HomeMy WebLinkAbout3318 185th Pl Ne Bldg D_BLD1851_2025 ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA009
PERMIT #: 1851 DATE: 4/22/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Epoxied Dowels for Interior Footing Tie-In w/Perimeter Footings Building D, All Interior/Exterior Footing Intersections
Reference Drawing(s): RFI #7
Item(s) Inspected Comments
Base Material Condition Dry Concrete, 5º
Drill Bit Type Hilti Carbide Tip w/Vacuum
Hole Diameter/Depth 3/4", 4-1/2"
Hole Cleanliness Clean
Anchor Spacing/Edge Distance Per Plan
Anchor Type Grade 60 Deformed Reinforcing Steel
Anchor Diameter/Length 5/8", 44"
Anchor Embedment 4"
Adhesive Type Hilti HY-200 R
Adhesive Expiration Date 09/ 2019
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the installation of the above
reinforcing steel dowels. The dowels at the locations listed on this report were found to be in
conformance with the project structural drawings and were installed as recommended by the
manufacturer published instructions.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: AA009
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
The contractor had drilled and
cleaned the holes in the
perimeter foundation prior to
applying the epoxy.
ADHESIVE ANCHOR INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: AA019
PERMIT #: 1851, 1852, 1853, 1854, 1856 DATE: 8/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Epoxied Anchor Bolts for Holdowns Building D, E, F, G, J (Each End of Entry Party Walls)
Reference Drawing(s): RFI #43, Structural Drawings
Item(s) Inspected Comments
Base Material Condition Fully Cured Concrete, 63º
Drill Bit Type Drilled Prior
Hole Diameter/Depth 3/4", 9"
Hole Cleanliness Blown, Brushed & Blown Clean
Anchor Spacing/Edge Distance NA
Anchor Type Threaded Rod
Anchor Diameter/Length 5/8", 14"
Anchor Embedment 9"
Adhesive Type Hilti Hit HY-200 R
Adhesive Expiration Date 2/2020
Adhesive ICC-ES Report 3187
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the installation of the anchor bolts. The contractor
followed the manufacturer’s published instructions. The anchors were found to conform with the RFI and with
the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF078
PERMIT #: 1849, 1850, 1851, 1852, 1859, 1877, 1878 DATE: 8/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Gable Truss Reinforcing Sheathing for Roof Anchors Building B, C, D, E
Shear Wall Sheathing (Sheathing in Progress) Building M, All Perimeter Shear Walls
Wall Sheathing Garage #13 and #14, all Wall Locations
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members All Walls Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The above items, (not in-progress) were found to be in conformance with the project drawings. A few locations
were marked at building M for correction.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB015
PERMIT #: 1851, 1852 DATE: 3/28/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Building D Perimeter Footings and Plinth Footings, Building E Stem Walls and Plinth Bases
Sample Location: Building D Footings, Truck Load 4, Middle of Batch
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 4.50 15
Mix # 02550C Air Content, % (C231) NT
Mix Description 7/8" Aggregate Unit Weight, pcf (C138) NT
Truck/Ticket # C084 / 219757 Air/Mix Temp.,°F (C1064) 59 / 58 JM4
Strength Required 4000 psi at 28 days Field Cure Temperature, °F 47/74
Quantity Placed, cy 80 Cure Method - Initial / Final Container / Water Tank
Time Batched 10:43 AM Water Added on Job, gals 0
Time Sampled 11:20 AM Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
93804 7 04-04 65600 4.01 12.63 5190 TYPE 3:
93805 28 04-25 0 0.00 0.00 0
93806 28 04-25 0 0.00 0.00 0
93807 28 04-25 0 0.00 0.00 0
93808 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on site for inspection of the above-referenced items. Reinforcing steel
was reviewed in accordance with structural drawings. Placement of concrete was done by
pump and consolidated through mechanical vibration. All items inspected were in conformance
with approved plans and drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 4 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB015
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Placement and Consolidation
of Concrete in Progress
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB018
PERMIT #: 1851, 1853 DATE: 4/3/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Building D Stem Walls and Plinth Bases, Building F Perimeter and Plinth Footings
Sample Location: Building F Plinth Bases
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.00 15
Mix # 02550C Air Content, % (C231) NT
Mix Description 7/8" Aggregate Unit Weight, pcf (C138) NT
Truck/Ticket # C141 / 220086 Air/Mix Temp.,°F (C1064) 58 / 60 JM5
Strength Required 3000 psi at 28 days Field Cure Temperature, °F
Quantity Placed, cy 80 Cure Method - Initial / Final Container / Water Tank
Time Batched 9:20 AM Water Added on Job, gals 0
Time Sampled 9:40 AM Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
93984 7 04-10 59820 4.02 12.69 4710 TYPE 2:
93985 28 05-01 77500 4.00 12.57 6170 TYPE 2:
93986 28 05-01 77370 4.00 12.57 6160 TYPE 2:
93987 28 05-01 78730 4.00 12.57 6260 TYPE 2:
93988 30 05-03 73590 4.01 12.63 5830 TYPE 2:
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site for inspection of the items referenced above. Reinforcing
steel was reviewed per schedule on S3.1 for the footings, 7/S4.1 for the stem walls and
12/S4.1 for the plinths. Concrete was placed via pump and was consolidated through
mechanical vibration. All items inspected were in conformance with the approved plans and
drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB018
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Concrete Placement and
Consolidation in Progress
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB028
PERMIT #: BLDG 1851 DATE: 4/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Placement Location: Building D Exterior Slabs on Grade
Sample Location: First Truck, Directly From Chute, Mid-Pour, Western Exterior Slabs
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 5.50 9
Mix # 0260A6C Air Content, % (C231) 4.0 1
Mix Description 6 Sack, 7/8" agg, pea agg, MBAE 90, MB Poly 997 Unit Weight, pcf (C138) NT
Truck/Ticket # C116 / 615870 Air/Mix Temp.,°F (C1064) 47 / 63 TC5
Strength Required 3000 psi at 28 days Field Cure Temperature, °F 40/72
Quantity Placed, cy 30 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:15 AM Water Added on Job, gals 0
Time Sampled 8:00 AM Water Requested by
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
95107 7 05-03 68260 4.01 12.63 5400 TYPE 3: Exterior
95108 28 05-24 76430 4.00 12.57 6080 TYPE 2: Exterior
95109 28 05-24 77160 4.00 12.57 6140 TYPE 2: Exterior
95110 28 05-24 75490 4.00 12.57 6010 TYPE 2: Exterior
95111 Hold 00-00 0 0.00 0.00 0 Exterior
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to provide concrete placement observation,
inspection, and testing services. Concrete was placed via pump truck and was hand finished.
For reinforcement inspection, please refer to report IR011. GeoTest will return for further
observation and inspection as requested.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB028
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Figure 1. The placement and
hand finishing process of
exterior slabs on grade
(looking northwest).
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB029
PERMIT #: BLDG 1851 DATE: 4/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tristan Coragiulo
Placement Location: Building D Interior Slab on Grade
Sample Location: First Truck, Mid-Pour, Directly from Chute, Western Interior Slab
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.50 9
Mix # 02550C Air Content, % (C231) NT
Mix Description 5.5 Sack, 7/8" agg, pea agg, MB Poly 997, MB NC 534 Unit Weight, pcf (C138) NT
Truck/Ticket # C060 / 615873 Air/Mix Temp.,°F (C1064) 50 / 60 TC5
Strength Required 3000 psi at 28 days Field Cure Temperature, °F NA
Quantity Placed, cy 115 Cure Method - Initial / Final Container / Water Tank
Time Batched 7:55 AM Water Added on Job, gals 17
Time Sampled 8:50 AM Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
95112 7 05-03 48270 4.01 12.63 3820 TYPE 3: Interior
95113 28 05-24 63310 4.00 12.57 5040 TYPE 2: Interior
95114 28 05-24 59590 4.00 12.57 4740 TYPE 2: Interior
95115 28 05-24 61560 4.00 12.57 4900 TYPE 3: Interior
95116 Hold 00-00 0 0.00 0.00 0 Interior
Reinforcement Inspection NT n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms NT n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest was on site as requested to provide concrete placement observation,
inspection, and testing services. Concrete was placed via pump truck and hand finished. For
reinforcement inspection, please refer to report IR011. GeoTest will return for further
observation and inspection as requested.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: CB029
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Figure 1. The placement and
hand finishing process of
interior slab on grade concrete
(looking northeast).
Concrete Inspection & Compressive Strength Test Report
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: CB056
PERMIT #: 1853, 1851, 1883 DATE: 7/12/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Placement Location: Garage 6, Garage 4, and Bus Stop Stem Walls
Sample Location: Garage 6, First Load, Middle of the Batch
Field Data: Eq. No.
Supplier Miles Sand and Gravel Company Slump, in. (C143) 6.00 15
Mix # 02550C Air Content, % (C231) NT
Mix Description 7/8" Agg, 5.5 Sack Unit Weight, pcf (C138) NT
Truck/Ticket # C011 / 124192 Air/Mix Temp.,°F (C1064) 73 / 74 JM3
Strength Required 4000 psi at 28 days Field Cure Temperature, °F NT
Quantity Placed, cy 20 Cure Method - Initial / Final Container / Water Tank
Time Batched 1:13 PM Water Added on Job, gals 10
Time Sampled 2:10 PM Water Requested by Contractor
Laboratory Data:
Lab Test Age Test Total Load Avg.D Area Compressive
No. (Days) Date (lbs) (in) (in²) Strength (psi)
98840 7 07-19 52380 4.00 12.57 4170 TYPE 2:
98841 28 08-09 65540 4.00 12.57 5210 TYPE 2:
98842 28 08-09 64680 4.00 12.57 5150 TYPE 2:
98843 28 08-09 62660 4.00 12.57 4980 TYPE 2:
98844 Hold 00-00 0 0.00 0.00 0
Reinforcement Inspection Yes n/a: not applicable Specimen Size 4" X 8"
Reinforcement Conforms Yes n/t: not tested Test Reference ASTM C31/C39/C1231
Comments: GeoTest on-site for inspection of the stem walls referenced above. Reinforcing steel was inspected
per detail 8/S4.1. Concrete was placed by pump and consolidated through vibration. All elements inspected
were in conformance with approved plans and drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD027
PERMIT #: BLDG 1851 DATE: 2/19/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Suzie Miller
Compaction Of: Building Pad D
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 TOG DT/2 125.9 20.5 104.4 1 79 95 F
2 See Figure 1 TOG DT/2 138.3 11.9 123.6 1 93 95 F
3 See Figure 1 TOG DT/6 140.5 13.4 123.9 1 93 95 F
4 See Figure 1 TOG DT/10 123.5 12.7 120.2 1 91 95 F
5 See Figure 1 TOG DT/10 134.3 14.5 117.3 1 88 95 F
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4330A Select Borrow Imported, Vienna 132.8 7.9 13 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek/3500/3052 M/D Standard Count: 425/3163
Comments: See comments on page 2.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
daveb@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avsc
ommunities.com, jonr@exxelpacific.com, kolander@arlingtonwa.gov ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD027
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
TOG - Top of Grade
GeoTest was onsite as requested to provide in-place density testing at the above
location for building pad D.
Structural fill was placed in approximate 4" lifts and compacted with an
Ingersoll-Rand-70Dsingle drum vibrating roller. All tests failed to meet
compaction requirements. The subgrade was observed pumping underfoot and
the roller. GeoTest noted that moisture content was well above optimum.
GeoTest will return to the site for retesting of these areas.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD027
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Figure 1 - Approximate test
locations.
Figure 2 - Compaction of fill
with roller.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD028
PERMIT #: BLDG Permit #1851 DATE: 2/20/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Suzie Miller
Compaction Of: Building Pad D
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 -3.0 DT/10 132.3 11.0 119.0 1 90 95 F
2 See Figure 1 -2.5 DT/8 132.8 11.7 118.9 1 90 95 F
3 See Figure 1 -2.5 DT/10 135.3 12.5 120.3 1 91 95 F
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4330A Select Borrow Imported, Vienna 132.8 7.9 13 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek/3500/3052 M/D Standard Count: 429/3141
Comments: See comments on page 2.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
daveb@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avsc
ommunities.com, jonr@exxelpacific.com, kolander@arlingtonwa.gov ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD028
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
GeoTest was onsite as requested to provide in-place density testing at the above location for
building pad D.
Structural fill was placed in approximate 4" lifts and compacted with an Ingersoll-Rand-70D
single drum vibrating roller. All tests failed to meet compaction requirements.
The subgrade was observed pumping underfoot and the roller. GeoTest noted that moisture
content was well above optimum.
GeoTest will return to the site for retesting of these areas.
Figure 1 - Approximate test
locations.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD028
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Figure 2 - Compaction with
roller.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD029
PERMIT #: BLDG Permit #1851 DATE: 2/21/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Suzie Miller
Compaction Of: Building D Structural Fill
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 SW Corner of Pad -2.5 10T 134.9 13.0 119.3 1 90 95 F
2 SW Corner of Pad TOG TOG 137.7 10.8 124.3 1 94 95 F
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4330A Select Borrow Imported, Vienna 132.8 7.9 13 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek/3500/2082 M/D Standard Count: 409/3172
Comments: See comments on page 2
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
daveb@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avsc
ommunities.com, jonr@exxelpacific.com, kolander@arlingtonwa.gov ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD029
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
TOG - Top of Grade.
GeoTest was onsite as requested to provide in-place density testing at the above location for
building pad D.
The structural fill was placed in approximate 4" lifts and compacted with an Ingersoll-Rand-70D
single drum vibrating roller. All tests failed to meet compaction requirements.
The subgrade was observed pumping underfoot and the roller. GeoTest noted that moisture
content was well above optimum.
GeoTest observed a proof-roll on Building Pad B with an Ingersoll-Rand-70D single drum
vibrating roller. Pumping and defection was seen in the subgrade.
GeoTest will return to the site for retesting of these areas.
Figure 1 - Building D Pad
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD029
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Figure 2 - Proof-roll with singe
drum roller.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD030
PERMIT #: BLDG Permit #1851 DATE: 2/22/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Suzie Miller
Compaction Of: Building Pad D
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 SW Corner of Pad TOG BS 127.3 14.6 111.1 1 84 95 F
2 Center of Pad TOG DT/6 141.2 13.8 124.0 1 93 95 F
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4330A Select Borrow Imported, Vienna 132.8 7.9 13 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek/3500/2082 M/D Standard Count: 405/3148
Comments: See comments on page 2. AMENDED 3/1/19: Please see FD033 for passing
retest results.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD030
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
TOG - Top of Grade
GeoTest was onsite as requested to provide in-place density testing at the above location for
building pad D.
GeoTest had previously tested these areas on 2/19/19 and the tests failed to meet compaction
requirements. (See Report FD027). It appeared that the areas had been recompacted since
GeoTest previous visits. All tests taken on this date failed to meet compaction requirements.
GeoTest will return to the site for retesting of these areas.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD031
PERMIT #: Building D 1851, Building F 1853 DATE: 2/25/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Harrison Simons
Compaction Of: Structural Fill Within Building Pads D and F
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 Building D Footprint - East TOG DT/8 134.4 13.6 118.3 1 89 95 F
2 Building D Footprint - Central TOG DT/8 130.1 8.0 120.5 1 91 95 F
3 Building D Footprint - West TOG DT/12 139.0 11.2 125.0 1 94 95 F
4 Building F Footprint - Central TOG DT/12 132.5 8.1 122.6 2 96 95 P
5 Building F Footprint - Central TOG DT/12 131.9 9.0 121.0 2 95 95 P
6 Building F Footprint - Central TOG DT/12 132.5 8.5 122.1 2 96 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4330A Select Borrow Imported from Vienna 132.8 7.9 13 ASTM D1557/D4718
2-4332A Structural Fill Lenz Enterprises (D-255) 127.2 9.6 ASTM D1557/D4718
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek / 3500 / 1505 M/D Standard Count: 722/2362
Comments: See comments on page 2.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
daveb@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cgengineering.com, jkim@avsc
ommunities.com, jonr@exxelpacific.com, kolander@arlingtonwa.gov ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD031
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
TOG - Top of Existing Grade.
Tests for Building D were conducted near the proposed subgrade elevation for the building.
Tests for Building F were conducted at approximately -2.5’ from proposed subgrade elevation
(according to the contractor)
GeoTest Services was on-site to provide in-place soil density and moisture testing on structural
fill that had been placed and compacted within the building footprint for Buildings D and F.
Compaction tests had attained the required compaction within the Building F footprint but had
not attained the required compaction within the Building D footprint. Structural fill within
Building Pad D was generally over the optimum moisture contents.
This test report has been marked discrepant because structural fill placed within the Building D
footprint had failed to attain the required compaction.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD032
PERMIT #: 1851, 1853 DATE: 2/26/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Compaction Of: Building D and F Pad Base
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 BLDG F, East Half 1’6" 12 133.8 7.2 124.8 1 98 95
P
2 BLDG F, West Half -3 12 134.6 8.0 124.6 1 98 95 P
3 BLDG D, NW Quadrant -3 12 139.1 11.3 124.9 2 94 95 F
4 BLDG D, NE Quadrant FSG 12 118.9 5.5 112.7 2 85 95 F
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4332A Select Borrow Lenz Enterprises 127.2 9.6 17 ASTM D1557
2-4330A Gravel Borrow Vienna 132.8 7.5 13 ASTM D1557
3- 0.0 None
Gauge Make/Model/Serial#: InstroTek/ 3500/BG164 M/D Standard Count: 430/3124
Comments: GeoTest on site for nuclear density testing of the building pads for buildings D and
F. Soils were compacted with a vibratory roller. AMENDED 3/1/19: Please see FD033 for
passing retest results.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD032
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Compaction of Subgrade for
Building D Pad
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD033
PERMIT #: 1851, 1853 DATE: 2/27/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Joel Morder
Compaction Of: Buildings D and F Building Pads
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 BLDG D, NE Quadrant FSG 12 144.7 10.4 131.1 1 99 95 P
2 BLDG D, N Center FSG 12 142.7 11.4 128.1 1 96 95 P
3 BLDG D, NW Quadrant -3 12 145.8 13.7 128.2 1 97 95 P
4 BLDG F, East half -6" 10 131.4 9.2 120.3 2 95 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4330A Gravel Borrow Vienna 132.8 7.9 13 ASTM D1557
2-4332A Gravel Borrow Lenz Enterprises 127.2 9.6 17 ASTM D1557
3- 0.0 None
Gauge Make/Model/Serial#: InstroTek/3500/BG164 M/D Standard Count: 421/3147
Comments: GeoTest on site for nuclear density testing of the above-referenced locations. Soils
were compacted using a drum vibratory roller. The passing results of this inspection correct the
failing results from GeoTest’s Field Density-Moisture Reports FD027 through FD032.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD033
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Potholed Section of Building
Pad D, in NW Quadrant
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD034
PERMIT #: BLDG Permit #1851 and BLDG Permit #1853 DATE: 2/28/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Suzie Miller
Compaction Of: Subgrade of Building D and Building F
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 West Side of Pad D -1.5 DT/12 131.5 8.0 121.7 1 96 95 P
2 East Side of Pad F -0.5 DT/6 131.0 8.3 120.9 1 95 95 P
3 Middle of Pad F -2.0 DT/12 131.7 7.3 122.7 1 96 95 P
4 West Side of Pad F -3.0 DT/8 134.3 8.0 124.4 1 98 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4332A Select Borrow Lenz Enterprises (D-255) 127.2 9.6 17 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Instrotek/3500/2082 M/D Standard Count: 403/3142
Comments: See comments on page 2.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 6 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
741 Marine Drive, Bellingham, WA 98225 www.geotest-inc.com
20611 67th Ave. NE. Unit A. Arlington, WA 98223
phone: (360) 733.7318 toll free: (888) 251.5276 fax: (360) 733.7418
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD034
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
All locations and elevations are approximate and provided by the contractor.
GeoTest was onsite, as requested to provide in-place density testing on the structural fill of the
building pads for buildings D and F.
Prior to GeoTest’s arrival, the structural fill had been placed and partially compacted. While
GeoTest was on site, the structural fill of building F was compacted with an Ingersollrand
SD-70D single drum vibrating roller. All tests met compaction requirements.
GeoTest noted that pumping underfoot was felt on the western section of building pad D.
Pumping was observed with light foot traffic.
Figure 1 - Compaction of
Building Pad F
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: FD048
PERMIT #: 1851 DATE: 4/17/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Devin Murphy
Compaction Of: Subgrade for Slab-on-Grade
Field Data:
Depth/ DT/ Wet Field Dry Compaction
Test Location Elev BS Density Moisture Density Lab % Pass/
# (ft) (in) (pcf) (%) (pcf) # Attained Required Fail
1 See Figure 1 FG DT/12 131.9 8.9 121.2 1 95 95 P
2 See Figure 1 FG DT/12 131.3 9.0 120.4 1 95 95 P
3 See Figure 1 FG DT/12 132.6 9.8 120.8 1 95 95 P
4 See Figure 1 FG DT/12 135.2 10.0 122.9 1 97 95 P
Lab Max. Dry Optimum Retained
Sample Soil Type Source Density Moisture On #4 Test
# (pcf) (%) (%) Method
1-4332A PGS w/G Lenz Enterprises Pit (D-255) 127.2 9.6 17 ASTM D1557/D4718
2- 0.0 None
3- 0.0 None
Gauge Make/Model/Serial#: Troxler/3440/22281 M/D Standard Count: 589/1853
Comments: FG - Final Grade
As requested, GeoTest was onsite to provide in-place soil density testing at building D interior
slab subgrade. The slab subgrade was placed and compacted prior to our arrival. Adequate
compaction of at least 95% of the materials maximum dry density was achieved at the
locations tested.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 7 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
The above test results relate only to the sample (or location) tested.
FIELD DENSITY/MOISTURE REPORT
Nuclear Gauge * ASTM D6938
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: FD048
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Figure 1. Image of
approximate test locations.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF026
PERMIT #: B-1849, D-1851, E-1852, F-1853 DATE: 5/21/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm, Sheathing Buildings B, D and F 3rd Floor
Shear Wall Sheathing Building E, 2nd Level Entry Wall
Reference Drawings: Structural Drawing
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Sturdi-Floor, 23/32", Exp.1 (Walls Rated Sheathing 15/32" Exp.1)
Shear wall/diaphragm length, location Per Plan at Above Locations
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148" X 2-1/4", 6 & 10"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: Geotest was on site as requested to inspect the above items. The sheathing at the locations was
found to be in conformance with the project structural drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF029
PERMIT #: 1848, 1851, 1864 DATE: 5/28/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Walls: Sheathing Building D, Second Floor Entry Walls (Sheathing is Per Plan)
Shear Wall Sheathing and Holdown Straps Bldg A, Level 1, 2 & 3 All Exterior Locations In Progress
Shear Walls: Interior Framing Rec. Building Inspection in Progress
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size LSL; D-Fir, Hem-Fir
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location
Panel edges bear on framing members Shear Walls Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Sheathing, 148" X 2-1/4"
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Yes
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The sheathing at building D second level entry walls was complete and in accordance with the project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF036
PERMIT #: 1850, 1851, 1852 DATE: 6/6/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Roof Diaphragm: Sheathing Building C
Floor Diaphragm: Sheathing Building D, 3rd Floor
Shear Wall: Sheathing Building E, 1st Floor
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Per Plan
Shear wall/diaphragm length, location
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
The contractor corrected all items GeoTest discovered on site. Above items were in conformance with the
project drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF038
PERMIT #: 1851, 1853. 1862, 1863 DATE: 6/10/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 3
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing Buildings D and F, 3rd Floor Entry Walls
Final Framing (In Progress Inspection) Building P, 1st Floor and Building Q all Levels
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size Per Plan
Structural panel grade and thickness, glue Per SW Schedule
Shear wall/diaphragm length, location As Detailed
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related As Detailed
Connection of blocking to wall top plates A35 and LTP4 Clips Were in Place
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Per SW Schedule
Nail diameter, length, number of lines, spacing Per SW Schedule
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location HDU, Per Plan
Lag bolts/proper hole size At Stair Stringer to Landing Connections
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. See below for
additional comments.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF038
CONTRACTOR: Exxel Pacific PAGE #: 2 of 3
Many of the stud packs, which
the holdown straps are
connected to, were not nailed
together per detail 3 on sheet
S5.1
Some of the blocks connecting to the first joist were
toenailed but the drawings require three 131 X 3" nails
through the joist and into the end of the blocking.
The contractor is in the process of adding the nails in
accordance with detail 3 on sheet S5.2 of the project
drawings.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF038
CONTRACTOR: Exxel Pacific PAGE #: 3 of 3
Building Q: West End Wall
Plate Damage:
The top and bottom plates
were damaged with drilled
holes. The contractor has
added CS16 strap at these
damaged locations as per the
project engineer directions.
Along with the above three
items, the floor joists adjacent
to the center entry were
installed at 16" on center, but
the drawings require the joist
at these locations to be
spaced at 12" on center.
The contractor will address
this item.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF051
PERMIT #: 1851, 1853, 1855, 1857 DATE: 7/2/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 1
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm Sheathing Buildings H & K, 2nd Level
Roof Diaphragm Sheathing Buildings D & F
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" , T&G, Exp.1 . Roof Sheathing, 15/32" Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Where Required
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 2-1/4", Per Plan
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Roof Sheathing: Contractor Added Nails at Over-Driven Locations
Hold down, type, location
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on-site as requested to inspect the items mentioned above. All items found were
addressed prior to our leaving the project. The above items were found to be in conformance with the project
drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF056
PERMIT #: 1851, 1858 DATE: 7/9/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Floor Diaphragm: Sheathing Building L, 2nd Level
Shear Wall Sheathing and HD Strapping Building D, Levels 1 to 3
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sturd-i-Floor, 23/32" (SW-15/32") , T&G, Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing .148 X 3", 3, 4 and 12" On center
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Satisfactory
Hold down, type, location MST37 and 48 HD Straps, CMST14 Perf. SW Straps
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the items mentioned above.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF056
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Building L 2nd level floor sheathing was found to be in conformance with the project structural
drawings.
Building D exterior shear walls were in progress. All areas were marked at the location
describing the issue and correction.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF057
PERMIT #: 1851 DATE: 7/11/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 2
CONTRACTOR: Exxel Pacific INSPECTOR: Tim Martin
Item(s) Inspected Location
Shear Wall Sheathing and HD Strapping-Reinspection Building D: All Exterior Shearwalls, Levels 1 to 3
Reference Drawings: Structural Drawings
Items Inspected Comments
Lumber grade, species, size
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Plan
Panel edges bear on framing members SW’s are Fully Blocked
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Yes and Yes
Foundation plates or sills on concrete are treated
Base-plate bolting complies
Nail diameter, length, number of lines, spacing
Pneumatic or mechanically driven fasteners conform
Nail heads driven flush Yes
Hold down, type, location MST37 & 48 Floor to Floor Straps and CMST48 at Perf. SW’s
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF057
CONTRACTOR: Exxel Pacific PAGE #: 2 of 2
Photo of the area marked
during our previous inspection.
This area was addressed
along with all other marked
areas. The contractor has
addressed the items which
were found during our
previous inspection or noted
as in progress in framing
report LF056 (dated 7/9/19).
Building D exterior shear wall
sheathing and straps at levels
1 to 3 are now in conformance
with the project structural
drawings.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
ADDRESS: 18506 Smokey Point Boulevard, Arlington, WA REPORT #: LF082
PERMIT #: 1851, 1879, 1880, 1886 DATE: 9/11/2019
CLIENT: Villas at Arlington Partners LLLP PAGE #: 1 of 4
CONTRACTOR: Exxel Pacific INSPECTOR: John Silk
Item(s) Inspected Location
Final Framing and Interior Shear Wall Sheathing Building D, Garages 15+16, Storage Building
Reference Drawings: Approved Structural Drawings
Items Inspected Comments
Lumber grade, species, size DougFir #2
Structural panel grade and thickness, glue Rated Sheathing, 15/32", Exp.1
Shear wall/diaphragm length, location Per Structural Plan
Panel edges bear on framing members Yes
Diaphragm chord, drag strut, braces and related
Connection of blocking to wall top plates Hardware per Shearwall Schedule
Gypsum board with wood framing conforms
3" nom. framing in place, nails staggered where shown Per Shearwall Schedule
Foundation plates or sills on concrete are treated Yes
Base-plate bolting complies Per Shearwall Schedule
Nail diameter, length, number of lines, spacing Per Shearwall Schedule
Pneumatic or mechanically driven fasteners conform Per General Notes
Nail heads driven flush Acceptable
Hold down, type, location Per Structural Drawings
Lag bolts/proper hole size
Cold-formed framing-proper size, gage, spacing
Screw type, spacing, driven flush
Cold-formed welding conforms (AWS D1.1 and D1.3)
Other
The above items were conforming Nonconforming Items (see below)
Comments: GeoTest was on site as requested to inspect the above items. The contractor
addressed all items prior to GeoTest’s departure. Buildings inspected for framing and interior
sheathing were in conformance with the drawings.
COPIES: brian.j.anderson7@gmail.com, charliesr@cmaarch.com, chumphrey@safebuilt.com, cobyj@exxelpacific.com, Reviewed by
davidb@exxelpacific.com, davidh@exxelpacific.com, dennist@cgengineering.com, dspencer@safebuilt.com, jaredu@cg
engineering.com, jkim@avscommunities.com, jonr@exxelpacific.com ...and 5 more.
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF082
CONTRACTOR: Exxel Pacific PAGE #: 2 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF082
CONTRACTOR: Exxel Pacific PAGE #: 3 of 4
LATERAL FRAMING INSPECTION REPORT
PROJECT: The Villas at Arlington JOB #: 18-0760
CLIENT: Villas at Arlington Partners LLLP REPORT #: LF082
CONTRACTOR: Exxel Pacific PAGE #: 4 of 4
SPECIAL INSPECTION SUMMARY
PROJECT: The Villas at Arlington â€Â BLD D JOB #: 18â€0760
ADDRESS: 18506 Smokey Point Blvd, Arlington, WA 98223 DATE: 10â€22â€2019
CLIENT: Villas at Arlington Partners LLLP PERMIT #: 1851
CONTRACTOR: Exxel Pacific PAGE: 1 of 1
This letter summarizes our special inspection and testing efforts for The Villas at Arlington – BLD D
project located in Arlington, Washington. GeoTest’s services took place from October 9, 2018
through October 22, 2019. Our testing and inspections included the following scope of work:
TEST/INSPECTION ITEM REFERENCE
Field Density Moisture Reports FD023, FD027
 Earthwork – FD034 & FD048 and Soil Observation Report
SO003
Concrete Break Reports CB015, CB018, CB019,
ï‚· Reinforced Concrete
CB028 & CB029 and Inspection Report IR011
Lateral Framing Inspection Reports LF026,
ï‚· Lateral Framing LF029, LF036, LF038, LF051, LF056, LF057,
LF078 & LF082
Adhesive Anchor Inspection Reports AA009 &
ï‚· Proprietary Anchors
AA019
All work requiring special inspection for the project to date has been completed. To the best of
our knowledge the inspected work is in conformance with the approved project plans and
specifications and the applicable workmanship provisions of the International Building Code. All
related laboratory tests performed by GeoTest have met or exceeded the minimum test
requirements.
This is GeoTest’s final special inspection and testing submittal for The Villas at Arlington â€Â BLD D
project. If we can be of further assistance, please contact the undersigned.
Copies: Villas at Arlington Partners LLLP Safe Built
Charles Morgan and Associates LLC The Alliant Company
City of Arlington Anderson, Brian
Exxel Pacific Charles Morgan and Associates LLC Logan Senrud
CG Engineering Technical Director
This report shall not be reproduced except in full, without the written approval of GeoTest Services, Inc.
Permit #: 1851
Permit Date: 03/09/18
Permit Type: MULTI-FAMILY
Project Name: Villas at Arlington
Applicant Name: Villas at Arlington, LLLP
Applicant Address: 105 Cresent Bay Drive, Suite D
Applicant, City, State, Zip: Laguna Beach, CA 92651
Contact: Carmel Gregory
Phone: 425-778-8500
Email: carmelg@cgengineering.com
Scope of Work: New Multi-Family Development
Valuation: 2503351.89
Square Feet: 23049
Number of Stories: 3
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 11/01/2018
Permit Expires:
Form Permit Type:
Status: COMPLETE
Assigned To: Kristin Foster
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
VILLAS AT 137 Multiple Family
31052000100800 3318 185TH PLACE NE
ARLINGTON 101 - 200 Units
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
323A CONSTRUCTION
EXXEL PACIFIC INC 360-734-2872 UBI 601 175 198
TELEGRAPH RD CONTRACTOR
323A CONSTRUCTION Labor and
EXXEL PACIFIC INC 360-734-2872 EXXELPI073KN
TELEGRAPH RD CONTRACTOR Industries
Plan Reviews
Date Review Type Description Assigned To Review Status
COMMERCIAL
03/09/2018 BUILDING
BUILDING
Fees
Fee Description Notes Amount
Building Plan Review Table 4-2 $10,254.61
Building Plan Review Table 4-2 $177.30
Building Permit Table 4-1 $16,049.09
Park - Community MF Multi-family $35,928.00
Processing/Technology $25.00
State Surcharge - Commercial Commercial Only $25.00
State Surcharge - add'l DU Residential Additional Units $48.00
Traffic Mitigation - C/MF Commercial/Multi-family $31,227.36
Total $93,734.36
Attached Letters
Date Letter Description
09/19/2018 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
03/08/2018 Alliant Capital Ltd. 18506 Bldg. D Check #104500 Kristin Foster $10,254.61
03/08/2018 Alliant Capital Ltd. 18506 Bldg. D Check #104500 Kristin Foster $177.30
10/11/2018 Fidelity National Title check #26379 Launa Black $83,302.45
Outstanding Balance $0.00
Uploaded Files
Date File Name
02/21/2020 6267004-Villas Bldg D C of O.pdf
11/01/2018 4145046-1851_Villas Building Permit.pdf
03/09/2018 3141529-Commercial Application - Building D.pdf
SUBMITTAL PACKAGE Page 1
DATE: 1/14/2019
Your Logo Here FOR APPROVAL PACKAGE NUM: 35
PACKAGE REV: 0
Exxel Pacific, Inc. SPEC #: 061753
201808. - Villas at Arlington
To: Dennis Titus From: Nick Santini
CG Engineering PLLC Exxel Pacific, Inc.
250 4th Ave South #200 323 Telegraph Road
Edmonds, WA 98020 Bellingham, WA 98226
We are transmitting the following Submittal Package Number: “35â€, Revision: “0†Description:
“Prefabricated Wood Trusses - Buildings C, D, K & L†for your review, intended to be compliant with
contract Specification Number: “061753â€.
Please review and respond to: Nick Santini, by: 1/28/2019 in accordance with the contract documents.
Additional Notes:
Spec Number Submittal Description Submittal Details
1. 061753 Prefabricated Wood Trusses - Buildings C, Shop Drawings
D, K & L
Sincerely,
Nick Santini
EXXEL PACIFIC, INC.
323 TELEGRAPH RD.
BELLINGHAM, WA
98226
✔
REVIEWED
BY Nick Santini DATE 1/14/2019
SUBMITTAL# 35 SPEC 061753