HomeMy WebLinkAbout3318 185th Pl Ne Bldg P_BLD1862_2025 741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA002
PERMIT #: 1862 DATE: 3/5/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Item(s) Inspected Location
Building P Footing Stem Wall - Footing at All Locations of Building P
Reference Drawing(s): RFI 7
Item(s) Inspected Comments
Base Material Condition Concrete, dry
Drill Bit Type Hollow Bit Roto-hammer
Hole Diameter/Depth 3/4" X 4"
Hole Cleanliness Clean
Anchor Spacing/Edge Distance 5" On-Center
Anchor Type #5 Rebar
Anchor Diameter/Length 5/8"
Anchor Embedment 4"
Adhesive Type Hilti HY 200
Adhesive Expiration Date 9/2019
Adhesive ICC-ES Report 3187 and 3963
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest on site for inspection of the epoxied bar for the above-referenced locations. Reviewed hole
depth, spacing, and size in accordance with RFI 7. Verified cleanliness prior to epoxy installation.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA013
PERMIT #: O-1861, P-1862, CH-1864 DATE: 5/23/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Threaded Rod for HDU5 Holdowns BLD P, O (2) Bolt at West & East Party Wall & 1 at Center Wall
Threaded Rod Anchor Bolt w/ 27" of Embed Depth for HDU5 Clubhouse, North Wall at Basketball Court West Side of Wall
Threaded Rod for HDU5 Holdowns Clubhouse, 6 Bolts Total at Interior Shear Walls
Reference Drawing(s): Engineer Revised Sketches
Item(s) Inspected Comments
Base Material Condition Fully Cured Concrete
Drill Bit Type Drilled Prior
Hole Diameter/Depth 3/4", 9"
Hole Cleanliness Blown, Brushed, Blown Clean
Anchor Spacing/Edge Distance Per Plan
Anchor Type Threaded Rod
Anchor Diameter/Length 5/8", 16"
Anchor Embedment 9 to 10"
Adhesive Type Hilti HY-200R
Adhesive Expiration Date 12/19
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. The anchor bolts
were found to be in conformance with the engineers revised sketches and were installed as
recommended by the manufacturer’s published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: AA013
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo shows the framing
contractor using compressed
air to clean one of the drilled
holes at the clubhouse.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA014
PERMIT #: 1857, 1858, 1863, 1862 DATE: 5/30/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Interior Wall Footing Reinforcing Steel Dowels Building K and L at Perimeter Foundation Intersections
Holdown Anchor Bolts (5/8" X 14" w/9" Embed) Building Q and P, Center Party Wall (Non-Entry Side of Wall)
Reference Drawing(s): RFI #7, Structural Drawings
Item(s) Inspected Comments
Base Material Condition Satisfactory , Dry Concrete. 57º
Drill Bit Type Carbide Tip, Rotor Hammer w/Vacuum
Hole Diameter/Depth 3/4" X 4"
Hole Cleanliness Clean - Flushed with Water Until Clear/Brushed/Flushed
Anchor Spacing/Edge Distance Per Plan
Anchor Type Grade 60 Deformed Reinforcing Steel
Anchor Diameter/Length 5/8", 44"
Anchor Embedment 4"
Adhesive Type Hilti HY200 R
Adhesive Expiration Date 9/2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the epoxied dowels.
The above dowels were found to conform with the project structural drawings and RFI #7. The dowels were
installed as recommended by the manufacturer’s published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB003
PERMIT #: 1862,1863 DATE: 1/24/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building Q Perimeter Stem Wall, Building P Continuous Wall Footings and Column Plinth Pads
Sample Location: 1st Load, Place at the Stem Walls on the West Half of Building Q
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.50
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5sk. 7/8", WRA, 50% HW Unit Weight, pcf (C138) NT
Truck/Ticket # C137 / 217512 Air/Mix Temp.,°F (C1064) 51 / 69 TM01
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 45/65 TM01
Quantity Placed, cy 70 Cure Method - Initial / Final Container / Moist Room
Time Batched 11:16 A.M Water Added on Job, gals 8
Time Sampled 12:10 P.M Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
91679 7 01-31 61820 4.01 12.63 4890 TYPE 2:
91680 28 02-21 74990 4.02 12.69 5910 TYPE 3:
91681 28 02-21 75190 4.02 12.69 5930 TYPE 2:
91682 28 02-21 72560 4.02 12.69 5720 TYPE 3:
91683 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: Geotest was on site as requested to inspect the concrete placement at the above
locations. The reinforcing steel was in place and was found to be in conformance with the
project structural drawings. The holdown anchor bolts were tied in place with the required
embedment at building P continuous footing and the sill plate anchor bolts at building Q were
wet set in the stem wall
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB003
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo was taken looking
west down building P north
side.
As requested by the Arlington City Inspector:
GeoTest verified that the reinforcement for Building's Q (and Building P) plinths was in place as
detailed plus the contractor has placed additional vertical dowels for larger embed ties.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB004
PERMIT #: 1862, 1863, 1860 DATE: 1/31/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building P, Stem Walls and Plinths Building Q, Plinths Building N, Perimeter Wall Footings and Plinth
Footings
Sample Location: 1st Load Placed at Building P, Stem Walls and Plinths West Half of Building
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 4.75 19
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 Sack 7/8", Pea. WRA Unit Weight, pcf (C138) NT
Truck/Ticket # C116 / 615146 Air/Mix Temp.,°F (C1064) 52 / 62 TM02
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 37/71 TM02
Quantity Placed, cy Cure Method - Initial / Final Container / Water Tank
Time Batched 11:47 A.M Water Added on Job, gals 15
Time Sampled 12:33 P.M Water Requested by Concrete Contrac
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
91861 7 02-07 54230 4.01 12.63 4290 TYPE 2:
91862 28 02-28 0 0.00 0.00 0
91863 28 02-28 0 0.00 0.00 0
91864 28 02-28 0 0.00 0.00 0
91865 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to inspect the concrete placement at the above
locations. The reinforcing steel was in place and was found to be in conformance with project
structural drawings. The concrete was placed using a boom pump and was mechanically
consolidated.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avscommunities.com,
kolander@arlingtonwa.gov, lpeterson@arlingtonwa.gov, Matthew.Breiner@alliantcapital.com ...and 2 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB004
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Photo shows the contractor
placing and consolidating the
concrete at Building P
footings.
Photo of the continuous
footing reinforcement with one
of the 'UFER' electrical
grounding bars tied to one of
the footing's continuous bars.
Two of these were installed at
the building's east end.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB009
PERMIT #: 1862 DATE: 3/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Slab on Grade, Building P
Sample Location: Exterior Patios of Slab on Grade, Middle of Truck Batch
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.50 15
Mix # 0260A6C Air Content, % (C231) 5.5 18
Mix Description 7/8" Agg. Unit Weight, pcf (C138) NT
Truck/Ticket # C116 / 615313 Air/Mix Temp.,°F (C1064) 33 / 58 JM6
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 35/63
Quantity Placed, cy 20 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:16 AM Water Added on Job, gals 0
Time Sampled 8:00 AM Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
92956 7 03-15 58940 4.01 12.63 4670 TYPE 2:
92957 28 04-05 75120 4.00 12.57 5980 TYPE 2:
92958 28 04-05 75580 4.00 12.57 6010 TYPE 2:
92959 28 04-05 74960 4.00 12.57 5960 TYPE 2:
92960 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on site for inspection of concrete placed for the Building P slab on grade.
Verified final clearances and debris removal prior to concrete activities. All items inspected
were in conformance with approved plans and drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB009
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Sample Location: Interior Slab on Grade, West Half, Middle of Truck Batch
Field Data:
Truck/Ticket # C060 / 615316 Slump, in. (C143) 6.00
Time Batched 8:06 AM Air Content, % (C231) NT
Time Sampled 9:10 AM Unit Weight, pcf (C138) NT
Air Temperature,°F 35 Water Added on Job, gals 0
Mix Temp.°F(C1064) 60 Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
92961 7 03-15 54430 4.01 12.63 4310 TYPE 2:
92962 28 04-05 72320 4.00 12.57 5750 TYPE 2:
92963 28 04-05 67290 4.00 12.57 5350 TYPE 2:
92964 28 04-05 74150 4.00 12.57 5900 TYPE 2:
92965 Hold 00-00 0 0.00 0.00 0
Comments: This set represents Miles mix 02550C, which is not entrained with air.
Sample Location:
Field Data:
Truck/Ticket # / Slump, in. (C143)
Time Batched Air Content, % (C231)
Time Sampled Unit Weight, pcf (C138)
Air Temperature,°F Water Added on Job, gals
Mix Temp.°F(C1064) Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB009
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Concrete Placement and
Consolidation in Progress
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD036
PERMIT #: 1853, 1854, 1862 DATE: 3/4/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Compaction Of: Building Pads F, G, and P
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 TOG DT/12 127.3 10.8 114.9 1 102 95 P
2 See Figure 1 TOG DT/12 117.9 9.1 108.1 1 96 95 P
3 See Figure 1 TOG DT/12 126.8 12.4 112.8 1 100 95 P
4 See Figure 1 TOG DT/12 120.9 9.6 110.3 1 98 95 P
5 Building F, Eastern Third TOG DT/12 135.2 6.7 126.6 2 100 95 P
6 Building F, Middle Third -.5 DT/12 132.2 8.1 122.2 2 96 95 P
7 Building G, NW Quadrant -2 DT/12 132.6 5.9 125.2 2 98 95 P
8 Building G, NE Quadrant -2 DT/12 131.3 6.7 123.1 2 97 95 P
9 Building G, SE Quadrant -2.5 DT/12 129.9 6.9 121.5 2 96 95 P
10 Building G, SW Quadrant -2.5 DT/12 131.0 7.1 122.3 2 96 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4282A SP Native 112.6 13.9 5 ASTM D1557/D4718
2-4332A SP with Gravel Lenz Enterprises Pit (D-255) 127.2 9.6 17 ASTM D1557/D4718
3- 0.0 None
Gauge Make/Model/Serial#: Instro/3500/2082 M/D Standard Count: 403/3174
Comments: Please see page 2 for comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD036
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
TOG -Top of Grade
GeoTest was on-site as requested to provide in-place density testing at the above locations. All
locations and elevations are approximate and were provided by the contractor.
Tests 1 - 4 were taken at the request of the contractor on Building Pad P (Figure1). Prior to our
arrival, the soil in these areas had been re-worked and compacted with a plate compactor, per
the contractor. The material that was tested was comprised of mostly native fill. Tests 5-10
were taken on imported, graded, and compacted structural fill for Building Pads F and G.
Compaction was achieved in these areas with a single-drum vibratory roller.
All tests taken on this date met compaction requirements. These compacted soils exhibited
firm and unyielding conditions with optimum moisture contents.
GeoTest will return for further inspection and observation as requested.
Figure 1. In-place density
testing locations of re-worked
structural fill for Building P.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: IR006
PERMIT #: 1862 DATE: 3/7/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
INSPECTION OF:
Slab on Grade, Building P
Comments: GeoTest on site for inspection of the building P slab on grade. Reviewed reinforcing steel in
accordance with RFI 34, which approves substituting wire mesh with #3 rebar spaced at 18" on center each way.
Work was found to conform with the approved plans and specifications.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF001
PERMIT #: BLD-1862, BLD-1863 DATE: 3/22/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Straps Beam to Top Plate Building P and Q, Level 1 ADA Units
Floor Diaphragm, Sheathing Building Q, Level 2
Reference Drawings: Notes on S1.1, S1.2 and S2.1.1 and Details on S5.1
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, T & G, 23/32", Exp.1
Shear wall/diaphragm length, location At Above Locations Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing See Comments .148 X *2-1/4" (Drawings Call for .148 X 3")
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Adequate
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: See comments on page 2.
AMENDED 4/19/19: GeoTest was provided with RFI 044 accepting the use of .148 x 2.25"
nails at glued down diaphragms.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF001
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
GeoTest was on site as requested to inspect the above items.
*The drawings call for the floor sheathing to be nailed using 10d common nails - .148" X 2-1/4
were used, Engineer approval pending.
MST37 strap nailed to the top
plate. For the ADA units
added support beam
connections.
Nails connecting the diaphragm sheathing to an interior
shear wall (blocking) spaced at 6" on center per plan.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF001
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
The photo was taken looking
east across Building O 2nd
level floor sheathing.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF002
PERMIT #: BLD.1862 BLD.1863 DATE: 3/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing Building P, 2nd Level
Shear Wall: Sheathing (Inspected Prior to Dens-Glass) Buildings P and Q, 1st Floor Stairway Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir 2
Structural panel grade and thickness, glue Walls: Struct. 1, 15/32", Exp.1 / Floor: Rated Sheathing, 23/32", Exp.1
Shear wall/diaphragm length, location At Above Locations Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" x 2-1/4" (Nail Size is Acceptable Per Engineer’s Email Dated 3/25/19)
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Adequate
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items mentioned above. The
items listed above were found to be in conformance with the approved drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF002
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Stairway Type SW6 Shear
Wall Sheathing
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20527 67th Ave NE, Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF003
PERMIT #: 1862 & 1863 DATE: 3/27/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings P and Q, 2nd Level Stairway Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir 2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location At Above Locations Per Plan
Panel edges bear on framing members Sheathing Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Adequate
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Geotest was on site as requested to inspect the above shear walls prior to the installation of the
Dens-Glass wallboard. The sheathing and fasteners were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF007
PERMIT #: 1862 and 1863 DATE: 4/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing and Fasteners Buildings P and Q, 3rd Level
Reference Drawings: S1.1, S1.2, S2.1.1, S2.1.2, S5.1, S5.2
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 23/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148", 2-1/4", 6" and 10"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. The third level floor
sheathing was in accordance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF007
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
This photo was taken facing
east standing on the west end
of the 3rd-floor deck
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF009
PERMIT #: 1848, 1860, 1861, 1862. 1863, 1864 DATE: 4/11/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Walls: Sheathing Rec. Bld. at all Shear Wall Locations Except for SW2 Wall
Shear Walls: Sheathing East Wall at Buildings N & O, West Walls at Buildings P & Q
MST37 Straps Nailed to Wall Top Plate Building A (5) Locations, ADA Units Closets
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location See Comments
Panel edges bear on framing members All Edges Were Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148", 2-1/4", Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the shear wall sheathing and straps
at the above locations.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF009
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The MST37 straps were
fastened to the wall top plate
using 148 X 2-1/2" nails.
In this picture, the door on the
left is not shown on the
structural drawings. The
contractor will reach out to the
project engineer regarding
moving the holdown location
to the other side of the door.
The sheathing and the nailing
of the sheathing at the
locations mentioned in this
report were found to be in
conformance with the
structural drawings.
The contractor plans to sheath
the interior side of the SW2
shear wall at the buildings
east side as directed by the
project structural engineer.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF014
PERMIT #: 1860, 1862, 1863 DATE: 4/23/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Building N, 3rd Level Stair Walls
Shear Wall Sheathing and Straps (In Progress) Building P and Q: Levels 1, 2 & 3 Exterior Shear Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32" . EXP.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", Per Plan & RFI #44
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location In Progress
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
See the following page for continued comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF014
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The stair wall sheathing at building N’s three stairs was found to conform with the project
drawings.
The exterior shear wall at buildings P and Q were found to be still in progress. GeoTest walked
both buildings with the framing contractor and determined the walls were not complete and that
they need to conduct an inspection themselves prior to scheduling us to return for a follow-up
inspection for these walls.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF021
PERMIT #: 1849, 1850, 1862 DATE: 5/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing Building C, 3rd Floor
Shear Wall Sheathing Building B, 3rd Floor Entry Walls (Each Side of Stairs)
Roof Diaphragm: Sheathing Building P
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing (Sturd-I-Floor at Building B), 15/32" (23/32 at Bld B) Exp.1
Shear wall/diaphragm length, location Per Plan at Above Locations
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" X 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Geotest was on site as requested to inspect the above items.
All items found were corrected prior to our leaving the project.
Sheathing and fasteners were per plan.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF021
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Photo of Building (P) roof was
taken looking east across the
south half.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF038
PERMIT #: 1851, 1853. 1862, 1863 DATE: 6/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings D and F, 3rd Floor Entry Walls
Final Framing (In Progress Inspection) Building P, 1st Floor and Building Q all Levels
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Per SW Schedule
Shear wall/diaphragm length, location As Detailed
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related As Detailed
Connection of blocking to wall top plates A35 and LTP4 Clips Were in Place
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Per SW Schedule
Nail diameter, length, number of lines, spacing Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location HDU, Per Plan
Lag bolts/proper hole size At Stair Stringer to Landing Connections
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. See below for
additional comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF038
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Many of the stud packs, which
the holdown straps are
connected to, were not nailed
together per detail 3 on sheet
S5.1
Some of the blocks connecting to the first joist were
toenailed but the drawings require three 131 X 3" nails
through the joist and into the end of the blocking.
The contractor is in the process of adding the nails in
accordance with detail 3 on sheet S5.2 of the project
drawings.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF038
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Building Q: West End Wall
Plate Damage:
The top and bottom plates
were damaged with drilled
holes. The contractor has
added CS16 strap at these
damaged locations as per the
project engineer directions.
Along with the above three
items, the floor joists adjacent
to the center entry were
installed at 16" on center, but
the drawings require the joist
at these locations to be
spaced at 12" on center.
The contractor will address
this item.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF041
PERMIT #: 1862 DATE: 6/13/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Wall Sheathing Building P, 3rd Floor
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips are in Progress
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to conduct a final framing inspection at the above locations. The
above locations are in progress, these locations will need to be reinspected prior to cover.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF042
PERMIT #: 1862 DATE: 6/14/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Walls Building P, Floors 2 and 3
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates Clips are in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The above interior framing and shear wall sheathing have been found to conform with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
Soil Observation Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: SO010
PERMIT #: 1862 DATE: 3/1/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
OBSERVATION OF: Building P Slab Sub-base
GeoTest on site for inspection of the sub-base for the building P Slab on Grade. The contractor
had placed a mix of various soils with varied proctors, as such the ground was probed with a
3/8" T-probe. Soils appeared to be firm and stable with an average penetration of about 4" into
the subgrade.
Soils of the Sub-base for
Building P
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
GeoTest's representatives are on-site to observe, test and provide recommendations. The Contractor retains sole responsibility for the methods,
operations and sequences of construction, including obtaining approval from the design authority and owner prior to proceeding with any change in the work scope and/or
any associated costs.
SPECIAL INSPECTION SUMMARY
PROJECT: The Villas at Arlington - BLD P JOB #: 18-0760
ADDRESS: 18506 Smokey Point Blvd, Arlington, WA 98223 DATE: 9-11-2019
CLIENT: Villas at Arlington Partners LLLP PERMIT #: 1862
CONTRACTOR: Exxel Pacific PAGE: 1 of 1
This letter summarizes our special inspection and testing efforts for The Villas at Arlington - BLD P
project located in Arlington, Washington. GeoTest’s services took place from October 9, 2018
through September 11, 2019. Our testing and inspections included the following scope of work:
TEST/INSPECTION ITEM REFERENCE
Field Density Moisture Reports FD014, FD019,
• Earthwork
& FD036 and Soil Observation Report SO010
Concrete Break Reports CB003, CB004 &
• Reinforced Concrete
CB009 and Inspection Report IR009
Lateral Framing Inspection Reports LF001 –
• Lateral Framing LF003, LF007, LF009, LF014, LF015, LF021,
LF038, LF041 & LF042
Adhesive Anchor Inspection Reports AA002,
• Proprietary Anchors
AA013 & AA014
All work requiring special inspection for the project to date has been completed. To the best of
our knowledge the inspected work is in conformance with the approved project plans and
specifications and the applicable workmanship provisions of the International Building Code. All
related laboratory tests performed by GeoTest have met or exceeded the minimum test
requirements.
This is GeoTest’s final special inspection and testing submittal for The Villas at Arlington - BLD P
project. If we can be of further assistance, please contact the undersigned.
Copies: Villas at Arlington Partners LLLP Safe Built
Charles Morgan and Associates LLC The Alliant Company
City of Arlington Anderson, Brian
Exxel Pacific Charles Morgan and Associates LLC Logan Senrud
CG Engineering Technical Director
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Sieve Analysis Test Report - ASTM C136/C117
6 in. 3 in. 2 in. 1½ in. 1 in. ¾ in. ½ in. 3/8 in. #4 #10 #20 #30 #40 #60 #100 #140 #200
100 WSDOT-16 9-03.14(2) Select Borrow
90
80
70
60
50
40
PERCENT FINER
30
20
10
0
100 10 1 0.1
GRAIN SIZE - mm.
% Gravel % Sand % Fines
% +3"
Coarse Fine Coarse Medium Fine Silt
0 5 42 11 22 15 5
SIEVE PERCENT SPEC.* PASS? Material Description
SIZE FINER PERCENT (X=NO) WSDOT 9-03.14(2) Select Borrow
6" 100 99 - 100 Structural fill material
3" 100 75 - 100 poorly graded sand with silt and gravel
1-1/2" 100
Atterberg Limits
3/4" 95
PL= LL= PI=
5/8" 91
1/2" 84 Coefficients
3/8" 74 D90= 15.3228 D85= 13.1481 D60= 6.2296
1/4" 61 D50= 4.1113 D30= 0.8428 D15= 0.2961
#4 53 D10= 0.1946 Cu= 32.02 Cc= 0.59
#10 42
Classification
#20 30
USCS= AASHTO=
#40 20 0 - 50
#60 13 Remarks
#100 8 Sample does not meet gradation but meets SE spec.
#200 5.4 0.0 - 10 Percent Passing #200 based on #4: 10.2% (Spec: 5% Max)
Sand Equivalent: 37 (Spec: 30 min)
* WSDOT-16 9-03.14(2) Select Borrow
Location: East Valley Sand & Gravel - East Valley Sand & Gravel Pit (D-355)
Sample Number: 4327A Date: 2-6-19
Client: Villas at Arlington Partners LLC
Project: The Villas at Arlington
18506 Smokey Point Boulevard, Arlington, WA, 98223
This report may not be reproduced, except in full, without the prior written approval of GeoTest Services, Inc.Project No: 18-0760 Figure SP007
Tested By: JP/AH Checked By: BF
Moisture-Density (Proctor) Test Report
145
142.5 6.9%, 142.0 pcf
7.2%, 141.0 pcf
140
Dry density, pcf
137.5
135
ZAV for
Sp.G. =
2.75
132.5
3 4.5 6 7.5 9 10.5 12
Water content, %
- Rock Corrected - Uncorrected
Test specification: ASTM D 1557-12 Method C Modified
ASTM D4718-15 Oversize Corr. Applied to Each Test Point
Elev/ Classification Nat. % > % <
Sp.G. LL PI
Depth USCS AASHTO Moist. 3/4 in. No.200
5 5.4
ROCK CORRECTED TEST RESULTS UNCORRECTED MATERIAL DESCRIPTION
WSDOT 9-03.14(2) Select Borrow
Maximum dry density = 142.0 pcf 141.0 pcf
Structural fill material
Optimum moisture = 6.9 % 7.2 % poorly graded sand with silt and gravel
Project No. 18-0760 Client: Villas at Arlington Partners LLC Remarks:
Project: The Villas at Arlington SPG: Assumed
18506 Smokey Point Boulevard, Arlington, WA, 98223 Date: 2-6-19
Loc.: East Valley Sand & Gravel - East Valley Sand & Gravel Pit (D-355)
This report may not be reproduced, except in full, without the prior written approval of GeoTest Services, Inc.Figure SP007
Tested By: AH Checked By: BF
Permit #: 1862
Permit Date: 03/09/18
Permit Type: MULTI-FAMILY
Project Name: Villas at Arlington
Applicant Name: Villas at Arlington, LLLP
Applicant Address: 105 Cresent Bay Drive, Suite D
Applicant, City, State, Zip: Laguna Beach, CA 92651
Contact: Carmel Gregory
Phone: 425-778-8500
Email: carmelg@cgengineering.com
Scope of Work: New Multi-Family Development
Valuation: 2067934.40
Square Feet: 19040
Number of Stories: 3
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 11/01/2018
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
VILLAS AT 137 Multiple Family
31052000100800 3318 185TH PLACE NE
ARLINGTON 101 - 200 Units
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
323A CONSTRUCTION
EXXEL PACIFIC INC 360-734-2872 UBI 601 175 198
TELEGRAPH RD CONTRACTOR
323A CONSTRUCTION Labor and
EXXEL PACIFIC INC 360-734-2872 EXXELPI073KN
TELEGRAPH RD CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
03/09/2018 BUILDING
BUILDING
Fees
Fee Description Notes Amount
Building Plan Review Table 4-2 $8,791.51
Building Plan Review Table 4-2 $148.88
Building Permit Table 4-1 $13,754.44
Park - Community MF Multi-family $26,946.00
Processing/Technology $25.00
State Surcharge - Commercial Commercial Only $25.00
State Surcharge - add'l DU Residential Additional Units $36.00
Traffic Mitigation - C/MF Commercial/Multi-family $23,420.52
Total $73,147.35
Attached Letters
Date Letter Description
09/19/2018 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
03/08/2018 Alliant Capital Ltd. 18506 Bldg. P Check #104500 Kristin Foster $8,791.51
10/11/2018 Fidelity National Title check #26379 Launa Black $64,355.84
Outstanding Balance $0.00
Uploaded Files
Date File Name
12/23/2019 6021844-Villas Bldg. P C of O.pdf
04/22/2019 4790934-1299_4-15-19 FL Inspection Bldg P.pdf
11/01/2018 4145079-1862_Villas Building Permit.pdf
03/09/2018 3141691-Commercial Application - Building P.pdf
SUBMITTAL REVIEW
â–¡ NO EXCEPTION TAKEN
□✔ MAKE CORRECTION NOTED
â–¡ REJECTED
â–¡ REVISE AND RESUBMIT
â–¡ SUBMIT SPECIFIED ITEM
THIS REVIEW IS ONLY FOR GENERAL CONFORMANCE
WITH THE DESIGN CONCEPT OF THE PROJECT AND
GENERAL COMPLIANCE WITH THE INFORMATION
GIVEN IN THE CONTRACT DOCUMENTS. CONTRACTOR
REMAINS RESPONSIBLE FOR FULL COMPLIANCE WITH
THE PLANS AND SPECIFICATIONS. DIMENSIONS AND
QUANTITIES WERE NOT REVIEWED AND ARE THE
RESPONSIBILITY OF THE CONTRACTOR.
BY Morgan Kruse DATE 11/21/18