HomeMy WebLinkAbout21125 SMOKEY POINT BLVD_BLD927_2026 18204 59th Ave.
Arlington, WA 98223 REVIEW COMMENT FORM
(360) 403-3500
Project Name: Stillaguamish Tribes Permit No.: 927 Review Date: 3/16
Contact: Josh Wells Phone No.: 360-722-4350 Review Phase: 1st Round Report Date: 3/9/16
Reviewing Dept.: CED Applicant: Emerald Fire DWG Issue Date: 3/7/16
# Rev. Dwg. or Add’l Ref.
City
Comment Response/Resolution
Spec. Ref. Check
off
1. CJY 1 of 1 Head Quantity inconsistent with plan As-builts (shop drawings) will be required √
2. CJY 1 of 1 TJI flange supports for bracing – structural load Verify through structural drawings √
calculation conducted?
3. CJY 1 of 1 Sammy Screw depth at 2 ½ inches or bracing at 10’ Field verify √
4. CJY 1 of 1 Sidewinder screws in TJI’s – engineering call out Confirmation required √
5. CJY FP1.01 Bracing of riser required Field verify √
6. CJY FP1.01 Draft stops required in soffits, eaves, etc. with dry pipe Field verify √
sprinklers not exceeding 160 cubic feet
7. CJY U1.0 8†DCVA requires testing Field verify √
8. CJY U1.2 Thrust blocking and or restraint system required Field verify √
9. CJY U1.2 Hydro-static, flow, flush, and purity tests required Field verify √
10. CJY FA1.01 Pull Station and Smoke required in Sprinkler Room Field verify √
11. CJY FA1.01 Provide Battery Backup calculations Upon system certification √
12. CJY Specs Specs call out 18 smokes, 5 horn strobes, 12 strobes, 3 As-builts (shop drawings) required upon √
pull stations and the plans do not show locations of all the completion.
appliances. Also, no wiring diagram (Class A or B)?
13. CJY Misc. Acceptance tests required on all life safety systems prior
to occupancy.
14.
15.
16.
17.
18.
19.
20.
21.
Page 1 of 2
18204 59th Ave.
Arlington, WA 98223 REVIEW COMMENT FORM
(360) 403-3500
Project Name: Stillaguamish Tribes Permit No.: 927 Review Date: 3/16
Contact: Josh Wells Phone No.: 360-722-4350 Review Phase: 1st Round Report Date: 3/9/16
Reviewing Dept.: CED Applicant: Emerald Fire DWG Issue Date: 3/7/16
# Rev. Dwg. or Add’l Ref.
City
Comment Response/Resolution
Spec. Ref. Check
off
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
Page 2 of 2
✔
21125 Smokey Pt. Blvd., Arlington WA 98223 N/A
$42,000.00 98 4590
Stillaguamish Tribe of Indians (360) 652-7362
3310 Smokey Point Dr. Arlington WA 98223
Josh Wells (360) 403-9123
(360) 722-4350 jwells@stillaguamish.com
P.O. Box 277 Arlington WA 98223
Emerald Fire (253) 857-2056
11020 SR 302 Gig Harbor WA 98329
EMERAFL980MR July 19, 2016
03/08/2016
Josh Wells
Permit #: 927
Permit Date: 03/08/16
Permit Type: FIRE SPRINKLER
Project Name: River Rock Convenience Store
Applicant Name: Stillaquamish Tribe of Indians
Applicant Address: P.O. Box 277
Applicant, City, State, Zip: Arlington, WA 98223
Contact: Josh Wells
Phone: 360-406-9123
Email: jwells@stillaquamish.com
Scope of Work:
Valuation: 42000.00
Square Feet: 4590
Number of Stories: 2
Construction Type:
Occupancy Group:
ID Code:
Permit Issued:
Permit Expires:
Form Permit Type:
Status: EXPIRED
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
STILLAGUAMISH 699 Other
21125 SMOKEY POINT
31050800300100 TRIBE OF Miscellaneous
BLVD
INDIANS Services NEC
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
Michelle 11505 Burnham CONSTRUCTION
Emerald Fire 253-857-2056 COA 602211955
Hillstrom Dr, Ste 201 CONTRACTOR
Michelle 11505 Burnham CONSTRUCTION Labor and
Emerald Fire 253-857-2056 EMERAFL980MR
Hillstrom Dr, Ste 201 CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
Ok to issue with redlined drawing as conditions outlined
03/08/2016 FIRE SPRINKLER z.Christopher Young
in the Plan Review Comment Letter
03/08/2016 FIRE SPRINKLER BUILDING
Fees
Fee Description Notes Amount
Photocopies 2 sets of Fire Sprinkler Plans $12.00
Fire System Plan Review Table 4-1 $100.00
Fire Sprinkler System Commercial NFPA 13/13R Valuation: 42K $781.55
Total $893.55
Attached Letters
Date Letter Description
03/09/2016 Building Permit
Notes
Date Note Created By:
The building and systems have been under construction for several months without any
involvement with the Building or Fire Depts. The Tribe opted not to submit for plan review or
03/09/2016 Chris Young
inspection services and have appeared to change their mind regarding the life safety systems so
we are issuing life safety systems only. This does not constitute compliance for a C of O. CJY
Uploaded Files
Date File Name
03/09/2016 1510448-Plan Review Comment Letter.docx
03/09/2016 1510324-Fire Sprinkler Specs. _Part3.pdf
03/09/2016 1510325-Fire Sprinkler Specs. _Part1.pdf
03/09/2016 1510326-Fire Sprinkler Specs. _Part2.pdf
03/09/2016 1510269-Stillaguamish River Rock - Fire Plans For Review.pdf
03/08/2016 1508796-BLD_927 Application.pdf
03/08/2016 1508797-Stillaguamish River Rock - Fire Plans For Review.pdf
âˆ
â„„
Ø