Permit #: 3919
Permit Date: 05/24/21
Permit Type: FIRE SPRINKLER
Project Name: Steadfast Star
Applicant Name: Advanced Fire Protection
Applicant Address: PO Box 1543
Applicant, City, State, Zip: Woodinville, WA 98072
Contact: Michael Balsley
Phone: 425-483-5657
Email: mikd@advfire.net
Scope of Work: Fire Sprinkler alteration
Valuation: 60000.00
Square Feet: 0
Number of Stories: 0
Construction Type:
Occupancy Group:
ID Code:
Permit Issued: 06/14/2021
Permit Expires: 12/13/2021
Form Permit Type:
Status: COMPLETE
Assigned To: Raelynn Jones
Property
Parcel # Address Legal Description Owner Name Owner Phone Zoning
282 Plastics &
STEADFAST STAR
00793300002300 7220 201ST ST NE Synthetic Resins,
LLC
Rubber, Ex. Glass
Contractors
Contractor Primary Contact Phone Address Contractor Type License License #
ADVANCED FIRE CONSTRUCTION Labor and
425-483-5657 P.O.BOX 1543 ADVANFP199B6
PROTECTION CONTRACTOR Industries
Inspections
Date Inspection Type Description Scheduled Date Completed Date Inspector Status
FS07. FIRE
06/22/2022 cover inspection 06/24/2022 06/24/2022 FIRE Completed
SPRINKLER FINAL
Plan Reviews
Date Review Type Description Assigned To Review Status
05/24/2021 FIRE SPRINKLER BUILDING
1. Permit and set of approved plans to remain on site
during installation.
2. Significant deviations from approved plans made during
installation shall be required to be resubmitted for review
prior to inspections: may include hangers, earthquake
bracing, sprinkler locations and pipe re-routing that could
impact hydraulic calculations. Failure to submit revisions
could result in cancellation of an inspection while a review
of an as-built resubmittal is conducted.
05/24/2021 FIRE SPRINKLER FIRE
3. Cover inspection required.
4. Hydrostatic test required: 200 psi for 2 hours minimum.
5. Any mechanical tee cut-outs shall be tied to sprinkler
piping and be visible at time of cover inspection.
6. Sprinkler system Contractor’s Material and Test
Certificate shall be submitted to The Compliance Engine
prior to close out of permit.
7. Owner shall be provided with a set of approved plans
and associated documents for their files.
Fees
Fee Description Notes Amount
Fire Sprinkler System Commercial NFPA 13/13R $475.00
Processing/Technology $25.00
Fire System Plan Review Table 4-1 $697.67
Credit Card Service $35.93
Total $1,233.60
Attached Letters
Date Letter Description
06/09/2021 Building Permit
Payments
Date Paid By Description Payment Type Accepted By Amount
06/11/2021 Peter Foltz 87014484 $1,197.67
06/11/2021 87014484 Raelynn Jones $35.93
Outstanding Balance $0.00
Uploaded Files
Date File Name
05/24/2021 8877231-3919_Application.pdf
City of Arlington FI E
R M
E S
Fire Department
June 2, 2021
Permit Number: BLD 3919
Project Address: 7220 201st Street NE, Arlington
Project Description: Fire Sprinkler Plans for Steadfast Star
Contractor: Advanced Fire Protection
PO Box 1543
Woodinville, WA 98072
Re: Fire Suppression Shop Drawing Review Comments/Approval
The Arlington Fire Department has completed a review of the Fire Suppression shop drawing submittal and
approves the issuance of the permit with the following conditions:
1. Permit and set of approved plans to remain on site during installation.
2. Significant deviations from approved plans made during installation shall be required to be resubmitted for
review prior to inspections: may include hangers, earthquake bracing, sprinkler locations and pipe re-
routing that could impact hydraulic calculations. Failure to submit revisions could result in cancellation of
an inspection while a review of an as-built resubmittal is conducted.
3. Cover inspection required.
4. Hydrostatic test required: 200 psi for 2 hours minimum.
5. Any mechanical tee cut-outs shall be tied to sprinkler piping and be visible at time of cover inspection.
6. Sprinkler system Contractor’s Material and Test Certificate shall be submitted to The Compliance Engine
prior to close out of permit.
7. Owner shall be provided with a set of approved plans and associated documents for their files.
Items noted above are conditions on the issued permit and shall be verified as part of the final inspection of the
system at project completion. Final approval will not be provided until all conditions are verified. Call at least
48 hours in advance to schedule inspections.
If there are any questions please do not hesitate to call.
Sincerely,
Mike Makela
Mike Makela
Assistant Fire Chief
Arlington Fire Department