HomeMy WebLinkAbout18204 59th Ave Ne_BLD2657_2026 T CITY OF ARLINGTON
238 N. OLYMPIC AVE -ARLINGTON, WA. 98223
PHONE; (360) 403-3551
BUILDING PERMIT
Address:18530 59th Dr NE Permit#:2657
Parcel#:3 1052200200 100 Valuation: 1489.00
OWNER APPLICANT CONTRACTOR
Name:CITY OF ARLINGTON Name:Sonitrol Pacific Name:SONITROL PACIFIC
Address: 18204 59TH AVE NE Address:2221 California St Address:2221 CALIFORNIA ST
City,State Zip:ARLINGTON,WA 98223 City,State Zip:Everett,WA 98201 City,State Zip:EVERETT,WA 98201
Phone: Phone:253-878-2714 Phone:425-258-3655
LIC: SONITP*948D7 EXP:03/27/2020
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
Name: Name:
Address: Address:
City,State,Zip: City,State,Zip:
Phone: Phone:
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Alarm CODE YEAR: 2015
STORIES: CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY;
NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S
COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR
A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/IRC110.
SALES TAX NOTICE:Sales tax relating to construction and construction materials in the City of Arlington must be reported on your sales tax return form
and coded City of Ar' gton#3101.
Signature Print Name Date Rcicascd By Dat
CONDITIONS
1. Permit and set of approved plans to remain on site during installation. Installers shall present NICET II
certification upon request. 2. Trouble condition to be verified for signaling circuits. 3. Signal transmission to
Central Station Monitoring Company to be verified. 4. Installation completion form shall be submitted prior
to project close-out.
THIS PERMIT AUTHORIZS ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION
ON THE PUBLIC DOMAIN(CURBS,SIDEWALKS,DRIVEWAYS,MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
7/15/2019 Fire Alarm Plan Review Fee $100.00
7/15/2019 Fire Permit Fee $78.30
7/15/2019 Processing/Technology Fee $25.00
Total Due: $203.30
Total Payment: $0.00
Balance Due: $203.30
CALL FOR INSPECTIONS
BUILDING(360)403-3417
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
i
N%a
City of Arlington
0
DepartmentFire
�LlN G
July 8, 2019
Permit Number: BLD 2657
Project Address: 18530 59th Drive NE, Arlington
Project Description: Telguard Cellular Communicator Installation
Contractor: Erin Flemming
Sonitrol Pacific
2221 California Street
Everett, WA 98201
Re: Fire Alarm Shop Drawing Review Comments and Approval
The Arlington Fire Department has completed a review of the Fire Alarm shop drawing submittal and approves
the issuance of the permit with the following conditions:
1. Permit and set of approved plans to remain on site during installation. Installers shall present NICET II
certification upon request.
2. Trouble condition to be verified for signaling circuits.
3. Signal transmission to Central Station Monitoring Company to be verified.
4. Installation completion form shall be submitted prior to project close-out.
Items noted above are conditions on the issued permit and shall be verified as part of the final inspection of the
system at project completion. Final approval will not be provided until all conditions are verified. Please call at
least 48 hours in advance to schedule an inspection.
If there are any questions please do not hesitate to call.
Sincerely,
7&4&&
Mike Makela
Assistant Fire Chief
Arlington Fire Department
OFFICE COPY
i mo
Permit Information
Date 7/2/2019
Permit Number 2657
Project Name Glasair Fire Alarm Alteration
Applicant Name Sonitrol Pacific
Applicant Address 2221 California St
City, State,Zip Everett,WA 98201
Contact Erin Flemming
Phone 253-878-2714
Email eflemming@soundsecurity.biz
Permit Type Fire Alarm
Site Address 18530 59th Dr NE
Valuation 1489.00
Status Applied
Permit Issued
Permit Expires
Square Feet 0
Type of Construction/Occupancy Load Fire Alarm Alteration/Addition
Number of Stories 0
Proposed Use
MIC/Opportunity Zone
Assigned To Raelynn Jones
Property
Parcel Address Legal Owner Owner Phone Zoning
31052200200100 18204 59TH AVE NE CITY OF ARLINGTON 1431 Airports&Flying Fields
Contractors
Contractor Name Primary Contact Phone Email Contractor Type License License#
5ONITROL PACIFIC 425-258-3655 CONTRACTOR _&I ONITP*948D7
Fees
Fee Des cri tion Notes Amount
Fire Alarm Plan Review Fee 345.83.00.00 $100.00
Fire Permit Fee 322.10.00.00 $78.30
Processin /Techn logy Fee 341.43.00.02 $25.00
Total $203.30
Notes
Date Note
7/2/2019 Specs/Site Plan submittal ok per KO
Uploaded Files Upload File
�}
7
Data File Uploaded B
7/2/2019 3:09:34 PM 2657 Application.pdf Jones,Rael nn (
7/2/2019 3:09:34 PM 2657 Specs and Site Plan.odf Jones.Rael nn x
7/2/2019 3:07:38 PM 2657 Application.pdf Jones,Rael nn x
Y FIRE ALARM
PERMIT APPLICATION
Department of Community &Economic Development
City of Arlington• 18204 59th Ave NE -WA 98223- Phone(360)403-3551
THIS APPLICATION MUST BE ACCOMPANIED BY TWO(2)SETS OF COMPLETE AND SCALED PLANS FOR EACH FIRE
ALARM PERMIT APPLICATION.INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO,INCLUDE SPECIFICATION
SHEETS,WIRING DIAGRAMS, (POINT TO POINT WIRING),AND ALL OTHER INFORMATION ON EQUIPMENT PROPOSED TO
BE INSTALLED PRIOR TO INSTALLATION.
Type of permit: (check one) New Fire Alarm �✓ Fire Alarm Alteration/Addition
Project Address: 18530 59th Dr NE Arlington, WA 98223
1 Parcel ID#:
Number of Zones/Panels:1 Building Area(Sq Ft): 2500 Valuation: 1489.00
Owner: Rob Hunsinger Phone Number: 425-870-9839
Address: PO Box 3222 City.Arlington State:WA Zip Code:98223
Contact Person:Erin Flemming Phone Number: 253-878-2714
Cell Phone: 253-878-2714 Email: EFlemming@soundsecurity.biz
Address: 5911 Orchard ST W City:Tacoma State:WA Zip Code: 98467
Contractor: Sonitrol Pacific Phone Number: 253-878-2714
City: State: Zip Code:
Address: 2221 California ST Everett WA 98201
Contractor's License Number:S ON ITP*948D7 Expiration:03/20
Contact Person:
Erin Flemming Email: EFlemming@soundsecurity.biz
Electrical Contractor: Sonitrol Pacific Phone Number253-878-2714
2221 California St Everett WA 98467
Address: City: State: Zip Code:
Contractor's License Number$0NffP*948D7 Expiration.3/20
I hereby certify the above information is correct and that the construction on, and the occupancy and the use of the above described
roperty w�!i,hP.a�yrnrrlance with the laws,rules and regulations of the State of Washington
„ .... ..-.......,...,.... 07/01/2019
Applicants Signature Date
Erin Flemming
Print Applicants Name
FOR STAFF USE ONLY Received
1�D4� JUL 01 2019
Permit# Accep y Amount Received Receipt# Date Received
WEB Form—130 Page 1 of 1 6/16LP
.f =
.�• i Industries
Safety&Health Claims&Insurance 0 Workplace Rights Trades&Licensing
Washington State Department of
k, Labor & Industries
SONITROL PACIFIC
Owner or tradesperson 2221 CALIFORNIA AVE
Principals EVERETT,WA 98201
Bradley,Beau,PRESIDENT 425-258-3655
SNOHOMISH County
Bullis,Joe(Joseph)M,VICE PRESIDENT
Payne,James M,VICE PRESIDENT
Bradley,Debra,SECRETARY
Buckner,Lisa C,TREASURER
BRADLEY,BEAU R,AGENT
Doing business as
SONITROL PACIFIC
WA UBI No. Business type
600 365 884 Corporation
Parent company Governing persons
SOUND SECURITY INC BEAU
R
BRADLEY
BEAU BRADLEY;
DEBRA L BRADLEY;
LISA C BUCKNER;
JOE JOSEPH M BULLIS;
Certifications & Endorsements
License
Verify the contractor's active registration/license/certification(depending on trade)and any past violations.
Electrical Contractor Active.
Meets current requirements.
License specialties
LIMITED ENERGY
License no.
SONITP"948D7
Effective—expiration
03/27/2006—03/27/2020
Designated administrator Active.
MOORS,GARY Meets current requirements.
License type License no.
Electrical Administrator MOOREG'941 RN
Bond
Contractors Bonding&Insurance Co $4,000.00
Bond account no.
P16275
Received by L&I Effective date
02/19/2013 02/20/2013 Help us improve
i �: r `
Expiration date
Until Canceled
Savings
No savings accounts during the previous 6 year period.
License Violations
Infraction no.
EBODU00288 Satisfied
Issue date RCW/WAC
06/15/2018 19.28.101 RCW
Violation city Violation amount
EVERETT $100.00
i
Type of violation
ELECTRICAL CITATION
Description
Class B eligible work-Failing to obtain an
electrical/telecommunications work permit,or
post a provisional electrical work permit,or
valid Class B label prior to beginning the
electrical/telecommunication installation or
alteration as referenced in WAC 296-46B-901.
Infraction no.
EJMAX00756 Satisfied
Issue date RCW/WAC
01/09/2018 19.28.101 RCW
Violation city Violation amount
EVERETT $250.00
Type of violation
ELECTRICAL CITATION
Description
Failing to get an inspection or obtain a valid
electrical/telecommunications work permit or
post a provisional electrical work permit prior
to beginning the electrical/telecommunication
installation or alteration as referenced in WAC
296-46B-901.
Infraction no.
EROMA00870 Satisfied
Issue date RCW/WAC
09/17/2013 19.28.101 RCW
Violation city Violation amount
Everett $100.00
Type of violation
ELECTRICAL CITATION
Description
Class B eligible work-Failing to obtain an
electrical/telecommunications work permit,or
post a provisional electrical work permit,or
valid Class B label prior to beginning the
electrical/telecommunication installation or
alteration as referenced in WAC 296-46B-901.
Workers' comp
Public Works Requirements
Workplace safety and health
a e a
1
CITY OF ARLINGTON
BUILDING DEPARTMENT
DA t l 1 Legend
NO CHANGES AUTHORIZED
UNLESS APPROVED BY THE PHOTO SMOKE
BUILDING INSPECTOR C�P DETECTOR
C1OPY IF] MANUAL PULL STATION
OFFICE
G
HEAT DETECTOR
HORN
�GD 75 SYTEM SENSOR 2RL
RESPONSIBLE PARTIES STROBE WALL MOUNT
75CD
INSTALLATION: SOUND SECURITY, INC. dba SONITROL PACIFIC
ANNUNCIATOR
MONITORING: SONITROL PACIFIC ANNUN
TESTING/MAINTENANCE: SONITROL PACIFIC
FACP FIRE ALARM CONTROL
1- - PANEL
TELGUARD TG7FS
CELL SOLE PATH CELL
COMMUNICATOR
°
STANDBY BATTERY REQUIRMENTS D 0
1 8AH SLA BATTERY FOR CELL COMMUNICATOR
PROJECT SCOPE: _
Install new cellular communicator to monitor existing fire alarm system.
_ y
Project: 18530 LLC TG7FS
Prepared by: Gary Moore
Date:June 4,2019
Reviewed by:
Date:
DPP vcCJ NATIONAL INSTnVM FOR CERTIFICATION INICET III#:
IN ENGINEERING TECHNOLOGIES' lRevision 1
Charles l_Miller
FIRE ALARM SYSCEMSU
Fi rt.✓Vitals Ira.,..� Y
1�Irv►A�Vn G,•��OGP� .
�J CERTN0.102181 VALIDTHRU 2/1/2022
- Received
JUL 01 2019
0� �u IF,
Legend
2 PHOTO SMOKE
DETECTOR
P
NA'nONAL INSTITUTE FOR CERTIFICATION E
i IN ENGINEERING TECHNOLOGIES' MANUAL PULL STATION
Charles R.Mullex
FIRE ALARM SYSTEMSR11 OH HEAT DETECTOR
HORN
CERT NO.102191 VALID THRII 2/1/2022 ®° SYTEM SENSOR 2RL
STROBE WALL MOUNT
75CD
ANNUN ANNUNCIATOR
FACP FIRE ALARM CONTROL
PANEL
TELGUARD TG-7FS
CELL SOLE PATH CELL
COMMUNICATOR
[-AREA OF WORK
Project 18530 LLC TG7FS
Prepared by: Gary Moore
Date,June 4,2019
Reviewed by:
Date:
NICET III#:
Revision 1
N
n
Legend
PHOTO SMOKE
DETECTOR
P
lT..m.Im.LM(RMll M.dA) .TMrx fi b uh tNwn.1 law*
X* . ,x .. .m F MANUAL PULL STATION
•d, i i 3DE 3oE
° 3DE
a TELGUARD
"N rw. � M ^• r _ ` O HEAT DETECTOR
•a.n•a- A<.M+W Mbb1 R.n/. J
Standby: 24 hours(1440 minutes)
--
AxD Device Quantity Current(Amp/Hourl Total HORN
n D.nxwLeoxxreTn G e
A C OTn,CME Supervision
with 5 Minute Servisian 1 x 60 mA x24 1440 mA
Subtotal: 1440 mA
co 75 $YTEM SENSOR 2RL
Add 30%for battery depletion: 432 mA
so .TA ' w ® STROBE WALL MOUNT
TnwAae Standby Subtotal: 1972 mA
75CD
Tarry�TE _ Tue
nco MAW �
Alarm Made S minutes
?� ANNUNCIATOR
e r" Device Quantity Current(Amp/Hour) Total
......m TG-7FS with 5 Minute Supervision 1 x 250 mA i 12 20.83 mA FIRE ALARM CONTROL
Subtotal: 20.83 mA FACP PANEL
Abe q.nr
c7� LLARTH Add 30%for battery depletion: 5.25 mA
GROUND 4
CgUTN)N:Ixco...n ' Alarm Mode Subtotal: 27.08 mA TELGUARD TG7
a CELL SOLE PATH CELL �
„„,.r,e ;TAW C�`A COMMUNICATOR
_ NAME DATE
w,nrcc xuU nu.T.s T.
�xAL PREPARED BY D.nbl R.ub. OTrzlltx Standby Subtotal: IB72 mA
REVIEWED eY D.nbl Rn..b. DTmnx Plus Alarm Mode Subtotal: 27.08 mA
TITLE ORIGINALDOCUMENTNO System Current Demand: 1899.08 n1A
TG-7FS LTE-SOLE PATH 56050602
12V flattery recommended: 7A(7000mA)
I
NATIONAL INSMUrE FOR CERTIFICATION Project: 185W LLC TG7FS
y IN ENGINEERING TECHNOLOGIES` Prepared by: Gary Moore
Data:June 4.2019
Charles P-Miller Reviewed by:
Date:
FIRE ALARM SYSCEM�S1111 NICET III :
Revision 1
CERT NO.102181 VALID THRO 2/1/2022
N
Legend_
QP PHOTO SMOKE
DETECTOR
[F]
MANUAL PULL STATION
OHEAT DETECTOR
SYSTEM L'Smoke Detector specifications
.,.
SENSOR c' " ,. . HORN
Co 75 SYTEM SENSOR 2RL
a n I 1
Aanl..l ,
I 1' STROBE WALL MOUNT
Photoelectric • , I I. " I , 75co
Smoke Detectors I I
a I I e =NN ANNUNCIATOR
cpuratingvakago
;e.r,,5?n;pr ernes_r�n.kedere tor. ;resent FACP FIRE ALARM CONTROL
u..un nFlppkyaRao. I. ,yfLla�• = PANEL
C f,JRI 7_(Jn f i![]'![1n Lc(rvnl`Jn I�t I'If>,n h_ir.j'if Pt�Cff{JR St,nCunrM ,i:. .y:T'.r'�1•Hl:r.inr'.L.l M�J'll,.r,D nil][
M--AliIIIICwrem ;, r,.I,—Jbr:�r.._la�=1�.:,. . n....., TELGUARDTG7FS
Tfl !`Sarr;l7yF;Jr.;nerlFaor'iti7rerp,•Inrll'lif5. n5i[jIi0(!nrI PeakAmdbyCurrent -r. (SELL SOLE PATH CELL
ot3
N-CMtRt tlnUnQl COMMUNICATOR
epe,1nr��ll,gpr)fg',Clrld In;![7r;7!n�7�•r,lOrl
Di enuo t dudwY 6w I
114 M
atk,yl Irryw.lur.Rarl.)r 1 , � ItIYI iir,`.
Op ihU Humidify HUngc
-
Features nr....h•ri...lr,lellyl:x eo.^watlll fL.,.to�N• ,._. +'r, I,-
Ilu,r+rrJr�,n Ihr.ellu,t .rclaller Htz r�sr r:•v^�'r•au fl,, �anwmtp ", A
.ul......�...
Inputhrmn,k ,A.`s
. r lr,Iilm-,i III,hw;l„.-r!vl!:'•:-,j online lrnuu„Ih
•i�rq, ;nr=r..lr.,�__,rr "'I. Mmm�ng 9 •r>:r.:�:a J
dn._Ie i t•:I•�enTl. wrin ll�P•r•nlr,Ins(dr'hr t,r-,-'le Len _, -
,J
•44—ren v-1-v:
ulan:r:ryl �c_IL��tLUc:%1.�-,glrrt::<k 1 -. �I ,-illar:nu(a _v,I J011:tl, _•JIB .F .., �r ,L
t.�.r.or.•u.'1,,:2de,0 111,'1=J;xjod illeh--4h.,,llapl.`.uF-rul''dl.._
•rd L4 ti LC!<k. tlm
■lalep■nc■.ray-."urfolrer:,^unrl �rtzl6aanr`eature: tfAMok Green LLD NedLLO CondNlon
.Frr,ne�;GI:AI?.ee n c-.c uTi�h:�mh�, r;�1lr�nl'F•,•rcSTil la�n^malnt,r„"o_LIr1r LcmC'ens3onr a^d
•F I .r yr n .J 1. Ill r.r arr I'nlrll.:I'Ih>-,`I n"I n r'." ,'d ..I•.•,- N. -
hn.=
u.-ar.-eola rl hwTr_I`riI(-�.ar rlrr PI11,..,.+ c^t
• TIh rUlrrn'r5N•Udnil Sn::Uth•,0 dloi o'd Pil I(tl�rGlr.'„9�dlnTn•�,•:r ilor-AVIFMn: r t-?du--['I•,
;Irt bnrrl.�fnla:'yTn'dAIR �rl Iti,oT r,+r ulnh,-mnr.,mr.duk mapdnd r:,wpf1M -"h rh'
,Vlr}r•-anlalr,npl-rrl:,r l rl'I lri.'. .7•Inn pr:,;or ul 7h.�sf^1'}Nfl(,a ler rlr-r.ir.t,r-&s;la:-;i--srnn(I,•n•,.�f,•
a d A� i�� n�em
.I.,,I,,,-,.,T e.�I',1•II fr,Ld r vaw7
e h,,n•. •. d, I■:luacl■.p«u.n il„ -I pl a. na•-.luylr<•rinud Project 18510LLCTG7FS
cpem ff)I.,cd:pl I.,naanl In`.prcnn^at tlm drlr;Iw F: .I ,6..'•J
.wti,T ul�uur,nl•Ael,d:r„y�r -.ellapwh nl.al�n.�'*Irrr,r ll„uLlr
,rI rut I I, I Prepared by: Gary MOOro
>r, Date:June 4,2019
,.,,j-„ x t.a Reviewed by:
I cl>II["h,C''U'Ur I Tfl V,IIA I .f: •T f JIL n Ard"I a
d ul r ti,+=I%='trm.T[r I1 t.[• ih d'.. r d u'�I_,Th I IDete:
/rNi6 :mow eh<oM1vi•,�rr r.:: ,I. .,� �, .:1
NICET III#:
Revision 1
A2*ncy Listings �g� a /
Q •...wMe , I AaGM !:��;sYAs �lls,Mu• (awl t :.._
L15T� aproY.d ■pPnesvd
N
Permit#: 2657
Permit Date: 07/02/19
Permit Type: FIRE ALARM
Project Name: Glasair Fire Alarm Alteration
Applicant Name: Sonitrol Pacific
Applicant Address: 2221 California St
Applicant, City, State, Zip: Everett,WA 98201
Contact: Erin Flemming
Phone: 253-878-2714
Email: eflemming@soundsecurity.biz
Scope of Work:
Valuation: 1489.00
Square Feet: 0
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 07/16/2019
Permit Expires:
Form Permit Type:
Status: IN PROCESS
Assigned To: Raelynn Jones
Property
Parcel# Address Legal Description Owner Name Owner Phone Zoning
31052200200100 18204 59TH AVE NE CITY OF 431 Airports&
ARLINGTON Flying Fields
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
SONITROL PACIFIC 425-258-3655 2221 CONSTRUCTION L&I SONITP*948D7
CALIFORNIA ST CONTRACTOR
Plan Reviews
Date Review Type Description Assigned To Review Status
07/02/2019 FIRE ALARM BUILDING
07/02/2019 FIRE ALARM 1.Permit and set of approved plans to remain on site FIRE
during installation.Installers shall present NICET II
certification upon request.
2.Trouble condition to be verified for signaling circuits.
3.Signal transmission to Central Station Monitoring
Company to be verified.
4.Installation completion form shall be submitted prior to
project close-out.
Fees
Fee Description Notes Amount
Fire Alarm Plan Review Fee $100.00
Fire Sprinkler System Commercial NFPA 13/13R $78.30
Processing/Technology $25.00
Credit Card Service $6.10
Total $209.40
Attached Letters
Date Letter Description
07/15/2019 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
07/15/2019 Erin Flemming 76171908 iTransact CC $203.30
07/15/2019 76171908 CC Surcharge Raelynn Jones $6.10
Outstanding Balance $0.00
Notes
Date Note Created By:
07/02/2019 Specs/Site Plan submittal ok per KO Raelynn Jones
Uploaded Files
Date File Name
07/16/2019 5328475-2657 Signed Permit.pdf
07/02/2019 5277368-2657 Specs and Site Plan.pdf
07/02/2019 5277369-2657 Application.pdf
07/02/2019 5277345-2657 Apylication.pdf