HomeMy WebLinkAbout4228 Airport Blvd_BLD3733_2025
Permit #: 3733
Permit Date: 02/25/21
Permit Type: FIRE SPRINKLER
Project Name: Fire Station 48
Applicant Name: American Sprinkler Corp
Applicant Address: 2311 153rd Avenue SE
Applicant, City, State, Zip: Snohomish, WA
Contact: Doug Buehler
Phone: 425-210-3841
Email: doug@americansprink.com
Scope of Work: New fire sprinkler installation for fire station
Valuation: 50000.00
Square Feet: 11780
Number of Stories: 2
Construction Type: VB
Occupancy Group: B; Business
ID Code: CIC
Permit Issued: 04/01/2021
Permit Expires: 09/28/2021
Form Permit Type:
Status: COMPLETE
Assigned To:
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
CITY OF 251 AP - BUSINESS
31052100202000 4228 AIRPORT BLVD
ARLINGTON / PROFESSIONAL
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
AMERICAN
DOUG 2311 153RD AVE CONSTRUCTION
SPRINKLER 425-335-4645 COA 601 404 481
BUEHLER SE CONTRACTOR
CORPORATION
AMERICAN
DOUG 2311 153RD AVE CONSTRUCTION Labor and
SPRINKLER 425-335-4645 AMERISC087NC
BUEHLER SE CONTRACTOR Industries
CORPORATION
Plan Reviews
Date Review Type Description Assigned To Review Status
02/26/2021 FIRE SPRINKLER BUILDING
1. Permit and set of approved plans to remain on site
during installation.
2. Significant deviations from approved plans made during
installation shall be required to be resubmitted for review
prior to inspections: may include hangers, earthquake
bracing, sprinkler locations and pipe re-routing that could
impact hydraulic calculations. Failure to submit revisions
could result in cancellation of an inspection while a review
of an as-built resubmittal is conducted.
3. Hangers and earthquake bracing shall be installed in
accordance with NFPA 13.
02/26/2021 FIRE SPRINKLER Mike Makela
4. Weatherproof horn strobe to be installed on side of
building facing Airport Blvd in place of proposed electric
bell. See approved FA plans.
5. Hydrostatic test required: Minimum of 200 psi for 2
hours.
6. Sprinkler system Contractor’s Material and Test
Certificate shall be submitted prior to close out of permit.
7. Final as-built drawings shall be submitted prior to close
out of permit.
8. Owner shall be provided with a set of approved plans
and associated documents for their files.
no comments for this review. The BFP is on the material
02/26/2021 FIRE SPRINKLER PW-WAT-REV
list
Fees
Fee Description Notes Amount
Fire System Plan Review Table 4-1 $628.71
Credit Card Service $18.86
Total $647.57
Attached Letters
Date Letter Description
03/24/2021 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
02/27/2021 Doug Buehler 85154140 $628.71
02/27/2021 Doug Buehler 85154140 Jennifer Pittman $18.86
Outstanding Balance $0.00
Notes
Date Note Created By:
03/25/2021 Emailed the permit for signature. Kristin Foster
Uploaded Files
Date File Name
09/21/2021 9725331-3733_Inspection - Sprinkler Cover.pdf
04/02/2021 8462948-3733_Issued Permit.pdf
02/26/2021 8234387-3733_Plans.pdf
02/26/2021 8234388-3733_PRODUCT DATA.pdf
02/26/2021 8234389-3733_Application.pdf
02/26/2021 8234390-3733_HYDRAULIC CALCULATIONS.pdf
02/26/2021 8234041-3733_Application.pdf