HomeMy WebLinkAbout19118 63rd Ave NE_BLD1801_2025
PLAN REVIEW COMMENTS
DATE: 10/12/2018
TO: Arlington Community Food Bank FROM: Amber Green
PHONE: PHONE: 206-718-7659
EMAIL: jerrie.inman@comcast.net EMAIL: agreen@safebuilt.com
PERMIT #: BLD1801 OCCUPANCY GROUP: S-2
PROJECT: Arlington Community Food Bank TYPE OF CONSTRUCTION: V-B
ADDRESS: 19118 63rd Ave NE NUMBER OF STORIES: 2
SAFEbuilt Inc. has reviewed the above project documents for conformance to the provisions of the 2015 International
Building Code, Uniform Plumbing Code, International Fuel Gas Code, International Mechanical Code and International
Energy Conservation Code as adopted and amended by the State of Washington and the City of Arlington.
The permit referenced above is recommended for release of the reviewed construction documents for this project. All
outstanding comments have been addressed in an adequate fashion and no comments remain. Please reference the
approved Deferred Submittal Agreement for outstanding requirements.
Please do not hesitate to contact me if any assistance is needed with this process.
Sincerely,
Amber Green
Plans Examiner
1621 114th Ave SE, Ste 219
Bellevue, WA 98004
agreen@safebuilt.com
City of Arlington
Community & Economic Development
March 3, 2018
Arlington Community Food Bank
19118 63rd Avenue NE
Arlington, WA 98223
Dear Ms. Inman,
The design documents submitted for this project have been reviewed for compliance with
the locally adopted codes and amendments. The following comments must be
addressed before a building permit is issued.
For processing:
ï‚· Please submit 2 sets of revised construction documents containing the requested
information or plan revisions with all revisions clouded or otherwise identified.
ï‚· Please respond in writing to each comment by marking the attached list or
creating a response letter. Indicate which plan sheet, detail, specification, or
calculation shows the requested information. Please send revisions to the attention
of the plans examiner with the building permit application number noted.
Revised drawings must clearly show code compliance.
A RESPONSE LETTER MUST BE INCLUDED WITH THE REVISED PLAN SUBMITTAL.
ï‚· Please be sure to include on the resubmittal the engineer’s or architect’s “wetâ€
stamp, signature, registration number and date on the cover page of any structural
calculations, all structural details and structural sheets of the plans.
In order to keep your permit in an “Active†status, please respond within 60 days. For
questions about the required information please contact Kevin Olander at 360-403-3433 or
kolander@arlingtonwa.gov.
Sincerely,
Kevin Olander
Combination Inspector
2015 IBC:
1. The upper landing does not meet the minimum headroom requirements of 80†per
the IBC Section 1011.3. Please revise location of stairs to meet minimum headroom
requirements. See attached IBC 1011.3
2. The chain guards at mezzanine edge do not meet the minimum requirements per
the IBC Section 1015.4 Exception 4. Please revise to meet maximum allowable
openings. See attached IBC 1015.4(4)
CITY OF ARLINGTON INSPECTION CARD
No building construction shall be commenced until permit holder
INSPECTION RECORD SHALL or his agent has posted this Inspection Record Card in a
REMAIN AT JOB SITE conspicuous place on the premises.
OWNER: CONTRACTOR:
JOB ADDRESS: LOT NUMBER TYPE GROUP
NATURE of WORK:
USE of BUILDING:
PERMIT No: DATE ISSUED:
INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB
DEPARTMENT INSPECTION DATE(S) PASS FAIL INITIALS
FOOTING
BUILDING FOUNDATION
(360) 403-3417 UNDERFLOOR
SHEARWALL
PLUMBING (groundwork)
ROUGH PLUMBING
GAS PIPING
ROUGH HEATING & VENTILATION
FRAMING
INSULATION
WALLBOARD (SHEAR/RATED WALLS)
CEILING GRID
STRUCTURAL SLAB
CROSS CONNECTION CONTROL IN PREMISE
(360) 403-3417 GRADING
TEMPORARY TECSP
ASBUILTS APPROVED
MAINTENANCE BOND
STORM DRAINAGE SYSTEM
PAVING, SIGNAGE & MARKINGS
LANDSCAPING
CONDITIONS
ONSITE UTILITIES WATER
ONSITE UTILITIES SEWER
Sewer OFFSITE UTILITIES WATER
(360) 403-3508 OFFSITE UTILITIES SEWER
SEWER PRETREATMENT
Water CROSS CONNECTION CONTROL PREMISE
(360) 403-3526 SIDE SEWER/ CLEANOUT/FINAL
WATER SERVICE INSTALLATION
WATER SERVICE FINAL
(360) 403-3417 HYDRO/FLUSH
UNDERGROUND**INCL FDC
FIRE ALARM /AUTOMATIC SPRINKLER
HOOD SUPPRESSION SYSTEM
FINAL FIRE WALK-THROUGH
(360) 403-3417 FINAL INSPECTION
ALL SIGNATURE BLOCKS MUST BE COMPLETE