Global Project Values: Project Name: Ironwood Apartments Standby Hours: 24 Project ID: 24-166 Alarm Mins: 5 Prepared By: JEFF BROSSARD Derating Factor: 1.2 6808 Battery Calculator (SK) Date: 6/14/2024 Voltage Drop Warning Version 18.05.29 Threshold % : 10 Panel ID: 6808 Model: 6808 Add. Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: RISER ROOM Volts: 24 VDC Max Panel Current: 6.0 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ Ckt.# Circuit Name Qty %Drop Standby Alarm & Type 1000 Ft. One-Way Ohms EOL 6808 6808 CTRL Panel 1 0.190 0.250 SK Photo, Photo-T, PhotoR 0.000 0.000 SK Heat, Heat-HT, ROR 0.000 0.000 SK Beam, Beam-T 0.000 0.000 SK Duct 0.000 0.000 SK Acclimate 0.000 0.000 SK FIRE-CO 0.000 0.000 SK-PHOTO-W Photo W 58 0.012 0.261 SK-PHOTO-R-W Photo-R-W 0.000 0.000 SK-PHOTO-T-W Photo-T-W 0.000 0.000 SK-HEAT-W Heat-W 0.000 0.000 SK-HEAT-ROR-WHeat-ROR-W 0.000 0.000 SK-HEAT-HT-W Heat-HT-W 0.000 0.000 SK Control 0.000 0.000 SK Control-6 0.000 0.000 SK RelayMon-2 0.000 0.000 SK Monitor, Minimon 13 0.005 0.065 SK Monitor-2 0.000 0.000 SK Monitor-10 0.000 0.000 SK Pull-SA, Pull-DA 17 0.006 0.085 SK Relay 3 0.001 0.020 SK Relay-6 0.000 0.000 N/A SK Zone 0.000 0.000 SK Zone-6 0.000 0.000 SK Isolator Module 0.000 0.000 B224BI Isolator Base 0.000 0.000 B200SR Sounder Base 0.000 0.000 B200S Intelligent Sounder Base 0.000 0.000 B200SR-LF Low Freq Sounder Base 0.000 0.000 B200S-LF Low Freq Sounder Base 0.000 0.000 B224RB Relay Base 0.000 0.000 RTS151 Magnetic Remote Test 0.000 0.000 RTS151KEY Key Activated Test 0.000 0.000 RA100Z Remote LED 0.000 0.000 5860 LCD Remote Annunc 2 0.040 0.050 5824 Serial/Parallel Module 0.000 0.000 5496 Power Expander 0.000 0.000 5895XL Power Expander 0.000 0.000 5865-4 LED Annunciator (4G) 0.000 0.000 5865-3 LED Annunciator (3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 5883 Relay Module 0.000 0.000 SK-NIC Network Input Card 0.000 0.000 SK-FML Muilti-Mode Fiber Card 0 0.000 0.000 SK-FSL Single-Mode Fiber Card 0 0.000 0.000 NAC #1 Notification Appl Circuit ### 0.000 0.663 #14 Solid 2.52 200 1.01 19.73 3.28% NAC #2 Notification Appl Circuit ### 0.000 0.421 #14 Solid 2.52 250 1.26 19.86 2.65% NAC #3 Notification Appl Circuit ### 0.000 0.421 #14 Solid 2.52 300 1.51 19.76 3.14% NAC #4 Notification Appl Circuit ### 0.000 0.000 #14 Solid 2.52 0 0.00 20.40 0.00% Total Standby Current (Amps) 0.254 0.000 Total Alarm Current (Amps) Standby Time In Hours 24 2.236 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 6.096 0.083 Total Alarm AH Required Total Combined AH Required 6.28 0.186 Command Shortcuts Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 7.54 Configure Circuits Print Page 18AH PROVIDED Circuit Configuration Project Information Project Name: Ironwood Apartments Project ID: 24-166 Prepared By: JEFF BROSSARD Date: 6/14/2024 Ckt. Number: NAC #1 Panel ID: 6808 Ckt. Name: Notification Appl Circuit Use: Current Draw Each Current Draw Total Qty Device Standby Alarm Standby Alarm 2 P2WL 75CD 0.000 0.121 0.000 0.242 7 P2WL 15CD 0.000 0.054 0.000 0.378 1 SWL 15CD 0.000 0.043 0.000 0.043 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.663 Ckt. Number: NAC #2 Panel ID: 6808 Ckt. Name: Notification Appl Circuit Use: Current Draw Each Current Draw Total Qty Device Standby Alarm Standby Alarm 7 P2WL 15CD 0.000 0.054 0.000 0.378 1 SWL 15CD 0.000 0.043 0.000 0.043 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.421 Ckt. Number: NAC #3 Panel ID: 6808 Ckt. Name: Notification Appl Circuit Use: Current Draw Each Current Draw Total Qty Device Standby Alarm Standby Alarm 1 SWL 15CD 0.000 0.043 0.000 0.043 7 P2WL 15CD 0.000 0.054 0.000 0.378 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.421 Circuit Configuration Project Information Project Name: Ironwood Apartments Project ID: 24-166 Prepared By: JEFF BROSSARD Date: 6/14/2024 Ckt. Number: NAC #4 Panel ID: 6808 Ckt. Name: Notification Appl Circuit Use: Current Draw Each Current Draw Total Qty Device Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 SK-PS10 Battery Calculation Ironwood Bldg 1 HB-1 Secondary Power Source Requirements Standby Current (amps) Secondary Alarm Current (amps) Device Type Qty Current Draw Total Qty Current Draw Total Main Circuit Board Choose EOLR used ↓ 4.7k 1 X 0.1560 = 0.1560 1 X 0.1850 = 0.1850 Main Circuit Board with ZNAC-PS Class A card 0 X 0.1490 = 0.0000 0 X 0.1590 = 0.0000 NAC / Output # 1 1 X 0.0000 = 0.0000 1 X 0.6830 = 0.6830 NAC / Output # 2 1 X 0.0000 = 0.0000 1 X 0.1430 = 0.1430 NAC / Output # 3 1 X 0.0000 = 0.0000 1 X 0.1430 = 0.1430 NAC / Output # 4 1 X 0.0000 = 0.0000 1 X 0.2860 = 0.2860 NAC / Output # 5 1 X 0.0000 = 0.0000 1 X 0.2640 = 0.2640 NAC / Output # 6 1 X 0.0000 = 0.0000 1 X 0.2860 = 0.2860 NAC / Output # 7 1 X 0.0000 = 0.0000 1 X 0.1620 = 0.1620 Total Standby Load 0.1560 Total Alarm Load 2.1520 Note 1: You are fully responsible for verifying these calculations. Note 2: You only need to make entries in the yellow cells Calculation in Total Sheet Required Standby Time in Hours 24 Hours Standby Load Current (Amps) 0.1560 Amps X 24 = 3.744 AH Required Alarm Time in Hours 15 Minutes Alarm Load Current (Amps) 2.1520 Amps X 0.25 = 0.538 AH Total Current Load 4.28 AH *Multiply by the Derating Factor 1.2 = x 1.20 Total Ampere Hours Required 5.14 AH Recommended Batteries: BAT-1270 - 7AH Batteries * Derating Factor required to compensate for the non-linear discharge characteristic of a battery. Page 1 6/14/2024 SK-PS10 Circuit Detail NAC / Output # 1 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total SWL 15CD 3 x 0.000000 = 0.000000 3 x 0.043000 = 0.129000 P2RK 75CD 1 x 0.000000 = 0.000000 1 x 0.176000 = 0.176000 P2WL 15CD 7 x 0.000000 = 0.000000 7 x 0.054000 = 0.378000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.683000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.683000 14AWG 2.520000 100 0.504 20.055768 0.01687412 0.683000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 2 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total PC2WL 75CD 1 x 0.000000 = 0.000000 1 x 0.143000 = 0.143000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.143000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.143000 14AWG 2.520000 100 0.504 20.327928 0.00353294 0.143000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 3 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total PC2WL 75CD 1 x 0.000000 = 0.000000 1 x 0.143000 = 0.143000 0 x 0.000000 = 0 x 0.000000 = Page 2 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.143000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.143000 14AWG 2.520000 100 0.504 20.327928 0.00353294 0.143000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 4 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total PC2WL 75CD 2 x 0.000000 = 0.000000 2 x 0.143000 = 0.286000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.286000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.286000 14AWG 2.520000 100 0.504 20.255856 0.00706588 0.286000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 5 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total PC2WL 75CD 1 x 0.000000 = 0.000000 1 x 0.143000 = 0.143000 P2WL 75CD 1 x 0.000000 = 0.000000 1 x 0.121000 = 0.121000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 3 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.264000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.264000 14AWG 2.520000 100 0.504 20.266944 0.00652235 0.264000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 6 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total PC2WL 75CD 2 x 0.000000 = 0.000000 2 x 0.143000 = 0.286000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.286000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.286000 14AWG 2.520000 100 0.504 20.255856 0.00706588 0.286000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 7 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total P2WL 15CD 3 x 0.000000 = 0.000000 3 x 0.054000 = 0.162000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 4 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.162000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.162000 14AWG 2.520000 100 0.504 20.318352 0.00400235 0.162000 12AWG 1.59 0 0 20.400000 0 Page 5 6/14/2024 SK-PS10 Battery Calculation Ironwood Bldg 1 HB-2 Secondary Power Source Requirements Standby Current (amps) Secondary Alarm Current (amps) Device Type Qty Current Draw Total Qty Current Draw Total Main Circuit Board Choose EOLR used ↓ 4.7k 1 X 0.1560 = 0.1560 1 X 0.1850 = 0.1850 Main Circuit Board with ZNAC-PS Class A card 0 X 0.1490 = 0.0000 0 X 0.1590 = 0.0000 NAC / Output # 1 1 X 0.0000 = 0.0000 1 X 1.5120 = 1.5120 NAC / Output # 2 1 X 0.0000 = 0.0000 1 X 1.7280 = 1.7280 NAC / Output # 3 1 X 0.0000 = 0.0000 1 X 1.2960 = 1.2960 NAC / Output # 4 1 X 0.0000 = 0.0000 1 X 1.5120 = 1.5120 NAC / Output # 5 1 X 0.0000 = 0.0000 1 X 1.2960 = 1.2960 NAC / Output # 6 1 X 0.0000 = 0.0000 1 X 1.8720 = 1.8720 NAC / Output # 7 1 X 0.0000 = 0.0000 1 X 0.7560 = 0.7560 Total Standby Load 0.1560 Total Alarm Load 10.1570 Note 1: You are fully responsible for verifying these calculations. Note 2: You only need to make entries in the yellow cells Calculation in Total Sheet Required Standby Time in Hours 24 Hours Standby Load Current (Amps) 0.1560 Amps X 24 = 3.744 AH Required Alarm Time in Hours 15 Minutes Alarm Load Current (Amps) 10.1570 Amps X 0.25 = 2.539 AH Total Current Load 6.28 AH *Multiply by the Derating Factor 1.2 = x 1.20 Total Ampere Hours Required 7.54 AH Recommended Batteries: BAT-12180 - 18AH Batteries * Derating Factor required to compensate for the non-linear discharge characteristic of a battery. Page 1 6/14/2024 SK-PS10 Circuit Detail NAC / Output # 1 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 14 x 0.000000 = 0.000000 14 x 0.108000 = 1.512000 0 x 0.000000 = 0 x 0.176000 = 0 x 0.000000 = 0 x 0.054000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.512000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.512000 14AWG 2.520000 200 1.008 18.875904 0.07471059 1.512000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 2 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 16 x 0.000000 = 0.000000 16 x 0.108000 = 1.728000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.728000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.728000 14AWG 2.520000 200 1.008 18.658176 0.08538353 1.728000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 3 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 12 x 0.000000 = 0.000000 12 x 0.108000 = 1.296000 0 x 0.000000 = 0 x 0.000000 = Page 2 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.296000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.296000 14AWG 2.520000 200 1.008 19.093632 0.06403765 1.296000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 4 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 14 x 0.000000 = 0.000000 14 x 0.108000 = 1.512000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.512000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.512000 14AWG 2.520000 200 1.008 18.875904 0.07471059 1.512000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 5 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 12 x 0.000000 = 0.000000 12 x 0.108000 = 1.296000 0 x 0.000000 = 0 x 0.121000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 3 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.296000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.296000 14AWG 2.520000 200 1.008 19.093632 0.06403765 1.296000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 6 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 2 x 0.000000 = 0.000000 2 x 0.108000 = 0.216000 SWL 15CD 4 x 0.000000 = 0.000000 4 x 0.043000 = 0.172000 P2WL-LF 135 7 x 0.000000 = 0.000000 7 x 0.212000 = 1.484000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.872000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.872000 14AWG 2.520000 200 1.008 18.513024 0.09249882 1.872000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 7 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 7 x 0.000000 = 0.000000 7 x 0.108000 = 0.756000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 4 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.756000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.756000 14AWG 2.520000 200 1.008 19.637952 0.03735529 0.756000 12AWG 1.59 0 0 20.400000 0 Page 5 6/14/2024 SK-PS10 Battery Calculation Ironwood Bldg 1 HB-3 Secondary Power Source Requirements Standby Current (amps) Secondary Alarm Current (amps) Device Type Qty Current Draw Total Qty Current Draw Total Main Circuit Board Choose EOLR used ↓ 4.7k 1 X 0.1560 = 0.1560 1 X 0.1850 = 0.1850 Main Circuit Board with ZNAC-PS Class A card 0 X 0.1490 = 0.0000 0 X 0.1590 = 0.0000 NAC / Output # 1 1 X 0.0000 = 0.0000 1 X 1.5120 = 1.5120 NAC / Output # 2 1 X 0.0000 = 0.0000 1 X 1.7280 = 1.7280 NAC / Output # 3 1 X 0.0000 = 0.0000 1 X 1.2960 = 1.2960 NAC / Output # 4 1 X 0.0000 = 0.0000 1 X 1.5120 = 1.5120 NAC / Output # 5 1 X 0.0000 = 0.0000 1 X 1.2960 = 1.2960 NAC / Output # 6 1 X 0.0000 = 0.0000 1 X 1.1190 = 1.1190 NAC / Output # 7 1 X 0.0000 = 0.0000 1 X 1.3740 = 1.3740 Total Standby Load 0.1560 Total Alarm Load 10.0220 Note 1: You are fully responsible for verifying these calculations. Note 2: You only need to make entries in the yellow cells Calculation in Total Sheet Required Standby Time in Hours 24 Hours Standby Load Current (Amps) 0.1560 Amps X 24 = 3.744 AH Required Alarm Time in Hours 15 Minutes Alarm Load Current (Amps) 10.0220 Amps X 0.25 = 2.506 AH Total Current Load 6.25 AH *Multiply by the Derating Factor 1.2 = x 1.20 Total Ampere Hours Required 7.50 AH Recommended Batteries: BAT-12180 - 18AH Batteries * Derating Factor required to compensate for the non-linear discharge characteristic of a battery. Page 1 6/14/2024 SK-PS10 Circuit Detail NAC / Output # 1 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 14 x 0.000000 = 0.000000 14 x 0.108000 = 1.512000 0 x 0.000000 = 0 x 0.176000 = 0 x 0.000000 = 0 x 0.054000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.512000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.512000 14AWG 2.520000 250 1.26 18.494880 0.09338824 1.512000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 2 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 16 x 0.000000 = 0.000000 16 x 0.108000 = 1.728000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.728000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.728000 14AWG 2.520000 250 1.26 18.222720 0.10672941 1.728000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 3 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 12 x 0.000000 = 0.000000 12 x 0.108000 = 1.296000 0 x 0.000000 = 0 x 0.000000 = Page 2 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.296000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.296000 14AWG 2.520000 250 1.26 18.767040 0.08004706 1.296000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 4 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 14 x 0.000000 = 0.000000 14 x 0.108000 = 1.512000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.512000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.512000 14AWG 2.520000 250 1.26 18.494880 0.09338824 1.512000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 5 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 12 x 0.000000 = 0.000000 12 x 0.108000 = 1.296000 0 x 0.000000 = 0 x 0.121000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 3 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.296000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.296000 14AWG 2.520000 250 1.26 18.767040 0.08004706 1.296000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 6 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 8 x 0.000000 = 0.000000 8 x 0.108000 = 0.864000 SWL 15CD 1 x 0.000000 = 0.000000 1 x 0.043000 = 0.043000 P2WL-LF 135CD 1 x 0.000000 = 0.000000 1 x 0.212000 = 0.212000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.119000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.119000 14AWG 2.520000 200 1.008 19.272048 0.05529176 1.119000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 7 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 8 x 0.000000 = 0.000000 8 x 0.108000 = 0.864000 SWL 15CD 2 x 0.000000 = 0.000000 2 x 0.043000 = 0.086000 P2WL-LF 135CD 2 x 0.000000 = 0.000000 2 x 0.212000 = 0.424000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 4 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.374000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.374000 14AWG 2.520000 200 1.008 19.015008 0.06789176 1.374000 12AWG 1.59 0 0 20.400000 0 Page 5 6/14/2024 SK-PS10 Battery Calculation Ironwood Bldg 2 HB-1 Secondary Power Source Requirements Standby Current (amps) Secondary Alarm Current (amps) Device Type Qty Current Draw Total Qty Current Draw Total Main Circuit Board Choose EOLR used ↓ 4.7k 1 X 0.1560 = 0.1560 1 X 0.1850 = 0.1850 Main Circuit Board with ZNAC-PS Class A card 0 X 0.1490 = 0.0000 0 X 0.1590 = 0.0000 NAC / Output # 1 1 X 0.0000 = 0.0000 1 X 0.5540 = 0.5540 NAC / Output # 2 1 X 0.0000 = 0.0000 1 X 1.3310 = 1.3310 NAC / Output # 3 1 X 0.0000 = 0.0000 1 X 1.1880 = 1.1880 NAC / Output # 4 1 X 0.0000 = 0.0000 1 X 1.0800 = 1.0800 NAC / Output # 5 1 X 0.0000 = 0.0000 1 X 1.1880 = 1.1880 NAC / Output # 6 1 X 0.0000 = 0.0000 1 X 1.0800 = 1.0800 NAC / Output # 7 1 X 0.0000 = 0.0000 1 X 0.0000 = 0.0000 Total Standby Load 0.1560 Total Alarm Load 6.6060 Note 1: You are fully responsible for verifying these calculations. Note 2: You only need to make entries in the yellow cells Calculation in Total Sheet Required Standby Time in Hours 24 Hours Standby Load Current (Amps) 0.1560 Amps X 24 = 3.744 AH Required Alarm Time in Hours 15 Minutes Alarm Load Current (Amps) 6.6060 Amps X 0.25 = 1.652 AH Total Current Load 5.40 AH *Multiply by the Derating Factor 1.2 = x 1.20 Total Ampere Hours Required 6.47 AH Recommended Batteries: BAT-1270 - 7AH Batteries * Derating Factor required to compensate for the non-linear discharge characteristic of a battery. Page 1 6/14/2024 SK-PS10 Circuit Detail-BUILDING 2 NAC / Output # 1 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total P2WL 15CD 7 x 0.000000 = 0.000000 7 x 0.054000 = 0.378000 P2RK 75CD 1 x 0.000000 = 0.000000 1 x 0.176000 = 0.176000 0 x 0.000000 = 0 x 0.054000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.554000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.554000 14AWG 2.520000 200 1.008 19.841568 0.02737412 0.554000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 2 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 8 x 0.000000 = 0.000000 8 x 0.108000 = 0.864000 SWL 15CD 1 x 0.000000 = 0.000000 1 x 0.043000 = 0.043000 P2WL-LF 135CD 2 x 0.000000 = 0.000000 2 x 0.212000 = 0.424000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.331000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.331000 14AWG 2.520000 100 0.504 19.729176 0.03288353 1.331000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 3 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 11 x 0.000000 = 0.000000 11 x 0.108000 = 1.188000 0 x 0.000000 = 0 x 0.000000 = Page 2 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.188000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.188000 14AWG 2.520000 200 1.008 19.202496 0.05870118 1.188000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 4 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 10 x 0.000000 = 0.000000 10 x 0.108000 = 1.080000 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.080000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.080000 14AWG 2.520000 200 1.008 19.311360 0.05336471 1.080000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 5 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 11 x 0.000000 = 0.000000 11 x 0.108000 = 1.188000 0 x 0.000000 = 0 x 0.121000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 3 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.188000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.188000 14AWG 2.520000 250 1.26 18.903120 0.07337647 1.188000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 6 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total HWL-LF 10 x 0.000000 = 0.000000 10 x 0.108000 = 1.080000 0 x 0.000000 = 0 x 0.043000 = 0 x 0.000000 = 0 x 0.212000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 1.080000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 1.080000 14AWG 2.520000 250 1.26 19.039200 0.06670588 1.080000 12AWG 1.59 0 0 20.400000 0 NAC / Output # 7 Device Qty Non-Alarm Draw Total Qty Alarm Draw Total 0 x 0.000000 = 0 x 0.108000 = 0 x 0.000000 = 0 x 0.043000 = 0 x 0.000000 = 0 x 0.212000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Page 4 6/14/2024 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.000000 Current Draw Alarm Wire AWG/Type Ohms Per 1000' Length Actual Ohms Volts @ EOL %Drop 0.000000 14AWG 2.520000 200 1.008 20.400000 0 0.000000 12AWG 1.59 0 0 20.400000 0 Page 5 6/14/2024 6808 Addressable Fire Alarm Control Panel The 6808 is an addressable fi re alarm control panel (FACP) that can be confi gured to achieve an overall point capacity of up to 198 points. It has one built-in signaling line circuit (SLC), which can support 99 System Sensor® (SK) sensors and 99 SK modules or 127 Hochiki® (SD) devices per loop. A common communications and annunciation link allows up to 17 panels to be connected via copper or fi ber optic cable. A designated panel is confi gured as the communicator for all panels in the link for convenient single-point communications. It also has a built-in, dual- line POTs and IP communicator and optional cellular side-cars. 6808 The 6808 system can be enhanced by adding modules such as the 6860 remote annunciator which also has four programmable function It supports a variety of devices, including the buttons to help automate tasks and reduce time spent at the panel. 6860, 5860, and 6855 remote annunciators, 5824 serial parallel printer interface module (for SWIFT® wireless compatibility provides options for wireless detection printing system reports), the 5496 NAC expander, through a Class A mesh network. It is ideal for hard-to-wire locations, 5895XL power module, and SK or SD devices. buildings where new wiring is not allowed, or to provide an easy install fi re system for new construction projects. SWIFT devices can be combined with other hard-wired 6808 compatible devices. The 6808 also has Form C trouble relay, and two programmable Form C relays, along with powerful features such as drift compensation, pre- trouble maintenance alert, a built-in sensor test to comply with NFPA 72 calibration testing requirements, and calibration trouble alert. FE ATURES & BENEFITS • Capable of providing • Convenient • 6860 annunciator with • Programmable date • 125 software zones up to 198 points to ï¬ eld-upgradeable a 4 x 40 large display, setting for automatic and 125 output satisfy smaller ï¬ rmware and 4 programmable and convenient groups for fl exible installation needs function buttons. Daylight Saving Time design options • Integrated dual path Free-up time spent at changes • Connect up to 17 IP and POTs the panel. Program panels on one site with communications and • Built-in dual phone them for simple or convenient single- optional cellular line and digital alarm complex tasks. point access using the side-cars for reliable communicator/ SK-NIC Network backup • Built-in USB interface transmitter (DACT) for Interface Card. for convenient and additional Connected panels can quick programming communication have mixed compatible options FACP models. 6808 Product Information SIGNAL LINE CIRCUIT (SLC) non-coded) signaling services. The 6808 SLC loop supports multiple • UL Listed device types, maintenance alerts, and a • CSFM 7165-0559:0502 built-in sensor test to comply with NFPA 72 calibration testing requirements. • FDNY COA# 6246 • FM approved INDICATOR LIGHTS • Seismic (CA) (pending) • General Alarm (Red): Flashes if in alarm; solid when alarm is silenced 6808 KEYPAD ORDERING INFORMATION • Supervisory (Yellow): Flashes if a PROGRAMMING 6808: Addressable Fire Alarm supervisory condition exists; solid Control Panel. (Red cabinet). The 6808 system offers several options when supervisory is silenced to simplify and speed-up programming. COMPATIBLE ANNUNCIATORS • System Troubles (Yellow): Flashes JumpStart® AutoProgramming 6860: 4x40 LCD remote fire if a trouble condition exists; minimizes programming required to annunciator (4 lines and up to solid when trouble is silenced start a new system. The built-in keypad, 160 characters) per system; four • System Silenced (Yellow): or the 6860, 5860 or 6855 remote programmable buttons On when an alarm, trouble or annunciators give you on-site access 5860: 4x20 LCD remote fire supervisory condition has been to current system programming. You annunciator. 5860 is gray; 5860R is red silenced but not yet cleared can also program the system using the Honeywell Fire Software Suite 6855: 4x20 LCD remote fire • System Power (Green): Flashes (HFSS), which is Windows® based. annunciator for AC failure; solid when 5865-3 or 5865-4: LED annunciators power systems are normal SOFTWARE TOOLS can display up to 30 LEDs (15 red and USER INTERFACE SKST: Silent Knight Selection Tool 15 yellow). The 5865-4 has key switches provides the installer or design architect for silence and reset, and a system The 6808 built-in 4 x 20 annunciator with a Windows® software system trouble LED. with 80 character LCD display configuration tool to create a detailed and large easy-to-use tactile 5880: LED / IO module has 40 Bill of Material (BOM) and battery touchpad can be used for system programmable LED outputs and eight calculations. operation, programming and supervised dry contact inputs which are maintenance. It has five LEDs for HFSS: Honeywell Fire Software Suite useful for custom applications. You can alarm, supervisory, system trouble, provides communication and panel use up to eight 5880 modules on one system silenced and system power. programming, detector status, event control panel for maximum flexibility. history and additional data. Requires a Its compact size allows mounting inside System operations include silencing Windows-based computer. the annunciator, or in an accessory alarms and troubles, resetting alarms cabinet. and the display of alarm troubles and ADDITIONAL INFORMATION memory. The system's non-volatile Twisted-unshielded pair event history buffer stores 1,000 wire is recommended. events for viewing from the built- The 6808 also has 13 preset in or remote annunciator. System notification cadence patterns operations can be initiated with a (including ANSI 3.41). mechanical firefighter's key or a valid 4- to 7-digit operator's code. AGENCY LISTINGS AND APPROVALS NFPA 13, NFPA 15, NFPA 16, NFPA 70, NFPA 72: Central station; remote Signaling; Local Protective Signaling Systems; Auxiliary Protected Premises Unit; Water Deluge releasing service. Suitable for automatic, manual, waterflow, sprinkler supervisory (DACT 6808 COMPATIBLE DEVICES AND B200S-LF: Low-frequency intelligent smoke detector ACCESSORIES sounder base WSK-PHOTO-T: Wireless Multi-criteria See the data sheets listed below for a B224RB: Relay base photoelectric smoke detector with thermal complete listing of the SK, SD or SWIFT B224BI: Isolator base detection (135°F fixed temperture) and devices. B510W 4" base 53623: SK Devices Data Sheet SD COMPATIBLE ADDRESSABLE WSK-HEAT: Wireless Heat, (135°F fixed 53624: SD Devices Data Sheet DEVICES temperture) and B510W 4" base SD505-6AB: Addressable 6" base 350614, 350616 & 350618: SWIFT WSK-HEAT-ROR: Wireless heat, ROR wireless devices SD505-6IB: Addressable 6" short circuit (135°F fixed temperture) and B510W 4" isolator base base For a complete and current listing of compatible devices and accessories go to SD505-6RB: Addressable 6" relay base WSK-MONITOR: Wireless monitor module www.silentknight.com SD505-6SB: Addressable 6" sounder base WSK-RELAY: Wireless relay module Important: You cannot mix SK and SD SD500-AIM: Addressable input module W-USB: SWIFT Tools USB transceiver used devices in the same fire alarm system. (switch input) for communication with SWIFT devices SD500-ANM: Addressable notification SK COMPATIBLE ADDRESSABLE module SBUS ACCESSORIES DEVICES SD500-ARM: Addressable relay module 5496: A 6 amp notification power expander SK-ACCLIMATE: Multi criteria SD505-DTS-K: Remote test switch and with four power-limited notification photoelectric smoke detector with thermal LED indicator for the SD505-DUCTR appliance circuit outputs. 135°F fixed temperture SD505-DUCT: Addressable Duct Smoke 5883: Relay Interface. Provides 10 Form C SK-BEAM: Reflected beam smoke detector Detector. relays. without test feature SD505-DUCTR: Addressable Duct 5824: Serial/Parallel Printer Interface SK-BEAM-T: Reflected beam smoke Detector housing with relay base. Module for printer connection. detector with test feature SD505-HEAT: Absolute temperature 5895XL: Power Supply with six Flexputâ„¢ SK-CONTROL: Supervised control module heat detector. Trip point range from circuits, and two Form C relays. Max. 16 per SK-CONTROL-6: Six circuit supervised 135°F–150°F (0°C–37°C). system. control module SD500-LIM: Addressable Line isolator 5815RMK: Remote mounting kit. SK-DUCT: Photoelectric duct smoke module Dimensions: 10 3/8â€W x 10-3/16â€H x 3â€D detector with extended air speed range SD500-MIM: Addressable Mini input SK-FIRE-CO: Four criteria fire and carbon COMMUNICATION OPTIONS monitor module (switch input) monoxide detector CELL-CAB-SK: Cellular communicator, SD505-PHOTO: Photoelectric smoke SK-HEAT: Fixed thermal detector (135°F) metal enclosure with lock/key* detector SK-HEAT-ROR: Fixed rate of rise detector SD500-PS/-PSDA: Addressable Single or CELL-MOD: Cellular communicator, plastic (135°F) enclosure* dual action pull station SK-HEAT-HT: Fixed high temperature *Sole path, powered by panel. SD500-SDM: Addressable smoke detector thermal detector (190°F) module IPGSM-4G: Dual path fire alarm SK-ISO: Fault isolator module communicator, cellular and/or IP (primary SK-MINIMON: Mini monitor module AUDIBLE/VISIBLE DEVICES or backup, selectable) SK-MONITOR: Monitor module These AV devices are all 2-wire. Color: “R†SK-IP-2: Remote reporting via the Internet. SK-MONITOR-2: Dual input monitor indicates red; “W†denotes white. For a Requires a VisorAlarm® receiver at the module complete listing of Silent Knight AV devices central station SK-MON-10: 10 input monitor module go to www.silentknight.com. CHSRL/CHSWL: Wall chime/strobe MISC. ACCESSORIES SK-PHOTO: Photoelectric smoke detector CHSCRL/CHSCWL: Ceiling chime/strobe SK-NIC: Network Interface Card. Provides SK-PHOTO-T: Photoelectric smoke a common communications link for the detector with thermal (135°F fixed CHRL/CHWL: Wall chime 6808. temperture) HRL/HWL: Wall horn SK-NIC-KIT: Installation Accessory Kit SK-PHOTOR: Photoelectric detector with P2RL/P2WL: Wall horn/strobe SK-FML: Fiber-Optic Multi Mode, remote test capability PC2RL/PC2WL: Ceiling horn/strobe transmitter and receiver SK-PULL-SA: Addressable single action SRL/SWL: Wall strobe SK-FSL: Fiber-Optic Single Mode pull station SCRL/SCWL: Ceiling strobe RBB: Remote battery box accessory cabinet SK-PULL-DA: Addressable dual action pull SPSCRL/SPSCWL: Ceiling speaker/strobe for batteries that are too large to fit in the station SPSRL/SPSWL: Wall speaker/strobe FACP cabinet. Dimensions: 16†W x 10†H x SK-RELAY: Addressable relay module SPRL/SPWL: Wall speaker 6†D (406mm W x 254mm H x 152mm D). SK-RELAY-6: Addressable Six relay control SPCRL/SPCWL: Ceiling speaker SK-SCK: Seismic Compliance Kit used to module securely fasten batteries to the fire panel. SK-RELAYMON-2: Addressable Dual relay/ SWIFT WIRELESS DEVICES monitor module SWIFT is only compatible with SK-ZONE: Addressable zone interface module System Sensor (SK) devices. It is not compatible with Hochiki (SD) devices. SK-ZONE-6: Six zone interface module B210LP: 6" mounting base WSK-WGI: Wireless Gateway B501: 4" Flangeless mounting base WSK-PHOTO: Wireless Photoelectric B200S: Intelligent sounder base 6808 Technical Specifications PHYSICAL NOTIFICATION APPLIANCE CIRCUITS (NACs) For a complete listing of all Overall Dimensions: 16.36â€W x 26.37â€H x 3.91â€D Four programmable circuits which can be compliance approvals and certifications, please visit Shipping Weight: 32 lbs. programmed individually as: www.silentknight.com. Color: Red NACs: 3A @ 27.4VDC per circuit, power-limited (with a maximum current of 6A) Microsoft, Windows, and ENVIRONMENTAL Auxiliary Power Circuits: 3A @ 27.4VDC per circuit, the Windows Logo are registered trademarks Operating Temperature: 32°F to 120°F (0°C to power-limited or trademarks of 49°C) Microsoft Corporation. Humidity: 0 to 93% relative humidity (non- Supports Class B (Style 4) and Class A (Style 6 or 7) configuration for the SLC Silent Knight®, Honeywell® condensing) and SWIFT® are registered trademarks of Honeywell ELECTRICAL WIRING: See the product manual for wiring details International, Inc 6808 Primary AC: 120 VAC @ 60Hz, 3.3A Total Accessory Load: 6A @ 27.4VDC power-limited This document is not intended to be used for Standby Current: 190mA installation purposes. We Alarm Current: 250mA try to keep our product Battery Charging Capacity: 7 to 35AH information up-to date and accurate. We Battery Size: 7AH to 18AH max. allowed in control cannot cover all specific panel cabinet. Larger capacity batteries can be applications or anticipate housed in RBB accessory cabinet. all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 351608 | A | 11/17 800-328-0103 © 2017 Honeywell International Inc. SK-PS6 / SK-PS10 6 Amp and 10 Amp, 24 Volt Power Supplies The PS Series are independently configurable power supplies, allowing you to pair any input with any output, and feature LED diagnostics for troubleshooting. The PS Series is a remote power supply line from Silent Knight and is a direct replacement for the 5495/5499. The SK-PS6 is a 6 amp and the SK-PS10 is a 10 amp, remote power supply with battery charger that may be connected to any 12 or 24 volt fire alarm control panel (FACP) or used as a standalone power supply. The PS Series provides 24 VDC power for NACs (notification appliance circuits) configured as either Class B or Class A (requires the ZNAC-PS option card) with multiple sync protocol options. The PS Series also provides auxiliary power, constant or resettable, suited for detectors, annunciators, door holders, and other fire alarm system peripherals. The PS Series cabinet can hold two 7 AH or 18 AH batteries and can charge up to 33 AH batteries in a separate cabinet. FEATURES AND BENEFITS • Up to five (6 amp model) or seven (10 amp power supply, or a control module, single or corrosion-resistant powder coat chip and model) independently-configurable, power- multi, which may be housed within the scratch-resistant finish limited output circuits for: power supply cabinet • Cabinet designed with ten double –Class B and/or Class A NACs • Ability to cascade up to four power supplies knockouts and a removable door for ease of –Class B and/or Class A resettable or non- • Two (6 amp model) or three (10 amp model) installation and wiring resettable 24V auxiliary power fully-isolated input/control circuits which • Includes integral battery charger capable of –door holder power can be programmed to any output charging up to 33 AH batteries • Converts from Class B to Class A wiring • Two Form C normally-closed trouble relays • Cabinet can house two 7 AH or 18 AH without losing any outputs using the ZNAC- for AC Trouble and General Trouble batteries PS converter card (sold separately) • 6 or 10 amp full load output, respectively, • Battery charger may be disabled via DIP • Optimal for powering four-wire smoke with 3 A maximum/circuit switch for applications requiring larger detectors, annunciators, and other system • Individual NAC power and trouble LEDs for batteries and external battery charger peripherals requiring regulated power diagnostic efficiency • Removable terminal blocks accommodate • Optional addressable control, monitor, and • Trouble history mode for diagnostic support up to 12 AWG (3.1mm2) wire relay modules and power-supervision relay • Wide range end-of-line supervision value • Works with any UL 864 FACP which utilizes (EOLR-1) (normal: 2-27K ohms) an industry-standard reverse-polarity • Configurable for ANSI® Temporal 3 or • Selectable earth fault detection (enable or notification circuit Temporal 4 coded output disable) • UL-Listed NAC synchronization using • AC trouble report delay timer System Sensor®, Wheelock®, Gentex®, or • Completely configurable via onboard DIP AMSECO® appliances switches, no extra software required • Synchronization can be triggered from • Self-contained in compact, locking cabinet FACP NAC/remote sync outputs, cascaded constructed of heavy gauge steel with a ORDERING INFORMATION SK-PS6: 6.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, red SK-PS10: 10.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, red ZNAC-PS: Optional Class A converter card, sold separately SK-CONTROL: Addressable Control Module for one Class B or Class A zone of supervised, polarized Notification Appliances. Notification Appliance Circuit option requires external 24 VDC to power notification appliances. SK-RELAY: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch SK-MONITOR: Addressable Monitor Module for one zone of normally open dry-contact initiating devices. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Class B or Class A SK-MONITOR-2: Dual Monitor Module. Same as SK-MONITOR except it provides two inputs for Class B wiring only SK-RELAYMON-2: Provides two monitored inputs and two Form-C relays. Functions in Class B wiring only SK-CONTROL-6: Six-circuit supervised control module SK-RELAY-6: Six Form-C relay control module EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire smoke detector power BAT-1270-BP: Battery, 12 volt, 7.0 AH, 5-pack (two required) BAT-12180-BP: Battery, 12 volt, 18AH, 2-pack BAT-12330: Battery, 12 volt, 33AH SEISKIT-MULTI-1: Seismic kit for the PS Series. Includes bracket and hardware for two 7AH or two 18AH batteries. Page 2 of 3 — SK-61095:C • 3/10/2021 SK-PS6 / SK-PS10 TECHNICAL SPECIFICATIONS PRIMARY (AC) POWER SECONDARY POWER (BATTERY) CHARGING CIRCUIT Silent Knight® and System Sensor® SK-PS6: 120 VAC, 50/60 Hz, 5.0A are registered trademarks of maximum • Supports lead-acid batteries only Honeywell International, Inc. SK-PS10: 120VAC, 50/60 Hz, 6.2 A • Float-charge voltage: 27.6 VDC Wheelock® is a registered trademark maximum • Maximum current charge: 1.5 A of Cooper Technologies Company. Wire Size: #12-14 AWG with 600 V • Maximum battery capacity: 18 AH (inside Gentex® is a registered trademark of insulation cabinet) Gentex Corporation. AMSECO® is a COMMAND INPUT CIRCUIT • Maximum battery charging capacity: 33 AH registered trademark of Potter (external cabinet) Trigger Input Voltage: 9 to 32 VDC Electric Signal Company, LLC. Trigger Current: 2.0 mA (16 - 32 V); Per PHYSICAL ANSI® is a registered trademark of Input: 1.0 mA (9 - 16 V) the American National Standards Dimensions: 20.0â€H x 14.5â€W x 3.5â€D (cm: 50.8H x 36.83W x 8.9D) Institute, Inc. RELAY CIRCUITS ©2021 by Honeywell International Weight: with two 7Ah batteries is 24 pounds Trouble Contact Rating: 4 A at 24 VDC Inc. All rights reserved. (10.9 kg), with two 18 AH batteries is 39 OUTPUT CIRCUITS pounds (17.7 kg) Unauthorized use of this document is strictly prohibited. • 24 VDC filtered STANDARDS AND CODES • SK-PS6: TB8-TB9 – 1A Regulated, 3A The SK-PS complies with the following This document is not intended to be special applications; TB10-TB12 – 0.3A standards: used for installation purposes. We Regulated, 3A special applications NFPA 72: National Fire Alarm Code try to keep our product information • SK-PS10: TB8-TB11 – 1.5A Regulated, 3A up-to-date and accurate. We cannot UL 864: Standard for Control Units for Fire special applications; TB12-TB14 – 0.3A Alarm Systems (NAC expander mode) cover all specific applications or Regulated, 3A special applications anticipate all requirements. All UL 1481: Power Supplies for Fire Alarm • 6.0 A (SK-PS6) or 10.0 (SK-PS10) maximum Systems specifications are subject to change total continuous current for all outputs without notice. AGENCY LISTINGS AND APPROVALS Country of origin: USA These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S3511 CSFM: 7315-0559:0522 FDNY Approved FM Approved Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 SK-61095 | C | 03/21 www.silentknight.com ©2021 Honeywell International Inc. INTELLIKNIGHT ACCESSORY 5860 Remote Annunciator Bring the power to control an IntelliKnight fire alarm control panel to every area within your facility. Now you can operate and program your IntelliKnight system from up to eight locations throughout your facility. The 5860 remote annunciator provides the same advanced, easy-to-use interface found on the IntelliKnight panel’s built-in annunciator. The 80-character display and ergonomically designed keypad allow for simple and error-free system operation. All operations—including reset, silence, detector status checking, fire drill, and programming—are identical. Access to the system is through a firefighter’s key or an access code. For security, a special installation code is needed for programming functions. The 5860 connects to the IntelliKnight panel via the RS-485 system bus. Wire runs can be up to 6000 feet from the panel. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103. Description multiple 5860s Features include an 80-character • RS-485 interface to panel backlit LCD providing easy-to- • Operation and appearance is understand system messages. The identical to 5860 built-in annunciator is ergonomically annunciator designed with over-sized buttons • On-board piezo sounder audibly for the most frequently used indicates alarms, troubles, and supervisories features, like Reset and Silence. • Five status LEDs for alarm, In addition to status messages supervisory, trouble, silence and displayed on the LCD, there are AC power conditions five LEDs for alarm, supervisory, • Wiring lengths up to 6000 ft. from trouble, silence, and AC power the FACP (depending on wire status. gauge and number of devices on 5860 SBUS) Environmental The annunciator is available in gray • UL listed, complies with NFPA 72 Operating Temperature: 32ºF – to match virtually any decor and red for applications where the • CSFM approved 120ºF (0ºC – 49ºC) annunciator must stand out. The Electrical Specifications Humidity: 10% – 93% non- annunciator enclosure can be Operating Voltage: 24 VDC condensing surface or flush mounted. A trim Standby Current: 20 mA max Compatibility ring kit is available for surface Alarm Current: 25 mA The 5860 is compatible with the mounting. following FACP’s: Wiring Distance: 6,000 max. from Features FACP (depending on wire gauge • 5820XL Addressable Fire Control • 80-character backlit LCD display and number of devices on the Panel (4 lines with 20 characters on SBUS) • 5820XL-EVS FACP with each line) Emergency Voice System • Tactile and audible feedback Max Per System: 8 • 5808 Addressable Fire Control • Accepts user codes or fire Mechanical Specifications Panel fighter’s key Physical 9.1†W x 7.4†H x 1.5†D • 5700 Addressable Fire Control • Larger keypad buttons for system (23.1 W x 18.8 H x 3.8 D cm) Panel reset and silence Shipping Weight: 2.8 lbs (1.3 kg) Listings • Install up to eight 5860s per FACP Color NFPA 72; UL Listed; • Available in red or light gray 5860R: Red CSFM 7170-0559: 135; 5860: Gray MEA 429-92-E Vol. IX; • Support for simultaneous use of FM Approved INTELLIKNIGHT ACCESSORY 5860 Remote Annunciator Engineering Specifications The main control must have a built-in annunciator and must support up to eight remote annunciators. Remote annunciators shall have the same control and display layout so as to match the appearance of the built-in annunciator. Remote annunciators shall be available in two colors, red or light gray. Remote annunciators shall have identical functionality and operation as the built-in annunciator. All annunciators must have an 80-character LCD display and must feature five LEDs for: General Alarm, Supervisory, System Trouble, System Silence, and System Power. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of .040 inches. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad or by using a firefighter’s key. The annunciator must have two levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple user input simultaneously. Ordering Information 5860R Remote Annunicator four line LCD annunciator with 20 characters per line. Red. 5860 Remote Annunciator.Four line LCD annunciator with 20 characters per line. Gray. Accessories 5860TR Red Trim Ring for surface mounting. 5860TG Gray Trim Ring for surface mounting. This document is not intended to be used for installation purposes. We try to MADE IN AMERICA keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350224 Rev F subject to change without notice. For more information, contact Silent Knight © 2013 Honeywell International Inc. 12 Clintonville Road, Northford, CT 06472-1610. Phone: (800) 328-0103, Fax: (203) 484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com SK-PHOTO-W Series Intelligent Plug-In Photoelectric Smoke Detector Honeywell Silent Knight SK-PHOTO-W Series plug-in smoke detectors are designed for both performance and aesthetics. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The SK-PHOTO-W Series detector sensitivity can be programmed in the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. Dual electronic thermistors add 135°F (57°C) fixed temperature thermal sensing on the SK-PHOTO-T-W. The SK-PHOTO-R-W is a remote test SK-PHOTO-W capable detector for use with DNR Series duct detector housings. FE ATURES & BENEFITS • New modern profile for • Dual LED design • Expanded color • Optional relay, improved aesthetics provides 360° viewing options isolator, and sounder angle bases • Stable communication • SEMS screws for technique with noise • Remote test feature wiring of the separate • Plugs into separate immunity from the panel base base for ease of installation and • Low standby current • Built-in functional test maintenance switch activated by • Two-wire SLC external magnet connection • Built-in tamper- • Optional remote, resistant feature single- gang LED accessory • Sealed against back pressure DETECTOR SPACING AND INTELLIGENT BASES ACCESSORIES APPLICATIONS B300-6: White, standard flanged CK300: Color Kit (includes cover and Honeywell recommends spacing low-profile mounting base. trim ring), white, 10-Pack. detectors in compliance with NFPA 72. B300-6-BP: Bulk pack of B300-6, CK300-IV: Color Kit (includes cover In low airflow applications with smooth package contains 10. and trim ring), ivory, 10-Pack. ceiling, space detectors 30 feet (9m). B300-6-IV: Ivory, standard flanged CK300-BL: Color Kit (includes cover For specific information regarding low-profile mounting base. and trim ring), black, 10-Pack. detector spacing, placement, and B501-WHITE: White, standard M02-04-01: Detector test magnet. special applications refer to NFPA 72. European flangeless mounting base. UL M02-09-00: Telescoping test magnet. System Smoke Detector Application listed. RA100Z: Remote LED annunciator Guide, document A05-1003, is available B501-BL: Black, standard European at systemsensor.com SMB600: Surface Mounting Kit flangeless mounting base. UL listed. (flanged). B501-IV: Ivory, standard European INSTALLATION TR300: Replacement trim ring for flangeless mounting base. UL listed. The SK-PHOTO-W Series plug-in B300-6, white. B200S-WH: White, Intelligent, detectors use a separate base to TR300-IV: Replacement trimring for programmable sounder base. simplify installation, service, and B300-6-IV, ivory. maintenance. Installation instructions B200S-IV: Ivory, Intelligent, are shipped with each detector. programmable sounder base. B200SR-WH: White, Intelligent sounder Mount base (all base types) on an base for retrofit applications. electrical backbox which is at least 1.5" B200SR-IV: Ivory, Intelligent sounder (3.81 cm) deep. base for retrofit applications. B200S-LF-WH: White, Low Frequency NOTE: Intelligent, programmable sounder • Because of the inherent supervision base. provided by the SLC loop, end-of-line B200S-LF-IV: Ivory, Low Frequency resistors are not required. Wiring Intelligent, programmable sounder “T-taps†or branches are permitted for base. Style 4 (Class “Bâ€) wiring. B200SR-LF-WH: White, Low • When using relay or sounder bases, Frequency Intelligent sounder base for consult the installation sheet for device retrofit applications. limitations between isolator modules B200SR-LF-IV: Ivory, Low Frequency and isolator bases. Intelligent sounder base for retrofit applications. ORDERING INFORMATION B224RB-WH: White, plug-in System SK-PHOTO-W: Photoelectric smoke Sensor relay base. detector, white. B224RB-IV: Ivory, plug-in System SK-PHOTO-R-W: Photoelectric smoke Sensor relay base. detector, remote test capable, for use B224BI-WH: White, plug-in System with DNR(W) duct smoke detectors, Sensor isolator detector base. white. B224BI-IV: Ivory, plug-in System SK-PHOTO-T-W: Photoelectric smoke Sensor isolator detector base. detector with thermal sensing, white. SK-PHOTO-W Series Detector Technical Specifications PHYSICAL COMPATIBILITY For a complete listing of all compliance approvals and Height: 2.0" (51mm) installed in B300-6 base The SK-PHOTO-W series detectors are certifications, please visit compatible with the following Honeywell Silent www.silentknight.com. Diameter: 6.2" (156mm) installed in B300-6 base 4.1" (104 mm) installed in B501 base Knight fire alarm control panels: Microsoft, Windows, and the Windows Logo are Weight: 3.4 oz (95 g) 6820: Addressable fire alarm control panel registered trademarks or trademarks of 6820EVS: Addressable fire alarm control panel ENVIRONMENTAL Microsoft Corporation. with an emergency voice system. Operating Temperature range: Silent Knight®, System 6808: Addressable fire alarm control panel Sensor® and Honeywell® Photo: 32°F to 122°F (0°C to 50°C) are registered 6700: Addressable fire alarm control panel trademarks of Honeywell Photo with Thermal: 32°F to 100°F (0°C to International, Inc. 5700: Addressable fire alarm control panel 38°C) This document is not 5808: Addressable fire alarm control panel UL listed Velocity range: Photo/Photo with intended to be used for 5820XL: Addressable fire alarm control panel installation purposes. We Thermal: 0 to 4,000 fpm (0 to 20 m/sec) try to keep our product (suitable for installation in ducts) 5820XL-EVS: Addressable fire alarm control information up-to date and accurate. We Humidity: 10% to 93% non-condensing panel with an emergency voice system cannot cover all specific applications or anticipate Thermal Ratings: Fixed Temperature Set point: AGENCY LISTINGS AND APPROVALS all requirements. All 135°F (57°C) For exact certification listings for each model, specifications are subject please reference the respective agency Web site. to change without notice. ELECTRICAL RATINGS UL listed: S6173 For Technical Support, FM approved call 800-446-6444. Voltage Range: 15 to 32VDC peak CSFM: 7272-0559:0523 Operating Current @ 24VDC: 200µA (one communication every 5 seconds with green LED blink on communication) Maximum Current: 4.5mA @ 24VDC (one communication every 5 seconds with amber LED solid on). For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 Doc 351634 | Rev A | 04/18 800-328-0103 © 2018 Honeywell International Inc. Wiring SK-Pull-SA To Addressable Pull Station Next Addressable Document 52151 I56-3446-005 From Device FACP SLC SLC SK-Pull-SA Addressable Pull Station 1 2 3 4 Document 52151 I56-3446-005 STRIP GAUGE Description The SK-Pull-SA Addressable pull station is a non-coded, single-action manual pull station with a key-lock reset feature. It provides Silent Knight intelligent fire alarm control panels (FACP) with one addressable alarm initiating input. The addressable module is housed inside the pull station. The SK-Pull-SA is compatible with all Silent Knight intelligent panels that use the Intelligent Device Protocol (IDP). Refer to the FACP Installation Manual to determine if the Intelligent Device Protocol is supported. The SK-Pull-SA meets the ADAAG controls and operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5 P0252-03 P0267-00 lb. maximum pull force to activate the pull station. Operating instructions are molded into the pull station handle along with Braille text. Molded Terminal numbers are also present. WARNING! Do not loop wiring under any Conforms to ANSI/UL Standard 38. terminals. Break wire run to maintain IDC supervision. Ratings Normal Operating Voltage: 24VDC. Average Operating Current (LED Flash): 375 µA. CAUTION! Maximum Operating Current (LED On): 5 mA. Do not detach the door of the pull station during installation. The door of the pull station Temperature Range: 32°F – 120°F (0°C – 49°C). cannot be reattached to the backplate after the backplate has already been installed onto an Relative Humidity Range: 10% - 93% non-condensing. electrical box. Installation CAUTION! The SK-Pull-SA Addressable pull station can be surface mounted to a SB-I/O surface Install the Silent Knight SK-Pull-SA addressable pull station in accordance with these instructions, backbox or semi-flush mounted on a standard single-gang, double-gang or 4Ë (10.16 cm) applicable NFPA standards, national and local Fire and Electrical codes and the requirements square electrical box. The optional BG-TR trim ring can be used if the SK-Pull-SA is to be of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conducted semi-flush mounted. in accordance with the appropriate NFPA standards. Failure to follow these directions may result in failure of the device to report an alarm condition. Silent Knight is not responsible for Operation devices that have been improperly installed, tested or maintained. To activate the single-action pull station, simply pull down the handle. The word ‘ACTI- VATED’ appears after the handle is pulled down. This will remain until the pull station is reset. ADA Compliance The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O) For ADA compliance, if the clear floor space only allows forward approach to an object, the switch which closes upon activation of the pull station. maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space Resetting the Pull Station allows parallel approach by a person in a wheelchair, the maximum side reach allowed is 1. Insert the key into the lock and rotate 1/4 turn counterclockwise. 54 inches (137.16 cm). 2. Open the door until the handle returns to normal. 3. Close and lock the door. NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Opening the door will not activate or deactivate the alarm switch. 1 I56-3446-005 07-24 Setting the SK-Pull-SA Address The SK-Pull-SA Addressable pull station is factory preset with address ‘00.’ Set the address for the pull station by turning the rotary address switches on the addressable module mounted inside the pull station. Only one device per address is allowed. Multiple modules may not be set to the same address on the Signaling Line Circuit. Once the address is set, record it in the space provided on the product ID label located inside the pull station. 15 0 0 14 1 1 13 2 2 12 4 3 2 3 1 3 11 4 4 10 5 5 9 6 9 6 8 7 8 7 TENS ONES NORMAL ACTIV ATED P/N 50997 REV-A LOOP ADDRESS M UL NOTIFIER PRODUCT IDENTIFICANBG - 12 Series AHDHDHTION LABEL LISTEDUL Approved Label HereNON-CODED 23424 14 15 FIRE ALARM BOX 13 0 REFER TO DOCUMENT 1 12 2 11 3 10 4 5 9 8 6 7 ADDRESS 15 0 0 14 1 1 13 2 2 12 Note – Opening the pull 3 3 station door will not activate 11 LOOP 4 4 or deactivate the alarm switch. 10 5 5 9 6 9 6 8 7 8 7 LED OPERATION Alarm: Steady RED Normal: Flash GREEN Note: LED is visible through LED translucent handle. ROTARY ADDRESS SWITCHES 12 Clintonville Road Northford, CT 06472 P0130-00 203-484-7161 Fax: 203-484-7118 www.silentknight.com Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc. 2 I56-3446-005 ©2017 Honeywell. 07-24 Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features • Updated Modern Aesthetics The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry • Small profile devices for Horns and Horn Strobes with lower current draws and modern aesthetics. With white and red • Plug-in design with minimal intrusion into the back box plastic housings, standard and compact devices, and plain, FIRE, • Tamper-resistant construction and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. • Automatic selection of 12- or 24-volt operation at 15 and 30 candela The L-Series line of wall-mount horns, strobes, and horn strobes • Field-selectable candela settings on wall units: include a variety of features that increase their application versatility 15, 30, 75, 95, 110, 135, and 185 while simplifying installation. All devices feature plug-in designs • Horn rated at 88+ dBA at 16 volts with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming • Rotary switch for horn tone and two volume selections ground faults. • Mounting plate for all standard and all compact wall units • Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring • Electrically Compatible with legacy SpectrAlert and SpectAlert continuity before the device is installed. Advance devices • Compatible with MDL3 sync module Installers can also easily adapt devices to a suit a wide range • Listed for wall mounting only of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Agency Listings S5512 FM approved except 7125-1653:0504 S4011 for ALERT models 7135-1653:0503 3057383, 3057072 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17â„8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuitâ„¢ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411â„16 × 411â„16 × 21â„8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1,2 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6Ë L × 4.7Ë W × 1.91Ë D (143 mm L × 119 mm W × 49 mm D) Compact Wall-Mount Dimensions (including lens) 5.26†L x 3.46†W x 1.91†D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6Ë L × 4.7Ë W × 1.25Ë D (143 mm L × 119 mm W × 32 mm D) Compact Horn Dimensions 5.25†L x 3.45†W x 1.25†D (133mm L x 88mm W x 32mm D) 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) UL Max. Horn Current Draw (mA RMS) 8–17.5 Volts 16–33 Volts 8–17.5 Volts 16–33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Candela Range (15–115 cd) 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 Horn Tones and Sound Output Data Horn and Horn Strobe Output (dBA) 8–17.5 16–33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9* Coded High 85 90 90 10* 3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on the 2-wire horn strobes. L-Series Dimensions Compact Strobe / Horn Strobe Compact Horn Strobe / Horn Strobe Horn L-Series Ordering Information Model Description Model Description Wall Horn Strobes Horns P2RL 2-Wire, Horn Strobe, Red HRL Horn, Red P2WL 2-Wire, Horn Strobe, White HWL Horn, White P2GRL 2-Wire, Compact Horn Strobe, Red HGRL Compact Horn, Red P2GWL 2-Wire, Compact Horn Strobe, White HGWL Compact Horn, White P2RL-P 2-Wire, Horn Strobe, Red, Plain Accessories P2WL-P 2-Wire, Horn Strobe, White, Plain TR-2 Universal Wall Trim Ring Red P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO TR-2W Universal Wall Trim Ring White P2WL-SP 2-Wire, Horn Strobe, White, FUEGO SBBRL Wall Surface Mount Back Box, Red Wall Strobes SBBWL Wall Surface Mount Back Box, White SRL Strobe, Red SBBGRL Compact Wall Surface Mount Back Box, Red SWL Strobe, White SBBGWL Compact Wall Surface Mount Back Box, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT Notes: All -P models have a plain housing (no “FIRE†marking on cover) All -SP models have “FUEGO†marking on cover All -ALERT models have “ALERT†marking on cover 3825 Ohio Avenue • St. Charles, IL 60174 ©2017 System Sensor. Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. www.systemsensor.com AVDS86503 • 03/17 Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry • Plug-in design with minimal intrusion into the back box with lower current draws and modern aesthetics. With white and red • Tamper-resistant construction plastic housings, wall and ceiling mounting options, System Sensor • Automatic selection of 12- or 24-volt operation L-Series can meet virtually any application requirement. at 15 and 30 candela The entire L-Series product line of ceiling-mount strobes and horn • Field-selectable candela settings on ceiling units: strobes include a variety of features that increase their application 15, 30, 75, 95, 115, 150, and 177 versatility while simplifying installation. All devices feature a plug-in • Horn rated at 88+ dBA at 16 volts design with minimal intrusion into the back box, making installations • Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and time- consuming ground faults. • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity To further simplify installation, the L-Series utilizes a universal before device installation mounting plate so installers can mount them to a wide array of back • Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes. With an onboard shorting spring, installers can test wiring Advance devices continuity before the device is installed. • Compatible with MDL3 sync module Installers can also easily adapt devices to a suit a wide range of • Listed for ceiling mounting only application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Agency Listings S5512 FM approved except 7125-1653:0504 S4011 for ALERT models 7135-1653:0503 3057383 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17â„8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuitâ„¢ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11â„16 × 4 11â„16 × 2 1â„8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions (including lens) 6.8" diameter × 2.5" high (173 mm diameter × 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) (SBBCRL, SBBCWL) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS86800 UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) 8–17.5 Volts 16–33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 115 N/A 158 191 150 N/A 189 228 177 N/A 226 264 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones and Sound Output Data Horn and Horn Strobe Output (dBA) 8–17.5 16–33 Volts Volts Switch Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 AVDS86800 L-Series Dimensions Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box L-Series Ordering Information Model Description Model Description Ceiling Horn Strobes Ceiling Strobes PC2RL 2-Wire, Horn Strobe, Red SCRL Strobe, Red PC2WL 2-Wire, Horn Strobe, White SCWL Strobe, White SCWL-CLR-ALERT Strobe, White, ALERT Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White ©2017 System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensor.com Phone: 800-SENSOR2 • Fax: 630-377-6495 for current product information, including the latest version of this data sheet. AVDS86801 • 03/17 Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. Features SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic • Weatherproof per NEMA 4X, IP56 housings, wall or ceiling mounting options, and plain or FIRE-printed • Listed to UL 1638 (strobe) and UL 464 (horn) devices, SpectrAlert Advance can meet virtually any application • Compatible with System Sensor synchronization protocol and requirement, including indoor, outdoor, wet, and dry applications in legacy SpectrAlert products temperatures from −40°F to 151°F. • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, Like the entire SpectrAlert Advance line, outdoor horns, strobes, 135, 150, 177, and 185 and horn strobes for wall applications include a variety of features • Automatic selection of 12- or 24-volt operation at 15 and that increase application flexibility and simplify installation. First, 15/75 candela field-selectable settings, including candela, automatic selection of • Rotary switch for horn tone and three volume selections 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F Next, SpectrAlert Advance devices use a universal mounting plate • Universal mounting plate with an onboard shorting spring that for both wall and ceiling applications. This mounting plate includes tests wiring continuity before devices are installed an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without • Plug-in design with minimal intrusion into the back box mounting the devices and exposing them to potential construction • Tamper-resistant construction damage. Once the plates are mounted, all SpectrAlert Advance • Listed for ceiling or wall mounting devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- Agency Listings out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, knock-outs at the back. A screw-in NPT plug with an O-ring gasket S4011 (chimes, horn strobes, horns) chime strobes) S3593 (outdoor and alert strobes) 3023572 MEA452-05-E 7135-1653:189 (horns, chimes) for a watertight seal is included with each back box. SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuitâ„¢ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6Ë L × 4.7Ë W × 2.5Ë D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6Ë L × 4.7Ë W × 1.3Ë D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB) 5.7Ë L × 5.1Ë W × 2.0Ë D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) UL Max. Horn Current Draw (mA RMS) 8–17.5 Volts 16–33 Volts 8–17.5 Volts 16–33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-Temporal High 57 56 69 75 95 NA NA 181 176 Non-Temporal Medium 42 50 60 69 110 NA NA 202 195 Non-Temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) 8–17.5 Volts 16–33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) 16–33 Volts 16–33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Candela Derating Horn Tones and Sound Output Data For K series products used at low temperatures, listed Horn and Horn Strobe Output (dBA) candela ratings must be reduced in accordance with 8–17.5 16–33 24-Volt Nominal this table. Switch Sound Volts Volts Reverberant Anechoic Strobe Output (cd) Position Pattern dB DC FWR DC FWR DC FWR DC FWR Listed Candela Candela rating at –40°F 1 Temporal High 78 78 84 84 88 88 99 98 15 2 Temporal Medium 74 74 80 80 86 86 96 96 15/75 Do not use below 32°F 3 Temporal Low 71 73 76 76 83 80 94 89 30 4 Non- High 82 82 88 88 93 92 100 100 75 44 Temporal 95 70 5 Non- Medium 78 78 85 85 90 90 98 98 110 110 Temporal 115 115 6 Non- Low 75 75 81 81 88 84 96 92 135 135 Temporal 150 150 7†Coded High 82 82 88 88 93 92 101 101 177 177 8†Coded Medium 78 78 85 85 90 90 97 98 185 185 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. AVDS01201 SpectrAlert Advance Diagrams 4.7Ë 2.5Ë 6.8Ë Dia. 2.5Ë 5.6Ë Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box SpectrAlert Advance Ordering Information Model Description Wall Horn Strobes P2RK*†2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P2RHK*†2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) P2WK*†2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2WHK*†2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) P4RK†4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK*†Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) SRHK*†Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) SWK*†Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) SWHK*†Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) Horns HRK†Horn, Red, Outdoor (includes plastic weatherproof back box) Accessories SA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box Notes: * Add “-P†to model number for plain housing (no “FIRE†marking on cover), e.g., P2RK-P. †Add “-R†to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW. “Standard cd†refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd†refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. ©2012 System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensor.com Phone: 800-SENSOR2 • Fax: 630-377-6495 for current product information, including the latest version of this data sheet. AVDS01201 • 3/12 Indoor Selectable- Output Low Frequency Sounders and Low Frequency Sounder Strobes System Sensor L-Series audible visible notification products are rich with features guaranteed to maximize profits with lower current draw and modern aesthetics. Features The L-Series offers the most versatile and easy-to-use line of low frequency sounder and low frequency sounder strobes in the • 520 Hz ± 10% square wave tone, NFPA compliance industry. With white and red plastic housings, listed for wall and • Full candela range plus High/Low tone options to optimize current ceiling mounting, L-Series Low Frequency can meet virtually any draw for a wide variety of applications application requirement. • Compact, standard, and round ceiling options The low frequency sounder and low frequency sounder strobes were • Field-selectable candela settings. Wall units: 15, 30, 75, 95, 110, designed to address the NFPA 72 sleeping space requirements that 135, and 185. Ceiling units: 15, 30, 75, 95, 115, 150, and 177 require a low frequency notification appliance that operates within frequency range of 520 Hz ± 10% and is of a square wave tone. Like • Rotary switch for High/Low, Temp3, Temp4, and Continuous the entire L-Series product line they include a variety of features that settings. Sounder-only models also offer a Coded setting. increase their application versatility while simplifying installation. All • Plug-in design with minimal intrusion into the back box devices feature plug-in designs with minimal intrusion into the back • Mounting plate shorting spring checks wiring continuity before box, making installations fast and foolproof while virtually eliminating device installation costly and time-consuming ground faults. • Electrically compatible with legacy SpectrAlert and SpectrAlert To further simplify installation and protect devices from construction Advance devices (Direct replacement for HW/R-LF and damage, L-Series uses a universal mounting plate with an onboard P2R/WH-LF) shorting spring, so installers can test wiring continuity before the device is installed. • Compatible with MDL3 sync module • Wall and ceiling moun t options available Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, 24- • Updated modern aesthetics volt operation, and a rotary switch for 520 Hz low frequency sounder tones. Agency Listings PR452768 Horns only: 7135-1653:0516 S4011 Horn/Strobes: 7125-1653:0517 AVDS910-01 • 9/15/2020 • Page 1 L-Series Specifications Architect/Engineer Specifications General L-Series low frequency sounder and low frequency sounder strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17â„ 8-inch back box. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuitâ„¢ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit (0°C to 49°C) from a regulated DC or full-wave rectified unfiltered power supply. Low Frequency Sounder strobes shall have field-selectable candela settings. Wall units: 15, 30, 75, 95, 110, 135, and 185. Ceiling units: 15, 30, 75, 95, 115, 150, and 177. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone and have a permanent marking on the housing that reads “520 Hzâ€. Low Frequency Sounder The low frequency sounder shall be a System Sensor L-Series Model _______ listed to UL 464 and shall be approved for fire protective service. The low frequency sounder and the Sync•Circuitâ„¢ MDL3 Module accessory, if used, shall be powered from a notification appliance circuit output and shall operate on a nominal 24 volts (includes fire alarm panels with built-in sync). When used with the Sync•Circuit Module MDL3, 24-volt rated notification appliance circuit outputs shall operate between 16.5 to 33 volts. If the notification appliances are not UL 9th edition listed with the corresponding panel or power supply being used, then refer to the compatibility listing of the panel to determine maximum devices on a circuit. The low frequency sounder has an option to switch between temporal three or temporal four pattern, non- temporal (continuous) pattern and coded supply within the frequency range of 520 Hz ± 10% square wave tone. The low frequency sounder shall operate on a coded or non-coded power supply with high and low volume settings. Low Frequency Sounder Strobe Combination The low frequency sounder strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The low frequency sounder strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The sounder shall have an option to switch between a temporal three or temporal four pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The low frequency sounder on low frequency sounder strobe models shall operate on a non-coded power supply with high and low volume settings. The field selectable tones will sound within the frequency range of 520 Hz ±10% square wave tone. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The module shall mount to a 411â„ 16 × 411â„ 1 16 × 2 â„8-inch back box. The module shall also control two Class B circuits or one Class A circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Frequency Range 520 Hz ± 10% Strobe Flash Rate 1 flash per second Nominal Voltage Low Frequency Sounder Regulated 24 DC/FWR1 Nominal Voltage Range Low Frequency Sounder Strobe Regulated 24 VDC/FWR1 Operating Voltage Range 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Dimensions Wall Sounder Strobe (including lens) 5.6" L x 4.7" W x 1.9" D (142 mm L x 119 mm W x 49 mm D) Ceiling Sounder Strobe (including lens) 6.8†diameter x 2.47†high (173mm diameter x 62.7 mm D) Standard Wall Sounder 5.6" L × 4.7" W × 1.5" D (142 mm L × 119 mm W × 38 mm D) Compact Wall Sounder 5.25" L x 3.46" W x 1.5" D (133mm L x 88mm W x 38mm D) Ceiling Sounder 6.8" diameter x 1.4" high (173mm diameter x 36mm high) Standard Wall Sounder with SBBRL/SBBWL Surface 5.70†L x 4.8†W x 3.3†D Mount Back Box (145 mm L x 120 mm W x 87 mm D) Compact Wall Sounder with SBBGRL/SBBGWL Surface 5.4†L x 3.6†W x 3.0†D (137 mmL x 91mm W x 76 mm D) Mount Back Box Low Frequency Ceiling Sounder with SBBCRL/SBBCWL 6.9" diameter x 3.9" high (175mm diameter x 99mm high) Surface Mount Back Box Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. AVDS910-01 • 9/15/2020 • Page 2 UL Current Draw and Sound Output Data Low Frequency Sounder Strobe Current Draw (mA) and Sound Output (dBA) Sound Current Draw (mA) Output Wall Sounder Strobe (dBA) Volume 16-33 VDC 16-33 FWR 16-33 V Pos Tone Setting 15cd 30cd 75cd 95cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd DC FWR 1 Temporal 3 High 98 115 158 173 182 212 266 136 153 188 206 228 258 304 80 80 2 Temporal 3 Low 98 102 141 162 173 202 255 150 150 176 194 216 242 280 76 76 3 Temporal 4 High 98 108 137 151 178 202 252 200 198 169 188 212 242 290 80 80 4 Temporal 4 Low 102 104 122 136 163 187 237 176 174 154 173 197 227 275 76 76 5 Continuous High 141 158 198 216 234 264 305 190 207 249 268 289 321 368 80 80 6 Continuous Low 120 128 179 196 215 244 285 165 182 226 244 266 297 342 76 76 Sound Current Draw (mA) Output Ceiling Sounder Strobe (dBA) Volume 16-33 VDC 16-33 FWR 16-33 V Pos Tone Setting 15cd 30cd 75cd 95cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd DC FWR 1 Temporal 3 High 98 115 158 173 197 236 259 136 153 188 206 238 287 291 80 80 2 Temporal 3 Low 98 102 141 162 181 224 244 150 150 176 194 226 269 269 76 76 3 Temporal 4 High 98 108 145 161 186 224 249 200 198 169 189 222 269 277 80 80 4 Temporal 4 Low 102 104 122 136 170 208 227 176 174 154 173 206 252 263 76 76 5 Continuous High 141 158 198 216 245 293 295 190 207 249 268 302 357 357 80 80 6 Continuous Low 120 128 179 196 225 271 273 165 182 226 244 278 330 330 76 76 UL Max. Low Frequency Sounder Current Draw (mA RMS) Sound Current Draw Wall and Ceiling Sounder Output (dBA) (mA) Reverberant Volume 16–33 Volts 16–33 Volts Pos Tone Setting DC FWR DC FWR 1 Temporal 3 High 108 150 80 80 2 Temporal 3 Low 78 76 76 76 3 Temporal 4 High 111 151 80 80 4 Temporal 4 Low 80 76 76 76 5 Continuous High 111 151 80 80 6 Continuous Low 80 76 76 76 7 Coded High 111 151 80 80 8 Coded Low 80 76 76 76 *NOTE: For coded tones, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the sounder output will remain constantly on. Coded ratings provided are for continuous voltage. AVDS910-01 • 9/15/2020 • Page 3 L-Series Dimensions 4.700 1.453 4.700 1.453 (119.4 mm) (36.9 mm) (119.4 mm) (36.9 mm) 5.670 5.670 (144 mm) (144 mm) Wall LF Sounder Strobe Wall LF Sounder 1.438 2.470 6.830 (36.5 mm) 6.800 (62.7 mm) (173.5 mm) (173.5 mm) 1.377 (34.98 mm) 173,5] Ceiling/Wall LF Sounder Strobe Ceiling/Wall LF Sounder 3.455 1.453 [87,8] [36,9] 5.265 [133,7] Compact Wall LF Sounder Part No. Description Red White Low Frequency Sounder Strobes P2RL-LF P2WL-LF LF Sounder Strobe, Wall PC2RL-LF PC2WL-LF LF Sounder Strobe, Ceiling/Wall Low Frequency Sounders HRL-LF HWL-LF LF Sounder, Wall HGRL-LF HGWL-LF Compact LF Sounder, Wall HCRL-LF HCWL-LF LF Sounder, Ceiling/Wall Accessories MDL3R MDL3W Sync•Circuitâ„¢ Module, UL-listed SBBRL SBBWL Surface Mount Back Box, Wall SBBCRL SBBCWL Surface Mount Back Box, Ceiling SBBGRL SBBGWL Surface Mount Back Box, Wall, Compact System Sensor® is a registered trademark and Sync•Circuitâ„¢ is a trademark of Honeywell International, Inc. ©2020 System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensor.com Phone: 800-SENSOR2 • Fax: 630-377-6495 for current product information, including the latest version of this data sheet. AVDS910-01 • 9/15/2020 INTELLIKNIGHT ACCESSORY SK-Monitor Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Monitor is intended for use in intelligent, two-wire systems, where individual address of each module is selected using the built-in rotary switches. The SK-Monitor supports Class A supervised or Class B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. Features • Single contact monitor • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green in normal state and is solid red in alarm • Attractive ivory cover plate SK-Monitor • Rotary address switches for fast installation • SEMS screws for easy wiring Specifications • UL Listed Physical Height: 4.5†(11.4 cm) Installation Width: 4†(10.2 cm) The SK-Monitor mounts directly into a 4†square electrical box. The box must have a minimum depth of 2-1/8â€. A Depth: 1.25†(3 cm) surface mount electrical box (System Sensor® PN Shipping Weight: 6.3 oz (196 g) SMB500) is available from Silent Knight. Electrical Compatibility Operating Voltage: 15 – 32 VDC The SK-Monitor is compatible with the following Current Draw (LED on): 5.0 mA max IntelliKnight FACP’s: Operating Current (LED flashing): 375 µA 5700 5808 5820XL 5820XL-EVS INTELLIKNIGHT ACCESSORY Model SK-Monitor Intelligent Monitor Module 2-Wire Initiating Circuit Configuration, NFPA Style B 4-Wire Initiating Circuit Configuration, NFPA Style D Standby Current: Environmental 400 µA max @ 24 VDC (one communication every 5 Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) sec with 47K EOL) Humidity: 10% – 93% non-condensing 550 µA max @ 24 VDC (one communication every 5 sec with EOL <1K) Ordering Information 5.5 mA (with LED latched on) SK-Monitor Monitoring Module LED Current: 5.5 mA (with LED latched on)End-of-Line Resistance: 47K W Accessories Initiating Device Circuit Wiring Resistance: 1,500 W max SMB500 4†Square Surface Mount Electrical Box SLC Loop Resistance: 40 W max. This document is not intended to be used for installation purposes. We try to MADE IN AMERICA keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Silent Knight FORM# 350131 Rev D 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800) 328-0103, © 2013 Honeywell International Inc. Fax: (203) 484-7118. For Technical Support, Please call 8200-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Relay Intelligent Relay Module The SK-Relay Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built in rotary switches. For more information about the IntelliKnight system, or to locate you nearest source, please call 800-328-0103. Description The SK-Relay is an addressable relay module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Relay allows a Silent Knight FACP to switch discrete contacts by code command. The relay contains two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The SK-Relay contacts can be used for virtually any normally open or normally closed application. Each SK- SK-Relay Relay is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls the Installation SK-Relay, the relay is triggered by the FACP. The SK-Relay mounts directly into a 4†square Features electrical box. The box must have a minimum depth of 2-1/8â€. A surface mount electrical box • Two sets of Form C contacts (System Sensor® PN SMB500) is available from • Rotary address switches for fast installation Silent Knight • Contacts are rated for a variety of amps (see Specifications) Compatibility • Panel controlled status LED that flashes green in normal The SK-Relay is compatible with the following IntelliKnight FACP’s: state and is solid red in alarm 5820XL • Relay programming is completely flexible–can be mapped 5820XL-EVS 5808 to zone conditions 5700 • Polling LED visible through the cover plate 5600 (Rev 2.0 or higher) • Attractive ivory cover plate • SEMS screws for easy wiring • UL Listed INTELLIKNIGHT ACCESSORY Model SK-Relay Intelligent Relay Module Specifications End-of-Line Resistance: not used Physical Standby Current: 300 µA max @ 24 VDC (one Height: 4.65†communication every 5 sec with LED enabled) Width: 4.25†LED Current: 5.5 mA (with LED latched on) Depth: 1.1†SLC Loop Resistance: 40W max. Shipping Weight: 6.3 oz (196 g) Relay Contact Ratings Electrical 3.0A @ 30 VDC resistive Operating Voltage: 15 – 32 VDC 0.9A @ 110 VDC resistive Current Draw: 6.5 mA max (LED on) 0.9A @ 125 VAC resistive Operating Current: 0.5A @ 125 VAC inductive (PF = .35) 230 µA (LED flashing) direct poll 0.7A @ 75 VAC inductive (PF = .35) 255 µA (LED flashing) group poll This document is not intended to be used for installation purposes. We try MADE IN AMERICA to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350127 Rev D subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: © 2013 Honeywell International Inc. (800) 328-0103, Fax: (203) 484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com 425-244-1445 P.O. BOX 3711ARLINGTON, WA 98223LIC. BHFIRHF842KWPH: DESIGNER: JEFF BROSSARD NICET LEVEL 3 ID # 148093 LICENSE: BROSSJB951L7 REFERENCE: 2015 IFC AND 2016 NFPA 72 FIRE ALARM PLAN - BUILDING 2 - 2ND FLOOR 2 SCALE: 1/8"=1'-0" BUILDING 2 18620 WOODLANDS WAYARLINGTON, WASHINGTON IRONWOOD APARTMENTS ISSUES REV DATE DESCRIPTION TITLE: FIRE ALARM PLAN BUILDING 2 1ST & 2ND FLOORS DATE: JUNE 13, 2024 PROJECT NO.: 24-023 SHEET: FIRE ALARM PLAN - BUILDING 2 - 1ST FLOOR 1 SCALE: 1/8"=1'-0" FA-1 Original Size: 30"x42" 425-244-1445 P.O. BOX 3711ARLINGTON, WA 98223LIC. BHFIRHF842KWPH: DESIGNER: JEFF BROSSARD NICET LEVEL 3 ID # 148093 LICENSE: BROSSJB951L7 REFERENCE: 2015 IFC AND 2016 NFPA 72 BUILDING 2 18620 WOODLANDS WAYARLINGTON, WASHINGTON FIRE ALARM PLAN - BUILDING 2 - 3RD FLOOR 1 SCALE: 1/8"=1'-0" IRONWOOD APARTMENTS ISSUES REV DATE DESCRIPTION TITLE: FIRE ALARM PLAN BUILDING 2 3RD FLOOR DATE: JUNE 13, 2024 PROJECT NO.: 24-023 SHEET: FA-2 Original Size: 30"x42" 425-244-1445 P.O. BOX 3711ARLINGTON, WA 98223LIC. BHFIRHF842KWPH: DESIGNER: EQUIPMENT LEGEND JEFF BROSSARD NICET LEVEL 3 ID # 148093 LICENSE: BROSSJB951L7 REFERENCE: 2015 IFC AND 2016 NFPA 72 WIRE LEGEND FIRE ALARM ONE-LINE RISER DIAGRAM SCALE: NONE GENERAL NOTES: DESIGNED AUDIBILITY LEVEL PER SEQUENCE OF OPERATIONS OCCUPANCY CLASSIFICATION BUILDING 2 18620 WOODLANDS WAYARLINGTON, WASHINGTON IRONWOOD APARTMENTS ANNUNCIATE SOUNDER AT FACP ANNUNCIATE SOUNDER AT REMOTE ANNUNCIATORTRIGGER BUILDING AUDIBLE/VISUAL APPLIANCESWATERFLOW ALARM SIGNAL TO CENTRAL STATIONALARM SIGNAL TO CENTRAL STATIONTROUBLE SIGNAL TO CENTRAL STATIONSUPERVISORY SIGNAL TO CENTRAL STATION WATERFLOW DEVICE X X X X TAMPER DEVICE X X X ISSUES BUILDING PULL STATION X X X X REV DATE DESCRIPTION BUILDING SMOKE DETECTOR X X X X AC POWER LOSS X X X LOW BATTERY X X X TITLE: FIRE ALARM LEGENDS, NOTES AND RISER DIAGRAM DATE: JUNE 13, 2024 PROJECT NO.: 24-023 SHEET: FA-3 Original Size: 30"x42" From: Hailey Brossard To: Hannah Hardwick Subject: Re: BLD6047- Expiration Notice Date: Saturday, December 14, 2024 1:26:03 PM Attachments: image001.png This message is from an External Sender This message came from outside the City of Arlington Good Afternoon Hannah, I would like to request an extension on this permit as construction is not going to be finaled by next month. Construction contractor is still working on sheetrock. Hailey Brossard Assistant Construction Manager B&H Fire and Security, LLC PO Box 3711 Arlington, WA 98223 Lic. BHFIRHF842KW O: 844.793.8509 On Tue, Nov 26, 2024 at 10:59 AM Hannah Hardwick <hhardwick@arlingtonwa.gov> wrote: Hello, This email is to inform you of the upcoming expiration date for permit 6047. This permit will expire on 01/13/2025. Please ensure that an inspection has been requested and approved prior to the expiration date. If you are not ready an inspection prior to the expiration date, please reply requesting an extension. The request needs to state cause for the extension and requires approval by the Building Official once received. Additional fees may be required upon extension approval. Please use the link below to view and request an inspection. You can also call in an inspection at 360-403-3417. Permits - Arlington (iworq.net) Sincerely, Hannah Hardwick Arlington Community & Economic Development, Permit Technician I 18204 59th Ave NE, Arlington, WA 98223 O: 360.403.3549 hhardwick@arlingtonwa.gov | www.arlingtonwa.gov Note: Emails and attachments sent to and from the City of Arlington are public records and may be subject to disclosure pursuant to the Public Records Act. From: Hailey Brossard To: Hannah Hardwick Subject: Re: BLD6047- Expiration Notice Date: Tuesday, July 8, 2025 9:54:01 AM Attachments: image001.png This message is from an External Sender This message came from outside the City of Arlington Hi Hannah, We are still working away at these projects. We will not meet the completion date and get inspections before our permit expires. I would like to request an extension on this permit please. Thanks, Hailey Brossard | Assistant Construction Manager B&H Fire and Security, LLC PO Box 3711 Arlington, WA 98223 Lic. BHFIRHF842KW O: 844.793.8509 Emergency After Hour Service Line: 425.508.4675 On Fri, May 30, 2025 at 11:25 AM Hannah Hardwick <hhardwick@arlingtonwa.gov> wrote: Hello, This email is to inform you of the upcoming expiration date for permit 6047. This permit will expire on 7/11/2025. Please ensure that an inspection has been requested and approved prior to the expiration date. If you are not ready an inspection prior to the expiration date, please reply requesting an extension. The request needs to state cause for the extension and requires approval by the Building Official once received. Additional fees may be required upon extension approval. Please use the link below to view and request an inspection. You can also call in an inspection at 360-403-3417. Permits - Arlington (iworq.net) Sincerely, Hannah Hardwick Arlington Community & Economic Development, Permit Technician I 18204 59th Ave NE, Arlington, WA 98223 O: 360.403.3549 hhardwick@arlingtonwa.gov | www.arlingtonwa.gov Note: Emails and attachments sent to and from the City of Arlington are public records and may be subject to disclosure pursuant to the Public Records Act. Permit #: 6047 Permit Date: 06/20/24 Permit Type: FIRE ALARM Project Name: Ironwood Place Bldg. 2 Applicant Name: B & H Fire and Security Applicant Address: PO Box 3711 Applicant, City, State, Zip: Arlington, WA 98223 Contact: Hailey Brossard Phone: 360-322-7634 Email: hailey@bnhfire.com Scope of Work: Install new addressable fire alarm system Valuation: 18500.00 Square Feet: 18023 Number of Stories: 3 Construction Type: VB Occupancy Group: R-2; Residential ID Code: Permit Issued: 07/17/2024 Permit Expires: 01/11/2026 Form Permit Type: FIRE ALARM Status: COMPLETE Assigned To: Kristin Foster Property Parcel # Address Legal Description Owner Name Owner Phone Zoning GRANDVIEW 126 MULTI- 00738500103100 18620 WOODLANDS WAY NORTH LLC FAMILY MKT Contractors Contractor Primary Contact Phone Address Contractor Type License License # B & H FIRE AND ELECTRICAL JEFF BROSSARD 425-244-1445 PO BOX 3711 COA 603 612 112 SECURITY LLC CONTRACTOR B & H FIRE AND ELECTRICAL LABOR & JEFF BROSSARD 425-244-1445 PO BOX 3711 BHFIRHF842KW SECURITY LLC CONTRACTOR INDUSTRIES Inspections Date Inspection Type Description Scheduled Date Completed Date Inspector Status FA00. FIRE ALARM 08/15/2025 Scheduled for 1:30pm 08/19/2025 08/19/2025 BUILDING Approved FINAL FA00. FIRE ALARM 08/15/2025 Scheduled for 1:30pm 08/19/2025 FIRE Assigned FINAL Plan Reviews Date Review Type Description Assigned To Review Status 06/21/2024 FIRE ALARM BUILDING Approved PERMIT EXTENSION 12/16/2024 BUILDING In Review REQUEST Fees Fee Description Notes Amount Fire Alarm System Permit NFPA 72 - 105.7.3 $293.18 Credit Card Service $8.80 Processing/Technology $25.00 Fire Alarm System Permit NFPA 72 - 105.7.3 $56.82 FACP / Transmitter - New $200.00 Fire System Plan Review Table 4-2 $293.18 Credit Card Service $17.25 Permit Extension $110.00 Credit Card Service $3.30 Total $1,007.53 Attached Letters Date Letter Description 07/17/2024 Building Permit Payments Date Paid By Description Payment Type Accepted By Amount XBP Conf: 06/20/2024 $293.18 202876677 06/20/2024 Jeff Brossard 202876677 Hannah Hardwick $8.80 XBP Conf: 07/17/2024 $575.00 205070097 07/17/2024 Jeff Brossard 205070097 $17.25 07/08/2025 Jeff Brossard 236457949 Hannah Hardwick $3.30 XBP Conf: 07/08/2025 $110.00 236457494 Outstanding Balance $0.00 Notes Date Note Created By: 05/30/2025 sent expiration notice Hannah Hardwick 11/26/2024 sent expiration notice Hannah Hardwick 06/20/2024 Emailed for hard copies. Kristin Foster 06/20/2024 Received the plan review fee and hard copies. Kristin Foster Uploaded Files Date File Name 07/08/2025 27230279-20250708_BLD6047_Permit Extension Request.pdf 12/16/2024 23509145-20241216_BLD6047_PErmit Extension Request.pdf 07/17/2024 21648827-20240715_BLD6047_ApprovedPlans.pdf 07/17/2024 21648824-20240717_BLD6047_IssuedPermit.pdf 06/20/2024 21163575-20240617_BLD6047_EquipmentSpecs.pdf 06/20/2024 21163577-20240617_BLD6047_Application.pdf 06/20/2024 21163578-20240617_BLD6047_Calculations.pdf