes should not be used on coded or pulsing signaling circuits.However,use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe,horn,and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION,REFERENCE AVSM CONTROL MODULE DATA SHEET(8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 4 OF 4 06/13 GENTEX CORPORATION GOE OUTDOOR ENCLOSURE Applications A C C E S S O R I E S The Gentex GOE Outdoor Enclosure is ANSI/UL 464 listed for use in indoor and P A G E outdoor applications when used with the Gentex GEH Series horn and WGE Series strobe and horn/strobe. Standard Features • ANSI/UL 464 listed • Back box with side mount tabs • Made of clear Lexan°- providing maximum visibility and reliability • Unit Dimensions: 5.75" (14.61 cm) high x 4.75" (12.10 cm)wide x l •�,''- 4.18" (10.62 cm) deep • 3/4"conduit knockouts l'llll� • Reinforcement steel hardware --- R • Outdoor resistant gasket • Available in red or off-white GOE-R GOE-W GOELP OUTDOOR ENCLOSURE Applications The Gentex GOELP Low Profile Outdoor Enclosure that creates a surface mount look, is ANSI/UL 464 listed for use in indoor and outdoor applications when used with the Gentex GEH Series horn and WGE Series strobe and horn/strobe. Standard Features • ANSI/UL 464 listed • Back box with outdoor resistant seal for mounting to wall GOELP GOE • Made of clear Lexan°- providing maximum visibility and reliability • Unit Dimensions: 5.75" (14.61 cm) high x 4.75" (12.10 cm)wide x 3.25" (8.255 �+- cm) deep • 3/4"conduit knockouts • Reinforcement steel hardware • Outdoor resistant gasket • Available in red or off-white GOE AND GOELP NOTES: • Product does not meet ANSI/UL 1971 light distribution requirements • To allow for drainage, the seal on the bottom edge is not water tight GOELP-R GOELP-W GBLP OUTDOOR BACK BOX Applications f ►'� The Gentex GBLP Outdoor Back Box is constructed of durable plastic is ANSI/UL _ •, 464 listed for use indoor and outdoor applications when used with the WSSPK Series speaker and speaker/strobe. Gl Standard Features o' v • ANSI/UL 464 listed ,.. • 1/2"conduit knockouts with metal washer reinforcements i • Wiremold knockouts for 500, 700 Series and pendulum mount • Unit Dimensions: 6.20" (15.75 cm) square x 2.04" (5.18 cm) deep • Reinforcement steel hardware GBLP-R GBLP-W • Outdoor resistant gasket • Available in red or off-white ACCESSORIES PAGE GSB SURFACE BACK BOX Applications The Gentex GSB Surface Back Box is constructed of durable plastic and is fully compatible with the Commander' (GE)and Commander'(GE3) Series horns, strobes and horn/strobes. Standard Features • ANSI/UL listed for indoor use • 1/2" conduit knockouts with metal washer reinforcement • Wiremold knockouts for 500 and 700 Series • Unit Dimensions: 5.57" (14.15 cm) high x 4.55" (11.56 cm) wide x 1.47" (3.73 cm) deep • Screw heads hidden GSB-R • Available in red or off-white ALERT & AGENT BEZELS Applications The Gentex ALERT and AGENT bezels are constructed of durable plastic and is q fully compatible with the Commander (GE)and Commander' (GE3) Series horns, l strobes and horn/strobes. E Standard Features R T • Easy to install I • ALERT or AGENT wording on both sides of bezel • Available in red or off-white ALERT-W AGENT-R GCSB CEILING SURFACE BACK BOX Applications The Gentex GCSB Surface Back Box is constructed of durable plastic and is fully compatible with the Commander (GC) Series strobes and horn/strobes. Standard Features • ANSI/UL listed for indoor use • 1/2"conduit knockouts with metal washer reinforcement • Wiremold knockouts for 500, 700 Series and pendulum mount • Unit Dimensions: 6.2" (15.75 cm) round x 1.67" (4.24 cm) deep • Screw heads hidden • Available in red or off-white GCSB-R GCSB-W Important Notice: 551-0031-02 G E N T E X These materials have been prepared Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and arere not purported to servee as legal advice and should not be used as such. Gentex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws, CORPORATION regulations and rules. The materials do not address all legal considerations as there is inevitable Fire Protection Products Group•www.gentex.com uncertainty regarding interpretation of laws,regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the 10985 Chicago Drive •Zeeland, Michigan 49464 obligations that exist under applicable laws,regulations or rules. Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. 9 8 7 6 5 4 3 2 1 HRE PROTECTION INC- 1730 Gibson Road Everett,WA.g8204 DEVICE INSTALLATION REQUIREMENTSPARK 77 PARTMENTS VICINITY MAP 425-290-9600 DAVID MOW mxc wear CEIUNG MOUNTED 3' YIN osruvx NOT PERMITTED SMOKE/HEAT+ iF&I HFRE DETECTOR + CJUNG 1' T �' /ll% 120904, AUoIO/MSUAL L x• a VISUAL DEVCES 4- NOT LEVEL III PERM,TIED ERMHE 'r HERE HERE BUILDING'�'I _:;9�44 PERMITTED, HERE McDowr NFPA D FRCP ME P= - 000805173 B nclrlEa ncBtn IE,y rao�a tuvnsEr x $ex �aw " FIRE ALARM _ u'wix ey-p ROY L CATS sas•x tAT'R �, HSD zs B —� � ; - QPO7ECr P�■^■ �`,, ■■9 n•AR W., WArr WAN, FIRE tMANUAL i ...,. (° �AirMiN N.0-st PHDNE PULL Aerospace a JACK STATION nufacwnngTech° 6 NFPA yC d� ti ARLI N GTO N, WA CFPS 46'MAX r FINISHED iL00R CITY OF REDMOND DAVID MOW - ...sea INSTALLATION NOTES Fire Alarm Symbol Legend 204TH STREET N.E. o 1) Prior to calling for inspection,the installer shall provide SYMBOL DESCRIPTION PART NUMBER MFG QTY BACKBOX REQUIREMENTS MOUNTING REQIXREMENTS lu 2 documentation to the local AHJ stating that the system has been � w C I^^' LCD REMOTE ANNUNCIATOR RA-6075 POTTER 1 v H n installed,tested,evaluated and confirmed to be in accordance with all governing codes and the approved plans.The Fire Alarm System PS INTELLIGENT 10 AMP REMOTE POWER EXPANDER PSN-10W POTTER , AREA OF WORK U Re Z y N C installer shall complete an NFPA72 Record of Completion(NFPA72 Ts SPRINKLER TAMPER BY OTHERS BY OTHERS Z 01 U = 01 10.18.2.1.1). The completed Record of Completion shall be provided to BUILDING 11 0 0 DUAL INPUT CONTACT MODULE DCM-0 POTTER 1 BBOX-0.Standard backbox..4 - f C- -t7� the AHJ inspector at the time of inspection(NFPA72 10.18.2.1.2.4). ® BLDG.13 o z'o w«a ❑F PULL STATION SINGLE ACTION P31-IT POTTER 1 BBOX-2.Standard backbox.2 4W AFF _ — — ——— Q O tY G J^ 2) Instructions for the operating,testing and maintenance of the ? o�to W a t o>.W o (xS) SMOKE,PHOTO,2-WIRE 2W-B SYSSENSOR , BBOX-2,Standard backbox,2 I >W O a N system,along with record drawings otherwise referred to as �� = I m rc W W$ ("as-built")and equipment specifications shall be provided at an LF LED,LF,HORN/STROBE,MC,WH LLFHSW WHEELOCK 9 BBOX4,Standard backbox,4 ffi AFF BLDG.12' BLDG.11 j 3 o $ o approved location(NFPA72 10.18.2.3). _W W m tr a FUI wD STROBE,EXCEDER 24V M-C,WALL,WHITE STW WHEELOCK 7 BBOX-2,Standard backbox,2 82"AFF BLDG.14 _ _ I U N 4r� W `-------J REVISION RECORD 3) All systems and devices shall be installed and tested per the = �' manufactures listing and the authority having jurisdiction(NFPA72 wco HORNSTROBE,EXCEDER 24V.M-C.WALL,WHITE HEW WHEELOCK 4 BBOX-2,Standard backbox.2 82"AFF - DATE/DESCRIPTION 10.14.2.1).Label all device locations containing EOL resistors. c BLDG. 17 �_ I LF HORN LOW FREQUENCY,WH GHLFW GENTEX 16 BBOX4,Standard backbox,4 82"AFF /� w 4)FRCP&all Remote Power Supplies REQUIRE a DEDICATED 120VAC ca / Building m BLDG-15 �BLDG.9 a 20amp circuit.A notice placed in the FRCP shall direct personnel to the MINI HORN,WH MHT-1224W POTTER 8 BBOX-2.Standard backbox.2 62-AFF BLDG.10 — location of the electrical panel that is supplying DEDICATED power to wP 'Z, --r = SHEET LIST „edb HORN/STROBE,2WIRE,M-C,RED,WALL HS-24WR POTTER , BBOX.2,Standard backbox,2 82"AFF —����� N the system(NFPA72,Section 10.5.5.1). The DEDICATED circuit breaker I `� R FA 0.0 FA DETAILS that serves the fire alarms stem shall be Labeled and Secured against Fa WATERFLOW SWTICH BY OTHERS BvorHERs I BLDG.8 y g BLDG.16 I _ D FA 1.0 FIRE ALARM tampering with a RED breaker lockout(NFPA72,Section 10.5.5.2). _ FgCP FRCP LOCATED IN BUILDING 17 P3o0 POTTER E _ r'z rBLDG.6 BLDG.?_ I � -� FA 2.0 RI$ER/CALC$ OUTDOOR HIS WEATHERPROOF ENCLOSURE GOELP POTTER I L i(= -BLDG.5 I , - B 5)This property will have one FACP located in the Community Building. ' Each residential building will have a Remote Power Supply and a - --�-- - Remote Fire Alarm Annunciator connected to the main FACP in the Community Building.The FACP will monitor each buildings fire sprinkler system via SLC,the occupant notification devices in each the building will only activated when a fire alarm device from that BLDG.2 f BLDG.3; BLDG.4 speck building(waterflow,smoke detector,pull-station) is activated. __ J L. ter Lr� 6) Wall mounted strobes shall be placed 80"minimum to 9611 maximum above floor level.(NFPA72 18.5.4.1&2).Wall mounted strobes shall be SITE PHASING PLAN sized in accordance with(NFPA72 Table 18.5.4.3.1(a).Ceiling mounted SYSTEM OUTPUTS strobes shall be placed and sized in accordance with(NFPA72 Table Required Fire Safety Control 18.5.4.3.1(b). cormol Unit Annuncia on ti c /// 0; SCALE: 1/8"=1' c DATE: 10/10/16 7) When MORE than two notification appliances are visible at the same o o c.c . time whether they are in the same room or adjacent space within the h o'Coy; PROJECT NAME field of view,the flash of those strobes shall be synchronized(NFPA72, �° `y s° y Section 18.5.4.3.2(3)&(4). z yc°"°��2 CIRCUIT LINE TYPE Circuit Legend w a O o s.o 8) Pull stations shall be placed between 42 and 48 inches above floor a« o a ; Z Z Q level.Devices shall be red in color(ICC A117.1 309&NFPA 72 17.14.5) F yo`` o Q = A Abbreviation Type Name w 9 Outdoor strobes required fora approaching Emergency Vehicles to d Qe�> `y F y� ---- u U #18/4 FPLR SLC-SIGNAL LINE CRKT H Q Z q o pp g g y a e a as A #1614 FPLR TWISTED PAIR NAC-NOTIFICATION CRKT O Z A be located in the upper 25/o of the building(at a serviceable height), Q Q 4 y o+3 y ry Q — = O and to be clearly visible from the emergency vehicle approach path. , , q e e;g; e B #18/4 FPLR SBUS d 0 n U A Z 10)Fire Alarm circuits to be installed/securedherminated in accordance SYSTEM INPUTS A B C D E F G H O J h CD —C) J with NEC,NFPA 72,IFC and Local AHJ requirements&standards. 1 Manual Fire Alarm Boxes ♦ ♦ ♦ ♦♦ 1 Y C4 Q -L Smoke Detectors ♦ ♦ ♦ ♦♦ 2 N 11)The means of communication to the central stations for the fire 8 Waterflow ♦ ♦ ♦♦♦♦ s Fire Alarm Device Numbering d 4 alarm system is to be provided by a Potter UD-1000 DACT as per plan. Sprinkler Control Valve ♦ ♦ 4 6 Fire Alarm AC Power Failure ♦ 7 . ♦ 6 (SLC)ADDRESSABLE DEVICES NOTIFICATION DEVICES System requires 2 x POTS telephone lines,1 of these lines is required 6 Fire Alarm System Low Battery ♦ ♦ 6 to be DEDICATED to the FACP.The FACP is located in building 17. 7 Open Circuit ♦ ♦ . 7 CIRCUIT CIRCUIT 8 Ground Fault ♦ - ♦ g DEVICEADDRESS DEVICEY SHEET DESCRIPTION 12)All building linking conduit&wiring to be provided/installed by 9 Notification Appliance Circuit Short ♦ ♦ 6 CANDELA 5Lc•uRM /L^1 FIRE ALARM 10 Remote Power Supply Trouble ♦ ♦ 10 `�V.7// ' DETAILS others. ABC0E FOH I J OPERATIONAL MATRIX SMOKE DETECTOR SHOWN AS EXAMPLE C[ SHEET NUMBER FA 0.0 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE PROTECTION INC. 1730 Gibson Road Everett,WA.98204 425-290-9600 DAVID MOW e m J LEVEL III D - UNIT B-11 1 n UNIT B-10 �--- UNIT B-9 sly I j- I UNIT B42 p H NFPA 614 FPLR SIG S 000805173 PS IN RISER ROOM t I I J I H ---- O_ ROY L CATS I A i I� i �QPOTECTjO �1 l i I O I = I A _- - i- --- #1473 IJ 1 -J STAIR/ j STAIRI _— sirso�, A I •.,,� ENTRY -L.I I ENTRY sicsaro I 7 DN I�_ `- —- DN —Ia. CITY OFREDMOND DAVIVIDo MOW R sacs ooz na#16-B-141co O W H m U q W 2 N z F 6 3RD FLOOR - f O J H V J 3OCOo ZOW p 9YWFW OmzFO Y WDu.mY m�W W6K 3 H W 0 R'0: 614 THHN'BUILDING THE FAC 0 U 2:H-+a u: (LOCATED IN BUILDING 17 REVISION RECORD 61 FPLR SIG 3 — 6/2 THHN SLC TO THE FAC O PS IN RISER ROOM - I OCATED IN BUILDING t7 DATE I DESCRIPTION 17614 FPLR SIG 2 O PS IN RISER ROOM /— --- F ZNhW1 �r Z S,zN _ _ — SHEET LIST - I -. _ FA 0.0 FA DETAILS sici•a,aam — � UNIT B-7 _ - - FA 1.0 FIRE ALARM k-� UNIT B-2 UNIT BJ UNIT B-1 I ' Type A sicaaas Type A =� Ts Fs UNIT B-6 srr% FA 2.0 RISER/CALCS I—D --- ZN]•001 2Ni•Wt I B Type A I I °oc° I UNIT B 4 UNIT B-5 sct•u o F� sr----- ----- UNIT 68 7 ,, sxo-------- -- O' I SIG— �s°r°oo. I Type A '. - F _.� r I 1614 PLR SIG 4 I SIG-3AL J I -- \- A I O PS IN RISER ROOM ---- -- r------ - _�� I I -- __ T I TI I sr*001 I 1614 FPLR SIG( I A - I( I -�iJrx° I I�tss cc3r cos IrJv�s_oo: sIlI�x�°�III •— I I ,-rI -------I --- �° nI�- -T -rntaa-w° 'f�rsc -- _- Gz STAIR! If STAIRr:-� cv � SCALE 1/8"=1' L6TAIw l SAIw ENTRY ENTRY ENTRY r ENTRY -- r -- UP - I DATE: 10/10/16 uP_ EaSN.° --i-- -�,� I rc•aae PI RJR, sr� PROJECT NAME A y J _ ` dl I li \ /-I - i s •ma s' I .. sir..ms T ttOC° 11aC° -- w wt. Z � 5 G3 005 � _ --- w � t9QZ — —�-- = O A � a. CL a UP q UP Q Jn � _ r Z 1ST FLOOR -N 2ND FLOOR N ^ m CD 11714 � N Q a SHEET DESCRIPTION FIRE ALARM SHEET NUMBER FA 1 .0 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 �'�� Aw FIRE PROTECTION INC. 1730 Gibson Road Everett,WA.98204 Battery Calculations for Panel:PS BUILDING 11 425-290-9600 Part No:PSN-1000-INTELLIGENT 10AMP REMOTE POWER EXPANDER DAVID MOW Part No. Qty. Description Standby Total Standby. Alarm Total Alarm ('N Panel Equipment PSN-1000_MB 1 10AMP POWER EXPANDER MB 75.000OmA 75.000OmA 215.000Omh 215.0000mATotal Panel Stby 75.000OmA TotalPanel Ale 215. �' Peripheral Devices 2W-B 1 SMOKE,PHOTO,2-WIRE(Initiefing) 0DIO0.4 0.0100mA 6.5000mA 6.5000mA 120904 P31-1T 1 PULL STATION SINGLE ACTION(Initiafing) 0.0000mA O.000DMA 000ODrrA 0.0000mA ILEVEL III LLFHSW 9 LED,LF,HORNISTROBE,MC,WH(Notification) 0.000OmA 0.000OmA 292.0000mA 2628.000OmA STW 7.STROBE,EXCEDER 24V M-C,WALL,WHITE(Notification) 0.0000mA M000DmAj 57.0000mA 399.ODOOmA HSW 4 HORNISTROBE,EXCEDER 24V,MC,WALL, A WHITE(Notification) 000WmA 0.0000.A 102.0000nA 408.0000mA D GHLFW 16 HORN LOW FREQUENCY,WH(Notification) O.aooOmA O.a000mA 99.40aomA 159D.4600m MHT-1224W MINI HORN,WH(Notification) 0.0000mA 0.000OmA 22.0000mA 176.000OmA HS-24WR 1 HORNISTROBE.2 WIRE,M.C.RED,WALL(Notification) O.00DDMA 0.0000mA 1860000.A 186.0000MAD Total Peripheral Stby 0.0100rr1A Total Periph Alarm 5=3.90001M NFPA Total Standby Amps 75.01ODmA Total AlarmAmps 56D8.9000mA 000805173 Standby time:24 Hm ISM ROYL CATS Alarm time:5 Min 0.467M Q9DTECj� Battery requirement: 226BAh 0F' dy Compensation Factors-Standby:12 Alarm:1.2 Requirement with compensation: 2.721M y NF1 a PA' S ''o y Circuit Calculations Panel:PS Card:00 Circuit:SIG1 Circuit Calculations Panel:PS Card:00 Circuit:SIG2 Circuit Calculations Panel:PS Card:00 Circuit:SIG3 CFP6 Clrcuit "a SIGT Circuithlame:SIG2 CircultName:SIG3 #1473 CimuitType:Notification Terminal Voltage:20.4V:DC Amperage:3.000DA Cimuit Type:Notification Terminal Voltage:20.4V:DC Amperage:30DDOA Circuit Type:Notification Terminal Voltage:20AV:DC Amperage:3.00DOA Cable:1614C TWISTED FPLR#16 Cable:1614C TWISTED FPLR 016 Cable:1614C TWISTED FPLR#16 Calculations based on Running Total Length. Calculations based on Running Total Length. Calculations based on Running Total Length. Design Criteria:Ambient temperature:1STF Max.operatingvoltagedrop:15% Design Cdteria:Ambiemtempemtum:16TF Max.operatingwitagedrop:l5% Design Criteria:Ambient temperature:1677 Max.operating voltage drop:15% Device Part No Appliance Desc Distance Current Voltage Voltage Drop Device Part No Appliance Desc Distance C_urreM Voltage Voltage Drop Device Part No Appliance Desc Distance Current Voltage Voltage Drop CITY OF REDMOND PSN-1000 Panel 20AV PSN-1000 Panel 20.4V PSN-10DO Panel 20AV DAVID MOW 001 HSW HORN/STROBE,EXCEDER 24V,M-C,WALL,WHITE,30CD 39-01 102. 19 (0.4165V)i Out LLFHSW LED,LF.HORN/STROBE,MC,WH,11DCD 4& 292.0000mA 19.812 (0.5873V) 001 STW STROBE,EXCEDER 24V M-C,WALL,WHITE,15GD 102'-0 57. 19.310 (1.0693V) na arcs..or as a 002 STW STROBE,EXCEDER 24V MC,WALL,WHITE,I5CD Z-O 57.00DDmA 19.9641 (0.019414) 002 STW STROBE,EXCEDER 24V M-C,WALL,WHITE,I5CD 15 57oDD0mA 19. (0.1407V) 002 HSW HORN/STROBE,EXCEDER 24V,MC,WALL,WHITE,30CD 2T-0 102.000OmA 19.0981 (0.212 #16-B-141co STW STROBE,EXCEDER 24V MC,WALL,WHITE,I5CD 2V-0 57.0000mA 19. _(0.19161n OD3 STW STROBE,EXCEDER 24V M-C,WALL,WHITE,I5CD 1T 57.0DD0mA 19.5221 (0.15V) om STW STROBE,EXCEDER 24V M-C,WALL,WHITE,I5CD 16 5T0000mA 18.9521 (0.146V) 004 LLFHSW LED,LF,HORNISTROBE,MC,WH,110CD 7-0 292.00DOnA 19.7564V J0 1 1 DD4 HSW HORNISTROBE,EXCEDER 24V,MC,WALL,WHITE,3DCD 21 102.0000m 19.348 (0.1735V) 004 LLFHSW LED,LF,HORNISTROBE,MC,WH,110CD 19-0 292.DDDOmA 18. (0.1628V) 005 LLFHSW LED,LF,HORNISTROBE,MC,WH,IIDCD 26--0 292-00DOmA 19. -(0.148M 005 LLFHSW LED,LF,HORWSTROBE,MC,WH,110CD T-0 292.DDDOmA 19.2977V to 0509u) 005 LLFHSW LED,LF,HORNISTROBE,MC,WH,IIOCD V-0 292.0000 18.7 (0.0228V) O ODS LLFHISW LED,LF,HORNISTROBE,MC,WH,110CD 7'0 292. 19aD1 (0.IXI57V) HSW HORWSTROBE,EXCEDER 24V MC,WALL,WHITE,30CD 19 102.ODDOmA 19.21 (0.0838Vj LLFHS LED,LF,HORN/STROBE,MC,WH,110CD 14' 292.ODDOmA 18.7 to 9" w C 92'-0 1092 o90DmA 007 LLFHSW LED,LF,HORNISTROBE,MC,WH,110CD V D 292.0D00 19.2 (0.0137V) 179-01092DWOmA - > a Total Current 1092.000DmA 008 STW STROBE,EXCEDER 24V M-C,WALL,WHITE.I5CD 29 57 0000.A 19.7 (0.0162V) Total Current 1092.0000mA w Dial VDr Percent:3.92%) Trial Voltage Dr 0.7988V IW_o 1251.Oo00mA (Total VDr Percent82D%) Total Voltage Drop:1.6735V m U W w (r oP Drop: oP P w ro_m a C Total Current:lzst.txllXhoA U m q Vl (Total vorop Percem:5.96%) Total Voltage Drop:1.21. Z odo# l2 0uO ut H Q CC1 J� Circuit Calculations Panel:PS Card:00 Circuit:SIG4 Circuit Calculations Panel:PS Card:00 Circuit:SIG5 e e m w 5 o CircuitName:SIG4 CimuilName:SI(35 Circuit Type:Notification Terminal Voltage:20AVDC Ampemge:3.0000A Circuit Type:Notification Terminal Voltage:20AV'DC Amperage:30000A =LL w J<w Cable:1614C TWISTED FPLR#16 Cable:16/4C TWISTED FPLR#16 3 TO Q O= Calculations based on Running Total Length. Calculations based on Running Total Length. Design Criteria:Ambienttempmatum:167°F Max.operating voltage drop:15% Design Criteria:Ambienttampmtum:167°F Max operating voltage drop:15% DU2:V) au. Device Part No Appliance Desc Distance Current Voltage Voltage Drop Device Part No Appliance Desc Distance Current Voltage Voltage Drop REVISION RECORD PSN-1000 Panel 20AV PSN-1000 Panel 20.4 DATE/DESCRIPTION 001 GHLFW HORN LOW FREQUENCY,WH 44'-0 99.4000mA 19.8971V (p.5029V) 001 GHLFW HORN LOW FREQUENCY,WH 66-0 99.4000mA 19.6941V (0.5059V) 002 HT-1224W MINI HORN,WH 6.0 22.0000 19.a44 (OD52311) 002 GHLFW HORN LOW FREQUENCY,WH 13'-0 99A00DmA 19.8071 (0.087V) OW HS-24WR HORNISTROBE,2 WIRE,MC,RED,WALL,110CD 21' 186.000OmA 19.6299V (0.2151V) MHT-1224W MINI HORN,WH Y-0 22.000OmA 19,7899V (0.0172V) GHLFW HORN LOW FREQUENCY,WH 11' 99.40DD.A 19.5371V (00926V) 0154 GHLFW HORN LOW FREQUENCY,WH 39-0 99.4000rnA 19.591 (0.1982V) 005 GHLFW HORN LOW FREQUENCY,WH 3'-0 99.40DOmA 19.5148 (OD224V) MHT-1224W MINI HORN,WH 31'-0 22.0000mA 19.4511 (0.1406V) DDSMHT-1224W MINI HORN,WH 56-0 22.00DOmA 19.152V (0.3628V) ON GHLFW HORN LOW FREQUENCY,WH 6499.4000rM 19A295V (0.0216V) SHEET LIST 007, GHLFW HORN LOW FREQUENCY,WH 6-0 99.4000mA 19.1207V (0A313V) 00 MHT-1224W MINI HORN,WH 3T-O 22.0000mA 19.3191 (0.1104V) 008 GHLFW HORN LOW FREQUENCY,WH 37-0 99.4000mA 18.951 (0.169310 008 GHLFW HORN LOW FREQUENCY.WH 9-0 99.4000mA.19.3M4 (0.0157V) FA 0.0 FA DETAILS 009MHT-1224W MINI HORN,WH 49-0 22.0000mA 18.7527V (0.1987V) 009GHLFW HORN LOW FREQUENCY,WH 34'-0 99.4000mA 18.23V (OD734Vj FA 1.0 FIRE ALARM D1 GHLFW HORN LOW FREQUENCY,WH 5-0 99.40DOmA 18.7322 (0.0205V) 01 GHLFW HORN LOW FREQUENCY,WH 14'-0 99.40 A 19.2134 (0.O166V) 011 GHLFW HORN LOW FREQUENCY,WH 42'-0 99.4000mA 18.6007V (0.1315V) O11 MHT-1224W MINI HORN,WH 4'-0 22.00DOmAl 19.2125V (0.0009V) FA 2.0 RISERICALCS 012 GHLFW HORN LOW FREQUENCY,WH V-0 99.4000mA 18.592V (0 1 244'-0 783-8OD0mA 13 013 GHLFW HORN LOW FREQUENCY,WH 26-0 99AODOmA 18.5623V (0.029M Total Current:783.80DOmA 01 MHT-1224W MINI HORN,WH Y-0 22.0000mA 18.5617V (0.0006V) (Total VDrop Percent5.82%) Total Voltage Drop:1.1875V 302'-0 1165.6000mA Total Current:116BS000mA (Total VDrop Percent:9.01%) Total Voltage Drop:1.8383V SCALE:1/8"=1r H H LF LF LF FHj LF FHj LF H LF LF DATE: 10/10/16 A9 Sao h YYK q5 PROJECT NAME LF LF LF LF H LF LF H LF LF H LF V, Z LLI a �a Jr W Z � T loco ; noCo +1x0 nsc0 15co O 15cp Q Z LF LF LF /r( [t Z = O A 5cJR a _j ^ Z A 30CD -D i5c0 11.0 ¢ 110cD b 10 15CD 'Iwo J r = m CD LF LF JD Cj L,F¢ F Y 01,11 0L0 BLDG 11 11000PS 1f000 7-VI t5C0 r5C0 p� LF LF LF � tt � W �� >g e ' 4icrn TS SHEET DESCRIPTION FACP FS a� FS FIRE ALARM IN CALCS/RISER BUILDING 17 ANN SHEET NUMBER FA 2.0 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE PROTECTION INC. 1730 Gibson Road Everett 98204 425-290-90-9800 INSTALLATION NOTES ONDUIT WITH �g L D G. 1 � \ DAVID MOW 1 CONDUIT ROUTES ARE FOR REFERENCE, EXACT 6x THHN#16 1 x RED,1 x BLACK ROUTE TO BE DETERMINED BY THE ELECTRICIAN. 1 x BLUE,1 x WHITE \ BUILDING LINKING MUST BE DONE AS SHOWN FOR 1 xGREEN 1 xYELLOW \ A CLASS A LOOP AND PROJECT PHASING. 120904, \ \ / LEVEL III p 2)JUNCTION BOXES SHOWN ARE TO BE LOCATED IN THE FIRE SPRINKLER RISER ROOM OF EACH / \ \ BLDG 12 �� �� n BUILDING OR ON THE EXTERIOR WALL OF EACH . SPRINKLER RISER ROOM WITH A MINIMUM OF 16 J \\ \\ 4 f BLDG. 11 _ NFPA AWG WIRE AS SHOWN. JUNCTION BOX LOCATIONS 000sos173 SHOWN ARE BASED ON INDIVIDUAL BUILDING \ ROYL CATS ONDUIT WITH ONDUIT WITH Qaoreo> PLANS. i x THHN#16 x THHN#16 1 x RED 1 x BLACK 1 x RED,1 x BLACK ONDUIT WITH w 1 x BLUE,1 x WHITE 2 X THHN#16 L'1►J BLDG. 14 1XBLUE,IXWHITE 3) BUILDING LINKING CONDUITS/WIRING TO BE RUN 1 x GREEN,1 x YELLOW � 1x GREEN,1xYELLOW �' ,J 2xRED,2xBLAC b�JNFPAyyc TO A GUTTER IN THE ELECTRICAL/MECHANICAL `� \ 2x BLUE,2x WHIT E CFPS ROOM IN BUILDING 17 THE SITE FACP IS LOCATED 2x GREEN,2xYELLOW #1473 IN BUILDING 17). \\ \� / I I I I �& 4 ALL FIRE SPRINKLER RISER ROOMS REQUIRE 1 x ONDUIT WITH I I I CITY OF REbMOND DEDICATED 120VAC 20AMP CIRCUIT FOR EACH \ xTHHN#16 ONDUITWITH - C .,abnswo MO o BLDG. 17 xTHHN#16 1 x RED,1 z BLACK o.#16-B-141 w REMOTE POWER SUPPLY. 1 x DEDICATED 120VAC J- �� 1 x BLUE,1 x WHITE 1 x RED,1 x BLACK 20AMP CIRCUIT IS REQUIRED AT THE MAIN FACP IN \, 1 xGREEN,1 xYELLOW 1 x BLUE,1 x WHITE I 1 1 1 cn Community w 1 x GREEN,1 x YELLOW Q BUILDING 17 ( SEE FIRE ALARM DRAWINGS FOR oNDu1TWITH GEC ROOM II I T. d� w BUILDING FIRE ALARM DETAILS). -ONDUIT WITH xTHHN#16 Building �. _��� W x THHN#16 1 x RED,1 x BLACK G —m W N y w,oVm 'wx 1 x RED,1 x BLACK 1 x BLUE,1 x WHITE y � z#H a C 1 x BLUE,1 x WHITE t x GREEN,1 x YELLOW 1X GREEN,IX YELL OW oo� pS2 -BLD . 15� �� BLDG. 9 2 CI_ FilEXTERIOR OUTDOOR RATED JUNCTION BOX `� \ ® J ,,. _ __ N p o m a ONDUIT WITH __�� 1 a W p W a. x THHN#16 \ _ � , W 3o� a ` W 1 x RED,1 x BLACK N >a o a ELEC.GUTTER TO BE LOCATED IN ELEC RM OF BUILDING 17 \ J w La;; z a 1 x BLUE,1 x WHITE ����_ p O w N M w 1 x GREEN,1 x YELLOW \ g L D G. 10 ONDUIT TH REVISION RECORD \ WI x THHN M6 ^ DATE/DESCRIPTION 1 x RED,1 x BLACK {+� ONDUIT WITH 1 x BLUE,1 x WHITE x THHN ON WITH 1 x GREEN,1 x YEL I x LOW BLDG. 8 1 x RED, x BLACK x THHNHHN#16 r ` 1 x BLUE,1 x WHITE 1 x RED,1 x BLACKSHEET LIST r 1 x GREEN,1 x YELLOW 1 x BLUE,1 x WHITE 1 �.nnnnn�I I ' 1 x GREEN,1 x YELLOW Wuu BLDG. 16 N �� ONDUIT WITH o x THHN#16 B WI!® — 's—� f 1 x RED,1 x BLACK N J 1 x GREEN,1'xYETLLOW B _ BLDG. 5 ; J BLDG. 6, J BLDG. 7 a � N — ONDUIT WITH ONDUIT WITH x THHN#16 tu x THHN#16 1 x RED,1 x BLACK (� = 1 x RED,1 x BLACK _ t x BLUE 1 x WHITE \1 1 x BLUE,1 x WHITE 1 x GREEN,1 x YELLOW DATE: 10/10/16 ONDUITXTHH WITH 1 xGREEN 1 xYELLO e J� PROJECT NAME 2 X THHN#16 a 2 x RED,2 x BLACK 2 x BLUE,2 x WHITE 2 x GREEN,2 x YELLOW ~ LU I W Z Q BLDG. 1 ��BLDG. 2 BLDG. 3_ BLDG. 4 Q Z A Boa p� N ONDUIT WITH ONDUIT WITH d x THHN#16 x THHN#16 t x RED,1 x BLACK 1 x RED,1 x BLACK 1 x BLUE,1 x WHITE 1 x BLUE 1 x WHITE 1 x GREEN 1 xYELLOW 1 x GREEN,1 x YELLOW SHEET DESCRIPTION N FIRE ALARM SITE BUILDING 41 LINKING PLAN SITE BLDG LINKING PLAN E SHEET NUMBER 9 1 8 1 7 1 6 1 5 1 4 1 3 1 2 1 1 \ FIRE ALARM ` PERMIT APPLICATION �iI1 CK�O Department of Community & Economic Development City of Arlington • 18204 59th Ave NE •WA 98223 • Phone(360)403-3551 THIS APPLICATION MUST BE ACCOMPANIED BY TWO (2)SETS OF COMPLETE AND SCALED PLANS FOR EACH FIRE ALARM PERMIT APPLICATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO, INCLUDE SPECIFICATION SHEETS,WIRING DIAGRAMS, (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON EQUIPMENT PROPOSED TO BE INSTALLED PRIOR TO INSTALLATION. Type of permit: (check one) ✓❑ New Fire Alarm ❑ Fire Alarm Alteration/Addition Project Address: 20201 77TH AVE NE BUILDING 11 Parcel ID#: 00829100000103-109 Njm 2 ber of Zones E3i d ng Area i 7000,Sq f C: Valuation: 3000.00 Owner: WD ARLINGTON INVESTMENTS Phone Number: 360 6710113 Address: 1020 CASINO ROAD W C ty:EVERETT State: WA Z p Code: 98204 Contact Person:DAVID MOW Phone Number: 425 290 9600 Cell Phone: 425 290 9600 Livia : DAVID@FPISEATTLE.COM Address: 1730 GIBSON ROAD C ty:EVERETT State:WA Z p Code: 98204 Contractor: FIRE PROTECTION INC Phone Number: 425 290 9600 Address: 1730 GIBSON ROAD City: EVERETT State: WA Z p Code:98204 Contractor's License Number: FIREPI*021ML Expiration:7/31/17 Contact Person: DAVID MOW Email: DAVID@FPISEATTLE.COM Electrical Contractor: FIRE PROTECTION INC Phone Number:4252909600 1730 GIBSON ROAD EVERETT WA 98204 Address C ty: State: Zip Code: Contractor's License Number:FIREPI*021ML Expiration:7/31/17 I hereby certify the above information is correct and that the construction on, and the occupancy and the use of the above described ro wqu_e-ar-nrrianWith the laws,rules and regulations of the State of Washington. 10/24/2016 Applicants Signature Date DAVID MOW Print Applicants Name FOR STAFF USE ONLY Permit# Accepted By Amount Received Receipt# Date Received WEB Form—130 Page 1 of 1 6/16LP CITY OF ARLINGTON 238 N. OLYMPIC AVE -ARLINGTON, WA. 98223 PHONE; (360)403-3551 BUILDING PERMIT Address:20227 77th Avenue NE,#11 Permit#:1195 Parcel#:00829100000103 Valuation:3500.00 OWNER APPLICANT CONTRACTOR Name:WD ARLINGTON INVESTMENT LLC Name:Fire Protection,Inc. Name:FIRE PROTECTION INC Address: 1020 WEST CASINO RD Address:1730 Gibson Road Address: 1730 Gibson Rd City,State Zip:EVERETT,WA 98204 City,State Zip:Everett,WA 98204 City,State Zip:Everett,WA 98204 Phone: Phone:425-290-9600 Phone:425-290-9600 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR Name: Name: Address: Address: City,State,Zip: City,State,Zip: Phone: Phone: LIC#: EXP: LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: Fire Alarm CODE YEAR: 2015 STORIES: 3 CONST.TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: 1 OCC LOAD: PERMIT APPROVAL I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY;NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC IOARCI10. SALES TAX NOTICE:Sales tax relating to construction and construction materials in the Ci ) Arlington must be reported on your sales tax return form and c i .Ar i 101. Signature Print Name Date Released Date CONDITIONS Adhere to approved plans. THIS PERMIT AUTHORIZS ONLY THE WORK NOTED,THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS,SIDEWALKS,DRIVEWAYS,MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount Total Due: $0.00 Total Payment: $0.00 Balance Due: $0.00 CALL FOR INSPECTIONS BUILDING(360)403-3417 When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon CITY OF ARLINGTON ' 238 N. OLYMPIC AVE -ARLINGTON, WA. 98223 PHONE; (360) 403-3551 BUILDING PERMIT _ Address:20227 77th Avenue NE,#11 Permit#: 1195 Parcel#:00829100000103 Valuation:3500.00 OWNER APPLICANT CONTRACTOR Name:WD ARLINGTON INVESTMENT LLC Name:Fire Protection,Inc. Name:FIRE PROTECTION INC Address: 1020 WEST CASINO RD Address:1730 Gibson Road Address: 1730 Gibson Rd City,State Zip:EVERETT,WA 98204 City,State Zip:Everett,WA 98204 City,State Zip:Everett,WA 98204 Phone: Phone:425-290-9600 Phone:425-290-9600 MECHANICAL CONTRACTOR PLUMBING CONTRACTOR Name: Name: Address: Address: City,State,Zip: City,State,Zip: Phone: Phone: LIC#: EXP. LIC#: EXP: JOB DESCRIPTION PERMIT TYPE: Fire Alarm CODE YEAR: 2015 STORIES: 3 CONST.TYPE: DWELLING UNITS: OCC GROUP: BUILDINGS: 1 OCC LOAD: PERMIT APPROVAL I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY;NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27. THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID. IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC1l0/IRC110. SALES TAX NOTICE:Sales tax relating to construction and construction materials in the Ci jo�Arlingtoq must be reported on your sales tax return form and c t Ar' 101. Signature Print Name Date Released I a1c CONDITIONS Adhere to approved plans. THIS PERMIT AUTHORIZS ONLY THE WORK NOTED THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS,SIDEWALKS,DRIVEWAYS,MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION. PERMIT FEES Date Description Fee Amount Total Due: $0.00 Total Payment: $0.00 Balance Due: $0.00 CALL FOR INSPECTIONS BUILDING(360)403-3417 When calling for an inspection please leave the following information: Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon i G .r Date 10/24/2p 6 Permit Number 1195 Project Name Park 7-,— Applicant Name Fire PrQt�ction Inc. Applicant Address 1730 Gibson Road City, State, Zip Everett. VVA 98204 Contact David Mow Phone 425-290_9g00 Email david a@fpiSeattfe,com Permit Type Fire Alarm Site Address 20227 77th q�enUe NE,#11 Valuation 3500.00 Status Applied Permit Issued Permit Expires Square Feet 0 Type of Construction/Occupancy Load Number of Stories 0 Proposed Use Apartments Assigned To Launa Peterson W /:00829100000103 TRLINGN INVEST MENT LLCParcet 0227 77h • Avenue NE WD ARLINGTLC ON IN 1020 WEST CASINO RD • • EVERETT, WA 98204 IRE PROTECTION INC avid Mow 25-290-9600 avid • f iseattle.�m •- - . ONTRACTOR abor and Industries - IREPI 021 ML 10/24/2016 Pire Alarm 11/7/2016 • .•• ev,n Olander n Review 10/24/2016 2:54:24 PM 611 Fire S eos Part2. df Upload File 10/24/2016 2:54:24 PM 11 Fire Specs Part1.0f 10/24/2016 2:54:24 PM ll Fire Alarm Permit Ilcation ' ' = C ZBJ rnxaNr CG{< >d! eterson Launa eterson Launa eterson, Launa k i 1 FACP FOR ALL BU` ,DINGS LOCATED " I BUILDING 17 @POTTER P300 PIUS� Fire Alarm Control Panel Features • 127 expandable to 381 Analog Addressable Points.Any combination of detectors/modules • 5 Amp Power Supply.Expandable to 315 amps • 2 NAC circuits rated at 3 amps maximum,expandable to 188. • 2 Input/Output(I/O)Circuits for system flexibility rated at 1 Amp each • Built-in UL Listed IP Communicator • Built-in email event notification and report capability. • Optional Dual Line Digital Alarm Communicator • System wide synchronization of Potter/AMSECO,Gentex, Cooper/Wheelock,and System Sensor signals. • No twisted or shielded wiring required. • Cabinet will accommodate up to 18AH batteries.Panel will charge up to 55AH. • Capable of Class A or Class B wiring configurations • Built-in NFPA 72 compliant smoke detector sensitivity test • Dead-front cabinet design • 1000 Event History Buffer ` NYC Fire Dept. Certificate of Approval Potter/Nohmi Protocol Features S735 7165-0328:0195 6156 • Less than 4 second polling time Product includes a 5 year warranty • LED's visible from 360' • Adjustable Smoke Detector Sensitivity • Adjustable Heat Detector Temperature annunciators,intelligent power supplies and other optional modules. • Temperature Heat Detector as fixed temp The P-Link will support 31 accessories in any combination.The RA- High6075 is a 2 x 16 LCD annunciator.The RA-6500 offers a larger 4 x • Drift Compensation 40 line LCD display that allows points and descriptions to be shown • Maintenance Alerts simultaneously.Intelligent remote power supplies repeat the P-Link data • Day/Night Mode and can be mounted 6,500 feet from reach other.P-Link devices such as the RLY 5 relay module,SPG-1000 serial parallel gateway and DRV 50 O e s c ri pt i o n LED driver can be mounted anywhere in the chain of communication with a maximum of 31 of each P-Link devices.A total of two(2) The P300 is a mid-sized analog/addressable fire alarm control panel SLCE-127 Signaling Line Circuit Expanders(loop cards)may be with a total of 381 points.The points may be any combination of smoke installed in the P300 enclosure,in a remote enclosure such as the AE-8 sensors,heat detectors or modules.This panel has a 5 amp power supply or with a PSN-1000E remote intelligent power supply. that is distributed across two Notification Appliance Circuits(NACs) and two Input/Output(I/O)Circuits. The entire system,including the SLC,NACs and P-Link may be converted with a CA-6075 Class A module.The entire system is The NAC circuits are rated at a maximum of 3 Amps each and the I/O programmed using a Windows based computer software and requires circuits are rated for a maximum of 1 Amp each.All of the outputs may the use of a software programming software key. be configured for notification or auxiliary power.In addition,each NAC and Output can be programmed for strobe synchronization and utilizes The P300 can communicate to a monitoring station using the on board Quadrasync for strobe synchronization across circuits of various brands. Ethernet connection to an IP communicator or using optional UL listed The I/O may also be programmed for a dry contact input such as a water UD-1000 traditional two line alarm communicator.The UD-1000 flow switch or pull station. connects to the main board and has two phone line jacks provided. The IP communicator uses a RJ-45 connection and when connected The cabinet will hold two 12 volt,8 amp/hour batteries or two 12 volt, to the internet may be programmed to E-mail system status,history 18 amp/hour batteries.The system when fully loaded will charge 55 reports,reminders and the configuration file.The panel may be updated amp/hour batteries.Anything larger than 18 amp/hour will require an remotely using the UD-1000.If the Ethernet connection is needed external battery cabinet the SSU-00050. remotely,the FCB-1000 fire communication bridge may be installed to The panel has the Potter P-Link connection for expansion with remote allow the Ethernet connection to be installed in a rack. Potter Electric Signal Company,LLC • St.Louis,MO 600-325-3936 • www.pottersignal.com Pam' #8830035-REV A PAGE I OF 4 08/12 P POT P300 Plus Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 381 addressable devices or modules in any combination.The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PSA Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PSHA Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135'Fahrenheit heat detector FHA Analog Fixed Temperature Heat Detector that is selectable from 135'F to 185°F RHA Analog Rate or Rise Heat Detector that has a fixed temperature selection from 135°F and 1747 and also will alarm if the temperature increase 12-157 in one minute DDA Addressable Duct Smoke Detector AB-6 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors AB4 4"round base that may be mounted to an electrical box and wired for connection to the above sensors AIB Isolater base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop ARB Addressable Relay Base that contains two relays controlled by the SLC.One relay is rated at 8 amps at 240 VAC/30VDC and the other is rated at 2 amps 240 VAC/30 VDC ASB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. Modules Device Description MCM Miniature Contact Module provides a small foot print contact module for mounting inside an enclosure. APS-SA Single Action Addressable Pull Station APS-DA Dual Action Addressable Pull Station SCM-4 Single Contact Module is a standard contact module with an LED that mounts into a 4"square electrical box. DCM-4 Dual Contact Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. TRM-4 Twin Relay Module provides two form C relays that simultaneously active when the module is triggered by the control panel. Each relay is rated for 2 amps at 24VDC or 0.5 amps at 125VAC. MOM4 Monitored Output Module is a power switching module that monitors the circuit that is controlled by the control panel. CIZM4 Conventional Input Zone Module is used to connect conventional smoke detectors to the system that receive their power from the module.This module is like a conventional zone on the SLC. SCI Short Circuit Isolater interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • www.pottersignal.com O +AZ✓ #8830035-REV A PAGE 2 OF 4 08/12 P POTTgz* P300 Fire Alarm Control Panel S LC Features RA-6075—2 x 16 LCD annunciator with a key pad in a locked metal enclosure. The Potter/Nohmi protocol is a digital protocol with a proven design for reliability and noise immunity.The system does not require special RA-6500—4 x 40 LCD annunciator with a key pad in a locked metal cable or conductors for connection of the Signaling Line Circuit as enclosure long as the cable is compliant with NFPA 70 and NFPA 72.The system LED4 6—16 LED annunciator with common indicators in a locked allows for Class A or Class B installations as well as"T-Taps." metal enclosure The total polling time for the protocol is about four(4)seconds which PSN-1000(E)—10 amp,remote intelligent power supply with 6 NACs, allows two polling cycles in the ANSI/UL 864 requirement of alarms 2 I/Os and a P-Link repeater reporting in less than ten seconds.Each loop is capable of 127 points with the exception of the P 100 and P200. CA-6075—Class A convertor that converts the SLC,NACs and P-Link connection Sensor Features UD-1000—UL listed,Dual line telephone alarm communicator The sensors through the fire alarm control panel provide a real DRV-50—LED driver expander,used to connect up to 50 LEDs in a time status as to the condition of the system.The smoke detector graphic display sensitivity,heat detector temperature level and drift compensation FCB-1000—Fire communication bridge,provides remote mounting of as all programmable options.The system also allows for a day/night the Ethernet connection mode where the panel automatically adjusts the sensitivity depending on the time of day.To assist in the reduction of false alarms,the smoke FIB-1000—Fiber interface module,used to extend P-Link to multi- detectors also have a maintenance warning that sends a trouble signal mode fiber(2 required) when a detector is dirty to the point that it can no longer maintain the RLy--5—Relay module,provides 5 form C relay contacts rated at 3.0 programmed sensitivity. amps 24VDC/125AC User Interface SPG-1000—Serial parallel gateway,allows for the connection to a serial or parallel printer The fire alarm control panel has a 4 x 40 LCD display to provide information to the system status.The keypad has navigation keys The FIB-]000,FCB-1000 and the SPG-1000 may be installed in the t stacker bracket or ordered with the optional rack mount enclosure. o allow manipulation of the Menu on board the panel.The panel is shipped standard with the following LEDs: AE-8—Eight card expansion cabinet • AC Power—Green AE-14—Fourteen card expansion cabinet • Alarm—Red Ethernet/I.P. Connection • Earth Fault—Amber The P300 is shipped standard with an Ethernet connection.This • Supervisory-Amber connection is the programming port and may be connected to a building • Silenced-Amber Wide Area Network(WAN)or Local Area Network(LAN).Once connected to the Internet,the panel may be selectively programmed to • Trouble-Amber e-mail alarm conditions,trouble conditions,supervisory conditions,test, The common buttons include a Silence,Reset,Acknowledge and Drill. Event History and detector status.An e-mail may be sent to the panel All of the buttons are accessible once the locked door is opened. and the panel will e-mail the event history,detector status,configuration file or server status to an authorized E-mail account.In addition, P-Link reminders may be set to send an e-mail for service,testing or other The P300 has a proprietary communication protocol that communicates conditions. through a RS-485 connection to field devices.Up to thirty-one In addition,the Ethernet connection is UL listed as an IP communicator. (31)devices may be connected to a single P-Link connection.The The IP communicator is listed to report to the UL listed Sur-Gard III P-Link includes the communication terminals and regulated 24 VDC IP receiver.The IP communicator replaces the traditional less reliable connection for the field devices.The field devices may be any of the alarm communicator transmitter that utilized telephone lines.The IP following: communicator is an active method of connection and communication to SLCE-127-Analog/Addressable loop expansion module(maximum of 2 the monitoring station. per P300) Potter Electric Signal Company,LLC • St.Louis,MO ©pM-R_ 800-325-3936 • www.pottersignal.com "� RZOV 98830035-REV A PAGE 3 OF 4 08/12 P POTTER P300 P/US J Fire Alarm Control Panel Specifications 1&91" �I.so• Electrical Specs:AC Mains O p p TOP u 3.0 Amps @ 120 VAC 50/60 HZ 2.0 Amps @ 240 VAC 50/60 HZ 4.41" 3.75- Battery O DEPTH 0 130 ttfA Standby 0 220mA Alarm O • 5 Amps power for NACs,I/O and P-Link • 3 Amps per NAC.regulated 8 0 N 0 • 1 Amp per I/O circuit,regulated O• Battery Charger range 8-55 Ah O0 • Battery Charger voltage 27.3 VDC • P-Link maximum current of 1 Amp • Panel holds(2)8AH or(2)18AH batteries f1GHT SIDE LEFTSIDE Cabinet • 16 gauge cold rolled steel with removable BOTTOM O locked door • Dimensions—18 "/16"W x 27 5/1e"H x 4 7/1e"D • Dead front to cover all electronics • Lexan viewing window Temperature and Humidity This fire alarm control is listed and approved for operation in an indoor application with temperature range fluctuations of 32'to 120'(0°C to 49°C) with a maximum humidity of 93%non-condensing.The ideal temperature is 77°F +/-10°F(25°C+/-5°C). Standards The P300 series fire alarm control panel complies with the following standards and codes. • NFPA 13,70 and 72 • ANSI/UL 864 o Local(L),Remote Station(RS),Central Station(CS),Propriety(PPU),Auxiliary(AUX) o Type of Service:Automatic(A),Manual(M),Water flow(WF)Sprinkler Supervisory(SS) o Type of Signaling:Digital Alarm Communicator(DAC),March Time(March),Non Coded(NC),Reverse Polarity(Rev Pol),Other Technologies(OT) • IBC 2000,2003,2006,2009,2012 Potter Electric Signal Company,LLC • St.Louis,MO 800-325-3936 • www.pottersignal.com O Plus 49930035-REV A 08/12 PAGE 4 OF 4 (E) POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Features Standby Current 20 mA Alarm Current 25 mA Operating Temperature 0°C-49°C(32°F-120°F)10%-93% @ 30°C(86°F)non-condensing humidity 0 Maximum Wire Length 6500 FT 0 Maximum Annunciators 31 Dimensions(WxHxD) 8"x 6-1/4"x 1-5/8"(Cabinet) Wire Gauge 14AWG-22AWG Display 2 lines x 16 characters Product includes 5 year warranty LISTED S2930 7165-0328:0195 Description Installation The RA-6075 is a LCD remote annunciator for the PFC-6075 and The RA-6075 is connected to the PFC-6075 using a four wire RS-485 PFC-6030 addressable fire control panel.The RA-6075 communicates connection.The connection is power limited and supervised.Up to using a RS-485 connection to the main panel providing common thirty-one(31)RA-6075 LCD annunciators can be connected using indication of Alarms,Supervisory,Trouble and other system status and Class B or Class A wiring.Class A wiring requires an optional Class A control functions. Expander. The RA-6075 features a 32 character, 16x2 LCD display with LED's for Power,Alarm,Supervisory,Trouble,and Silenced conditions. It can be mounted on a single gang electrical box or a four square electrical box.The annunciator is enclosed in a sheet metal enclosure install in accordance with compatible fire alarm panel. and has a Potter lock securing the keypad. Figure 1:RA-6075 Class B Wiring Example Figure 2:RA-6075 Class A Wiring Example To the next annuncialor CA-6075 a omwcUonf Panel + Remote + anelamettllWt nacllonAnnunciator Remote -1- + Remote Remote Annunciator + Annunciator Potter Electric Signal Company,LLC-St.Louis,MO-Cust Service:866-956-1211-Tech Support:866-240-1870•Canada:888-882-1833-www.pottersignal.com PRINTED IN USA MFG.95406077-REV B-I PAGE l OF 2 9/11 (E) POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Address Settings The RA-6075 address is set by dip switch S 1 located on the back of the RA-6075.The address must be set in the range of 1 to 31 to be recognized by the control panel. Figure 3:RA-6075 Class A(back panel view) ]FAR aywffw u IN Tw ,- Dip Switch Settings Refer to the table below for dip switch settings per Annunciator Address. Annunciator Dip Switch Settings Annunciator Dip Switch Settings Address SW-1 SW-2 SW-3 SW4 SW-5 Address SW-1 SW-2 SW-3 SW4 SW-5 1 On Off Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Ott' On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Off On On On 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On PRINTED IN USA MFG.#5406077-REV 13-1 PAGE 2 OF 2 9/I1 (E) POTTER PSN-1000(E) The Symbol of Protection POWER EXPANDER Features • 10 Amp Power Supply • 3 Amps,regulated per NAC • 6 NACs Class B or 3 NACs Class A • 2 dry contact inputs • Fully programmable and monitored through control panel • Isolated P-Link repeater connection,Class A or B • Up to 31 power supplies per control panel with system wide sync • Quadrasync feature synchronizes strobes from Potter/AMSECO, Gentex,Cooper-Wheelock and System Sensor. P+�0,T PSN-1000 Compatible with all Potter PFC-6000 series fire alarm control panels. ■ V��yp Poww SUPPh Electrical Specs • 120/240 VAC Input at 50/60 HZ • 5.1 Amps/3.0 Amps max draw • Standby Current 60 mA • Alarm Current 200 mA S2930 7165-0328: 0195 Product includes a 5 year warranty Description The PSN-1000 series is a UL listed intelligent 10 amp notification power supply and P-Link(RS-485)repeater.The power supply connects to the P-Link bus from the control panel and is operated and supervised from the panel.The power supply may be installed 6,500 feet from the control panel.The PSN-1000 then repeats the P-Link communication for another 6,500 feet. The power supply has six(6)Class B or three(3)Class A power outputs.Each output is regulated and power limited with a 3 Amp maximum rating.In addition,the PSN-1000 has two(2)programmable dry contact inputs.The dry contact inputs are Class B,supervised inputs. The power supply operates on either 120 or 220 VAC power and has a regulated 24 VDC output.In addition,the panel can charge up to 55 AH batteries and will house 18 AH batteries.The cabinet is constructed out of 18 gauge cold rolled steel with a durable red powder coat finish.A standard Potter key lock is provided for securing the door.Electrical conduit knockouts are provided on the sides and top providing installers with multiple options for installing conduits and providing proper power separations. The PSN-1000 is a self contained intelligent power supply/P-Link repeater complete with cabinet.The PSN-1000E is the intelligent power supply/P-Link repeater with additional cabinet room for the exclusive Stacker Bracket for SLCE-127 loop expanders.Both cabinets include space for 18 AH batteries. The power supplies are programmed and controlled through the main control panel P-Link bus.The panel displays any troubles or off normal conditions of the power supply and the events are stored in the panel history buffer. Each output can be independently configured to provide one of four synchronization patterns,constant power,ANSI temporal Code 3 or Door Holder power.The panel can be configured to synchronize Potter/AMSECO®,Gentex®,Cooper Wheelock®and System Sensor®. Potter Electric Signal Company,LLC•St Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830032-REV B PAGE 1 OF 2 09/14 (E) POTTER PSN4000(E) The Symbol of Protection POWER EXPANDER 18.91" 17.60" TOP 0 LU 4.41" 3.75" DEPTH d y O 0 Q _ N ( ) N ® 1/ b O Q � LEFT SIDE RIGHT SIDE BOTTOM O Dimensional drawings showing the cabinet in all three planes. Knock out locations. PRINTED IN USA MFG#8830032-REV B PAGE 2 OF 2 09/14 SYSTEM SENSOR" f 1 . Photoelectric Smoke Detectors System Sensor i3'"series smoke detectors represent significant advancement in conventional detection. The i3 family is founded on three principles:installation TM ease,intelligence,and instant inspection. Features Installation ease.The i3 line redefines installation ease with its •Plug-in detector line,mounting base included plug-in design.This allows an installer to pre-wire bases(included with heads).The large wire entry port and in-line terminals provide Large wire entry port ample room for neatly routing the wiring inside the base.The base •In-line terminals with SEMS screws accommodates a variety of back box mounting methods as well as •Mounts to octagonal and single-gang back boxes,4-square back direct mounting with drywall anchors.To complete the installation,i3 boxes,or direct to ceiling heads plug into the base with a simple Stop-Drop'N Lock'"action. Stop-Drop'N Lock attachment to base Intelligence.i3 detectors offer a number of intelligent features Removable detector cover and chamber to simplify testing and maintenance.Drift compensation and •Built-in remote maintenance signaling smoothing algorithms are standard with the 13 line to minimize nuisance alarms.2-wire 13 detectors can generate a remote LED- Drift compensation and smoothing algorithms indicated maintenance signal when connected to the 2W-MOD2 Simplified sensitivity measurement loop test/maintenance module or a panel equipped with the i3 •Wide-angle,dual-color LED indication protocol.The SENS-RDR,a wireless device,displays the sensitivityof P Loop testing via EZ Walk feature detectors in terms of percent-per-foot obscuration. • •Built-in test switch Instant inspection.The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition:normal standby,out-of-sensitivity,alarm,or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol,the EZ Walk loop test feature is available on 2-wire i3 detectors.This feature verifies the initiating loop wiring by providing LED status indication at each detector. �—� Listings �� M MEA MSFM �(�� LISTED wo - _ approved approved �$ \,,,,� ),t' 1 1446 77" 3180932 rL1,)Smoke Detector Specifications Architectural/Engineering Specifications Smoke detector shall be a System Sensor P Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.[he detector shall be a photoelectric type(Model 2W-B,4W-B)or a combination photoelectric/thermal(Model 2WT-B,4WT-B)with thermal sensor rated at 135°F (57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal,single-gang,and 4-inch square back boxes with a plaster ring,or direct mount to the ceiling using drywall anchors.Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual- color LED indication that blinks to indicate power up,normal standby,out of sensitivity,alarm,and freeze trouble(Model 2WT-B,4WT-B)conditions.When used in conjunction with the 2W-MOD2 module,2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verifythe circuit without testing each detector Individually. Electrical Specifications Operating Voltage Nominal: 12/24V non-polarized Minimum: 8.5V Maximum:35 V Maximum Ripple Voltage 30%peak to peak of applied voltage Standby Current 2-wire:50 pA maximum average;4-wire:50 pA maximum average Maximum Alarm Current 2-wire:130 mA limited by control panel;4-wire:20 mA @12 V,23 mA @ 24V Peak Standby Current 2-wire:100 VA;4-wire:n/a Alarm Contact Ratings 2-wire:n/a;4-wire:0.5 A @ 30 V AC/DC Physical Specifications Dimensions(including base) 5.3 inches(127 mm)diameter;2.0 inches(51 mm)height Weight 6.3 oz(178 g) Operating Temperature Range 2W-B and 4W-B:32°F to 120°F(0°C to 49°C);2WT-B and 4WT-B:32°F to 100°F(0°C to 37.8°C) Operating Humidity Range 0 to 95%RH non-condensing Thermal Sensor 135°F(57.2°q fixed Freeze Trouble 2WT-B and 4WT-B only:417(5°C) Sensitivity 2.51/6/ft nominal Input Terminals 14 to 22 AWG Mounting 31/2-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling r r Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal(standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm Of tinlid Ordering Information Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max.limited by control panel 2WT-B Yes 2-wire 130 mA max.limited by control panel 4W-B No 4-wire 20 mA @ 12 V,23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V,23 mA @ 24 V Accessories 2W-MOD2 2-wire loop test/maintenance module RT Removal/replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket,6.6 inch(16.76 cm)diameter SYSTEM ®2uh09 ange System out not. 3825 Ohio Avenue•St.Charles,IL 60174 Roductspecificauonssu6Jecttochangewithou[nouce.Nsl[systemsens«.comfa SENSOR Phone:800-SENSOR2•Fax:630-377-6495 Nnencpmdmm�raman-031Budin-6/09.latest oesionofmisaatasneet AUS-031&007.6/U9•p2169 PULL STATION SERIES PPOTTER DIE-CAST METAL The Symbol of Protection MANUAL PULL STATIONS • UL and cUL Listed,FM Approved,CSFM Listed,MEA Approved,ADA Compliant • Single or Dual Action Terminal connectors PULL D0W8 • 10 Amp Snap Action Switch l l Gold plated SPST contacts • Optional auxiliary contacts • Mounts on standard single gangbox • Surface backboxes available • High-gloss red enamel finish • Glass breakrod , O b,M Made in the U.S.A. Description Engineering Specifications The Potter Pull Station Series offers a complete line of die-cast pull The contractor shall furnish and install the Potter series of pull stations for a variety of applications focusing mainly on fire alarm stations as indicated.The pull station shall be die cast construction systems.The pull stations are available in single or dual action with a"T"type pull handle that is ADA compliant.Single action pull models.All of the pull stations have a 10-amp snap action switch and stations shall be a P32-1T.Dual action pull stations shall be the Potter a dedicated terminal block for the ease of wire connections.All of P32-IT-LP.Any manual pull station installed in an outdoor or wet the metal is completely coated to inhibit corrosion and provide for a location shall be a RMS-IT-WP weather proof unit.The contact shall uniform and quality finish. be a single pole,single throw switch rated at I amp 30V DC/125V The standard models have a hex key reset,however a key reset is also AC.The device shall have a terminal block for ease of wiring.Once available.The models are available with shallow and deep surface activated,the pull station shall be reset by opening the front cover. mount back boxes and as a weatherproof version. Opening of the cover in a normal state shall initiate an alarm. Operation Specifications The Potter single action series of pull stations operate by pulling Switch Rating: 1 Amp @ 30 VDC the white operating handle straight down and the handle will lock 10 Amps @ 125 VAC into place.The dual action stations require the lifting of the front Pull Station Dimensions: 4-3/4"H x 3-1/4"W x 7/8"D cover and then pulling the white operating handle straight down.The Color:Red with raised white letters,white pull bar with raised red letters stations are reset by opening the front and placing the handle in the normal position. For special application manual stations see bulletin#8910014. For explosion proof manual stations see bulletin#8880014. Ordering Information Type Model Number Stock Number Contact Type P32-IT 1000447 SPST RMS-2T 1000477 DPST Single Action RMS-6T 1000478 DPDT RMS-IT KL 1000451 SPST RMS-IT KO 1000450 SPST,key operated,no pull Weather Proof RMS-IT-WP 1000401 Dual Action P32-1 T-LP 1000476 SPST Weather Proof Dual Action RMS-IT WP-LP 1000403 Accessories Notes Dual Action RMS-LP 1000480 Converts single action to dual action Back Box P32-BB 1000444 Surface mount back box Back Box I P327DBB 1 1000445 Deep surface mount back box Glass Rods I RMS-GB 1 1000470 Replacement glass rods(10 per pkg) Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-1211•Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#9900097-REV L PAGE I OF 1 9/10 P• TPOTTER• OHM/• DCM-4 e Symbol of Protection Dual Contact Module Features • Single module with dual contact monitoring inputs • Two(2)Class B or one(1)Class A monitoring inputs • SLC Class A(Style 6,7)&Class B(Style4) • Mounts in a standard 4"or double gang box s _ • Wiring terminals accessible when mounted in box `� .awarro..w • All wiring terminals accept 22 to 14 AWG • Product includes a 5 year warranty ;VOTE: This addressable module does not support 2-wire smoke rz '- ci i zi detectors. Stock Number: 1430822 C U� us LISTED S2930 7165-0328:0196 Application Technical Specifications The DCM-4 is compatible with Potter's PFC-6000 series and PFC- Operating Voltage 22.0-24.OV 8500 addressable fire alarm control panels.The DCM-4 is an interface Max SLC Standby Current 325 µA module used to monitor dry contact devices such as sprinkler water Aux Power Required 1mA flow,valve tamper switches,or conventional pull stations.The module is capable of monitoring two separate Class B or one Class A circuits. Max Wig Resistance of IDC 100 it Max Wiring Cpacitance of IDC 1 µF Description EOL Resistor 5.1K Q The DCM-4 uses two (2) consecutive SLC loop addresses when Operating Temperature Range 32 to 120°F(0 to 49"C)Operating Humidity Range 0 to 93%(non-condensing) monitoring two(2)Class B circuits or one(1)address when monitoring a single class A(Style D)circuit.The module mounts on either a 4" Max no.of Module Per Loop 127 units(Class A)or 63 units square or double gang box.The module is capable of monitoring two (Class B) (2)separate class B circuits making it ideal for monitoring sprinkler Dimensions 4.17"(106mm)L X 4.17" waterflow and valve tamperswitches when they are located in the same (I06mm)W x 1.14"(29mm)D proximity.The DCM-4 includes one red LED to indicate the modules Standard 4"Square or status.In normal condition,the LED flashes when the device is being Mounting Options Double Gang Box polled by the control panel.When a contact is activated,die LED wil I light continuously and in case of an open circuit,the LED will turn off. Shipping Weight 0.6 lbs Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-0988/Customer Service: 866-572-3005 • www.pouersignal.com 8830008-REV B • 7/14 PAGE i OF 2 l P P OT T E I Z*I V, HM/• DC M-4 The Syrnbol of Protection Dual Contact Module Setting the Address Each addressable module,smoke sensor,heat detector and combination sensor/detector must be assigned an address prior to installing the device.The address is set using either the hand held device programmer or the addressing feature on the PFC 6000/PFC 8500 Series control panels.When the DCM- 4 is used to monitor two individual Class B circuits a single device address is assigned,with the second address number assigned automatically by the module assuming the next consecutive address.For example,if the first address number is assigned as"2",the second address number will automatically be assigned as SLC device address"3". Before connecting a device to the SLC loop,take the following precautions to prevent potential damage to the panel or device verify the following: 1.Power to the device is removed 2.Field wiring is correctly installed. 3.Field wiring has no open or short circuits. Installation Using Compatible Electrical Box �O O ° e ° 0 O � Q a 0e a . 0 0 0 Wiring Diagrams DCM4 With One ClassA Circuit NOl FROM FACP OR C I PREVIOUS MODULE S+ ZI S. NO2 TO THE NEXT MODULE ppppINp C2 0000 LED Q Z2 - SELECT STYLE U 00000000 NOTE:END-OF-LINE RESISTOR IS NOT REQUIRED DCM4 WithTwo Class B Circuits NOI FROM FACP OR CI PREVIOUS MODULE S+ ZI END-OF-LINE RESISTOR 5.1K OHM 1/2W S_ NO2 TO THE NEXT MODULE Sp-p C2 00008 LED O Z2 SELECT STYLE H 0000 END-OF-LINE RESISTOR 5A K OHM 1/2 W Potter Electric Signal Company,LLC • St. Louis,MO Tech Support: 866-956-0988/Customer Service: 866-572-3005 www.pottersignal.com 1110 2002:2000 DESMING,MMUFACTURNG, a 7.7iii�.i.LJ I&DISTRIRMNG WALITY SYSTEMS 8830008-REV B • 7/14 PAGE 2 OF 2 GENTEX CORPORATION Low Frequency Audible Signal GHLF Applications A V®C The GHLF is a high quality,low profile,low frequency audible appliance that offers a 24 dependable audible alarm with a low current draw. The GHLF is ideal for any 5 E R I E S occupancy that requires notification appliances. The GHLF horn offers a 520 Hz square wave,temporal 3 tone. A jumper selection is available for normal or loud decibel tone. A temporal 4 pattern is available when used with the Gentex GTSM Synchronization Control Module. The GHLF is shipped with a standard 4"metal mounting plate which incorporates the popular Super-Slide",feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The GHLF also features the patented Checkmate®-Instant Voltage Verification feature which allows the installer to check the voltage drop and match it to the blueprint. The GHLF horn is listed to ANSI/UL 464 and CAN/ULC S525, is listed for use with fire Product Listings protective systems and is warranted for three years from date of purchase. „`..; SIGNALING Standard Features • Nominal voltage 24 VDC • Input terminals accept 12 to 18 AWG C U� us • Unit Dimensions:6-1/8"(15.55 cm)high x e Produces a 520Hz square wave,temporal 3 r LISTED 5-1/2"(13.97 cm)wide x 1-5/8"(4.13 cm) tone deep • Jumper selection for normal or loud dBA • ANSINL 464 Usted • Super-Slide®Bracket-Ease of Supervision • Temporal 4 pattern available when used • CAN/ULC S525 Listed Testing with Gentex GTSM Synchronization Module • CSFM: Pending • Checkmate®-Instant Voltage Verification • Temporal 4 520Hz measured per Product Compliance • Synchronize horn with Gentex GTSM ANSI/UL 2075 • NFPA 72 Synchronization Control Module • Tamperproof re-entrant style grill and • IBCAFCnRC • Prewire entire system,install mounting locking screw(optional use) • Quality Management System bracket,then install signals • Faceplate available in red or off-white is certified to:ISO 9001:2008 Model Number Part Number Nominal Voltage Model Designations: asm � ` R=Red Faceplate MKI1191fiR —r aHLFW 904-0530 002 24VDC W=White Faceplate ASSEMBLED IN aHLFR 904-0531-002 24 VDC All units are plain(no lettering) THE USA Horn Decibel Levels: 24VDC Nominal Horn Horn Current Ratings Reverberant Room Current Ratings(mA) Over Input Voltage Range of 16-33V(mA) Minimum SPL Minimum SPL 24VDC 24VDC 24VFWR 24VFWR Regulated Regulated Regulated Regulated at 10Ft.Per at 1OFt.Per Operating Operating24VDC Max 24VDC Max. 24VFWR Max.24VFWR Max Horn Mode Operating g Operating n Operating ANSINL 464 ANSINL 464 Current Current Current Current Operating Operating Operating (NORMAL) (LOUD) (NORMAL) (LOUD) (NORMAL) (LOUD) Current Current Current Current (NORMAL) (LOUD) (NORMAL) (LOUD) emporal 3 62o I-Iz i 778 dBA 1 19.8 dBA 72.1 mA 120.1 mA 104.6 mA 158.4 mA 99.4 mA 155.8 mA 152.1 mA 213.5 mA 1Iemporal4520Hz*1 81.5 dBA 1 83.4 dBA 75.9 mA 116.0 mA 1 108.1 mA 182.0 mA 1 100.1 mA 1 157.2 mA I 163.1 mA 235.2 mA O "Temporal 4 520 Hz measured per ANSI/UL 2075 NOTES: '-perating temperature:32'to 120"F(0"to 49°C).The GHLF is not listed for outdoor use. • For nominal and peak current across ANSINL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output ratio,q. RMS current ratings are per ANSI/UL average RMS method. ANSI/UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units). For unfiltered FWR ratings,see installation manual. t GHLF 24 VDC 1 SERI UL Listed NOTES: Control THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR Panel signal signal PULSING SIGNALING CIRCUITS s+ s+ s- H+ H- S. s+ S. H+ H- THE FOUR PULSE TEMPORAL PATTERN(TEMPORAL 4)CAN ONLY BE Supervised 0 0 ( 0 OBTAINED ON THIS PRODUCT WHEN USED IN CONJUNCTION WITH Signal Circuit THE GENTEX GTSM SYNCHRONIZATION MODULE \ + • SEE GTSM CONTROL MODULE MANUAL(550-0632,MANUAL ISSUE END OF RE STORE DATE(02-01-15)FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. GTSM MANUAL CAN BE OBTAINED AT WWW.GENTEX.COM FiHE OR CALL GENTEX CORPORATION AT 1-800-436-8391. 0011df NrIS � Q LOCKING S+ SCREW S Q s- (optional) o o IH++§. .I M RED WIRES so Q BLACK WIRES ID No, O O O p o NORMAL-LOUD c �J DECIBEL JUMPER. FOR LOUD DECIBEL INSTALL JUMPER. SLIDE ONTO BRACKET Gentex Checkmate`' Gentex Super-Slide® LOCKING Instant Voltage Verification: Mounting Bracket: SCREW It is often necessary to confirm the voltage drop Allows the installer to pre-wire the system, (optional) along a line of devices.The access holes are test for system supervision,remove the provided in the back of the terminal block to signal head until occupancy,switch out allow the voltage to be measured directly without Gentex signals without changing removing the device.Typically this would be done mounting brackets and has locking edge at the end of the line to confirm design criteria. connector for snap-in-place installation. Most measurements will be taken using the S+ and S-locations although access is provided to other locations. NOTICE.CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES. Architect & Engineering Specifications The alarm horns shall be Gentex model GHLF.The appliance shall be listed with Underwriters Laboratories(ANSI/UL)for use with fire protective signaling systems(ANSI/UL 464)and with CAN/ULC S525 with intended use in fire alarm systems. The GHLF will produce a peak sound output of 88.3 dBA as measured in an anechoic chamber. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. 24 units per carton Important Notice' GHLF-01 G E N T E X These materials have been prepared p Gentex Corporation l Gentex')for informational of be purposes only,are O necessarily summary,and are not purported to serve re legal advice and should not ri used as such. Oenlex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-dale,or in compliance with all relevant local,slate and federal laws,regulations and rules. CORPORATION The materials do not address all legal considerations as there is inevitable uncertainly regarding interprelalion of laws,regulations and rules and the application of such laws,regulations and rules to Fire Protection Products Group•www.gentex.com particular fact patterns.Each person's activities can differently affect the obligations that exist under applicable laws,regulations or rules.Therefore,these materials should be used only for informational 10985 Chicago Drive •Zeeland, Michigan 49464 purposes and should not be used as a substitute for seeking professional legal advice.Genlex will not be 616.392.7195 • 1.800 436.8391 • 616.392.4219 Fax responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. (E) POTTER MHT 1224 SERIES • The Symbol of Protection LOW CURRENT MINI-HORN Features • Single unit is capable of 12 or 24 VDC determined by the input ! voltage I Unit Dimensions:4.48"(11.38cm)high x 2.84"(7.21 cm)wide x 0.5"(1.27 eun)deep • Jumper selectable temporal 3 or continuous tone Horn frequency is 3100Hz Terminal blocks(12 AWG to 18 AWG) + Imo,/� Low current consumption Ir" —_. �= Variety of mounting options for new construction and retrofit I t r j applications 1 1 Synchronize using the AVSM Series control module • ANSUUL 464 listed for fire protective service • Textured finish high impact plastic faceplate,available in red or off-white Ordering Information Operating Temperature(indoor use only) Stock Number Model Number Model Designations 32°to 120°F(0-to 49°C) 4890001 MHT 1224R R=Red facepalte 4890002 MHT 1224W W=Off-White faceplate 4890003 MHT 1224PR P=Plain 4890004 MH'f 1224PW SIGNALING U� LISTED Product includes a 5 year warranty Description The MHT-1224 Series mini-hom is a high quality remote The MHT 1224 can be used on the same sync circuit(AVSM audible signaling appliance that offers dependable remote annunciation. Series Control Module)as other Potter signals.The MHT-1224 Series The MHT-1224 is ideal for applications where a dependable audible is ANSI/UL 464 listed for use with fire protective systems. alarm signal is required in applications such as hotels, dormitories, and apartments.The MHT 1224 is listed for use with both filtered and unfiltered power and a jumper is provided to select either temporal 3 or continuous tone. Architect&Engineering Specifactions The alarm horns shall be Potter model MHT 1224.The appliance shall be listed with Underwriters Laboratories(ANSI/UL)for use with fire protective signaling systems(ANS1/UL 464)and produce a peak sound output of 90dBA or greater as measured in an anechoic chamber.The appliance shall be of solid-state construction and be polarized to operate from 8-33VDC with a 22mA current drain at 24VDC.The appliance shall be provided with 2 terminals,and mount to a variety of single-gang back boxes. Potter Electric Signal Company,LLC•St Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830065-REV A PAGE 1 OF 2 06/l3 (DPO-ffER MHT 1224 SERIES The Symbo!of Protection LOW CURRENT MINI-HORN Mini-Horn Wiring LL MHT-1224 MHT-1224 LISTED WIRING DIAGRAM FOR DUAL CLASS B CIRCUITS WITH A SINGLE AVS44 CONTROL MODULE CONTROL PANEL + _ + _ SYNCHRONIZATION FACV MODULE +•++++ +�+� SUMItVi5E0 ENDOFLINE SIGN& RESISTOR { I;INGII' I S EOLR \ tl Rrn TD �:?D RFD SIGNAL CIRCUITS R,ACK RACK RACK R.ACK wRan+ rnRr-zznj G�.— » Wiring Diagram ` E EOLR Mini-Horn Wiring Use a screwdriver to break the jumper for a continuous tone. DO NOT BREAK JUMPER IF TEMPORAL 3 TONE IS NEEDED. Horn Mode Minimum SPL at 10 Minimum SPL at 10 Reverberant dBA at 10 In Anechoic MHT-1224 Current Ratings feet per ANSI/UL feet per ANSUUL feet per ANSUUL 464 Room dBA C 24 VDC 22 mA 464 at 24 VDC 464 at 12 VDC 10 ft. Temporal 3 81 dBA 78 dBA 78-86 90 24 VDC UL Max 18 mA Continuous 86 dBA 83 dBA 78-86 90 12 VDC UL Max 13 mA NOTES:The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. 1 RMS current ratings are per ANSUUL average RMS method.ANSUUL max current is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units)(8-17 VDC for 12 VDC units).For strobes,the ANSI/UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units)(8 VDC for 12 VDC units).For audibles,the max current is usually at the maximum listed voltage.For unfiltered FWR ratings,see installation manual. PRINTED IN USA MFG.#8830065-REV A PAGE 2 OF 2 06/13 TechnicA Dii1a TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Description Eaton's Cooper Notification business has developed the Wheelock • ' ° Exceder LED Low Frequency Sounder Strobes and Sounders to meet the new National Fire Protection Association (NFPA)low °.; frequency sounder requirements for sleeping rooms -NFPA 72 for °•°•�•�•�•�•°•°•°• fire alarm and NFPA 720 for Carbon Monoxide(CO)alarm. In a single '•'•'•' device,the Exceder LED Low Frequency Sounders can provide alarm °•':•: •�°: signals for dual applications-T3(Fire)and T4(CO)tones. It is the first product in the industry to be listed to the audibility requirements '•:;;;;;:•° of UL 2034 and UL 2075 for CO applications. The Exceder LED Low Frequency Sounder Strobes and Sounders ' feature multiple 520 Hz modes of operation:T3(fire),T4(CO), Continuous,T3/T4 Sync Control. The 520 tone is generated within the appliance itself. When the selector switch is set for T3 or T4,the sound pattern is also generated within the appliance. When the selection switch is set to continuous,the product is listed for coded operations. TheT3/T4 pattern or other pattern must be generated by the FACP according to the alarm condition sensed by the panel (fire or CO alarm). When the device is set to T3/T4,the appliance can switch from T3 to T4 based upon the condition sensed by the FACP and passed to the Wheelock DSM module. Like the entire Wheelock Exceder LED product line,the Low Frequency Sounder Strobes will utilize Light Emitting Diode(LED) as the light source—a breakthrough optical design, resulting in best- in-class efficiency that enables material and system cost savings, allowing for a greater number of appliances on the notification appliance circuit and fewer power supplies. All LLFHS strobe models include a 110 candela setting. Providing a sleek aesthetic appearance, the Exceder LLFHS and LLFHN models feature one of the industry's smallest footprints and a sleek, modern, low profile design. Installers will benefit from its comprehensive feature list, multiple 520 Hz modes of operation, lowest current draw, no tools needed for setting changes, and convenient mounting options.These products are suitable for indoor wall-mount applications.The Sounder and Sounder Strobe models are for 24V operation. Exceder LED Sounder Strobes may be synchronized when used in conjunction with the DSM Sync Modules,Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol.Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. The Exceder LED Low Frequency Sounders and Sounder Strobes are UL Listed for indoor use under Standard 1971 and 464 and ULC under 5525 and 5526. The appliances are Restriction of Hazardous Substances (RoHS) compliant and contain no mercury or other EMT*N hazardous substances. Powering Business Worldwide Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Effective May 2014 Features Drawings Meets dual low frequency sounder codes for sleeping rooms in a 4 56 1.29 single device • NFPA 72 for fire alarm • NFPA 720 for CO alarm _•,, °°000°oo�o 0 • 4 Settings in 1 device o00000000000000 T3 (fire) 0°00 0000000000 °0°0°0 0o?o 00 00°00°00000°0°o°o°o • T4(CO) e00000000000 00 00 00 00 o°o°O0°Oo°Oo°O°o°o°000000. • Continuous(Coded) o°0°0°00000°0°0°000°0 °oo°00°0�000000000000000°0 6. 10 T3/T4 00°000e0000OO 00000 0000 • Energy efficient 0°o0e0ee°e°e°eeeo0o°0 oo0o°ec°e00000 Patented LED technology provides industry's lowest current draw • Low-profile design • Smallest footprint with sleek, modern aesthetics • 110 candela setting 140 • Easy-to-install • Finger slide switches—No tools needed for setting changes • Built-in level adjustment feature and snap-on grille cover Figure 1.Wall Low Frequency Sounder Strobe • IN/OUT screw terminals using#12 to#18 - —I AWG wires • Mounting Options include Exceder LSPKBB backboxes and 4" square backboxes o00o°oo°O0000 0000000000000°0 • Strobe synchronization components o000000000000000o o°O000°0°0°00°0°0°00 0 • Meet synchronizing standards with Wheelock's DSM Sync 00000°000000$000 0000 Modules or PS-6/8 Power Supplies 000°0o°0o°OOopOo0 00%Q a o°o°0°0°0°000°0°00000 • Compliance aoso°oo o°o°poo°o°o°og000�o°�o0 6.10 • UL 2034, UL 2075, UL 1971, UL 464, ULC S525, ULC S526 000°o°o°0o0000°o°o00 °o°oee°0000 00 00°e°o°oo • California State Fire Marshal (CSFM) 0°0°0o°oeo°oe00000°0 • ADA/NFPA/ANSI/OSHA 0oeeeoo • RoHS Note: All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION Figure 2.Wall Low Frequency Sounder INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT.VISIT WWW.000PERNOTIFICATION.COM OR CONTACT Table 1.Horn Strobe Current Draw COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. UWLC Max Current a FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION Exceder LED Sounder Strobes 24VDC AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, 16-33 Volts WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR Model Horn Setting 110 cd DEATH TO YOU AND/OR OTHERS. LLFHS Continuous 0.292 Code 3 0.292 Code 4 0.292 General Notes Code 3/Code 4 0.292 - • Strobes are designed to flash at 1 flash per second minimum over Table 2.Horn Only Current Draw their"Regulated Voltage Range:' Note that NFPA-72 specifies a Y flash rate of 1 to 2 flashes per second and ADA Guidelines specify UL/ULC Max Current a a flash rate of 1 to 3 flashes per second. Exceder LED Sounders 24VDC • All candela ratings represent minimum effective Strobe intensity Model Horn Settings 16.0•33.0 based on UL 1971. LLFHN Continuous 0.113 Code 3 0.113 Code 4 0.113 Code 3/Code 4 0.113 2 EATON www.eaton.com Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes and Sounders Effective May 2014 Table 3. Sound Output(SPL)-UL Table 4. Sound Output(SPL)-ULC LLFHS/LLFHN 24V LLFHS/LLFHN Reverberant dBA per UL 464 dBA per ULC S525-07c Description 16.0V 24.OV 33.OV Description 16.0V 24.0V 33.OV Continuous 80 80 80 Continuous 80 80 80 Code 3 76 76 76 Code 3 80 80 80 Code 4 b 85 85 85 Code 4 80 80 80 Code 3/Code 4 76 76 76 Code 3/Code 4 80 80 80 Table 5. Specification&Ordering Information c w/DSM or Syn Model Strobe Candela Red White Lettering Wheelock Power Supplies Sounder Strobes LLFHSR 110 X FIRE X LLFHSW 110 X FIRE X LLFHSR-AL 110 X ALERT X LLFHSW-AL 110 X ALERT X LLFHSR-CO 110 X CO X LLFHSW-CO 110 X CO X LLFHSR-N 110 X No Lettering X LLFHSW-N 110 X No Lettering X Sounders LLFHNR-AL X ALERT X LLFHNW-AL X ALERT X LLFHNR-CO X CO X LLFHNW-CO X CO X LLFHNR-N X No Lettering X LLFHNW-N X No Lettering X Accessories Description Red White LSPKBB-R 0756 Exceder LED Backbox X LSPKBB-W 0757 Exceder LED Backbox X Table 6. Specifications Physical Material Red or white textured UV stabilized,colored impregnated engineered plastic. Exceeds 94V-0 UL flammabil- ity rating Weight 1.10 lbs. Lens Light Emitting Diode(LED)in a rugged Lexan lens Uimensions 6.1"H x 4.bb"W x 1.4" U Operating Temperature Indoor:33.8°F to 120.2°F(0°C to 49°C)and maximum humidity of 85% Mounting&Wire Connections Mounting(indoor only) Wall-inount applications only. Exceder LSPKBB backboxes or to 4" square backboxes Wire Connections #12 through#18 AWG Power&General Operating voltage 24 VDC: 16-33 VDC Strobe Output Rating UL 1971: 110 candela output Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies,using Wheelock patented sync protocol Temporal Audible Pattern Continuous, Code 3, Code 4 or Code 3/Code 4 Sync Control. The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat)is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. The Code 4 temporal pattern (four cycles of 100 milliseconds t 10 percent"on" and 100 milliseconds t 10 percent"off;'followed by 5 seconds t 10 percent"off) is specified by NFPA 720. a RMS current ratings are per UL maximum RMS method.UL max current rating is the maximum RMS current within the listed voltage range(16-330. For strobes the UL max current is usually at the minimum listed voltage. For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation instructions. b Code 4 setting rated per UL 2075,UL 2034. c For dwelling use only. 3 EATON www.eaton.com Technical Data TDO01009EN Exceder LED Low Frequency Sounder Strobes & Sounders Effective May 2014 Architects and Engineers Specifications backboxes and to standard 4" square backboxes. The sounder and The low frequency sounders and sounder strobes appliances shall sounder strobe shall incorporate a mounting plate with a snap-on be Wheelock®ExcederTM LED Series LLFHN Sounder and LLFHS grille cover and shall mount to standard electrical hardware requiring Sounder Strobe for wall-mount applications with a low-profile design no additional trimplate or adapter. Removal of an appliance shall or approved equals.The sounders shall be UL Listed under UL 464 result in a supervision fault condition by the Fire Alarm Control Panel for Fire Protective Service and to the requirements of UL 2034/UL (FACP). All notification appliances shall be backwards compatible. 2075 for CO applications and ULC S525.Sounders equipped with The Series LLFHN wall model shall have a low profile measuring strobes shall be listed under UL 1971 for Emergency Devices for the 6.1" H x 4.56"W x 1.29" D.The Series LLFHS wall model shall have Hearing-Impaired and ULC S526.The Series shall be Restriction of a low profile measuring 6.1" H x 4.56"W x 1.4" D. Finish shall be Hazardous Substances (RoHS)compliant and contain no mercury or red or white.Special lettering,ALERT,CO and No lettering, shall be other hazardous substances. In addition,the sounder strobes shall available. meet the requirements of FCC Part 15.All inputs shall be compatible When synchronization is required,the appliance shall be with standard reverse polarity supervision of circuit wiring by a Fire compatible with Wheelock's DSM Sync Modules, PS 6/8 Power Alarm Control Panel(FACP)with the ability to operate from 16 to 33 Supplies, or other manufacturer's panels with built-in Wheelock VDC. Patented Sync Protocol.The strobes shall not drift out of synchro- nization at any time during operation. If the sync protocol fails to The Series LLFHS Sounder Strobe shall produce a flash rate of one operate,the strobe shall revert to a non-synchronized flash-rate and (1)flash per second over the Regulated Voltage Range and shall still maintain (1)flash per second over its Regulated Voltage Range. incorporate a Light Emitting Diode (LED)as the light source with a The appliance shall also be designed so that the audible signal may rugged Lexan®lens.The Series shall be of low current design.The be silenced while maintaining strobe activation when used with strobe intensity shall have a 110 candela for wall mount applications. Wheelock patented sync protocol. The audible shall have a minimum of four(4)520 Hz modes of operation:T3(fire),T4(CO), Continuous,T3/T4 Sync Control. UL 1971, UL 464, ULC S525, ULC S526, CSFM, FCC, RoHS The Series LLFHS and LLFHN shall be designed for indoor surface or flush mounting. Mounting options shall include LED speaker Note: Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. NOM WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland,OH 44122 United States Eaton.com Cooper Notification 273 Branchport Ave. Long Branch,NJ 07740 Coope rN oti fi ca ti on.com ©2014 Eaton All Rights Reserved Eaton is a registered trademark. �I•H Printed in USA Publication No.TDO01009LN All other trademarks are property Powering Business Worldwide June 2014 of their respective owners. 000 COOPER Notification ED "' Strobe, Horn Strobe, and Horn Notification Appliances FIRE' / \ VI- Ceiling Wall Description: The Wheelock®Excederr"Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. p ♦4% - Save u to 1 cost of installation** The Wheelock®ExcederTm Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single U0 Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings,can be set without the use of a tool and are located behind the appliance to prevent tampering. �iFinger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTm Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes completewith a Contact Cover for protection againstdirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a 90,95,99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if *, required. Wall models provide an optional locking screw for extra Universal Mounting Base secure installation, while the ceiling models provide a captivated v Ceiling and Wall screw to prevent the screw from falling during installation. Mounts to 5 Backbox Types Compliance Environmentally Friendly -UL 1971, UL464, ULC, CSFM, FM Low Current Draw -ADA/NFPA/ANSI/OSHA -RoHS Compatibility and Requirements -Synchronize using the Wheelock®Sync Modules or panels with built-in Wheelock®Patented Sync Protocol -Compatible with UL"Regulated Voltage"using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage"range "Compared to competitive models "`Patented "'Compared to previous models NOTE:All CAUTIONS and WARNINGS are Identlfled by the symbol A.All warnings are printed In Bold capltal letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT W W W.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION ANDIOR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE.AND SERIOUS INJURY OR DEATH TO YOU ANDIOR OTHERS. General Notes: General Notes: •Strobes are designed to flash at 1 flash per second minimum over their'Regulated Voltage Range". •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. •Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32•F to 120"F(II to 49'C)and maximum humidity of 93%(t 2%)UL 464(85%UL 1971). •Series Exceder home are under UL Standard 464 for audible signal appliances endoor use only). Low Current Draw = FewerPower • • Strobe Ratings per UL Standard 1971 UL Max Current' 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 W, 0.205 0.253 10,110 Horn Strobe Ratings per UL 1971 &Anechoic at 24 VDC AnechoicUL Max Current' at 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 L2� 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.102 Im0.141 0.148 0.176 0.197 0.242 0.282 0.125 Anechoic 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 M0.230 0.272 0.122 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.2671 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL Anechoic Model Regulated Voltage Range VDC 99 dB 95 dB 90 dB ' HN 16-33.0 0.064 0.044 0.022 HNC 16-33.0 0.084 0.044 0.022 HN 8.0-17.5 0.047 0.026 0.017 HNC 8.0-17.5 0.047 0.026 0.017 'UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units).For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units). For unfiltered ratings,see installation instructions. Specification & Ordering Information Sync w/ Model Strobe DSM or 12/24 VDC" Mounting Candela Wheelock Power Options tions Supplies • HSR 15/1575/30/75/95/110/135/185 X X UMB** HSW 15/1575/30/75/95/110/135/185 X X UMB** HSRC 15/30/60/75/95/115/150/177 X X UMB** HSWC 15/30/60/75/95/115/150/177 X X UMB** STR 15/1575/30l75/95/110/135/185 X X UMB** STW 15/1575/30l75/95/110/135/185 X X 67B** STRC 15/30/60l75/95/115/150/177 X X UMB** STWC 15/30/60/75/95/1151150/177 X X UMB** HNR X X UMB** HNW X X UMB** HNRC UMB** HNWC X X UMB"* *12 VDC models feature 15&15/75 settings **UMB=Universal Mounting Base Model Legend HN =Horn A =Agent Lettering r1: ST =Strobe (Strobes only) HS =Horn Strobe AL=Alert Lettering C =Ceiling Mount (Strobes only) W =White N =No Lettering R = Red (Strobes only) Example 1: STRC=Strobe,Red,Ceiling Mount Example 2: HER I torn Strobe,Red,Wall Mount , Example 3: HSW=Horn Strobe,White,Wall Mount / Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering Example. mple'HSWC ♦ AP • , t •UMB co,tact. NOTE:Due to continuous development of our products,specifications and offerings are subject to change without notice In accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock®ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. Where Multi-Candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30,75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant.The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68"x 1.50"D. When synchronization is required,the appliance shall be compatible with Wheelock@'s DSM Sync Modules,Wheelock®Power Supplies or other manufacturer's panels with built-in Wheelock@ Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1) flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock@ synchronization protocol. Wall Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC, FM, RoHS Ceiling Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC, FM, RoHS WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3YEAR WARRANTY Exceder- Spec Sheet 5/13 NJ Location Long Branch, NJ -0 800-631-2148 Cooper Notification is Wheelock" —mj_3_)C) SAFEPATH' wAV So COOPER Notification E) POTTER 5-24 & HAND SELECTABLE CANDELA The Symbol of Protection STROBE &HORN/STROBES Features • 24VDC units have field selectable candela options of 15,30,60, 75,& 110 • Super-Slide®Bracket-Ease of Supervision Testing • Checkmate®-Instant Voltage Verification • Synchronize strobe and/or hom with AVSM Control Module • Prewire entire system,install mounting bracket,then install _ — signals • Documented lower installation and operating costs • Input terminals accept 12 to 18 AWG • Switch selection for high or low dBA _ Switch for chime,whoop,mechanical and 240011z tone Tamperproof re-entrant style grill f} Switch for continuous or temporal 3 tone(not available on whoop tone) • Surface mount with the AVBB(Surface Mount Back Box) • Silence audible while visual appliance will remain flashing(for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature • 320F to 120OF(0°C to 49°C).The HS and S Series are not listed for outdoor use. Unit Dimensions • 5"(12.7 cm)high x 4.5"(11.43 cm)wide x 2.5"(6.35 cm)deep U� LISTED S3247 Description The S-24/HS-24 Series is a low profile strobe and horn/strobe This Series is shipped with a standard 4" metal mounting combination that offers dependable audible and visual alarms and the plate which incorporates the popular Super-Slide®feature that allows absolute lowest current available, the installer to easily test for supervision.The product also features a locking mechanism which secures the product to the bracket without The S-24 & HS-24 Series 24VDC offers tamperproof field any screws showing. selectable candela options of 15,30,60,75,and 110 candela. The S-24/1-IS-24 also features the patented Checkmate® - The Strobe and Horn/Strobe offers a continuous or sync Instant Voltage Verification feature which allows the installer to check temporal three in 240011z and mechanical tone, a chime and whoop the voltage drop draw and match it to the blueprint. tone.All tones are easy for the professional to change in the field by the use of switches. The S-24& HS-24 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed for use with fire protective systems and are The S-24 & HS-24 Series has a minimal operating current warranted for three years from date of purchase. and has a minimum flash rate of 1Hz regardless of input voltage. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA•CustService:866-572-3005•Tech Support:866-956-0988•Canada888-882-1833•www pottersignal-com PRINTED IN USA MFG.#8830054-REV A PAGE 1 OF 4 06/13 POTTER 5-24 & HS-24 SELECTABLE CANDELA The Symbol of Protection STROBE &HORN/STROBES Tone Switch Locations TONE SWITCH POSITION . 3 4 5 Mechanical Temporal 3 ON ON ON N® Mechanical-Continuous OFF ON ON -E —_A6 2400Hz-Temporal 3 ON OFF ON S¢ On 240011 a® S¢z-Continuous OFF OFF ON 3- Chime-Temporal 3 ON ON OFF ® �3 0# i# Chime-Continuous OFF ON OFF I=Q0C11= �3 H- Whoop ON OFF OFF CEKI Whoop OFF OFF OFF NOTE: • Switch Positions 1 and 2 in the OFF position to select isolated horn and strobe power inputs • Switch Position 6 ON=HIGH dBA • Switch Position 6 OFF=LOW dBA Super Slide®Mounting Bracket Checkmate®Instant Allows the installer to pre-wire Voltage Verification the system,test for system It is often necessary to confirm the voltage supervision,remove the signal drop along a line of devices.The access head until occupancy,switch holes are provided in the back of the out signals without — terminal block to allow the voltage to be changing mounting brackets measured directly without removing the and has locking edge connector device.Typically,this would be done at the for snap-in-place installation. end of line to confirm design criteria.Most measurements will be taken using the S+ and S-locations althouhg access is provided to other locations. NOTE:Care should be taken to not short the test probes. Candela selection slider switch. Depress center and slide switch to desire brightness level. J Break off pin and insert 4s into hole at the bottom of t6 the selector to lock w candela setting.Signal ; ie must be removed from _ bracket and pin pushed forward from backside out ' of hole to change candela. To remove bezel,grip both sides of bezel and pull in a download and outward motion. PotterElectric Signal Company,LLC•St Louis,MO 63042 USA-Cust Service:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal com PRINTED IN USA WG.#8830054-REV A PAGE 2 OF 4 06/13 E) P( OTTER 5-24 & HS-24 SELECTABLE CANDELA The Symbol of Protection STROBE &HORN/STROBES S-24 24 VDC Selectable Candela,Low Profile Evacuation Strobe Model Part Nominal Candela Number Number Voltage (ANSI/UL 1971) S-24WR 4890010 24 VDC 15,30,60,75, 110 S-24WW 4890011 24 VDC 15,30,60,75, 110 HS-24 24 VDC Selectable Candela,Low Profile Evacuation Horn/Strobe Model Part Nominal Candela Reverberant dBA at In Anechoic Room Number Number Voltage (ANSI/UL 1971) 10 ft.,per ANSI/UL 464 dBA at 10 ft. HS-24WR 4890030 24 VDC 15,30,60,75, 110 62-82 100 HS-24WW 4890031 24 VDC 15,30,60,75, 110 62-82 100 S-24&HS-24 Product Strobe Current Ratings(mA) 24 VDC(16-33 Volts) Model Designations: W=Wall Mount Candela 24 VDC UL Max R=Red Faceplate W=White Faceplate 15 cd 30 mA 42 mA 30 cd 35 mA 58 mA All units are available in plain(no lettering). Plain units are non-returnable. 60 cd 66 mA 97 mA 75 cd 80 mA 116 mA ALERT bezel available for order. 110 cd 103 mA 161 mA ALERT bezel available for order. S-24&HS-24 Product Horn Current Ratings Horn Decibel Levels Horn Current Ratings Minimum SPL Minimum SPL Regulated 24 VDC Horn Mode at 10 ft.,per at 10 ft.,per Max.Operating @ ANSI/UL 464 ANSI/UL 464 High Setting(mA) (HIGH) (LOW) Temp 3 2400 Hz 78 dBA 71*dBA 28 mA Temp 3 Mechanical 76 dBA 70*dBA 25 mA Temp 3 Chime 70*dBA 66*dBA 15 mA Continuous 2400 Hz 81 dBA 74*dBA 28 mA Continuous Mechanical 80 dBA 72*dBA 25 mA Continuous Chime 70*dBA 66*dBA 15 mA Whoop 82 dBA 69*dBA 56 mA El NOTES: • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified]) power,see installation manual. • Potter does nto recommend usign a coded or pulsing signaling circuit with any of our strobe products. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use.Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). PotterElectric Signal Company,LLC•St.Louis,MO63042USA•CustService:866-572-3005•TechSupport:866-956-0988•Canada888-882-1833•www.pottersignal com PRINTED IN USA NEG-#8830054-REV A PAGE 3 OF 4 06/13 E) POTTER 5-24 & H A-24 ND SELECTABLE CANDELA The Symbol of Protection STROBE &HORN/STROBES Architect&Engineering Specifications The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 hom/strobe Series or approved equal and shall be listed by Underwriters Laboratories,Inc.per ANSI/UL 1971 and/or ANSI/UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM)and the California State Fire Marshal(CSFM). The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage.The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. Conventional Wiring Diagrams for Emergency Notification Evacuation Series UL Listed UL Listed Control Control Panel Signal Signal Panel Signal Signal S+ S+ S- H+ H- S+ S+ S- H+ H- S+ S+ S- H+ H- S• S+ S. H. H- Supervised Supervised I IS 0 & & Signal Circuit Signal Circuit + \ + \ END of LINE LI END OF NE RESISTOR RESISTOR \ + END OF LINE RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage.Strobes should not be used on coded or pulsing signaling circuits.However,use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe,horn,and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION,REFERENCE AVSM CONTROL MODULE DATA SHEET(8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. PotterElectric Signal Company,LLC-St.Louis,MO 63042 USA•CustService:866-572-3005-Tech Support:866-956-0988•Canada888-882-1833•wwwpottersignal.com PRINTED IN USA MFG.48830054-REV A PAGE 4 OF 4 06/13 GENTEX CORPORATIOIM GOE OUTDOOR ENCLOSURE Applications A C C E S S ® R I E S The Gentex GOE Outdoor Enclosure is ANSI/UL 464 listed for use in indoor and P A G E outdoor applications when used with the Gentex GEH Series horn and WGE Series strobe and horn/strobe. Standard Features • ANSI/UL 464 listed • Back box with side mount tabs • Made of clear Lexan®-providing maximum visibility and reliability • Unit Dimensions:5.75"(14.61 cm) high x 4.75"(12.10 cm)wide x zt 4.18"(10.62 cm)deeN• 3/4"conduit knockouts • Reinforcement steel hardware • Outdoor resistant gasket • Available in red or off-white GOE-R GOE-W GOELP OUTDOOR ENCLOSURE Applications The Gentex GOELP Low Profile Outdoor Enclosure that creates a surface mount look, is ANSI/UL 464 listed for use in indoor and outdoor applications when used ° with the Gentex GEH Series horn and WGE Series strobe and horn/strobe. Standard Features • ANSI/UL 464 listed • Back box with outdoor resistant seal for mounting to wall GOELP GOE • Made of clear Lexan®-providing maximum visibility and reliability • Unit Dimensions: 5.75"(14.61 cm) high x 4.75"(12.10 cm)wide x 3.25"(8.255 cm)deep i • 3/4"conduit knockouts • Reinforcement steel hardware • Outdoor resistant gasket • Available in red or off-white GOE AND GOELP NOTES: • Product does not meet ANSI/UL 1971 light distribution requirements • To allow for drainage,the seal on the bottom edge is not water tight GOELP-R GOELP-W GBLP OUTDOOR BACK BOX Applications The Gentex GBLP Outdoor Back Box is constructed of durable plastic is ANSI/UL 464 listed for use indoor and outdoor applications when used with the WSSPK Series speaker and speaker/strobe. Standard Features < • ANSI/UL 464 listed • 1/2"conduit knockouts with metal washer reinforcement t • Wiremold knockouts for 500,700 Series and pendulum mount • Unit Dimensions: 6.20"(15.75 cm)square x 2.04" (5.18 cm)deep • Reinforcement steel hardware GBLP-R GBLP-W • Outdoor resistant gasket • Available in red or off-white GSB SURFACE BACK BOX Applications The Gentex GSB Surface Back Box is constructed of durable plastic and is fully compatible with the Commander'(GE)and Commander'(GE3)Series horns, strobes and horn/strobes. Standard Features • ANSI/UL listed for indoor use • 1/2"conduit knockouts with metal washer reinforcement • Wiremold knockouts for 500 and 700 Series • Unit Dimensions: 5.57" (14.15 cm) high x 4.55" (11.56 cm) wide x 1.47" (3.73 cm) deep • Screw heads hidden GSB-R • Available in red or off-white ALERT & AGENT BEZELS —0-m- "- Applications The Gentex ALERT and AGENT bezels are constructed of durable plastic and is fully compatible with the Commander'(GE)and Commander'(GE3) Series horns, strobes and horn/strobes. Standard Features • Easy to install is ALERT or AGENT wording on both sides of bezel • Available in red or off-white ALERT-W AGENT-R GCSB CEILING SURFACE BACK BOX Applications The Gentex GCSB Surface Back Box is constructed of durable plastic and is fully compatible with the Commander'(GC)Series strobes and horn/strobes. Standard Features ' • ANSI/UL listed for indoor use • 1/2"conduit knockouts with metal washer reinforcement • Wiremold knockouts for 500, 700 Series and pendulum mount • Unit Dimensions: 6.2" (15.75 cm) round x 1.67" (4.24 cm)deep ' as Screw heads hidden • Available in red or off-white GCSB-R GCSB-W GENTEX TheseImportan tee 551-0031-02 These materials have been prepared by Gentex Corporation('Gentex')for rNormatlonel purposesonly,are necessanty<ummary,and are not laaportad to serve as legal advice and should not he used as such.Gentex makes no representations and warranties,express or implied,that these materials are complete and accumle,up-to-date,or in compliance with all relevant local,state and federal laws, CORPORATION regulations and rules.The materials do not address all legal considerations as there is inevitable Fire Protection Products Group•www.gentex.com uncertainty regarding interpretation of laws,regulations and rules and the application of such laws, regulations and rules to particular fact pabems.Each person's activities can differently affect the 10985 Chicago Drive •Zeeland, Michigan 49464 obligations that exist under applicable laws,regulations or rules.Therefore,these materials should be used only for informational purposes and should not be used as a substitute for aealdng proleosional 616.392.7195• 1.800.436.8391 •616.392.4219 Fax legal advice.Gm1n9 will nut In.nesponsWlo tar any action or failure to act in relienae upon the intormabon contained to this matnn.L Gentex Corporation reserves the right to make changes to the product data sheet at their discretion P0 FIRE ALgR APpLIC., City of ArlDing ME:, Of ent of O� F�204 5 rnlunity &�EOOncTHIS APPLICATION MUST BE ACCOMPANIEp S Ago NE • mtC Cevet°pment SHEETSALARM ,WIRING DIAGRAMERMIT OSNPO(POINT TO Poll"��-��q�P2)SETS OF �3 Phone(360)403-3551 BE INSTALLED PRIOR TO INSTALLATION. ��t�sNG) AND ALL ALL pTHER INFOABLE' ALSO,INCLUDE MPLETEAND SCALED LANS FOR EACH Type of permit: (check one) ✓0 Ne�n0. I- "ATION IENTPR PO ON 20201 77TH AVE NE BUILp G e '41ar►n EQUIPMENT pROPO Project Address: N Z EJ Fire Alarm Alteration/ Number of Zones/Panels:2 Build i r-� Addition Owner: WD ARLINGTON INVESTMENTS s Are CsgFt): 7000 parcel ID 00829100000103-109 Address 1020 CASINO ROAD W Valuation: '000.00 DAVID MOW city_ EVERETT Phone Number: 3606710113 Contact Person: State: WA Cell Phone: 425 290 9600 Zip Code:98204 1730 GIBSON ROAD E"ari' DAVID@FPIS Phone Number:425 290 9600 Address. City_ EVERETT EArnE.COM FIRE PROTECTION INC State: WA Contractor: Zip Code: 98204 Address: 1730 GIBSON ROAD FIREPI*021ML City. EVERE� Phone Number: 425 290 9600 Contractor's License Number: State: w= 9 DAVID MOW Zip Code: 8204 Contact Person: Electrical Contractor: co FIRE PROl1=CT10N INC Email: O'4�//D c@i FPISEgEj�EtiOn- 1/17 1730 GIBSON ROAD -- Address EV FIREPI*021ML City ERE7T Phone Number:425 290 9600 Contractor's License Number: State. WA Zip Code:98204 1 hereby certify the above information is correct and that t Expiration:7131117 property !�1 ��r (�th the laws,rules and regutathOns ofsh�S non, and the. b w . ate of Washington cuPanCY and the use DAVID MOW 4�2016 of the Applicants Signature 1012 above described Print Applicants Name Oate F0RSTAFF kY qS- USE0_ eceiVed Permit Accept Amon— c ec WEB Form-130 Page 7 of 1 e"m OCT 24 2016 Receip A, DaleR': e 6/f6LP J �l` _ 1 FIRE PROTECTION, INC_ PO BOX 12642 MILL CREEK,WA 98082 14251290-9600 OR 1-800-681-1125 FAX [AW:;'PSJ35314546 City of ARLINGTON - PLAN RETTZ- O"Oh"20,Y016 RE; FIRE ALARM SYSTEM EW Please find enclosed plans fo r EM located in building 17 ( lower a FIRE: ALARM SYST building) , all residential bu i 1 1 Dor of this building The FACP will bealarm annunciator and remote p o wings will have is the site co mmuni sprinkler systems will be tied to r supply. All their own individual fire ty building 17 . The site electric ,i a d by -residential buildings and monitore building linking conduit/wi r i r1S s (Express Elect iche FACP located in linking plan. The SLC and SBUS `ems Shown on the are Providin �1 11 be included site g When a Waterflow, Smoke De tec t o r or in a Class building run residential building, it will $n full-station is `� loop as Shown. specific building and also at t ntznciate at theactivated in a p annunciatorin building occupant notificat iorz de FACP located in building that initiating device in that bui 1 di n vices will only at 17• Residential occupant notification devices �"ti 1 i is triggered ate when an per NFPA 72, 2013 edition re active• Th. s ste other buildinq,s current and your additional rqa r r ents as well y to has been designed Qui' aments , as . IBC, IFC 20121 NEC The building is fully-sprinkled _ activation as well as separate t The System shall provided via UL listed Central r�tible signals , monitor by zone P S tat • Monitoring Audibility shall be in co liars ,ion, The Ala g shall be be 75 DB minimum throughout, (I oW i th NFPA standards . erEY g• WA. INSTALLED IN RESIDENTAL SLEEPING �EAVECNY NOTIFICATION DEV for DB shall agreement is in force for the pro A full ICES TO BE serv' requirements . A full pre-test and NFPAefoice and ice and monitoring completed prior to calling the AHJ nn shall bemai conducted per NFPA far acceptance testing. and INSTALLATION COMPANY Fire Protection, Inc. 1730 Gibson Rd. Everett, WSCL# FIREPI*021ML UL CERT 98204 #608242-002 JOB SITE Park 77 Apartments *Building 20201 77th Ave Ne 11* Arlington, WA Received OCT 2 4 2016 VjLb [l qS D 13L MONITORING COMPANY ePRO Inc. /FPI 429-0991 Alarm Center► SE Lacey, WA $00- 4300 3rd Ave. UL CERT #902799-02 PARTIES . Installation' RESPONSIBLE Testing, 'ONTRACTUAL Monitoring; Service; Inc. Fire Protection, TEMPER7',TURES service equipment shall AIENT No area with alarm common areas shall fall below 40 degrees , be at 68 degrees per builder T NOISE RAGE the Fire Alarm Control and ptyglEN All areas serviced b Will be as listed for notif icatio n system PeY UBC listings, Per builders as well as remotes OPERATIONS enunciate at FACP for all SEQNCE OF shall shall cause re-dispatch Trouble conditions Zones of alarm to CS, All Alarm and Station. zone sigi,aL� listed Central send alarm and supervisory notify UL to activate, Trouble to site, (no circuits runner service. FPI runner service notification dispatch FPI dispatch emergency contact to Eire and CS which will On site transmit to activate. ) S shall be retarded Y $ shall shall at 25lbs, circuits Wet Waterflow ALARMS activate notification otif ied. smoke, Waterf low shall be n seconds . Low air personnel than 45 A short on FACP Shorts oa period of not more naI a alar►n- station shall cause a supervisory sig condition. causing for and dry) and Pull shall cause a Supervisory Switches , <<iAet low air zones signal- ,IV, and Hi- a trouble PI�1, tamp zones shall cause for to contact me Opens Da any lease feel free Should you have any further questions, P directly- David Mow Designer VP of operations/ NICET-3 #120904 R. #16-B-141 CITY OF REDMOND D•O• **DDE957M6 WA JOURNE`jM" LICENSE #MOW � Z I e v s 9 L 6 83ewnN 133HS NMOH + �r 3ldWVX3 Sy $aO1J31303NOWS Ey I rl r� %Ia1VW l-riTo BdO — SlItl13O oJe H r"+ems �/- I I r l N o,t 3 0 0 Mew WMbIV 3bld vrJ ' ' \S/ wa-n of ♦ • +Ir+++t ,+++A+Ia+N9 et •siay;o N0I1daOS30133HS u sslaoav 3:x+30�� • ♦ ♦ ♦ /q Palle;sul/papinad aq o;6uu!m•g;!npuoo 6uiNull Bu!pl!nq IIV(ZLaJ3a unrd oun+,o • trnaru ulaaJ i " ♦ • Iroa,.Jr+ao + 11,6ulppnq u!p9;e001 sl dOVd 041'dOVd 841 o;031VO103a aq of • • • u+a,.+lulu sWWro+,ld • S30N30 NOI1MJIiLLON S30N303latlsS3a0Utl(0151 • • • a,nl!ed,aw,od 0V w,elV end y pallnbei SI scull asayl;O L'scull 9uOyd0101 S1Od x z sal!nbal wa;s6S 6uu9gwnN aalnea WJ6IVailj r ♦ ♦ +nlenl+nuoJHnvras r ueld lad se Lovci OOOL-an l9440d e a y pa plAoid aq o;s!wa;sts wiele D o s ♦♦•♦ • • A.11/LM o ail;ay;30;suo4e;s lei;uao ay;o;uopo!unwwoo;o sueew a41 ILL IJ s ♦• • • ♦ +'°�"I+o+'I+m• t •spiepue;s g s;uawailnbai rHtl le0ol pue 0jl'ZL tlddN`03N 43!M t ♦♦ ♦ • • ..:oawn.nimwm t z-4 - r 1 N o+]0 7 a v •inch&W1•AY _ _ _ $R¢ s aouepJ0oae ul pa;euluuappalnoas/palle;sw aq o;s;ma!n WjeIV ai!j(oL d � C �- SneS aldd 4/8L# 9 a t$at��� O= Z M 1NNO NOILtlO1dI10N-OVN 2lIVd 031SIM1?lldj b/9L# tl r a`m -a w tiled 4oeaidde 013140A RJUaBloula agl gloi;alg w Apoo!o aq of pue C � y'p '� '1146iay algeaolnlos o tel Buipl!nq ay;/o i.SZ laddn ay;ul pow3ol aq V Z G 3 1N213 3NIl IVNEIIS 31S H1dj 4/81# n ----- z �N 1F of soloiyap,AW013JOW3 6unloaoldde lo/Pallnbal sagol;s mopin0 (6 m aweN adti 1 uol;eina�g91I O D m z C r �� � ` (S'44'L L ZL VddN 8 60E L'L l Ltl OOI)loloo u! ai a 0 lanai I ueBa !noji m A "e s`:f m; q paoeld aq gays sua!;e;s Ilnd (e N p 1;. 'J 3dA1 3NIl 11nomo r N= �_ �a,° a`a a �001;anoge sayoUl et,pue ZI,uaa a Z D `® � ? �. (I,)I?(E)Z'£'o-s'9 L uo!;aas 3WVN iogmltld Q a IFa" q ; 44;o gseg ay;`MOIA JO plc!; `ZLVdjN)pazluayOuRs aq pays sa of s aso 9NOL/0i. 31V0 O qa°/ a4;my;lM 93eds;ueoe(pe to wool awes ay;ul ace bay;jay;aym ew!; Z � t,. 8 awes ay;;e alq!S!A aie seouelldde uol;eo9!;ou oNq ue443NOW Ua4M (L L=„8/L-3ltlOS Z 0 D M ,ronnaunnW run P4uoO 0 > � ZZ Nt��d J N I S`dH d ! �l I S C7 0� �A.�N«r•.nir.«�«l, algal ZLVdjN)Ui!m a0uepi000e u1 paz!s pue paoeld p pays sapoi;s d unau orlamis I O'(e)L'E'b S 9L algal ZLtlddN)4Am aoue l000e u! azls Q palunow 6ul la <�1 v aq llegs sagals pa;unow IIeM'(Z-9 L'4'S'91,ZLVddN)'lanal loot;anoge wnwlxew„96 of wnwlulw„Og paled a O -{N (TI I q Ileys sagoi;s pa;unow IIeM (9 ;mmv z �. r c;n a e DGIB I Z�Dule -� 'pa;enl;oe sl (uol;eis-llnd`lo;0a;ap allows`mollialem)Bulpl!nq 0g!oads cley;W Oi;aolAap wiele ail}a U84M pa;eng0e Aluo!l!m 6u!pl!nq a43 8 _ yoea ul SOO!Aap uol;eol;l;ou luedn000 e4;`OIS e!A wais is lapluuds aj s---_------------ aUl u l;s6ul phew lnq a ea0tolluow HIM d3Vj a41'Bu!pling R;!unwwo0 dOVd 43 3 peioauuoo lolelounuuV .1'IV ai!j a;owaa A B 1 d e pue AiddnS lamOd a;OWaa a ane4 II!m BwpOnq lel;uap!sai g3e3 831yala3sla 0'l V! L'J-Q7.9. 9 gals'! ''9 Me = 1 a3llOd 81300 3anSOlJN3lO0ada3H1V3M SM a0001n0 6u!pllne A;lunwwo0 ag;w pa;e0ol dOVj auo ane4 Il!m lyladoid still (S 9 3 83uod coed LlONI01IneNIa31VJOlaOVd aJv3 3 S`ZLVddN)ino>tool ia>,eaiq 03a a um 6uuadwe; WaVltl3ald 0'L VA v i r• �]�L• '(Z'S'S'OL uol Oa -- g'J-Ola I sa3HloAa Sa3H10Aa HJIIMSMOlda31VM H ;su!LBu poinoeS pue palagel aq!lays wa;sRs Lunle sig ay;somas;eq; SlIV130 tld 0'0 V! __ la>leaiq;lnoil0 031V01030 a41 '(L'S'S-O L uog0e divza L'xowneq wepue�s z-xoee 1 a3uoe aMr2-SH lT/h1 03a'J'W'3aIMZ'3a0alANaOH a �� S`ZLVdjN)wo;sAs ay; 1SIl 133HS - -- - of �Q1H of lamod C13iV3IG3G Bu!6lddns sl;ey;laued p3ploole a4;;o uo!;eool 1 r Hdv.ze z'xogry,egp,epuels'z-xoee s a3uoa MYzzrlHw HM NaOHINIW ag;o;lauuosiad loai!p Ile's dOVd aUl u!paoeld ao!you V•;!noi!o dwe0Z 6 dale BuTrNng St 901H v n OVAOZL 031V01030 a 3LIln036 sallddnS lamod a;owaa HOT d3VzI(4 _ lyUI1WU10� ,, 3dtl.Z5 y xogypvq wepu�S t^%Oaa 9l x31N30 MTHO HM'AON3nD3ad MOl NaOH ,a (1 POlB 'siolslsai l03 6ululeI000 suo!;e001 ao!Aap Ile lagel'(L'Z'4L-(L IldiaJ$3l]131VQ - aI` iitl.Za Z'xogpuegp,eWeIS Z-XOaa V 51OO133HM W. 311HM IIVM'0-W'AYZa3O30X3 3....ANNOH ZL Oi!003il NOISIA3il Vd�N)uol;Olpsunf 6ulney R;uoy;ne ay ;O;pue 6u!;s!I Baine;nuew r______._^ a4;lad pa;sa;pue Palle;Sul aq!lays s00!Aap pue swe;sRs IIV (C TvrN O ! 1 ddv.Za Z'xogry�eq wepuel5',XOea L xJ(1133HM MLS 311HM'IIVM'J-W AM a3O3Jx3'390a15 `oin3� I Ll-�l8 � - T #O ! t ,ZL g(j'lg ddtl.ZS y'x"WNp,epuals'V-X09a 6 NJOl33HM MSH3T HM'JW'390a15/NaOH'dl'03l q'01 dl 'opeol(E'Z'8L'0L ZLtlddN)uo!;eool panadde y TS m I a ue Is Papinad aq Ile4s su ;!oods;uawdlnba pue(„;8nq-se„) O,,M m 3 I ( Z'wogry'egwnpuelS Z-XOee 1 aOSN355AS e-MZ 3aIM-Z'010Nd 3x0WS Ly+l Se o;palls;ai as!�a4;0 SBUIMeip piO3ai y;lM 6u0le'Wa;sRs F o A O$ ;_---It �. 04;;o a0ueua;ulew pue 6ul;se;`6uyelado ag;lo;suo!pni;sul (Z �N m O z 5 -- 3dtl,B6 z'xogrypeq wePuelS'Z-XOaa L a3110d ll-tea NOI1Jtl 3l0NIS NOI1V1S find C OyKo - it tiaIF3 b' qp.q p,epup5'Y 11'XOea L a30d Y-W00 31n0 L on 1JV1N00 indNI Wna 1 '(o'Z' 'Z'e1'0L ZLVdd !;N)uol;aadsuI jo awa4;le bloods u!rH V a4; O n o (•� ENI41In9 o;papinad ag lleys ua;aldwoO;o pio0aa palaldwoa ayl x 1yA y L h N A= Sa31-L10 AS Sa3H10 AS a3dWtl1 H31NNIMS Ls71 MOM JO dEI�d ZLVdjN)uolla!dw00;o piwaa ZLtlddN ue alaldwo0IIe4sialle;su! mN y m e 1 83uod OOOL-NSd a30NtldX3 113MOd 310W3a d-.l 1N3-TI-1 sd wa;s6s wielV ailj ayl sueld panoidde aq;pue sopoo 6UIWaA06 Z 1 a3uod scos-va a iVIONNNNV 3iOMNCJ1 r� Ile Ui!m aouepi000e ul aq o;pauuyuoo pue pa;enlena'pa;sa;'pa0elsu! o _sw3wae{viau;av1lNrx>++I -s1N3w3alna3axoeaJaa _A _03uv a3ewnN lava Nd1�LNJ930 uaaq sag Wo1sAs al-4044 Bu!;e;s rHV IUDOI a4;o;u0!;e;uawnoop 3 N 133a1S H1bOZ pusBal IogaS W1elVailj hl1156 ap!Aoid 0eLls lalle;sul ay;'uogoadsu!lo;61,110e3 o;loud (L SMON N011dllV-LSNI MOW OIAVO ONOWO3a j0 A1IO dM "NO -MV 1 etrtr Wn 03HSINU d Xra.et f 1 ��� M00 301JJO uv,fuse I � m3 s nr.vs 0080080 _ L I WHVIV 3UU O JUVJ6 Cl[90.00 F UM QC � ^s.PleuWUW 77 feW i•II 3eN A:1\"A U .leualeS J / OLlrafJO ro ♦III 13A31 .m 3 Q 1aH GO l O thou 6 b� -� '� S�AIvmlVoronv E) Niciii no INI -3 ` '� A aun70 aluYa aNlax (Pon).0 atu.W.0VOR rA n Y dVW illIN131A ' `�� MOW OIAva 0096-O6Z-SZ6 oozes ua4'ilalaAI UNDIMM 51H MOLLVTWJBNI gau31 a ' f3.LN3W1NVdV LL MUVd peoy uosgr�JeA 'JN/W N011�310ad 3alj �►� z i c I ti 1 s 9 1 L 1 8 16 L 8 6 0' V� M39WI1N 133HS WHVIV Maki NO11.nHaS30 133Ha v �N � c.4 d c)-4 r a bOOIA ONZ a001� 1S 6 -4-4 0 — en 0=Z� ZC - tl T �m Z m 1 1 1 — ---- --- � D m Z m. ua Cn I lap 3WVN1O3fONd i 91,M/01, :31VO I ., in __l an AL1N3 I 1 AVIN3 11L ' a I I uuNa j f 1 I /arols I I RIMS I �� i � I -• l+oc�a v3sla ryl se or: 1 „I 1 r 1 '°' I I I �---� `�-- _-__ N09tl.i1$41.M_111-SdO ��--- � Y1 1 I I aro�ty� fYi •I. 1 Y! 8 1 .,,: _ --- salty VW/Ii , ..�..�F ----------1 .a.Y..I 1 VodA e9 JJNn - H I ••••• P911Nn / t811Nn 1 Ra -- c °Y I I SOlYOR13Sla 0'Z V1 "� n m y I �7- .e,,..,.. a-� Va 11Nn 8 WNVIV 3NIA 0I,tl! ""' 4(��j' I ( Vad41 Val iF I Slrol3a vA 0'O Vd 1.9 imn LINO >:'911Nn 1SIl 133HS I I wr,S S) i I 1 @tl_N!NtG/, N0lld1H7S30/31Y0 LS NI QdA1!;1Q. �t_`J)�l�d;l.IRJIt f IIQ11Y U36R1 N1_&L (180092i NOISIA38 3 — [ t_m3114*11 v� w n n �.►.,p1ry Title N�Q;f;}V.Q91 ����� BSINHH1MlM �wrommt r?mi�p ���• Do N* Moo-1=1 aUC D N by — — hiW� o Mow OIAv0 „ '�5 .►to. _ allowa311 io nil] ---- w , AalN3 LL9lF 1 �—a—• —_rl J l I .ww e v ------1—_-1 ( I I t cctson000 .W90L s U3yp11d 8iQ.4 I l 1 a Vd�N wed idir+elM •+�.� .1."— U ZL-811Nn 1 1 `pp91 OL-811Nn 6-B AM LL-a llNn _ Q II VO60ZL ' MOW OIAtlO 0096.06Z-9Z0 POd96 HM'IJeieA9 pe°d U-WID om '3NI Noll 031Odd 3dld L Z £ y S I 9 1 8 " 6 - 07 d=1 aa£��vnN 133Hs a3SILl�S�ltl� �—cL�Nlmins WNVIV 3NIA a� d •.dl..uq.Y OHd ! ^ N011dWS30133HS wll O0l9 ux1 nv a�a .Ixa. axe gzry n c sd liyf r1N � A O n C V ni1!L nx, a•L. nru 2 o= zD S wa R. �m m el H roen n n n n n ,1 3WVN 1o3f o8d 9 fw io 4 :31va ,AC10f'1-aep aaVlM LNe1 s1oY Wwae IMII 8 YIe000f9Ht ar1111D Igol ... Y9Li tOC AQflt'1' Igal aaQA1NeL __m nuoa9l 'iaA'iaiO+iKiw tsr -to M1•0009Cos Wn1101ga1 m ASt1a91 as IVA'AOH3110MIAIMOl Nti0M A11D10 l0 0000'[QL1P./fL 'm SYa9f{ 'N .b HM'A3N3n03Ni MOl NNOHIM31H9 IUO S31VOlt13SIM WE 4laoaom tZet�vla0oo0 Lt!4) IIM'Ny011 V {t0 ISI' K00af1 'M .Zb HMAON3nD3Nd.-s NNOH MnHO It WNv1v3Nlj0'Lvd {om letlLel MLa00r86 sl NMA /i11Di93 P111011 Mi1H9 l0 ffi ,ILZt917tt.—._-'�- .S HM A7N3nO3tlJ MDl10y011 IAL0 G� at WgOor OB"UK_ NM'A7rtXW3 A 1rJMRAZA H.H Mlm ALLptn�MMQu Osr �" NM'ralOLlew L tlAlSlQm a,L Mu0001.1a S Wyl'AA1311D3M3Nl71Mg11 M a i—'AKWQl N�IOOObM INNL'40N3f10StllAW1NUW sMi1MJ -- — ALOital�nn000ree WAAOH311G3Y1MAlrlYDH Ai110 teQ woua 1e1ca�.Yrl0000u o.EE wui'roio�iranl�'zi1�•— oo twat ...— __-_... _..._....._ 1SI�133HS im eljwwQ.ea A IIMA0119Ig3N1MOt MJYW _-- - -. Wg00r� Aa INA'Oa1p11nw4trtZ�•t. -- t-10— HSr11,V-4Wmmu :IS WA r9R%11WsW r }��I�Z�tO�M- •M►Isai '86.._$ -•AOFI311071NMO NtlGH IA211101 lQSIII iV-0mvIN �_' w 1so"Xiom l�cM�0�1'" 1NilND T— �LrV'm AILSSat a8 .Ll HMAON3nD3Ni=1 NNOH MilH9 m I�ILL1Qa) LQ/1a'WWK�.0 — Im.Lw>t OZZI-1H '1ALSIZm 'AORLaa1 W10�9aL .tZ OOOLL IIrM'D3N O•W'3NIMZ'390tlLSMNOH NMVZ-SH �• rrgepl/0 p$3 NM'/w�11�Ep]Ik1AW7N11�1,Mi1H0 AOlri-N I"•MSOQQOTZ o-.S HM'NiIOHINMY IAAKZt IH � NOI1dR10S30/31WI as .90 NM' —3YlNK)1NU—MdlH9 100 WifGO_ AUSIGU68 :bp _ HMAON3n071MMOl NNOHJAMIFIS ILOO I'OZ �d plp{ypN yA>TLY 0?3009N NOISIA3N dole a6e110A a911NY1 MH!uQ0 700-"gddV !Ool.Ufd r200a 0 ell A! 11-A Illallg Imuelsl 1 y `oly Ued-laalnaq del a6 0 a6e O p� asap aauel dd r m 1a!n o �sL�IW -- _. -„ow d.tal:«aN.luw(Iwaiuv:wWOw�it •u9L:aay- rv+ww.ao.ara d esL u,min«wro:.non,D KaD V P>S3S 418ual lelol BwuunH uo paseq uo9elnalo0 4lauel lgol auluunN uo peseq s,,q I.O D a�p2y 9 L9 Hld3031SIM1 OD!9l:e19e0 9LO Nld3031SIM1 OP i 9L:a19eO N T t7 m m VOOOOC:eBe,edwb' 00:AVOZ eBWMleww,ol ualasil!WN adkl—1 a0000E a�-duM OO:AVOZ a MPAIeu!-1 umIm!MN:a Alnmlh SEAS—Nlnw!0 m :awnNmuo T suoeloleo l!no1!O d suoppo a 1no11 VJIS:Enos! oo 'A9141 f•AeasW—ddd/an lgoll VVg0Lg 11LI WIw01N11 _ my m ti ASEL9 l.d ^`l— wdred dwOA IgoL _ _ — i f 4A11 A901t40 T Iql wO ebegM IW1 MOZ 9l __ aSgIM 1go1 l'•�--'--_• m w = vuwao ZBOL!ue„no 1-1 amoi IYI Vug000LSi bAa OOSI'31SNt'71YM'OwAK U3LI37a133tt011l9. - 1LLa.Wolydt� g Z+ vm0000ta01[r 9LL i0m� el WAapO=4) WaN lVA"7d1'30pS11S7lNOH lt'077qV-d*0V&a t O WIQa000Aa D{ Imo..., t/^ m AS9tt QliV'0000Mt .b! OOOLL'HM OW 39oNLSMHOH dl 03l iMSHdlI Is00 !�ACOO'm Kel Vrg00at01 O41 070E 1LIVA•t1VM.1W'MZtl3077%7'700N1 M1t11� 11 Wg000tu ; O]DN IrAy1'19gDNr9uWp1 i1n31 ilm"M1LiLN A59a10LIrLua000t1C V OOOLL'HM'0W'390N1SMNOH jl'O3lMSHdII 1500 (aQOaam et81 V1110000 Z9L d[ O'i011.1iM'JNl-3e0tl1S'IIN011 il'Q7'1 I'm Nu900a71L D9L 07ou iNn'.7./•36oalswldL n a9I 900WQpppta[ _ _ OOOLIHM0W3OON1S/NNOH'dl'O3l!MSHdIIb001a1 el WOLQt R.IZ 070E'311WMZTgp 971AYLN303:1113'aBDN15N110NIQm a1INg00a'ML R.0 O:gll'WA� SNtlDN'1tU37(A9►1 g1 AIZ9111 YLg00a L9 AI 6093'71NM1gM91r Mi Yd037913'3101LL4f 3 C00 ImZLae/w'0mis 041 0051'3IWA-MM1'"A1V1V3030X331KOWS lat'01 _ 'a1111�I�000L4 P.IC OJaI'3LIVA"17YM'bwNL330VS caoLVI 9.91'J rnezlz of nlpaOSL ml .It ODOC 9lMM'TIMN�SIrML Nlicut 3-3MISHM" id km ' al rm00oott OSt CM 3l� 11A TWM7nAVCN9p901L3'3g0N►9 WOL V�OQpa19 Q.L O�SI'31HMTVA1'Dw AK113030%9.3aDuke ��..AEB901! ntnLEBL L6 SOt 00S t1taA'OtY ArZ tl30lg3',tgpyt9.' 9 100P} LLQaiti'g0000-(Q[baa 07m1'HM"JON'3BDN14wdokl'it'Q➢t IiOD 11 Mu0000Y0t !a Q;,IOC3UNM lt/M'7WNLL13630if3 MOW OIAtlO ONOW03H 30 AID Ab'OZ p!>Rd WILY 'QLdole a6e110Aa6e11oA-1wun� f70fNl03 owp wuaaddV 'ON UQd f71A0Q /JI Imas ,,j 00-m p atop a�uollday datp aBIgl. 96epOA--. 4U-0 aauelslp 0lfpsau9!IddLl d At* %Sl mpo pn ,4woda KIA 3..9t:a,nwadwal luogmV.emp,0uesa0 ,.WI,�tQryIOA 'sp'1 S/9L snLIgLYtl,q LrgPUY'gMW9 %SL 4Wa.5%-VNbaa',AY')1,L91I"qu-ill-l11Nptiv g/4LDuaRaO 418ue1 Ig 1 B/uunm uo paseq suogelnoleO '45ue1 Igol BuluudN uo Paseq—.q.ro e0 41Bua1 eu!uunN 90 H1dd 031SIML OP 19L:81gB3 9L%Nldd O31SIM1Ob191 algao 1ga1 uo paseq suaBgnapO V0000'E:.Bwad.V 00:Ab OZ:a6elloAleulwwl uoP-WN:�Al P-1 VOOOOE:oBwedwV OO:ryb OZ:aBglM leu!uua 9LQNldd O39NLLOb/9L:eIgv3 1 uognrMl adAlrnwlO V0000 E:aeerduy OO:ACOZ:0-Mlauluual uos—j.N.a sjmn'1110 ELbto E915 oworyyny!O tolls "017q — - tD19.WMAHIt CM1, £JIS1!noj!O 00:P1eO Sd:laved suo!lelnoleO 1!no1!O MIS:Eno1!0 00:P1eO Sd:laued suogeloleo 1!no1!O LJIS:I!nol!O 00:p1eO Sd:laued suo!le!noleO l!no1!O WL 4VB9ZZ :lu-,wnh.,k t,% 9p 0 .1N 9:ew!l—1V 4V9 L wH bZ:ewg Agpu%S CLISOR000 YLaC000 Pori`smmruVsropPl'V_t_u0_OI09L rAerrr41191gg Cl �►d�N �N000l1at5m f t t—�.» .« ell Q ,v Q 7NMt'Qitl'Ow :390N19:19g11 Yw000riail �VVO00✓16- 0 Q __ .___..IWI_N11011�a1' _-Iwttl•1M1 Q w00000 o OM41JWofdW1A3a1f9fg3WMpl11U011 1Allft .rW9:19efm'.nwommt awDODO0 f 3I1VAltYM•Dw'M9 Ism mM'a la"tlOH 001 YIIIQQOIY1at •MAOWQt9 o awOp000 3L1/M tt.M'Dw MLt13D3J1'13 A10N1a mis III l3l131 Wit"' ---- awaaoo0 wn'xti-3e0rtsaamM'n-071 MSHA11 v'V00000 bILg000'0 Yugo000 TODW60 - IQWAIY[i NOLLOv 3'IYJIYNOUr14 iVW 1 L' L-Lw 9060ZI, ree`o'oe1 !NVO.OI!S_Y awoo Do awOQ3D0 9 .LM�31Wri'OLOHe 150 i I WW 1 _ 9W 000E-N wtq^WNo Qt� VuVaOC9K�HIGOOOSLZ wb000 sL 7w00GV SL - _ 301a/dL3N&UOdi11N01 1 1 _ Pwd11b.71!IWd IY11111 Or101' w1eIV _ A9Pue1S IeWl A9Pue1S— - 1(l. ON fled. MOW OIAVO u�aMYoaaltataol dr/ra1N391tta1w�oeoFN9dwlrw 0096'06Z-.Z6 66 JNIOline Sd:laved 1ol suoge!noleO keNeB t'om"VM•A�aA3 P.-Z uosq,M0 DELI 'ONI NOU03108d 3NIj AV z I £ I v 1 s 1 s 1 i e I e 1:13ewnN L331-Is 3NVId !DNINNII E) CImlO 3ilS NVId VNINNII EJNIaime 311S WHV1V 381A N NOI1 dIa D530 139N6 MO1l3A x L N33a0 x L M0113A x t'N3980 x t 3 3Lx�ni x L 311HM x I.'3n19 x t N�V18 x t 03a x I, NOV19 x l'031!x t l m NH Hl= 9W NHHl x�, D H11M 11naN0 _ H11M lino oD, V 0= n m 3 _ _ .�JQ�B _ D z I - _ �'`----11 - I l - - i -- �- m trii li l + l l I - - - I -311 x me=Z. 1 r''.._- — NO x a3a x 9 1 3WVN 103r0i1d 1 `II` 9LM Hl%L r I I I I j II ' =i'N3Hafl x t 9L/Ot/ol -:11Vp x L N33al t �I i 3L x t 3nl8 x l� _ 311HM=L M x t L I]3sl x_ Movie x t = HLM x cn S&P NHH x 1 _ H11N1 na It I _LLB U -o e _ ><=►' s.x_► �_L 'SGI8 9 '9a�8 , 5 'Ja�B -- -��_ -movi x t'3n113 x� - I it NOVl9xl'o3aXL L_ - ( r --. D I V/ 8 1 II M H11M imaN0 9 Y •V a 8 f f Mol�1Ax L�N33HO x 1SIl 133HS ---- 31t►tM x L 3me x L .- MOT3A x t N33ao x L -V •9a�U ! NOvlexL axL j -- I � -- BMNHHlx � � MIV'19xL 3LxL l3 I _�• — } 1 MOT3Ax L N33HO x t HiWI11nON0 r BFRNHNI= I 7 1HMxL 3fll9xL "P x t 03a x t. llfla _ NOI1dIbOS30l31Va 8t/NHHl 02l003N NOISIA3a - -- 11I BLIM4UnQNQ* J �* _ �- x x / Ll'JNla�ln9 d0 W8 a313 NI 031VD0�39 Ol i3311no 3313 b � N ~; N�OV1_ 9 LtJ L X09 NOIlDNnf a31Vi1 HOOOlnO MOIi131X3Irl "#wog L Ax xt14 \\ ccoll'i 3IHMxL3n19xt A e� y N9tll8x t 3a=L ` \ Dtll 9LN 03a xt g zm M�l03 �U�pl! HUmiinoiuo 7i H11Mlln (SlIV13aWMV1V3Nl=lEftallns O N33aOx L I I / NOd SJNIMV21a WNV1V 3NI=l 33S 1 L4 ONlallne _x&n e x M0113A x N33al Il I U n 1 J O / NI dOVd NIVW 3Hl 1V a3211ntM SI lInOL110 dWVOZ I __x x ,nB-xtx 1 x x 311HM Came t r mowamva In ' 1 ttiNHHtx a 9*1.'a3a x l ` Q OVAOZ6 a31VO1aM x 4 'AlddnS N3MOd 310W311 UNOW03UJDAI13 ' I �� lµ 90NHHlx9, L 8 �� / HOV3 mo=i vnONIO dWVOZ OVAOU 031V01a3a I H11M L1nON0� l � � � `�� x 6 32iIn03a SW002!83SRl 2131NNIadS 32i1d llV(V -(L6°JNIalIn9 NI MOl13AxZ N ORE) I /! / f 031VOO1 SI dOVd 311S 3HD L6 EJNIalm Ni WOON 311HM x Z 3n%B. �� ' J.. :' 1VOINVHO3W/1VORilO313 3H1 NI a311no V Ol 1IdlH ' - 'NOV1H x Z'03a= r MOT x N33a0=L ti --•- } / nnoT3A x L N3 O x t 91ary_HHlx r• 3 IHMxL 3n19x t: I_ `^► }^-� 3i1HM=�inG Nna 39 Ol`JNI211M/S11naNOO JNIHNII JNlalln9(£ motne x L a3"'•M x-I / •vave �l1[- �M11f10N0_, j8 SNr/ld 11 t � Hx ONIalIn9 1VnO1AIGNI NO a3SV9 3NV NMOHS ruG08000 +` �' _ r / f SNOUVOOl X09 NOIlONnr'NMOHS SV 3MIM 0MV d WAN 1 _- �, �, •�a,8 V j 'i r f n d0 WnWINIW V HIM WOOM U3SIN U31NNINdS F"ov - 7 HOV3 d0 llVM aOR131X3 3H1 NO NO ClNIalIn9 gam . HOV3 d0 WOOa N3SIN N31MNINdS 9MU 3Hl Ni 3 n I _ }`j a31VO01 39 Ol 3NV NMOHS S3XOS NOIlONnr(Z 31 006oz/ II _ __-�`l�el +-l-rr jl r 'ONISVHd 103roNd ONV dOOI V SSV1O V L �_ .j Z M0113Ax t'N3380 x I, NO=l NMOHS SV 3N0a 39 1snW JNINNII JNIalIn9 7"FJ 1 311HM x t•3n19 x► 'NVIOIN10313 3Hl AS a3NIWN313a 3e Ol 31nou 1 - ^ ^ >oV19 x t'a3a x i ��, - Ja�B- 9t=NHHl x9 i3VX3 3ON3N3d3N MOd 3MV S31n02111naNOO(4 MOW a3nva I+ _- - �• i /// ---, - «<JJJ _ __ Him imONO b0096-06Z'USZP,a en3 --� I ``'--� `� "' S310N NOIJLV-II �1SNI '0N1 N0110310ad,t z e v s 9 L e I 6 eune-1'uosiale 1p NO0 Nexw7gz 0 uogea!1 V I!waad w.ielb allyLLt1 AdbZ:bS:Z9L0Z/tZ/0l. eunel 'uosia;a ;po 71Jed Sao S aJI3 W1 Ad 17Z:bS:Z 9LOZ/17Z/0L eune-i uosJala 1 'Zaaed SOa S OJIJ LLt# Ad bZ:bS:Z MZA001, Aq .apeol al!d peoldfl Malnaa U1 Japue1O ulna 960Z/L/4l wjL'FV oj!A 9LOZ/bZ/00 IALZO.ld3HI sa!jlsnpul pue joge Ho_LOVaINO01 woa @pleas! ! pine 0096-06Z-9Z Mold P!AeR ONI N011031O2ld 3a1 @dAi jolociluoo • •O AJcw'Jd OweN J0PeJlu03 17OZ86 VM`113N3A3 3N anuany 4ILL LZZOZ (IN ONISVO 1S3M OZOL 011 1N3W1S3AN1 NO1JNI-IaV 4M Oil 1N3W1S3AN1 NO1JNI-18V GM £060000066Z800:#IGDaed uosJa;ad eune-I of PeuBlssV s;uaw;aedV asn posodOJd 0 saljo;s;o jagwnN peo-1 Aouednoao/uol;*nj;suo:);o odA.L 0 ;aa:j aienbg sojidx3 WuMd ponssl ;luaJad pa!lddy sn;e;g 00,005E uol;enleq L6#'3N anuany q;LL LZZOZ ssaJPPV a;Ig wjely and edAl;IwAad woo'algeas!d;@np!Aep IleW3 0096-06Z-5Zb auoyd MOIN p!neQ ;*e;u03 bOZ86 VM'49aaA3 dlZ le;e;g °A;13 peon{uosg10 O£LL sseippV ;ueoilddV •oul'uo!;aa;oJd end aweN ;ueollddV LL Nied awery ;aa[oJd 56L4 jagwnN ;IwAOd 9LOZ/bZ/06 a;ea mmi . • t � i(= ■ To ■ T ■ 0 ■ ■ J ■ 7 ■ ■ 1 IMMEMEN ' . ■ ■ 01 ■ 571 ■ p2. MEN . . ■ ■ ■ ■ ' ■ immommom m r � r7 ■ ■ ■ M ■ ■ ■ ME No - IMEMEN IMMEME ME ■ ■ ■ 0 ■ ■ ' . ■ ■ ■ ■ ■ ME 0 ME ■ ■ ■ ■ ■ 1 r 1 1 . . . ■ ■ 'No I I F ' ` T ■ ■ 1 d191/9 I;o I 86ed woo panlaoad oleo #ld!aoa}3 d 93M pan!aoaa lunowy Iaaooy I!uLed 94OZ if 00 A-NO C / SS b 3Sfl dd'd1SliOd PeAI909H aweN slueollddV lulad oleo amleu6lS slueollddy MOW dlAVa 9 60Z/tiZ/0 6 uoAuHseM;o 9191S 94110 suolleln6ai pue salni`smal a41411Ma j , pagposap anoge 94110 asn eql pue Aouedn000 941 pue `uo uollonalsuoo ayl leyl pue loaajoo sl uollewao;ul anoge ayl�(;il�ao IfPA ga ayd j uollej ldx3 LT/TE/L lWTZO*Id3l JagwnN asueoll s,ioloeiluo3 VOZ86 apt dIZ VM.a1e1S 113a3n3 .b113 .ssaippv 0096 06Z SZti''agwnN auo4d GVON NOS.91l?e0CL�leouloay JNI NOU-D3102dd 3a1A :llew3 MOW GIAVa _ - :uosaad loeluoO WOJ'3-LLLVBSId3N7al/�Va Li/IE/L uollealdx3 :jagwnN asueol-1 s,joloeiluoo IWTZO*Id32I13 ti0Z86�apaJ d!Z bM .a1e1S 113213n3 An GV021 NOS8IE OOELT :ss"ppV jegwnN auoyd 0096 06Z SZti 3NI NOLL33IOLId 3ldIJ a°1oea;uo3 ti0Z86 aPaJ diZ vm:a1eiS - L3a3n3.A113 dV02I NOS819 OELT :ss"ppV WOJ'3111V3SId=l@)GI VG 'llew3 0096 06Z SZti auoyd I103 0096 06Z SZti:aagwnN auo4d MOW alnb'd:uosaad 10e1u03 ti0Z86:aPo`J dIZ vm :a1e1S -L13d3A3:40 M OVOZl ONISVJ OZOi _ssa'PPV ETTO TL9 09E "'agwnN auo4d SIN3WIS3ANl NOIDNI-IaV CIM :JeUA°O :uogenleA :(13 bS)earV pl 6ul In 00,000E OOOL a Z:slaued/seuoZ;ojegwnN :#al laoJed 601-E0100000T6Z800 Ti ONI(ning 3N 3AV HILL TOZOZ :ssai ppb'loafoad uoIIIPPdNOIIeJGIId uiaeld 0413 waelb aal3 MaN Q (auo)Ioayo) :Ilwaad}o adAjL Ol a3SOdOad 1N3Wdino3 NO NOLLVWdOdNI H3H10 lIV ONV`ONIHIM 1NIOd Ol 1NI0d) `WI 80VIO JNIN M`S133HS NOLLVOLHOUS 3anl3N1'OSIV'3l8VOIlddV 383HM SNVId'1V31H133l3 3unioNl'NOLLV31lddV 11W113d WaVIV 3a13 HOV3 UOd SNVId a3lV3S aNV 313ldWO3 c10 S13S(Z)OMl A8 a31NVdWO33V 381sm NOIIVOIIddV SIHl 199E-£Oti(09£)0uo4d •£ZZ96 VM• 9N 8AV 4169 DOZ8 G •uol6ut luowdolaneQ alwouoo3 v Allunwwo I �°Al!:) 3uawNedaa N0l.LV3llddV llWH3d wmvi 1 3ml:f I i Qa c 910Z t9 iJ0 pania0a6 KM 'uO45UTTzry aH GAY g,4LL TOZOZ *TT buzpTTng* squeupandY LL 312 ed zlis gor zoo-zbz809# MEMO In rlmzo*IazuIa #73sm VOZ86 KM '4492aAg •pU uosgig OELT -oul 'uOT409402a azTJ XKvdraoo HoisvirlvlsHi -bui4684 aouv4dsoo8 203 rxy ago buiTTWO 04 zoizd p949TdmOD Pug pe4onpuoo aq TTggs mz09 YdJK pug 4884-92d TTn3 V -squemazinbaz YdJN zad BDugu94UTVM pug 60TA28s zadozd aqq 203 9020g uT sT 4uamaazbg BUT204TUOM pug 80TAz88 TTn3 H 'Spa zuy oxiazzas 7wiNzaisz i Ni azar isms 38 Oy szoiA8a Noiivoijixom zRoanazis MOZ) 'gnogbnozg4 mnmTuim sa SL eq TTggs 8a 20iz94ul •spzgpug48 YaJX RITA aougiTdmoO ut aq TTVRS A4TTTgTpnv 'KM 'XZOV7 284UBO =VTV ally 'u0T4V4S TgzIua' p048TT In giA papiAozd aq TTggs buT=04Tu0H -sTgubis sTgnozq 94g2gd9s sg TTam sg U0TgVATgDV auoz Aq zogzuom TTggs ma4sAs agy -paTxuTxds-ATTnJ sT buipTTnq sqy -s4u9mazznb8z TguOT4TPPg znoA pug quezzno OZK 'ZTOZ OJI '08I 'OKM sg TTam sg squemexTnbaz uoTITpe £TOZ 'ZL YdJK zad peubisep uaaq sgq ma4sAs agy •aAz40g TTTA Z80TAap uoTggoTgTgou qugdn000 s ,buTPTznq zaggo ou 'pazabbiz� si buipTinq �gg� ui aOTAaP buiggtgTUT ug UBgA 94VAT40V ATuo TTTA saoTAep uoTgvoTgTgou qugdn000 buTPTTnq TvT4u6PTs8g -LT buTPTTnq uT P84vDOT d3YJ ago qg osTg pug buTPTznq oTgTosds ggg4 uT 204gTDunuug ago Ig 04vTDunuug TTTA IT 'buTPTinq Tgi4uapisaz g uT P94VAT40V ST uOT4v4s-TTnd To =04094BG axomS 'us0T9xQ4vf4 g usgM -umogs sg dOOT V ssgTO g uT unz eq TTTA Sf18S Pus OZS agy -ugTd buTXuTT buTPTTnq egTs papnTOuz ago uo uAOgs sg buTzTx/gTnpuoo buTAuTT buipTTnq bu-rpiAozd azg (0iz409T8 ssazdxg) 8uvT0Tx40aT9 84Ts agy -LT buTPTTnq uz pa4vDOT dOYJ eqq Aq pezogTu0m pug oq peTj eq TTTm sm848As zaTAutzds sbuTPTTnq TgiquaPTsaz TTY -ATddns xemod agomaz pug zogvTounuug =vTg 9zi9 TgnPTAipui UKO ziagq aegg TTTA sbuTPTTnq TvT4u9pis8z TTg ' (buTPTTnq AgTunmmoo a-4is aq-4 si bu-rPTTnq sigq 30 z00T3 .79KOT ) LT Bu-rp-rTnq ui pa-4vDOT aq TTTA dOVJ eql, zlsxs HUVW ZULH g z09 sugTd pasOTOua puTJ asgaTd xmLsAs xsvw mula !" ANIASH 1 V7cT - NOJ.OAiI'lHV 3O AIia 9109'01 AW130 91wegs(9111 xv] 9991-989-008-180 0096-061 19111 Z8086 vm 111380111W 999911I08 Od 'ONI `NOIl03l00d 1911 9NLS63aa**maK# ZSHZOI'I NNMKZ kMOr YM TVI-S-90 --d-o-a abmomazu 30 1CSIa V060ZT# £-SSOIN ssu5Tssa/suoiggs9dp 3o dA mox PTAga -ATgaasip am gogquoo og asag Taa3 asveld 'suoigsanb saggsn3 Aug sAgg noA pTnogS •Tgubis sTgnosq g so3 ssnvO TTggs sauoz Aug uo suadp •uoigipuoo AsosTmadnS g asngo TTggs sauoz sig AOT-TH Pug sadmeg 'AId uo sgsogS 'msgTg g asngo TTggs uOTlvgs TTnd pug (Asp pug qem) 'sagogTms AOTgxsgvM 'axoms WMI uo gsogs V •Tgubis AzosTAsadns g so3 buisngo 'sgTSZ qg aggAigog TTggs sig A0q •spuooas Sy uggq asom qou 30 poissd g Aq papsggas sq TTggs SNH<aiTY AOTgasgYK gsM •psTgjgou aq TTggs Tsuuossad gogquoo AOusbssms agis up ( 'aggATgog TTggs sgTnoxTo uoTgvoTgTgou ON 'agis og aoiAsas sauuns Ida goggdsip TTTA gOTMA SO oq gTmsugsg TTggs sTgubis AsosTAsadns pug sTgnosy •aoTAsas sauuns Ida goggdstp pug asi3 oq goggdslp-as 'SO oq suoz msgTg puss 'sggATgOg oq sgTnosio u0igv0T9Tg0u TTg s03 asngo TTggs msgTg 30 sauoz •uOTlvgS Tgsguaa pagsTT 'III A3igou agomas sg TTSA sg avgj qv agvTounus TTggs suOTITMoo aTgnosy pug msgTY TTV sHoisAMMIao 3o HONZa gs 'sapTTnq sad 'sbuT46TT OSII sad so3 pagsTT sg aq TTTA magsAs uoiggoTgTgou pug T0sgu0D msgTY asz3 aqq Aq paojAsas sgasg TTV ZONVE asiom sHZzENa sapTTnq sad sassbap 89 qv aq TTggs sgasg uommoo 'saasbap Ob AOTsq TTg3 TTggs quamdinbe aotAsas msgTg MgTA gasp off sM,nIVEMMs sHZiMM •ouI 'uoigoagosa 82TJ :buigssy :soiAsaS :buisogzuON :uozggTTggsul sZisEaa ZzgisHoasZU zvnsovusHoo ZO-66LZ06# IUMD 'III T660-6Zb-008 MM 'AsOva 3S *OAV WE 00£b Ida/ 'Oul 'saqusO msgTV .xKvciNoo vNiuosixoN an azAoxaav Date: 04/03/2026 Permit#: 1195 Perm Date: 10/24/2016 Review Date: 10/24/2016 Perm Type: FIRE ALARM Review Type: FIRE ALARM Target Date: 11/07/2016 Scheduled Time 00:00 Com pleted Date: 11/08/2016 Description: Ok to issue Review Status: Assigned To: z.Christopher Young Tim eln: 00:00 Time O it: 00:00 H curs: 0.0 Property Information PDrcel#: 00829100000103 W ARLINGTON INVESTMENT LLC WDARLINGTON INVESTMENT LLC 1 020 WEST CASINO RD 20227 77th Avenue NE E VERETT,WA98204 Zoning: 910 Undeveloped (Vacant) LandLot: Block: jari@william anvest.com Permit#: 1195 Permit Date: 10/24/16 Permit Type: FIRE ALARM Project Nam e Park 77 Applicant Nam a Fire Protection, Inc. Applicant Address: 1730 Gibson Road Applicant, City, State, Zip: Everett,WA98204 Contact: David Mow Phone: 425-290-9600 Em al: david@fpiseattle.com Scope of Work: Apartm olts Valuation: 3500.00 Square Feet: 0 Num ber of Stories: 0 Construction Type: O xupancy G ioup: ID Code: Permit Issued: 11/16/2016 Permit Expires: Form Permit Type: Status: LASERFICHE Assigned To: Launa Black Property Parcel# Address L egal Description O wrier Nam e Caner Phone Zoning 00829100000103 2 0227 77thAvenue NE WDARLINGTON 910 Undeveloped INVESTMINT LLC (Vacant)Land Contractors Contractor P rim ay Contact P hone A ddress C ontractor Type L icense License# FIRE PROTECTION David Mow 4 25-290-9600 1 730 Gibson Rd CONSTRUCTION UBI 601 848 346 INC CONTRACTOR FIRE PROTECTION CONSTRUCTION Labor and INC David Mow 4 25-290-9600 1 730 Gibson Rd CONTRACTOR Industries FIREPI*021ML Inspections Date I nspection Type D escription S cheduled Date C om lieted Date I nspector S tatus 08/31/2017 FA00.FIRE ALARM 08/30/2017 B UILDING C om Iieted FINAL Plan Reviews Date Review Type D escription A ssigned To R eview Status 10/24/2016 FIRE ALARM O k to issue z.Christopher Young Attached Letters Date Letter D escription 11/10/2016 Building Perm i Notes Date Note C reated By: 09/01/2017 Bldg.#10 Kristin Foster 11/08/2016 See Master Alarm Perm 1#1194(Phase I)for fees.This Perm i contains Type A Units. C hris Young Uploaded Files Date File Nam e 11/16/2016 1953071-1195 Issued Permt.pdf 10/24/2016 1909820411 Fire Alarm Perm i Application CgZBJlmxaNgCGK.pdf 10/24/2016 1909821-#II Fire Specs Partl.pdf 10/24/2016 1909822411 Fire Specs Part2.pdf