ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA001
PERMIT #: 1863 DATE: 3/4/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Dave Bufalini
Item(s) Inspected Location
Thickened Footing to Stem Wall Rebar Dowels Building Q - One Connection, Northwest Corner
Reference Drawing(s): RFI 7
Item(s) Inspected Comments
Base Material Condition Sound Concrete
Drill Bit Type Hilti Hollow Drill Bit
Hole Diameter/Depth 3/4" X 6"
Hole Cleanliness Hilti Vacuum System
Anchor Spacing/Edge Distance Per Plan
Anchor Type Grade 60 Reinforcement
Anchor Diameter/Length 5/8" X 42"
Anchor Embedment 6"
Adhesive Type Hilti Hit-HY 200
Adhesive Expiration Date 9/2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: Work was found to conform to the above referenced RFI as well as the manufacturers installation
recommendations.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA014
PERMIT #: 1857, 1858, 1863, 1862 DATE: 5/30/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Interior Wall Footing Reinforcing Steel Dowels Building K and L at Perimeter Foundation Intersections
Holdown Anchor Bolts (5/8" X 14" w/9" Embed) Building Q and P, Center Party Wall (Non-Entry Side of Wall)
Reference Drawing(s): RFI #7, Structural Drawings
Item(s) Inspected Comments
Base Material Condition Satisfactory , Dry Concrete. 57º
Drill Bit Type Carbide Tip, Rotor Hammer w/Vacuum
Hole Diameter/Depth 3/4" X 4"
Hole Cleanliness Clean - Flushed with Water Until Clear/Brushed/Flushed
Anchor Spacing/Edge Distance Per Plan
Anchor Type Grade 60 Deformed Reinforcing Steel
Anchor Diameter/Length 5/8", 44"
Anchor Embedment 4"
Adhesive Type Hilti HY200 R
Adhesive Expiration Date 9/2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the epoxied dowels.
The above dowels were found to conform with the project structural drawings and RFI #7. The dowels were
installed as recommended by the manufacturer’s published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA018
PERMIT #: 1848, 1849, 1850, 1863 DATE: 6/25/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Holdown Anchor Bolts Buildings A, B, C and O (Each End of Entry Party Walls)
Reference Drawing(s): Structural Drawings, RFI #43
Item(s) Inspected Comments
Base Material Condition Dry Fully Cured Concrete
Drill Bit Type Drilled Prior
Hole Diameter/Depth 3/4", 9"
Hole Cleanliness Blown, Brushed, Blown Clean
Anchor Spacing/Edge Distance Per Plan
Anchor Type Threaded Rod
Anchor Diameter/Length 5/8", 14"
Anchor Embedment 9"
Adhesive Type Hilti Hit HY-200 R
Adhesive Expiration Date 9/19
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The dowels were installed as per the project engineer instructions, project drawings and as recommended by
the product manufacturers published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB002
PERMIT #: 1864, 1863 DATE: 1/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Erik Fulmer
Placement Location: Clubhouse Stem Walls, Building Q
Sample Location: Second Truck, Mid Load at Approximately 15 Cubic Yards
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 7.50 20
Mix # 02550C Air Content, % (C231) NT NA
Mix Description 5.5 Sack, M9 POLY 997 Unit Weight, pcf (C138) NT NA
Truck/Ticket # C186 / 614985 Air/Mix Temp.,°F (C1064) 49 / 60 EF1
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 54/73
Quantity Placed, cy 77 Cure Method - Initial / Final Container / Water Tank
Time Batched 11:52 AM Water Added on Job, gals 5
Time Sampled 12:25 PM Water Requested by Truck Driver
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
91436 7 01-24 54260 4.01 12.63 4300 TYPE 2:
91437 28 02-14 66390 4.01 12.63 5260 TYPE 2:
91438 28 02-14 70490 4.01 12.63 5580 TYPE 2:
91439 28 02-14 71540 4.01 12.63 5660 TYPE 2:
91440 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on-site as requested to provide sampling and testing of concrete placed. Concrete was
placed via pump truck and was mechanically consolidated. AMENDED 2/15/19: Remarks regarding additional
cylinders were remove as they were not applicable.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avscommunities.com,
kolander@arlingtonwa.gov, lpeterson@arlingtonwa.gov, Matthew.Breiner@alliantcapital.com ...and 2 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB003
PERMIT #: 1862,1863 DATE: 1/24/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building Q Perimeter Stem Wall, Building P Continuous Wall Footings and Column Plinth Pads
Sample Location: 1st Load, Place at the Stem Walls on the West Half of Building Q
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.50
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5sk. 7/8", WRA, 50% HW Unit Weight, pcf (C138) NT
Truck/Ticket # C137 / 217512 Air/Mix Temp.,°F (C1064) 51 / 69 TM01
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 45/65 TM01
Quantity Placed, cy 70 Cure Method - Initial / Final Container / Moist Room
Time Batched 11:16 A.M Water Added on Job, gals 8
Time Sampled 12:10 P.M Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
91679 7 01-31 61820 4.01 12.63 4890 TYPE 2:
91680 28 02-21 74990 4.02 12.69 5910 TYPE 3:
91681 28 02-21 75190 4.02 12.69 5930 TYPE 2:
91682 28 02-21 72560 4.02 12.69 5720 TYPE 3:
91683 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: Geotest was on site as requested to inspect the concrete placement at the above
locations. The reinforcing steel was in place and was found to be in conformance with the
project structural drawings. The holdown anchor bolts were tied in place with the required
embedment at building P continuous footing and the sill plate anchor bolts at building Q were
wet set in the stem wall
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB003
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo was taken looking
west down building P north
side.
As requested by the Arlington City Inspector:
GeoTest verified that the reinforcement for Building's Q (and Building P) plinths was in place as
detailed plus the contractor has placed additional vertical dowels for larger embed ties.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB004
PERMIT #: 1862, 1863, 1860 DATE: 1/31/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building P, Stem Walls and Plinths Building Q, Plinths Building N, Perimeter Wall Footings and Plinth
Footings
Sample Location: 1st Load Placed at Building P, Stem Walls and Plinths West Half of Building
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 4.75 19
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5sk. 7/8", Pea. WRA Unit Weight, pcf (C138) NT
Truck/Ticket # C116 / 615146 Air/Mix Temp.,°F (C1064) 52 / 62 TM02
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 37/71 TM02
Quantity Placed, cy Cure Method - Initial / Final Container / Water Tank
Time Batched 11:47 A.M Water Added on Job, gals 15
Time Sampled 12:33 P.M Water Requested by Concrete Contrac
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
91861 7 02-07 54230 4.01 12.63 4290 TYPE 2:
91862 28 02-28 0 0.00 0.00 0
91863 28 02-28 0 0.00 0.00 0
91864 28 02-28 0 0.00 0.00 0
91865 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to inspect the concrete placement at the above
locations. The reinforcing steel was in place and was found to be in conformance with project
structural drawings. The concrete was placed using a boom pump and was mechanically
consolidated.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avscommunities.com,
kolander@arlingtonwa.gov, lpeterson@arlingtonwa.gov, Matthew.Breiner@alliantcapital.com ...and 2 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB004
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Photo shows the contractor
placing and consolidating the
concrete at Building P
footings.
Photo of the continuous
footing reinforcement with one
of the 'UFER' electrical
grounding bars tied to one of
the footing's continuous bars.
Two of these were installed at
the building's east end.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB007
PERMIT #: 1863 DATE: 3/4/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Placement Location: Building Q - Exterior and Interior Slabs on Grade
Sample Location: Second Truck, Mid-Pour, Directly From Chute, Exterior Slabs
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.50 9
Mix # 260A6C Air Content, % (C231) 5.5 1
Mix Description 6 SK, 7/8" Agg, Pea, MBAE 90, MB Poly 997, MB NC 534. Hot Water Unit Weight, pcf (C138) NT
Truck/Ticket # C142 / 615268 Air/Mix Temp.,°F (C1064) 29 / 49 TC1
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 25/75
Quantity Placed, cy 30 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:37 AM Water Added on Job, gals 0
Time Sampled 8:30 AM Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
92696 7 03-11 65940 4.01 12.63 5220 TYPE 2: Set 1
92697 28 04-01 78650 4.00 12.57 6260 TYPE 2: Set 1
92698 28 04-01 75600 4.00 12.57 6010 TYPE 2: Set 1
92699 28 04-01 78380 4.00 12.57 6240 TYPE 2: Set 1
92700 Hold 00-00 0 0.00 0.00 0 Set 1
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on-site as requested to provide concrete testing, inspection, and
placement observation for the above locations. Concrete was placed via pump truck for both
exterior and interior slabs on grade (two mix designs). Concrete was mechanically
consolidated and hand finished. An additional sample was taken for the second mix design for
the interior slab (Set 2).
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB007
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Sample Location: Fifth Truck, Mid-Pour, Directly from Chute, Eastern Half of Interior Slab
Field Data:
Truck/Ticket # C013 / 218555 Slump, in. (C143) 7.00
Time Batched 8:36 AM Air Content, % (C231) NT
Time Sampled 9:20 AM Unit Weight, pcf (C138) NT
Air Temperature,°F 32 Water Added on Job, gals 10
Mix Temp.°F(C1064) 61 Water Requested by Miles
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
92701 7 03-11 59430 4.01 12.63 4710 TYPE 2: Set 2
92702 28 04-01 71170 4.00 12.57 5660 TYPE 2: Set 2
92703 28 04-01 68350 4.00 12.57 5440 TYPE 2: Set 2
92704 28 04-01 69980 4.00 12.57 5570 TYPE 2: Set 2
92705 Hold 00-00 0 0.00 0.00 0 Set 2
Comments: This second set is of a different mix design meant for the interior slab on grade (Mix code: 2550C)
. Both mixes have the same compressive strength requirement. This 5.5 sack mix contained 7/8" aggregate, pea
gravel, MB Poly 997, MB NC 534, and hot water. 70 cubic yards of this mix were placed for the interior slab.
Sample Location:
Field Data:
Truck/Ticket # / Slump, in. (C143)
Time Batched Air Content, % (C231)
Time Sampled Unit Weight, pcf (C138)
Air Temperature,°F Water Added on Job, gals
Mix Temp.°F(C1064) Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB007
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Figure 1. One of Building Q's
exterior slabs on grade
following placement and hand
finishing of concrete (looking
southwest).
Figure 2. The placement and
finishing process of concrete
for Building Q's interior slab on
grade (looking west).
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB008
PERMIT #: 1848, 1850 DATE: 3/7/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Building A Stem Walls and Plinth Bases, Building C Perimeter and Plinth Footings
Sample Location: Building A Stem Wall, Northeast Quadrant
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.00 15
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 Sack 7/8" Aggregate Unit Weight, pcf (C138) NT
Truck/Ticket # C116 / 615309 Air/Mix Temp.,°F (C1064) 34 / 61 JM6
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 32/70
Quantity Placed, cy 80 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:26 AM Water Added on Job, gals 7
Time Sampled 8:15 AM Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
92810 7 03-14 56110 4.01 12.63 4440 TYPE 2:
92811 28 04-04 0 0.00 0.00 0
92812 28 04-04 0 0.00 0.00 0
92813 28 04-04 0 0.00 0.00 0
92814 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on site for inspection of concrete placed at the locations referenced
above. Verified clearances prior to placement. All items inspected were in conformance with
plans and drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB008
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Placement of Concrete
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: IR004
PERMIT #: 1863 DATE: 3/4/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Dave Bufalini
INSPECTION OF: Reinforcement - Slab-on-Grade and Thickened Footings - Building Q
GeoTest was on-site to observe the reinforcement at the above-referenced location.
Reinforcement was in-place, secure and found to conform to all applicable General Notes,
Beam Schedule, Lap Splice Schedule as well as RFI 7 and RFI 34.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF001
PERMIT #: BLD-1862, BLD-1863 DATE: 3/22/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Straps Beam to Top Plate Building P and Q, Level 1 ADA Units
Floor Diaphragm, Sheathing Building Q, Level 2
Reference Drawings: Notes on S1.1, S1.2 and S2.1.1 and Details on S5.1
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, T & G, 23/32", Exp.1
Shear wall/diaphragm length, location At Above Locations Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing See Comments .148 X *2-1/4" (Drawings Call for .148 X 3")
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Adequate
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: See comments on page 2.
AMENDED 4/19/19: GeoTest was provided with RFI 044 accepting the use of .148 x 2.25"
nails at glued down diaphragms.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF001
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
GeoTest was on site as requested to inspect the above items.
*The drawings call for the floor sheathing to be nailed using 10d common nails - .148" X 2-1/4
were used, Engineer approval pending.
MST37 strap nailed to the top
plate. For the ADA units
added support beam
connections.
Nails connecting the diaphragm sheathing to an interior
shear wall (blocking) spaced at 6" on center per plan.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF001
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
The photo was taken looking
east across Building O 2nd
level floor sheathing.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF002
PERMIT #: BLD.1862 BLD.1863 DATE: 3/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing Building P, 2nd Level
Shear Wall: Sheathing (Inspected Prior to Dens-Glass) Buildings P and Q, 1st Floor Stairway Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir 2
Structural panel grade and thickness, glue Walls: Struct. 1, 15/32", Exp.1 / Floor: Rated Sheathing, 23/32", Exp.1
Shear wall/diaphragm length, location At Above Locations Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" x 2-1/4" (Nail Size is Acceptable Per Engineer’s Email Dated 3/25/19)
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Adequate
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items mentioned above. The
items listed above were found to be in conformance with the approved drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF002
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Stairway Type SW6 Shear
Wall Sheathing
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF003
PERMIT #: 1862 & 1863 DATE: 3/27/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings P and Q, 2nd Level Stairway Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir 2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location At Above Locations Per Plan
Panel edges bear on framing members Sheathing Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Adequate
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Geotest was on site as requested to inspect the above shear walls prior to the installation of the
Dens-Glass wallboard. The sheathing and fasteners were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF004
PERMIT #: BLD-1863 DATE: 3/29/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Building Q, 2nd Level Perimeter Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir 2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Walls are Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" x 2-1/4", 6 &12"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Geotest was on site as requested to inspect the above items.
The nailing of the sheathing was in progress. The above items were being installed as detailed in the
structural drawings. A final inspection is required and GeoTest will return upon request.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF007
PERMIT #: 1862 and 1863 DATE: 4/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing and Fasteners Buildings P and Q, 3rd Level
Reference Drawings: S1.1, S1.2, S2.1.1, S2.1.2, S5.1, S5.2
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 23/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148", 2-1/4", 6" and 10"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. The third level floor
sheathing was in accordance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF007
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
This photo was taken facing
east standing on the west end
of the 3rd-floor deck
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF008
PERMIT #: 1864. 1863 DATE: 4/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Walls: Sheathing Building Q, 3rd Level Walls at the 3 Stairs
Shear Walls: Sheathing Rec. Building: Building North Walls
Diaphragm: Sheathing Rec. Building Roof
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32" . EXP.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", Per Plan & RFI #44
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the sheathing at the locations mentioned above. The
above sheathing and fasteners were found to conform with the structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF009
PERMIT #: 1848, 1860, 1861, 1862. 1863, 1864 DATE: 4/11/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Walls: Sheathing Rec. Bld. at all Shear Wall Locations Except for SW2 Wall
Shear Walls: Sheathing East Wall at Buildings N & O, West Walls at Buildings P & Q
MST37 Straps Nailed to Wall Top Plate Building A (5) Locations, ADA Units Closets
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location See Comments
Panel edges bear on framing members All Edges Were Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148", 2-1/4", Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the shear wall sheathing and straps
at the above locations.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF009
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The MST37 straps were
fastened to the wall top plate
using 148 X 2-1/2" nails.
In this picture, the door on the
left is not shown on the
structural drawings. The
contractor will reach out to the
project engineer regarding
moving the holdown location
to the other side of the door.
The sheathing and the nailing
of the sheathing at the
locations mentioned in this
report were found to be in
conformance with the
structural drawings.
The contractor plans to sheath
the interior side of the SW2
shear wall at the buildings
east side as directed by the
project structural engineer.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF012
PERMIT #: 1860, 1861, 1863 DATE: 4/18/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Building N, Level 2 Walls at Each of (3) Stair Locations
Shear Wall Sheathing Building O, Level 2 Walls at Each of (3) Stair Locations
Post Bolted Connections to Foundation Embed Building Q, 1st Level at (6) C8 Column Locations
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Walls Were Inspected Prior to Being Installed Into Building
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148, 2-1/4", 6 & 12"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Geotest was on site as requested to inspect the above items. The items inspected
were found to be in conformance with the project structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF012
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Post Connection: One of the
six columns to foundation
connections at Building Q.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF013
PERMIT #: 1848, 1863 DATE: 4/22/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing and Straps Building Q, Exterior Wall, Level 1, 2 & 3
Shear Wall Sheathing Building A, (Level 2) Walls at 3 Stairs
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location See Comments
Panel edges bear on framing members Panels Were Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates Only Exterior Side of Wall was Inspected
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", Per SW Schedule & EOR’s EMail
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Floor to Floor Straps
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
See the following page for comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF013
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo shows the north
side of building Q
The nailing of the sheathing
and the installation of the floor
to floor holdown straps at
building Q were in progress.
The contractor will schedule a
follow-up inspection when the
in-progress items are
complete.
The stair walls at the second
level of building A were per
plan.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF014
PERMIT #: 1860, 1862, 1863 DATE: 4/23/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Building N, 3rd Level Stair Walls
Shear Wall Sheathing and Straps (In Progress) Building P and Q: Levels 1, 2 & 3 Exterior Shear Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32" . EXP.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", Per Plan & RFI #44
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location In Progress
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
See the following page for continued comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF014
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The stair wall sheathing at building N’s three stairs was found to conform with the project
drawings.
The exterior shear wall at buildings P and Q were found to be still in progress. GeoTest walked
both buildings with the framing contractor and determined the walls were not complete and that
they need to conduct an inspection themselves prior to scheduling us to return for a follow-up
inspection for these walls.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF019
PERMIT #: 1863 DATE: 5/2/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Roof Diaphragm Sheathing Building Q
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Gable End Will be Braced Per Option B (3 on S6.1) no Brace Blocking
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148, 2-1/4"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the sheathing at building Q roof. All items found were
addressed prior to GeoTest’s departure.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF035
PERMIT #: 1863 DATE: 6/5/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear and Bearing Walls Interior Framing Buliding Q, Floors 1 to 3
Shear Wall Sheathing Building Q, Floors 1 to 3 Interior Shear Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan at Above Locations
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan at the Above Locations
Connection of blocking to wall top plates A35 Clips Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per HD Schedule and Projects Plan View Drawing
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Amended 6-14-2019: Please see GeoTest’s Lateral Framing Inspection report
LF039, dated 6-11-2019 for reinspection conformance.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF035
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
GeoTest was on site as requested to inspect the above items. At Building Q, there were
missing nails, break in top plates and trade damage. The contractor was notified of these
items.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF037
PERMIT #: 1852, 1853, 1863 DATE: 6/7/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing Building F, 3rd Level
Shear Walls: Sheathing Building E, 1st Level Entry Walls
Final Framing (In Progress Inspection) Building Q, 1st, 2nd & 3rd Levels
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D-Fir #2
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The items listed on this report were found to be in conformance with the project drawings. Building Q is in
progress. A follow-up inspection is required.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF038
PERMIT #: 1851, 1853. 1862, 1863 DATE: 6/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings D and F, 3rd Floor Entry Walls
Final Framing (In Progress Inspection) Building P, 1st Floor and Building Q all Levels
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Per SW Schedule
Shear wall/diaphragm length, location As Detailed
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related As Detailed
Connection of blocking to wall top plates A35 and LTP4 Clips Were in Place
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Per SW Schedule
Nail diameter, length, number of lines, spacing Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location HDU, Per Plan
Lag bolts/proper hole size At Stair Stringer to Landing Connections
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. See below for
additional comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF038
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Many of the stud packs, which
the holdown straps are
connected to, were not nailed
together per detail 3 on sheet
S5.1
Some of the blocks connecting to the first joist were
toenailed but the drawings require three 131 X 3" nails
through the joist and into the end of the blocking.
The contractor is in the process of adding the nails in
accordance with detail 3 on sheet S5.2 of the project
drawings.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF038
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Building Q: West End Wall
Plate Damage:
The top and bottom plates
were damaged with drilled
holes. The contractor has
added CS16 strap at these
damaged locations as per the
project engineer directions.
Along with the above three
items, the floor joists adjacent
to the center entry were
installed at 16" on center, but
the drawings require the joist
at these locations to be
spaced at 12" on center.
The contractor will address
this item.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF039
PERMIT #: 1861, 1863 DATE: 6/11/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing and HD Strapping (Reinspection) Building O, All Exterior Shear Walls
Final Framing and Interior Shear Walls (Reinspection) Building Q, All Locations
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan at Above Locations
Panel edges bear on framing members Yes Fully Blocked Per Plan
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The exterior sheathing at Building O is in accordance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF039
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Building Q Final Framing:
The contractor has addressed the framing items in GeoTest's Lateral Framing Inspection
Report LF035, dated 6-5-2019.
In addition to the above items, the contractor has removed the 2nd and 3rd level floor joist in
the rooms adjacent to the center entry; these were spaced at 16" on center and were replaced
at the correct spacing of 12" on center.
Framing and interior shear wall sheathing at Building Q is complete and has been found to be
in accordance with the project drawings.
SPECIAL INSPECTION SUMMARY
PROJECT: The Villas at Arlington - BLD Q JOB #: 18-0760
ADDRESS: 18506 Smokey Point Blvd, Arlington, WA 98223 DATE: 9-11-2019
CLIENT: Villas at Arlington Partners LLLP PERMIT #: 1863
CONTRACTOR: Exxel Pacific PAGE: 1 of 1
This letter summarizes our special inspection and testing efforts for The Villas at Arlington - BLD Q
project located in Arlington, Washington. GeoTest’s services took place from October 9, 2018
through September 11, 2019. Our testing and inspections included the following scope of work:
TEST/INSPECTION ITEM REFERENCE
Field Density Moisture Reports FD014, FD016,
• Earthwork
FD017 & FD019
Concrete Break Reports CB002 – CB004 &
• Reinforced Concrete CB007 and Inspection Reports IR002, IR004 &
IR005
Lateral Framing Inspection Reports LF001 –
• Lateral Framing LF004, LF007 – LF009, LF012 – LF015, LF019,
LF035 & LF037 – LF039
Adhesive Anchor Inspection Reports AA001 &
• Proprietary Anchors
AA014
All work requiring special inspection for the project to date has been completed. To the best of
our knowledge the inspected work is in conformance with the approved project plans and
specifications and the applicable workmanship provisions of the International Building Code. All
related laboratory tests performed by GeoTest have met or exceeded the minimum test
requirements.
This is GeoTest’s final special inspection and testing submittal for The Villas at Arlington - BLD Q
project. If we can be of further assistance, please contact the undersigned.
Copies: Villas at Arlington Partners LLLP Safe Built
Charles Morgan and Associates LLC The Alliant Company
City of Arlington Anderson, Brian
Exxel Pacific Charles Morgan and Associates LLC Logan Senrud
CG Engineering Technical Director
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Permit #: 1863
Permit Date: 03/09/18
Permit Type: MULTI-FAMILY
Project Name: Villas at Arlington
Applicant Name: Villas at Arlington, LLLP
Applicant Address: 105 Cresent Bay Drive, Suite D
Applicant, City, State, Zip: Laguna Beach, CA 92651
Contact: Carmel Gregory
Phone: 425-778-8500
Email: carmelg@cgengineering.com
Scope of Work: New Multi-Family Development
Valuation: 2067934.40
Square Feet: 19040
Number of Stories: 3
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 11/01/2018
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
VILLAS AT 137 Multiple Family
31052000100800 3318 185TH PLACE NE
ARLINGTON 101 - 200 Units
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
323A CONSTRUCTION
EXXEL PACIFIC INC 360-734-2872 UBI 601 175 198
TELEGRAPH RD CONTRACTOR
323A CONSTRUCTION Labor and
EXXEL PACIFIC INC 360-734-2872 EXXELPI073KN
TELEGRAPH RD CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
03/09/2018 BUILDING
BUILDING
Fees
Fee Description Notes Amount
Building Plan Review Table 4-2 $8,791.51
Building Plan Review Table 4-2 $148.88
Building Permit Table 4-1 $13,754.44
Park - Community MF Multi-family $26,946.00
Processing/Technology $25.00
State Surcharge - Commercial Commercial Only $25.00
State Surcharge - add'l DU Residential Additional Units $36.00
Traffic Mitigation - C/MF Commercial/Multi-family $23,420.52
Total $73,147.35
Attached Letters
Date Letter Description
09/19/2018 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
03/08/2018 Alliant Capital Ltd. 18506 Bldg. Q Check #104500 Kristin Foster $8,791.51
10/11/2018 Fidelity National Title check #26379 Launa Black $64,355.84
Outstanding Balance $0.00
Uploaded Files
Date File Name
12/23/2019 6021872-Villas Bldg. Q C of O.pdf
04/22/2019 4790747-1299_4-15-19 FL Inspection Bldg Q.pdf
11/01/2018 4145080-1863_Villas Building Permit.pdf
03/09/2018 3141700-Commercial Application - Building Q.pdf
SUBMITTAL REVIEW
â–¡ NO EXCEPTION TAKEN
□✔ MAKE CORRECTION NOTED
â–¡ REJECTED
â–¡ REVISE AND RESUBMIT
â–¡ SUBMIT SPECIFIED ITEM
THIS REVIEW IS ONLY FOR GENERAL CONFORMANCE
WITH THE DESIGN CONCEPT OF THE PROJECT AND
GENERAL COMPLIANCE WITH THE INFORMATION
GIVEN IN THE CONTRACT DOCUMENTS. CONTRACTOR
REMAINS RESPONSIBLE FOR FULL COMPLIANCE WITH
THE PLANS AND SPECIFICATIONS. DIMENSIONS AND
QUANTITIES WERE NOT REVIEWED AND ARE THE
RESPONSIBILITY OF THE CONTRACTOR.
BY Morgan Kruse DATE 11/21/18