HomeMy WebLinkAbout505 E 3RD STREET_BLD3291_2026 NOTICE
TO PERMITEE AND/OR OWNER
❑ PARTIAL APPROVAL ❑ CORRECTIONS REQUIRED
❑ DO NOT OCCUPY E'APPROVED
PERMIT#: I AM PM DATE:
JOB ADDRESS: b 5 E :„ LOT#:
PROJECT:
TYPE OF INSPECTION:
OTHER:
❑ NO PERMIT-STOP WORK-OBTAIN PERMIT
❑ CONSTRUCTION IS NOT IN ACCORDANCE WITH APPROVED PLANS AND
PERMIT -STOP WORK
❑ STOP WORK UNTIL AUTHORIZED TO CONTINUE BY INSPECTOR.
❑ CORRECTIONS LISTED BELOW MUST BE MADE BEFORE WORK CAN BE
APPROVED.
❑ WORK NOT READY FOR INSPECTION: $50 REINSPECTION FEE (PER IBC)
MUST BE PAID PRIOR TO NEXT INSPECTION.
❑ CONTACT INSPECTOR 360-403-3551 ❑ CALL FOR REINSPECTION
THE ACTIONS OR CORRECTIONS INDICATED ABOVE ARE REQUIRED WITHIN DAYS OR
PENALTIES IMPOSED BY LAW MAYAPPLY.
FOR INSPECTION CALL: 360-403-3417
'-/-.-)5-d oDo
INSPECTOR DATE
Cl PLANNING Cl CIVIL Cl BUILDING CITY OF ARLINGTON
CITY OF ARLINGTON
18204 59th Avenue NE,Arlington, WA 98223
INSPECTIONS:360-403-3417-Permit Center:360-403-3551
BUILDING PERMIT
505 E Third Street NE Permit#:3291
Permit Expiration Date: 12/28/2020
Parcel#: 31050200401500 Valuation:2119.00
OWNER APPLICANT CONTRACTOR
ARLINGTON SCHOOL DISTRICT 16 Commercial Fire Protection,Inc. Commercial Fire Protection,Inc
315 N FRENCH AVENUE 17199 Bennett Rd 17199 Bennett Rd
ARLINGTON,WA 98223 Mount Vernon,WA 98273 Mount Vernon,WA 98273
360-848-9093 ext113 360-848-9093
LIC:COMMEFP132MM EXP:08/I6/2020
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR: 2015
STORIES: 1 CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: I OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for, or approval of,any violation of this Code or any
other ordinance or order of the City, of any state or federal law,or of any order,proclamation,guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order, state or federal law,or any order,proclamation,guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBCI 10/IRCI 10.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
aaoM q, by ON Wk4 w
Della Dellinger W.UE Della Dellinger 7/16/2
as 7 � �
Signature Print Name Date cleased By l Dat
CONDITIONS
1. Permit and set of approved plans to remain on site during installation. 2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections; may include hangers,earthquake bracing,
sprinkler locations and pipe re-rousing that could impact hydraulic calculations.Failure to submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is conducted.3. Hangers and earthquake bracing shall be
installed in accordance with NFPA 13.4.Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom.5.Hydrostatic test required:working pressure for 2 hours minimum 6.Sprinkler system
Contractor's Material and Test Certificate shall be submitted prior to close out of permit.7.Owner shall be provided with a set of
approved plans and associated documents for their files. 8.Adhere to approved plans.9.Approved job copy shall be onsite for
inspections. 10.Call for inspections.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS,SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
07/16/2020 Fire Sprinkler Permit $75.00
07/16/2020 Processing(Technology Fee $25.00
07/16/2020 Fire System Plan Review $100.00
07/16/2020 Credit Card Surcharga $6.00
Total Due: $206.00
Total Payment: $206.00
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
CITY OF ARLINGTON
` 18204 59th Avenue NE,Arlington, WA 98223
INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551
BUILDING PERMIT
Permit#:3291
505 E Third Street NE Permit Expiration Date: 12/28/2020
Parcel#: 31050200401500 Valuation: 2119.00
OWNER APPLICANT CONTRACTOR
ARLINGTON SCHOOL DISTRICT 16 Commercial Fire Protection,Inc. Commercial Fire Protection,Inc
315 N FRENCH AVENUE 17199 Bennett Rd 17199 Bennett Rd
ARLINGTON,WA 98223 Mount Vernon,WA 98273 Mount Vernon,WA 98273
360-848-9093 ext 113 360-848-9093
LIC:COMMEFP132MM EXP:08/16/2020
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR: 2015
STORIES: 1 CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: i OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any
other ordinance or order of the City, of any state or federal law, or of any order,proclamation,guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order, state or federal law,or any order,proclamation, guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC 110/IRC110.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
Signature Print Name Date eleased By tl bat
CONDITIONS
1. Permit and set of approved plans to remain on site during installation.2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections: may include hangers,earthquake bracing,
-�
I
sprinkler locations and pipe re-rout' )hat could impact hydraulic calculations.Failt submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is conducted. 3. Hangers and earthquake bracing shall be
installed in accordance with NFPA 13.4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom. 5.Hydrostatic test required:working pressure for 2 hours minimum 6. Sprinkler system
Contractor's Material and Test Certificate shall be submitted prior to close out of permit. 7.Owner shall be provided with a set of
approved plans and associated documents for their files. 8.Adhere to approved plans. 9. Approved job copy shall be onsite for
inspections. 10. Call for inspections.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
07/16/2020 Fire Sprinkler Permit $75.00
07/16/2020 Processing/Technology Fee $25.00
07/16/2020 Fire System Plan Review $100.00
07/16/2020 Credit Card Surcharge $6.00
Total Due: $206.00
Total Payment: $206.00
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
CITY OF ARLINGTON
` 18204 59th Avenue NE,Arlington,WA 98223
INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551
BUILDING PERMIT
505 E Third Street NE Permit#: 3291
Permit Expiration Date: 12/28/2020
Parcel#: 31050200401500 Valuation: 2119.00
OWNER APPLICANT CONTRACTOR
ARLINGTON SCHOOL DISTRICT 16 Commercial Fire Protection, Inc. Commercial Fire Protection,Inc
315 N FRENCH AVENUE 17199 Bennett Rd 17199 Bennett Rd
ARLINGTON,WA 98223 Mount Vernon,WA 98273 Mount Vernon,WA 98273
360-848-9093 ext113 360-848-9093
LIC:COMMEFP132MM EXP:08/16/2020
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
A& JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR:
STORIES: CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: OCC LOAD:
MEW
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any
other ordinance or order of the City,of any state or federal law,or of any order,proclamation,guidance advice or decision of the
Governor of this State.To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid. The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City,or of any state or federal law, or of any order,proclamation,
guidance advice or decision of the Governor.The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order, state or federal law,or any order,proclamation,guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/iRCI 10.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
� l3
Signature Print Name Date Released By bate
CONDITIONS
1.Permit and set of approved plans to remain on site during installation. 2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections: may include hangers,earthquake bracing,
sprinkler locations and pipe re- ',ng that could impact hydraulic calculations.F`)e to submit revisions could result in
cancellation of an inspection while..review of an as-built resubmittal is conducted. 's.riangers and earthquake bracing shall be
installed in accordance with NFPA 13.4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom. 5.Hydrostatic test required:working pressure for 2 hours minimum 6. Sprinkler system
Contractor's Material and Test Certificate shall be submitted prior to close out of permit.7.Owner shall be provided with a set of
approved plans and associated documents for their files. 8.Adhere to approved plans. 9.Approved job copy shall be onsite for
inspections. 10.Call for inspections.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PEWMIT FEES
Date Description Fee Amount
07/13/2020 Fire Sprinkler Permit $75.00
07/13/2020 Processing/Technology Fee $25.00
07/13/2020 Fire System Plan Review $100.00
Total Due: $200.00
Total Payment: $0.00
Balance Due: $200.00
C':kl,L FOR INSFEMOIiS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
i �.,
:!
4
•
Permit#: 3291
Permit Date: 07/01/20
Project Name: Arlington School District
Site Address: 505 E Third Street NE
Company/Applicant Name: Commercial Fire Protection, Inc.
Company/Applicant Address: 17199 Bennett Rd
City, State, Zip: Mount Vernon, WA 98273
Contact: Della Dellinger
Phone: 360-848-9093 ext 113
Email: della@cfirepro.com
Permit Type: Fire Sprinkler
Valuation: 2119.00
Square Feet: 40
Number of Stories: 0
Type of Construction:
Occupancy Type:
Scope of Work: Sprinkler relocation
MIC/Opportunity Zone:
Permit Issued:
Permit Expires: 12/28/2020
DNU:
Status: IN PROCESS
Property
Parcel# Address Legal Description Owner Name Owner Phone Zoning
ARLINGTON
31050200401500 505 E 3RD STREET SCHOOL
DISTRICT 16
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
Commercial Fire Della L Dellinger 360-848-9093 17199 Bennett Rd CONTRACTOR Labor& COMMEFP132MM
Protection,Inc Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
07/01/2020 Fire Sprinkler Building In Review
07/01/2020 Fire Sprinkler Mike Makela In Review
" :.
� _
4�
I
1
Fees
Fee Description Notes Amount
Fire Sprinkler Permit Commercial NFPA 13/13R $75.00
Processing/Technology Fee $25.00
Fire System Plan Review Table 4-2 or 4-10 $100.00
Total $200.00
Uploaded Files
Date File Name
07/01/2020 6917282-3291 Plans.pdf
07/01/2020 6917283-3291 ApplicatiMp-d
c� 1"NK4 r FIRE SPRINKLER
PERMIT APPLICATION
Department of Community &Economic Development
City of Arlington• 18204 59th Ave NE• Arlington,WA 98223• Phone(360) 403-3551
THIS APPLICATION MUST BE ACCOMPANIED BY TWO (2) SETS OF COMPLETE AND SCALED PLANS, TWO (2)
SETS OF HYDRAULIC CALCULATIONS, TWO (2) SETS OF EQUIPMENT SPECIFICATIONS FOR EACH FIRE
SPRINKLER PERMIT APPLICATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO INCLUDE
SPECIFICATION SHEETS, WIRING DIAGRAMS (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON
ALL EQUIPMENT TO BE INSTALLED PRIOR TO INSTALLATION.
Type of Permit: ❑ New Fire Sprinkler ❑✓ Fire Sprinkler Add/Alt ❑ Underground Fire Line
Project Address: 505 E. 3rd St. Parcel ID#:
Project Valuation: 2119.00 Number of Heads: 1 Building Area(Sq Ft) 40
Owner: Arlington School District #16 Phone Number: 360 631-3116
Address: 135 S. French Ave City:Arlington State: WA Zip Code: 98223
Contact Person:Mark Webb Phone Number: 360 631-3116
Cell Phone: 360 631-3116 Email: mwebb@asd.wednet.edu
Address: 17199 Bennett Rd City: Mount Vernon State: WA Zip Code:98273
Contractor: Commercial Fire Protection, Inc. Phone Number: 360 848-9093 EXT113
Address: 17199 Bennett Rd. City: Mount Vernon State: WA Zip Code:98273
Contractor's License Number: COMMEFP132MM Expiration:08/16/20
Contact Person:
Della Dellinger Email:della@cfirepro.com
hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the above-
described roperty will be in accordance with the laws,rules and regulation of the State of Washington.
�P,ll.2�elf�sr�e� j
06/30/2020
Applicants Signature Date
Della Dellinger
Print Applicants Name
/ FOR STAFF USE ONLY Receivem
J U N 3 0 2020
Permit# Acce By Amount Received Receipt# Date Received
WEB Forms—131 Page 1 of 1 6/16LP
i
I
-, �� �
I
Permit#: 3291
Permit Date: 07/01/20
Project Name: Arlington School District
Site Address: 505 E Third Street NE
Company/Applicant Name: Commercial Fire Protection, Inc.
Company/Applicant Address: 17199 Bennett Rd
City, State, Zip: Mount Vernon, WA 98273
Contact: Della Dellinger
Phone: 360-848-9093 ext 113
Email: della@cfirepro.com
Permit Type: Fire Sprinkler
Valuation: 2119.00
Square Feet: 40
Number of Stories: 0
Type of Construction:
Occupancy Type:
Scope of Work: Sprinkler relocation
MIC/Opportunity Zone:
Permit Issued:
Permit Expires: 12/28/2020
DNU:
Status: W PROCESS
Property
Parcel# Address Legal.Description Owner Name Owner Phone Zoning
ARLINGTON
31050200401500 505 E 3RD STREET SCHOOL
DISTRICT 16
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
Commercial Fire Della L Dellinger 360-848-9093 17199 Bennett Rd CONTRACTOR Labor& COMMEFP 132MM
Protection,Inc Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
07/01/2020 Fire Sprinkler Building In Review
07/01/2020 Fire Sprinkler 1.Permit and set of approved plans to remain on site Mike Makela Approved with
during installafi(II—) Conditions
2.significant deviations from approved plans made during
installation shall be required to be resubmitted for review
prior to inspections:may include hangers,earthquake
bracing,sprinkler locations and pipe re-routing that could
impact hydraulic calculations.Failure to submit revisions
could result in cancellation of an inspection while a review
of an as-built resubmittal is conducted.
3.Hangers and earthquake bracing shall be installed in
accordance with NFPA 13.
4.Relocated EC sprinkler shown on drawing appears to be
greater than maximum allowed distance from north wall
of classroom.
5.Hydrostatic test required:working pressure for 2 hours
minimum
6.Sprinkler system Contractor's Material and Test
Certificate shall be submitted prior to close out of permit.
7.Owner shall be provided with a set of approved plans
and associated documents for their files.
Fen
Fee Description goiffiaiii,, Notes Amount
Fire Sprinkler Permit Commercial NFPA 13/13R $75.00
Processing/Technology Fee $25.00
Fire System Plan Review Table 4-2 or 4-10 $100.00
Total $2N.80
bates -
1f)ate � Note Created By:
1.Permit and set of approved plans to remain on site during installation.
2.Significant deviations from approved plans made during installation shall be required to be
resubmitted for review prior to inspections:may include hangers,earthquake bracing,sprinkler
locations and pipe re-routing that could impact hydraulic calculations.Failure to submit
revisions could result in cancellation of an inspection while a review of an as-built resubmittal
is conducted.
07/13/2020 3.Hangers and earthquake bracing shall be installed in accordance with NFPA 13. Kristin Foster
4.Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom.
5.Hydrostatic test required:working pressure for 2 hours minimum
6.Sprinkler system Contractor's Material and Test Certificate shall be submitted prior to close
out of permit.
7.Owner shall be provided with a set of approved plans and associated documents for their
files.
U
Date File Name
07/01/2020 6917282-3291 Planspdf
07/01/2020 6917283-3291 Agplication.pdf
�� :�
a f ..
a
a
I
City of • •
ri
% Fire
Department E 1
�l G •�
July 9, 2020
Permit Number: BLD 3291
Project Address: 505 E 3 d Street, Arlington
Project Description: Fire Sprinkler Plans for Presidents Elementary School
Contractor: Commercial Fire Protection, Inc.
17199 Bennett Road
Mount Vernon, WA 98273
Re: Fire Suppression Shop Drawing Review Comments/Approval
The Arlington Fire Department has completed a review of the Fire Suppression shop drawing submittal and
approved the issuance of the permit with the following conditions:
1. Permit and set of approved plans to remain on site during installation.
2. Significant deviations from approved plans made during installation shall be required to be resubmitted for
review prior to inspections: may include hangers, earthquake bracing, sprinkler locations and pipe re-
routing that could impact hydraulic calculations. Failure to submit revisions could result in cancellation of
an inspection while a review of an as-built resubmittal is conducted.
3. Hangers and earthquake bracing shall be installed in accordance with NFPA 13.
4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed distance from
north wall of classroom.
5. Hydrostatic test required: working pressure for 2 hours minimum
6. Sprinkler system Contractor's Material and Test Certificate shall be submitted prior to close out of permit.
7. Owner shall be provided with a set of approved plans and associated documents for their files.
Items noted above are conditions on the issued permit and shall be verified as part of the final inspection of the
system at project completion. Final approval will not be provided until all conditions are verified. Call at least
48 hours in advance to schedule inspections.
If there are any questions please do not hesitate to call.
Sincerely,
W". C W&&a
Mike Makela
Assistant Fire Chief
Arlington Fire Department
OFFICE COP
Y
��� �, 1
i '
�''. � ta� —�1 1. ' w
zZ CM
O z 2
0
1 c 1 ~ (T 8 _0 clJ
1 0 o U N N 1 CO) W >
C1C oC 1 i-W al Et_J
W w c$ 1 } N 1 as 0 0 c� crs
WN �+ � A! � O r N Z
S 1 eo a _ U
oz—C Q �,' J 1 Q CL ci I �- i 3� LL 0 Wo
a. r £ I5)2z = 1 m Zoo g
U) 2 0 10Uz c I M m¢ 8 ~OTC
z ~ ~ a' 100� M o: S�z off
W � W IzWo >2 _ �( 1 .v ^�zi 8 _Z
CL Z W O Z Q. K Jdm I �_ w O�wcl)
U O r U J � J I Ua C��W - S mI Cn(n�Q
W LJU W y` v ' =OEM -a O ZH-0�
U aC Q U E� m°b g 1 OZccz
Z W U j " �ci� a U) C'3��� W o
U j m O ������������J Z Fn Q c7
J JWWK wW
W O � W Irmo¢ o _Y
Qa.inQ
z
doh Z a
V CL U U W o k W Q c..) LLJ
CC U
- w 5
w J 1
Y ru
0LL
O �VR °' /z� N Q LL. e Y
z
�� 2
ZIP N �w
W w0 X W
- -�_ J W a o
— cr
CL: W
f
—��— --- --- ---- - 0 � Q
C !!rtrt z U
L V
o a O z w
J Z w
m V O W g O
oF_ E. Z Z
z rc Fr in¢ O Q } CL
a
� o Z ~ w oco o O
< ~ ¢ � COEwa cc W Ow00
I- w o a Z U z m
SW_ — Y
W � a �aC� ¢ U ¢ � am
Z � Z zQZ Y J2N � co .. .. .. ..
O � C� =gip z > � U � QW f W
/ram J Q UwJ d Z Q 00 LLiz00 LL
C Z= m LL
Z � a Z a
m W O = z z
f-1 Q a � � U Ir
w
Q N Z p z 3 j
s a
o Qc) <
ArlingtonCity of Fir �
- Department
July 9, 2020
Permit Number: BLD 3291
Project Address: 505 E 3rd Street, Arlington
Project Description: Fire Sprinkler Plans for Presidents Elementary School
Contractor: Commercial Fire Protection, Inc.
17199 Bennett Road
Mount Vernon, WA 98273
Re: Fire Suppression Shop Drawing Review Comments/Approval
The Arlington Fire Department has completed a review of the Fire Suppression shop drawing submittal and
approved the issuance of the permit with the following conditions:
1. Permit and set of approved plans to remain on site during installation.
2. Significant deviations from approved plans made during installation shall be required to be resubmitted for
review prior to inspections: may include hangers, earthquake bracing, sprinkler locations and pipe re-
routing that could impact hydraulic calculations. Failure to submit revisions could result in cancellation of
an inspection while a review of an as-built resubmittal is conducted.
3. Hangers and earthquake bracing shall be installed in accordance with NFPA 13.
4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed distance from
north wall of classroom.
5. Hydrostatic test required: working pressure for 2 hours minimum
6. Sprinkler system Contractor's Material and Test Certificate shall be submitted prior to close out of permit.
7. Owner shall be provided with a set of approved plans and associated documents for their files.
Items noted above are conditions on the issued permit and shall be verified as part of the final inspection of the
system at project completion. Final approval will not be provided until all conditions are verified. Call at least
48 hours in advance to schedule inspections.
If there are any questions please do not hesitate to call.
Sincerely,
UC
Mike Makela
Assistant Fire Chief
Arlington Fire Department
OFFICE C
y �� FIRE SPRINKLER
PERMIT APPLICATION
ItNGV� Department of Community & Economic Development
City of Arlington• 18204 59th Ave NE• Arlington, WA 98223• Phone(360) 403-3551
THIS APPLICATION MUST BE ACCOMPANIED BY TWO (2) SETS OF COMPLETE AND SCALED PLANS, TWO (2)
SETS OF HYDRAULIC CALCULATIONS, TWO (2) SETS OF EQUIPMENT SPECIFICATIONS FOR EACH FIRE
SPRINKLER PERMIT APPLICATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO INCLUDE
SPECIFICATION SHEETS, WIRING DIAGRAMS (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON
ALL EQUIPMENT TO BE INSTALLED PRIOR TO INSTALLATION.
Type of Permit: ❑ New Fire Sprinkler ❑✓ Fire Sprinkler Add/Alt ❑ Underground Fire Line
Project Address: 505 E. 3rd St. Parcel ID#:
Project Valuation: 2119.00 Number of Heads: 1 Building Area(Sq Ft):40
Owner. Arlington School District #16 Phone Number: 360 631-3116
Address: 135 S. French Ave City:Arlington State: WA Zip Code: 98223
Contact Person:Mark Webb Phone Number: 360 631-3116
Cell Phone: 360 631-3116 Email: mwebb@asd.wednet.edu
Address: 17199 Bennett Rd City: Mount Vernon State: WA Zip Code:98273
Contractor: Commercial Fire Protection, Inc. Phone Number: 360 848-9093 EXT 113
Address. 17199 Bennett Rd. City: Mount Vernon State: WA Zip Code:98273
Contractor's License Number: COMMEFP132MM Expiration:08/16/20
ro.comfi
Della Dellinger della@cre
Contact Person: Email: P
I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the above-
described property will be in accordance with the laws,rules and regulation of the State of Washington.
e,es=oeo,9eseeoe =ea4�esa�d 06/30/2020
Applicants Signature Date
Della Dellinger
Print Applicants Name
FOR STAFF USE ONLY
Permit# Accepted By Amount Received Receipt# Date Received
WEB Forms—131 Page 1 of 1 6116LP
D co D N
cn 70 ? �
c O Z Z r
u m �j0z g x
z
z 0
Z0 fTl
Z oocZ
-n Om -nO0 D m C ? O C
m --I m � co Z C Fmo D r
N = W D 0 �D To 0
w z o V
O D W D r " Z > Z
m
1 Z (n a ZJ M O C
co M
m 2 w < Q -0 r
0 mo � 7H O �
O m � C)ao o m --I -1 -n Cl) z
� ?' M o �� C7m � n -� m
�mv ,z.� y � W
S m Z m � m
n m
r z
0
c) ZO Dm
m G) K Z Z
z z
m r--
m
x
m ` V x O m m
m x _0 � m
FA O
x A U) c m
} _ 0l z m
a n o
m N ca
g ( o m
Q I m (n_
1 m �W m 1 i
m°� �` 0 C:
z
o 4-0 ) j
"'<
0
m m �L m m —1 m
mmr x m 0 x
zz° D Cn z �.������������ (A O W (n
Z 0w�� (0)co n 1 Z D �7 z
?mzo m ,n
���z o Im ' 996 m� 1 % � m m r0 m
commit = 3 1 uCD n), 070 1 n it
A ° Nmm= m w 1 mil t mm � m
o m w- mO ; Kim �Dzl 0
....
Zr -3 a. 1 °< 0mzl a m m
�0 Z3� M' I 0w z001
DCn mom` "a 1 0 �m� -Z-�
Z O z (n� Kim eaa I o �K�15 20 J7
(D T m �� � D� � 7mo� 1 ? z Z
0
o 0n rag°0 -�� 1 6\ �zml o r
00 - Kz a, I n l m m
o (D r 3 es 10 0 -4 1
o C- m o Im 1
C o
om LJ
M
, ,,n z
N p Z
N
C �S
NOTICE
TO PERMITEE AND/OR OWNER
❑ PARTIAL APPROVAL Cl CORRECTIONS REQUIRED
Cl DO NOT OCCUPY aAPPROVED
PERMIT#: 3 0 1 J AM PM DATE G
JOB ADDRESS: 6 5 E .P. LOT#:
PROJECT: p„ ,,,� .A F ,„ „
TYPE OF INSPECTION:
OTHER:
❑ NO PERMIT-STOP WORK-OBTAIN PERMIT
❑ CONSTRUCTION IS NOT IN ACCORDANCE WITH APPROVED PLANS AND
PERMIT -STOP WORK
❑ STOP WORK UNTIL AUTHORIZED TO CONTINUE BY INSPECTOR.
❑ CORRECTIONS LISTED BELOW MUST BE MADE BEFORE WORK CAN BE
APPROVED.
❑ WORK NOT READY FOR INSPECTION: $50 REINSPECTION FEE (PER IBC)
MUST BE PAID PRIOR TO NEXT INSPECTION.
❑ CONTACT INSPECTOR 360-403-3551 ❑ CALL FOR REINSPECTION
THE ACTIONS OR CORRECTIONS INDICATED ABOVE ARE REQUIRED WITHIN DAYS OR
PENALTIES IMPOSED BY LAW MAYAPPLY.
FOR INSPECTION CALL: 360-403-3417
`I-,)5-doDo
INSPECTOR DATE
`fit Y O�
• •
[I PLANNING O CIVIL 0 BUILDING CITY OF ARLINGTON ' ti,
• •1
CITY OF ARLINGTON
a 18204 59th Avenue NE,Arlington, WA 98223
INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551
BUILDING PERMIT
505 E Third Street NE
Permit#: 3291
Permit Expiration Date: 12/28/2020
Parcel#: 31050200401500 Valuation:2119.00
OWNER APPLICANT CONTRACTOR
ARLINGTON SCHOOL DISTRICT 16 Commercial Fire Protection, Inc. Commercial Fire Protection,Inc
315 N FRENCH AVENUE 17199 Bennett Rd 17199 Bennett Rd
ARLINGTON,WA 98223 Mount Vernon,WA 98273 Mount Vernon,WA 98273
360-848-9093 ext113 360-848-9093
LIC:COMMEFP132MM EXP:08/16/2020
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR: 2015
STORIES: I CONST. TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: I OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for, or approval of,any violation of this Code or any
other ordinance or order of the City, of any state or federal law, or of any order,proclamation,guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation, guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid. The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order, state or federal law,or any order,proclamation, guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC I I O/IRC 110.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
Digitally signed by Della Dellinger
DDmail=d�Dell@ofireproer,o,' US Della Dellinger 7/16/2
Della Dellinger
Date:2gzo.o7.1s1s:sa:2s-g7•oo• 7 lzv
Signature Print Name Date Released By bat
CONDITIONS
1. Permit and set of approved plans to remain on site during installation. 2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections: may include hangers, earthquake bracing,
sprinkler locations and pipe re-routing that could impact hydraulic calculations.Failure to submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is conducted. 3. Hangers and earthquake bracing shall be
installed in accordance with NFPA 13.4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom.5.Hydrostatic test required:working pressure for 2 hours minimum 6. Sprinkler system
Contractor's Material and Test Certificate shall be submitted prior to close out of permit. 7. Owner shall be provided with a set of
approved plans and associated documents for their files. 8.Adhere to approved plans. 9.Approved job copy shall be onsite for
inspections. 10. Call for inspections.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
07/16/2020 Fire Sprinkler Permit $75.00
07/16/2020 Processing/Technology Fee $25.00
07/16/2020 Fire System Plan Review $100.00
07/16/2020 Credit Card Surcharge $6.00
Total Due: $206.00
Total Payment: $206.00
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
Commercial COMMERCIAL FIRE PROTECTION, INC.
Fire Protection 17199 BENNETT ROAD, MOUNT VERNON, WA 98273
trtc. (360) 848-9093 FAX (360) 848-1072
CONTRACTOR'S LICENSE NO. COMMEFP132MM
WET SYSTEM - SYSTEM REVISION
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROJECT NAME ARLINGTON SCHOOL DIST. PRESIDENTS ELEM. JOB NO. 2020522
PROJECT ADDRESS 505 E. THIRD ST. NE
ARLINGTON, WA 98233
SYSTEM NO. 1 SERVES NEW TIMEOUT ROOM
Upon completion of work,inspection and tests shall be made by the contractor's representatives and witnessed by an AHJ and/or owner's
PROCEDURE representative. All defects shall be corrected and systems left in service before contractor's personnel finally leaves the job.
A certificate shall be filled out and signed by both representatives- Copies shall be prepared for approving authorities,owners and contractor. It is
understood that owner's representative's signature to no way prejudices any claim against contractor for faulty material,poor workmanship,or failure
to comply with approving authority's requirements or local ordinances
AUTHORITY HAVING CITY OF ARLINGTON
JURISDICTION 6231 188T"ST.,ARLINGTON,WA 98223
PERMIT NO. 3291
PLANS Installation conforms to accepted plans ®YES ❑NO
Equipment used is approved ®YES ❑NO If no,explain
PIPE AND PIPE CONFORMS TO NFPA 13 - 2016 STANDARD ®YES ❑ NO
FITTINGS FITTINGS CONFORM TO NFPA 13 - 2016 STANDARD ® YES ❑ NO
Do you certify as the sprinkler contractor that welding procedures used comply with the minimum ❑ YES ❑NO
requirements of AWS B2.1,ASME Section IX Welding and Brazing Qualifications,or other applicable
qualification standard as required by the AHJ?
WELDED PIPING Do you certify that all welding was performed by welders or welding operators qualfied in accordance the ❑ YES ❑NO
rri minimum requirements of AWS B2.1,ASME Section IX Welding and Brazing Qualifications,or other
ElYES ® NO r applicable qualification standard as required by the AHJ?
ui Do you certify that welding was conducted in compliance with a documented quality control procedure to ❑YES ❑NO
ensure that(1)all discs are retrieved;(2)that openings in piping are smooth,that slag and other welding
residue are removed,(3) the internal diameters of piping are not penetrated;(4)completed welds are free
from cracks,incomplete fusion,surface porosity greater than 1/16 inch in diameter,undercut deeper than
25%of the wall thickness or 1/32 inch;and(5)completed circumferential butt weld reinforcement does not
exceed 3/32 inch?
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi for two hours or 50 psi above static pressure in excess of 150 psi for two
hours All aboveground piping leakage shall be stopped
HYDROSTATIC TEST ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS? [:1YES ❑ NO
IF NO,STATE REASON
WITNESSED BY FOR CITY OF.ARLINGTON _
SIGNATURE TITLE f � DATE
Underground mains and lead-in connections to system risers flushed before connection made to sprinkler piping.
FLUSHING VERIFIED BY COPY OF UNDERGROUND PIPING TEST CERTIFICATE? ❑ YES ® NO
VERIFICATION FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING? ❑ YES ® NO
OTHER—EXPLAIN EXISTING SYSTEM
ADDITIVE AND DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS,SODIUM
CORROSIVE SILICATE OR DERIVATIVES OF SODIUM SILICATE,BRINE,OR OTHER CORROSIVE CHEMICALS WERE NOT USED
CHEMICAL FOR TESTING SYSTEM OR STOPPING LEAKS? ® YES ❑ NO
VERIFICATION
BLANK TEST GASKETS Number Used 0 Locations Number Removed 0
MANUFACTURER SIN TYPE MODEL YR.OF K- TEMP QUANTITY
NUMBER MFG FACTOR RATING °F
VIKING VK3021 RECD SSP QR 2020 5.6 200 1
SPRINKLERS
TOTAL 1
ALARM DEVICE ALARM DEVICE MAX-TO OPERATE THRU TEST PIPE
TYPE MAKE MODEL MIN SEC
EXISTING
EQUIPMENT EQUIPMENT OPERATES PROPERLY ® YES ❑ NO
OPERATION IF NO,
EXPLAIN
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND ® YES ❑ NO
CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
IF NO,
EXPLAIN
INSTRUCTIONS HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES?
1_ SYSTEM COMPONENTS INSTRUCTIONS
YES ❑ NO
2 CARE AND MAINTENANCE INSTRUCTIONS
_ ® YES ❑ NO
3- NFPA 25
❑ YES NO
HYDRAULIC DATA NAME PLATE PROVIDED ❑ YES ® NO
NAMEPLATE IF NO, NO ADDITIONAL HYDRAULIC CALCULATIONS ARE PROVIDED FOR THE TENANT IMPROVEMENT THE
EXPLAIN TENANT IMPROVEMENT IS LESS DEMANDING THAN THE HYDRUALICALLY MOST DEMANDING AREA
ORGINALLY CALCULATED
CUT OUT(DISC) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUT OUTS(DISCS)ARE
RETRIEVED? ❑ YES ❑ NO
CERTIFICATION IF NO,EXPLAIN
PRESSURE LOCATION MAKE& STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
REDUCING &FLOOR MODEL SETTING INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) (GPM)
VALVEINSTALLED
❑YES ®NO
PRESSURE REDUCING LOCATION& STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
VALVE INSTALLED FLOOR MAKE&MODEL SETTING INLET(PSI) OUTLET(PSI) INLET(PSI) OUTLET(PSI) FLOW(GPM)
❑YES ® NO
IF POWDER DRIVEN STUDS ARE USED IN CONCRETE,HAS REPRESENTATIVE SAMPLE TESTING BEEN
POWDER DRIVEN SATISFACTORILY COMPLETED? ❑ YES ❑ NO
STUD INSTALLED IF NO,
❑YES ® NO EXPLAIN
IN-SERVICE DATE DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN
MAIN DRAIN READING GAUGE LOCATED NEAR WATER SUPPLY TEST PIPE RESIDUAL PRESSURE WITH VALVES IN TEST PIPE
TEST STATIC PRESSURE: PSI OPEN WIDE PSI
FOR AHJ CITY OF ARLINGTON r Q
FINAL ACCEPTANCE SIGNATURE TITLE ryyQ-V%44-frbLJ DATE ` .a S��
FOR PROPIATY O NER OR THEIR AUTHORIZED AGENT
TEST WITNESSED SIGNATURE 1. TITLE 1T�> ! /I� lu DATE
BY FOR
C 0 MMERCIAL FIRE P )ECTION, INC.
SIGNATURE TITLE FOREMAN DATE
-�-
I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT
THIS SPRINKLER SYSTEM WAS INSTALLED IN ACCORDANCE
WITH RCW 18-160 AND THE RULES ADOPTED BY THE
WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED �rrrr�rrrrrr�orrrrrrr�rrr�rrr�
BYTHE STATE FIRE MARSHAL. WA31IN110MTONSTATE
I CERTSFIOATE OF 009FLTS11OY
Eric Si Fm FRaTac77OM'"""°"`men
Sys
CERTIFICATION g Eric Ray Sigmon
74734607-CEO Level
PRINTED NAME OF CERTIFICATE OF COMPETENCY HOLDER 1 ;
CERTIFICATE REGISTRATION NO. 7473-0607-CEG a COnwlwmhd Fire Protacdon,Ino. r
COMMEF1213 M �
,tislao 16
SIGNATURE OF CERTIFICATLY OF COMPETENCY HOLDER a.r.rr.rr.".. ��r"r""r'r�
DATE 20 20�Q
Commercial Fire Protection, Inc. I ransmittai
17199 Bennett Road
Mt.Vernon WA98273-9789 Today's Date: 11/17/2020
360 848-9093
COMMEFP 132 MM Date Sent: 11/17/2020
TO:Arlington Air Port, City Project: 2020522
18204 59th Ave NE Arlington School District Corrections
Arlington WA 98223 3 Bldgs Addesses in Notes
Arlington WA 98223
Prepared By: DELLA DELLINGER
Item Quantity Description
1 1 Aboveground Test Certificate
Notes
Please sign and date this form as proof that you are in receipt of the above listed items.
Return form to Commercial Fire Protection, Inc.
Signed: Date:
Printed Name:
I
I
.1
CITY OF ARLINGTON
a 18204 59th Avenue NE,Arlington, WA 98223
INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551
BUILDING PERMIT
505 E Third Street NE
Permit#: 3291
Permit Expiration Date: 12/28/2020
Parcel#: 31050200401500 Valuation:2119.00
OWNER APPLICANT CONTRACTOR
ARLINGTON SCHOOL DISTRICT 16 Commercial Fire Protection, Inc. Commercial Fire Protection,Inc
315 N FRENCH AVENUE 17199 Bennett Rd 17199 Bennett Rd
ARLINGTON,WA 98223 Mount Vernon,WA 98273 Mount Vernon,WA 98273
360-848-9093 ext113 360-848-9093
LIC:COMMEFP132MM EXP:08/16/2020
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR: 2015
STORIES: I CONST. TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: I OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for, or approval of,any violation of this Code or any
other ordinance or order of the City, of any state or federal law, or of any order,proclamation,guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation, guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid. The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code,any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City,or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order, state or federal law,or any order,proclamation, guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC I I O/IRC 110.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
Signature Print Name Date Released By bat
CONDITIONS
1. Permit and set of approved plans to remain on site during installation. 2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections: may include hangers, earthquake bracing,
sprinkler locations and pipe re-routing that could impact hydraulic calculations.Failure to submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is conducted. 3. Hangers and earthquake bracing shall be
installed in accordance with NFPA 13.4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom.5.Hydrostatic test required:working pressure for 2 hours minimum 6. Sprinkler system
Contractor's Material and Test Certificate shall be submitted prior to close out of permit. 7. Owner shall be provided with a set of
approved plans and associated documents for their files. 8.Adhere to approved plans. 9.Approved job copy shall be onsite for
inspections. 10. Call for inspections.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
07/16/2020 Fire Sprinkler Permit $75.00
07/16/2020 Processing/Technology Fee $25.00
07/16/2020 Fire System Plan Review $100.00
07/16/2020 Credit Card Surcharge $6.00
Total Due: $206.00
Total Payment: $206.00
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
INSPECTION REQUEST PROCEDURE
To schedule an inspection:
Call the Automated Inspection Line
(360) 403-3417
Required Information:
-Permit Number (Building, Right of Way or Civil)
-Inspection Request (Type)
-Inspection Time (am or pm)
• A.M. inspections are scheduled from 8:00 am to 12:00 pm
• P.M. inspections are scheduled from 1:00 am to 4:00 pm
• You may request a specific time. We will do our best to honor
the time requested.
The Automated Inspection Line responds exactly like voicemail.
Simply listen to the voice message and leave the information
indicated above. You may stay on the line and request multiple
inspections giving the required information each time.
• Inspections must be called in before 3:3 0 PM to be on the next
day inspection schedule
Fire Suppression (fire alarm,fire sprin1der) inspection requests
require at least 48 hours advanced notice
a To cancel or modify an inspection please call (360) 403-3433.
CITY OF ARLINGTON INSPECTION CARD
No building construction shall be commenced until permit holder
INSPECTION RECORD SHALL or his agent has posted this Inspection Record Card in a
REMAIN AT JOB SITE conspicuous place on the premises.
OWNER: ARLINGTON SCHOOL DISTRICT CONTRACTOR: COMMERCIAL FIRE PROTECTION INC
JOB ADDRESS: 505 E THIRD STREET NE LOT NUMBER TYPE GROUP
NATURE of WORK: FIRE SPRINKLER ALTERATION
USE of BUILDING: SCHOOL
PERMIT No: BLD-3291 DATE ISSUED:7/13/2020
INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB
DEPARTMENT INSPECTION DATE(S) PASS FAIL INITIALS
FOOTING
BUILDING FOUNDATION
(360)403-3417 UNDERFLOOR
SHEARWALL
PLUMBING(groundwork)
ROUGH PLUMBING
GAS PIPING
ROUGH HEATING&VENTILATION
FRAMING
INSULATION
WALLBOARD(SHEAR/RATED WALLS)
CEILING GRID
STRUCTURALSLAB
CROSS CONNECTION CONTROL IN PREMISE
(360)403-3417 GRADING
TEMPORARY TECSP
ASBUILTS APPROVED
MAINTENANCE BOND
STORM DRAINAGE SYSTEM
PAVING,SIGNAGE&MARKINGS
LANDSCAPING
CONDITIONS
ONSITE UTILITIES WATER
ONSITE UTILITIES SEWER
Sewer OFFSITE UTILITIES WATER
(360)403-3608 OFFSITE UTILITIES SEWER
SEWER PRETREATMENT
Water CROSS CONNECTION CONTROL PREMISE
(360)403-3526 SIDE SEWER/CLEANOUT/FINAL
WATER SERVICE INSTALLATION
WATER SERVICE FINAL
(360)403-3417 HYDRO/FLUSH
UNDERGROUND**INCL FDC
FIRE ALARM /AUTOMATIC SPRINKLER
HOOD SUPPRESSION SYSTEM
FINAL FIRE WALK-THROUGH
(360)403-3417 FINAL INSPECTION
4LL SIGNATURE BLOCKS MUST BE COMPLETE
GAT Y U�
City of • •
July 9, 2020
Permit Number: BLD 3291
Project Address: 505 E Td Street, Arlington
Project Description: Fire Sprinkler Plans for Presidents Elementary School
Contractor: Commercial Fire Protection, Inc.
17199 Bennett Road
Mount Vernon, WA 98273
Re: Fire Suppression Shop Drawing Review Comments/Approval
The Arlington Fire Department has completed a review of the Fire Suppression shop drawing submittal and
approved the issuance of the permit with the following conditions:
1. Permit and set of approved plans to remain on site during installation.
2. Significant deviations from approved plans made during installation shall be required to be resubmitted for
review prior to inspections: may include hangers, earthquake bracing, sprinkler locations and pipe re-
routing that could impact hydraulic calculations. Failure to submit revisions could result in cancellation of
an inspection while a review of an as-built resubmittal is conducted.
3. Hangers and earthquake bracing shall be installed in accordance with NFPA 13.
4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed distance from
north wall of classroom.
5. Hydrostatic test required: working pressure for 2 hours minimum
6. Sprinkler system Contractor's Material and Test Certificate shall be submitted prior to close out of permit.
7. Owner shall be provided with a set of approved plans and associated documents for their files.
Items noted above are conditions on the issued permit and shall be verified as part of the final inspection of the
system at project completion. Final approval will not be provided until all conditions are verified. Call at least
48 hours in advance to schedule inspections.
If there are any questions please do not hesitate to call.
Sincerely,
A We %W/C&
Mike Makela
Assistant Fire Chief
Arlington Fire Department
JOB COPY
NEW
TI
I
ROOM--
NEW PENDENT S RINKLER
AN FLEXDROP �+
i I
EXISTING EC PENDENT SPRINKLER
TO BE RELOCATED
o . `
NEW WALLS TO BOTTOM T
OF ACT CEILING CP
Ft RELOCATE 1" DROP WITH
EXISTING EC PENDENT SPRINKLER
EXISTING CLASSROOM
9'-6"
N
SPRINKLER PLAN
13� o 4
SCALE 1/4'=V-0"
—METAL DECK
141 T.EILINGCON#610
TEK PLATE
ER RING
------------�---------7
WASHINGTON STATE
HANGER 1CPI CERTIFICATE OF COMPETENCY
; FIRE PROTECTION SPRINKLER SYSTEMS
Mike Hinton
73
Commerc a Fire Protection,Inc. E>�ires
COMMEFP132MM 12/31/20 ;
SPRINKLER LEGEND w �0�29�Z0 i
SVM I SIN# I MANUFACTURER I TYPE MODEL I
VK3021 I VIKING RECD SSP OR I CHROME I CHROME 5.6 1/2' 200° 1 m ' !i9 nature Date �
CONTRACT WITH COMMUCIAL FIBS FBITHTIOR, INC.
ARLINGTON PUBLIC SCHOOLS 17199 BENNETT ROAD
MT VERNON,WA 98273
315 NORTH FRENCH AVENUE LICENSE#COMMEFP132MM
ARLINGTON,WA 98223 1 PHONE: (360)848-9093 FAX (360)848-1072
PROJECT MANAGER:MARK WEBB ARLINGTON SCHOOL DISTRICT CORRECTIONS
PHONE:360-631-3116 PRESIDENTS ELEMENTARY SCHOOL
FAX: 505 EAST 3RD STREET
SUPERINTENDENT: ARLINGTON,WA 98223
PHONE:
FAX: DESIGNER I DATE SHEET JOB NO.
KEY PLAN MIKE HINTON 6/24/20 1 OF 1 2020522
Date: 03/30/2026
Permit#: 3291
Permit 07/01/2020
Date:
Review 07/01/2020
Date:
Permit FIRE SPRINKLER
Type:
Review FIRE SPRINKLER
Type:
Target Date: 07/15/2020
Scheduled 00:00
Time:
Completed 07/09/2020
Date:
Description: 1. Permit and set of approved plans to remain on site during installation. 2. Significant deviations
from approved plans made during installation shall be required to be resubmitted for review prior
to inspections: may include hangers, earthquake bracing, sprinkler locations and pipe re-routing
that could impact hydraulic calculations. Failure to submit revisions could result in cancellation
of an inspection while a review of an as-built resubmittal is conducted. 3. Hangers and
earthquake bracing shall be installed in accordance with NFPA 13. 4. Relocated EC sprinkler
shown on drawing appears to be greater than maximum allowed distance from north wall of
classroom. 5. Hydrostatic test required: working pressure for 2 hours minimum 6. Sprinkler
system Contractor's Material and Test Certificate shall be submitted prior to close out of permit.
7. Owner shall be provided with a set of approved plans and associated documents for their files.
Review
Status:
Assigned Mike Makela
To:
Time In: 00:00
Time Out: 00:00
Hours: 1.0
Notes
07/13/2020 1. Permit and set of approved plans to remain on site during installation.
2. Significant deviations from approved plans made during installation shall be required to be
resubmitted for review prior to inspections: may include hangers, earthquake bracing, sprinkler
locations and pipe re-routing that could impact hydraulic calculations. Failure to submit
revisions could result in cancellation of an inspection while a review of an as-built resubmittal
is conducted.
3. Hangers and earthquake bracing shall be installed in accordance with NFPA 13.
4. Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom.
5. Hydrostatic test required: working pressure for 2 hours minimum
6. Sprinkler system Contractor's Material and Test Certificate shall be submitted prior to close
out of permit.
7. Owner shall be provided with a set of approved plans and associated documents for their
files.
Property Information
Parcel#: 31050200401500 ARLINGTON SCHOOL DISTRICT 16
ARLINGTON SCHOOL DISTRICT 16 315 N FRENCH AVENUE
505 E 3RD STREET ARLINGTON, WA 98223
Zoning: Lot: Block:
Permit#: 3291
Permit Date: 07/01/20
Permit Type: FIRE SPRINKLER
Project Name: Arlington School District
Applicant Name: Commercial Fire Protection, Inc.
Applicant Address: 17199 Bennett Rd
Applicant, City, State, Zip: Mount Vernon,WA 98273
Contact: Della Dellinger
Phone: 360-848-9093 ext 113
Email: della@cflrepro.com
Scope of Work: Sprinkler relocation
Valuation: 2119.00
Square Feet: 40
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 07/17/2020
Permit Expires: 01/13/2021
Form Permit Type:
Status: LASERFICHE
Assigned To:
Property
Parcel# Address Legal Description Owner Name Owner Phone Zoning
ARLINGTON
31050200401500 505 E 3RD STREET SCHOOL DISTRICT
16
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
Commercial Fire Della L Dellinger 360-848-9093 17199 Bennett Rd CONSTRUCTION COA 601 011 373
Protection,Inc CONTRACTOR
Commercial Fire Della L Dellinger 360-848-9093 17199 Bennett Rd CONSTRUCTION Labor&COMMEFP132MM
Protection,Inc CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
07/01/2020 FIRE SPRINKLER BUILDING
1.Permit and set of approved plans to remain on site
during installation.
2.Significant deviations from approved plans made during
installation shall be required to be resubmitted for review
prior to inspections:may include hangers,earthquake
bracing,sprinkler locations and pipe re-routing that could
impact hydraulic calculations.Failure to submit revisions
could result in cancellation of an inspection while a review
of an as-built resubmittal is conducted.
07/01/2020 FIRE SPRINKLER 3.Hangers and earthquake bracing shall be installed in Mike Makela
accordance with NFPA 13.
4.Relocated EC sprinkler shown on drawing appears to be
greater than maximum allowed distance from north wall
of classroom.
5.Hydrostatic test required:working pressure for 2 hours
minimum
6.Sprinkler system Contractor's Material and Test
Certificate shall be submitted prior to close out of permit.
7.Owner shall be provided with a set of approved plans
and associated documents for their files.
Fees
Fee Description Notes Amount
Fire Sprinkler System Commercial NFPA 13/13R $75.00
Processing/Technology $25.00
Fire System Plan Review Table 4-1 $100.00
Credit Card Service $6.00
Total $206.00
Attached Letters
Date Letter Description
07/01/2020 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
07/14/2020 Della Dellinger 81301369 $200.00
07/14/2020 Della Dellinger 81301369 Launa Black $6.00
Outstanding Balance $0.00
Notes
Date Note Created By:
07/23/2020 Emailed Della the approved plans,packet and permit to print for the job site. Kristin Foster
07/14/2020 Emailed the permit for signature. Kristin Foster
07/13/2020 1.Permit and set of approved plans to remain on site during installation. Kristin Foster
2.Significant deviations from approved plans made during installation shall be required to be
resubmitted for review prior to inspections:may include hangers,earthquake bracing,sprinkler
locations and pipe re-routing that could impact hydraulic calculations.Failure to submit
revisions could result in cancellation of an inspection while a review of an as-built resubmittal is
conducted.
3.Hangers and earthquake bracing shall be installed in accordance with NFPA 13.
4.Relocated EC sprinkler shown on drawing appears to be greater than maximum allowed
distance from north wall of classroom.
5.Hydrostatic test required:working pressure for 2 hours minimum
6.Sprinkler system Contractor's Material and Test Certificate shall be submitted prior to close
out of permit.
7.Owner shall be provided with a set of approved plans and associated documents for their
files.
Uploaded Files
Date File Name
09/24/2021 9758427-3291 IC 9.25.2020.pdf
07/17/2020 7000120-3291 Issued Permit.pdf
07/01/2020 6917282-3291 Plans.pdf
07/01/2020 6917283-3291 Application.pdf