HomeMy WebLinkAbout21125 SMOKEY POINT BLVD_BLD928_2026 18204 59th Ave.
Arlington, WA 98223 REVIEW COMMENT FORM
(360) 403-3500
Project Name: Stillaguamish Tribes Permit No.: 927 Review Date: 3/16
Contact: Josh Wells Phone No.: 360-722-4350 Review Phase: 1st Round Report Date: 3/9/16
Reviewing Dept.: CED Applicant: Emerald Fire DWG Issue Date: 3/7/16
# Rev. Dwg. or Add’l Ref.
City
Comment Response/Resolution
Spec. Ref. Check
off
1. CJY 1 of 1 Head Quantity inconsistent with plan As-builts (shop drawings) will be required √
2. CJY 1 of 1 TJI flange supports for bracing – structural load Verify through structural drawings √
calculation conducted?
3. CJY 1 of 1 Sammy Screw depth at 2 ½ inches or bracing at 10’ Field verify √
4. CJY 1 of 1 Sidewinder screws in TJI’s – engineering call out Confirmation required √
5. CJY FP1.01 Bracing of riser required Field verify √
6. CJY FP1.01 Draft stops required in soffits, eaves, etc. with dry pipe Field verify √
sprinklers not exceeding 160 cubic feet
7. CJY U1.0 8†DCVA requires testing Field verify √
8. CJY U1.2 Thrust blocking and or restraint system required Field verify √
9. CJY U1.2 Hydro-static, flow, flush, and purity tests required Field verify √
10. CJY FA1.01 Pull Station and Smoke required in Sprinkler Room Field verify √
11. CJY FA1.01 Provide Battery Backup calculations Upon system certification √
12. CJY Specs Specs call out 18 smokes, 5 horn strobes, 12 strobes, 3 As-builts (shop drawings) required upon √
pull stations and the plans do not show locations of all the completion.
appliances. Also, no wiring diagram (Class A or B)?
13. CJY Misc. Acceptance tests required on all life safety systems prior
to occupancy.
14.
15.
16.
17.
18.
19.
20.
21.
Page 1 of 2
18204 59th Ave.
Arlington, WA 98223 REVIEW COMMENT FORM
(360) 403-3500
Project Name: Stillaguamish Tribes Permit No.: 927 Review Date: 3/16
Contact: Josh Wells Phone No.: 360-722-4350 Review Phase: 1st Round Report Date: 3/9/16
Reviewing Dept.: CED Applicant: Emerald Fire DWG Issue Date: 3/7/16
# Rev. Dwg. or Add’l Ref.
City
Comment Response/Resolution
Spec. Ref. Check
off
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
Page 2 of 2
Permit #: 928
Permit Date: 03/08/16
Permit Type: FIRE ALARM
Project Name: River Rock Convenience Store
Applicant Name: Stillaquamish Tribe of Indians
Applicant Address: P.O. Box 277
Applicant, City, State, Zip: Arlington, WA 98223
Contact: Josh Wells
Phone: 360-403-9123
Email: jwells@stillaquamish.com
Scope of Work:
Valuation: 13000.00
Square Feet: 4590
Number of Stories: 2
Construction Type:
Occupancy Group:
ID Code:
Permit Issued:
Permit Expires:
Form Permit Type:
Status: IN PROCESS
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
STILLAGUAMISH 699 Other
21125 SMOKEY POINT
31050800300100 TRIBE OF Miscellaneous
BLVD
INDIANS Services NEC
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
12617 108th CONSTRUCTION
White Security Systems 405-402-0366 Labor & Industries WHITESS044JP
Avenue NE CONTRACTOR
19010 61st Ave CONSTRUCTION Labor and
Elite Electric 360-653-6135 ELITELE132B9
NE Unit 1 CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
Ok to issue permit with redlined drawings and Plan
03/08/2016 FIRE ALARM BUILDING
Review Comment Letter.
Fees
Fee Description Notes Amount
Photocopies $12.00
Fire Alarm Plan Review Fee Valuation: 13K $309.03
Fire System Plan Review Table 4-1 $100.00
Total $421.03
Attached Letters
Date Letter Description
03/09/2016 Building Permit
Notes
Date Note Created By:
The building and systems have been under construction for a few months and it appeared that
03/09/2016 Chris Young
the Tribe opted not to submit for plan review and inspection services and now have. CJY
Uploaded Files
Date File Name
03/09/2016 1510488-Plan Review Comment Letter.docx
03/08/2016 1509011-BLD_928 Application.pdf