Model Number YSC060E3EMA**C00000000300000000000000000
Customer : .
Project : .
Name : .
YSC060E3EMA0047
General
Unit function DX cooling, gas heat Unit efficiency Standard efficiency
Airflow Convertible configuration Airflow Application Downflow
Design Airflow 2000 Evaporator rows 4.00
Fresh air selection Econ-dry bulb 0-100% 3hp Evaporator fin spacing 192
Evaporator face area 7.71 Tonnage 5 Ton
Evaporator face velocity 259 Min. unit operating weight 613.0
Cooling Entering DB 80.00 Max. unit operating weight 824.0
Cooling Entering WB 67.00 Ent Air Relative Humidity 51.08
ASHRAE 90.1 Yes Ambient Temp 95.00
Rated capacity (AHRI) 60.00 Heating capacity Medium gas heat 3ph
Heating EAT 70.00 Voltage 208-230/60/3
Design ESP 0.500 Major design sequence E - R-410A
Main Cooling
Tonnage 5 Ton Cooling Entering DB 80.00
Cooling Entering WB 67.00 Ent Air Relative Humidity 51.08
Ambient Temp 95.00 Evap Coil Leaving Air Temp (DB) 57.73
Evap Coil Leaving Air Temp (WB) 56.93 Cooling Leaving Unit DB 59.56
Cooling Leaving Unit WB 57.63 Gross Total Capacity 62.27
Gross Sensible Capacity 48.11 Gross Latent Capacity 14.16
Net Total Capacity 59.10 Net Sensible Capacity 44.94
Net Sensible Heat Ratio 0.76 Fan motor heat 3.17
Dew Point 56.41 Refrig charge (HFC-410A) - ckt 1 9.4
Saturated Discharge Temp Circuit 1 121.07 Saturated Suction Temp Circuit 1 52.21
Main Heating
Heating capacity Medium gas heat 3ph Input Heating Capacity 80000.00
Output Heating Capacity 64000.00 Output Heating Cap. w/Fan 67171.27
Heating EAT 70.00 Heating LAT 99.90
Heating Delta T 29.90
Motor/Electrical
Page 1
Voltage 208-230/60/3 Design ESP 0.500
Component SP 0.180 Total Static Pressure 0.680
Field supplied drive kit required None Indoor mtr operating power 0.964
Indoor RPM 1076 Indoor Motor Power 0.72
Outdoor Motor Power 402.6 Compressor Power 4.34
System Power 5.46 SEER @ AHRI 13.00
MCA 27.40 MOP 40.00
Compressor 1 RLA 15.90 Compressor 2 RLA 0.00
Condenser fan FLA 2.50 Evaporator fan FLA 5.00
Exhaust fan power 0.870
DX Cooling, Gas Heat 3-10 Ton
Unit controls Electro mechanical controls 3ph Refrigeration controls Frostat and crankcase heater 3ph
Page 2
Y4C
Job Information
.
.
.
Tag YSC060E3EMA0047
Quantity 1 Model number YSC060E3EMA**C00000
00030000000000000000
0
Meets
Unit Information
Tonnage 5 Ton Unit function DX cooling, gas heat
Min. unit operating weight 613.0 lb Max. unit operating weight 824.0 lb
Design Airflow 2000 cfm
Cooling Information
Gross Total Capacity 62.27 MBh Gross Sensible Capacity 48.11 MBh
Gross Latent Capacity 14.16 MBh Net Total Capacity 59.10 MBh
Net Sensible Capacity 44.94 MBh Net Sensible Heat Ratio 0.76 Number
Cooling Entering DB 80.00 F Cooling Entering WB 67.00 F
Cooling Leaving Unit DB 59.56 F Cooling Leaving Unit WB 57.63 F
Ambient Temp 95.00 F
Heating Information
Heating capacity Medium gas heat 3ph Input Heating Capacity 80000.00 Btuh
Output Heating Capacity 64000.00 Btuh Heating EAT 70.00 F
Heating LAT 99.90 F Heating Delta T 29.90 F
Motor/Electrical Information
Voltage 208-230/60/3 Design ESP 0.500 in H2O
Indoor Motor Power 0.72 kW Indoor mtr operating power 0.964 hp
Indoor RPM 1076 rpm Outdoor Motor Power 402.6 W
Compressor Power 4.34 kW System Power 5.46 kW
MCA 27.40 A MOP 40.00 A
Compressor 1 RLA 15.90 A Evaporator fan FLA 5.00 A
Condenser fan FLA 2.50 A
Electrical values provided are estimated only and are subject to change without notice and may differ from nameplate values .
Field installed low or high static drive kits may be needed. Please check the fan performance tables in the product catalog for application ranges.
12/26/2014
Page 1 of 1
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Page 9
Page 10
General
The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for units with
microprocessor controls. Operating range for units with electromechanical controls shall be between 115°F and 40°F. Cooling performance shall be rated
in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to
check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and
numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for Central Cooling Air Conditioners.
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a
weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction
shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners
while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil-faced,
fire-retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with 1/8 inch, foil-faced, closed-cell insulation. All insulation
edges shall be either captured or sealed. The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch
high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have
provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit.
Unit Top
The top cover shall be one piece construction or, where seams exist, it shall be double-hemmed and gasket-sealed. The ribbed top adds extra strength
and enhances water removal from unit top.
Filters
Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall also be available.
Compressors
All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a
voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors.
Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on
7½-10 ton models and allow for efficient cooling utilizing 3-stages of compressor operation for all high efficiency models.
Notes:
Crankcase heaters are optional on YSC (036, 048, 060, 072, 090, 102, 120); standard on YHC (036, 048, 060, 072, 092, 102, 120).
Indoor Fan
The following units shall be equipped with a direct drive plenum fan design (T/YSC120E, T/YHC092,102, 120E). Plenum fan design shall include a
backward-curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed
adjustment potentiometer located in the control box. 3-5 ton units (standard efficiency 3-phase or high efficiency 3-phase with optional motor) are belt
driven, FC centrifugal fans with adjustable motor sheaves. 3-5 ton units (1-phase or high efficiency 3-phase) have multispeed, direct drive motors. All 6-8½
ton units (standard efficiency) shall have belt drive motors with an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All
motors shall be thermally protected. All 10 tons and 7½-8½ (high efficiency) have variable speed direct drive motors. All indoor fan motors meet the U.S.
Energy Policy Act of 1992 (EPACT).
Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor shall be
permanently lubricated and shall have built-in thermal overload protection.
Evaporator and Condenser Coils
Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. The microchannel type condenser coil is
standard for the T/YSC 10 ton models and 7½ ton high efficiency models. The microchannel type condenser coil is not offered on the 7½ ton
dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube-to-fin bond, microchannel coil has better heat transfer
performance. Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better
compressor reliability. Compact all-aluminum microchannel coils also help to reduce the unit weight. All-aluminum construction improves re-cyclability.
Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat
streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure
integrity. The evaporator coil and condenser coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The condenser coil
shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A removable, reversible, double-sloped condensate drain pan
with through the base condensate drain is standard.
Page 11
Controls
Unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an
external location for mounting a fused disconnect device. A choice of microprocessor or electromechanical controls shall be available. Microprocessor
controls provide for all 24V control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to
electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes
drift from set point, and provides better building comfort. A centralized microprocessor shall provide anti-short cycle timing and time delay between
compressors to provide a higher level of machine protection. 24-volt electromechanical control circuit shall include control transformer and contactor
High Pressure Control
All units include High Pressure Cutout as standard.
Phase monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal.
Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments. The module will automatically reset from a
fault condition.
Refrigerant Circuits
Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter driers are factory-installed as standard.
An area shall be provided for replacement suction line driers.
Gas Heating Section
The heating section shall have a progressive tubular heat exchanger design using stainless steel burners
and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes. The
heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before
ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units
shall be suitable for use with natural gas or propane (field-installed kit) and also comply with the California requirement for low NOx emissions
(Gas/Electric Only).
Economizer
This accessory shall be available with or without barometric relief. The assembly includes fully modulating 0-100 percent motor and dampers, minimum
position setting, preset linkage, wiring harness with plug, spring return actuator and fixed dry bulb control. The barometric relief shall provide a pressure
operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment off cycle. Optional solid state or differential
enthalpy control shall be available for either factory or field installation. The economizer arrives in the shipping position and shall be moved to the
operating position by the installing contractor.
Frostat
This option is to be utilized as a safety device. The Frostat opens when temperatures on the evaporator coil fall below 10°F. The temperature will need to
rise to 50°F before closing. This option should be utilized in low airflow or high outside air applications. (Cooling with Electric Heat Only.)
Frostat
This option is to be utilized as a safety device.The Frostat opens when temperatures on the evaporator coil fall below 10°F.The temperature will need to rise
to 50°F before closing.This feature should be utilized in low airflow or high outside air applications (cooling only).
Page 12
Permit #: 826
Permit Date: 10/23/15
Permit Type: COMMERCIAL MECHANICAL
Project Name: Center Pointe Building, LLC
Applicant Name: Smith Mechanical
Applicant Address: 6146 Portal Way
Applicant, City, State, Zip: Ferndale, WA 98248
Contact: Jared Murphy
Phone: 360-815-6947
Email: jmurphy@smithmechanical.com
Scope of Work: New RTU on existing roof curb
Valuation: 18000.00
Square Feet: 0
Number of Stories: 1
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 10/29/2015
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Launa Black
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
CENTERPOINTE 539 Other Retail
00645300000601 3204 SMOKEY POINT DR
BUILDING LLC Trade NEC
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
CONSTRUCTION
Smith Mechanical Brad Ludwigsen 360 384 3203 6146 Portal Way COA 602003351
CONTRACTOR
CONSTRUCTION Labor &
Smith Mechanical Brad Ludwigsen 360 384 3203 6146 Portal Way SMITHMI004CA
CONTRACTOR Industries
Inspections
Date Inspection Type Description Scheduled Date Completed Date Inspector Status
R15.
HVAC installation & duct
11/06/2015 MECHANICAL 11/06/2015 11/06/2015 BUILDING Approved
sealing approved
FINAL
C10.
11/06/2015 MECHANICAL 11/06/2015 BUILDING Approved
ROUGH-IN
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
10/23/2015 BUILDING
MECHANICAL
Fees
Fee Description Notes Amount
Gas Piping/Units Enter # of units $10.00
Mechanical Fee (Enter Fixture Fee) $25.00
Mechanical Base Permit Fee $25.00
Mechanical Commercial Plan Review Table 4-1 $250.00
Total $310.00
Attached Letters
Date Letter Description
10/27/2015 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
10/29/2015 Centerpointe Building, LLC check #3312 Launa Black $310.00
Outstanding Balance $0.00
Uploaded Files
Date File Name
01/22/2016 1435061-0110_001.pdf
01/22/2016 1435057-0109_001.pdf
01/22/2016 1435054-0108_001.pdf
10/29/2015 1344929-826_Issued Permit.pdf
10/23/2015 1337383-Mechanical Site Plan.pdf
10/23/2015 1337384-Mechanical_Permit_Application_CVXz0bKZy9DL3b.pdf
10/23/2015 1337385-3204_Dabestani TI mechanical plan.pdf
10/23/2015 1337386-3204_YSC060E3EMA0047_Submittal.pdf
Google Maps https://www.google.com/maps/@48.1543418,-122.1869938,77m/data=!...
✔ ✔
3204 Smokey Point Dr.
Set RTU on existing curb and install ductwork install for TI
18000
The Dabestani Group 360-653-9899
3204 Smokey Pt Dr Suite 202 Arlington WA 98223
mallorie@dabestanigroup.com
Jared Murphy
360-815-6947
6146 Portal Way Ferndale WA 98248
jmurphy@smithmechanical.com
Smith Mechanical 360-384-3203
6146 Portal Way Ferndale WA 98248
jmurphy@smithmechanical.com
1/29/16
SMITHMI004CA
1
1
10/21/2015
Jared Murphy