HomeMy WebLinkAbout3318 185th Pl Ne Bldg J_BLD1856_2025 ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA012
PERMIT #: 1856 DATE: 5/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Item(s) Inspected Location
Concrete Footing Building J
Reference Drawing(s): RFI 7
Item(s) Inspected Comments
Base Material Condition Concrete, dry
Drill Bit Type Rotohammer
Hole Diameter/Depth 3/4" X 4"
Hole Cleanliness Clean
Anchor Spacing/Edge Distance 3 Per Footing, Each Side
Anchor Type #5 Rebar
Anchor Diameter/Length 5/8"
Anchor Embedment 4"
Adhesive Type Hilti HY 200R
Adhesive Expiration Date 9-2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest on-site for periodic inspection of the items referenced above. Hole
cleanliness and depth was verified prior to epoxy activities. Anchor installation was completed
in accordance with approved plans and drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: AA012
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Anchor Installation in Progress
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA019
PERMIT #: 1851, 1852, 1853, 1854, 1856 DATE: 8/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Epoxied Anchor Bolts for Holdowns Building D, E, F, G, J (Each End of Entry Party Walls)
Reference Drawing(s): RFI #43, Structural Drawings
Item(s) Inspected Comments
Base Material Condition Fully Cured Concrete, 63º
Drill Bit Type Drilled Prior
Hole Diameter/Depth 3/4", 9"
Hole Cleanliness Blown, Brushed & Blown Clean
Anchor Spacing/Edge Distance NA
Anchor Type Threaded Rod
Anchor Diameter/Length 5/8", 14"
Anchor Embedment 9"
Adhesive Type Hilti Hit HY-200 R
Adhesive Expiration Date 2/2020
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the installation of the anchor bolts. The contractor
followed the manufacturer’s published instructions. The anchors were found to conform with the RFI and with
the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB024
PERMIT #: 1854, 1856 DATE: 4/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Devin Murphy
Placement Location: Building G Stem Walls and Plinth Bases, Building J Perimeter and Plinth Footings
Sample Location: Building J, Sampled Mid of a 10 CY Load at 10 CY Total
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 4.50 29
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 Sk, 7/8" Agg, MB polly 997, Hot water Unit Weight, pcf (C138) NT
Truck/Ticket # C082 / 220912 Air/Mix Temp.,°F (C1064) 52 / 59 DM6
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 49.1/75.0
Quantity Placed, cy 70 Cure Method - Initial / Final Container / Water Tank
Time Batched 10:06 AM Water Added on Job, gals 10
Time Sampled 10:35 AM Water Requested by Miles
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
94583 7 04-24 66110 4.01 12.63 5230 TYPE 2:
94584 28 05-15 75760 4.00 12.57 6030 TYPE 3:
94585 28 05-15 74570 4.00 12.57 5930 TYPE 3:
94586 28 05-15 80010 4.00 12.57 6370 TYPE 3:
94587 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: As requested, GeoTest was onsite to provided concrete testing and steel reinforcement inspection at
the locations stated above. The concrete was placed via boom pump and was mechanically consolidated. The
steel reinforcement was found to conform to the approved project documents.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB027
PERMIT #: 1856, 1857 DATE: 4/24/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Placement Location: Building J Stem Walls, Building K Stem Wall, and Plinth Footings
Sample Location: Second Truck, Mid-Pour, Directly From Chute, Southern Perimeter of Building J
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.00 9
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 SK, 7/8" Agg, pea Agg, MB Poly 997, Hot Water Unit Weight, pcf (C138) NT
Truck/Ticket # C183 / 221304 Air/Mix Temp.,°F (C1064) 52 / 60 TC5
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 53-83
Quantity Placed, cy 80 Cure Method - Initial / Final Container / Water Tank
Time Batched 8:41 AM Water Added on Job, gals 15
Time Sampled 9:15 AM Water Requested by Miles
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
94917 7 05-01 58730 4.00 12.57 4670 TYPE 3:
94918 28 05-22 78040 4.00 12.57 6210 TYPE 2:
94919 28 05-22 77070 4.00 12.57 6130 TYPE 2:
94920 28 05-22 75980 4.00 12.57 6040 TYPE 2:
94921 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to provide concrete placement observation as
well as concrete testing. Concrete was placed via pump truck, mechanically consolidated, and
was hand finished for both buildings pours. For reinforcement inspection, please refer to report
IR010. GeoTest will return for further inspection and observation as requested.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB027
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Figure 1. Building J stem wall
placement (looking north).
Figure 2. Building K stem wall
and plinth footing placement
(looking southeast).
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB040
PERMIT #: J-1856, H-1855, SB1-1886 DATE: 5/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building J Interior Slab on Grade With Continuous Wall Footings and Spread Footings, Building H Stem
Walls and Column Plinths, Storage Building #1 Continuous Footing
Sample Location: South Half of Building J, Continuous Wall Footings,
1st Load
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.50 19
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5sk. 7/8", Pea. WRA, NC Accel. Unit Weight, pcf (C138) NT
Truck/Ticket # C183 / 222659 Air/Mix Temp.,°F (C1064) 50 / 60 TM06
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 56 / 76 TM06
Quantity Placed, cy 118 Cure Method - Initial / Final Container / Water Tank
Time Batched 8:23 AM Water Added on Job, gals 10
Time Sampled 9:32 AM Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
96237 7 05-24 52180 4.00 12.57 4150 TYPE 2:
96238 28 06-14 63890 4.01 12.63 5060 TYPE 2:
96239 28 06-14 60100 4.01 12.63 4760 TYPE 2:
96240 28 06-14 64910 4.01 12.63 5140 TYPE 2:
96241 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to inspect the concrete placement at the
locations mentioned above. The reinforcing steel was in place and was found to be in
conformance with the projects structural drawings. Concrete placement at the slab occurred
during a light rain.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB040
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Sample Location: 80 Yards Placed at North End of Slab
Field Data:
Truck/Ticket # C113 / 222677 Slump, in. (C143) 5.75
Time Batched 9:52 AM Air Content, % (C231) NT
Time Sampled 11:04 AM Unit Weight, pcf (C138) NT
Air Temperature,°F 51 Water Added on Job, gals 15
Mix Temp.°F(C1064) 59 Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
96242 7 05-24 54950 4.00 12.57 4370 TYPE 2:
96243 28 06-14 71310 4.01 12.63 5650 TYPE 2:
96244 28 06-14 71900 4.01 12.63 5690 TYPE 2:
96245 28 06-14 70680 4.01 12.63 5600 TYPE 2:
96246 Hold 00-00 0 0.00 0.00 0
Comments:
Sample Location:
Field Data:
Truck/Ticket # / Slump, in. (C143)
Time Batched Air Content, % (C231)
Time Sampled Unit Weight, pcf (C138)
Air Temperature,°F Water Added on Job, gals
Mix Temp.°F(C1064) Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
Concrete Compressive Strength Test Report * Continuation
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB040
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Concrete Placement
This picture was taken looking
north across Building J slab.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB041
PERMIT #: 1856 DATE: 5/20/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Placement Location: Building J, Exterior Slabs on Grade, Patios, and Entryways
Sample Location: Footings for East Side Patios and South Entry
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.50 19
Mix # 0260A6C Air Content, % (C231) 4.9 2
Mix Description 6sk. 7/8", WRA, AEA Unit Weight, pcf (C138) NT
Truck/Ticket # C145 / 616205 Air/Mix Temp.,°F (C1064) 52 / 57 TM06
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 53 / 71
Quantity Placed, cy 21 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:27 A.M Water Added on Job, gals 8
Time Sampled 8:15 A.M Water Requested by Conc. Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
96269 7 05-27 58910 4.00 12.57 4690 TYPE 5:
96270 28 06-17 74130 4.00 12.57 5900 TYPE 2:
96271 28 06-17 74510 4.00 12.57 5930 TYPE 2:
96272 28 06-17 76630 4.00 12.57 6100 TYPE 2:
96273 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to inspect the concrete placement at the above locations. The two
#5 bars were wet-set into the thickened edges. The concrete was placed using a boom pump.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD053
PERMIT #: BLDG Permit #1856 DATE: 5/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Suzie Miller
Compaction Of: Building J Slab Subgrade
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 TOG DT/8 131.4 6.9 122.9 1 97 95 P
2 See Figure 1 TOG DT/8 141.9 6.6 133.1 1 105 95 P
3 See Figure 1 TOG DT/6 140.8 7.0 131.6 1 103 95 P
4 See Figure 1 TOG DT/8 128.3 5.3 121.9 1 96 95 P
5 See Figure 1 TOG DT/6 132.4 6.7 124.1 1 98 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4332A PGS w/ Gravel Lenz Enterprises Pit (D-255) 127.2 9.6 17 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek/3500/2082 M/D Standard Count: 399/3179
Comments: TOG Top of Grade
GeoTest was onsite, as requested to provide in-place density testing at the above location.
Prior to GeoTest’s arrival, the material had been placed and compacted. Initial tests resulted in
failing tests on the north end of the building pad. The contractor was informed of the failing
result. The area was recompacted with a jumping jack and plate compactor. All tests met or
exceeded compaction requirements.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 7 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD053
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Figure 1 - Test Locations
Figure 2 - Compaction with
jumping jack.
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: IR014
PERMIT #: 1855, 1856, 1859 DATE: 5/13/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
INSPECTION OF: Reinforcing Steel Placement
GeoTest was on site as requested to inspect the placement of the reinforcing steel at the
following locations.
Building H, Perimeter Wall Footing and Column Plinth Footings.
Building J, Slab on Grade with Interior Wall Footings and Column Pads.
Building M, Perimeter Stem Wall, and Column Plinths.
The reinforcing steel was in place at the above locations and was found to have been installed
as detailed on sheet S4.1, in accordance with the notes and schedules and notes on sheets
S1.1, S2.4.1 S2.5.1, S2.6.1, and S3.1.
This photo of the reinforcing steel at building J
was taken looking in a southwest direction
across the slab.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF040
PERMIT #: 1950, 1956 DATE: 6/12/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm Sheathing Building J, 2nd Floor Level
Shear Wall Sheathing and HD Strapping (In Progress) Building C, Exterior Shear Walls 1st, 2nd & 3rd Floor Levels
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The completed items listed above were found to conform to the project structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF043
PERMIT #: 1849, 1850, 1854, 1856 DATE: 6/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Roof Diaphragm Sheathing Building B
Floor Diaphragm Sheathing Building G, 3rd Level
Shear Wall Sheathing Building J, 2nd Level (Entry Walls)
Exterior Sheathing and Straps Final Inspection Building C
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips are in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items listed above. All the above items and at the
locations mentioned were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF049
PERMIT #: J-1856 DATE: 6/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Diaphragm Sheathing and Fasteners Building J, 3rd Level
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32", T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Yes
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the sheathing and fasteners for the above floor
diaphragm. All items found were addressed prior to our leaving the project. Above items were in conformance
with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF050
PERMIT #: J-1856, O-1861 DATE: 6/27/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Framing Building O, All 1st Level Locations
Shear Wall Sheathing Building J, 3rd Floor Entry Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members SW’s are Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
Building J’s 3rd-floor entry wall was per plan. The framing at Building O is in progress.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF062
PERMIT #: G-1854, H-1855, J-1856, K-1857 DATE: 7/18/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings, G, H, J, 1st Level
Floor Diaphragm Sheathing Building K, 3rd Level
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" X 2-1/4" (2-1/2" at Diaphragm), Per Plan/SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The above items were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF064
PERMIT #: 1855, 1856, 1857, 1859, 1861 DATE: 7/22/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Sean Rogerson
Item(s) Inspected Location
Shearwall Sheathing (Nailing, Sheathing) Building J & H Entry Walls, Level 1
Shearwall Sheathing (Nailing, Sheathing) Building K Entry Walls, Level 3
Shearwall Sheathing (Nailing, Sheathing) Building M Entry Walls, Level 2
Previously Noted Discrepancies Building O, Entire Building
Reference Drawings: Approved Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue 15/32" APA Rated OSB, Exposure 1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Acceptable
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Acceptable
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other Previous GeoTest Reports/Ongoing Inspection Checklist
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site to provide special inspection of lateral framing items as noted above. All
items were found to be in conformance with the project plans. Building O had been previously inspected and at
this time all remaining checklist items are complete.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF065
PERMIT #: 1856, 1857, 1858 DATE: 7/23/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 4
CONTRACTOR: Exxel Pacific INSPECTOR: John Silk
Item(s) Inspected Location
Shear Walls Buildings L & K
Roof Sheathing Building J
Reference Drawings: Approved Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Structural Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Shearwall Schedule
Pneumatic or mechanically driven fasteners conform Per General Notes
Nail heads driven flush Acceptable
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above item. The contractor
addressed all items found prior to our leaving the project. Above items were in accordance with
the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF065
CONTRACTOR: Exxel Pacific PAGE #: 2 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF065
CONTRACTOR: Exxel Pacific PAGE #: 3 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF065
CONTRACTOR: Exxel Pacific PAGE #: 4 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF069
PERMIT #: 1856, 1859 DATE: 7/31/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm Sheathing Building M, 3rd Level
Shear Wall Sheathing and HD Strapping Building J, Exterior All Levels
Shear Wall Sheathing Building M, 1st Level Entry Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4" (2-1/2" at Floor), Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items mentioned above. The floor and entry wall
sheathing was per plan. The sheathing at Building J was marked at locations
which will need to be addressed.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF074
PERMIT #: J-1856, K-1858, L-1857 DATE: 8/15/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Roof Diaphragm Sheathing Building L
Shear Wall Sheathing & Floor- Floor Straps, Final Inspection Building J, K
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Drawings
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" x 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Over-Driven Nails Were Corrected
Hold down, type, location Floor to Floor and Perf. SW Straps Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. All nonconforming items were addressed
prior to our leaving the job site. Above items were in conformance.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF086
PERMIT #: 1855, 1856 DATE: 9/18/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Walls Building H Level 1 and J Level 1
Reference Drawings: S5.09
Items Inspected Comments
Lumber grade, species, size D-Fir #2, Hem Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 5/8", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members SW Fully Blocked
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes
Foundation plates or sills on concrete are treated Sill Plates Treated
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location See Comments
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. This was an in-progress inspection.
Items found were marked include an HDU2 holdown where an HDU5 is called out.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF087
PERMIT #: 1855, 1856 DATE: 9/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing Buildings J and H, Level 1 All Perimeter SW Locations
Final Framing: Interior SW Sheathing and Framing Buildings J and H, Level 1 All Interior Wall SW Locations
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D-Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members SW Sheathing Was Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates Sheathing Lapped at Rim or A35 Clips in Place Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Per SW Schedule
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Per SW Schedule & General Notes
Nail diameter, length, number of lines, spacing Per Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location HDU and MST Holdowns Found to Conform with HD Schedule
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items listed above. This was an in-progress
inspection. Items found were marked and will require reinspection.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF088
PERMIT #: 1856, 1855, 1883, 1885 DATE: 9/20/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing of Perimeter Shear Walls Buildings J and H, 2nd & 3rd Floors
Sheathing and Framing Covered Sitting Area & Maint./Stor. Building, Roof & Walls
Interior Shear Walls, Sheathing and Framing Buildings J and H, 2nd & 3rd Floors
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D, Fir
Structural panel grade and thickness, glue Rated Sheathing, 15/32"
Shear wall/diaphragm length, location Per Plan at Above locations
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Per Plan and SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location MST Straps Conform with HD Schedule
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. The sheathing at the maintenance/
storage building and covered seating area structure were in conformance with the project drawings. The
framing at buildings J and H was in progress.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF093
PERMIT #: Permits Listed Below DATE: 10/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Walls - Reinspection Buildings G, H, J / Permits - 1854, 1855 & 1856
Final Framing and Interior Shear Walls Buildings K, L, M / Permits - 1857, 1858 & 1859
Wall and Roof Sheathing and Framing Garage 10, 11 & 12 / Permits - 1874, 1875, & 1876
BBQ Enclosure Framing - Reinspection BBQ Enclosures 1 & 2 / Permits - 1881 & 1882
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue APA Rated Sheathing, 15/32" (23/32") at Floors) Exp.1
Shear wall/diaphragm length, location Per Plan at Above Shear Walls
Panel edges bear on framing members Fully Blocked
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Per Plan SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site to inspect the above items. See the following page for
comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF093
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo shows the now
installed flat blocking at the
BBQ enclosure. Both BBQ
enclosures are in
conformance with the project
drawings. This item was noted
in report LF091 (dated
10/2/19) as nonconforming.
The contractor has addressed all outstanding items found during GeoTest's previous
inspections and all items found this date during the final framing/interior shear wall inspection
of buildings K, L and M. At the locations on page one of this report; the lateral framing was
found to be in conformance with the project drawings.
SPECIAL INSPECTION SUMMARY
PROJECT: The Villas at Arlington â€Â BLD J JOB #: 18â€0760
ADDRESS: 18506 Smokey Point Blvd, Arlington, WA 98223 DATE: 10â€22â€2019
CLIENT: Villas at Arlington Partners LLLP PERMIT #: 1856
CONTRACTOR: Exxel Pacific PAGE: 1 of 1
This letter summarizes our special inspection and testing efforts for The Villas at Arlington – BLD J
project located in Arlington, Washington. GeoTest’s services took place from October 9, 2018
through October 22, 2019. Our testing and inspections included the following scope of work:
TEST/INSPECTION ITEM REFERENCE
ï‚· Earthwork Field Density Moisture Report FD053
Concrete Break Reports CB024, CB027, CB040
ï‚· Reinforced Concrete & CB041 and Inspection Reports IR010 &
IR014
Lateral Framing Inspection Reports LF040,
ï‚· Lateral Framing LF043, LF049, LF050, LF062, LF064, LF065,
LF069, LF074, LF086 – LF088 & LF093
Adhesive Anchor Inspection Reports AA012 &
ï‚· Proprietary Anchors
AA019
All work requiring special inspection for the project to date has been completed. To the best of
our knowledge the inspected work is in conformance with the approved project plans and
specifications and the applicable workmanship provisions of the International Building Code. All
related laboratory tests performed by GeoTest have met or exceeded the minimum test
requirements.
This is GeoTest’s final special inspection and testing submittal for The Villas at Arlington â€Â BLD J
project. If we can be of further assistance, please contact the undersigned.
Copies: Villas at Arlington Partners LLLP Safe Built
Charles Morgan and Associates LLC The Alliant Company
City of Arlington Anderson, Brian
Exxel Pacific Charles Morgan and Associates LLC Logan Senrud
CG Engineering Technical Director
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Permit #: 1856
Permit Date: 03/09/18
Permit Type: MULTI-FAMILY
Project Name: Villas at Arlington
Applicant Name: Villas at Arlington, LLLP
Applicant Address: 105 Cresent Bay Drive, Suite D
Applicant, City, State, Zip: Laguna Beach, CA 92651
Contact: Carmel Gregory
Phone: 425-778-8500
Email: carmelg@cgengineering.com
Scope of Work: New Multi-Family Development
Valuation: 2071084.09
Square Feet: 19069
Number of Stories: 3
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 11/01/2018
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
VILLAS AT 137 Multiple Family
31052000100800 3318 185TH PLACE NE
ARLINGTON 101 - 200 Units
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
323A CONSTRUCTION
EXXEL PACIFIC INC 360-734-2872 UBI 601 175 198
TELEGRAPH RD CONTRACTOR
323A CONSTRUCTION Labor and
EXXEL PACIFIC INC 360-734-2872 EXXELPI073KN
TELEGRAPH RD CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
03/09/2018 BUILDING
BUILDING
Fees
Fee Description Notes Amount
Building Plan Review Table 4-2 $8,802.10
Building Plan Review Table 4-2 $149.08
Building Permit Table 4-1 $13,771.04
Park - Community MF Multi-family $26,946.00
State Surcharge - Commercial Commercial Only $25.00
State Surcharge - add'l DU Residential Additional Units $36.00
Traffic Mitigation - C/MF Commercial/Multi-family $23,420.52
Processing/Technology $25.00
Total $73,174.74
Attached Letters
Date Letter Description
09/19/2018 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
03/08/2018 Alliant Capital Ltd. 18506 Bldg. J Check #104500 Kristin Foster $8,802.10
10/11/2018 Fidelity National Title check #26379 Launa Black $64,372.64
Outstanding Balance $0.00
Uploaded Files
Date File Name
03/11/2020 6373804-Villas Bldg. J C of O.pdf
11/01/2018 4145053-1856_Villas Building Permit.pdf
03/09/2018 3141587-Commercial Application - Building J.pdf
SUBMITTAL PACKAGE Page 1
DATE: 1/14/2019
Your Logo Here FOR APPROVAL PACKAGE NUM: 36
PACKAGE REV: 0
Exxel Pacific, Inc. SPEC #: 061753
201808. - Villas at Arlington
To: Dennis Titus From: Nick Santini
CG Engineering PLLC Exxel Pacific, Inc.
250 4th Ave South #200 323 Telegraph Road
Edmonds, WA 98020 Bellingham, WA 98226
We are transmitting the following Submittal Package Number: “36â€, Revision: “0†Description:
“Prefabricated Wood Trusses - Buildings E & J†for your review, intended to be compliant with contract
Specification Number: “061753â€.
Please review and respond to: Nick Santini, by: 1/28/2019 in accordance with the contract documents.
Additional Notes:
Spec Number Submittal Description Submittal Details
1. 061753 Prefabricated Wood Trusses - Buildings E & Shop Drawings
J
Sincerely,
Nick Santini
EXXEL PACIFIC, INC.
323 TELEGRAPH RD.
BELLINGHAM, WA
98226
✔
REVIEWED
BY Nick Santini DATE 1/14/2019
SUBMITTAL# 36 SPEC 061753