HomeMy WebLinkAbout17212 51ST AVE NE STE 101_BLD3961_2026 y �� FIRE SPRINKLER
• PERMIT APPLICATION
Department of Community&Economic Development
City of Arlington • 18204 59th Ave NE •Arlington,WA 98223 • Phone (360)403-3551
THIS APPLICATION MUST BE ACCOMPANIED BY TWO (2) SETS OF COMPLETE AND SCALED PLANS, TWO (2)
SETS OF HYDRAULIC CALCULATIONS, TWO (2) SETS OF EQUIPMENT SPECIFICATIONS FOR EACH FIRE
SPRINKLER PERMIT APPLICATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO INCLUDE
SPECIFICATION SHEETS, WIRING DIAGRAMS (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON
ALL EQUIPMENT TO BE INSTALLED PRIOR TO INSTALLATION.
Type of Permit: ❑ New Fire Sprinkler ❑x Fire Sprinkler Add/Alt ❑ Underground Fire Line
Project Address:
17260 51 st Ave. NE Parcel ID#: 31052100400100
Project Valuation: 19,750.00 Number of Heads: 39 Building Area(Sq Ft):
2756
Owner: Smartcap Phone Number: 425-896-8561
Address:8201 164th Ave SE #110 City. Redmond State:WA Zip Code: 98052
Contact Person: Derek Gust Phone Number: 253-284-3527
Cell Phone: 253-405-6202 Email: derekg@patriotfire.com
Address:
2707 70th Ave E City: Tacoma State: WA Zip Code:98424
Contractor:
Patriot Fire Protection Phone Number: 253-284-3527
Address: 2707 70th Ave E city: Tacoma State: WA Zip Code: 98424
Contractor's License Number: PATRIFP099CF Expiration: 1231/21
Contact Person: Derek Gust Email: derekg@patriotfire.com
I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the above-
cnbed property will be in accordance with the laws, rules and regulation of the State of Washington.
4m6/10/21
Applicants Signature Date
Derek Gust
Print Applicants Name
FOR STAFF USE ONLY R ece i ve,_1
'JUN 14 2021
Permit# Accepted By Amount Received Receipt# Date Received
WEB Forms—131 Page 1 of 1 6/16LP
3 lid— f 3- - -0-3�Y- 3 •— 33--0- - 3f — Q- - 3—� -0— �{ - - — H)3fdKl- -3 —� 3 — 3 - -OI— 3
0-6 I -0 • 3 • •, — — —
HANGER LEGEND
A "U" HOOK
B COACH SCREW ROD
D BM. CLAMP
E EYELET
LUSH SHELL
CEILING "STRAP
r
--- A 3F_ --- -- 1 1 1 ---- )1 G CEILING FLANGE
-..._ xEw RTxxE•D NODE,zwe,W.
33 o, W�NouxDxc BRA KET
H SIDE BEAM BRACKET
x.,o 0 o I K SHORT CLIP
42'-11 1-7 1 I • E IM ALL
342 —24 — 3 — 3 — 3 3 4 3 14'-2" N TOGGLE R NUT
D ROD
q1/2
O �1 P POWDER DRIVEN STUD_ 0-6 — — — — — — — J — — — — —� — 3— •� — — 3 — — -• — CUM TEe/ —SPIDIMM HUD R EXPANSION BOLT
�p \ TOE ) S PIPE SPIKE
0 2'-1" T
J48 /2) NEW FULL HEIGHT TYP. FLEXHEAD DETAIL D
WALL v
B0�'� 2 • SCALE:N.T.S. XD • -U _ Y
— — —
4,)F z
NEW FULL HEIGHT
• L STATE CERTIFICATION SPRINKLER LEGEND
WALL �� 1 MEh I,
•-I^ Q�J \ 1 1 0 • J rc MIME SUES
I ih 5 _ / I ��� ����H���TP����� � AND ttPE
•
3 3 3 I 3 3 3� ` • - - - - - _ _ - PIWB:RGtECTG„gypiHNEREp6Y TEMB i N, 5 3 , 1 0 0 /
0=6 —� - - - - — - -i—o- � —II- -� —� — — — — (IF—�E S�E�JLE
1 1 DerekJ.Gust SPRAT +z
o JQ' 1 9202-0912-C Leva13 1 T S 1"
I
- 1 Q LLLCCC I- O CI,v LIGHTS 1 Patriot Fire Protection,Ina 1 3 q ❑ ❑�3/a
Wa
I
��. . 1 P�jTgIFP 99CF �•1 T 3i svRAr � ■ 1
— S
__ O $I 1
o _________ __ 1 J.. �� +zronzA J T TIT LL
�s I' T DRY ttPE
I - � eBREAK � �7 2-WAY EARTHQUAKE BRACE TEMP MTING yc y $ z 3
oQ��' °Q� GWB CEILING AT
WAY EARTHOUAKE BRACE
I
9'-0" A.F.F. s,z o/2"a 1•
J" FITTING LEGEND
_ — z
3 3 0 (�T �_ � 0 3 3 3 � �• 1"
j0 1- P PIPE-Q-LET
D p p o - �jNf{(ii— SN GROOVED SHAPED NIPPLE
22! 1 � � HEAVY DASHED iNE INDICATES! X TEN THREADED SHAPEDHIPPE
N.A.S. BELOW 1 Q EN WHERE WALLS UN HRGUGH y AM AILANGE BE DROP NIPPLE APPROVAL REQUIRED
EXISTING CANOPY
, i1.G FIANCE CITY OF ARUNGTON
- G CEILING LURID T KE P AREAS RC REDUCING COUPI,NG
1� 0� �.�• O SPRINKLER HEAD LEGEND
_ 1 ,
1 �yR� r. 1� �-�-��
T � G 1 0
-_- - - O R'�I OW 1,5G0 S F. i m NAMN. NODFL Wx TYPE HUD nWEAD E xEAn E¢ural roe an
- - - � -_ i Mrtxex slsE FAcrOR nwsx Rxl9t
NEW FULL HEIGHT o-FIRM F1Raa w,NH DER PI)M W2 Vr 5M DDIM N/A 2Z 5
1 } OF F o F • RB➢K cs-56 PAAi5 6R WIVALE) W3 1 r 5.6c wN E 16R 22
- -- O Iff1P9E 0 W12 W PBBEM N1 1' 25A RDE A 165 16
Y
ALL
3 ; 1 3 ', x"' 3 3 3 Is6u W/165F Mg ME -W MME G5-% k%I5 6R M CDO W5 1 5A ME UK 217 z
�_.1 . UI� 4 SURFACE MOUNTED LED _6
- - - - —•— _•— — —•- - - - - - -fl - - - - � —
(�6 I LLG
o 1
I
AE
O 1 0e SUSPENDED-- \O� "'\�� '�Oel.. / /- 1 Taiu 39
_ _ CEILING AT �+�1/2, ,
IS I G SOFFIT-
0 � 1 I - - __ /��o��.( r !". E.F.
3 —.1-1-ON. DATE
A.
EXISTING
9' 0" A
I i
GENERAL NOTES
0 3 -6 S' sKoD HHEME ARE DENIER TO DDRER MPT RODS a DWDmol6 D.
a-.)—RE END TO DID.
6 • _ — — — —�.— _ — — 2�• — _ — • '_ • • _ • - — —.. — 2'x 4 A— I— — — — — — EAR,~DNAKE RRAaND=tea SE PRDWom W A�DRD W N
L—I Y L E_D NFPA PAN N X0.13,jQ}Q FD DN
^�... - - A- a. 'PE xAxuRs AxD NETxoO a xAxDBw ro¢IN
AcmRGAxEE wm1
L /( - �• HPPA PINPXI£T NO.13,2016 fDIDOX.
\ X
oJQ f �ti\ IGH I
OFF I( 0 6 OFF - c 1 FIX;
s. PPxD sxAu RE M AcaROAxDE wlm XWA pANPxIEr xo.13.2016 EDITrox
O 1 O O i i0 O O 6. JOIMNc of PIPE AM FO N1cs,THREAUS a WDDED.S-a M Acm1mANDE
/ cv MTH HIM PANPH1n No.13,wle Ewnal.
7. OWNER TO PROWOE xDEO N HAT A AREAS PBOTEC,ED EY A WET PIPE SPHNDER
O O O
-' -
II 2 - I > a•. � � �'� G�Fes' 1-0
E ' STD TD R NT WA ER H NES ROM PED)LNG.O
— — —- _,�— _ - — — — _ ,��� _- _ — — a. Au welllc w EI£OTaCM DEvroEs 6F REauREDI ro DE PROnDEO
O ar OTHERB.
o i o o PAIN1nD OF PPE:EWPHONT(R RE H.).BE-DE.
3 - _ - Br oTxEPs
3 3Appfov�
B.
- .____. 1D.FNRPoNO aP nPE a EaupNENT N REaIxREo TO BE PRovDEo
1-0
DESIGN CRITERIA
--�
Arlanaen F.rt Oe..+N e NF 5 P i. DESIGNED PER NFPA 13,2016 ED.
See a#oaA.eRl plern+.�H eaA�r✓••a,Ns
----------------------------------------------------------- = -- - ------- -
---------------------- ---------------------- -- -- ---- --------� CITY OF ARLINGTON
EXISTING SOFFIT- EXISTING CANOPY-
BUILDING DEPARTMENT
N.A.S. BELOW N.A.S. BELOW APPROVED
PIPE NOTES
OATgy 1. THREADED PIPE TO BE BLACK SCH. 40.
NO CHANGES AUTHORIZED
UNLESS APPROVED BY THE
BUILDING INSPECTOR
REVISIONS
1 2 JOB COPY ND DA E DEBGRIPTIDN
PARTIAL FIRE SPRINKLER PLAN
SEAT 7-17 ° 81
SMARTCAP CONSTRUCTION
SCALE Ile 1'-0" SITE 8201 164TH AVE. NE, SUITE 110
REDMOND.WA. 98052
SCOPE OF WORK ftbn IMd- �u --"---
MODIFY EXISTING FIRE SPRINKLER SYSTEM FOR NEW T.I.WALLS AND CDUNGS T—.�-._— -_.-.—._,-- NKNEDE WE:
ADD AND RELOCATE FIRE SPRINKLERS AS NEEDED 4 VOLUNTEERS OF AMERICA
f PARTIAL FIRE SPRINKLER PLAN �0,6atkl
2"x STIFFENER 17260 ARLINGTON,TWA E. NE Received
& TOLCO #R 2. DENOTES NEW FIRE SPRINKLER PIPING. o - •A a GENERALNOTESr7
W�6"x2" LAG BOLT --- - _ JUN 14 2021
--
& 4P6" WASHER 1. -------- DENOTES EXISTING FIRE SPRINKLER PIPING. - -
Ya" ALL THREAD ROD 3. ALL EXISTING FIRE SPRINKLER HEADS TO REMAIN U.N.O. I I " pATRIOT PATRIFP099CF
4. REFERENCE SPRINKLER HEAD LEGEND FOR NEW HEADS TO BE INSTALLED. .,,.. < WWW.PATRIOTRRE.COM
5. NEW 25.2K ESFR SPRINKLERS SHALL BE INSTALLED PER NFPA 13,SECTION 8.12 DERIXG®patn0lfire.Dorn
ANVIL FIG. G NEW 25.2K ESFR SPRINKLERS SHALL BE INSTALLED SO THE DEFLECTORS ARE NOT MORE 1Q _ ■FIRE PROTECTION INC.
HANGER RING R
1>T'AND NOT LESS THAN 6" BELOW THE CEILING PER SECTION 8.12.4.1.3. - _ [ 2707 70TH AVENUE EAST TEL- (253)926-2290
6. ALL CEILING HEIGHTS TO BE 9'-0'AFF U.N.O. TACOMA,WA 96424 FAX:(253)922-6150
TYP.HANGER DETAIL KEY PLAN VICINITY MAP DESIGNER DEREK G. SHEET
SCALE:N.T.S. SCALE N.T.S. SCALE:N.T.S.
' , JOB ENO. JUN2-2259621 OF FP-1
CITY OF ARLINGTON
18204 59th Avenue NE,Arlington,WA 98223
INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551
BUILDING PERMIT
Permit#:3961
17212 51ST AVE NE#100 PERMIT EXPIRES 180 DAYS AFTER
DATE OF ISSUANCE.
Parcel#: 31052100400100 Valuation: 19750.00
OWNER APPLICANT CONTRACTOR
SMARTCAP ARLINGTON AIRPORT patriot Fire Protection,Inc PATRIOT FIRE PROTECTION
INDUSTRIAL PARK QOZB,LLC
8201 164TH AVE NW, SUITE 110 2707 70th Ave E. 2707 70th Ave E.
REDMOND,WA 98052 Tacoma,WA 98424 Tacoma,WA 98424
2532843527 253-926-2290
LIC:PATRIFP099CF EXP: 10/05/2022
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR: 2018
STORIES: CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any
other ordinance or order of the City,of any state or federal law, or of any order,proclamation,guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City, or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order,state or federal law,or any order,proclamation,guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/IRC110.
SALES TAX NOTICE-Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
Derek Gust July 8 2021
Signature Print Name Date Released By ate
CONDITIONS
1.Permit and set of approved plans to remain on site during installation. 2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections: may include hangers, earthquake bracing,
sprinkler locations and pipe re-routing that could impact hydraulic calculations.Failure to submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is conducted. 3.Cover inspection required.4.Hydrostatic
test required: 200 psi for 2 hours minimum. 5. Sprinkler system Contractor's Material and Test Certificate shall be submitted to
The Compliance Engine prior to close out of permit. 6. Owner shall be provided with a set of approved plans and associated
documents for their files.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
07/07/2021 Fire Sprinkler Permit $300.00
07/07/2021 Processing/Technology Fee $25.00
07/07/2021 Fire System Plan Review $312.71
Total Due: $637.71
Total Payment: $0.00
Balance Due: $637.71
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
CITY OF ARLINGTON
18204 59th Avenue NE,Arlington,WA 98223
INSPECTIONS: 360-403-3417-Permit Center: 360-403-3551
BUILDING PERMIT
Permit#:3961
17212 51ST AVE NE#100 PERMIT EXPIRES 180 DAYS AFTER
DATE OF ISSUANCE.
Parcel#: 31052100400100 Valuation: 19750.00
OWNER APPLICANT CONTRACTOR
SMARTCAP ARLINGTON AIRPORT patriot Fire Protection,Inc PATRIOT FIRE PROTECTION
INDUSTRIAL PARK QOZB,LLC
8201 164TH AVE NW, SUITE 110 2707 70th Ave E. 2707 70th Ave E.
REDMOND,WA 98052 Tacoma,WA 98424 Tacoma,WA 98424
2532843527 253-926-2290
LIC:PATRIFP099CF EXP: 10/05/2022
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC#: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR: 2018
STORIES: CONST.TYPE:
DWELLING UNITS: OCC GROUP:
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for,or approval of,any violation of this Code or any
other ordinance or order of the City,of any state or federal law, or of any order,proclamation,guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law,or order,proclamation,guidance
advice or decision of the Governor of this State,this permit shall not authorize such work and shall not be valid.The building
official is authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this
jurisdiction or any other ordinance or executive order of the City, or of any state or federal law,or of any order,proclamation,
guidance advice or decision of the Governor. The building official is authorized to suspend or revoke this permit if it is
determined to be issued in error or on the basis of incorrect,inaccurate or incomplete information,or in violation of any City
ordinance,regulation or order,state or federal law,or any order,proclamation,guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY,NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE
OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/IRC110.
SALES TAX NOTICE-Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington#3101.
�Z7� 71
Signature Print Name Date Released By ate
CONDITIONS
1.Permit and set of approved plans to remain on site during installation. 2. Significant deviations from approved plans made
during installation shall be required to be resubmitted for review prior to inspections: may include hangers, earthquake bracing,
sprinkler locations and pipe re-routing that could impact hydraulic calculations.Failure to submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is conducted. 3.Cover inspection required.4.Hydrostatic
test required: 200 psi for 2 hours minimum. 5. Sprinkler system Contractor's Material and Test Certificate shall be submitted to
The Compliance Engine prior to close out of permit. 6. Owner shall be provided with a set of approved plans and associated
documents for their files.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED.THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN(CURBS, SIDEWALKS,DRIVEWAYS,
MARQUEES,ETC.)WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
07/07/2021 Fire Sprinkler Permit $300.00
07/07/2021 Processing/Technology Fee $25.00
07/07/2021 Fire System Plan Review $312.71
Total Due: $637.71
Total Payment: $0.00
Balance Due: $637.71
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection,allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number,Type of Inspection being requested,and whether you prefer morning or afternoon
• 1
Permit#: 3961
Permit Date: 06/15/21
Permit Type: FIRE SPRINKLER
Project Name: Volunteers of America
Applicant Name: Patriot Fire Protection, Inc
Applicant Address: 2707 70th Ave E.
Applicant, City, State, Zip: Tacoma,WA 98424
Contact: Derek Gust
Phone: 2532843527
Email: derekg@patriotfire.com
Scope of Work: Fire sprinkler Alteration
Valuation: 19750.00
Square Feet: 2756
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 07/08/2021
Permit Expires: 01/06/2022
Form Permit Type:
Status: COMPLETE
Assigned To:
Property
Parcel# Address Legal Description Owner Name Owner Phone Zoning
SMARTCAP ARLINGTON 301 AP-INDUSTRIAL/
31052100400100 17212 51 ST AVE NE STE 101 AIRPORT AIRPORT INDUSTRIAL MANUFACTURING
PARK QOZB,LLC
Contractors
Contractor Primary Contact Phone Address Contractor Type License License#
PATRIOT FIRE PROTECTION Derek Gust 2532843527 2707 70th Ave E. CONSTRUCTION Labor and Industries PATRIFP099CF
CONTRACTOR
Inspections
Date Inspection Type Description Scheduled Date Completed Date Inspector Status
09/02/2021 C00.CONSULTATION 06/02/2021 BUILDING Approved
FS05.ABOVEGROUND Move sprinkler head 4"away from Corrections-
08/27/2021 HYDRO demising wall 08/27/2021 FIRE Needs reinspection
Plan Reviews
Date Review Type Description Assigned To Review Status
06/15/2021 FIRE SPRINKLER BUILDING
1.Permit and set of approved plans to remain on site during installation.
2.Significant deviations from approved plans made during installation shall be
required to be resubmitted for review prior to inspections:may include
hangers,earthquake bracing,sprinkler locations and pipe re-routing that could
impact hydraulic calculations.Failure to submit revisions could result in
cancellation of an inspection while a review of an as-built resubmittal is
06/15/2021 FIRE SPRINKLER conducted. FIRE
3.Cover inspection required.
4.Hydrostatic test required:200 psi for 2 hours minimum.
5.Sprinkler system Contractor's Material and Test Certificate shall be
submitted to The Compliance Engine prior to close out of permit.
6.Owner shall be provided with a set of approved plans and associated
documents for their files.
Fees
Fee Description Notes Amount
Fire Sprinkler System Commercial NFPA 13/13R $300.00
Processing/Technology $25.00
Fire System Plan Review Table 4-1 $312.71
Credit Card Service $19.13
Total $656.84
Attached Letters
Date Letter Description
07/07/2021 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
07/07/2021 Derek Gust 87399378 $637.71
07/07/2021 87399378 Ameresia Lawlis $19.13
Outstanding Balance $0.00
Notes
Date Note Created By:
10/30/2023 confirmed by KO file is complete.Filing for retention in 2023 Hannah Hardwick
07/08/2021 Approved plans emailed to applicant Raelynn Jones
Uploaded Files
Date File Name
07/08/2021 9192535-3961 Permit-signgd.pdf
06/15/2021 9030276-3961 Application.pdf
City , Arlington
• , aR ,
• T:�
Fire Department
June 29, 2021
Permit Number: BLD 3961
Project Address: 17212 5111 Avenue NE #100, Arlington
Project Description: Fire Sprinkler Plans —Volunteers of America
Contractor: Patriot Fire Protection
2707 70' Avenue E
Tacoma, WA 98424
Re: Fire Suppression Shop Drawing Review Comments/Approval
The Arlington Fire Department has completed a review of the Fire Suppression shop drawing submittal and
approves the issuance of the permit with the following conditions:
1. Permit and set of approved plans to remain on site during installation.
2. Significant deviations from approved plans made during installation shall be required to be resubmitted for
review prior to inspections: may include hangers, earthquake bracing, sprinkler locations and pipe re-
routing that could impact hydraulic calculations. Failure to submit revisions could result in cancellation of
an inspection while a review of an as-built resubmittal is conducted.
3. Cover inspection required.
4. Hydrostatic test required: 200 psi for 2 hours minimum.
5. Sprinkler system Contractor's Material and Test Certificate shall be submitted to The Compliance Engine
prior to close out of permit.
6. Owner shall be provided with a set of approved plans and associated documents for their files.
Items noted above are conditions on the issued permit and shall be verified as part of the final inspection of the
system at project completion. Final approval will not be provided until all conditions are verified. Call at least
48 hours in advance to schedule inspections.
If there are any questions please do not hesitate to call.
Sincerely,
K&
Mike Makela
Assistant Fire Chief
Arlington Fire Department