HomeMy WebLinkAbout8512 E Gilman Ave_BLD4612_2025
Permit Packet Coversheet
Community and Economic Development
City of Arlington • 18204 59th Avenue NE • Arlington, WA 98223 • Phone (360) 403-3551
Page 1 of 1
Permit Number: Permit Type:
Address/Parcel: Completed (Month/Year):
Land Use
Notice of Decision
Staff Report
Application
Narrative
Legal Description
Vicinity Map
Site Plan
Landscape Plan
Complete Streets Checklist
Traffic Impact Analysis
Snohomish County Traffic Mitigation Offer
WSDOT Traffic Offer Form
Tree Survey
Stormwater Drainage Report
Geotech Report
Critical Area Evaluation Form
SEPA Checklist
Public Notice Material
Noticing and Related Documents
Water / Sewer Availability Certificate
Unanticipated Discovery Plan Form
Aerial Photo of Site
Proposed Building Materials
Lighting Plans and Lighting Cut Sheets
Color Elevations
Design Matrix
Plat Map
Title Report
Lot Closures
Preliminary Civil Plans
Archaeological Survey
o Confidential Documents. Contact the
City to obtain.
Topography (Existing Conditions)
CC&R’s
Deeds / Easements / Conveyances
/Dedications
Developer’s Agreement
Recorded Copies
Bonding or Assignment of Funds
o Confidential Documents. Contact the
City to obtain.
Letters and Project Documents
Other:
Civil
Issued Permit
Application
Other Applications
Construction Calculation Worksheet
Approved Plans
Review Comment Form
Letters and Project Documents
Other Agency Permits
Reports:
o Drainage Report Pg:
o Stormwater Pg:
o Geotech Pg:
o All Other Reports
SEPA and Noticing Materials
Inspections
As-Builts
Other:
Building
Issued Permit
Application
Additional Applications
Approved Plans
Site Plan
Letters and Project Documents
Calculations
Project Specification Manuals
Reports
Certificate of Occupancy
Inspections
Other:
BLD4612 Fire Sprinkler
8512 E Giloman Ave December 2024
✔
✔
✔
✔
✔
✔
Model RFC Cover Plate
Model RFC43 & RFC43LLModel RFC30 & RFC30LL
Model RFC49 & RFC49LL Model RFC58
Features
• cULus Listed as Residential Sprinklers
• Push-On cover plate installation
• Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in ac-
cordance with UL 1626. In addition, Model RFCLL Series
sprinklers are cULus Certified for Health Effects to NSF/ANSI
standard 61 Annex G (LL) and Australian WaterMark Certified
(WMCS).
Model RFC30 sprinklers have a 165°F (74°C) temperature
rated fusible-link operating element. Model RFC43, RFC49,
RFC58, and RFC76 sprinklers are offered with either a 165°F
(74°C) or 212°F (100°C) temperature rated fusible-link oper-
ating element. Sprinklers with a 165°F (74°C) temperature
rating are ordinary temperature classification and are listed
for use with a 135°F (57°C) temperature rated cover plate.
Sprinklers with a 212°F (100°C) temperature rating are inter-
mediate temperature classification and are listed for use with
a 165°F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
cover plate. Model RFC cover plates may be installed by ei-
ther pushing or threading the cover plate into the sprinkler
cup. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and
RFC49LL sprinklers allow 1/2” (13 mm) of cover plate adjust-
ment. Model RFC58 and RFC76 sprinklers allow 3/4” (19 mm)
of cover plate adjustment. Model RFC cover plates are avail-
able in a variety of finishes as listed in Table H.
www.reliablesprinkler.com
Sprinkler Model Nominal K-Factor
gpm/psi1/2 (l/min/bar1/2)
Max. Coverage Area
ft x ft (m x m)
Listings &
Approvals
Sprinkler Identification
Number (SIN)
RFC30 3.0 (43)14 x 14 (4.3 x 4.3)cULus RA0611
RFC30LL 3.0 (43)14 x 14 (4.3 x 4.3)cULus, LL, WMCS RA3211
RFC43 4.3 (62)20 x 20 (6.1 x 6.1)cULus RA0612
RFC43LL 4.3 (62)20 x 20 (6.1 x 6.1)cULus, LL, WMCS RA3212
RFC49 4.9 (71)20 x 20 (6.1 x 6.1)cULus RA0616
RFC49LL 4.9 (71)20 x 20 (6.1 x 6.1)cULus, LL, WMCS RA3216
RFC58 5.8 (84)20 x 20 (6.1 x 6.1)cULus RA0613
RFC76 7.6 (109)20 x 20 (6.1 x 6.1)cULus RA0618
Table A
cULus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service.
LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content).
WMCS: Australian WaterMark Certified.
Model RFC76
cULus Listed
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
Bulletin 006 May 2019
Bulletin 006
May 2019
Page 2 of 8
www.reliablesprinkler.com
Model RFC30 & RFC30LL Sprinkler Components and Dimensions Figure 1
Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria Table B
Minimum Flow and Residual Pressure (1)
Max. Coverage Area (2)
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
12 x 12
(3.6 x 3.6)
9
(34)
9.0
(0.62)
14 x 14
(4.3 x 4.3)
10
(38)
11.0
(0.76)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1R1/2
Nominal K-Factor: 3.0 (43 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC30LL only)
Watermark Certified (RFC30LL only)
Bottom View
Model RFC30 & RFC30LL Residential Sprinklers RFC30: SINRA0611
RFC30LL: SINRA3211
Bulletin 006
May 2019
Page 3 of 8
www.reliablesprinkler.com
Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria Table C
Minimum Flow and Residual Pressure (1)
Max. Coverage Area (2)
ft. x ft.
(m x m)
Ordinary Temperature Intermediate Temperature
Flow
gpm
(l/min)
Pressure
psi
(bar)
Flow
gpm
(l/min)
Pressure
psi
(bar)
15 x 15
(4.6 x 4.6)
12
(45)
7.8
(0.54)
12
(45)
7.8
(0.54)
16 x 16
(4.9 x 4.9)
13
(49)
9.1
(0.63)
13
(49)
9.1
(0.63)
18 x 18
(5.5 x 5.5)
18
(68)
17.5
(1.21)----
20 x 20
(6.1 x 6.1)
21
(79)
23.8
(1.64)----
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Model RFC43 & RFC43LL Sprinkler Components and Dimensions Figure 2
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1R1/2
Nominal K-Factor: 4.3 (62 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC43LL only)
Watermark Certified (RFC43LL only)
Bottom View
Model RFC43 & RFC43LL Residential Sprinklers RFC43: SINRA0612
RFC43LL: SINRA3212
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1R1/2
Nominal K-Factor: 4.9 (71 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC49LL only)
Watermark Certified (RFC49LL only)
Model RFC49 & RFC49LL Sprinkler Components and Dimensions Figure 3
Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria Table D
Minimum Flow and Residual Pressure (1)
Max. Coverage Area (2)
ft. x ft.
(m x m)
Ordinary Temperature Intermediate Temperature
Flow
gpm
(l/min)
Pressure
psi
(bar)
Flow
gpm
(l/min)
Pressure
psi
(bar)
16 x 16
(4.9 x 4.9)
13
(49.0)
7.0
(0.48)
13
(49.0)
7.0
(0.48)
18 x 18
(5.5 x 5.5)
17
(64.3)
12.0
(0.83)
17
(64.3)
12.0
(0.83)
20 x 20
(6.1 x 6.1)
20
(75.7)
16.7
(1.15)
21
(79.5)
18.4
(1.27)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006
May 2019
Page 4 of 8
www.reliablesprinkler.com
Bottom View
Model RFC49 & RFC49LL Residential Sprinklers RFC49: SINRA0616
RFC49LL: SINRA3216
Model RFC58 Residential Sprinkler SIN RA0613
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Chrome Plated Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed
Model RFC58 Sprinkler Components and Dimensions Figure 4
Model RFC58 Sprinkler Hydraulic Design Criteria Table E
Minimum Flow and Residual Pressure( 1)
Max. Coverage Area (2)
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
16 x 16
(4.9 x 4.9)
16
(60.6)
7.6
(0.53)
18 x 18
(5.5 x 5.5)
18
(68.1)
9.6
(0.66)
20 x 20
(6.1 x 6.1)
20
(75.7)
11.9
(0.82)
Bulletin 006
May 2019
Page 5 of 8
www.reliablesprinkler.com
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bottom View
Bulletin 006
May 2019
Page 6 of 8
www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 3/4” NPT or ISO 7-1R3/4
Nominal K-Factor: 7.6 (109 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed
Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria Table E
Minimum Flow and Residual Pressure( 1)
Max. Coverage Area (2)
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
16 x 16
(4.9 x 4.9)
21
(79.5)
7.6
(0.52)
18 x 18
(5.5 x 5.5)
24
(90.8)
9.9
(0.68)
20 x 20
(6.1 x 6.1)
34
(128.7)
20
(1.4)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bottom View
Model RFC76 Residential Sprinkler SIN RA0618
Model RFC76 Sprinkler Components and Dimensions Figure 5
Standard Finishes Special Application Finishes
White Polyester Off White Paint Black Paint Raw Brass
Chrome Plated Bright Brass Finished Bronze Black Plated
Satin Chrome Stainless Steel Clad(3)Custom Color Paint(2)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Custom color paint is semi-gloss, unless specified otherwise.
3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side. Cover plates
are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.
Cover Plate Finishes(1) Table H
Bulletin 006
May 2019
Page 7 of 8
www.reliablesprinkler.com
Notes:
1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method
prior to installation. A 1/2” x 1/2” brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing
sprinklers.
2. For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C).
3. For use with 212°F (100°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F (66°C).
Sprinkler
Model
Cover
Plate
Model
Cover Plate
Diameter
inch (mm)
Recommended
Hole Diameter
in Ceiling
inch (mm)
Cover Plate
Adjustment
inch (mm)
Min. to
Max. Face
of Fitting to
Ceiling(1)
inch (mm)
Min. to Max.
Dropped Deflector
Distance below
Ceiling
inch (mm)
Cover Plate
Temperature
Rating
RFC30,
RFC30LL RFC 3-5/16
(84)
2-5/8
(67)
1/2
(13)
1-1/2 to 2
(38 to 51)
1/2 to 1
(13 to 25)
135°F
(57°C)
RFC43,
RFC43LL,
RFC49,
RFC49LL
RFC 3-5/16
(84)
2-5/8
(67)
1/2
(13)
1-1/2 to 2
(38 to 51)
1/2 to 1
(13 to 25)
135°F(2)
(57°C)
or 165°F(3)
(74°C)
RFC58,
RFC76 RFC 3-5/16
(84)
2-5/8
(67)
3/4
(19)
1-1/2 to 2-1/4
(38 to 57)
1/4 to 1
(6 to 25)
135°F(2)
(57°C)
or 165°F(3)
(74°C)
Table JInstallation Dimensions
Installation
Model RFC series sprinklers are intended to be installed in ac-
cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the
requirements of applicable authorities having jurisdiction. Mod-
el RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in
the cup are open and unobstructed following installation. Model
RFC series sprinklers are shipped with a wrench-able protec-
tive cap that should remain on the sprinkler until the sprinkler
system is placed in service following construction.
Model RFC series sprinklers can be installed without removing
the wrench-able protective cap using the Model W3 wrench.
Alternatively, Model RFC series sprinklers can be installed us-
ing the Model FC wrench by temporarily removing the protec-
tive cap during installation of the sprinkler. The use of any other
wrench to installed Model RFC series sprinklers is not permit-
ted and may damage the sprinkler. Fully insert the Model W3
wrench over the cap until it reaches the bottom of the cup, or
the Model FC wrench over the sprinkler until the wrench engag-
es the body. Do not wrench any other part of the sprinkler/cup
assembly. The Model W3 and FC wrenches are designed to be
turned with a standard 1/2” square drive. Tighten the sprinkler
into the fitting after applying a PTFE based thread sealant to the
sprinkler’s threads. Recommended installation torque is 8 to 18
ft-lbs (11 to 24 N-m) for 1/2” thread sprinklers and 14 to 20 ft-lbs
(19 to 27 N-m) for 3/4” thread sprinklers.
Do not exceed the maximum recommended torque. Exceeding
the maximum recommended torque may cause leakage or im-
pairment of the sprinkler. Use care when inserting or removing
the wrench from the sprinkler to avoid damage to the sprinkler.
Install the cover plate by hand by pushing the cover plate into
the cup and turning the cover in the clockwise direction until it
is tight against the ceiling.
Application
Model RFC series sprinklers are intended for installation where
residential sprinklers are permitted or required by NFPA 13,
NFPA 13R, and NFPA 13D. The sprinklers are concealed pen-
dent residential sprinklers.
Model RFC 30 and RFC30LL sprinklers are available in ordinary
temperature classification for installation where the Maximum
Ceiling Temperature does not exceed 100°F (38°C). Model
RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprin-
klers are available in either ordinary or intermediate tempera-
ture classification for installation where the Maximum Ceiling
Temperature does not exceed 100°F (38°C) or 150°F (66°C),
respectively.
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Patents
Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL,
RFC58, and RFC76 sprinklers are covered by U.S. Patent No.
9,248,327 and U.S. Patent No. 7,275,603.
Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are
additionally covered by U.S. Patent No. 8,776,903.
Ordering Information
Specify the following when ordering.
Sprinkler
• Model (RFC30, RFC30LL, RFC43, RFC43LL,
RFC49, RFC49LL, RFC58, RFC76)
• Temperature Rating
Cover Plate
• Model RFC
• Temperature Rating
• Finish (See Table H)
Sprinkler Wrench
• Model FC
• Model W3
Maintenance
Model RFC series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace
any sprinkler cover plate assembly which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non-oper-
ation.
Bulletin 006
May 2019
Page 8 of 8
www.reliablesprinkler.com
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada to UL1626, Residential Sprinklers for Fire-protection
Service (cULus).
Certified by Underwriters Laboratories, Inc. and Underwrit-
ers Laboratories of Canada for Health Effects to NSF/ANSI
Standard 61 Annex G (LL) (RFC30LL, RFC43LL, and RFC49LL
only).
Australian WaterMark Certified (RFC30LL, RFC43LL, and
RFC49LL only).
P/
N
9
9
9
9
9
7
0
2
6
1
Model FC
For use with Model RFC Series sprinklers
without wrench-able cap installed
Wrench
Model W3
For use with Model RFC Series sprinklers
with wrench-able cap installed
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bu
l
l
e
t
i
n
0
3
3
F
e
b
r
u
a
r
y
2
0
1
9
Bulletin 033 February 2019
Model F1 RES LL
Residential Sprinklers
Types:
1. F1 Res 30 LL Pendent
2. F1 Res 30 LL Recessed Pendent/F2
3. F1 Res 30 LL Recessed Pendent/FP
4. F1 Res 49 LL Pendent
5. F1 Res 49 LL Recessed Pendent/F1
6. F1 Res 49 LL Recessed Pendent/FP
7. F1 Res 58 LL Pendent
8. F1 Res 58 LL Recessed Pendent/F1
9. F1 Res 58 LL Recessed Pendent/FP
10. F1 Res 30 LL CCP Pendent
11. F1 Res 49 LL CCP Pendent
12. F1 Res 58 LL CCP Pendent
13. F1 Res 44 LL HSW
14. F1 Res 44 LL Recessed HSW/F2
15. F1 Res 58 LL HSW
16. F1 Res 58 LL HSW Recessed HSW/F2
17. F1 Res 44 LL SWC
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus) for Safety to ANSI/
UL1626.
2. Certified by Underwriters Laboratories, Inc. and Under-
writers Laboratories of Canada for Health Effects to NSF/
ANSI Standard 61 Annex G (Less than 0.25% Lead Con-
tent.)
3. WaterMark certified. WaterMark Certificate Number
23347
Additional Bulletins applicable to all
F1RES LL Sprinklers
• Wall Wetting - Bulletin 007
• Design and Installation - Bulletin 140
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the
Model F1 Res 49 LL & 58 LL Pendent Sprinklers
Other patents pending.
F1 Res 30 LL, 49 LL, & 58
LL Recessed Pendent/FP
F1 Res 49 LL & 58 LL Recessed
Pendent / F1, F1 Res 30 LL
Recessed Pendent/F2
F1 Res 44 LL & 58 LL
Recessed HSW/F2
F1 Res 30 LL, 49 LL & 58 LL
CCP Pendent
F1 Res 44 LL
SWC
Product Description
Model F1 Res LL Pendent sprinklers (Figs. 1, 2, 3, & 4) are
fast response sprinklers combining excellent durability, high
sensitivity glass-bulb and low profile decorative design. The
F1 Res LL Horizontal Sidewall sprinklers (Figs. 5, & 6) are
equally attractive when above ceiling piping cannot be used.
The 3mm glass-bulb pendent sprinklers permit the efficient
use of residential water supplies for sprinkler coverage in resi-
dential fire protection design.
The low flow F1 Res LL sprinklers are specially engineered
for fast thermal response to meet the sensitive fire protection
application needs of the latest residential market standards
(UL 1626 Standard). Upon fire conditions, rising heat causes
a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly distributing
the discharged water to control a fire.
Technical Data:
• Thermal Sensor: Nominal 3mm glass-bulb
• Sprinkler Frame : Brass
• Sprinklers’ Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: ½” NPT (R½)
• K-Factor: 3.0 (Actual) - F1 Res 30 LL Pendent Sprinkler
4.9 (Actual) - F1 Res 49 LL Pendent Sprinkler
5.8 (Actual) - F1 Res 58 LL Pendent & HSW Sprinkler
4.4 (Actual) - F1 Res 44 LL HSW Sprinkler
Specifically Listed for use in Multipurpose Systems that serve both
domestic water and fire protection.
F1 Res 30 LL, 49 LL & 58 LL
Pendent
F1 Res 44 LL & 58 LL
HSW
2.
Application
Model F1 Res LL sprinklers are cULus Listed in accor-
dance with UL 1626 for installation in accordance with
NFPA 13, NFPA 13R, and NFPA 13D. Sprinkler systems
using Model F1 Res LL sprinklers must be hydraulically
designed to provide at least the flow identified in the Tech-
nical Data tables in this bulletin. For NFPA 13 installations,
the flow per sprinkler must be the greater of: (1) the flow
listed in the applicable Technical Data table and (2) the
flow required to achieve a minimum design density of 0.1
gpm/sq ft over the design area of the sprinkler. For cover-
age area dimensions less than those listed in the Technical
Data tables, use the minimum required flow for the next
larger max. coverage area listed.
Installation
Models F1 Res LL sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith, are
the only recessed escutcheons to be used with Model F1
Res LL sprinklers. Use of any other recessed escutcheon
will void all approvals and warranties. For installing Model
F1 Res LL Pendent sprinklers use only the Model W2 sprin-
kler Wrench; for installing Models F1 Res LL Recessed
Pendent, CCP & SWC sprinklers use only the Model GFR2
sprinkler wrench; for installing Model F1 LL Res Recessed
HSW sprinklers use only the Model GFR2 Sprinkler Wrench.
Use of wrenches other than those specified may damage
these sprinklers. Install F1 Res 44 LL with a ceiling to de-
flector distance of 4” - 12”. Flow arrow on deflector must
point away from near wall and “Top” marking must face
ceiling.
Escutcheon*, F1 or F2, Data:
Type Adjustment
Inch (mm)
“A”
Inch (mm)
Face of fitting
to ceiling
Inch (mm)
F1 3/4 (19.0)Min.=3/4” (19.1)
Max.=11/2” (38.1)
3/16 - 15/16
(4.7 - 24.0)
F2 1/2 (12.7)Min.=15/16” (23.8)
Max.=11/2” (38.1)
3/16 - 11/16
(4.7 - 17.4)
* Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49 LL & 58 LL Recessed Pendent Sprinkler
• Model F1 Res 30 LL, 49 LL & 58 LL Pendent
• Model F1 Res 30 LL Recessed Pendent / F2
• Model F1 Res 49 LL & 58 LL Recessed Pendent / F1
Fig. 1
Fig. 2
F1 escutcheon, 3/4” (19mm) adjustment
3.
Technical Data: F1Res 30 LL Pendent and Recessed Pendent (SIN RA3311)
Thread
Size
Nominal Orifice
Inch (mm)
Max. Pressure
psi (bar)
Sprinkler Temp. Rating Max. Ambient Temp.Actual K
Factor
Sprinkler Length
Inch (mm)°F °C °F °C
½” NPT
(R½)21/64” (8.2)175 (12)155
175
68
79 100 38 3.0 (43.2)2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max.
Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)8 (30.3)7.0 (0.48)8 (30.3)7.0 (0.48)Smooth Ceilings 1” to 4”
(25mm to 100mm)
Beamed Ceilings per NFPA 13,
13D, or 13R
8 (2.4)14 x 14 (4.3 x 4.3)14 (4.3)10 (37.8)11 (0.76)10 (37.8)11 (0.76)
16 x 16 (4.9 x 4.9)16 (4.9)13 (49)18.8 (1.3)13 (49)18.8 (1.3)
Technical Data: F1Res 49 LL Pendent and Recessed Pendent (SIN RA3316)
Thread
Size
Nominal Orifice
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient Temp.
Actual
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)7/16” (11)175 (12)155
175
68
79
100
150
38
66 4.9 (70.6)2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Deflector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)13 (49)7.0 (0.48)13 (49)7.0 (0.48)
Smooth Ceilings 1” to 4”
(25mm to 100mm)
Beamed Ceilings per NFPA
13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)13 (49)7.0 (0.48)13 (49)7.0 (0.48)
16 x 16 (4.9 x 4.9)16 (4.9)13 (49)7.0 (0.48)13 (49)7.0 (0.48)
18 x 18 (5.5 x 5.5)18 (5.5)17 (64.3)12 (0.83)17 (64.3)12 (0.83)
20 x 20 (6.1 x 6.1)20 (6.1)20 (75.7)16.7 (1.14)20 (75.7)16.7 (114)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Deflector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)15 (57)9.4 (0.65)15 (57)9.4 (0.65)
Smooth Ceilings 4” to 8”
(100mm to 200mm)8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)16 (60.5)10.6 (0.73)16 (60,5)10.6 (0.73)
16 x 16 (4.9 x 4.9)16 (4.9)17 (64.3)12.0 (0.83)17 (64.3)12.0 (0.83)
18 x 18 (5.5 x 5.5)18 (5.5)19 (72)15.0 (1.0)19 (72)15.0 (1.0)
20 x 20 (6.1 x 6.1)20 (6.1)22 (83.2)20.2 (1.4)22 (83.2)20.2 (1.4)
FP push-on/thread-off escutcheon
4.
• Model F1 Res 30 LL, 49 LL & 58
LL CCP Pendent
• Model F1 Res 30 LL, 49 LL & 58
LL Recessed Pendent / FP
Fig. 3 Fig. 4
Technical Data: F1Res 58 LL Pendent and Recessed Pendent (SIN RA3313)
Thread
Size
Nominal Orifice
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient Temp.Actual
K Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)½” (13)175 (12)155
175
68
79
100
150
38
66 5.8 (83.5)2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Deflector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)16 (61)7.6 (0.53)16 (61)7.6 (0.53)
Smooth Ceilings 1” to 4”
(25mm to 100mm)
Beamed Ceilings per NFPA 13,
13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)16 (61)7.6 (0.53)16 (61)7.6 (0.53)
16 x 16 (4.9 x 4.9)16 (4.9)16 (61)7.6 (0.53)16 (61)7.6 (0.53)
18 x 18 (5.5 x 5.5)18 (5.5)19 (72)10.8 (0.75)19 (72)10.8 (0,75)
20 x 20 (6.1 x 6.1)20 (6.1)22 (83,3)14.4 (1.0)22 (83.3)14.4 (1.0)
5.
Technical Data: F1Res 30 LL CCP Pendent and Recessed Pendent/FP (SIN RA3311)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)21/64” (8.2)175 (12)135 57 100 38 3.0 (43.2)2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spac-
ing Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)8 (30.3)7.0 (0.48)Smooth Ceilings 1/2” to 1”
(13mm to 25mm) using CCP or FP escutcheon
Beamed Ceilings per NFPA 13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)11 (37.8)13.4 (0.92)
Technical Data: F1Res 49 LL CCP Pendent and Recessed Pendent/FP (SIN RA3316)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)7/16” (11)175 (12)135 57 100 38 4.9 (70.6)2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)13 (49)7.0 (0.48)
Smooth Ceilings 1/2” to 1”
(13mm to 25mm) using CCP or FP
escutcheon
Beamed Ceilings per NFPA 13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)13 (49)7.0 (0.48)
16 x 16 (4.9 x 4.9)16 (4.9)14 (53)8.2 (0.56)
18 x 18 (5.5 x 5.5)18 (5.5)18 (68.1)13.5 (0.93)
20 x 20 (6.1 x 6.1)20 (6.1)20 (75.7)16.7 (1.14)
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
Technical Data: F1Res 58 LL CCP Pendent and Recessed Pendent/FP (SIN RA3313)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)1/2” (13)175 (12)135 57 100 38 5.8 (83.5)2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)16 (61)7.6 (0.53)
Smooth Ceilings 1/2” to 1”
(13mm to 25mm) using CCP or FP escutcheon
Beamed Ceilings per NFPA 13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)16 (61)7.6 (0.53)
16 x 16 (4.9 x 4.9)16 (4.9)16 (61)7.6 (0.53)
18 x 18 (5.5 x 5.5)18 (5.5)19 (72)10.8 (0.75)
20 x 20 (6.1 x 6.1)20 (6.1)22 (83.3)14.4 (1.0)
6.
• Model F1 Res 44 LL & 58 LL HSW
• Model F1 Res 44 LL & 58 LL Recessed HSW/F2
F2 escutcheon, 1/2” (13mm) adjustment
Technical Data: F1Res 44 LL HSW & HSW/F2 (SIN RA3331)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)3/8” (10)175 (12)155
175
68
79
100
150
38
66 4.4 (63)2.45 (62)
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting
to wall
Inch (mm)
F2 1/2 (13)3/16 - 11/16
(4.7 - 17.4)
Max. Coverage area
Ft x Ft (m x m)
Max. Spac-
ing Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)12 (45.4)7.5 (0.52)12 (45.4)7.5 (0.52)
4 to 6 (100 to 152)
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)14 (53.0)10.2 (0.71)14 (53.0)10.2 (0.71)
16 x 16 (4.9 x 4,9)16 (4.9)16 (60.6)13.3 (0.92)16 (60.6)13.3 (0.92)
16 x 18 (4.9 x 5.5)16 (4.9)18 (68.1)16.8 (0.53)18 (68.1)16.8 (0.53)
18 x 18 (5.5 x 5.5)18 (5.5)19 (72.0)18.7 (1.29)19 (72.0)18.7 (1.29)
16 x 20 (4.9 x 6.1)16 (4.9)23 (87.1)27.4 (1.89)23 (87.1)27.4 (1.89)
12 x 12 (3.6 x 3.6)12 (3.6)14 (53.0)10.2 (0.71)14 (53.0)10.2 (0.71)
6 to 12 (152 to 305)
14 x 14 (4.3 x 4.3)14 (4.3)16 (60.6)13.3 (0.92)16 (60.6)13.3 (0.92)
16 x 16 (4.9 x 4.9)16 (4.9)17 (64.4)15.0 (1.04)17 (64.4)15.0 (1.04)
16 x 18 (4.9 x 5.5)16 (4.9)20 (75.7)20.7 (1.43)20 (75.7)20.7 (1.43)
16 x 20 (4.9 x 6.1)16 (4.9)23 (87.1)27.4 (1.89)23 (87.1)27.4 (1.89)
Fig. 5
7.
Technical Data: F1Res 44 LL SWC (SIN RA3331)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
Cover
Temp.
Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)3/8” (10)175 (12)135 57 100 38 4.4 (63)2.45 (62)
• Model F1 Res 44 LL SWC
Fig. 6
Technical Data: F1Res 58 LL HSW & HSW/F2 (SIN RA3333)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)1/2” (13)175 (12)155
175
68
79
100
150
38
66 5.8 (83.5)2.45 (62)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)16 (60.6)7.6 (0.53)16 (60.6)7.6 (0.53)
4 to 6 (100 to 152)
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)18 (68.2)9.7 (0.69)18 (68.2)9.7 (0.69)
16 x 16 (4.9 x 4.9)16 (4.9)21 (79.5)13.2 (0.91)21 (79.5)13.2 (0.91)
16 x 18 (4.9 x 5.5)16 (4.9)25 (94.7)18.6 (1.28)25 (94.7)18.6 (1.28)
16 x 20 (4.9 x 6.1)16 (4.9)29 (109.8)25.0 (1.73)29 (109.8)25.0 (1.73)
12 x 12 (3.6 x 3.6)12 (3.6)22 (83.3)14.4 (1.0)22 (83.3)14.4 (1.0)
6 to 12 (152 to 305)
14 x 14 (4.3 x 4.3)14 (4.3)22 (83.3)14.4 (1.0)22 (83.3)14.4 (1.0)
16 x 16 (4.9 x 4.9)16 (4.9)26 (98.4)20.1 (1.39)26 (98.4)20.1 (1.39)
16 x 18 (4.9 x 5.5)16 (4.9)31 (117.4)28.6 (1.97)31 (117.4)28.6 (1.97)
Maintenance
Model F1 Res 30 LL, 49 LL, F1 Res 58 LL and F1 Res 44
LL Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D, and
13R. Do not clean sprinkler with soap and water, Ammonia
or any other cleaning fluids. Remove dust by using a soft
brush or gentle vacuuming. Replace any sprinkler which
has been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should remain
in the original cartons and packaging until used. This will
minimize the potential for damage to sprinklers that could
cause improper operation or non-operation.
Model F1 Res 30 LL, 49 LL & 58 LL Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [WaterMark Certified
WMCS] low flow residential pendent sprinklers engineered
to provide a minimum design density of 0.05 gpm/ft2 over
the listed coverage area. Listed flows as specified by the
manufacturer’s technical data sheets are to be used. Resi-
dential sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the applicable
installation standard. Deflector-to-ceiling distance listing
shall be 1” to 4” maximum, unless specifically listed other-
wise. Sprinkler frame and deflector shall be of bronze frame
construction having a ½” NPT thread. Water seal assembly
shall consist of a PTFE-coated Belleville spring washer with
top-loaded extruded or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a temperature
rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall
have a nominal K-factor of 3.0, 4.9 and 5.8. Standard fin-
ish: [Bronze] [Chrome-plated] [White Polyester] [Special
finish– specify]. Residential pendent sprinklers shall be
Reliable Model F1 Res 30 LL, 49 LL & 58 LL, SIN RA3311,
RA3316 & RA3313 (Bulletin 033).
Model F1 Res 49 LL & 58 LL Recessed
Pendent/F1
Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/F2
Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/FP Specifications
Sprinklers shall be [cULus Listed] [WaterMark Certified
WMCS] low flow residential recessed pendent sprinklers
engineered to provide a minimum design density of 0.05
gpm/ft2 over the listed coverage area. Listed flows as
specified by the manufacturer’s technical data sheets are
to be used. Residential sprinklers shall be installed in con-
formance with the manufacturer’s installation guidelines
and the applicable installation standard. Deflector-to-ceil-
ing distance listing shall be 1” to 4” maximum, unless spe-
cifically listed otherwise. Sprinkler frame and deflector shall
be of bronze frame construction having a ½” NPT thread.
Water seal assembly shall consist of a PTFE-coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic parts,
and having a temperature rating of [155°F (68°C)] [175°F
(79°C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9
& 5.8. Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish– specify]. Recessed escutcheon
assembly shall be a steel, two-piece escutcheon [with ½”
adjustment (Model F2)] [with ¾” adjustment (Model F1)] [of
push-on and thread off design with ½” adjustment (Model
FP)]. Standard finish shall be [brass][bright chrome] [white
painted]. Residential recessed pendent sprinklers shall be
Reliable [Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/F1] [Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/F2] [Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/FP] SIN RA3311, RA3316 & RA3313 (Bulletin 033).
8.
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)12 (3.6)13 (49.2)8.7 (0.60)
4 to 6 (100 to 152)
8 (2.4)
14 x 14 (4.3 x 4.3)14 (4.3)14 (53.0)10.2 (0.71)
16 x 16 (4.9 x 4.9)16 (4.9)17 (64.3)15.0 (1.1)
16 x 18 (4.9 x 5.5)16 (4.9)19 (71.8)18.7 (1.13)
16 x 20 (4.9 x 6.1)16 (4.9)23 (87.1)27.4 (1.89)
12 x 12 (3.6 x 3.6)12 (3.6)14 (52.9)10.2 (0.71)
6 to 12 (152 to 305)
14 x 14 (4.3 x 4.3)14 (4.3)15 (56.7)11.7 (0.81)
16 x 16 (4.9 x 4.9)16 (4.9)18 (68.1)16.8 (1.16)
16 x 18 (4.9 x 5.5)16 (4.9)20 (75.6)20.7 (1.43)
Technical Data: F1Res 44 LL SWC (SIN RA3331) continued
Model F1 Res 30 LL, 49 LL & 58 LL CCP Pendent
(Concealed) Specifications
Sprinklers shall be [cULus Listed] [WaterMark Certified
WMCS] low flow residential concealed sprinklers engi-
neered to provide a minimum design density of 0.05 gpm/
ft2 over the listed coverage area. Listed flows as speci-
fied by the manufacturer’s technical data sheets are to be
used. Residential sprinklers shall be installed in confor-
mance with the manufacturer’s installation guidelines and
the applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having a ½”
NPT thread. Water seal assembly shall consist of a PTFE-
coated Belleville spring washer with top-loaded extruded
or cold head cup with 3 mm glass bulb containing no plas-
tic parts, and having a temperature rating of 155°F (68°C).
Cover plate assembly shall consist of a brass cover plate
and copper alloy retainer flange. Method of attaching the
cover plate to the sprinkler cup shall be a push-on and
thread-off design allowing a ½” cover plate adjustment.
Cover plate temperature rating shall be 135°F (57°C). A
plastic protective cap shall be provided and factory in-
stalled inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before the
cover plate is installed. Standard cover plate finish: [White]
[Custom Color– specify]. ]. Concealed pendent sprinklers
shall be Reliable Model F1 Res 30 LL, 49 LL & 58 LL CCP,
SIN RA3311, RA3316 & RA3313 (Bulletin 033).
Model F1 Res 44 LL Horizontal Sidewall
Residential Sprinkler Specifications
Sprinklers shall be [cULus Listed] [WaterMark Certified
WMCS] low flow residential horizontal sidewall sprinklers
engineered to provide a minimum design density of 0.05
gpm/ft2 over the listed coverage area. Listed flows as
specified by the manufacturer’s technical data sheets are to
be used. Residential sprinklers shall be installed in confor-
mance with the manufacturer’s installation guidelines and
the applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having a ½”
NPT thread. Water seal assembly shall consist of a PTFE-
coated Belleville spring washer with top-loaded extruded
or cold head cup with 3 mm glass bulb containing no plas-
tic parts, and having a temperature rating of [155°F (68°C)]
[175°F (79°C)]. Sprinklers shall have a nominal K-factor
of 4.4 (62.8). Standard finish: [Bronze] [Chrome-plated]
[White Polyester] [Special finish– specify]. Residential hori-
zontal sidewall sprinklers shall be Reliable Model F1 Res
44 LL, SIN RA3331 (Bulletin 033).
Model F1 Res 44 LL Recessed
Horizontal Sidewall Sprinkler Specifications
Use description for the Model F1 Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
“horizontal sidewall sprinkler” with “recessed horizontal
sprinkler.” Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½” adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish– specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model F1
Res 44 LL/F2, SIN RA3331 (Bulletin 033).
Standard Finishes
Sprinkler F1, F2, FP
Escutcheons Cover Plates
Bronze
Chrome Plated
White and Black Polyester
Coated
Brass
Bright Chrome Plated
White Painted
White Painted
Chrome
Special Application Finishes
Sprinkler F1, F2,
Escutcheons Cover Plates
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are available on special order.
Consult factory for details.
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 02/19 P/N 9999970411
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.
1ProPEX® is a registered trademark of Uponor, Inc. ProPEX™ is a trademark of Uponor Ltd.
2Visit listing agency’s website for complete information. 3For ¾", 1" and 1¼" pipe only. 4For ¾" to 3" pipe.
Uponor AquaPEX® White, coils
Submittal information
Project information
Technical data
180°F (82°C) at 100 psi (689 kPa)
73.4°F (23°C) at 160 psi (1,103 kPa)
½", ¾", 1", 1¼", 1½" and 2" Uponor AquaPEX® White only:
120°F (49°C) at 130 psi (896 kPa)
Product information and application use
as radiant heating/cooling and hydronic piping systems containing no ferrous corrodible components or where ferrous
components are isolated from the piping.
Description Part number I.D. O.D. Weight
⅜" Uponor AquaPEX White, 400-ft. coil
⅜" Uponor AquaPEX White, 1,000-ft. coil
½" Uponor AquaPEX White, 100-ft. coil
½" Uponor AquaPEX White, 300-ft. coil
½" Uponor AquaPEX White, 500-ft. coil
½" Uponor AquaPEX White, 1,000-ft. coil
⅝" Uponor AquaPEX White, 300-ft. coil
⅝" Uponor AquaPEX White, 1000-ft. coil
¾" Uponor AquaPEX White, 100-ft. coil
¾" Uponor AquaPEX White, 300-ft. coil
¾" Uponor AquaPEX White, 500-ft. coil
1" Uponor AquaPEX White, 100-ft. coil
1" Uponor AquaPEX White, 300-ft. coil
1" Uponor AquaPEX White, 500-ft. coil
1¼" Uponor AquaPEX White, 100-ft. coil
1¼" Uponor AquaPEX White, 300-ft. coil
1½" Uponor AquaPEX White, 100-ft. coil
1½" Uponor AquaPEX White, 300-ft. coil
2" Uponor AquaPEX White, 100-ft. coil
2" Uponor AquaPEX White, 200-ft. coil
2" Uponor AquaPEX White, 300-ft. coil
2½" Uponor AquaPEX White, 100-ft. coil
2½" Uponor AquaPEX White, 300-ft. coil
3" Uponor AquaPEX White, 100-ft. coil
F1090375
F1120375
F1040500
F1060500
F1100500
F1120500
F1060625
F1120625
F1040750
F1060750
F1100750
F1041000
F1061000
F1101000
F1061250
F1021250
F1061500
F1021500
F1062000
F1052000
F1022000
F1062500
F1022500
F1063000
0.350"
0.350"
0.475"
0.475"
0.475"
0.475"
0.574"
0.574"
0.671"
0.671"
0.671"
0.862"
0.862"
0.862"
1.054"
1.054"
1.244"
1.244"
1.629"
1.629"
1.629"
2.011"
2.011"
2.400"
0.500"
0.500"
0.625"
0.625"
0.625"
0.625"
0.750"
0.750"
0.875"
0.875"
0.875"
1.125"
1.125"
1.125"
1.375"
1.375"
1.625"
1.625"
2.125"
2.125"
2.125"
2.625"
2.625"
3.125"
20.0 lbs.
44.0 lbs.
6.0 lbs.
18.0 lbs.
27.6 lbs.
54.0 lbs.
28.0 lbs.
86.0 lbs.
10.0 lbs.
34.0 lbs.
54.0 lbs.
20.0 lbs.
56.0 lbs.
93.0 lbs.
34.0 lbs.
106.0 lbs.
44.0 lbs.
133.0 lbs.
68.2 lbs.
136.4 lbs.
204.6 lbs.
88.0 lbs.
264.0 lbs.
128.0 lbs.
Installation
⅜"
Manual (PDAM), Complete Design Assistance Manual (CDAM), Hydronic Piping Design Assistance Manual (HPDAM) or AquaSAFE™ Residential Fire Sprinkler
Installation Guide for more information.
Listings2 Codes Standards
cNSFus-fs3; cNSFus-pw; cQAIus P321; UL;
CSA; PPI TR-4; ICC-ES; BMEC; CCMC UPC; UMC; NSPC; HUD;
UFGS; NPC of Canada;
NBC of Canada
F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101;
ASTM E814/ULC S115; CSA B137.5; CSA B214;
UL 18213; ULC/ORD-C199P3; AWWA C9044
Related applications Contact information
AquaSAFE™ fire safety systems
Radiant heating and cooling systems
Hydronic piping systems
Uponor, Inc.
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: 800.321.4739
Fax: 952.891.2008
uponorpro.com
Uponor Ltd.
6510 Kennedy Road
Mississauga, ON L5T 2X4 CANADA
Phone: 888.994.7726
Fax: 800.638.9517
uponorpro.com
1ProPEX® is a registered trademark of Uponor, Inc. ProPEX™ is a trademark of Uponor Ltd.
2Visit listing agency’s website for complete information; 3For ½", ¾", 1", 1¼", 1½" and 2" tubing only
ProPEX® Ring
Submittal information
Revision I: Nov. 1, 2018
Project information
Technical data
Material: Engel-method crosslinked polyethylene (PEX-a)
Density: 926 to 940 kg/m3
Degree of crosslinking: 70% to 89%
Product information and application use
Uponor ProPEX® rings are required to make a proper ProPEX connection.1 The ProPEX
ring with stop includes a leading edge chamfer and stop edge.
Description Part number Length I.D. O.D. Weight
⅜"
ProPEX Ring with Stop, ½"
ProPEX Ring with Stop, ⅝"
ProPEX Ring with Stop, ¾"
ProPEX Ring with Stop, 1"
ProPEX Ring with Stop, 1¼"
ProPEX Ring with Stop, 1½"
ProPEX Ring with Stop, 2"
ProPEX Ring with Stop, 2½"
ProPEX Ring with Stop, 3"
Q4690512
Q4690625
Q4690756
Q4691000
Q4691250
Q4691500
Q4692000
Q4692500
Q4693000
0.54"
0.63"
0.79"
0.87"
1.10"
1.35"
1.61"
1.97"
2.61"
3.12"
0.63"
0.75"
0.88"
1.13"
1.38"
1.63"
2.14"
2.66"
3.16"
0.74"
0.87"
1.00"
1.13"
1.42"
1.66"
1.91"
2.61"
3.25"
3.87"
0.005 lbs.
0.006 lbs.
0.008 lbs.
0.012 lbs.
0.020 lbs.
0.030 lbs.
0.040 lbs.
0.133 lbs.
0.230 lbs.
0.400 lbs.
Installation
Square cut the Uponor PEX tubing. Remove excess material. Slide the ProPEX ring over the end of the tubing (maximum 1/16" over-hang for rings without stop).
When using the ProPEX ring with stop, slide the ring on the tubing with the chamfered edge first until the end of the tubing contacts the stop edge. Expand the
tubing and ring. If using the ProPEX Manual Expander Tool, rotate the tool a quarter turn after each expansion to prevent the formation of grooves. Remove the
expansion tool and fully seat the tubing and ring against the shoulder of the fitting. Make ProPEX connections at temperatures above 5°F/-15°C. For more
information, refer to the Uponor ProPEX Connections Instructional Guide.
Listings2
cNSFus-fs3; cNSFus-pw; cNSFus-rfh; cQAIus; UL; CSA; PPI TR-4; ICC-ES; IAPMO; BMEC; CCMC; cQAIus P321
Codes
ICC; IPC; IMC; IRC; UPC; UMC; NSPC; HUD; UFGS; NPC of Canada; NBC of Canada
Standards
ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; ASTM
E814/ULC S115; CSA B137.5; CSA B214; UL 18213; ULC/ORD-C199P3
Related applications Contact information
AquaSAFE fire safety systems
Hydronic radiant heating and cooling systems
Snow melting systems
Turf conditioning systems
Permafrost prevention systems
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: 800.321.4739
Fax: 952.891.2008
uponorpro.com
Uponor Ltd.
6510 Kennedy Road
Mississauga, ON L5T 2X4 CANADA
Phone: 888.994.7726
Fax: 800.638.9517
uponorpro.com
1ProPEX® is a registered trademark of Uponor, Inc. ProPEX™ is a trademark of Uponor Ltd.
ProPEX® Engineered Polymer (EP) Tee
Submittal information
Project information
Technical data
Product information and application use
ProPEX® engineered polymer (EP) tees make diverting connections for Uponor crosslinked
polyethylene (PEX-a) tubing for use in hot and cold domestic potable water systems,
residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each
end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX® or Wirsbo hePEX™ tubing.1
Note: Branch size is listed last in the part descriptions.
Description Part
number A B Weight
Equivalent
length (ft.) length (ft.) Cv
through
Cv
branch
ProPEX EP Tee, ½" PEX x ½" PEX x ½" PEX
ProPEX EP Tee, ¾" PEX x ¾" PEX x ¾" PEX*
ProPEX EP Tee, 1" PEX x 1" PEX x 1" PEX*
ProPEX EP Tee, 1¼" PEX x 1¼" PEX x 1¼" PEX*
ProPEX EP Tee, 1½" PEX x 1½" PEX x 1½" PEX
ProPEX EP Tee, 2" PEX x 2" PEX x 2" PEX
ProPEX EP Tee, 2½" PEX x 2½" PEX x 2½" PEX
Q4757575
Q4751010
Q4751313
Q4751515
Q4752000
Q4752500
3.30"
4.10"
4.80"
5.80"
7.45"
10.56"
1.94"
2.47"
3.22"
3.82"
4.79"
5.45"
0.05 lbs.
0.07 lbs.
0.15 lbs.
0.25 lbs.
0.38 lbs.
1.14 lbs.
1.5
1.3
3.8
1.8
0.8
2.7
15.6
12.7
8.6
10.6
15.5
22.3
15.7
30.5
34.0
63.7
150.7
197.2
5.4
11.3
23.9
31.0
52.5
81.5
Installation
Use the appropriate ProPEX Ring for PEX-a tubing. Refer to the Uponor Professional Plumbing Installation Guide, AquaSAFE™ Residential Fire Sprinkler Installation
Guide or Uponor Radiant Installation Handbook for additional information.
Standards
ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61
Codes
IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC
Listings
cNSFus-pw; *cNSFus-pw-fs; cQAIus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code
Related applications Contact information
Hydronic radiant heating and cooling systems
Snow and ice melting systems
Turf conditioning systems
Permafrost prevention systems
AquaSAFE™ fire safety systems
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: 800.321.4739
Fax: 952.891.2008
uponorpro.com
Uponor Ltd.
6510 Kennedy Road
Mississauga, ON L5T 2X4 CANADA
Phone: 888.994.7726
Fax: 800.638.9517
uponorpro.com
1ProPEX® is a registered trademark of Uponor Inc. ProPEX™ is a trademark of Uponor Ltd.
ProPEX® Engineered Polymer (EP) Reducing Tee (up to 1½")
Submittal information
Project information
Technical data
Product information and application use
domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each
end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX® or Wirsbo hePEX™
1 Note:
Description Part
number A B Weight Equiv. length (ft.)
through
Equiv. length
(ft.) branch
Cv
v
ProPEX EP Reducing Tee, ½" PEX x ½" PEX x ¾" PEX Q4755575 2.86" 1.76" 0.03 lbs. 1.0 15.6 7.7 5.4
ProPEX EP Reducing Tee, ¾" PEX x ½" PEX x ½" PEX Q4757555 3.10" 1.70" 0.04 lbs. 3.5 6.4 4.6 3.4
ProPEX EP Reducing Tee, ¾" PEX x ¾" PEX x ⅝" PEX
ProPEX EP Reducing Tee, ¾" PEX x ¾" PEX x ½" PEX* Q4757550 3.30" 1.70" 0.04 lbs. 2.0 7.6 14.2 3.1
ProPEX EP Reducing Tee, ¾" PEX x ¾" PEX x 1" PEX* Q4757710 3.64" 2.32" 0.08 lbs. 1.5 5.7 15.7 8.7
ProPEX EP Reducing Tee, 1" PEX x ¾" PEX x ¾" PEX* Q4751775 3.90" 2.24" 0.08 lbs. 2.4 16.7 12.8 5.3
ProPEX EP Reducing Tee, 1" PEX x ¾" PEX x 1" PEX* Q4751751 3.90" 2.47" 0.08 lbs. 2.4 15.1 12.9 10.5
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x ¾" PEX* Q4751175 4.10" 2.24" 0.09 lbs. 1.7 6.4 27.8 8.2
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 1 ¼" PEX* Q4751113 4.38" 2.95" 0.13 lbs. 6.52 5.37 15.0 28.0
ProPEX EP Reducing Tee, 1¼" PEX x ¾" PEX x 1¼" PEX* Q4751373 4.61" 2.88" 0.13 lbs. 2.74 11.91 18.8 12.0
ProPEX EP Reducing Tee, 1¼" PEX x 1" PEX x ¾" PEX* Q4751317 4.50" 2.73" 0.11 lbs. 3.4 5.2 21.0 9.3
ProPEX EP Reducing Tee, 1¼" PEX x 1¼" PEX x ¾" PEX* Q4751337 4.70" 2.73" 0.13 lbs. 2.3 5.7 43.4 8.9
ProPEX EP Reducing Tee, 1¼" PEX x 1¼" PEX x 1" PEX* Q4751331 5.00" 2.97" 0.14 lbs. 4.2 6.3 33.0 15.8
ProPEX EP Reducing Tee, 1½" PEX x 1" PEX x ¾" PEX Q4751517 5.25" 3.06" 0.17 lbs. 4.0 5.1 19.5 9.3
ProPEX EP Reducing Tee, 1½" PEX x 1" PEX x 1" PEX Q4751511 5.25" 3.30" 0.18 lbs. 4.3 6.5 18.9 15.6
ProPEX EP Reducing Tee, 1½" PEX x 1¼" PEX x 1" PEX Q4751531 5.50" 2.85" 0.19 lbs. 3.1 13.1 36.4 11.2
ProPEX EP Reducing Tee, 1½" PEX x 1¼" PEX x 1¼" PEX Q4751533 5.50" 3.15" 0.21 lbs. 2.0 17.7 45.4 17.0
ProPEX EP Reducing Tee, 1½" PEX x 1½" PEX x 1" PEX Q4751551 5.75" 3.30" 0.21 lbs. 3.1 6.9 53.8 15.3
Installation
Standards Codes Listings
ASTM F877; ASTM F1960;
NSPC; UMC; UPC ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code
Related applications Contact information
Hydronic radiant heating and cooling systems
Snow and ice melting systems
Turf conditioning systems
Permafrost prevention systems
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: 800.321.4739
Fax: 952.891.2008
6510 Kennedy Road
Mississauga, ON L5T 2X4 CANADA
Phone: 888.994.7726
Fax: 800.638.9517
1ProPEX® is a registered trademark of Uponor, Inc. ProPEX™ is a trademark of Uponor Ltd.
ProPEX® Engineered Polymer (EP) Elbow
Submittal information
Project information
Technical data
pressure): 320°F (160°C)
Product information and application use
ProPEX® engineered polymer (EP) elbows make 90-degree connections for Uponor
crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic potable water
systems, residential fire safety and hydronic radiant heating and cooling systems. Each end
of the elbow is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX® or Wirsbo hePEX™ tubing.1
Description Part number A B Weight Equivalent
length (ft.)Cv
ProPEX EP Elbow, ¾" PEX x ¾" PEX*
ProPEX EP Elbow, 1" PEX x 1" PEX*
ProPEX EP Elbow, 1¼" PEX x 1¼" PEX*
ProPEX EP Elbow, 1½" PEX x 1½" PEX
ProPEX EP Elbow, 2" PEX x 2" PEX
ProPEX EP Elbow, 2½" PEX x 2½" PEX
ProPEX EP Elbow, 3" PEX x 3" PEX
ProPEX EP 45 Elbow, 1½" PEX x 1½" PEX
ProPEX EP 45 Elbow, 2" PEX x 2" PEX
ProPEX EP 45 Elbow, 2½" PEX x 2½" PEX
ProPEX EP 45 Elbow, 3" PEX x 3" PEX
Q4760750
Q4761000
Q4761250
Q4761500
Q4762000
Q4762500
Q4763000
Q4761515
Q4762020
Q4762525
Q4763030
1.60"
2.10"
2.45"
2.77"
3.76"
4.93"
5.88"
2.32"
2.91"
3.83"
4.48"
1.60"
2.10"
2.45"
2.77"
3.76"
4.93"
5.88"
2.32"
2.91"
3.83"
4.48"
0.03 lbs.
0.07 lbs.
0.11 lbs.
0.18 lbs.
0.30 lbs.
0.85 lbs.
1.44 lbs.
0.13 lbs.
0.32 lbs.
0.65 lbs.
1.07 lbs.
10.8
11.5
10.0
11.5
17.1
20.0
23.2
9.3
8.8
7.0
8.3
6.7
11.9
22.2
29.7
50.2
86.0
125.0
33.1
68.9
136.8
195.5
Installation
Standards
ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61
Codes
IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC
Listings
cNSFus-pw; *cNSFus-pw-fs; cQAIus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code
Related applications Contact information
Hydronic radiant heating and cooling systems
Snow and ice melting systems
Turf conditioning systems
Permafrost prevention systems
AquaSAFE fire safety systems
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: 800.321.4739
Fax: 952.891.2008
uponorpro.com
Uponor Ltd.
6510 Kennedy Road
Mississauga, ON L5T 2X4 CANADA
Phone: 888.994.7726
Fax: 800.638.9517
uponorpro.com
ProPEX® Fire Sprinkler Adapter
Submittal Information
Revision B: March 17, 2009
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer’s Representative: Approved By:
Technical Data
Material: 300 Series Stainless Steel
Product Information and Application Use
Use the ProPEX® Fire Sprinkler Adapter in conjunction with the
appropriate sprinkler to provide a multi-purpose residential fire
sprinkler system1. For residential applications, the system is
installed with the cold-potable portion of the Uponor plumbing
system. Make connections with Uponor ProPEX fittings. These
fittings are designed for use only with ¾" or 1" AquaPEX®
White tubing in the Uponor AQUASAFE® Looped System.
9 Description Part
Number A B C D E Weight
ProPEX Fire Sprinkler Adapter, ¾" PEX x ½" FNPT Q7517550 0.75" 1.88" 2.50" 1.82" 1.41" 0.268 lbs.
ProPEX Fire Sprinkler Adapter, 1" PEX x ½" FNPT Q7511050 0.75" 1.88" 2.50" 2.06" 1.54" 0.408 lbs.
Installation
Use appropriate ProPEX Ring for connecting the tubing. Refer to the AquaPEX Installation Handbook or the Uponor AQUASAFE®
Installation Guide for additional information.
Standards
CAN/CSA B137.5; ASTM F877; ASTM F 1960
Codes
IPC; UPC; NSPC; IRC; IMC; NPC of Canada
Listings
ANSI/NSF 14- and 61-certified; U.P. Code; ICC ESR 1099; HUD MR 1269; UL 1821; ULC/ORD - C 199 P
Related Applications Contact Information
PEX-a Plumbing Systems
AQUASAFE Fire Safety Systems
Uponor, Inc.
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: (800) 321-4739
Fax: (952) 891-2008
www.uponor-usa.com
Uponor Ltd.
2000 Argentia Rd., Plaza 1, Ste. 200
Mississauga, ON L5N 1W1 CANADA
Phone: (888) 994-7726
Fax: (800) 638-9517
www.uponor.ca
1ProPEX® is a registered trademark of Uponor, Inc. ProPEX™ is a trademark of Uponor Ltd.
A-PEX Design Services Inc.
sales@a-pexdesignservices.com
11112 47th Avenue West
Mukilteo, WA 98275
425-493-9680
Job Name : GILMAN WALK - PLAN ALKI - One Head Calculation (H.13)
Drawing : RESIDENTIAL
Location : ARLINGTON WA 98223
Remote Area : 1
Contract : 220118-02
Data File : Gilman Walk - Plan Alki.wx1
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 1
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13) Date 1/24/2022
HYDRAULIC DESIGN INFORMATION SHEET
Name - GILMAN WALK - PLAN ALKI Date - 01-18-2022
Location - ARLINGTON WA 98223
Building - RESIDENTIAL System No. - 1
Contractor - NW CUSTOM PLUMBING Contract No. - 220118-02
Calculated By - LIBBY BABB Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - RESIDENTIAL
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: (X)1 ( )2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 17 Gpm System Type
Listed Pres. at Start Point - 12.03Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 18 x 18 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model LL-RFC49
I Elevation at Highest Outlet - 116 Feet Size 3/8 K-Factor 4.9
G Note: Temperature Rating 155
N
Calculation Gpm Required 17 Psi Required 45.8 At Ref Pt STR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data:
A Date of Test - Rated Cap.
T Time of Test - @ Psi
E Static (Psi) - 90 Elev.
R Residual (Psi) - 20 Other
Flow (Gpm) - 500
S Elevation - 100
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 2
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13)Date 1/24/2022
10
20
30
40
E 50
R 60
U 70
S 80
S 90
E 100
R 110
P 120
130
140
150
50 100 150 200 250 300 350 400 450
FLOW ( N ^ 1.85 )
City Water Supply:Demand:
C1
C2
C1 - Static Pressure : 90
C2 - Residual Pressure: 20
C2 - Residual Flow : 500
D1 - Elevation : 6.930
D2 - System Flow : 16.995
D2 - System Pressure : 45.798
Hose ( Demand ) : _______
D3 - System Demand : 16.995
Safety Margin : 44.068
D1
D2
Water Supply Curve C
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 3
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13)Date 1/24/2022
Fitting Legend
Abbrev. Name
E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
G Generic Gate Valve 1 1 1 1 1 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Utb * Aquapex Tee - Branch 2 17 14 9 12 17 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Utr * Aquapex Tee - Run 1 2 2 4 2 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Fittings Used Summary
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 4
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13) Date 1/24/2022
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
STR 90.0 20 500.0 89.866 17.0 45.798
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
H.13 116.0 4.9 12.03 17.0
H.11 116.0 12.41
T.22 116.0 12.83
T.19 116.0 13.11
T.20 108.0 17.87
S.1 104.0 19.92
PRV 100.0 28.89
MTR 100.0 43.38
STR 100.0 45.8
H.14 116.0 12.39
T.25 116.0 12.93
T.23 108.0 17.26
T.21 108.0 17.85
H.10 116.0 12.95
H.8 116.0 13.01
H.7 116.0 13.07
T.17 116.0 13.09
H.3 116.0 13.13
T.16 116.0 13.17
T.15 108.0 17.25
H.1 108.0 17.38
H.5 108.0 17.53
T.18 116.0 13.13
H.4 116.0 13.15
H.2 108.0 17.25
H.6 108.0 17.25
H.9 108.0 17.25
T.24 108.0 17.25
H.12 108.0 17.26
Flow Summary - NFPA 2007
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 5
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13) Date 1/24/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
H.13 116 4.90 8.60 1 Utr 2.0 6.000 150 12.030
to 0.0 2.000 0.0
H.11 116 8.6 0.862 0.0 8.000 0.0470 0.376 Vel = 4.73
H.11 116 0.0 1 Utr 2.0 7.000 150 12.406
to 0.0 2.000 0.0
T.22 116 8.6 0.862 0.0 9.000 0.0471 0.424 Vel = 4.73
T.22 116 0.0 1 Utr 2.0 4.000 150 12.830
to 0.0 2.000 0.0
T.19 116 8.6 0.862 0.0 6.000 0.0470 0.282 Vel = 4.73
T.19 116 -1.76 1 2Utb 34.0 14.000 150 13.112
to 0.0 28.000 3.465
T.20 108 6.84 0.862 0.0 42.000 0.0308 1.294 Vel = 3.76
T.20 108 10.16 1.5 Utr 2.0 6.000 150 17.871
to T 3.443 5.443 1.732
S.1 104 17.0 1.244 0.0 11.443 0.0278 0.318 Vel = 4.49
S.1 104 0.0 1.5 2E 3.443 5.000 150 19.921
to 0.0 3.443 8.732 * * Fixed Loss = 7
PRV 100 17.0 1.244 0.0 8.443 0.0278 0.235 Vel = 4.49
PRV 100 0.0 1.5 2E 12.089 50.000 150 28.888
to 0.0 12.089 14.000 * * Fixed Loss = 14
MTR 100 17.0 1.61 0.0 62.089 0.0079 0.491 Vel = 2.68
MTR 100 0.0 1 E 2.336 20.000 150 43.379
to T 5.841 9.345 0.0
STR 100 17.0 0.995 G 1.168 29.345 0.0824 2.419 Vel = 7.01
0.0
STR 17.00 45.798 K Factor = 2.51
H.13 116 8.39 1 0.0 8.000 150 12.030
to 0.0 0.0 0.0
H.14 116 8.39 0.862 0.0 8.000 0.0449 0.359 Vel = 4.61
H.14 116 0.0 1 Utr 2.0 10.000 150 12.389
to 0.0 2.000 0.0
T.25 116 8.39 0.862 0.0 12.000 0.0450 0.540 Vel = 4.61
T.25 116 -2.90 1 2Utb 34.0 14.000 150 12.929
to 0.0 28.000 3.465
T.23 108 5.49 0.862 0.0 42.000 0.0205 0.861 Vel = 3.02
T.23 108 0.21 1 Utr 2.0 11.000 150 17.255
to Utb 17.0 16.000 0.0
T.21 108 5.7 0.862 0.0 27.000 0.0220 0.594 Vel = 3.13
T.21 108 4.45 1.5 0.0 2.000 150 17.849
to 0.0 0.0 0.0
T.20 108 10.15 1.244 0.0 2.000 0.0110 0.022 Vel = 2.68
0.0
T.20 10.15 17.871 K Factor = 2.40
T.25 116 2.90 1 Utr 2.0 2.000 150 12.929
to 0.0 2.000 0.0
H.10 116 2.9 0.862 0.0 4.000 0.0062 0.025 Vel = 1.59
H.10 116 0.0 1 Utr 2.0 7.000 150 12.954
to 0.0 2.000 0.0
H.8 116 2.9 0.862 0.0 9.000 0.0062 0.056 Vel = 1.59
Final Calculations - Hazen-Williams - 2007
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 6
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13) Date 1/24/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
H.8 116 0.0 1 Utr 2.0 7.000 150 13.010
to 0.0 2.000 0.0
H.7 116 2.9 0.862 0.0 9.000 0.0063 0.057 Vel = 1.59
H.7 116 0.0 1 Utr 2.0 1.000 150 13.067
to 0.0 2.000 0.0
T.17 116 2.9 0.862 0.0 3.000 0.0063 0.019 Vel = 1.59
T.17 116 0.0 1 Utr 2.0 5.000 150 13.086
to 0.0 2.000 0.0
H.3 116 2.9 0.862 0.0 7.000 0.0063 0.044 Vel = 1.59
H.3 116 0.0 1 Utr 2.0 4.000 150 13.130
to 0.0 2.000 0.0
T.16 116 2.9 0.862 0.0 6.000 0.0062 0.037 Vel = 1.59
T.16 116 1.76 1 2Utb 34.0 13.000 150 13.167
to 0.0 28.000 3.465
T.15 108 4.66 0.862 0.0 41.000 0.0151 0.620 Vel = 2.56
T.15 108 -0.21 1 Utr 2.0 7.000 150 17.252
to 0.0 2.000 0.0
H.1 108 4.45 0.862 0.0 9.000 0.0139 0.125 Vel = 2.45
H.1 108 0.0 1 Utr 2.0 9.000 150 17.377
to 0.0 2.000 0.0
H.5 108 4.45 0.862 0.0 11.000 0.0139 0.153 Vel = 2.45
H.5 108 0.0 1 Utb 17.0 9.000 150 17.530
to 0.0 14.000 0.0
T.21 108 4.45 0.862 0.0 23.000 0.0139 0.319 Vel = 2.45
0.0
T.21 4.45 17.849 K Factor = 1.05
T.19 116 1.76 1 Utr 2.0 6.000 150 13.112
to 0.0 2.000 0.0
T.18 116 1.76 0.862 0.0 8.000 0.0025 0.020 Vel = 0.97
T.18 116 0.0 1 Utr 2.0 6.000 150 13.132
to 0.0 2.000 0.0
H.4 116 1.76 0.862 0.0 8.000 0.0025 0.020 Vel = 0.97
H.4 116 0.0 1 Utr 2.0 4.000 150 13.152
to 0.0 2.000 0.0
T.16 116 1.76 0.862 0.0 6.000 0.0025 0.015 Vel = 0.97
0.0
T.16 1.76 13.167 K Factor = 0.49
T.15 108 0.21 1 Utr 2.0 6.000 150 17.252
to 0.0 2.000 0.0
H.2 108 0.21 0.862 0.0 8.000 0.0001 0.001 Vel = 0.12
H.2 108 0.0 1 Utr 2.0 9.000 150 17.253
to 0.0 2.000 0.0
H.6 108 0.21 0.862 0.0 11.000 0 0.0 Vel = 0.12
H.6 108 0.0 1 Utr 2.0 10.000 150 17.253
to 0.0 2.000 0.0
H.9 108 0.21 0.862 0.0 12.000 0.0001 0.001 Vel = 0.12
H.9 108 0.0 1 Utr 2.0 4.000 150 17.254
to 0.0 2.000 0.0
T.24 108 0.21 0.862 0.0 6.000 0 0.0 Vel = 0.12
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 7
GILMAN WALK - PLAN ALKI - One Head Calculation (H.13) Date 1/24/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
T.24 108 0.0 1 Utr 2.0 8.000 150 17.254
to 0.0 2.000 0.0
H.12 108 0.21 0.862 0.0 10.000 0.0001 0.001 Vel = 0.12
H.12 108 0.0 1 0.0 12.000 150 17.255
to 0.0 0.0 0.0
T.23 108 0.21 0.862 0.0 12.000 0 0.0 Vel = 0.12
0.0
T.23 0.21 17.255 K Factor = 0.05
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.
sales@a-pexdesignservices.com
11112 47th Avenue West
Mukilteo, WA 98275
425-493-9680
Job Name : GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10)
Drawing : RESIDENTIAL
Location : ARLINGTON WA 98223
Remote Area : 1
Contract : 220118-02
Data File : Gilman Walk - Plan Alki.wx2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 1
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10) Date 1/24/2022
HYDRAULIC DESIGN INFORMATION SHEET
Name - GILMAN WALK - PLAN ALKI Date - 01-18-2022
Location - ARLINGTON WA 98223
Building - RESIDENTIAL System No. - 1
Contractor - NW CUSTOM PLUMBING Contract No. - 220118-02
Calculated By - LIBBY BABB Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - RESIDENTIAL
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7.04 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model LL-RFC49
I Elevation at Highest Outlet - 116 Feet Size 3/8 K-Factor 4.9
G Note: Temperature Rating 155
N
Calculation Gpm Required 26.0394 Psi Required 46.69 At Ref Pt STR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data:
A Date of Test - Rated Cap.
T Time of Test - @ Psi
E Static (Psi) - 90 Elev.
R Residual (Psi) - 20 Other
Flow (Gpm) - 500
S Elevation - 100
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 2
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10)Date 1/24/2022
10
20
30
40
E 50
R 60
U 70
S 80
S 90
E 100
R 110
P 120
130
140
150
50 100 150 200 250 300 350 400 450
FLOW ( N ^ 1.85 )
City Water Supply:Demand:
C1
C2
C1 - Static Pressure : 90
C2 - Residual Pressure: 20
C2 - Residual Flow : 500
D1 - Elevation : 6.930
D2 - System Flow : 26.039
D2 - System Pressure : 46.692
Hose ( Demand ) : _______
D3 - System Demand : 26.039
Safety Margin : 43.012
D1
D2
Water Supply Curve C
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 3
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10)Date 1/24/2022
Fitting Legend
Abbrev. Name
E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
G Generic Gate Valve 1 1 1 1 1 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Utb * Aquapex Tee - Branch 2 17 14 9 12 17 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Utr * Aquapex Tee - Run 1 2 2 4 2 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Fittings Used Summary
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 4
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10) Date 1/24/2022
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
STR 90.0 20 500.0 89.704 26.04 46.692
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
H.7 116.0 4.9 7.04 13.0
T.17 116.0 7.28
H.3 116.0 7.82
T.16 116.0 8.3
T.15 108.0 13.15
H.1 108.0 13.45
H.5 108.0 13.8
T.21 108.0 14.55
T.20 108.0 14.6
S.1 104.0 17.04
PRV 100.0 26.28
MTR 100.0 41.37
STR 100.0 46.69
H.8 116.0 7.06
H.10 116.0 4.9 7.08 13.04
T.25 116.0 7.59
T.23 108.0 13.16
H.14 116.0 7.86
H.13 116.0 8.04
H.11 116.0 8.22
T.22 116.0 8.43
T.19 116.0 8.56
H.4 116.0 8.37
T.18 116.0 8.46
H.2 108.0 13.15
H.6 108.0 13.15
H.9 108.0 13.15
T.24 108.0 13.15
H.12 108.0 13.15
Flow Summary - NFPA 2007
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 5
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10) Date 1/24/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
H.7 116 4.90 11.34 1 Utr 2.0 1.000 150 7.040
to 0.0 2.000 0.0
T.17 116 11.34 0.862 0.0 3.000 0.0783 0.235 Vel = 6.23
T.17 116 0.0 1 Utr 2.0 5.000 150 7.275
to 0.0 2.000 0.0
H.3 116 11.34 0.862 0.0 7.000 0.0786 0.550 Vel = 6.23
H.3 116 0.0 1 Utr 2.0 4.000 150 7.825
to 0.0 2.000 0.0
T.16 116 11.34 0.862 0.0 6.000 0.0785 0.471 Vel = 6.23
T.16 116 -4.13 1 2Utb 34.0 13.000 150 8.296
to 0.0 28.000 3.465
T.15 108 7.21 0.862 0.0 41.000 0.0340 1.392 Vel = 3.96
T.15 108 -0.16 1 Utr 2.0 7.000 150 13.153
to 0.0 2.000 0.0
H.1 108 7.05 0.862 0.0 9.000 0.0326 0.293 Vel = 3.88
H.1 108 0.0 1 Utr 2.0 9.000 150 13.446
to 0.0 2.000 0.0
H.5 108 7.05 0.862 0.0 11.000 0.0325 0.358 Vel = 3.88
H.5 108 0.0 1 Utb 17.0 9.000 150 13.804
to 0.0 14.000 0.0
T.21 108 7.05 0.862 0.0 23.000 0.0326 0.749 Vel = 3.88
T.21 108 9.06 1.5 0.0 2.000 150 14.553
to 0.0 0.0 0.0
T.20 108 16.11 1.244 0.0 2.000 0.0250 0.050 Vel = 4.25
T.20 108 9.93 1.5 Utr 2.0 6.000 150 14.603
to T 3.443 5.443 1.732
S.1 104 26.04 1.244 0.0 11.443 0.0612 0.700 Vel = 6.87
S.1 104 0.0 1.5 2E 3.443 5.000 150 17.035
to 0.0 3.443 8.732 * * Fixed Loss = 7
PRV 100 26.04 1.244 0.0 8.443 0.0612 0.517 Vel = 6.87
PRV 100 0.0 1.5 2E 12.089 50.000 150 26.284
to 0.0 12.089 14.000 * * Fixed Loss = 14
MTR 100 26.04 1.61 0.0 62.089 0.0174 1.082 Vel = 4.10
MTR 100 0.0 1 E 2.336 20.000 150 41.366
to T 5.841 9.345 0.0
STR 100 26.04 0.995 G 1.168 29.345 0.1815 5.326 Vel = 10.74
0.0
STR 26.04 46.692 K Factor = 3.81
H.7 116 1.66 1 Utr 2.0 7.000 150 7.040
to 0.0 2.000 0.0
H.8 116 1.66 0.862 0.0 9.000 0.0022 0.020 Vel = 0.91
H.8 116 0.0 1 Utr 2.0 7.000 150 7.060
to 0.0 2.000 0.0
H.10 116 1.66 0.862 0.0 9.000 0.0022 0.020 Vel = 0.91
H.10 116 4.90 13.04 1 Utr 2.0 2.000 150 7.080
to 0.0 2.000 0.0
T.25 116 14.7 0.862 0.0 4.000 0.1268 0.507 Vel = 8.08
T.25 116 -5.80 1 2Utb 34.0 14.000 150 7.587
to 0.0 28.000 3.465
T.23 108 8.9 0.862 0.0 42.000 0.0501 2.103 Vel = 4.89
Final Calculations - Hazen-Williams - 2007
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 6
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10) Date 1/24/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
T.23 108 0.16 1 Utr 2.0 11.000 150 13.155
to Utb 17.0 16.000 0.0
T.21 108 9.06 0.862 0.0 27.000 0.0518 1.398 Vel = 4.98
0.0
T.21 9.06 14.553 K Factor = 2.37
T.25 116 5.80 1 Utr 2.0 10.000 150 7.587
to 0.0 2.000 0.0
H.14 116 5.8 0.862 0.0 12.000 0.0227 0.272 Vel = 3.19
H.14 116 0.0 1 0.0 8.000 150 7.859
to 0.0 0.0 0.0
H.13 116 5.8 0.862 0.0 8.000 0.0228 0.182 Vel = 3.19
H.13 116 0.0 1 Utr 2.0 6.000 150 8.041
to 0.0 2.000 0.0
H.11 116 5.8 0.862 0.0 8.000 0.0226 0.181 Vel = 3.19
H.11 116 0.0 1 Utr 2.0 7.000 150 8.222
to 0.0 2.000 0.0
T.22 116 5.8 0.862 0.0 9.000 0.0227 0.204 Vel = 3.19
T.22 116 0.0 1 Utr 2.0 4.000 150 8.426
to 0.0 2.000 0.0
T.19 116 5.8 0.862 0.0 6.000 0.0227 0.136 Vel = 3.19
T.19 116 4.13 1 2Utb 34.0 14.000 150 8.562
to 0.0 28.000 3.465
T.20 108 9.93 0.862 0.0 42.000 0.0613 2.576 Vel = 5.46
0.0
T.20 9.93 14.603 K Factor = 2.60
T.16 116 4.13 1 Utr 2.0 4.000 150 8.296
to 0.0 2.000 0.0
H.4 116 4.13 0.862 0.0 6.000 0.0120 0.072 Vel = 2.27
H.4 116 0.0 1 Utr 2.0 6.000 150 8.368
to 0.0 2.000 0.0
T.18 116 4.13 0.862 0.0 8.000 0.0121 0.097 Vel = 2.27
T.18 116 0.0 1 Utr 2.0 6.000 150 8.465
to 0.0 2.000 0.0
T.19 116 4.13 0.862 0.0 8.000 0.0121 0.097 Vel = 2.27
0.0
T.19 4.13 8.562 K Factor = 1.41
T.15 108 0.16 1 Utr 2.0 6.000 150 13.153
to 0.0 2.000 0.0
H.2 108 0.16 0.862 0.0 8.000 0 0.0 Vel = 0.09
H.2 108 0.0 1 Utr 2.0 9.000 150 13.153
to 0.0 2.000 0.0
H.6 108 0.16 0.862 0.0 11.000 0.0001 0.001 Vel = 0.09
H.6 108 0.0 1 Utr 2.0 10.000 150 13.154
to 0.0 2.000 0.0
H.9 108 0.16 0.862 0.0 12.000 0 0.0 Vel = 0.09
H.9 108 0.0 1 Utr 2.0 4.000 150 13.154
to 0.0 2.000 0.0
T.24 108 0.16 0.862 0.0 6.000 0 0.0 Vel = 0.09
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A-PEX Design Services Inc.Page 7
GILMAN WALK - PLAN ALKI - Two Head Calculation (H.7 & H.10) Date 1/24/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
T.24 108 0.0 1 Utr 2.0 8.000 150 13.154
to 0.0 2.000 0.0
H.12 108 0.16 0.862 0.0 10.000 0 0.0 Vel = 0.09
H.12 108 0.0 1 0.0 12.000 150 13.154
to 0.0 0.0 0.0
T.23 108 0.16 0.862 0.0 12.000 0.0001 0.001 Vel = 0.09
0.0
T.23 0.16 13.155 K Factor = 0.04
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
PLAN REVIEW FEE PERMIT FEE PRO/TECH FEE TOTALS %
SF Const Type # of heads Valuation
1358 VB 88.16$ 450.00$ 538.16$ 22.55%
14 heads
1358 VB 88.16$ 450.00$ 538.16$ 22.55%
14 heads
1520 VB 101.14$ 450.00$ 25.00$ 576.14$ 25.87%
13 heads
1719 VB 113.50$ 450.00$ 563.50$ 29.03%
16 heads
Total Valuation 4597 25,248.13$ 390.96$ 1,800.00$ 25.00$ 2,215.96$ 100%
390.96$ DUE AT TIME OF SUBMITTAL
TOTAL FEES 2,215.96$
1,825.00$ DUE AT PERMIT ISSUANCE
FOURPLEX
PERMIT FEES
GILMAN WALK FOURPLEX FIRE PERMIT FEES