HomeMy WebLinkAbout3318 185th Pl Ne Bldg G_BLD1854_2025 ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA011
PERMIT #: 1854 DATE: 5/3/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Item(s) Inspected Location
Concrete Footing Building G
Reference Drawing(s): RFI 7
Item(s) Inspected Comments
Base Material Condition Concrete, Dry
Drill Bit Type Hollow Bit Roto-hammer
Hole Diameter/Depth 3/4" X 4"
Hole Cleanliness Clean
Anchor Spacing/Edge Distance 3 Per Footing, Each Side
Anchor Type #5 Rebar
Anchor Diameter/Length 5/8"
Anchor Embedment 4"
Adhesive Type Hilti HY 200R
Adhesive Expiration Date 9/2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest on site for inspection of the above-referenced items. Verified hole depth
and cleanliness prior to epoxy gluing. Installation was completed in accordance with approved
plans and drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: AA011
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Installation of Footing Bars in
Progress
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA019
PERMIT #: 1851, 1852, 1853, 1854, 1856 DATE: 8/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Epoxied Anchor Bolts for Holdowns Building D, E, F, G, J (Each End of Entry Party Walls)
Reference Drawing(s): RFI #43, Structural Drawings
Item(s) Inspected Comments
Base Material Condition Fully Cured Concrete, 63º
Drill Bit Type Drilled Prior
Hole Diameter/Depth 3/4", 9"
Hole Cleanliness Blown, Brushed & Blown Clean
Anchor Spacing/Edge Distance NA
Anchor Type Threaded Rod
Anchor Diameter/Length 5/8", 14"
Anchor Embedment 9"
Adhesive Type Hilti Hit HY-200 R
Adhesive Expiration Date 2/2020
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the installation of the anchor bolts. The contractor
followed the manufacturer’s published instructions. The anchors were found to conform with the RFI and with
the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB021
PERMIT #: 1854, 1853 DATE: 4/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Building F Stem Walls and Plinth Bases, Building G Perimeter and Plinth Footings
Sample Location: Building F Stem Walls, First Load, Middle of the Batch
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.00 15
Mix # 02550C Air Content, % (C231) NT
Mix Description 7/8" Aggregate Unit Weight, pcf (C138) NT
Truck/Ticket # C143 / 615720 Air/Mix Temp.,°F (C1064) 57 / 61 JM1
Strength Required 3000 psi at 28 days Field Cure Temperature, °F
Quantity Placed, cy 70 Cure Method - Initial / Final Container / Moist Room
Time Batched 8:15 AM Water Added on Job, gals 10
Time Sampled 9:10 AM Water Requested by Pump operator
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
94297 7 04-17 49250 4.01 12.63 3900 TYPE 2:
94298 28 05-08 60410 4.01 12.63 4780 TYPE 3:
94299 28 05-08 66620 4.01 12.63 5270 TYPE 5:
94300 28 05-08 67470 4.01 12.63 5340 TYPE 2:
94301 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on site for inspection of the above-referenced items. Reviewed
reinforcing steel per structural drawings. Concrete was placed by pump and consolidated
through mechanical vibration. All items were in conformance with approved plans and
drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB021
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Cconcrete Placement and
Consolidation in Progress
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB024
PERMIT #: 1854, 1856 DATE: 4/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Devin Murphy
Placement Location: Building G Stem Walls and Plinth Bases, Building J Perimeter and Plinth Footings
Sample Location: Building J, Sampled Mid of a 10 CY Load at 10 CY Total
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 4.50 29
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 Sk, 7/8" Agg, MB polly 997, Hot water Unit Weight, pcf (C138) NT
Truck/Ticket # C082 / 220912 Air/Mix Temp.,°F (C1064) 52 / 59 DM6
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 49.1/75.0
Quantity Placed, cy 70 Cure Method - Initial / Final Container / Water Tank
Time Batched 10:06 AM Water Added on Job, gals 10
Time Sampled 10:35 AM Water Requested by Miles
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
94583 7 04-24 66110 4.01 12.63 5230 TYPE 2:
94584 28 05-15 75760 4.00 12.57 6030 TYPE 3:
94585 28 05-15 74570 4.00 12.57 5930 TYPE 3:
94586 28 05-15 80010 4.00 12.57 6370 TYPE 3:
94587 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: As requested, GeoTest was onsite to provided concrete testing and steel reinforcement inspection at
the locations stated above. The concrete was placed via boom pump and was mechanically consolidated. The
steel reinforcement was found to conform to the approved project documents.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB035
PERMIT #: 1854 DATE: 5/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Building G Exterior Patios and Entrances
Sample Location: SW Patios, First Load, Middle of the Batch
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 4.50 15
Mix # 0260A6C Air Content, % (C231) 4.4 8
Mix Description 7/8" Aggregate, 6 Sack Unit Weight, pcf (C138) NT
Truck/Ticket # C114 / 222246 Air/Mix Temp.,°F (C1064) 60 / 67 JM1
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 54 / 93
Quantity Placed, cy 30 Cure Method - Initial / Final Container / Water Tank
Time Batched 6:17 AM Water Added on Job, gals 0
Time Sampled 7:05 AM Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
95920 7 05-17 67330 4.00 12.57 5360 TYPE 2:
95921 28 06-07 76320 4.01 12.63 6040 TYPE 2:
95922 28 06-07 76710 4.01 12.63 6070 TYPE 3:
95923 28 06-07 74300 4.01 12.63 5880 TYPE 2:
95924 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on site for inspection of concrete placed at the above-referenced locations. Elements are
un-reinforced and required no rebar inspection. All items were in conformance with approved plans and
drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB036
PERMIT #: 1854 DATE: 5/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Interior Slab on Grade, Building G
Sample Location: NW Quadrant, First Load of Mix, Middle of the Batch
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.00 15
Mix # 02550C Air Content, % (C231) NT
Mix Description 7/8" Aggregate, 5.5 Sack Unit Weight, pcf (C138) NT
Truck/Ticket # C057 / 222258 Air/Mix Temp.,°F (C1064) 60 / 67 JM1
Strength Required 3000 psi at 28 days Field Cure Temperature, °F
Quantity Placed, cy 90 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:13 AM Water Added on Job, gals 18
Time Sampled 7:50 AM Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
95925 7 05-17 49330 4.00 12.57 3920 TYPE 3:
95926 28 06-07 64960 4.01 12.63 5140 TYPE 2:
95927 28 06-07 58170 4.01 12.63 4610 TYPE 5:
95928 28 06-07 64980 4.01 12.63 5140 TYPE 2:
95929 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on site for inspection of the slab on grade referenced above. Reviewed
reinforcing steel per RFI 34. Also verified that the contractor had fixed each discrepancy noted
in IR013. All elements were in conformance with approved plans and drawings. AMENDED
5/21/19: Reference to previous discrepancies was corrected to IR013, original report
incorrectly referenced CB035.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB036
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Concrete Placement in
Progress
Rebar Layout
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD035
PERMIT #: 1862, 1852 DATE: 3/1/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Compaction Of: Pads for Buildings E and G
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 BLDG G, N Half FSG 12 136.7 8.0 126.6 1 100 95 P
2 BLDG G, S Half FSG 12 134.5 7.6 125.0 1 98 95 P
3 BLDG E, W Half FSG 12 133.2 6.7 124.8 1 98 95 P
4 BLDG E, E Half FSG 12 131.3 5.9 125.4 1 99 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4332A Select Borrow Lenz Enterprises 127.2 9.6 17 ASTM D1557
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: InstroTek/3500/BG164 M/D Standard Count: 420/3147
Comments: GeoTest on site for nuclear density testing of compacted soils for the pad of building G and
E. Material appeared to have been compacted using a smooth drum vibratory roller.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD036
PERMIT #: 1853, 1854, 1862 DATE: 3/4/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Compaction Of: Building Pads F, G, and P
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 TOG DT/12 127.3 10.8 114.9 1 102 95 P
2 See Figure 1 TOG DT/12 117.9 9.1 108.1 1 96 95 P
3 See Figure 1 TOG DT/12 126.8 12.4 112.8 1 100 95 P
4 See Figure 1 TOG DT/12 120.9 9.6 110.3 1 98 95 P
5 Building F, Eastern Third TOG DT/12 135.2 6.7 126.6 2 100 95 P
6 Building F, Middle Third -.5 DT/12 132.2 8.1 122.2 2 96 95 P
7 Building G, NW Quadrant -2 DT/12 132.6 5.9 125.2 2 98 95 P
8 Building G, NE Quadrant -2 DT/12 131.3 6.7 123.1 2 97 95 P
9 Building G, SE Quadrant -2.5 DT/12 129.9 6.9 121.5 2 96 95 P
10 Building G, SW Quadrant -2.5 DT/12 131.0 7.1 122.3 2 96 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4282A SP Native 112.6 13.9 5 ASTM D1557/D4718
2-4332A SP with Gravel Lenz Enterprises Pit (D-255) 127.2 9.6 17 ASTM D1557/D4718
3- 0.0 None
Gauge Make/Model/Serial#: Instro/3500/2082 M/D Standard Count: 403/3174
Comments: Please see page 2 for comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD036
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
TOG -Top of Grade
GeoTest was on-site as requested to provide in-place density testing at the above locations. All
locations and elevations are approximate and were provided by the contractor.
Tests 1 - 4 were taken at the request of the contractor on Building Pad P (Figure1). Prior to our
arrival, the soil in these areas had been re-worked and compacted with a plate compactor, per
the contractor. The material that was tested was comprised of mostly native fill. Tests 5-10
were taken on imported, graded, and compacted structural fill for Building Pads F and G.
Compaction was achieved in these areas with a single-drum vibratory roller.
All tests taken on this date met compaction requirements. These compacted soils exhibited
firm and unyielding conditions with optimum moisture contents.
GeoTest will return for further inspection and observation as requested.
Figure 1. In-place density
testing locations of re-worked
structural fill for Building P.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD037
PERMIT #: 1849, 1854 DATE: 3/5/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Compaction Of: Building B Footing Cuts, Building G Pad
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 NE Quadrant, BLDG B FTG -2 12 105.8 5.5 100.4 1 97 95 P
2 NW Quadrant, BLDG B FTG -2 12 109.2 6.8 102.2 1 99 95 P
3 SE Quadrant, BLDG B FTG -2 12 107.8 5.7 102.0 1 98 95 P
4 N Half, BLDG G Pad -0 12 132.2 7.7 122.6 2 96 95 P
5 S Half, BLDG G Pad -0 12 132.2 7.3 123.2 2 97 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4274A Native On-Site Stockpile 103.7 13.4 3 ASTM D1557
2-4332A Select Borrow Lenz Enterprises 127.2 9.6 17 ASTM D1557
3- 0.0 None
Gauge Make/Model/Serial#: InstroTek/3500/2082 M/D Standard Count: 410/3174
Comments: GeoTest on-site density testing of the above-referenced locations. In Building B,
the contractor had dug the footings, removed organic material from the soils then placed the
excavated soils back into the footing and compacted it.
All elevations were measured from the top of the building pad of the respective building the test
was performed at.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD037
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Compaction of Lenz Select
Borrow for Building G Pad
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: IR013
PERMIT #: 1854 DATE: 5/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
INSPECTION OF: Building G, Reinforcing Steel Placement at Slab on Grade with Continuous Wall Footings and Column Pads
GeoTest was on site as requested to inspect the items mentioned above.
Except for the following items the placement of the reinforcing steel was found to conform with
the project structural drawings and RFI #34.
See the following pages for items which will need to be addressed prior to placing the
concrete.
GeoTest will verify the corrections were completed.
AMENDED 5/21/19: Please see CB036 for conforming reinspection.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: IR013
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
A few of the #3 typical
reinforcing steel bars were too
far from the edge of the slab.
The bar needs to be added
along the slab edge.
A trim bar needs to be added at the edge of this entry
location.
Inspection Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: IR013
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
The grade was too high at this
location, the bar is set on the
vapor barrier.
Northeast corner, bar is too
high.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF030
PERMIT #: 1854 DATE: 5/29/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Diaphragm Sheathing Building G, 2nd Floor
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Stridi-Floor, 23/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" X 2-1/4", 6 and 12" On Center
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. The sheathing and fasteners were found
to be in conformance with the project structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF033
PERMIT #: 1854 DATE: 6/3/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Building G, Second Level Entry Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32"
Shear wall/diaphragm length, location
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 x 2-1/4", 6 and 12"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The items listed on this report were found to conform with the project’s drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF043
PERMIT #: 1849, 1850, 1854, 1856 DATE: 6/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Roof Diaphragm Sheathing Building B
Floor Diaphragm Sheathing Building G, 3rd Level
Shear Wall Sheathing Building J, 2nd Level (Entry Walls)
Exterior Sheathing and Straps Final Inspection Building C
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips are in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items listed above. All the above items and at the
locations mentioned were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF046
PERMIT #: 1854 DATE: 6/21/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: John Silk
Item(s) Inspected Location
Entry Shearwall Sheathing Building G, 3rd Floor
Reference Drawings: Plan Sheet S2.5.2, Shearwall Schedule on S3.1
Items Inspected Comments
Lumber grade, species, size Per Shearwall Schedule
Structural panel grade and thickness, glue Per Shearwall Schedule
Shear wall/diaphragm length, location Per Structural Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Shearwall Schedule
Pneumatic or mechanically driven fasteners conform Per Shearwall Schedule
Nail heads driven flush Acceptable
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Sheathing was inspected with the panels flat on the 3rd-floor diaphragm.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF046
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF060
PERMIT #: 1854 DATE: 7/16/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Diaphragm Sheathing and Fasteners Building G, Roof
Shear Wall Sheathing Building G, Entry Walls at Level One
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location
Panel edges bear on framing members
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. Both the roof and shear wall sheathing
was found to be in accordance with the project structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF062
PERMIT #: G-1854, H-1855, J-1856, K-1857 DATE: 7/18/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings, G, H, J, 1st Level
Floor Diaphragm Sheathing Building K, 3rd Level
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" X 2-1/4" (2-1/2" at Diaphragm), Per Plan/SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The above items were found to be in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF067
PERMIT #: 1854, 1858, 1855, 1848 DATE: 7/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing and HD Strapping Building G, All Exterior Locations
Shear Wall Sheathing Building L, 3rd Level Entry Walls
Column Connections to the Foundation Building G and H East Side of the Building at Entry
Interior Framing Building A
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips are in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Framing Notes and SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: See comments on Page 2.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF067
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
GeoTest was on site as requested to inspect the above items. The column connections at
Building G & H and walls at Building L were found to conform with the project drawings.
Building G - Exterior Shear Wall Sheathing: The items inspected will require corrections and
marked at the location.
Building A - Interior Framing: Items still requiring corrections, are as follows; holes in the shear
wall top plates, plumbing, and electrical and oversized holes require strapping.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF068
PERMIT #: 1848, 1854 DATE: 7/30/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Reinspection of Shear Sheathing and Straps Building G, All Exterior Locations
Reinspection: Interior FramingI and Shear Wall Sheathing Building A, All Interior Locations
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. Both the exterior sheathing and the
interior framing at the above locations are now in conformance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF085
PERMIT #: 1854 DATE: 9/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Walls: Final Framing Building G, Framing at all Shear Walls
Shear Wall Sheathing Building G, Interior Shear Walls
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size D.Fir #2, Hem. Fir
Structural panel grade and thickness, glue Rated Sheathing, 15/31", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members SW’s are Fully Blocked
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Clips are in Per SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Sill Plates Were Treated
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Nailing of the Sheathing is Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Yes
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to conduct a final Framing inspection at the above locations. The
few items found were marked and a follow-up inspection is required once the items have been addressed.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF093
PERMIT #: Permits Listed Below DATE: 10/8/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Final Framing and Interior Shear Walls - Reinspection Buildings G, H, J / Permits - 1854, 1855 & 1856
Final Framing and Interior Shear Walls Buildings K, L, M / Permits - 1857, 1858 & 1859
Wall and Roof Sheathing and Framing Garage 10, 11 & 12 / Permits - 1874, 1875, & 1876
BBQ Enclosure Framing - Reinspection BBQ Enclosures 1 & 2 / Permits - 1881 & 1882
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue APA Rated Sheathing, 15/32" (23/32") at Floors) Exp.1
Shear wall/diaphragm length, location Per Plan at Above Shear Walls
Panel edges bear on framing members Fully Blocked
Diaphragm chord, drag strut, braces and related Per Plan
Connection of blocking to wall top plates Per Plan SW Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Yes
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location Per Plan
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site to inspect the above items. See the following page for
comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF093
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The photo shows the now
installed flat blocking at the
BBQ enclosure. Both BBQ
enclosures are in
conformance with the project
drawings. This item was noted
in report LF091 (dated
10/2/19) as nonconforming.
The contractor has addressed all outstanding items found during GeoTest's previous
inspections and all items found this date during the final framing/interior shear wall inspection
of buildings K, L and M. At the locations on page one of this report; the lateral framing was
found to be in conformance with the project drawings.
SPECIAL INSPECTION SUMMARY
PROJECT: The Villas at Arlington â€Â BLD G JOB #: 18â€0760
ADDRESS: 18506 Smokey Point Blvd, Arlington, WA 98223 DATE: 10â€22â€2019
CLIENT: Villas at Arlington Partners LLLP PERMIT #: 1854
CONTRACTOR: Exxel Pacific PAGE: 1 of 1
This letter summarizes our special inspection and testing efforts for The Villas at Arlington – BLD G
project located in Arlington, Washington. GeoTest’s services took place from October 9, 2018
through October 22, 2019. Our testing and inspections included the following scope of work:
TEST/INSPECTION ITEM REFERENCE
Field Density Moisture Reports FD035 – FD037
ï‚· Earthwork
& FD052
Concrete Break Reports CB021, CB024, CB036
ï‚· Reinforced Concrete
& CB036 and Inspection Report IR013
Lateral Framing Inspection Reports LF030,
ï‚· Lateral Framing LF033, LF043, LF046, LF060, LF062, LF067,
LF068, LF085 & LF093
Adhesive Anchor Inspection Reports AA011 &
ï‚· Proprietary Anchors
AA019
All work requiring special inspection for the project to date has been completed. To the best of
our knowledge the inspected work is in conformance with the approved project plans and
specifications and the applicable workmanship provisions of the International Building Code. All
related laboratory tests performed by GeoTest have met or exceeded the minimum test
requirements.
This is GeoTest’s final special inspection and testing submittal for The Villas at Arlington â€Â BLD G
project. If we can be of further assistance, please contact the undersigned.
Copies: Villas at Arlington Partners LLLP Safe Built
Charles Morgan and Associates LLC The Alliant Company
City of Arlington Anderson, Brian
Exxel Pacific Charles Morgan and Associates LLC Logan Senrud
CG Engineering Technical Director
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Permit #: 1854
Permit Date: 03/09/18
Permit Type: MULTI-FAMILY
Project Name: Villas at Arlington
Applicant Name: Villas at Arlington, LLLP
Applicant Address: 105 Cresent Bay Drive, Suite D
Applicant, City, State, Zip: Laguna Beach, CA 92651
Contact: Carmel Gregory
Phone: 425-778-8500
Email: carmelg@cgengineering.com
Scope of Work: New Multi-Family Development
Valuation: 1991907.40
Square Feet: 18340
Number of Stories: 3
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 11/01/2018
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
VILLAS AT 137 Multiple Family
31052000100800 3318 185TH PLACE NE
ARLINGTON 101 - 200 Units
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
323A CONSTRUCTION
EXXEL PACIFIC INC 360-734-2872 UBI 601 175 198
TELEGRAPH RD CONTRACTOR
323A CONSTRUCTION Labor and
EXXEL PACIFIC INC 360-734-2872 EXXELPI073KN
TELEGRAPH RD CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
03/09/2018 BUILDING
BUILDING
Fees
Fee Description Notes Amount
Building Plan Review Table 4-2 $8,536.05
Building Plan Review Table 4-2 $143.91
Building Permit Table 4-1 $13,353.78
Park - Community MF Multi-family $26,946.00
Processing/Technology $25.00
State Surcharge - Commercial Commercial Only $25.00
State Surcharge - add'l DU Residential Additional Units $36.00
Traffic Mitigation - C/MF Commercial/Multi-family $23,420.52
Total $72,486.26
Attached Letters
Date Letter Description
09/19/2018 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
03/08/2018 Alliant Capital Ltd. 18506 Bldg. G Check #104500 Kristin Foster $8,536.05
10/11/2018 Fidelity National Title check #26379 Launa Black $63,950.21
Outstanding Balance $0.00
Uploaded Files
Date File Name
03/17/2020 6395596-Villas Bldg G C of O.pdf
03/09/2018 3141573-Commercial Application - Building G.pdf
SUBMITTAL PACKAGE Page 1
DATE: 11/27/2018
Your Logo Here FOR APPROVAL PACKAGE NUM: 9
PACKAGE REV: 0
Exxel Pacific, Inc. SPEC #: 061753
201808. - Villas at Arlington
To: Dennis Titus From: Nick Santini
CG Engineering PLLC Exxel Pacific, Inc.
250 4th Ave South #200 323 Telegraph Road
Edmonds, WA 98020 Bellingham, WA 98226
We are transmitting the following Submittal Package Number: “9â€, Revision: “0†Description: “Prefabricated
Wood Trusses - Buildings F, G, H & N†for your review, intended to be compliant with contract Specification
Number: “061753â€.
Please review and respond to: Nick Santini, by: 12/11/2018 in accordance with the contract documents.
Additional Notes:
Spec Number Submittal Description Submittal Details
1. 061753 Prefabricated Wood Trusses - Buildings F, Shop Drawings
G, H & N
SUBMITTAL REVIEW
Sincerely, â–¡ NO EXCEPTION TAKEN
â–¡ MAKE CORRECTION NOTED
â–¡ REJECTED
□✔ REVISE AND RESUBMIT
â–¡ SUBMIT SPECIFIED ITEM
Nick Santini
THIS REVIEW IS ONLY FOR GENERAL CONFORMANCE
WITH THE DESIGN CONCEPT OF THE PROJECT AND
GENERAL COMPLIANCE WITH THE INFORMATION
GIVEN IN THE CONTRACT DOCUMENTS. CONTRACTOR
REMAINS RESPONSIBLE FOR FULL COMPLIANCE WITH
THE PLANS AND SPECIFICATIONS. DIMENSIONS AND
QUANTITIES WERE NOT REVIEWED AND ARE THE
RESPONSIBILITY OF THE CONTRACTOR.
BY Morgan Kruse DATE 12/07/18
EXXEL PACIFIC, INC.
323 TELEGRAPH RD.
BELLINGHAM, WA
98226
✔
REVIEWED
BY Nick Santini DATE 11/21/2018
SUBMITTAL# 9 SPEC 067153