Form No. F_080488 Replaces page 51 a-e, dated April 25, 2008. (Updated sprinkler materials. Min. operating pressure for
LPCB and CE approval ONLY is 5 psi (0.35 bar). Added alternate frame material for Sprinklers 06661 B,
,-.,...--,,...,...,..... ,...--,,...,,...,... I .A,...,...,... .A r""\ - I I . ,...,....,...,-.. ,- ,..... f"\I"'\-,.,... A,.....
. . I .A .or, ;II--,. \
January 22, 2010 Sprinkler 51 e
MICROFAST® AND
-~M=i=crofastHP® QUICK
TECHNICAL DATA
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 51 d)
cULy§ Li§1ing Begyicement§:
Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in the Approval Chart for installation
in accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer
to the installation guidelines for old style (conventional) sprinklers.
FM A1;mrovi!I Rggl,!ir11ments:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global
Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTC: The FM lnatallatlon guidolino& may differ from ctlLus and/or NFPA criteria
IMPORTANT: Always refer to Bulletin Form No. F _091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
..
Sprinkler 51 d January 22, 2010
MICROFAST® AND
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE UPRIGHT AND
"IKINGi CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart I r.==
Microfast® and MicrofastMP® Quick Response Temperature KEY J
Finish
A~ Escutcheon (if applicable)
Upright and Conventional Sprinklers
Maximum 175 PSI (12 bar) WWP
Nominal Listings and Approvals3
Base Part Thread Size Overall Length
SIN K-Factor (Refer also to Design Criteria on page 51e.)
Number1
NPT I BSP U.S. I metric2 Inches mm cULus• I FM7 I NYC8 I VdS I LPCB I CE I 0
Uoriaht-Standard Orifice
06661 B VK300 1/2" I 15 mm 5.6 I 80.6 2-3/16 56 A2 I A3 I A2 I -- I -- I -- I --
07060 VK345 -- I 15 mm 5.6 I 80.6 2-3/16 56 -- I A3 I -- I A3 I A3 I B312 I B314
Conventional-Standard Orifice
06766B VK310 1/2" I 15 mm 5.6 I 80.6 2-3/16 56 A3 I -- I A3 I -- I A3 I B312 I B314
Uorloht-Laro e Orifice
06665B VK350 3/4" I -- 8.0 I 115.2 2-5/16 59 A2 I A3 I A2 I -- I A3 I B312 I --
14817 VK350 -- I 20 mm 8.0 I 115.2 2-5/16 59 A2 I A3 I A2 I -- I A3 I B312 I --
06764B VK350 1/2" I 15 mm 8.0 I 115.2 2-5/16 59 A2 I -- I A2 I -- I -- I -- I --
Conventional-Larae Orifice
06768B VK354 3/4" I 20 mm 8.0 I 115.2 2-5/16 59 A2 I -- I A3 I -- I A3 I B312 I --
Uori!1ht-Small Orlflce'"
06717B11 VK325 1/2" I 15 mm 2.8 I 40.3 2-3/16 56 A2 I A1 I A2 I -- I -- I -- I --
06719B11 VK327 1/2" I 15 mm 4.2 I 60.0 2-3/16 56 A2 I -- I A2 I -- I -- I ·- I --
11 VK327 -- I 10mm 4.2 I 60.0 2-3/16 56 -- I 13
06931 B -- I -- I A3 I -- I E1 I --
Maximum 250 PSI (17 bar) WWP
Upright-Standard Orifice
Nominal Listings and Approvals'
Base Part Thread Size Overall Length
SIN K-Factor (Refer also to Desian Criteria on oaae 51e.)
Number1
NPT I BSP U.S. I metric2 Inches mm cULus• I FM I NYC9 I VdS I LPCB I { E I 0
12281 VK315 1/2" I 15 mm 5.6 I 80.6 2-3/16 56 A2 I -- I A2 I -- I -- I -- I --
Uoriaht-Small Orifice"
1228611 VK340 1/2" I 15 mm 2.8 I 40.3 2-3/16 56 A2 I -- I A2 I -- I -- I -- I --
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), Approved Finishes
and 286 °F (141°C) 1 - Brass and Chrome-Enloy®
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) 2 - Brass, Chrome-Enloy®, White Polyester56 56
, Black Polyester ,
C - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 286 °F (141 °C) and Black Teflon®5
D - 135 °F (57 °C), 155 °F (68 °C), and 175 °F (79 °C) 3 - Brass, Chrome-Enloy®, White Polyester56 56
· , and Black Polyester ·
E - 155 °F (68 °C)
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10 0
3This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
• Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
7 For installation in accordance with the latest applicable FM Loss Prevention Data Sheets and Technical Advisory Bulletins.
8 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
9 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16.
10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or
internally galvanized.
11The sprinkler orifice is bushed.
12
( E Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.
13
( E Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131
1
• 0 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
January 22, 2010 Sprinkler 51c
MICROFAST® AND
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating1 Ceiling Temperature2
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings4
: White Polyester, Black Polyester, and Black Teflon®
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pages 51 d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
Protective
\v'rench Sprinkler
Flo. t Co.p
10896
Figure 1:
Standard Sprinkler Wrench 10896W/B
Sprinkler 51 b January 22, 2010
MICROFAST® AND
I MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Pip Cap and Insert Assembly Copper UNS-C11000 and Stainless Steel UNS-S30400
Pip Cap Attachment (for Sprinklers VK300 and VK325): Brass UNS-C36000
For Teflon® Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for
the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester= M-/W, Black Polyester= M-/B, and Black Teflon®= N
Temperature Suffix (°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G
For example, sprinkler VK300 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06661 BAB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000)
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Upright'and Conventional Sprinklers are available through a network
of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking
Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
January 22, 2010 Sprinkler 51 a
MICROFAST® AND
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE UPRIGHT AND
"IKINCG CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional
(Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers
available in several different finishes, temperature ratings, and K-Factors to
meet design requirements. The special Polyester and Teflon® coatings
can be used in decorative applications where colors are desired. In addi-
tion, these coatings have been investigated for installation in corrosive atmos-
pheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat-
ings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2020
NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16
ABS Certified: Certificate 04-HS407~84l:HJUA
VdS Approved: Certificate G4060054, G4060056, G4880046, G4930039, and G4980020
LPC Approved: Ref. No. 096e/03, TE30401, and TE30872
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, and
0786-CPD-40171
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Chart on page 51d and Design Criteria on page 51e for cULus and FM approval requirements that must be
followed.
3. TECHNICAL DATA
Specifications:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for Viking Technical Data may be found on
use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- http://www.vikinggroupinc.com.
sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent
the deflector. All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page.
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Chart OFFICE COPY
Nominal K-Factor: Refer to the Approval Chart
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length Refer to the Approval Chart
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06661 B, 06766B, 07060, and 12281. Brass UNS-C84400 for all
other sprinklers.
Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 06661B and 12281. Copper UNS-C19500 for Sprinklers
06665B, 06764B, and 07060. Brass UNS-C26000 for all other Sprinklers. Received
Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter SEP 15 2015
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw Brass UNS-C36000
Form No. F_080488 Replaces page 51 a-e, dated April 25, 2008. (Updated sprinkler materials. Min. operating pressure for
LPC8 and CE approval ONLY is 5 psi (0.35 bar). Added alternate frame material for Sprinklers 066618,
067668, 07060, and 12281. Removed VdSApproval from Sprinklers 066658, 067648, and 14817.)
Sprinkler 41 f March 14, 2008
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE PENDENT
"IKI~ SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
2-1/8" Ceiling Opening Size: 2-1/8"
2-5/16" (58,7 MM) MiniMUM (54 MM)
(54 rw1)
2-1/2" (63,5 MM) Mo.xiriuri
1-1/8" (28,6 MM)
MiniMUM 2"
(44,5 MM) t (50,8 MM) MiniMUM
Mo.xiMUM
t Mo.xiMuM t
t
l ns t o.ll e cl with o_ Microrio. tic
Iris t o.lle d with o thread on
Model E-1 Recessed Escutcheon
Model E-2 Recessed Escutcheon
Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Form No. F_081296 Replaces page 41 a-f, dated October 12, 2007. (Added LPCB Approval and updated CE
Approval for Sprinkler 06666B, Added Dry System note in approval chart for Small Orifice.)
March 14, 2008 Sprinkler 41e
-------i:------------
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE PENDENT
"IKINC; SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 41 d)
cULus List;nq Requirements:
Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
EM Approval Reau;rements:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-BN) and Technical Advisory Bulletins. FM Global
Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F _091699 - Care and Handllng of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Ceiling Opening Size:
2-5/16n (58,7 MM) MiniMUM
2-1/8ll
2-l/2ll (63,5 MM) MO.XiMUM
(54 MM)
W [:r \r
t It:•: ·••ttMtI\r
t 1-3/ 4" t
(44,5 MM) 2" 1-1/2" (38.1 MM)
1-5/8' (50,8 MM) MiniMuM
(41 1'1/"l) ! Mo.xiMUM
_L L
Insto.lled with o.
Pendent Sprinkler sto.ndo.rd 1/8" surfo.ce-
Insto.lled with o. Microfo.st
06662B <VK302) Mounted escutcheon,
Model F-1 Adjusto.ble Escutcheon
Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
Sprinkler 41 d March 14, 2008
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Approval Chart I r.== Temperature KEY J
Microfast® and MicrofastHP® Quick Response Pendent Sprinklers A~ Finish
Escutcheon (~ applicable)
Maximum 175 PSI (12 bat) WWP
Sprinkler Thread Size Nominal Overall Listings and Approvals3
Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.)
1
Part No. NPT BSP U.S. metric2 Inches mm cULus4 FM5 NYC6 VdS LPCB CE ®
Standard Orifice
06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X,B1Y A3X, B3Y A1X, B1Y A3 A3X, B3Y C3X, E3Y13 C3X, E3Y15
Large Orifice
06666B VK352 3/4" 20mm 8.0 115.2 2-3/8" 60 A1X, B1Y A2X, B2Y A1X, B1Y -- A3X cs= --
12104 VK352 3/4" 20mm 8.0 115.2 2-1/4" 58 -- -- -- G3 -- -- --
06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 A1X,B1Y -- A1X, B1Y A3 -- -- --
Small Orifice9
06718B10 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X, B1Y A2X A1X, B1Y -- -- -- --
06720B10 VK331 1/2" 15 mm 4.2 60.5 2-1/4" 58 A1X,B1Y -- A1X, B1Y -- -- -- --
06932B VK331 -- 10 mm 4.2 60.5 2-3/8" 60 -- -- -- A3 -- G214 --
Maximum 250 PSI (17 bar) WWP
Standard Orifice
Sprinkler Thread Size Nominal Overall Listings and Approvals3
Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.)
1
Part No NPT BSP U.S. metric2 Inches mm cULus4 FM NYC11 VdS LPCB CE (!)
12282 VK317 1/2" 15mm 5.6 80.6 2-1/4" 58 A1X,B1Y - A1X -- -- -- --
Maximum 250 PSI (17 bar) WWP
Small Orifice9
1229010 VK342 1/2" 15mm 2.8 40.3 2-3/16" 56 A1X,B1Y -- A1X -- -- -- --
Approved Temperature Ratings
Approved Escutcheons
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °c). 200 °F (93 °C), Approved Finishes
X - Standard surface-mounted escutcheon or
and 286 °F (141 °C)
1 - Brass, Chrome-Enloy®, White Poly- the Viking Microfast® Model F-1 Adjustable
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 'F (93 °C)
78 78 12
c - 155 °F (68 °C). 175 °F (79 °C), 200 °F (93 °C), and 286 °F ester · , Black Polyester • , and Black Escutcheon
(141 °C) Teflon®7 Y - Standard surface-mounted escutcheon or
D - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 286 °F 2 - Brass and Chrome-Enloy® the Viking Microfast® Model F-1 Adjustable
(141 °C) 3- Brass, Chrome-Enloy®, White Polyester8, Escutcheon12 or recessed with the Viking
E • 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
and Black Polyester8 Micromatic® Model E-1 or E-2 Recessed
F - 155 °F (68 °C). 175 °F (79 °C), and 286 °F (141 °C)
G - 155 °F (68 °C) Escutcheon
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 FM Approved for use only in wet-pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory
Mutual Engineering and Research Loss Prevention Data Sheets and Technical Advisory Bulletins.
6 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
7 cULus Listed as corrosion resistant.
8 Other colors are available on request with the same Listings and Approvals as the standard colors.
9 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems
only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.
10The sprinkler orifice is bushed.
"Accepted for use, Ci~ of New York Department of Buildings, MEA Number 89-92-E, Vol. 16.
12The Viking Microfas Model F-1 Adjustable Escutcheon is considered a surface-mounted escutcheon because it does not allow the fusible element of the
~rinkler to be recessed behind the face of the wall or ceiling.
13 E Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.
"C € Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40130 and 0786-CPD-40170.
15 ct) MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
March 14, 2008 Sprinkler 41 c
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE PENDENT
"IKINGi SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
-
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating1 Ceiling Temperature2
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings3
: White Polyester, Black Polyester, and Black Teflon®
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
' Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pages 41 d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
························~
. . • )?•· •<
Sprinkler \./rench
12144 \.//BllOI( for
insto-lling coo ted
ond/or recessed
pendent sprinklers Co.refully slide the
-~'~ •---
with protective co.ps. .-~---......- L---Lt ---------• wrench sidewo.ys
â—„ o.rounci the protective
't- ~ - --- - -t-1"
I I I I co.p, ensuring engo.ge-
t t I L., I ._I J I
nerrt with the sprinkler
wrench flo. ts.
**A 1/2° r-c tchet is required
(not o. vo.ilo.ble Fr-on Viking).
Figure 2: Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers
Sprinkler 41 b March 14, 2008
MicrofastHP® QUICK
TECHNICAL DATA
\IIKINC; RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
For Teflon® Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking pt ice list.)
Order Microfast® and MicrofastHP® Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin-
ish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-/W, Black Polyester= M-/B, and Black Teflon®= N
Temperature Suffix (°Fl°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G
For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06662BAB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000).
B. Wrench for coated and/or recessed sprinklers: Part No. 12144W/B** (available since 2003)
NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B.
**A½" ratchet is required (not available from Viking).
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Pendent 'vJrench
Sprinklers are available through a network of domestic and Flo.ts
international distributors. See The Viking Corporation web site for Protective
the closest distributor or contact The Viking Corporation. Sprinkler
Co.p
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule
or contact Viking directly.
10896 co
Figure 1:
Standard Sprinkler Wrench 10896W/B
March 14, 2008 Sprinkler 41 a
MicrofastHP® QUICK
TECHNICAL DATA
RESPONSE PENDENT
"IKINCG SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are small,
thermosensitive, glass-bulb spray sprinklers available in several different finishes and
temperature ratings and K-Factors to meet design requirements. The special Polyester
and Teflon® coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive at-
mospheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat-
ings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2020
NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16
ABS Certified: Certificate 04-HS407984C-PDA
VdS Approved: Certificate G4040095, G4040097, G4060056, G4060057, G488UU4b, G4930038, and G498002·I
LPC Approved: Ref. No. 096e/03 and 096e/04
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40130, and
0786-CPD-40170
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Chart on page 41d and Design Criteria on page 41e for cULus and FM approval requirements that must be
followed.
3. TECHNICAL DATA
Specifications:
Available since 1987. Viking Technical Data may be found on
Minimum Operating Pressure: 7 psi (0.5 bar) The Viking Corporation's Web site at
Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for http://www.vikinggroupinc.com.
use with water working pressures ranging from the minimum 7 psi The Web site may include a more recent
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- edition of this Technical Data Page.
sure (HP) sprinklers can be identified by locating "250" stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Chart
Nominal K-Factor: Refer to the Approval Chart
Glass-bulb fluid temperature rated to -65 °F (-55 °C) OFFICE COPY
Overall Length: Refer to the Approval Chart
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 06662B, 06666B, 06765B, and 12104. Copper
UNS-C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Received
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 SEP 15 2015
Pip Cap Attachment: Brass UNS-C36000
Ejector Spring (for Sprinkler 12104): Stainless Steel
Form No. F _081296 Replaces page 41a-f, dated October 12, 2007. (Added LPCB Approval and updated CE
Approval for Sprinkler 066668, Added Dry System note in approval chart for Small Orifice.)
~- ..
Sprinkler 105f October 25, 2010
QUICK RESPONSE ,
TECHNICAL DATA
"IKIN(; DRY PENDENT SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Deflector o. t
Minir-iurvi ciistunce
below ceiling
Up to 2' (50,8 MM)
o.djustMent o. vo.llo.ble.
40"F (4"C)
30'F c-i-c: Note,
20"F <- 7'C) 4 (100) 0 MiniMuM ceiling opening die.Meter: To loco. te the
1-3/4' (44,5 MM) deflector o. t
the
IO"F <-12"C) 8 (203) 1 <25.4) 0
Mo.xiMUM ceiling opening die.Meter: MlnlMuM dlsto.nce
0"F <-18"C) 12 (305) 3 <76) 0 2-1/ 4' (57 MM), below the ceiling,
-l0"F <-23"C) 14 (356) 4 (102) 1 (25.4) with no upwo.rd
-20"F <-29"C) 14 <356) 6 <152) 3 (76) ,---------- Seo.l the cleo.ro.nce o.djustMent a.
vo.il-
spo.ce a.round the o.ble, orcler
the
-30"1': <-34"C) 16 (406) 8 <203 4 (102) dry pendent sprink-
-40"F (-40"C) 18 (457) 8 (203) 4 sprinkler to o. void leo.k- ler 1' (25.4 MM)
-50"F <-46"0 20 (508) 10 <254 6 o.ge of o.ir Into the shorter tho.n
the
protected o.reo. o.ncl 'A' dlne nston.
-60"F <-5l"C) 20 (508) 10 (254 6
consequent for Mo. tion
of conclenso.te a.round
the fro.Me, which could Note:
inhibit opero. tion or To loco. te the
Sleeve finish co.use preMo.ture opero.- 4-7 /16' deflector o.t the
1-1/2' (38.J MM) -- -- no t c+ie s tion. Refer to Figure (112,7 MM) no xlnun c:Hsta.nce
die.Meter escutcheon 7 below. below the celling,
Ma.xlMUM with no downwo.rcl
If hunldl t y o.ncl t enp- o.djus tnent o.vo.il-
ero. ture clifferentio.l o.ble, orcler the
3-1/16'
(Protected Areo.) co.uses conclenso.t~n _l dry pendent sprink-
(77.8 MM) on the exposed dry ler 1' (25.4 MM)
sprinkler, consider longer tho.n the
wro.pping the exposed Deflector o. t "A" dlnerislon.
bo.rrel with insulo. tion, MO.XiMUM disto.nce
foo.M insulo. ting to.pe, below ceiling
or equivo.lent.
llEThe protected o.reo. refers to the o.reo. below the ceiling.
The omblerrt teMpero.ture is the teMpero.ture o.t the clischo.rge encl of the sprinkler.
For protected o.reo. teMpero.tures tho.t occur between the vo.lues listed, use the next cooler teMpero.ture.
**The MiniMUM required bo.rrel length Is not the so ne o s the 'A' dlMension. Refer to Figures 3-5 for the 'A' diMension.
NOTE: Exposed MiniMUM bo.rrel lengths o.re inclusive up to 30 Mph wind velocities.
Figure 6: Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area
(Adjustable Standard Dry Pendent Sprinkler is Shown)
Seo.l Po.rt No. 13864
(or equivo.lent Method)
Seo.l
Cleo.re.nee Insulo.ted
Opening Ceiling
Dry Sprinkler Seo.l on the Dry Sprinkler Seol vlithin the Ceiling
Exterior of the Ceiling
Figure 7: Dry Sprinkler Seal (Adjustable Standard Dry Pendent Sprinkler is Shown)
Form No. F_031793 Replaces page 105a-f, dated August 12, 2010.
( Revised sprinkler materials.)
October 25, 2010 Sprinkler 105e
QUICK RESPONSE
TECHNICAL DATA
"IKING:i DRY PENDENT SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 2 (FM) I r- remperatuni KEY J
Quick Response Dry Pendent Spr.inklers A+.-x Finish
Maximum 175 PSI (12 bar) 'lf,/WP 1X+-Escutcheon(lfappllcable)
Sprinkler Base SIN Thread Size Nominal K-Factor2 Order Length Increment FM Approvals4
Style
Part No.1 NPT BSP U.S. metric3 Inches mm (Refer also to Design Criteria below.)
t--_08_3_8_3_U_--, VK 1" -- 5.6 80.6 1/2" 12.7 A1
176 Adjustable Standard
16457U -- 25 mm -- 80.6 1/2" 12.7 A1
...___08_3_8_5_U_---< VK 1" -- 5.6 80.6 1/4" 6.35 B2
180 Adjustable Recessed
16453U -- 25mm -- 80.6 1/4" 6.35 B2
08387U 1" -- 5.6 80.6 1/2" 12.7 A3
>----16_4_5_5_U_---< VK 172 Plain Barrel
-- 25mm -- 80.6 1/2" 12.7 A3
Approved Temperature Ratings Approved Finishes and "A" Dimensions
1 - Brass, Chrome-Enloy®, or White Polyester sprinkler with a Brass, Chrome-Enloy® or White
A - 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C),
Polyester Sleeve and Escutcheon with "A" dimensions 1-1 /2" to 45-1 /2" (38.1 mm to 1, 156 mm)
and 286 °F (141 °C) 2 - Brass, Chrome-Enloy®, or White Polyester with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm)
B - 155 °F (68 °C), 175 °F (79°C), and 200 °F (93 °C) 3 - Brass, Chrome-Enloy®, or White Polyester with "A" dimensions 3" to 4 7" (76.2 mm to 1,194 mm)
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths ("A" Dimensions indicated above).
3 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
4 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any ad-
ditional approvals.
Dl;SIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-BI tees. When selecting other CPVC fittings,
contact Viking Technical Services.
FM Approval Requirements:
The Dry Pendent Sprinklers in the Approval Chart above are FM Approved as quick response Non-storage standard spray sprinklers as indicated in
the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (includ-
ing 2-0) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but
not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and
deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F _091699 - Care and Handling of Sprinklers. Also refer to page DRY1-3
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the
latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other simi-
lar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
For "A" Dtne rrslon
I. De t er-nme the distnnce
froM foce of tee to 'A" DiMension,
the finished ceiling.
DeterMine the
2. Round to nenrest 1/4'
(6.35 distance f'rori
MiniMuM ceiling opening, MM) between Outside the f'oce of the
2-1/8" (54 MM) dio ne t er-. 3-1/4' (82.5 MM) nnd diorieter:
47-1/2' (1,207 MM). tee to the bose
1-5/16' of the sprinkler.
MoxiMuM ceiling opening, (33.4 MM) ~Roundup to the
2-1/2" (63.5 MM) dinMeter. NOTE, Sprinkler will be (sor1e os next highest 1/2'
recessed o ppr-o xino tely
I" (25 MM) <t2.7 MM) incre-
5/16" <7.9 MM) obove
Schedule Ment between 3'
the finished ceiling with 40 pipe). <76.2 MM) oncl
Ad ju s trne n t: 5/8' (15.8 MM) vertical 4 7' (1,194 MM).
o d jus tmen t n vniloble.
5/16' (7.9 MM)~\==
5/16' <7.9 MM) ----i_ ~~, --'al J
J C = :;_ __ - - Finished ceiling
1-5/8'
MiniMUM' 1· <25.4 MM)__/ Li (48.3 MM)
MnxiMUM' 1-5/8' (42.l MM) i=-3-1/16' (77.9 MM) _J_
Figure 4: Adjustable Recessed Dry Pendent Sprinkler Figure 5: Plain Barrel Dry Pendent Sprinkler
Sprinkler 105d October 25, 2010
I QUICK RESPONSE
TECHNICAL DATA
DRY PENDENT SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Cbart 1 (UL) I f.= Temperature KEY
Quick Resp0nse Dry, Pendent Spr,inklers Finish
A~ EscutcheQ!l (ff applicable)
Maximum 175 PSI (12 bar:) WWP
2 Listings and Approvals•
Sprinkler Thread Size Nominal K-Factor Order Length Increment
1 SIN Style (Refer also to Design Criteria below.)
Base Part No. NPT BSP U.S. metric3 Inches mm cULus5 NYC6 VdS LPCB CE
®
08383U Adjustable 1" -- 5.6 80.6 1/2" 12.7 A1 A1 -- -- -- --
VK176
16457U Standard -- 25mm -- 80.6 1/2" 12.7 A1 -- -- -- -- --
08385U Adjustable 1" -- 5.6 80.6 1/4" 6.35 82 82 -- -- -- --
VK180
16453U Recessed -- 25 mm -- 80.6 1/4" 6.35 82 -- -- -- -- --
08387U Plain 1" -- 5.6 80.6 1/2" 12.7 A3 A4 -- -- -- --
VK172
16455U Barrel -- 25mm -- 80.6 1/2" 12.7 A3 -- -- -- -- --
Approved Finishes and "A" Dimensions
Approved Temperature Ratings
A - 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C), 1 - Chrome-Enloy® or White Polyester7 sprinkler with a Chrome-Enloy® or White Polyester Sleeve
and Escutcheon with "A" dimensions 1-1 /2" to 45-1 /2" (38.1 mm to 1, 156 mm)
and 286 °F (141 °C)
B - 155 °F (68 °C), 175 °F (79°C), and 200 °F 2 - Chrome-Enloy® or White Polyester7 with "A" dimensions 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm)
3 - Chrome-Enloy®, Brass, or White Polyester7 with "A" dimensions 3" to 47" (76.2 mm to 1,194 mm)
(93 °C)
4 - Chrome-Enloy® or Brass with "A" dimensions 3" to 47" (76.2 mm to 1,194 mm)
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths ("A" Dimensions indicated above).
3 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
4 This. chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
5 Listed by Underwriter's Laboratories for use in the U.S. and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 15.
7 cULus Listed as corrosion resistant.
DESIGN CRITERIA - UL
(Also refer to AJ;)proval Cl:lart 1 above.)
NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-BI tees. When selecting other CPVC fittings,
contact Viking Technical Services.
i.!JLY!i li§liag R!;!gyir!i!m!rn1!2:
Standard Dry Pendent Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for
standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies.
• The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F _091699 - Care and Handling of Sprinklers. Also refer to page
DRY1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.
October 25, 2010 Sprinkler 105c
QUICK RESPONSE
TECHNICAL DATA
'\IIKINCG DRY PENDENT SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Spr.lAkler Temperature Sprinkler Nominal Maximum Ambient
Classifieatior:1 Temperature Ratin91 2 Bulb Caler
Ceiling l'emperature
Ordinary 155 °F (68 °C) 1 oo °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome-Enloy® (patents pending), and White Polyester
Corrosion-Resistant Coating3·4: White Polyester in all temperature ratings
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant Polyester coating has passed the standard corrosion test required by the approving agencies indicated in Approval
Chart 1. These tests cannot and do not represent all possible corrosive environments. Note: This coating is NOT corrosion proof. Prior to
installation, verify through the end-user that the coating is compatible with or suitable for the proposed environment. Polyester coating is
applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester coatings.
4 When installed in some corrosive environments, the Polyester finish may change color. This natural discoloration over time is not in itself
an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or
tested as described in NFPA 25 on a more frequent basis.
For "A' Dlne nsloro 1. De t er nlrie the clisto.nce froM the fo.ce of the tee to the finished ceiling,
2. Rouncl to the ne o r e s t 1/2" 02,7 MM) between 1-1/2" o rid 45-1/2" (38.1 MM o.ncl 1,156 MM),
NOTE: The cleflector will be l or o t e d o.ppr-oxlno t et y 3-7 /16" (87.3 MM) below the ceiling,
with 1" (25.4 MM) upwo r-d o.ncl l' (25.4 MM) downwo r d o d ju s tmerrt.
Deflector o. t MiniMUM
clisto.nce below ceiling.
NOTE:
To loco. te the cleflector
o t the MiniMul"l dls to.nce
below the ceiling, with
no clownwo.rcl o.cljustMent
available, order the
MiniMUM ceiling opening
clry penclent sprinkler
clio.Meter: 1-3/ 4" (44.5 MM).
1" (25.4 MM) shorter
Mo.xiMUM ceiling opening
+ho n the 'A' dlne nslcn.
clio.Meter: 2-1/ 4" (57 MM).
13/16" NOTE:
(20,6 MM) To loco. te the deflector
o. t the no xlnun clisto.nce
below the ceiling, with
-- Sleeve finish no clownwo.rcl o.cljustMent
(38.1 Ml"l) Mo.tches escutcheon. available, order the
dlo ne t er-
clry penclent sprinkler
3-1/16" 1" (25.4 MM) longer
(77,8 MM) t ho n the "A" cliMension.
Deflector o. t Mo.xiMUM
clisto.nce below ceiling.
Figure 3: Adjustable Standard Dry Pendent Sprinkler
Sprinkler 105b October 25, 2010
QUICK RESPONSE
TECHNICAL DATA
DRY PENDENT SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Dry Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish, the appropriate suffix
for the temperature rating, and then the suffix for the length ("A" dimension) to sprinkler base part number. Order in a specific
length noted as the "A" dimension. The "A" dimension is the distance from the face of the fitting (tee) to the desired finished
surface of the ceiling.
These sprinklers are listed and approved in lengths from 1-1 /2" to 45-1 /2" (38.1 mm to 1, 156 mm) for the adjustable standard style, 3" to
47" (76.2 mm to 1,194 mm) for the plain barrel style, and 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm) for the adjustable recessed style.
Lengths exceeding the standard lengths are available, with no approvals, on a "made-to-order" basis: Recessed Dry Pendent up to
65-1/2" (1,664 mm). Adjustable Standard Dry Pendent up to 63-1/2" (1,613 mm). Plain Barrel Dry Pendent up to 65" (1,651 mm).
Contact the manufacturer for more information.
Finish Suffix: Brass = A, Chrome-Enloy® = F, and White Polyester = M-/W
Temperature Suffix (°F/°C): 155°/68° = B, 175°/79° = D, 200°/93° = E, 286°/141° = G
For example, sprinkler VK176 with a Chrome finish and a 155 °F/68 °C temperature rating, and "A" length of 1 O" = Part No.
08383UFB10.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the
Viking data book.) \Jrench
Sprinkler Wrenches: Flot
Protective
A. Standard Wrench: Part No. 07297W/B (available since 1991)
Sprinkler
B. Wrench for recessed sprinklers: Part No. 07565W/B**
Shield
(available since 1991)
**A½" ratchet is required (not available from Viking).
Sprinkler Guard: Chrome, with no listings or approvals, for installation
on dry pendent sprinklers made after May 1994 only (Part No. 08954).
Replacement Escutcheons:
A. Adjustable Standard Dry Escutcheon: Base Part No. 07741
B. Recessed Dry Escutcheon Cup: Base Part No. 05459A VIKING o,2s1 Q
4. INSTALLATION
Refer to appropriate NFPA Installation Standards. Figure 1: Standard Sprinkler Wrench 07297W/B
5. OPERATION
During fire conditions, the heat-sensitive liquid in
the glass bulb expands, causing the glass to
shatter, releasing the internal parts to open the
waterway. Water flowing through the sprinkler
orifice strikes the sprinkler deflector, forming a
uniform spray pattern to extinguish or control the fire.
Sprinkler \./rench
6. INSPECTIONS, TESTS & MAINTE' NANCE 07565\./IB** Must be
Refer to NFPA 25 for Inspection, Testing and usecl for insto_lling
recessed ciry
Maintenance requirements. sprinklers
7. AVAILABILITY
The Viking Quick Response Dry Pendent Sprink- Step 2, Co_refully press
the wrench upword o_nd
ler is available through a network of domestic turn slight! y to ensure
and international distributors. See The Viking engogeMent with the
Corporation web site for the closest distributor sprinkler wrench flo ts.
or contact The Viking Corporation. Step [, Co.r e Fuu y nA 1/2" r o tchet is ,
slicle the wrench required (Not o vnil- ] l l l
sidewo_ ys cr ound the oble froM Viking.)
8. GUARANTEE sprinkler deflector.
For details of warranty, refer to Viking's current
Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Pendent Sprinklers
list price schedule or contact Viking directly.
October 25, 2010 Sprinkler 105a
QUICK RESPONSE
TECHNICAL DATA
'\IIKII\IGj DRY PENDENT SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Quick Response Dry Pendent Sprinklers are thermosensitive spray sprinklers suit-
able for use in areas subject to freezing. The sprinklers are designed for dry systems and
preaction systems where it is necessary to prevent water or condensation from entering
the drop nipple before sprinkler operation. They may also be installed in spaces subject to
freezing and supplied from a wet system in an adjacent heated area.
Viking Quick Response Dry Pendent Sprinklers are available in various finishes and tem-
perature ratings to meet design requirements. The special Polyester coating has been
investigated for installation in corrosive atmospheres and is cULus listed as corrosion
resistant as indicated in Approval Chart 1. (Note: FM Global has no approval classification
for Polyester coatings as corrosion resistant.)
NOTE: When installed in some corrosive environments, the Polyester finish may
change color. This natural discoloration over time is not in itself an indication of
corrosion and should not be treated as such. All sprinklers installed in corrosive
environments should be replaced or tested as described in NFPA 25 on a more frequent basts.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2013 and 2015
NYC Approved: MEA 89-92-E Volume 15
Refer to Approval Chart 1 and Design Criteria on page 105d for cULus Listing requirements, and refer to Approval Chart 2 and
Design Criteria on page 105e for FM Approval requirements that must be followed.
3. TECHNICAL DATA Viking Technical Data may be found on
Specifications: The Viking Corporation's Web site at
http:/lwww.vikinggroupinc.com.
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: 175 psi (12 bar). Factory tested pneumatically to The Web site may include a more recent
100 psi (6.89 bar) edition of this Technical Data Page.
Thread size: 1" NPT or 25 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric*) for all listed and approved lengths.
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown
by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Material Standards: OFFICE COPY
Frame Casting: Brass UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Compression Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31400 or UNS-C31600
Pip Cap Adapter: Brass UNS-C36000
Orifice: Copper UNS-C22000 or UNS-C11000
Tube: ERW Hydraulic Steel Tube
Support (Internal): Stainless Steel UNS-S30400
Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish
Barrel End and Threads: QM Brass
Received
Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800
Escutcheon Materials:
Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800 SEP 15 2015
Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080
Form No. F _031793 Replaces page 105a-f, dated August 12, 2010.
(Revised sprinkler materials.)
BUILDING INSPECTION REPORT - Fire Sprinkler
Permit No. 786
Address: 123 E Burke Ave
Contractor: Commercial Fire Protection, Inc
Owner: SHOPPING CENTER PROP OF ARLINGTON LLC
Date: 11/4/2015
~ APPROVAL â–¡ PARTIAL APPROVAL
â–¡ CORRECTION â–¡ OTHER
INSPECTION: Sprinkler
FIRE SPRINKLER: 181 HEADS: 181
FACP ACCESS: 181 SPARE HEADS: 181
SPRINKLER ROOM ACCESS: 181 DOUBLE CHECK: 181
PIPING: 181 HYDRO: â–¡
SUPPORTS: 181 FLOW: 181
CONCEALED SPACES: â–¡ TAMPER: 181
ANNUNCIATION: 181 ALARM/BELL: 181
Date: 11/4/2015 Inspector: Kevin Olander
CITY OF ARLINGTON
238 N. OLYMPIC AVE - ARLINGTON, WA. 98223
PHONE; (360) 403-3551
BUILDING PERMIT
Address: 123 E. Burke Ave Permit#: 786
Parcel#:00461803000100 Valuation: 3 7000.00
OWNER APPLICANT CONTRACTOR
Name: SHOPPING CENTER PROP OF
Name: Commercial Fire Protection, Inc Name: Commercial Fire Protection, Inc
' ARLINGTON LLC
Address: PO BOX 271 Address: I 7 199 Bennett Rd Address: I 7 I 99 Bennett Rd
City, State Zip: BURLINGTON, WA 98233 City, State Zip: Mount Vernon, WA 98273 City, State Zip:Mount Vernon, WA 98273
Phone: Phone: 360-848-9093 ext 113 Phone: 360-848-1533
MECHANICAL CONTRACTOR PLUMBING CONTRACTOR
Name: Name:
Address: Address:
City, State, Zip: City, State, Zip:
Phone: Phone:
LIC #: EXP: LIC#: EXP:
JOB DESCRIPTION
PERMIT TYPE: Fire Sprinkler CODE YEAR:
STORIES: CONST. TYPE:
DWELLING UNITS: OCCGROUP:
BUILDINGS: OCC LOAD:
PERMIT APPROVAL
I AGREE TO COMPLY WITH CITY AND ST A TE LAWS REGULA TING CONSTRUCTION AND IN DOING THE WORI<. AUTHORIZED
THEREBY; NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO
WORKMEN'S COMPENSATION INSURANCE AND RCW 18.27.
THIS APPLICATION IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER DEPUTY AND ALL FEES ARE PAID.
BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL
BEEN GRANTED. IBCI 10/IRCI 10.
Released By Date
CONDITIONS
Adhere to approved plans
THIS PERMIT AUTHORIZS ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY
CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS, MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION.
PERMIT FEES
Date Description Fee Amount
9/16/2015 Fire Review Fee $100.00
9/16/2015 Fire Sprinkler Fee $697.35
Total Due: $797.35
Total Payment: $0.00
Balance Due: $797.35
CALL FOR INSPECTIONS
BUILDING (360) 403-34 I 7
'When calling for an inspection please leave the following information:
Permit Number, Type of Inspection being requested, and whether you prefer morning or afternoon
- UIV F~~ / CJO. c!JO
f{ r97. ~~
Permit Information
Date 9/15/2015
Permit Number 786
Project Name Grocery Outlet
Applicant Name Commercial Fire Protection, Inc
Applicant Address 17199 Bennett Rd
City, State, Zip Mount Vernon, WA 98273
Contact Della Dellinger
Phone 360-848-9093 ext 113
Email della@cfirepro.com
Permit Type Fire Sprinkler
Site Address 123 E. Burke Ave
Valuation 37000.00
Status Applied
Permit Issued
Permit Expires
Square Feet 0
Type of Construction/Occupancy Load
Number of Stories 0
Proposed Use Fire Sprinkler Addition
Assigned To Amy Rusko
Property Information Owner Information
Parcel#: 00461803000100 SHOPPING CENTER PROP OF ARLINGTON LLC
SHOPPING CENTER PROP OF ARLINGTON LLC PO BOX 271
123 E BURKE AVENUE BURLINGTON, WA 98233
Contractors
Contractor Name Primary Contact Phone Email Contractor Type License License#
Commercial Fire Protection, Inc ~60-848-1533 CONTRACTOR COMMEAD961 LS
Review
Date I Type I Description I Tarqet Date I Completed Date I Assiqned To I Status
9/15/2015 !Fire Sprinkler I 19/18/2015 I !Kevin Olander Un Review
Uploaded Files jUpload File..:]
Date File
9/15/2015 2:51 :00 PM 123 Sorinkler Soecs.odf )<
9/15/2015 2:51:00 PM 123 Hvdraulic Calculations.odf ,,. I<
9/15/2015 2:51 :00 PM 123 Annlication.odf
~ FIRE SPRINKL.ER
PERMIT APPLICATION
Department of Community & Economic Development
City of Arlington • 18204 59th Ave NE • Arlington, WA 98223 • Phone (360) 403-3551
THIS APPLICATION MUST BE ACCOMPANIED BY THREE (3) SETS OF COMPLETE AND SCALED PLANS, THREE
(3) SETS OF HYDRAL/C CALCULATIONS, THREE (3) SETS OF EQUIPMENT SPECIF/CATIONS FOR EACH FIRE
SPRINKLER PERMIT APPL/CATION. INCLUDE ELECTRICAL PLANS WHERE APPLICABLE. ALSO INCLUDE
SPECIF/CATION SHEETS, WIRING DIAGRAMS (POINT TO POINT WIRING), AND ALL OTHER INFORMATION ON
ALL EQUIPMENT TO BE INSTALLED PRIOR TO INSTALLATION.
Type of Permit: D New Fire Sprinkler [j] Fire Sprinkler Add/Alt D Underground Fire Line
123 E. Burke Ave
Project Address:------------------- Parcel ID#:
Project Valuation: 36963.00 Number of Heads: _2_9 _ Building Area (Sq Ft): _1_8_,8_0_0 _
Owner: Shopping Center Properties of Arlington Phone Number: _
Address: P.O. Box 271 City: Burlington State: WA Zip Code: _9_8_2_3_3 _
Contact Person: Della Dellinger Phone Number: 360 848-9093 EXT 113
Cell Phone: E-mail: della@cfirepro.com
----------
Address: 17199 Bennett Rd City: Mount Vernon State: WA Zip Code: _9_8_2_7_3 _
Contractor: Commercial Fire Protection, Inc. Phone Number: 360 848-9093 EXT 113
17199 Bennett Rd Mount Vernon WA 98273
Address: -------------City:------- State: --- Zip Code:--------
. COMMEFP132MM 08/16/16
Contractor's License Number: Expiration:
I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the above-
described prope ill be i cordance with the laws, rules and regulation of the State of Washington.
q }11/ /S
1 Datb
FOR STAFF USE ONLY
SEP 15 2015
£{1),8&
Permit# Accepted By Amount Received Receipt s Date Received
WEB Forms -131 Page 1 of 1 7/1 OCJY
Commercial Fire Protection, Inc. Transmittal
17199 Bennett Road
Mt. Vernon WA 98273-9789 Date: 09/11/2015
360 848-9093
License: COMMEFP 132 MM
To: Arlington Air Port, City Project: 2015535
18204 59th Ave NE Grocery Outlet Tenant Work
Arlington WA 98223 123 E. Burke Ave
Arlington WA 98223
Prepared By: DELLA uELLINGER
Item Quantity Description
1 3 Plans & Cales for Approval
2 3 Sprinkler Head Submittals
3 1 Permit Application
Notes
Received
Please sign and date this form as proof that you are in receipt of the above listed items.
Return form to Commercial Fire Protection, Inc. SEP 15 2015
Signed: _ Date:
0 MMERCIAL FIRE PRrJECTION, INC.
17199 Bennett Road • Mt Vernon, Washington 98273
Phone (360) 848-9093 • Fax (360) 848-1072
License# COMMEFP132MM
HYDRAULIC CALCULATION INFORMATION SHEET
PROJECT NAME GROCERY OUTLET T.I. JOB NO. 2015535
DATE 9/7/15
ADDRESS 123 EAST BURKE AVENUE BY MIKE HINTON
ARLINGTON, WA 98223
SYSTEM DESIGNATION: DRY SYSTEM #1
HAZARD DESCRIPTION: EXTERIOR WALKWAY
HAZARD CLASS PER NFPA 13: LIGHT HAZARD
SPECIFIC RULING: PER SECTION 11.2.3.3.7
.10 GPM/SQ.FT. OVER 5 SPRINKLERS
RULING MADE BY: OF
DENSITY: GPM OVER THE MOST HYDRAULICALLY REMOTE SQ. FT.
ALLOWANCES INCLUDED IN CALCULATIONS: ADDED AT:
INSIDE HOSE O GPM
OUTSIDE HOSE 100 GPM NODE0
IN-RACK SPRINKLER DEMAND N/A GPM
SYSTEM TYPE: DRY TOTAL NUMBER OF SPRINKLERS THIS SYSTEM 10
"C" FACTOR OVERHEAD: 100 "C" FACTOR UNDERGROUND : 140
MAXIMUM ACTUAL AREA OF COVERAGE PER SPRINKLER: 90 SQUARE FEET
SPRINKLER MANUFACTURER: VIKING MODEL: QR TEMPERATURE: 155 ° F
K-FACTOR: 5.6 SIN#: VK300
WATER SUPPLY: ELEVATION OF TEST: 0
STATIC 80 PSI DATE OF TEST: N/A
RESIDUAL 20 PSI DATA PROVIDED BY: ARLINGTON PUBLIC WORKS DEPARTMENT
FLOW 2000 GPM LOCATION OF TEST: SITE
·------WASHINGTONSTATE.------ ..
I CERTIFICATE OF COMPETENCY I
I FIRE PROTECTION SPRINKLER SYSTEMS I
I Mike Hinton ...---. I
I 7358-0100-C Level 3 Eliplres I
SUMMARY I Commercial Fire Protection, Inc. 12/31/15 1
I COMM.E~P132L I
175.39 GPM REQUIRED AT 29.42 PSI 1 dd,L k cr11J1s 1
I Slanalllre D918 I
AT CONNECTION TO CITY WATERMAIN ·-·--------------------~
(INCLUDING 100 GPM FOR TOTAL HOSE STREAMS) CITY OF ARLINGTON
csli!tJfUiltlGi~ <6'f.MiENT
Received APPROVED
OFFICE COPÂ¥ 10 201s
NO CHANGES AUTHORIZED
UNLESSAPPROVEOBYTHI
BUILDING INSPECTOR
N
u
(I) O>- (I)
ro ro
Cl. 0
0
0
00 .....
,-....
00
0
C')
0
0
0 c.o .....
~ :::>
:r:
z
E
C1l
.c
"O
C:
~
.....
0
..... .....
0
.....
$
"'"
::,
0
0::
- LO
~
0 .....
I o<
~z
I s:
0
_J
u..
....
0
:5 Q)
I 0
0 .....
0. E
0
(.)
I 0
0
0 00
0
000
OONN
i!!
....... :::,
:.) (I) (/) I 0
_., L.. (/):::: 0
:::, (I) 0 c.o
Q) (/) (/) Cl. L.. u.. -
2: .. ~--
::::, 2::-a. gJ gJ
I 0
.) §:.~ :Q :Q 0
>, :::,- (/) (/) N "'"
0.. (/)~ (I) (I) .... I 0 c 0
L.. (/) 0:: 0:: u 0
C. $• I
::::, CU..- N I N .... N
I) 3;:uuu C
.... 0 0 0 0 0 0
Q) -2:- LO C') N ..... 0 0 0 0 0 0 0 0 0 0
.... ro 0 ..... ..... "'" ..... ..... ..... ..... 0) 00 I'- c.o LO "'" C') N .....
> Cl. 0:: LlJ (/) (/) :::i 0:: LlJ
>
0 N
N
co
(1) Cl- (1)
ro ro
a.. 0
<D 0 ..-
0 '<t CO CO
N ..- r--- 0
..- N N<D<O
0 cr, N 0
N LO LO
!'- co
co
0
("')
0
<(
(/)
<D
::::,
I
N LO
:i
LO cr, ..- N N
E
ro
.c:
"O
C:
~
..-
..-
..-
2
:::,
0
0::
c.j
C
u
Q)
~
"O
N
I >,
.0 >,
ti)
0 '<tOCO
E
~
Cl e
0 C"l O <D
a..
....
Q)
'S
0.
0 NOLO
E
0
(_)
0 NO'<t
0 ..-OC"l
2:-
ro
E
E
:::,
I)
C 2:-
Cl)
Cl) -o (I) E ro E
:J C <llz <ll E
Cl) ~ :::,
C) CJ)
C ...J >
Ol (I)
~ ·- C ..c '- (I) -~
.=!:! ..c Ol C:
L Li.<( <( co Cl w (.9 I- :::,
Pressure / Flow Summary - STANDARD
"}
Page 3
Date
Node Elevation K-Fact Pt Pn Flow Density Area Press
'No. Actual Actual Reg.
0 0.0 29.42 na 100.0
1 1.0 28.98 na
2 5.0 22.25 na
3 10.75 19.76 na
4 10.75 19.06 na
5 2.79 21.8 na
6 3.67 18.71 na
7 4.67 18.03 na
101 10.0 5.6 7.75 na 15.58 0.1 90 7.0
102 10.0 5.6 7.36 na 15.19 0.1 90 7.0
103 10.0 5.6 7.13 na 14.96 0.1 90 7.0
104 10.0 5.6 7.03 na 14.85 0.1 90 7.0
105 10.0 5.6 7.0 na 14.82 0.1 90 7.0
The maximum velocity is 6.35 and it occurs in the pipe between nodes 5 and 6
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
')
Page 4
Date
\ Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 11c" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Lri. Total Pf Pn
0 -75.40 8.27 1T 55.354 50.000 29.424 Qa = 100
to 140.0 1G 6.326 90.148 -0.433
1 -75.4 0.0 1E 28.468 140.148 -0.007 Vel = 0.45
0.0 8.249 0.0 5.000 28.984
to 120.0 0.0 0.0 -6.732 * Fixed loss = -5
2 -75.4 0.0 0.0 5.000 0.0 Vel = 0.45
2 0.0 8.249 1A 34.061 5.750 22.252
to 120.0 0.0 34.061 -2.490
3 -75.4 -0.0001 0.0 39.811 -0.003 Vel = 0.45
3 0.0 3.068 1T 15.0 50.000 19.759
to 120.0 3E 21.0 36.000 0.0
4 -75.4 -0.0082 0.0 86.000 -0.701 Vel = 3.27
4 0.0 2.469 0.0 30.000 19.058
to 120.0 0.0 0.0 3.447
5 -75.4 -0.0234 0.0 30.000 -0.703 Vel = 5.05
5 0.0 2.203 3E 20.458 32.350 21.802
to 120.0 1T 13.639 34.097 -0.381
6 -75.4 -0.0409 0.0 66.447 -2.715 Vel = 6.35
6 0.0 2.703 1Dge 3.419 1.790 18.706
to 120.0 1B 10.88 14.299 -0.433
7 -75.4 -0.0151 0.0 16.089 -0.243 Vel = 4.22
7 0.0 2.203 SE 24.335 115.000 18.030
to 100.0 0.0 24.334 -2.308
101 -75.4 -0.0573 0.0 139.334 -7.977 Vel = 6.35
101 15.59 2.203 0.0 14.500 7.745 K Factor= 5.60
to 120.0 0.0 0.0 0.0
102 -59.81 -0.0266 0.0 14.500 -0.386 Vel = 5.03
102 15.19 2.203 0.0 14.500 7.359 K Factor= 5.60
to 120.0 0.0 0.0 0.0
103 -44.62 -0.0154 0.0 14.500 -0.224 Vel = 3.76
103 14.96 2.203 0.0 14.500 7.135 K Factor= 5.60
to 120.0 0.0 0.0 0.0
104 -29.66 -0.0073 0.0 14.500 -0.106 Vel = 2.50
104 14.84 2.203 0.0 14.500 7.029 K Factor= 5.60
to 120.0 0.0 0.0 0.0
105 -14.82 -0.0020 0.0 14.500 -0.029 Vel = 1.25
5.60 Qa = 5.60
-9.22 7.000 K Factor = -3.48
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087