HomeMy WebLinkAbout19223 68th Dr Ne_BLD2926_2025
Permit #: 2926
Permit Date: 12/09/19
Permit Type: FIRE ALARM
Project Name: R&L Carriers
Applicant Name: Olympic Security & Communication
Applicant Address: PO Box 3559
Applicant, City, State, Zip: Arlington, WA 98223
Contact: Vikki Ryason
Phone: 360-652-1088
Email: vikki@olympicsecurity.com
Scope of Work: New Fire Alarm
Valuation: 25000.00
Square Feet: 0
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 03/11/2020
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Raelynn Jones
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
31051400302900 19223 68th Drive NE SEC 14 TWP 31 RGE 05 RLR
TH PTN OF SW1/4 BEING INVESTMENTS
A PTN OF LOTS 3,5,6,9,10 LLC
& 11 OF SURV REC AF
NO 7905290175 DAF COM
AT SELY COR LOT 21 OF
SD SURV TH S79*55 47E
ALG N LN LOT 3 OF SD
SURV 60FT TH S10*04
13W102.20FT TO TPB TH
N46*01 15E 315.12FT TH
N10*04 13E 97.97FT TH
S79*55 47E 530.50FT TH
S10*04 13W 572.10FT TH
N88*50 41W 728.21FT TO
BEG OF CRV TO R
WHOSE RAD CTR BEARS
N01*09 19E 30FT TH ALG
ARC OFSD CRV TO R
66.92FT THRU A C/A OF
127*47 59 TO THE BEG
OF REV CRV TO L
WHOSE RAD CTR BEARS
N51*02 42W 280FT TH
ALG ARC OF SD REV
CRV TO L 141.16FT THRU
A C/A OF 28*53 05 TAP TH
BEARS S10*04 13W FR
TPB TH N10*04 13E
152.50FT TO TPB PER
BLA REC AF NO
9009260178
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
CONSTRUCTION Labor &
OLYMPIC SECURITY 360-652-1088 PO BOX 3559 OLYMPSC012QP
CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
12/09/2019 FIRE ALARM BUILDING
1. Permit and set of approved plans to remain on site
during installation. Installers shall present NICET II
certification upon request.
2. Battery load test required, switch system to battery
operation 24-hours prior to final inspection. Notification
appliances to operate for 5 minutes on battery power.
3. Trouble condition to be verified for initiation,
notification and signaling circuits.
4. WP horn strobe installed on exterior of office/terminal
12/09/2019 FIRE ALARM FIRE
building to be set at 75 cd.
5. Furnish a written statement to the Arlington Fire
Department stating that the system has been installed in
accordance with the approved plans and tested in
accordance with the manufacturer’s published instructions
and appropriate NFPA requirements prior to scheduling an
inspection (NFPA 72 Section 7.5.2).
6. The record of completion form shall be submitted prior
to project close-out.
Fees
Fee Description Notes Amount
Fire Alarm Plan Review Fee $100.00
Fire Sprinkler System Commercial NFPA 13/13R $373.72
Processing/Technology $25.00
Credit Card Service $14.96
Total $513.68
Attached Letters
Date Letter Description
12/09/2019 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
01/27/2020 Vikki Ryason 78759763 $498.72
01/27/2020 78759763 CC Surcharge Raelynn Jones $14.96
Outstanding Balance $0.00
Notes
Date Note Created By:
12/27/2019 Revisions received. Routed to Mike for review. Raelynn Jones
Uploaded Files
Date File Name
10/11/2021 9866258-2926_IC 7.7.2020.pdf
10/11/2021 9866259-2926_IC 7.13.2020.pdf
10/11/2021 9866260-2926_IC 6.15.2020.pdf
03/11/2020 6375712-2926_Issued Permit.pdf
12/09/2019 5968241-2926_Application.pdf
12/09/2019 5968234-2926_Application.pdf