HomeMy WebLinkAbout19118 63rd Ave NE_BLD1801_2025 PLAN REVIEW COMMENTS DATE: 10/12/2018 TO: Arlington Community Food Bank FROM: Amber Green PHONE: PHONE: 206-718-7659 EMAIL: jerrie.inman@comcast.net EMAIL: agreen@safebuilt.com PERMIT #: BLD1801 OCCUPANCY GROUP: S-2 PROJECT: Arlington Community Food Bank TYPE OF CONSTRUCTION: V-B ADDRESS: 19118 63rd Ave NE NUMBER OF STORIES: 2 SAFEbuilt Inc. has reviewed the above project documents for conformance to the provisions of the 2015 International Building Code, Uniform Plumbing Code, International Fuel Gas Code, International Mechanical Code and International Energy Conservation Code as adopted and amended by the State of Washington and the City of Arlington. The permit referenced above is recommended for release of the reviewed construction documents for this project. All outstanding comments have been addressed in an adequate fashion and no comments remain. Please reference the approved Deferred Submittal Agreement for outstanding requirements. Please do not hesitate to contact me if any assistance is needed with this process. Sincerely, Amber Green Plans Examiner 1621 114th Ave SE, Ste 219 Bellevue, WA 98004 agreen@safebuilt.com City of Arlington Community & Economic Development March 3, 2018 Arlington Community Food Bank 19118 63rd Avenue NE Arlington, WA 98223 Dear Ms. Inman, The design documents submitted for this project have been reviewed for compliance with the locally adopted codes and amendments. The following comments must be addressed before a building permit is issued. For processing:  Please submit 2 sets of revised construction documents containing the requested information or plan revisions with all revisions clouded or otherwise identified.  Please respond in writing to each comment by marking the attached list or creating a response letter. Indicate which plan sheet, detail, specification, or calculation shows the requested information. Please send revisions to the attention of the plans examiner with the building permit application number noted. Revised drawings must clearly show code compliance. A RESPONSE LETTER MUST BE INCLUDED WITH THE REVISED PLAN SUBMITTAL.  Please be sure to include on the resubmittal the engineer’s or architect’s “wet” stamp, signature, registration number and date on the cover page of any structural calculations, all structural details and structural sheets of the plans. In order to keep your permit in an “Active” status, please respond within 60 days. For questions about the required information please contact Kevin Olander at 360-403-3433 or kolander@arlingtonwa.gov. Sincerely, Kevin Olander Combination Inspector 2015 IBC: 1. The upper landing does not meet the minimum headroom requirements of 80” per the IBC Section 1011.3. Please revise location of stairs to meet minimum headroom requirements. See attached IBC 1011.3 2. The chain guards at mezzanine edge do not meet the minimum requirements per the IBC Section 1015.4 Exception 4. Please revise to meet maximum allowable openings. See attached IBC 1015.4(4) CITY OF ARLINGTON INSPECTION CARD No building construction shall be commenced until permit holder INSPECTION RECORD SHALL or his agent has posted this Inspection Record Card in a REMAIN AT JOB SITE conspicuous place on the premises. OWNER: CONTRACTOR: JOB ADDRESS: LOT NUMBER TYPE GROUP NATURE of WORK: USE of BUILDING: PERMIT No: DATE ISSUED: INSPECTOR MUST SIGN ALL SPACES PERTAINING TO THIS JOB DEPARTMENT INSPECTION DATE(S) PASS FAIL INITIALS FOOTING BUILDING FOUNDATION (360) 403-3417 UNDERFLOOR SHEARWALL PLUMBING (groundwork) ROUGH PLUMBING GAS PIPING ROUGH HEATING & VENTILATION FRAMING INSULATION WALLBOARD (SHEAR/RATED WALLS) CEILING GRID STRUCTURAL SLAB CROSS CONNECTION CONTROL IN PREMISE (360) 403-3417 GRADING TEMPORARY TECSP ASBUILTS APPROVED MAINTENANCE BOND STORM DRAINAGE SYSTEM PAVING, SIGNAGE & MARKINGS LANDSCAPING CONDITIONS ONSITE UTILITIES WATER ONSITE UTILITIES SEWER Sewer OFFSITE UTILITIES WATER (360) 403-3508 OFFSITE UTILITIES SEWER SEWER PRETREATMENT Water CROSS CONNECTION CONTROL PREMISE (360) 403-3526 SIDE SEWER/ CLEANOUT/FINAL WATER SERVICE INSTALLATION WATER SERVICE FINAL (360) 403-3417 HYDRO/FLUSH UNDERGROUND**INCL FDC FIRE ALARM /AUTOMATIC SPRINKLER HOOD SUPPRESSION SYSTEM FINAL FIRE WALK-THROUGH (360) 403-3417 FINAL INSPECTION ALL SIGNATURE BLOCKS MUST BE COMPLETE