HomeMy WebLinkAbout3318 185th Pl Ne Bldg L_BLD1858_2025 ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA014
PERMIT #: 1857, 1858, 1863, 1862 DATE: 5/30/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Interior Wall Footing Reinforcing Steel Dowels Building K and L at Perimeter Foundation Intersections
Holdown Anchor Bolts (5/8" X 14" w/9" Embed) Building Q and P, Center Party Wall (Non-Entry Side of Wall)
Reference Drawing(s): RFI #7, Structural Drawings
Item(s) Inspected Comments
Base Material Condition Satisfactory , Dry Concrete. 57º
Drill Bit Type Carbide Tip, Rotor Hammer w/Vacuum
Hole Diameter/Depth 3/4" X 4"
Hole Cleanliness Clean - Flushed with Water Until Clear/Brushed/Flushed
Anchor Spacing/Edge Distance Per Plan
Anchor Type Grade 60 Deformed Reinforcing Steel
Anchor Diameter/Length 5/8", 44"
Anchor Embedment 4"
Adhesive Type Hilti HY200 R
Adhesive Expiration Date 9/2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the epoxied dowels.
The above dowels were found to conform with the project structural drawings and RFI #7. The dowels were
installed as recommended by the manufacturer’s published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA020
PERMIT #: H-1855, L-1857, K-1858, M-1859 DATE: 9/13/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Anchor Bolts for HDU2 Holdowns at Interior Shear Walls (4) Bolts at Building H, K, & L (6) at Building M
Reference Drawing(s): Structural Drawings and RFI #43
Item(s) Inspected Comments
Base Material Condition Fully Cured Concrete, Dry, 65º
Drill Bit Type Drilled Prior
Hole Diameter/Depth 3/4", 9"
Hole Cleanliness Blown, Brushed and Blown Clean
Anchor Spacing/Edge Distance Per Plan
Anchor Type Galvanized Threaded Rod
Anchor Diameter/Length 5/8", 14"
Anchor Embedment 9"
Adhesive Type Hilti Hit HY-200 R
Adhesive Expiration Date 6/2020
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the installation of the epoxied anchor
for the interior shear walls at the buildings mentioned above. The anchor bolts were found to
conform with the project drawings, RFI and the manufacturer’s published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: AA020
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Photo showing the contractor
using compressed air to clean
one of the drilled holes at
Building L.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: AA020
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
The photo shows the contractor
injecting the epoxy into one of
the drilled holes at Building K.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB030
PERMIT #: 1857, 1858 DATE: 5/1/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building K, Stem Walls, and Column Plinths, Building L, Continuous Footings & Plinth Spread Footings
Sample Location: 2nd Load, Placed at South Half of Building K Stem Walls
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 8.00 19
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 sk. 7/8", Pea. WRA Unit Weight, pcf (C138) NT
Truck/Ticket # C143 / 615944 Air/Mix Temp.,°F (C1064) 53 / 61 TM07
Strength Required 3000 psi at 28 days Field Cure Temperature, °F
Quantity Placed, cy 78.5 Cure Method - Initial / Final Container / Water Tank
Time Batched 10:42 A.M Water Added on Job, gals 0
Time Sampled 11:38 A.M Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
95331 7 05-08 48640 4.00 12.57 3870 TYPE 2:
95332 28 05-29 59680 4.00 12.57 4750 TYPE 2:
95333 28 05-29 57980 4.00 12.57 4610 TYPE 2:
95334 28 05-29 62600 4.00 12.57 4980 TYPE 2:
95335 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to inspect the above items. Except for the
following item the reinforcing steel was in place and was found to conform with the project
structural drawings. The concrete was placed using a boom pump and was mechanically
consolidated.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB030
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The continuous stem wall reinforcement at building K was not continuous at the entry walls due
to a block-out being install for a large pipe. This needs approval from the project engineer.
AMENDED 5/31/19: GeoTest was provided with RFI 56 response accepting the discontinous
rebar. GeoTest will verify during framing inspections that sill anchorage is installed per RFI 56
and code minimums.
Plinth Footing Reinforcement
at Building L
Continuous Footing Reinforcement at Building L
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB033
PERMIT #: 1858, 1859 DATE: 5/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building L, Perimeter Stem Walls, and Entry Column Plinths
Building M, Perimeter Wall Footings and Column Plinth Footings
Sample Location: 1st Load, Building M, Placed at West End of the South Side of the Building
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.00 19
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5sk, 7/8", Pea, WRA Unit Weight, pcf (C138) NT
Truck/Ticket # C139 / 222121 Air/Mix Temp.,°F (C1064) 71 / 70 TM06
Strength Required 3000 psi at 28 days Field Cure Temperature, °F NT
Quantity Placed, cy 75 Cure Method - Initial / Final Container / Water Tank
Time Batched 11:39 A.M Water Added on Job, gals 20
Time Sampled 12:05 P.M Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
95764 7 05-15 51430 4.00 12.57 4090 TYPE 2:
95765 28 06-05 71960 4.01 12.63 5700 TYPE 2:
95766 28 06-05 68490 4.01 12.63 5420 TYPE 2:
95767 28 06-05 72560 4.01 12.63 5750 TYPE 2:
95768 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to inspect the concrete placement at the above
locations. The reinforcing steel was inspected and was found to be in conformance with the
project structural drawings. AMENDED 6/7/19: GeoTest was provided with email acceptance
of the HD’s below as-installed from CG engineering.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB033
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Note at Building L two
holdown anchor bolts at the
building west side were at the
wrong location. The contractor
added the two pictured 7/8"
anchor bolts. The drawings
call for the holdown anchor
bolts to be cast into both the
footing and the stem wall.
Engineer approval is required.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB047
PERMIT #: 1858 DATE: 6/5/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Dave Bufalini
Placement Location: Building L - Exterior Slab-on-Grade
Sample Location: Middle of 1st Truck, East Slab
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.50 30
Mix # 0260A6C Air Content, % (C231) 4.7 26
Mix Description 6 SK, 7/8" Agg., MB Poly997, MB AE90, MB NC534 Unit Weight, pcf (C138) NT
Truck/Ticket # C114 / 223718 Air/Mix Temp.,°F (C1064) 58 / 70 DPB01
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 59-82 DPB01
Quantity Placed, cy 30 Cure Method - Initial / Final Container / Water Tank
Time Batched 6:41 AM Water Added on Job, gals 19
Time Sampled 7:35 AM Water Requested by Miles QC
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
97085 7 06-12 56960 4.01 12.63 4510 TYPE 2:
97086 28 07-03 63420 4.00 12.57 5050 TYPE 2:
97087 28 07-03 65890 4.00 12.57 5240 TYPE 2:
97088 28 07-03 64880 4.00 12.57 5160 TYPE 2:
97089 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: Concrete was placed via pump and was hand finished.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB047
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB048
PERMIT #: 1858 DATE: 6/5/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Dave Bufalini
Placement Location: Building L - Interior Slab-on-Grade
Sample Location: Middle of 1st Truck, East End
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.50 30
Mix # 025506C Air Content, % (C231) NT
Mix Description 5.5 SK, 7/8" Agg., MB Poly 997 Unit Weight, pcf (C138) NT
Truck/Ticket # C183 / 223726 Air/Mix Temp.,°F (C1064) 60 / 70 DPB01
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 59-82 DPB01
Quantity Placed, cy 88 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:56 AM Water Added on Job, gals 12
Time Sampled 8:43 AM Water Requested by Miles QC
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
97090 7 06-12 51340 4.01 12.63 4060 TYPE 2:
97091 28 07-03 65190 4.00 12.57 5190 TYPE 3:
97092 28 07-03 65090 4.00 12.57 5180 TYPE 2:
97093 28 07-03 66300 4.00 12.57 5270 TYPE 2:
97094 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: Reinforcement was found to conform to the approved contract documents.
Concrete was placed via pump and was hand finished.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB048
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Sample Location: 6th Truck, at NW Corner
Field Data:
Truck/Ticket # C059 / 616312 Slump, in. (C143) 6.50
Time Batched 9:33 AM Air Content, % (C231) NT
Time Sampled 10:22 AM Unit Weight, pcf (C138) NT
Air Temperature,°F 65 Water Added on Job, gals 15
Mix Temp.°F(C1064) 69 Water Requested by Miles QC
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
97095 7 06-12 50050 4.01 12.63 3960 TYPE 2:
97096 28 07-03 64190 4.00 12.57 5110 TYPE 2:
97097 28 07-03 66740 4.00 12.57 5310 TYPE 2:
97098 28 07-03 65700 4.00 12.57 5230 TYPE 2:
97099 Hold 00-00 0 0.00 0.00 0
Comments:
Sample Location:
Field Data:
Truck/Ticket # / Slump, in. (C143)
Time Batched Air Content, % (C231)
Time Sampled Unit Weight, pcf (C138)
Air Temperature,°F Water Added on Job, gals
Mix Temp.°F(C1064) Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB048
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD055
PERMIT #: 1858 DATE: 5/23/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Compaction Of: Building L Structural Fill
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 TOG DT/12 145.1 6.8 135.9 1 96 95 P
2 See Figure 1 TOG DT/12 130.1 7.7 121.6 2 102 95 P
3 See Figure 1 TOG DT/12 138.3 7.0 129.2 2 108 95 P
4 See Figure 1 TOG DT/12 152.7 6.6 143.2 1 101 95 P
5 See Figure 1 TOG DT/12 145.8 6.5 136.9 1 96 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4327A PGS w/ Silt and Gravel East Valley Sand & Gravel (D-355) 142.0 6.9 47 ASTM D1557/D4718
2-4283A PGS w/ Gravel Native 119.6 8.7 20 ASTM D1557/D4718
3- 0.0 None
Gauge Make/Model/Serial#: Instro/3500/3052 M/D Standard Count: 411/3078
Comments: Please see page 2 for comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 7 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD055
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
TOG - Top of Grade
GeoTest was on site as requested to provide in-place density testing at the above locations
(Figure 1). All locations and elevations are approximate and were provided by the contractor.
Prior to our arrival, a plumbing trench within the building pad had been backfilled and
compacted with a HO-PAC and plate compactor. Please note that test 3 is indicative of
blending of both native and imported soils. All soils tested on this date exhibited firm and
unyielding conditions.
GeoTest will return for further inspection as requested.
Figure 1. Approximate
in-place density testing
locations.
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: IR019
PERMIT #: 1858 DATE: 6/4/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
INSPECTION OF:
Reinforcing Steel Placement
Comments: GeoTest was on site as requested to inspect the placement of the reinforcing steel at Building L’s
slab on grade and interior footings.
Except for the following item the placement of the reinforcing steel was in place and was found to be in
conformance with the project structural drawings.
About half of the interior footing’s continuous number five bars had too little lap at the splice locations.
The contractor was informed of this nonconformance and said that they would correct it prior to the placement
of the concrete. GeoTest will verify.
AMENDED 6/24/19: Please see CB048 for conforming reinspection.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF056
PERMIT #: 1851, 1858 DATE: 7/9/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing Building L, 2nd Level
Shear Wall Sheathing and HD Strapping Building D, Levels 1 to 3
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 3", 3, 4 and 12" On center
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location MST37 and 48 HD Straps, CMST14 Perf. SW Straps
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items mentioned above.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF056
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Building L 2nd level floor sheathing was found to be in conformance with the project structural
drawings.
Building D exterior shear walls were in progress. All areas were marked at the location
describing the issue and correction.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF058
PERMIT #: 1858 DATE: 7/12/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Building L: 2nd Level Entry Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Inspected Prior
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", 6" & 12"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Yes
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect sheathing at the above shear walls. The sheathing and
fasteners were found to conform to the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF061
PERMIT #: 1858 DATE: 7/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm Sheathing Building L, 3rd Level
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Strdi-Floor, 23/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/2", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items listed above. The sheathing and fasteners at
the above locations were found to conform with the project structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF062
PERMIT #: G-1854, H-1855, J-1856, K-1858 DATE: 7/18/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings, G, H, J, 1st Level
Floor Diaphragm Sheathing Building K, 3rd Level
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" X 2-1/4" (2-1/2" at Diaphragm), Per Plan/SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The above items were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF063
PERMIT #: 1858 DATE: 7/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Walls Sheathing Building L, 1st Level Entry Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", 6 and 12" On Center
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above item. The contractor addressed all items
found prior to our leaving the project. Above items were in accordance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF065
PERMIT #: 1856, 1857, 1858 DATE: 7/23/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 4
CONTRACTOR: Exxel Pacific INSPECTOR: John Silk
Item(s) Inspected Location
Shear Walls Buildings L & K
Roof Sheathing Building J
Reference Drawings: Approved Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Structural Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Shearwall Schedule
Pneumatic or mechanically driven fasteners conform Per General Notes
Nail heads driven flush Acceptable
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above item. The contractor
addressed all items found prior to our leaving the project. Above items were in accordance with
the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF065
CONTRACTOR: Exxel Pacific PAGE #: 2 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF065
CONTRACTOR: Exxel Pacific PAGE #: 3 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF065
CONTRACTOR: Exxel Pacific PAGE #: 4 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF066
PERMIT #: 1858 DATE: 7/24/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Diaphragm Sheathing and Fasteners Building L, 3rd Level
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Strdi-Floor, 23/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/2", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above mentioned items. The sheathing and fasteners
at the above floor diaphragm were in accordance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF067
PERMIT #: 1854, 1858, 1855, 1848 DATE: 7/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing and HD Strapping Building G, All Exterior Locations
Shear Wall Sheathing Building L, 3rd Level Entry Walls
Column Connections to the Foundation Building G and H East Side of the Building at Entry
Interior Framing Building A
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips are in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: See comments on Page 2.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF067
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
GeoTest was on site as requested to inspect the above items. The column connections at
Building G & H and walls at Building L were found to conform with the project drawings.
Building G - Exterior Shear Wall Sheathing: The items inspected will require corrections and
marked at the location.
Building A - Interior Framing: Items still requiring corrections, are as follows; holes in the shear
wall top plates, plumbing, and electrical and oversized holes require strapping.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF074
PERMIT #: J-1856, K-1858, L-1857 DATE: 8/15/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Roof Diaphragm Sheathing Building L
Shear Wall Sheathing & Floor- Floor Straps, Final Inspection Building J, K
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Drawings
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" x 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Over-Driven Nails Were Corrected
Hold down, type, location Floor to Floor and Perf. SW Straps Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. All nonconforming items were addressed
prior to our leaving the job site. Above items were in conformance.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF075
PERMIT #: 1849, 1858 DATE: 8/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shearwalls Building B, All Levels
Final Shear Wall Sheathing and Straps Building L, All Exterior Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D-Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Where Required
Base-plate bolting complies Per SW Schedule
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location See Comments
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
See below for additional comments and photo. AMENDED 8/23/19: Notes on page 2 edited for
accuracy. Items noted were reinspected in LF076 and are conforming.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF075
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Building L: The exterior
sheathing and straps were per
plan except for two wrong
sized HD straps and one
shear wall was missing edge
nails.
Building B: At the interior
shear walls and framing a few
items were found and marked.
The contractor was notified of
all items. GeoTest will return
and reinspect all
nonconformances when
scheduled.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF076
PERMIT #: 1879, 1880, 1852, 1858 DATE: 8/20/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Walls Building E, 1st Floor
Shear Wall Sheathing and Straps- Re-Inspection Building L, Exterior Walls
Roof Diaphragm and Shear Wall Sheathing Garage #15 and #16
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D-Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates 1st Floor at Building E, A35 Clips In Placed Per Plan
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Plan/ SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location BLDG. E HDU Were Per Plan, BLDG. L MST Straps are Now Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items mentioned above.
See below for additional comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF076
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Building L: Reinspection of Exterior Sheathing and Straps. The items listed on report LF075
(dated 8/19/19) have been addressed. The edge nailing and the wrong HD straps have been
corrected and are now in conformance with the project's structural drawings.
Building E: 1st Floor Framing and Interior Shear Walls. The contractor has addressed all items
found prior to our leaving the project. Interior shear walls and framing at the 1st floor of building
E was found to be in accordance with the project's drawings.
Garage #15 & #16. Shear Wall and Roof Diaphragm Sheathing was found to be in
conformance with the project's drawings. All items found were addressed by the contractor.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF093
PERMIT #: Permits Listed Below DATE: 10/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Walls - Reinspection Buildings G, H, J / Permits - 1854, 1855 & 1856
Final Framing and Interior Shear Walls Buildings K, L, M / Permits - 1857, 1858 & 1859
Wall and Roof Sheathing and Framing Garage 10, 11 & 12 / Permits - 1874, 1875, & 1876
BBQ Enclosure Framing - Reinspection BBQ Enclosures 1 & 2 / Permits - 1881 & 1882
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue APA Rated Sheathing, 15/32" (23/32") at Floors) Exp.1
Shear wall/diaphragm length, location Per Plan at Above Shear Walls
Panel edges bear on framing members Fully Blocked
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Per Plan SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site to inspect the above items. See the following page for
comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF093
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo shows the now
installed flat blocking at the
BBQ enclosure. Both BBQ
enclosures are in
conformance with the project
drawings. This item was noted
in report LF091 (dated
10/2/19) as nonconforming.
The contractor has addressed all outstanding items found during GeoTest's previous
inspections and all items found this date during the final framing/interior shear wall inspection
of buildings K, L and M. At the locations on page one of this report; the lateral framing was
found to be in conformance with the project drawings.
SPECIAL INSPECTION SUMMARY
PROJECT: The Villas at Arlington â€Â BLD L JOB #: 18â€0760
ADDRESS: 18506 Smokey Point Blvd, Arlington, WA 98223 DATE: 10â€22â€2019
CLIENT: Villas at Arlington Partners LLLP PERMIT #: 1858
CONTRACTOR: Exxel Pacific PAGE: 1 of 1
This letter summarizes our special inspection and testing efforts for The Villas at Arlington – BLD L
project located in Arlington, Washington. GeoTest’s services took place from October 9, 2018
through October 22, 2019. Our testing and inspections included the following scope of work:
TEST/INSPECTION ITEM REFERENCE
Field Density Moisture Report FD055 and Soil
ï‚· Earthwork
Observation Report SO003
Concrete Break Reports CB030, CB033, CB047
ï‚· Reinforced Concrete
& CB048 and Inspection Report IR019
Lateral Framing Inspection Reports LF056,
 Lateral Framing LF058, LF061, LF063, LF066 – LF067, LF074 –
LF076 & LF093
Adhesive Anchor Inspection Reports AA014 &
ï‚· Proprietary Anchors
AA020
All work requiring special inspection for the project to date has been completed. To the best of
our knowledge the inspected work is in conformance with the approved project plans and
specifications and the applicable workmanship provisions of the International Building Code. All
related laboratory tests performed by GeoTest have met or exceeded the minimum test
requirements.
This is GeoTest’s final special inspection and testing submittal for The Villas at Arlington â€Â BLD L
project. If we can be of further assistance, please contact the undersigned.
Copies: Villas at Arlington Partners LLLP Safe Built
Charles Morgan and Associates LLC The Alliant Company
City of Arlington Anderson, Brian
Exxel Pacific Charles Morgan and Associates LLC Logan Senrud
CG Engineering Technical Director
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Permit #: 1858
Permit Date: 03/09/18
Permit Type: MULTI-FAMILY
Project Name: Villas at Arlington
Applicant Name: Villas at Arlington, LLLP
Applicant Address: 105 Cresent Bay Drive, Suite D
Applicant, City, State, Zip: Laguna Beach, CA 92651
Contact: Carmel Gregory
Phone: 425-778-8500
Email: carmelg@cgengineering.com
Scope of Work: New Multi-Family Development
Valuation: 2503351.89
Square Feet: 23049
Number of Stories: 3
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 11/01/2018
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To:
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
VILLAS AT 137 Multiple Family
31052000100800 3318 185TH PLACE NE
ARLINGTON 101 - 200 Units
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
323A CONSTRUCTION
EXXEL PACIFIC INC 360-734-2872 UBI 601 175 198
TELEGRAPH RD CONTRACTOR
323A CONSTRUCTION Labor and
EXXEL PACIFIC INC 360-734-2872 EXXELPI073KN
TELEGRAPH RD CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
03/09/2018 BUILDING
BUILDING
Fees
Fee Description Notes Amount
Building Plan Review Table 4-2 $10,254.61
Building Plan Review Table 4-2 $177.30
Building Permit Table 4-1 $16,049.09
Park - Community MF Multi-family $35,928.00
Processing/Technology $25.00
State Surcharge - Commercial Commercial Only $25.00
State Surcharge - add'l DU Residential Additional Units $48.00
Traffic Mitigation - C/MF Commercial/Multi-family $31,227.36
Total $93,734.36
Attached Letters
Date Letter Description
09/19/2018 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
03/08/2018 Alliant Capital Ltd. 18506 Bldg. L Check #104500 Kristin Foster $10,254.61
10/11/2018 Fidelity National Title check #26379 Launa Black $83,479.75
Outstanding Balance $0.00
Uploaded Files
Date File Name
10/13/2021 9884989-1858_IC 4.2.2020.pdf
04/15/2020 6521243-Villas Bldg L C of O Signed.pdf
11/01/2018 4145075-1858_Villas Building Permit.pdf
03/09/2018 3141619-Commercial Application - Building L.pdf
SUBMITTAL PACKAGE Page 1
DATE: 1/14/2019
Your Logo Here FOR APPROVAL PACKAGE NUM: 35
PACKAGE REV: 0
Exxel Pacific, Inc. SPEC #: 061753
201808. - Villas at Arlington
To: Dennis Titus From: Nick Santini
CG Engineering PLLC Exxel Pacific, Inc.
250 4th Ave South #200 323 Telegraph Road
Edmonds, WA 98020 Bellingham, WA 98226
We are transmitting the following Submittal Package Number: “35â€, Revision: “0†Description:
“Prefabricated Wood Trusses - Buildings C, D, K & L†for your review, intended to be compliant with
contract Specification Number: “061753â€.
Please review and respond to: Nick Santini, by: 1/28/2019 in accordance with the contract documents.
Additional Notes:
Spec Number Submittal Description Submittal Details
1. 061753 Prefabricated Wood Trusses - Buildings C, Shop Drawings
D, K & L
Sincerely,
Nick Santini
EXXEL PACIFIC, INC.
323 TELEGRAPH RD.
BELLINGHAM, WA
98226
✔
REVIEWED
BY Nick Santini DATE 1/14/2019
SUBMITTAL# 35 SPEC 061753