DAILY FIELD REPORT
Date
AAR TESTING AND INSPECTION, INC. 10/13/2025
Report
7126 180th Ave NE, Suite C101, Redmond, WA 98052 | 425-881-5812 Number
BAV101325B
CLIENT INFORMATION PROJECT INFORMATION
Contact Project No. 25-644
Company Project Name
Address Address
City City
Contractor Five Star Mechanical Permit No. 6717
INSPECTION TYPE(S) STRUCTURE(S) / LOCATION(S)
Structural Steel Welding Roof Support Angle and Deck Puddle Welds - Grid C.8/5.5.
Weather Temperature (°F) Start Time End Time
Sunny 55 12:00 PM 01:30 PM
DRAWINGS / DOCUMENTS REFERENCED
AHBL drawing/S1.1, 4/S4.2. AWS D1.1.
INSPECTION OBSERVATION / REMARKS
1. I received a WABO welder card from Jerard J. Kolrud #W05085 expiration date 4/1/2026 of Northwest Erection & Fab.
2. I inspected the welds of new L5x5x5/16 L angles around penetration and cross member as shown on detail 4/S4.2.
3. 2" of bearing both sides and ends of angles with 3/16" fillet welds. Added clips in corners of cross member and welded all around with 3/16"
fillet welds.
4. I observed decking welded with 5/8" diameter at valley bottoms to angle cross member. The decking pieces were also crimped.
5. The welds are visually acceptable according to AWS D1.1 visual acceptance criteria.
Items inspected are in conformance with approved plans, specifications, and jurisdictional requirements
Inspectors Inspectors Name Report Date Reviewers Reviewed By Reviewed Date
Signature Brian Valukonis 10/13/2025 Signature Teajalam (TJ)
Gounden
e068c8ffca5bd98f-1760224347275
Inspection
DAILY FIELD REPORT
Date
AAR TESTING AND INSPECTION, INC. 10/13/2025
Report
7126 180th Ave NE, Suite C101, Redmond, WA 98052 | 425-881-5812 Number
BAV101325B
PHOTOS
Detail 4/S4.2. The roof opening.
The 2" long fillet welded on the angle at a roof joist. The cross member
Inspectors Inspectors Name Report Date Reviewers Reviewed By Reviewed Date
Signature Brian Valukonis 10/13/2025 Signature Teajalam (TJ)
Gounden
e068c8ffca5bd98f-1760224347275
Inspection
DAILY FIELD REPORT
Date
AAR TESTING AND INSPECTION, INC. 10/13/2025
Report
7126 180th Ave NE, Suite C101, Redmond, WA 98052 | 425-881-5812 Number
BAV101325B
Decking underside.
A5/8" puddle weld.
Inspectors Inspectors Name Report Date Reviewers Reviewed By Reviewed Date
Signature Brian Valukonis 10/13/2025 Signature Teajalam (TJ)
Gounden
e068c8ffca5bd98f-1760224347275
Inspection
DAILY FIELD REPORT
Date
AAR TESTING AND INSPECTION, INC. 10/13/2025
Report
7126 180th Ave NE, Suite C101, Redmond, WA 98052 | 425-881-5812 Number
BAV101325B
Crimped decking.
Inspectors Inspectors Name Report Date Reviewers Reviewed By Reviewed Date
Signature Brian Valukonis 10/13/2025 Signature Teajalam (TJ)
Gounden
e068c8ffca5bd98f-1760224347275
CITY OF ARLINGTON
18204 59th Avenue NE, Arlington, WA 98223
INSPECTIONS: 360-403-3417 - Permit Center: 360-403-3551
BUILDING PERMIT
18410 63RD AVE NE Permit #: 6717
PERMIT EXPIRES 180 DAYS AFTER
Parcel #: 31052200101000
DATE OF ISSUANCE.
Scope of Work: Install factory made venting on a furnace Valuation: 104000.00
OWNER APPLICANT CONTRACTOR
CASTING OPERATIONS LLC Five Star Mechanical Five Star Mechanical
21218 76TH AVE S 7509 Grange ST West 7509 Grange St. West
KENT, WA 98032 Lakewood, WA 98499 Lakewood, WA 98499
206-786-8278 206-786-8278
LIC: 601 937 083 EXP: 03/31/2026
LIC: FIVESM*010JT EXP: 05/01/2026
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
LIC #: EXP: LIC #: EXP:
JOB DESCRIPTION
PERMIT TYPE: COMMERCIAL MECHANICAL CODE YEAR: 2021
STORIES: 1 CONST. TYPE: llA
DWELLING UNITS: OCC GROUP: B; Business
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
The issuance or granting of this permit shall not be construed to be a permit for, or approval of, any violation of this Code or any
other ordinance or order of the City, of any state or federal law, or of any order, proclamation, guidance advice or decision of the
Governor of this State. To the extent the issuance or granting of this permit is interpreted to allow construction activity during any
period of time when such construction is prohibited or restricted by any state or federal law, or order, proclamation, guidance advice
or decision of the Governor of this State, this permit shall not authorize such work and shall not be valid. The building official is
authorized to prevent occupancy or use of a structure where in violation of this Code, any other City ordinances of this jurisdiction or
any other ordinance or executive order of the City, or of any state or federal law, or of any order, proclamation, guidance advice or
decision of the Governor. The building official is authorized to suspend or revoke this permit if it is determined to be issued in error or
on the basis of incorrect, inaccurate or incomplete information, or in violation of any City ordinance, regulation or order, state or
federal law, or any order, proclamation, guidance or decision of the Governor.
I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK
AUTHORIZED THEREBY; NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE
STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND
ALL FEES ARE PAID.
IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN
MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. IBC110/IRC110.
SALES TAX NOTICE: Sales tax relating to construction and construction materials in the City of Arlington must be reported on
your sales tax return form and coded City of Arlington #3101.
10/23/2025
Applicant Signature Date Building Official Date
CONDITIONS
Adhere to approved plans. Permit shall be onsite for inspection. Call for inspections.
The property owner shall ensure that the construction project complies with all applicable zoning codes and regulations. The property
owner shall also ensure that the construction project does not cause any adverse impact on the surrounding environment or
community. The property owner shall be responsible for obtaining all necessary permits and approvals from the relevant authorities
before commencing construction. The property owner shall ensure that the construction project complies with all applicable design
review requirements.
THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE
PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS,
MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
10/23/2025 Web Only - Mechanical Commercial Plan Review $995.40
10/23/2025 Credit Card Service $29.86
10/23/2025 Processing/Technology $25.00
10/23/2025 Ductwork/Dryer Duct $25.00
10/23/2025 Gas Piping/Units $15.00
10/23/2025 Credit Card Service $1.95
Total Due: $1,092.21
Total Payment: $1,092.21
Balance Due: $0.00
CALL FOR INSPECTIONS
Call by 3:30 pm for next day inspection, allow 48 hours for Fire Inspections
When calling for an inspection please leave the following information:
Permit Number, Type of Inspection being requested, and whether you prefer morning or afternoon
INSPECTION INFORMATION Pass/Fail
COMMERCIAL MECHANICAL APPLICATION
Community & Economic Development
City of Arlington • 18204 59th Ave NE • Arlington, WA 98223 • Phone (360) 403-3551
This application is for new, addition, altered or replaced mechanical installation and new or altered gas piping and
must be accompanied by ELECTRONIC CONSTRUCTION DRAWINGS and CUT SHEETS and/or information outlined
in the MECHANICAL SUBMITTAL REQUIREMENTS, if applicable.
Type of Permit: ï² New Installation ï² Addition ï² Alteration ï² Replaced ï² Gas Piping
Type I and Type II Hood Systems required submittal of the Commercial Mechanical Addenda
Property Address: Project Valuation:
Lot #: Parcel ID No.: Preferred Contact: ï² Owner ï² Contractor
Project Description:
Owner Name: Office No.:
Email Address: Cell No.:
Mailing Address: City: State: Zip:
Contractor Name: Office No.:
Email Address: Cell No.:
Mailing Address: City: State: Zip:
L&I Contractor License Number: Expiration Date:
• New gas piping requires a pressure test hooking to any appliance
• Sediment traps (drips) are required on all gas lines
• Gas lines are required to be supported/secured per IFGS, Section 415
• Proper Combustion air and venting required for all appliances
• A shut-off valve is required within 6 feet of each appliance
Gas Piping Specification and complete Schematic PAGE 3 ï² Not Applicable
ï² CSST ï²Brass ï²Other
Proposed Piping Material:
ï²Black Steel ï²Galvanized Steel
Proposed Piping Size: ï²Â½â€ ï² â…â€ ï² Â¾â€ ï² 1â€ ï² 1Â½â€ ï² 2â€
Inlet Pressure: Pressure Drop: Specific Gravity:
I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of
the above described property will be in accordance with the laws, rules and regulation of the State of Washington.
Signature Print Name Date
REV03.2022 Page 1 of 3
MECHANICAL PERMIT FEES (per unit)
Type of Fixture No. of Units Cost per Unit Subtotal
Additional Plan Review fees x $ 75.00 = $
Air Conditioning Unit ≤ 100 Btu/h x $ 15.00 = $
Air Conditioning Unit > 100 Btu/h x $ 25.00 = $
Air Conditioning Unit > 500 Btu/hp x $ 50.00 = $
Air Handling Units x $ 15.00 = $
Base Mechanical Fee $ 25.00 $ 25.00
Boiler <100Btu/h >3hp x $ 15.00 = $
Boiler >1 million Btu/h<50hp x $ 25.00 = $
Boiler >1.5 million Btu/h<50hp x $ 50.00 = $
Boiler >100Btu/h 3-15hp x $ 15.00 = $
Boiler >500Btu/h 15-30hp x $ 25.00 = $
Commercial Hoods -Type I x $ 25.00 = $
Commercial Hoods -Type II x $ 50.00 = $
Diffusers x $ 15.00 = $
Dryer Ducting x $ 15.00 = $
Ductwork (drawings required) x $ 25.00 = $
Evaporative Coolers x $ 15.00 = $
Exhaust/Ventilation Fans x $ 15.00 = $
Fireplace/Insert/Stove x $ 15.00 = $
Forced Air Heat ≤100 Btu/h x $ 15.00 = $
Forced Air Heat >100 Btu/h x $ 25.00 = $
Gas Clothes Dryer x $ 15.00 = $
Gas Fired Air Conditioning Unit ≤ 100 Btu/h x $ 15.00 = $
Gas Fired Air Conditioning Unit > 100 Btu/h x $ 25.00 = $
Gas Fired Air Conditioning Unit > 500 Btu/hp x $ 50.00 = $
Gas Piping ≤ 5 units x $ 15.00 = $
Gas Piping for each additional unit > 5 x $ 2.00 = $
Heat Exchangers x $ 15.00 = $
Heat Pump-Condensing Unit x $ 25.00 = $
Hot Water Heat Coils x $ 15.00 = $
Miscellaneous Appliance - regulated by $ 15.00 $
x =
mechanical code, not otherwise specified
Package Units ≤ 100 Btu / > 100 Btu x $ 25.00/$50.00 = $
Range/Cook top-Gas Fired x $ 15.00 = $
Refrigeration Unit ≤100Btu/h x $ 15.00 = $
Refrigeration Unit >100Btu/h x $ 25.00 = $
Refrigeration Unit >500Btu/h x $ 50.00 = $
Re-inspection fee (all) x $ 75.00 = $
Unit Heaters ≤ 100 Btu/h x $ 15.00 = $
Unit Heaters >100 Btu/h x $ 25.00 = $
Variable Air Volume Boxes (part of Air $ 10.00 $
x =
Conditioning System)
Wall Heaters - Gas Fired x $ 25.00 = $
Water Heater - Gas Fired x $ 25.00 = $
Permit Fee $
Table 4-8; Plan Review Fee $
Processing/Technology Fee $25.00
Total $
REV2.2024 Page 2 of 3
PRESSURE PIPING SCHEMATIC
COMPLETE FOR GAS PIPING ONLY
ï² SCHEMATIC IS TO SCALE ï² SCHEMATIC NOT TO SCALE
Show Pipe Size(s) and Length(s) from meter to all appliances
NOTE: Any interior pressure regulators must be indicated
REV2.2024 Page 3 of 3
WEATHER CAP
3
44'-8
4
5
42'-8
PETTICOAT & SCREEN BY OTHERS
8
3
8'-2
4
5
6'-4
8
ROOF CURB BY OTHERS
8
5
37'-8
8
3
THIMBLE BY OTHERS
3016 BOTTOM OF
OD ROOF DECK
5
32'-8
8
7
22'-1
8
UNINSULATED STACK
NOTE:
THE ENTIRE UNLINED STACK
3
34 MAX OD IS PAINTED TEMPERKOTE 850
16
HIGH TEMP SILVER
5
27'-8
8
AIR BREAK
5
22'-8
8
3
20'-8
4
35'-10
3
15'-8
4
AFTERBURNER
CONTROL/EXCESS
TEMP
THERMOCOUPLE
3
3
20'-8
10'-84
4
INSULATED AFTERBURNER
DRAWING SUBMITTED FOR APPROVAL
3
APPROVED AS SUBMITTED
5'-8
4
APPROVED WITH CHANGES
RE-SUBMIT
FOR REFERENCE ONLY
SIGNATURE
DATE
0
3
3
62
62
16
16
A0 06/10/25 KJS FOR APPROVAL
No. DATE BY DESCRIPTION
REVISION
UNINSULATED STACK G.A. TITLE
NOTICE: THIS PRINT IS OUR SC
UNISULATED STACK GENERAL ARRANGEMENT PROPERTY AND SUBJECT TO 3/8" = 1' - 0"
APPROX. 7,500 LBS.
RETURN UPON DEMAND. ALL
DRN
RIGHTS OF DESIGN AND
(1 REQ'D.)
. INVENTION ARE RESERVED. KJS 06/10/25
SHEET DWG No REV
TRU-HEAT BURNOUT FURNACE - 7 X 8 X 4
1
15660 LASALLE ST SOUTH HOLLAND IL 60473 CUST
1 17968GA2 A0
(708) 339-6810 www.armilcfs.com
BLUE CASTINGS (ARLINGTON, WA)
SHEET 1 OF 1 , 17968GA2 - Uninsulated Stack General Arrangement, 6/10/2025 4:08:33 PM
WEATHER CAP
3
44'-8
4
5
42'-8
PETTICOAT & SCREEN BY OTHERS
8
3
8'-2
4
5
6'-4
8
ROOF CURB BY OTHERS
8
5
37'-8
8
3
THIMBLE BY OTHERS
3016 BOTTOM OF
OD ROOF DECK
5
32'-8
8
7
22'-1
8
UNINSULATED STACK
NOTE:
THE ENTIRE UNLINED STACK
3
34 MAX OD IS PAINTED TEMPERKOTE 850
16
HIGH TEMP SILVER
5
27'-8
8
AIR BREAK
5
22'-8
8
3
20'-8
4
35'-10
3
15'-8
4
AFTERBURNER
CONTROL/EXCESS
TEMP
THERMOCOUPLE
3
3
20'-8
10'-84
4
INSULATED AFTERBURNER
DRAWING SUBMITTED FOR APPROVAL
3
APPROVED AS SUBMITTED
5'-8
4
APPROVED WITH CHANGES
RE-SUBMIT
FOR REFERENCE ONLY
SIGNATURE
DATE
0
3
3
62
62
16
16
A0 06/10/25 KJS FOR APPROVAL
No. DATE BY DESCRIPTION
REVISION
UNINSULATED STACK G.A. TITLE
NOTICE: THIS PRINT IS OUR SC
UNISULATED STACK GENERAL ARRANGEMENT PROPERTY AND SUBJECT TO 3/8" = 1' - 0"
APPROX. 7,500 LBS.
RETURN UPON DEMAND. ALL
DRN
RIGHTS OF DESIGN AND
(1 REQ'D.)
. INVENTION ARE RESERVED. KJS 06/10/25
SHEET DWG No REV
TRU-HEAT BURNOUT FURNACE - 7 X 8 X 4
1
15660 LASALLE ST SOUTH HOLLAND IL 60473 CUST
1 17968GA2 A0
(708) 339-6810 www.armilcfs.com
BLUE CASTINGS (ARLINGTON, WA)
SHEET 1 OF 1 , 17968GA2 - Uninsulated Stack General Arrangement, 6/10/2025 4:08:33 PM
INSTALLATION REQUIREMENTS:
Arlington, WA
LOCATION:
OXYGEN PROBE
(130 FT. ABOVE SEA LEVEL)
(SSI GOLD PROBE)
NATURAL GAS
FUEL: (1,000 BTU/CUBIC FOOT)
4,490 SCFH @ 2 PSIG
AFTERBURNER BURNER
1,551 SCFM DILUTION AIR,
MAKE-UP AIR:
BURNERS IN REAR 1,034 SCFM COMBUSTION AIR
6.5 FLA @ 460 VAC, 3 PH, 60 HZ
ELECTRICITY:
2" NPT GAS CONNECTION
65 kA SCCR
PNEUMATIC AIR: 15 SCFM @ 80 PSI MIN.
ELECTRICAL PANEL
FURNACE = 23,000 LBS.
3
EST. SHIPPING WEIGHTS: AFTERBURNER = 7,000 LBS.
1 178
TOTAL = 29,100 LBS.
36
2
PAINT COLOR: PROCESS BLUE
FURNACE SPECIFICATIONS:
OPERATING
CONTROL / EXCESS 450F - 2,200F
11
TEMPERATURE:
TEMP. THERMOCOUPLE DOOR LIFTING /
APPROX. 1 FT/SEC
LOWERING SPEEDS
12
1 1 APPROX.
1842 15'-42 13
DRAWING SUBMITTED FOR APPROVAL
1
APPROVED AS SUBMITTED
1 107
84 60 4
APPROVED WITH CHANGES
16
RE-SUBMIT
FOR REFERENCE ONLY
DOOR OPEN SIGNATURE
ROOF PENETRATION 9
& CLOSE BUTTONS DATE
T.B.D.
DOOR SWING
ROOF PENETRATION 12
3/4 NPT PNUEMATIC
TO BE DETERMINED
CONNECTION
17 17
13 9
13
12 72 12 10" COMBUSTION
AIR INLET STACK LIGHT
AFTERBURNER 96 1
12'-9 SHIPPING LENGTH
(OPENING WIDTH) COMBUSTION 4
SECTION A-A AIR BLOWER
49 SCALE 1 : 24
THERMOCOUPLE CONTROL/EXCESS TEMP
THERMOCOUPLE
(OPPOSITE SIDE)
1 1
APPROX. 618 *APPROX. 1.5 SEC 21 618
COMBUSTION PIPING RESIDENCE TIME *APPROX. 1.5 SECRESIDENCE TIME
FURNACE DOOR
AIR BLOWER ALLOWANCE PIPING
IN "UP" POSITION
ALLOWANCE
SPLIT
3 4 LINE
1
60 X 72 X 38
SPLIT LINE 20'-82
WORK ZONE
20'-8
12 193 ROOF HT. T.B.D. 12
8
1 1
PNEUMATIC DOOR
114 9'-6
4 4
CYLINDER
(SHIPPING 181.88
HEIGHT)
DOOR ROOF HT. T.B.D. 15'-2
APPROX. OPEN/CLOSE
5 5 BUTTON
128 10'-8
8 8
1 1
38
102 8'-6 60**
4 4
SHIPPING HEIGHT OPENING)
(FULL DOORA
A
1 2
5'-9
9'-6
49
1
30
4
(PASS HT.)
6 PNEUMATIC DOOR 12 72 REF.
12
SAFETY LOCKS 6
4 TRAY HT. A0 05/21/25 KJS APPROVAL REQUEST
1387 11'-67 11'-8 SHIPPING WIDTH 96 OPENING WIDTH
No. DATE BY DESCRIPTION
8 8
*RESIDENCE TIME SUGGESTED ELECTRONIC 3
6 PIER HT. REVISION
** NOTE: DOOR MAY ALSO 124
TITLE NOTICE: THIS PRINT IS OUR SC
*RESIDENCE TIME SUGGESTED FOR PMMA BURNOUT. CHART BE OPENED TO ONLY 48" 8
FURNACE GENERAL ARRANGEMENT PROPERTY AND SUBJECT TO 3/4" = 1' - 0"
RETURN UPON DEMAND. ALL
FOR PMMA BURNOUT. RECORDER
RIGHTS OF DESIGN AND DRNKJS 05/21/25
INVENTION ARE RESERVED.
FURNACE GENERAL ARRANGEMENT
SHEET DWG No REV
TRU-HEAT BURNOUT FURNACE - 7 X 8 X 4
1
(1 REQ'D.)
15660 LASALLE ST SOUTH HOLLAND IL 60473 CUST 17968GA1 A0
(708) 339-6810 www.armilcfs.com BLUE CASTINGS (ARLINGTON, WA) 1
SHEET 1 OF 1 , 17968AGA1 - Furnace General Arrangement, 5/21/2025
2:02:48 PM
NOTE STARTED WITH 16138 SEACAST
STRETCHED WIDTH OF FCE BY 12"
INCREASED iD OF AFTER BURNER FROM
32" TO 35"
5300 DENVER AVENUE SOUTH
SEATTLE, WASHINGTON 98108
(206) 787-8500
6 5 4.7
4.5 4 3.8 3.5
3.2 3 2.3 2
1 THE PLANS AND SPECIFICATIONS HEREIN
ARE OWNED BY AND FOR THE SOLE USE OF
ACCO ENGINEERED SYSTEMS, INC.
(“ACCOâ€), AND MAY NOT BE REPRODUCED OR
USED
BY OTHERS FOR ANY PURPOSE UNLESS
AUTHORIZED BY ACCO IN WRITING. ACCO
CANNOT ACCEPT ANY LIABILITY, WARRANTY,
OR
340'-0" OVERALL
OBLIGATION IN THE EVENT OF UNAUTHORIZED
USE.
340'-0" OVERALL
40'-0" 14'-0"
22'-0" 25'-0" 7'-0" 30'-0"
18'-0" 6'-0" 40'-0" 12'-0"
36'-0"
7'-0"
COTROL PANEL COTROL PANEL
5 PSI GAS METER
26,685 CFH
2" NG UP 4,560 CFH
2 1/2" NG 14" WC 22,125 CFH
POWER TRANS EMERGENCY GENERATOR
1" CDA
GR
GAS 4 1
WATER CONNECTIONS WATER CONNECTIONS CDA BLOW DOWN
A
CDA CDA CDA
1 1 ET 1" ICW DN FOR 1
4" SW DN TO FLOOR
WH-3
2" SW UP TO LV
4" LW
DN TO
3" LW DN 3
HUB DRAIN FOR
(1 FU)
FLOOR
HUB
FLOOR HUB WH 1 1/4" ICW DN
FIRE SPRINKLER DRAIN
(8 FU)
DRAIN (6 FU) SMOKE HOG
3 FOR HVAC
BLOWDOWN (MAX:
CDA DROP TO 16 FT AFF.
MAKE UP EYEWASH
100 GPM) 2" LVTR
LOCATE 9 FT FROM COLUMN A-4
3" LW CO TABLE TABLE 3/4" INDUSTRIAL WATERTABLE
4" SW CO
2" SV
WATER
DUST COLLECTOR DROP TO 10' AFF, VALVE
2" LVTR
4" LW
CO
(BY VATECH) AND CAP
3" DCW UP
3/4" INDUSTRIAL WATER
LAV-1
2" LVTR
BFP BFP
TP-1 3/4" ICW DROP VALVE AND CAP TO
CDA 3" LW CO
FEED WATER SOFTENER
1" ICW
3/4" INDUSTRIAL
1 2
WATER DROP TO 10'
FD-1
(2)2" SV UP
CDA
AFF, VALVE AND CAP PATTERN ASSEMBLY
4" SW UP TO WC
ICW ICW ICW
ICW ICW ICW ICW
ICW ICW ICW ICW
ICW WC-2 (4 FU)
3" LW DN TO
TP-1
1
1/2" ICW 4" SW UP TO WCO
3" LW DN TO
FLOOR HUB
FLOOR HUB
1/2"
DCW 1/2" TP UP
3/4" INDUSTRIAL
1 1/2" ICW 1 1/2" ICW
CDA BLOW DOWN 1 1/2" ICW DRAIN (6 FU)
DRAIN (6 FU) WATER DROP
FOR TP WH CP ET 2
1
WH
3" LW CO TO 10' AFF
2" LVTR
1 1 1 P3.02
1 1/2" INDUSTRIAL
A
3/4" ICW
MS-1 3/4" COND TO MS
WATER TO BFP-2
143863
2
SHEET NOTES:
2 1/2" NG 5 PSI
2" SVTR WC-2 WC-2 (2)2" SW UP
22,000 CFH 2 CDA BLOW DOWN
(2)1/2"
TP UP TO FD (4 FU) 1 CA DROP DOWN TO 10' AFF.
NG
TP-1
VALVE AND CAP
FD-1 WC-1 FD-1
4" SW UP B
ICW
CART
UR-1 2" SV UP 2 CA DROP FOR FUTURE. TEE
ICW
SHELL
1" ICW
BOILERCLAVE
CDA 1" CDA VALVE AND CAP LOCATED
ICW
VALVE AND CAP AT MAIN
2" SW
UP TO
1 FT NORTH OF GRID B
CDA INPUT
LV (2 FU) LAV-1
1" DHW CDA
LAV-1
DROP TO 10' AFF 1" CDA
AREA OF WORK
1 1/4"
DHW ICW
VALVE AND CAP
2 1/2" 5 PSI NG 1" CDA
KEYPLAN
1750 CFH
3" LW UP TO 1" CDA
FLOOR HUB
4" SW CO
DRAIN (6 FU)
PATTERN SETTER
2" DCW 3/4" HWR
3" LW CO 2
B
2
NG
TABLE
2" LVTR
3" CDA
3/4" INDUSTRIAL 1 1/2" CDA 3/4"
HWR
ICW 1" CDA
WATER DROP TO 10' CDA BLOW DOWN
ICW DEWAX FURNACE
AFF, VALVE AND CAP
1" 5 PSI NG
1" 5 PSI NG CDA CDA CDA
CDA CDA CDA CDA
2000 CFH
VALVE AND CAP DROP
1" 5 PSI NG CDA
FOR FUTURE USE
VALVE AND CAP DROP
1000 CFH 1" 5 PSI NG
FOR FUTURE USE 1" CDA 1" CDA
ICW
CDA
3" LW CO
1000 CFH
2 1/2" 5 PSI NG
CDA
20,000 CFH NG NG NG
NG NG NG NG
LOAD &NG
3/4" INDUSTRIAL
UNLOAD
1" INDUSTRIAL
SLURRY PREPARATION
2
WATER DROP WH 1
WATER DROP TO 10'
NG
AFF, VALVE AND CAP 4" LW CO
TO 10' AFF 5 P3.02
WH-5 FOR
4" LW CO CDA
ICW
UTILITY SINK
1
1
1 RINSE
CDA BLOW DOWN
3" LW UP TO
1
FLOOR HUB 2" LVTR
2" LW UP
SK (2 FU)
DRAIN (6 FU)
ICW
2" LVTR 3" LW UP TO ETCH
FLOOR HUB
1 1/2" ICW CDA 1" CDA
DRAIN (6 FU)
3/4" COND TO
CDA
HUB DRAIN
TYP 2
1
1" CDA
NG
2 1/2" 5 PSI NG
KIT AREA
VALVE AND CAP DROP
TABLE CDA
FOR FUTURE USE
ICW
1 1/2" CDA
1
20,000 CFH
2" CDA
CDA BLOW DOWN
NG 1
C
CDA CDA
2" LVTR
1" NG 14" WC 1
ICW
DROP FOR UH-4
AT GRID 7 C
125 CFH PRE PRE
CDA
APPROX 8' 5" STAIRS MOVED
2 1/2" 5 PSI NG HEAT 2 HEAT 1
VALVE AND CAP FOR
FUTURE USE
3" CDA
2"LV
CDA
F 4/7/2021 RECORD DRAWINGS
AS
ICW
E 11/18/2020 100%
CD AS
D 11/13/2020 50%
CD AS
CDA BLOW DOWN
x x x
C 10/20/2020 100%
DD AS
x
x
LV ICW B 09/30/2020 PERMIT
SET AS
BACKTILTFURNACE
REMOTE BOX
200D
201POT
FURNACE
TILT
FPI REST FPI DEVELOPER
MOLD LIFT
LAV-1
TC LANCE
3/4" ICW
(3)2"
SW UP A 08/31/2020 50% DD
AS
HOIST
x CDA
FPI INSPECTION
FD-1
BACKTILTFURNACE
REMOTE BOX
200D
201POT
LAV-1
FURNACE
TO (6)LV
TILT x
VALVE AND
FURNACE PROFILE
FURNACE DRIVE CHARGER RAM
RETRACTED
DISABLETEACH
2
FURNACE PROFILE
FURNACE DRIVE
ENABLEEXECUTETC LANCE
UP
No. Date Description
By
CHARGER HOIST
UP
REMOTE BOX
200A
CAP ABOVE
(6 FU) LAV-1
x x x
UR-1 UR-1 WC-1 WC-1 WC-2 Revisions
OXYGEN PROBE
DRAIN
2" SW UP LV
(SSI GOLD PROBE)
AFTERBURNER BURNER
4" LW UP TO
FPI REST
TO DF
BURNERS IN REAR
FLOOR HUB
WALK IN BLAST
2" NPT GAS CONNECTION
DRAIN (6 FU)
DF-1 Project
ELECTRICAL PANEL
CDA
3
17
3612 8 CL
2" VTR LAV-1 LAV-1 WC-1 WC-1 WC-1 WC-2 232'-0" OVERALL
ICW 4" LW CO
2
LAV-1
LV CASTING OPERATIONS
CONTROL / EXCESS
LAV-1
TEMP. THERMOCOUPLE
FPI DRIER
TP-1 FD-1
1 1 APPROX.
2 15'-42 13
ICW
1
2
LV
107
CDA
4
FPI EMULSIFIER
2" SW UP TO
1 1/2" CDA
6108 188TH STREET NE
SK (2 FU)
CDA
SK-1
DOOR OPEN
& CLOSE BUTTONS
2
ARLINGTON, WA 98223
DOOR SWING
4" SW DN
3/4 NPT PNUEMATIC 1"
ICW VALVE
CONNECTION AND
CAP 1" ICW VALVE
CDA CDA
LV TO CO
FPI
AND CAP FOR
1" CDA
10" COMBUSTION 1" ICW
FUTURE
AIR INLET LC
STACK LIGHT
1
12'-9 SHIPPING LENGTH
COMBUSTION 4
Title
AIR BLOWER
ICW
LV
CDA
3/4" INDUSTRIAL
4" LW CO
FPI RINSE
WATER DROP 1 1/2" ICW VALVE
4" LW UP TO
2
FIRST FLOOR
FOR PROCESS
2
TO 10' AFF
FLOOR HUB
PLUMBING PLAN
WATER SYSTEMS
DRAIN (8 FU)
ICW
LV
SEE P2.01A FOR CONTINUATION
FPI REST
SEE P2.01A FOR CONTINUATION D NORTH
SEE P2.01B FOR CONTINUATION
CDA
SEE P2.01B FOR CONTINUATION
2" LV
X:\942190_CASTING OPERATIONS\004-E-PL\DWG\Presentation\942190_P2_01A 1" ICW CDA CDA
3" LW CO
A.STIENS D.SHEARER
Designed By Checked
By
A.STIENS R.FENTON
Drawn By Project
Manager
FIRST FLOOR PLUMBING PLAN - NORTH
942190
Andrew Stiens
1
N
SCALE: 1/8" = 1'-0"
Job Number
AS SHOWN P2.01A
Scale
2021-04-07 03:59 PM
PRE-ENGR JOIST MFR SHALL
DESIGN TOP CHORD OF PRE-ENGR
OMIT L 3 x 3 IF EDGE DIST
JOIST FOR AXIAL SEISMIC FORCE
LESS THAN 1'-0"
SHOWN ON THE ROOF FRAMING
DECK PENETRATION
PLAN TO BE TRANSFERRED THRU
16" DIA (OR 16"x16")
THE BEARING SEAT AND ACROSS
OR LESS
STEEL JOIST ATTACH METAL DECK TO STEEL JOIST
THE JOIST GIRDER
ALL EDGES OF FRAME
PER SCHEDULE L 5 x 5 x 5
16
L 5 x 5 x 5
16
JOIST
PRE-ENGR JOIST PER PLAN TO GIRDER
1/4 4
TYPICAL
L 3 x 3 x 1
4 EA SIDE
OF PENETRATION
TACOMA
SEATTLE SPOKANE TRI-CITIES
2215
North 30th Street, Suite 300, Tacoma, WA 98403
L 2 x 2 x 14 x 0'-4" 253.383.2422TEL
253.383.2572 FAX www.ahbl.comWEB
AT CORNER
EXTEND 2'-0" BEYOND
PENE EA SIDE
CASTING
OPERATIONS
8'-0" MAX
188th St.
Business Park
ATTACH USING TYP DECK
ATTACHMENT METHOD AT EA
MECH UNIT -
DECK VALLEY - TYP
BEAR ONE SIDE
ON JOIST
CL DECK SUPPORTS
PRE-ENGR JOIST
FOR OPENINGS 16" DIA (OR 16"x16")
GIRDER PER PLAN
L 5 x 5 x 5
16
OR LESS IN METAL ROOF DECK
CUT DUCT PENETRATIONS THROUGH
BRACE WHERE REQ'D BY
DECK. NO ADDITIONAL SUPPORTS TYP
14800 NE NORTH WOODINVILLE WAY
PRE-ENGR JOIST MFR, TYP
REQUIRED 3/16
WOODINVILLE, WA
AT CONTRACTOR'S OPTION: COPE ONE LEG AND BEND AS
JST CONNECTION TO GIRDER
STEEL JOIST OMIT COPED LEG AND BUTT SHOWN - TYP STEEL JOIST
IS PART OF SFRS
WELD L 4 x 4 TO L 5 x 5
2" 3/16
L 4 x 4 x 1
4
L 5 x 5 x 5
SECTION
16
2200333.20
1
MECHANICAL UNIT TYPICAL FRAMING SUPPORT
1" = 1'-0"
1 MEMBER
4"
COPE
DECK ATTACHMENT IS PART OF SFRS BOTTOM
PERMIT SUBMITTAL
LEG
TYP MECH UNIT SUPPORT
TOP OF PARAPET PER
JUNE 24, 2020
ARCH
4
1" = 1'-0"
ATTACH AND SPLICE
LEDGER PER
3
S4.1
4'-0" MAX
ROOF JST PER PLAN
HSS 5x5x3/8"
1'-4"
1'-0" 1'-0"
DECK
PENETRATION
ELEV PER
ARCH 2"
10"
3/16
2"
NOTICE:
L 4 x 4 x 14
ALTERATION OF THIS DOCUMENT SHALL INVALIDATE THE
PROFESSIONAL SEAL AND SIGNATURE. PUBLICATION OF THIS
5
C15 x 33.90, SPLICE
DOCUMENT DOES NOT DEROGATE FROM RESERVED OWNERSHIP
L 5 x 5 x 16 TYP
RIGHTS IN IT. THIS DOCUMENT IS FOR USE ONLY FOR THE PROJECT
PER 3
IDENTIFIED IN THE TITLE BLOCK AND IS NOT TO BE USED FOR
EMB PL 3/4" x 12"x 12"
3/16 1
REPAIR, REMODEL OR ADDITION TO THAT PROJECT OR FOR ANY
ATTACH METAL DECK TO 22" 3/16
S4.3
OTHER PROJECT.
W/ (4) 5/8"DIA x 5"
HSS
ALL EDGES OF FRAME
WHS AT 8" GA TO
ADD C15 EQ SPACE AT
PER SCHEDULE
5/16 9 EMBED
8'-0"OC MAX
FOR OPENINGS GREATER THAN 16" DIA SUPPORT
END PL 3/8"x4"x1'-3" W/ (2)
1 MEMBER
5/8" DIA EXP ANCHORS
4"
(OR 16"x16") IN METAL ROOF DECK
EMBED 5"
KNIFE PL CONNECTION IS TYPICAL ROOF JOIST BEARING
COPE
PART OF SFRS WITHIN 18" OF PANEL EDGE
DECK ATTACHMENT IS PART OF SFRS
BOTTOM
LEG
SECTION
TYP OPENING IN METAL ROOF DECK
SECTION
2
3 5
1" = 1'-0"
1" = 1'-0"
1" = 1'-0"
PANEL JOINT LOC VARIES
5 3/16 3
1/4 4
LEDGER PER
S4.1
1
5/16
GIRDER BLKG PERS4.1
TOP OF PARAPET PER 3/16 5/16 12
ADD PL 3/8"x2"x1'-0" FOR DECK
ARCH
1 1 1
SUPPORT
2"12"12"
3 1
1/4 3 TYP END WALL EMBED
ROOF JST PER PLAN SPLICE PL 4 x 2 2 x 1'-8" 50KSI
LOCATE AT TOP OF 4
W27 PER PLAN
AT SIM BEVEL BACK EDGE TO FIT SNUG
GIRDER (LOWER THANS4.1
5/16 6 TO ANGLE FACE
REST)
PRE-ENG JOIST
SPLICE PL 3/8"x6"x0'-6"
GIRDER PLAN
3"
1'-0" 1'-0" 1/4
3"
L3x3x1/4"x0'3" W/
3" PL 1/2"x6x0'-11" W/
ROOF FRAMING
1/2" DIA EXP
END PL 3/8"x5"x0'-7"
3" ANCHOR, EMBED 4" HSS5x5x1/4"x0'-11 1/2"
MIN. SPACE AT AT CENTER AND (2) 5/8"
DETAILS
3"" 24"OC ALONG W27 DIA EXP ANCHORS
1'-01" 1"
112 EMBED 5" AT 8" GAGE
4 4"
(2) PL 3/8"x4"x0-'6"
3
(6) 4" DIA A325-N BOLTS
JST BEARING AT SIM, ONE TOP AND BTM
6"
HSS
ADD EMBEDS AND
PL'S TO
HSS PER 2 EMBED
KNIFE PL 1/2"
LAH CLR DLB
- 5/16 TYP
DO NOT WELD JOIST BOTTOM CHORD
ALL PL'S AND WELDS ARE
HSS COL PER FDN STRAP CONNECTION TO
TO STABILIZER PL
PART OF SFRS
PLAN WALL IS PART OF SFRS
STABILIZER PL 3/4"x6x0'-7" NOTCH
HSS AT CL
SECTION
SECTION SECTION
1/4
6 7
8
S4.2
1" = 1'-0"
1" = 1'-0" 1" = 1'-0"
13 18
DATE: June 22, 2020 FILENAME: Q:\2020\2200333\20_STR\CAD\2200333S-40.dwg
Q:\2020\2200333\20_STR\CAD\2200333S-40.dwg, 6/22/2020 9:30:14 AM, LHIGGINS,
DWG To PDF.pc3
Permit #: 6717
Permit Date: 09/17/25
Permit Type: COMMERCIAL MECHANICAL
Project Name: Arlington Amril Furnace venting install
Applicant Name: Five Star Mechanical
Applicant Address: 7509 Grange ST West
Applicant, City, State, Zip: Lakewood, WA 98499
Contact: John Ware
Phone: 206-786-8278
Email: johnw@fivestarmech.com
Scope of Work: Install factory made venting on a furnace
Valuation: 104000.00
Square Feet: 79000
Number of Stories: 1
Construction Type: llA
Occupancy Group: B; Business
ID Code:
Permit Issued: 10/24/2025
Permit Expires: 04/29/2026
Form Permit Type: COMMERCIAL MECHANICAL
Status: COMPLETE
Assigned To: Hannah Hardwick
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
Section 22 Township 31
Range 05 Quarter NE PAR
C CITY ARL BLA FILE NO CASTING 250 BUSINESS /
31052200101000 18410 63RD AVE NE
PLN-587 REC AFN OPERATIONS LLC PROFESSIONAL
201909245004 BEING PTN
NW1/4 NE1/4 SD SEC
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
7509 Grange St. CONSTRUCTION
Five Star Mechanical John Ware 206-786-8278 UBI 601 937 083
West CONTRACTOR
7509 Grange St. CONSTRUCTION Labor and
Five Star Mechanical John Ware 206-786-8278 FIVESM*010JT
West CONTRACTOR Industries
Inspections
Date Inspection Type Description Scheduled Date Completed Date Inspector Status
C08. GAS PIPING
10/28/2025 AM requested 10/29/2025 10/29/2025 BUILDING Approved
ROUGH-IN
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
09/17/2025 BUILDING Approved
MECHANICAL
Fees
Fee Description Notes Amount
Enter 1 if permit is for commercial
Web Only - Mechanical Commercial Plan mechanical
$995.40
Review
(Table 4-1)
Credit Card Service $29.86
Processing/Technology $25.00
Ductwork/Dryer Duct $25.00
Gas Piping/Units Enter # of units $15.00
Credit Card Service $1.95
Total $1,092.21
Attached Letters
Date Letter Description
10/23/2025 Building Permit
10/10/2025 Building Permit
09/17/2025 Web Form - Building Application
Payments
Date Paid By Description Payment Type Accepted By Amount
09/17/2025 John Ware 24259176 $29.86
XBP Conf:
09/17/2025 $995.40
243259176
10/10/2025 J Ware cc LaNay Hendrick $1.95
XBP Conf:
10/10/2025 $65.00
245512452
Outstanding Balance $0.00
Notes
Date Note Created By:
03/02/2026 sent expiration notice Hannah Hardwick
Uploaded Files
Date File Name
10/24/2025 29033839-20250917_BLD6717_Approved Venting Drawing2.pdf
10/24/2025 29033840-20250917_BLD6717_ApprovedStructural Drawing.pdf
10/24/2025 29033841-20250917_BLD6717_ApprovedGas Piping.pdf
10/24/2025 29033842-20250917_BLD6717_Approved Venting Drawing.pdf
10/24/2025 29033843-20250917_BLD6717_Approved Vent.pdf
10/24/2025 29033784-2025_BLD6717_Issued Permit.pdf
09/17/2025 6e1d6c4d08d7ffc10a2b6e02707cfc78_gas_pipe_drawing.pdf
09/17/2025 1f14cb0b5d61ea86cde109908327ab9a_s4.2_-_structural_openings_details.pdf
09/17/2025 4fbef211b12c48f05129b61b2f9d508b_stack_venting_drawing.pdf
09/17/2025 d3708cf2b795de2d46cc84aa41bb37bb_20814771-commercial_mechanical_-_permit_application.pdf
09/17/2025 d5361d74163589bee7c2e5e7d54789a1_furnace_drawing.pdf
09/17/2025 4fbef211b12c48f05129b61b2f9d508b_stack_venting_drawing.pdf