HomeMy WebLinkAbout17309 40th Ave NE_BLD3319_2025 Permit #: 3319
Permit Date: 07/23/20
Permit Type: FIRE ALARM
Project Name: Cedar Pointe Apartments
Applicant Name: Guardian Security Systems
Applicant Address: 1743 1st Avenue S
Applicant, City, State, Zip: Seattle, WA 98134
Contact: Elizabeth Fisher
Phone: 206-945-8844
Email: efisher@guardiansecurity.com
Scope of Work: AES installation
Valuation: 500.00
Square Feet: 0
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code: Opportunity Zone
Permit Issued: 09/28/2020
Permit Expires: 01/19/2021
Form Permit Type:
Status: COMPLETE
Assigned To:
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
CITY OF ARL BSP #418
REC AFN 201808215006 & AMWA CEDAR 110 Senior Citizen
31052100306900 17309 40TH AVENUE NE
AMD BSP REC AFN POINTE FUND LP Exemption Residual
201811065001
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
CONSTRUCTION
Guardian Security 206-622-6545 1743 1st Ave S. Labor & Industries GUARDSS233K5
CONTRACTOR
Plan Reviews
Date Review Type Description Assigned To Review Status
07/23/2020 FIRE ALARM BUILDING
1. Permit and set of approved plans to remain on site
during installation. Installer(s) shall present NICET II
certification upon request.
2. Trouble condition to be verified for signaling circuits.
07/23/2020 FIRE ALARM Mike Makela
3. Signal transmission to Central Station Monitoring
Company to be verified.
4. Installation completion form shall be submitted prior to
project close-out.
Fees
Fee Description Notes Amount
FACP / Transmitter - New $125.00
Fire Alarm System Permit NFPA 72 - 105.7.3 $100.00
Processing/Technology $25.00
Credit Card Service $7.50
Total $257.50
Attached Letters
Date Letter Description
07/23/2020 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
Guardian Security Systems
09/24/2020 82457957 $250.00
Elizabeth Fisher
09/24/2020 82457957 Raelynn Jones $7.50
Outstanding Balance $0.00
Notes
Date Note Created By:
08/12/2020 Contractor paid for out of city. Kristin Foster
1. Permit and set of approved plans to remain on site during installation. Installer(s) shall
present NICET II certification upon request.
08/12/2020 2. Trouble condition to be verified for signaling circuits. Kristin Foster
3. Signal transmission to Central Station Monitoring Company to be verified.
4. Installation completion form shall be submitted prior to project close-out.
07/23/2020 Question of fees per the fee resolution. Kristin Foster
07/23/2020 Contractor COA license expired 6/30/2020. Emailed the link for payment to renew. Kristin Foster
Uploaded Files
Date File Name
09/27/2021 9771212-3319_IC 8.13.2020.pdf
09/28/2020 7423773-3319_Issued Permit.pdf
07/23/2020 7027392-3319_AES Specs.pdf
07/23/2020 7027293-3319_Application.pdf
✔
17309 40th Avenue N.E 31052100306900
1 AES Radio AES install 500.00
AMWA Cedar Pointe Fund LP area 500- n/a
30141 Agoura Rd Suite 100 Agoura 1H0i0lls0 CA 91301
Elizabeth Fisher 2066226545
2069458844 efisher@guardiansecurity.com
same as contractor same as same same as contractor
contractor as
Guardian Security Systems 206-945-8844
contrac
1743 1st Ave S Seattle WA 98134
tor
GUARDSS233k5 09/30/2020
Elizabeth Fisher efisher@guardiansecuritysystems.com
same as contractor same as contractor
same as contractor
same as same same as contractor
same as contractor contractor as same as contractor
contrac
tor
07/14/2020
Elizabeth Fisher
Letter of Provisional Authorization
Authorization is granted to the Owner and/or Facility Manager as shown below, for the purpose of rebroadcasting the
Snohomish County 911 public safety frequencies using class "A" bi-directional amplifiers (BDA’s) or Distributive Antenna
Systems (DAS). Class "B" BDA/DAS systems will not be granted authorization to retransmit on the Snohomish County 911 radio
system.
Facility Name: BDA/DAS Manufacturer:
Address:
BDA/DAS Model:
City: State: Zip Code:
Buisness Phone: Latitude of Donor Antenna:
Longitude of Donor Antenna:
Owner/Contact Name:
Address: Donor Antenna Height:
City: State: Zip Code:
TO BE FILLED OUT BY SNO911
Phone:
Email:
SNO911 Site Name:
TO BE FILLED OUT BY SNO911
SERS System Donor Site Assignment: Site Distance:
West Simulcast Darrington Index IR
Donor Antenna Heading:
East Simulcast Skykomish IR
This form is authorization to rebroadcast on the Snohomish County 911 radio frequencies. This is not approval from the Fire
Marshall or Authority having Jurisdiction that the system meets necessary codes or coverage requirements. Snohomish
County 911 and the Fire Marshall reserve the right to make on-site inspections at any time. If problems are believed to exist,
the Owner and/or Facility Manager shall power-off their DAS or BDA equipment at Snohomish County 911's request.
Snohomish County 911 also reserves the right to suspend or terminate this agreement at its discretion.
_______________________________ ______
Snohomish County 911 Representative Date
_______________________________
Print or Type Name
1121 SE Everett Mall Way, Suite 200 www.sno911.org Office: (425) 407-3911
Emergency Responder Radio System
Coverage Report Test Results
Date Prepared: Jul 8, 2020
Test Location: Cedar Point Sr. Housing
17309 40th Ave. NE
Arlington WA, 98223
Technician: Lance Stafford
FCC#: PG00048282
Building: Cedar Point Sr. Housing
Result: Pass
Test Report Summary
Channel/ Freq (MHz) Ph Type Mod NAC PCI Ant Cable Result Areas Critical Pts
Ch Group gain loss passed (%) passed (%)
2 853.75000 0.00 0.00 Pass 96/96 (100%) 0/0 (0%)
Test Details
Number of Floors Tested: 4 Result Calculation: By area per floor
Number of Areas Tested: 96 Area Pass Criteria: 95%
Number of Critical Points Tested: 0 Critical Points Pass Criteria: 99%
Equipment Configuration
Vendor Application Device Calibrated Date Antenna info
PCTEL SeeHawk Touch SeeGull IBflex Device rel 9-12-2019
rel 2.8.0.0 3.3.3.0
SN: 081908027
Provided by: Clearline Engineering
Page 1 of 11
Threshold Settings
DL Area UL Area DL Critical UL Critical Use for
Measurement Point Point Point Point grading
P25 Power (RSSI) -95.0 dBm -95.0 dBm -95.0 dBm -95.0 dBm Yes
DAQ 3.0 Yes
Floors Result
2
Floor Plan 853.75000
1 Pass
2 Pass
3 Pass
4 Pass
Provided by: Clearline Engineering
Page 2 of 11
Floor: 1
Channel: 2
Result: Pass
Areas Tested: 24 Area Points Pass Criteria: 95 %
Critical Points Tested: 0 Critical Points Pass Criteria: 99 %
Total Grid Size: 61370.0 sq. ft Frequency (MHz): 853.75000
Provided by: Clearline Engineering
Page 3 of 11
Floor: 1
Channel: 2
Area Report
Grid Area DL DL UL UL Result DL Comment
Power DAQ Power DAQ Loss
(dBm) (dBm) (dB)
1 1 -68.78 Pass
1 2 -60.54 Pass
1 3 -79.31 Pass
1 4 -73.25 Pass
1 5 -78.91 Pass
1 6 -77.02 Pass
1 7 -59.66 Pass
1 8 -70.73 Pass
1 9 -75.49 Pass
1 10 -76.12 Pass
1 11 -72.84 Pass
1 12 -55.24 Pass
1 13 -57.38 Pass
1 14 -56.63 Pass
1 15 -58.27 Pass
1 16 -46.46 Pass
1 17 -48.73 Pass
1 18 -52.67 Pass
1 19 -51.70 Pass
1 20 -48.64 Pass
1 21 -43.07 Pass
1 22 -60.01 Pass
1 23 -46.34 Pass
1 24 -43.83 Pass
Provided by: Clearline Engineering
Page 4 of 11
Floor: 2
Channel: 2
Result: Pass
Areas Tested: 24 Area Points Pass Criteria: 95 %
Critical Points Tested: 0 Critical Points Pass Criteria: 99 %
Total Grid Size: 56055.8 sq. ft Frequency (MHz): 853.75000
Provided by: Clearline Engineering
Page 5 of 11
Floor: 2
Channel: 2
Area Report
Grid Area DL DL UL UL Result DL Comment
Power DAQ Power DAQ Loss
(dBm) (dBm) (dB)
1 1 -64.61 Pass
1 2 -57.25 Pass
1 3 -68.40 Pass
1 4 -63.77 Pass
1 5 -77.14 Pass
1 6 -79.00 Pass
1 7 -50.41 Pass
1 8 -53.27 Pass
1 9 -60.00 Pass
1 10 -73.22 Pass
1 11 -82.49 Pass
1 12 -58.82 Pass
1 13 -46.97 Pass
1 14 -37.12 Pass
1 15 -52.03 Pass
1 16 -42.84 Pass
1 17 -53.31 Pass
1 18 -64.63 Pass
1 19 -49.79 Pass
1 20 -45.40 Pass
1 21 -54.34 Pass
1 22 -47.12 Pass
1 23 -60.94 Pass
1 24 -60.33 Pass
Provided by: Clearline Engineering
Page 6 of 11
Floor: 3
Channel: 2
Result: Pass
Areas Tested: 24 Area Points Pass Criteria: 95 %
Critical Points Tested: 0 Critical Points Pass Criteria: 99 %
Total Grid Size: 57718.4 sq. ft Frequency (MHz): 853.75000
Provided by: Clearline Engineering
Page 7 of 11
Floor: 3
Channel: 2
Area Report
Grid Area DL DL UL UL Result DL Comment
Power DAQ Power DAQ Loss
(dBm) (dBm) (dB)
1 1 -54.27 Pass
1 2 -65.11 Pass
1 3 -71.72 Pass
1 4 -78.95 Pass
1 5 -68.74 Pass
1 6 -69.82 Pass
1 7 -52.23 Pass
1 8 -52.59 Pass
1 9 -80.85 Pass
1 10 -82.34 Pass
1 11 -82.02 Pass
1 12 -73.41 Pass
1 13 -67.33 Pass
1 14 -55.57 Pass
1 15 -77.83 Pass
1 16 -58.29 Pass
1 17 -59.47 Pass
1 18 -66.39 Pass
1 19 -47.41 Pass
1 20 -53.89 Pass
1 21 -69.11 Pass
1 22 -59.77 Pass
1 23 -58.43 Pass
1 24 -67.42 Pass
Provided by: Clearline Engineering
Page 8 of 11
Floor: 4
Channel: 2
Result: Pass
Areas Tested: 24 Area Points Pass Criteria: 95 %
Critical Points Tested: 0 Critical Points Pass Criteria: 99 %
Total Grid Size: 62254.5 sq. ft Frequency (MHz): 853.75000
Provided by: Clearline Engineering
Page 9 of 11
Floor: 4
Channel: 2
Area Report
Grid Area DL DL UL UL Result DL Comment
Power DAQ Power DAQ Loss
(dBm) (dBm) (dB)
1 1 -62.72 Pass
1 2 -75.15 Pass
1 3 -81.23 Pass
1 4 -76.74 Pass
1 5 -82.59 Pass
1 6 -79.51 Pass
1 7 -68.19 Pass
1 8 -77.13 Pass
1 9 -74.58 Pass
1 10 -72.71 Pass
1 11 -79.65 Pass
1 12 -74.43 Pass
1 13 -56.37 Pass
1 14 -56.45 Pass
1 15 -75.10 Pass
1 16 -61.62 Pass
1 17 -62.80 Pass
1 18 -76.71 Pass
1 19 -62.11 Pass
1 20 -54.75 Pass
1 21 -61.57 Pass
1 22 -62.95 Pass
1 23 -64.06 Pass
1 24 -76.26 Pass
Provided by: Clearline Engineering
Page 10 of 11
Additional Info
Provided by: Clearline Engineering
Page 11 of 11